Professional Documents
Culture Documents
Dual Input Redundancy Module - 24 56V, 40 A: Reference Manual
Dual Input Redundancy Module - 24 56V, 40 A: Reference Manual
- 24…56V, 40 A
Catalog Number 1606-XLSRED40HF
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
These labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Identifies information that is useful and can help to make a process easier to do or easier to understand.
Notes:
Earth, Ground This document uses the term “earth,” which is the same as the U.S. term “ground”.
A value that is displayed with the AC or DC before the value represents a nominal voltage
DC 24V with standard tolerances (usually ±15%) included. For example: DC 12V describes a 12V
battery disregarding whether it is full (13.7V) or flat (10V).
A value with the unit (V DC) at the end is a momentary value without any additional
24V DC tolerances included.
nom Indicates a nominal value.
typ Indicates a typical value.
— (alone in table cell) A dash alone in a table cell indicates that there is no information to be included in that cell.
Use of two identical power supplies in parallel to provide continued operation following
most failures in one power supply. Isolate the two power supply outputs from each other
1+1 Redundancy by using diodes or other switching arrangements. For example, two 10 A power supplies
are needed to achieve a 10 A redundant system.
Use of three or more identical power supplies in parallel, which are allowed to be
connected in parallel for higher output currents, to provide continued operation following
most failures in one power supply. Isolate all power supply outputs from each other by
N+1 Redundancy using diodes or other switching arrangements. For example, to achieve a 40 A redundant
system, five 10 A power supplies are needed in an N+1 redundant system. Confirm that the
power supplies are allowed to be connected in parallel to increase the output power.
IN 1 IN 2 IN 1 IN 2 IN 1 IN 2 IN 1 IN 2
+ - + -
Load Load
Product features:
• For 1+1 and N+1 redundant systems
• Dual-input with single output
• Suitable for all 1606 power supplies
• Only 60 mV voltage drop at 20 A output current
• Only 1.8 W loss at 20 A and 5.4 W at 40 A output current
• 160% (65 A) peak load capability
• Reverse input polarity protection
• Full power between -40…+60 °C (-40…+140 °F)
• Width only 46 mm (1.81 in.)
• Rugged metal housing
• Easy wiring; distribution terminal for negative pole included
Specifications
Attributes Values Notes
Input voltage DC 24…56V ±15%
Input voltage range 20.4…64.4V DC —
2 x 0…20 A
Input current Continuous for 5 seconds
2 x 20…32.5 A
0…40 A
Continuous for 5 seconds
Output current 40…65 A
45 A, max In overload(1) or short circuit mode
60 mV typical At 2 x 10 A
Input to output voltage drop 95 mV typical At 1 x 20 A
120 mV typical At 2 x 20 A
220 mW typical At 24V, no load
620 mW typical At 48V, no load
Power losses 1.8 W typical At 48V, 2 x 10 A input
2.3 W typical At 48V, 1 x 20 A input
5.4 W typical At 48V, 2 x 20 A input
Temperature range -40…+70 °C (-40…+158 °F) Operational
Derating 1 A/1 °C (1 A/1.8 °F) output 60…70 °C (140…158 °F)
46 x 124 x 127 mm
Dimensions WxHxD
(1.81 x 4.88 x 5 in.)
Weight 360 g (0.79 lb) —
(1) Currents at voltages below 6V.
Catalog Number
Catalog Number Description
1606-XLSRED40HF Dual redundancy module
Figure 3 - Input to Output Voltage Drop When Both Inputs Draw Current
(Typical 1+1 redundant case when the output voltages of both units are equal)
160
A: 25 °C (77 °F) 1606-XLSRED40HF Output
140 Variable Load,
B: 60 °C (140 °F) Power
Voltage Drop, mV (typ)
Figure 4 - Input to Output Voltage Drop When Only One Input Draws Current
120 1606-XLSRED40HF
A: 25 °C (77 °F) Output Variable Load,
105 Power I1 I OUT 0…40 A
B: 60 °C (140 °F) Supply +
Voltage Drop, mV (typ)
90 A A A
B 48V, Input 1 Output
75 20 A max V U1 U OUT V
60
-
45
30
Not used or
15 power supply
with Input 2
0
0 5 10 15 20 low voltage
Output Current, A I1 = I2 U1 = U2 Voltage Drop = U1 - UOUT
Power Losses
Attribute 24V DC 48V DC Notes
Typ 1.4 W 1.8 W Input: 2 x 10 A
Power losses Typ 5W 5.4 W Input: 2 x 20 A
Typ 2W 2.3 W Input: 1 x 20 A(1)
Typ 0.14 W 0.42 W At no output current(1)
Standby power losses
Typ 0.22 W 0.62 W At no output current(2)
(1) Only one input is connected to input voltage.
