Professional Documents
Culture Documents
Ib 0600189 ZZZF
Ib 0600189 ZZZF
INVERTER
INSTALLATION GUIDELINE
FR-F740-00023 to 12120-EC
CONTENTS
1 INSTALLATION OF THE INVERTER AND INSTRUCTIONS................. 1
2 OUTLINE DRAWING............................................................................... 2
3 WIRING.................................................................................................... 3
4 PRECAUTIONS FOR USE OF THE INVERTER..................................... 8
700
F700_kaigaidoukon_EC.book 1 ページ 2008年7月28日 月曜日 午前10時32分
A-1
F700_kaigaidoukon_EC.book 1 ページ 2008年7月28日 月曜日 午前10時32分
• Inverter Type
FR - F740 - 00126 - EC
Symbol Voltage Class Symbol Type number Rating plate
Three-phase 00023 Rating plate
F740 Displays the rated current.
400V class to
12120 Inverter type FR-F740-00126-EC
Input rating
Capacity plate
Output rating
Capacity plate FR-F740-00126-EC LD (50 C) XXA
SLD (40 C) XXA
Serial number
Inverter type Serial number
10cm or more *2
5cm or more *1
CAUTION
• Install the inverter on a strong surface securely and vertically with bolts.
• Leave enough clearances and take cooling measures.
• Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
• Install the inverter on a non-combustible wall surface.
1
F700_kaigaidoukon_EC.book 2 ページ 2008年7月28日 月曜日 午前10時32分
OUTLINE DRAWING
2 OUTLINE DRAWING
H1
H1
H
H
H
W1 W1 W1 W1 W1 W1
W D
W W
(Unit:mm)
Inverter Type W W1 H H1 D
FR-F740-00023-EC
FR-F740-00038-EC
FR-F740-00052-EC 150 125 140
FR-F740-00083-EC 260 245
FR-F740-00126-EC
FR-F740-00170-EC
170
FR-F740-00250-EC
220 195
FR-F740-00310-EC
300 285 190
FR-F740-00380-EC
FR-F740-00470-EC
250 230 400 380 190
FR-F740-00620-EC
FR-F740-00770-EC 325 270 550 530 195
FR-F740-00930-EC
FR-F740-01160-EC 435 380 550 525 250
FR-F740-01800-EC
FR-F740-02160-EC
620 595 300
FR-F740-02600-EC
465 400
FR-F740-03250-EC
740 715 360
FR-F740-03610-EC
FR-F740-04320-EC
498 200
FR-F740-04810-EC
FR-F740-05470-EC 1010 984 380
FR-F740-06100-EC 680 300
FR-F740-06830-EC
FR-F740-07700-EC
790 315 1330 1300
FR-F740-08660-EC
FR-F740-09620-EC 440
FR-F740-10940-EC 995 300 1580 1550
FR-F740-12120-EC
2
F700_kaigaidoukon_EC.book 3 ページ 2008年7月28日 月曜日 午前10時32分
3 WIRING
*1. DC reactor (FR-HEL) *1 Resistor unit
Source logic *6. A CN8 (for MT-BU5)
Be sure to connect the DC reactor (Option)
supplied with the 01800 or more. connector is provided
Main circuit terminal Brake unit
When a DC reactor is connected with the 01800 or more.
to the 01160 or less, remove the (Option)
Control circuit terminal Earth Jumper
jumper across P1-P/+. Jumper *7. Do not use PR and PX terminals.
Please do not remove the jumper
connected to terminal PR and PX.
MCCB MC P1 P/+ PX*7 N/- CN8*6
PR*7
U Motor
R/L1
Three-phase AC S/L2 V
power supply IM
T/L3 W
ON EMC filter
Earth
R1/L11 ON/OFF
Jumper
*2 S1/L21 OFF connector
*2. To supply power to the
control circuit separately, Earth Main circuit
remove the jumper across
R1/L11 and S1/L21. Control circuit
Control input signals (No voltage input allowed) C1 Relay output
Terminal functions vary Forward STF
with the input terminal rotation Terminal functions
assignment start B1 vary with the output
STR Relay output 1 terminal assignment
(Pr. 178 to Pr. 189) Reverse
(Refer to the Instruction rotation A1 (Fault output) (Pr. 195, Pr. 196)
Manual chapter4.) start STOP (Refer to the Instruction
Manual chapter4.)