(2) Both inputs are connected to input voltage.
A A
4 D: 48V, 60 °C (140 °F) 48V, Input 1 Output
20 A max V U1 U OUT V
3 -
2
Power I2
1 Supply + A
48V,
0 20 A max V U 2 Input 2
0 5 10 15 20 25 30 35 40 -
Output Current, A I1 = I2 U1 = U2 Losses = (U1 x I1 + U2 x I2) - UOUT x IOUT
3 1606-XLSRED40HF Output
A: 24V, 25 °C (77 °F) Variable Load,
Power I1 I OUT 0…40 A
2.5 B: 24V, 60 °C (140 °F) B Supply +
Power Losses, W (typ)
Lifetime Expectancy and The redundancy module has two input channels that are completely
Mean Time Between Failure independent from each other. Each control circuit, auxiliary voltage source, or
other circuitry in the module are designed separately for each input. The dual-
input redundancy module can be considered as two single redundancy
modules combined in one housing. The only common point is the circuit trace
that ties the two separate circuits together at the output.
The mean time between failure (MTBF) figures in the following table are for
the entire dual-input module. If the MTBF number of only one path is needed,
simply double the value from the table.
Input/output Input: 2 x 10 A Input: 2 x 20 A Notes
Current Conditions Output: 20 A Output: 40 A
448,000 h 222,000 h At 48V and 40 °C (104 °F)
Lifetime expectancy(1)
1,267,000 h 629,000 h At 48V and 25 °C (77 °F)
MTBF(2) SN 29500, 6,656,000 h 4,098,000 h At 48V and 40 °C (104 °F)
IEC 61709 11,990,000 h 7,808,000 h At 48V and 25 °C (77 °F)
211,000 h 178,000 h At 48V and 40 °C (104 °F) (Ground Fixed GF40)
288,000 h 238,000 h At 48V and 25 °C (77 °F) (Ground Fixed GF25)
MTBF (2) MIL HDBK 217F
959,000 h 839,000 h At 48V and 40 °C (104 °F) (Ground Benign GB40)
1,332,000 h 1,144,000 h At 48V and 25 °C (77 °F) (Ground Benign GB25)
(1) The Lifetime expectancy values that are shown in the table indicate the minimum operating hours (service life) and are
determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours
and is calculated according to the manufacturer specification of the capacitor. The manufacturer of the electrolytic capacitors
only states a maximum life of up to 15 years (131,400 h). Any number that exceeds this value is a calculated theoretical lifetime,
which can be used to compare devices.
(2) Mean time between failure (MTBF) is calculated according to statistical device failures, and indicates reliability of a device. It is the
statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. The MTBF value
is a statistical representation of the likelihood of a device to fail. An MTBF value of, for example, 1,000,000 h means that
statistically one unit fails every 100 hours if 10,000 units are installed in the field. However, it cannot be determined if the failed
unit has been running for 50,000 h or only for 100 h.
Terminals and Wiring The terminals are IP20 fingersafe constructed and suitable for field wiring.
To connect the chassis to the ground, use a ring-type terminal (ring cable lug)
that is suitable for an M4 screw. Connect this terminal to the chassis ground
terminal on top of the unit.
Attributes Input
• Screw terminals
Type • IP20 fingersafe construction
• Suitable for field installation
Solid wire 0.5…16 mm2
Stranded wire 0.5…10 mm2
American Wire Gauge 22…8 AWG
Wire diameter max 5.2 mm (0.2 in.) (including ferrules)
Wire stripping length 12 mm (0.5 in.)
Screwdriver 3.5 mm (0.138 in.) slotted or Pozidrive No 2
Recommended tightening torque 1.2 N•m (10.6 lb•in)
Wiring rules:
• The external circuitry of all terminals must meet the safety requirements
stipulated by IEC/EN/UL 60950-1: SELV.