Start self-holding selection C2
RH
High speed
B2
Multi-speed RM Relay output 2
Middle speed
selection A2
RL
Low speed
JOG RUN Open collector output
Jog mode Running
Terminal functions
RT SU vary with the output
Second function selection Up to frequency terminal assignment
MRS IPF (Pr. 190 to Pr. 194)
Instantaneous Refer to the
*3. AU terminal can be Output stop power failure Instruction Manual
used as PTC input RES *3 OL chapter4.
terminal. Reset Overload
AU
AU FU
Terminal 4 input selection Frequency detection
(Current input selection)
SOURCE
after instantaneous
power failure Sink/source common
SD
Contact input common (Sink)
(Common for external power supply transistor)
24VDC power supply PC PU
Contact input common connector
(Common for external power supply transistor) *4 Voltage/current
input switch
Frequency setting signal (Analog) 10E(+10V) 4 2
ON CA (+)
10(+5V) OFF Analog current output
Frequency setting 3 (0 to 20mADC)
2 0 to 5VDC Initial value (-)
potentiometer 2 0 to 10VDC
1/2W1kΩ selected *4
0 to 20mADC
*5 1 5
(Analog common) AM (+)
Analog signal output
*4. Terminal input specifications
can be changed by analog Initial 5 (0 to 10VDC)
0 to ±10VDC value (-)
input specifications switchover Auxiliary (+) 1
(Pr. 73, Pr. 267). Set the input (-) 0 to ±5VDC selected *4
voltage/current input switch in Initial TXD+ RS-485 terminals
the OFF position to select Terminal 4 to 20mADC value
voltage input (0 to 5V/0 to 4 input (+) 4 0 to 5VDC
selected *4 TXD- Data transmission
10V) and ON to select current (-) 0 to 10VDC
(Current
input (0 to 20mA). RXD+
(Refer to the input) Connector
Instruction Manual RXD- Data reception
chapter4.)
for plug-in option
connection SG
GND
*5. It is recommended to use
2W1kΩ when the Option connector 1 Terminating
frequency setting signal is resistor VCC 5V (Permissible load
changed frequently.
current 100mA)
CAUTION
• To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables.
• After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in a control box etc., take care not to allow chips and other foreign matter to enter the inverter.
• Set the voltage/current input switch correctly. Different setting may cause a fault, failure or malfunction.
3
F700_kaigaidoukon_EC.book 4 ページ 2008年7月28日 月曜日 午前10時32分
WIRING
R1/L11 S1/L21 PX
IM
Power supply Motor
Screw size
(M4)
IM Jumper
R/L1 S/L2 T/L3 N/- PR
Power supply Motor
IM
Screw size (M6)
Power supply Motor
Screw size (M5)
R1/L11 S1/L21
Screw size(M4)
Jumper
Screw size
(00770: M6
00930/01160: M8) Screw size Screw size
(01800: M8, 02160/02600: M10) Screw size (M10) (01800: M8, 02160/02600: M10)
4
F700_kaigaidoukon_EC.book 5 ページ 2008年7月28日 月曜日 午前10時32分
WIRING
Jumper Jumper
Screw size
(03250/03610: M10
04320/04810: M12)
5
F700_kaigaidoukon_EC.book 6 ページ 2008年7月28日 月曜日 午前10時32分
WIRING