• Use appropriate copper cables that are designed for minimum operating
temperatures of:
- 60 °C (140 °F) for ambient up to 45 °C (113 °F)
- 75 °C (167 °F) for ambient up to 60 °C (140 °F)
- 90 °C (194 °F) for ambient up to 70 °C (167 °F) minimum
• Follow national installation codes and installation regulations.
• Verify that all strands of a stranded wire enter the terminal connection.
• Verify that unused terminal compartments are securely tightened.
• Ferrules are allowed.
• Do not connect or disconnect the wires from the terminals below
-25 °C (-13 °F).
Control
+ +
Input 1 Output
- -
+ Chassis
Ground
Input 2
- Control
A Screw terminals
B Chassis ground terminal
To be connected on the top side of the housing with a ring-type terminal (ring
cable lug) that is suitable for a M4 screw. Chassis connection is optional and not
required since the unit fulfills the requirements according to protection class III.
C Input terminals for input 1
Screw terminals
D Input terminals for input 2
Screw terminals
Switching Frequency
The internal auxiliary supply is generated with a boost converter. Depending
on the input voltage, the switching frequency varies from 55… 180 kHz.
Environment
Attributes Values Notes
(1) -40…+70 °C (-40…+158 °F) —
Operational temperature
Storage temperature -40…+85 °C (-40…+185 °F) For storage and transportation
Output derating 1 A/1 °C (1 A/1.8 °F) 60…70 °C (140…158 °F)
Humidity(2) 5…95% r.H. IEC 60068-2-30
2…17.8 Hz: ±1.6 mm (0.063 in.)
Vibration sinusoidal(3) 17.8…500 Hz: 2 g IEC 60068-2-6
2 hours / axis
30 g 6 ms, 20 g 11 ms,
Shock(3) 3 bumps/direction, 18 bumps in total IEC 60068-2-27
0…2000 m (0…6560 ft) Without any restrictions
Altitude
2000…6000 m (6560…20,000 ft) Reduce output power or ambient temperature; see Figure 10
2.5 A/1000 m (2.5 A/3281 ft), or
Altitude derating >2000 m (6500 ft); see Figure 10
5 °C/1000 m (41 °F/3281 ft)
The concept of the overvoltage category is used for
Overvoltage category Not applicable equipment that is energized directly from the low voltage
mains (IEC 60664-1 §4.3.3.2.1).
Degree of pollution 2 IEC 62103, EN 50178, not conductive
(1) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2 cm (0.79 in.) below the
unit.
(2) Do not energize while condensation is present.
(3) Tested in combination with DIN rails according to EN 60715 with a height of 15 mm (0.59 in.) and a thickness of 1.3 mm (0.051 in.)
and standard mounting orientation.
Figure 9 - Output Current Versus Ambient Temperature Figure 10 - Output Current Versus Altitude
65 65
Short Term (< 5s) Short Term (<5 s)
Allowed Output Current, A
Allowed Output Current, A
50 50
Normal Mode Normal Mode
40 40 C
B
A
30 30
20 20
A: Tamb <70 °C (<158 °F)
10 10 B: Tamb <60 °C (<140 °F)
C: Tamb <50 °C (<122 °F)
0 0
-40 -25 0 20 40 60 70 0 2000 4000 6000
(-40) (-13) (68) (104) (140) (158) (6562) (13,123) (19,685)
Ambient Temperature, °C (°F) Altitude, m (ft)
Protection Features
Attributes Descriptions Notes
Output overcurrent protection Not included —
Reverse input polarity protection Included Unit does not start when input voltage is reversed
Degree of protection IP 20 EN/IEC 60529
Penetration protection >3.6 mm (0.14 in.) For screws and small parts
Over-temperature protection Not included —
Input transient protection Not included —
Safety Features
Attributes Descriptions Notes
Input/output separation No galvanic separation Mosfet between input and output
Class of protection III PE (Protective Earth) or chassis connection not required
PE resistance <0.1 Ω Between housing and chassis ground terminal
Dielectric Strength The input and output voltages have the same reference, are floating, and have
no ohmic connection to ground. The manufacturer conducts type and factory
tests. Field tests can be conducted in the field using the appropriate test
equipment that applies the voltage with a slow ramp (2 s up and 2 s down).
Connect input/output terminals together before conducting the test. When
testing, set the cutoff current settings to the value in Figure 11.