400V class (when input power supply is 440V based on the rated current for 110% overload for 1 minute)
Crimping Cable Sizes
(Compression)
Terminal HIV, etc. (mm2) *1 AWG/MCM *2 PVC, etc. (mm2) *3
Applicable Inverter Tightening Terminal
Screw Size
Type Torque N·m R/L1, R/L1, R/L1, R/L1,
*4 U, V, U, V,
S/L2, S/L2, cable S/L2, U, V, W S/L2, U, V, W cable
W W
T/L3 T/L3 T/L3 T/L3
FR-F740-00023 to
M4 1.5 2-4 2-4 2 2 2 14 14 2.5 2.5 2.5
00083-EC
FR-F740-00126-EC M4 1.5 2-4 2-4 2 2 3.5 12 14 2.5 2.5 4
FR-F740-00170-EC M4 1.5 5.5-4 5.5-4 3.5 3.5 3.5 12 12 4 4 4
FR-F740-00250-EC M4 1.5 5.5-4 5.5-4 5.5 5.5 8 10 10 6 6 10
FR-F740-00310-EC M5 2.5 8-5 8-5 8 8 8 8 8 10 10 10
FR-F740-00380-EC M5 2.5 14-5 8-5 14 8 14 6 8 16 10 16
FR-F740-00470-EC M6 4.4 14-6 14-6 14 14 14 6 6 16 16 16
FR-F740-00620-EC M6 4.4 22-6 22-6 22 22 14 4 4 25 25 16
FR-F740-00770-EC M6 4.4 22-6 22-6 22 22 14 4 4 25 25 16
FR-F740-00930-EC M8 7.8 38-8 38-8 38 38 22 1 2 50 50 25
FR-F740-01160-EC M8 7.8 60-8 60-8 60 60 22 1/0 1/0 50 50 25
FR-F740-01800-EC M8 7.8 60-8 60-8 60 60 38 1/0 1/0 50 50 25
FR-F740-02160-EC M10 14.7 100-10 100-10 80 80 38 3/0 3/0 70 70 35
FR-F740-02600-EC M10 14.7 100-10 150-10 100 100 38 4/0 4/0 95 95 50
FR-F740-03250-EC M10 14.7 150-10 150-10 125 125 38 250 250 120 120 70
FR-F740-03610-EC M10 14.7 150-10 150-10 150 150 38 300 300 150 150 95
FR-F740-04320-EC M12(M10) 24.5 100-12 100-12 2×100 2×100 38 2×4/0 2×4/0 2×95 2×95 95
FR-F740-04810-EC M12(M10) 24.5 100-12 100-12 2×100 2×100 38 2×4/0 2×4/0 2×95 2×95 95
FR-F740-05470-EC M12(M10) 24.5 150-12 150-12 2×125 2×125 38 2×250 2×250 2×120 2×120 120
FR-F740-06100-EC M12(M10) 24.5 150-12 150-12 2×150 2×150 38 2×300 2×300 2×150 2×150 150
FR-F740-06830-EC M12(M10) 24.5 200-12 200-12 2×200 2×200 60 2×350 2×350 2×185 2×185 2×95
FR-F740-07700-EC M12(M10) 24.5 C2-200 C2-200 2×200 2×200 60 2×400 2×400 2×185 2×185 2×95
FR-F740-08660-EC M12(M10) 24.5 C2-250 C2-250 2×250 2×250 60 2×500 2×500 2×240 2×240 2×120
FR-F740-09620-EC M12(M10) 24.5 C2-250 C2-250 2×250 2×250 100 2×500 2×500 2×240 2×240 2×120
FR-F740-10940-EC M12(M10) 24.5 C2-200 C2-200 3×200 3×200 100 3×350 3×350 3×185 3×185 2×150
FR-F740-12120-EC M12(M10) 24.5 C2-200 C2-200 3×200 3×200 100 3×400 3×400 3×185 3×185 2×150
*1 For the 01160 or less, the recommended cable size is that of the cable (e.g. HIV cable (600V class 2 vinyl-insulated cable)) with continuous
maximum permissible temperature of 75°C. Assumes that the ambient temperature is 50°C or less and the wiring distance is 20m or less.
For the 01800 or more, the recommended cable size is that of the cable (e.g. LMFC (heat resistant flexible cross-linked polyethylene insulated
cable)) with continuous maximum permissible temperature of 90°C. Assumes that the ambient temperature is 50°C or less and wiring is performed
in an enclosure.
*2 For the 00930 or less, the recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C.
Assumes that the ambient temperature is 40°C or less and the wiring distance is 20m or less.
For the 01160 or more, the recommended cable size is that of the cable (THHN cable) with continuous maximum permissible temperature of 90°C.
Assumes that the ambient temperature is 40°C or less and wiring is performed in an enclosure.
(Selection example for use mainly in the United States.)
*3 For the 00930 or less, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C.
Assumes that the ambient temperature is 40°C or less and the wiring distance is 20m or less.
For the 01160 or more, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90°C.
Assumes that the ambient temperature is 40°C or less and wiring is performed in an enclosure.
(Selection example for use mainly in the Europe.)
*4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for earthing.
A screw for earthing (grounding) of the FR-F740-04320 or more is indicated in ( ).
6
F700_kaigaidoukon_EC.book 7 ページ 2008年7月28日 月曜日 午前10時32分
WIRING
(4) Cable size of the control circuit power supply (terminal R1/L11, S1/L21)
· Terminal screw size: M4
· Cable size: 0.75mm2 to 2mm2
· Tightening torque: 1.5N·m
7
F700_kaigaidoukon_EC.book 8 ページ 2008年7月28日 月曜日 午前10時32分
The FR-F700 series is a highly reliable product, but incorrect peripheral circuit making or operation/handling method
may shorten the product life or damage the product. Before starting operation, always recheck the following items.
(1) Use crimping terminals with insulation sleeve to wire the power supply and motor.
(2) Application of power to the output terminals (U, V, W) of the inverter will damage the inverter. Never perform such wiring.
(3) After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes in
an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
(4) Use cables of the size to make a voltage drop 2% maximum.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque
to decrease especially at the output of a low frequency. Refer to page 6 for the recommended cable sizes.
(5) The overall wiring length should be 500m maximum.
Especially for long distance wiring, the fast response current limit function may decrease or the equipment connected to the
secondary side may malfunction or become faulty under the influence of a charging current due to the stray capacity of the
wiring. Therefore, note the overall wiring length. (Refer to page 7.)
(6) Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the
communication devices (such as AM radios) used near the inverter. An EMC filter can minimize noise interference.
(7) Do not install a power factor correction capacitor, surge suppressor or radio noise filter on the inverter output side.
This will cause the inverter to trip or the capacitor, varistor, or arrester to be damaged. If any of the above devices is
installed, immediately remove it.
(8) Before starting wiring or other work after the inverter is operated, wait for at least 10 minutes after the power supply has
been switched off, and check that there are no residual voltage using a tester or the like. The capacitor is charged with high
voltage for some time after power off and it is dangerous.
(9) A short circuit or earth fault on the inverter output side may damage the inverter modules.
· Fully check the insulation resistance of the circuit prior to inverter operation since repeated short circuits caused by
peripheral circuit inadequacy or an earth fault caused by wiring inadequacy or reduced motor insulation resistance
may damage the inverter modules.
· Fully check the to-earth insulation and phase to phase insulation of the inverter output side before power-on.
Especially for an old motor or use in hostile atmosphere, securely check the motor insulation resistance etc.
(10) Do not use the inverter input side magnetic contactor to start/stop the inverter.
Always use the start signal (ON/OFF of STF and STR signals) to start/stop the inverter.
(11) Do not apply a voltage higher than the permissible voltage to the inverter I/O signal circuits.
Application of permissible voltage to the inverter I/O signal circuit and incorrect polarity may damage the I/O terminal.
Especially check the wiring to prevent the speed setting potentiometer from being connected incorrectly to short
terminals 10E-5.
(12) Provide electrical and mechanical interlocks for MC1 and MC2
MC1
which are used for bypass operation. Interlock
When the wiring is incorrect and if there is a bypass operation Power R/L1 U
circuit as shown right, the inverter will be damaged when the supply IM
power supply is connected to the inverter U, V, W terminals, due S/L2 V MC2
to arcs generated at the time of switch-over or chattering caused T/L3 W Undesirable current
by a sequence error. Inverter
(13) If the machine must not be restarted when power is restored
after a power failure, provide a magnetic contactor in the inverter's input side and also make up a sequence which will
not switch on the start signal.
If the start signal (start switch) remains on after a power failure, the inverter will automatically restart as soon as the
power is restored.
(14) Instructions for overload operation
When performing operation of frequent start/stop of the inverter, increase/decrease in the temperature of the transistor
element of the inverter may repeat due to a continuous flow of large current, shortening the life from thermal fatigue.
Since thermal fatigue is related to the amount of current, the life can be increased by reducing bound current, starting
current, etc. Decreasing current may increase the life. However, decreasing current will result in insufficient torque and
the inverter may not start. Therefore, increase the inverter capacity to have enough allowance for current.
(15) Make sure that the specifications and rating match the system requirements.
(16) When the motor speed is unstable, due to change in the frequency setting signal caused by electromagnetic noises from
the inverter, take the following measures when applying the motor speed by the analog signal.
· Do not run the signal cables and power cables (inverter I/O cables) in parallel with each other and do not bundle them.
· Run signal cables as far away as possible from power cables (inverter I/O cables).
· Use shield cables as signal cables.
· Install a ferrite core on the signal cable (Example: ZCAT3035-1330 TDK).
8
F700_kaigaidoukon_EC.book 9 ページ 2008年7月28日 月曜日 午前10時32分
When a fault occurs, the inverter trips to output a fault signal. However, a fault output signal may not be output at an
inverter fault occurrence when the detection circuit or output circuit fails, etc. Although we assure best quality products,
provide an interlock which uses inverter status output signals to prevent accidents such as damage to machine when
the inverter fails for some reason and at the same time consider the system configuration where failsafe from outside
the inverter, without using the inverter, is enabled even if the inverter fails.
(1) Interlock method which uses the inverter status output signals
By combining the inverter status output signals to provide an interlock as shown below, an inverter alarm can be
detected.
No Interlock Method Check Method Used Signals Refer to Page
Refer to the chapter
Inverter protective Operation check of an alarm contact Fault output signal
1) 4 of the Instruction
function operation Circuit error detection by negative logic (ALM signal)
Manual.
Refer to the chapter
Operation ready signal
2) Inverter running status Operation ready signal check 4 of the Instruction
(RY signal)
Manual.
Start signal Refer to the chapter
Logic check of the start signal and
3) Inverter running status (STF signal, STR signal) 4 of the Instruction
running signal
Running signal (RUN signal) Manual.
Start signal
Refer to the chapter
Logic check of the start signal and (STF signal, STR signal)
4) Inverter running status 4 of the Instruction
output current Output current detection signal
Manual.
(Y12 signal)
Controller
System failure
Inverter Sensor
(speed, temperature,
air volume, etc.)
9
F700_kaigaidoukon_EC.book 10 ページ 2008年7月28日 月曜日 午前10時32分
PARAMETER LIST
6 PARAMETER LIST
REMARKS
⋅ The parameters marked are the simple mode parameters.
⋅ The parameters marked with in the table allow its setting to be changed during operation even if "0" (initial value)
is set in Pr. 77 Parameter write selection.
10
F700_kaigaidoukon_EC.book 11 ページ 2008年7月28日 月曜日 午前10時32分
PARAMETER LIST
11
F700_kaigaidoukon_EC.book 12 ページ 2008年7月28日 月曜日 午前10時32分
PARAMETER LIST
12
F700_kaigaidoukon_EC.book 13 ページ 2008年7月28日 月曜日 午前10時32分
PARAMETER LIST
0 to 8, 10 to 14, 0 to 50%,
AU terminal 245 Rated slip 9999
184 function selection
16, 24, 25, 37, 4 9999
62 to 67, 9999 Slip compensation
246 time constant
0.01 to 10s 0.5s
JOG terminal
185 function selection
5
Constant-power
CS terminal function range slip
186 6 247 compensation
0