IECEx Certificate
IECEx See 1606-CT031 at rok.auto/literature
CSA Certificate
Class I Div 2 Power Supplies for Hazardous Location
See 1606-CT046 at rok.auto/literature
DNV Certificate
Marine (DNV) DNV Type approved product
Manufacturer’s Statement
EU-Regulation on Waste Electrical and Electronic Equipment
WEEE Directive (WEEE)
Registered in Germany as business to business (B2B) products
EAC Certificate
EAC Eurasian Conformity-Registration Russia, Kazakhstan, and
EAC Registration Belarus
8504408200, 8504409000
+ -
VOUT
124
(4.88)
VIN1 VIN2
+ -
40.6 (1.6) DIN Rail
46 (1.81) Depth 127 (5)
Accessories The following accessories are available for the 1606-XLSRED40HF redundancy
module.
This bracket kit contains the two brackets that are needed for one device.
Figure 13 - Cat. No. 1606-XLC Wall/Panel Mount Bracket
The two aluminum brackets and the black plastic slider of the device must be
detached so that the steel bracket can be mounted.
For sideway DIN rail mounting, mount the removed aluminum brackets and
the black plastic slider on the side mount bracket.
Figure 14 - Cat. No. 1606-XLA-S44 Side Mount Bracket
Inductive and Capacitive The unit is designed to supply any kind of loads, including unlimited
Loads capacitive and inductive loads.
The clearance between the power supplies and the redundancy module can be
reduced to zero under the following conditions:
• 1+1 redundancy application with a maximum 20 A output current.
• The power supplies are from the 1606-XLS or 1606-XLE family series.
• The redundancy module is placed between the two power supplies.
• The output voltage is set to the same level on both power supplies.
Figure 15 - Sidewards Installation Clearance Example
20 A
Load
0 mm 0 mm
Example: Redundancy for In many cases, two power supplies are used, one for the demanding loads and
Controls another for the controls and sensitive loads. With the 1606-XLSRED40HF
redundancy module, the power supply for the demanding loads can be used as
a redundant source to supply the controls. This provides a cost-effective
solution to get redundant power for a PLC or controller system.
I I
L
N
PE
I I I I
L
N
PE
Mounting Orientations Mounting orientations other than input terminals on the bottom and output
on the top require a reduction in continuous output power or a limitation in
the maximum allowed ambient temperature.
The following curves indicate the allowed output currents for altitudes up to
2000 m (6562 ft).
Figure 18 - Mounting Orientation A (upright; standard)
40 A1
Output
Output Current, A
30
1606-XLSRED40HF 20
Redundancy
Module 10
0
Inputs 10 (50) 20 (68) 30 (86) 40 (104) 50 (122) 60 (140)
Ambient Temperature, °C (°F)
Inputs
30
Module 20
Redundancy
1606-XLSRED40HF 10
0
Output 10 (50) 20 (68) 30 (86) 40 (104) 50 (122) 60 (140)
Ambient Temperature, °C (°F)
30 A2
20 A1
10
0
10 (50) 20 (68) 30 (86) 40 (104) 50 (122) 60 (140)
Ambient Temperature, °C (°F)
30
1606-XLSRED40HF
20 A1
Redundancy
Output
Inputs
Module
10
0
10 (50) 20 (68) 30 (86) 40 (104) 50 (122) 60 (140)
Ambient Temperature, °C (°F)
Output Current, A
30
1606-XLSRED40HF
20 A1
Redundancy
Output
sInput
Module
10
0
10 (50) 20 (68) 30 (86) 40 (104) 50 (122) 60 (140)
Ambient Temperature, °C (°F)
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
Switched Mode Power Supply Specifications Technical Data, publication Provides specifications for Bulletin 1606-XL, -XLE, -XLP, and -XLS products and applications.
1606-TD002
Designing More Reliable 24V DC Systems Application Techniques, publication Provides information on properly configured redundancy modules, buffer modules, DC-UPS, and
1606-AT003 DC/DC converters.
Industrial Components Preventive Maintenance, Enclosures, and Contact Ratings Provides a quick reference tool for Allen-Bradley industrial automation controls and assemblies.
Specifications, publication IC-TD002
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides general
Safety Guidelines for the Application, Installation, and Maintenance of Solid- guidelines for the application, installation, and maintenance of solid-state control in the form of
State Control, publication SGI-1.1 individual devices or packaged assemblies incorporating solid-state components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details.
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our
content, complete the form at rok.auto/docfeedback.
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur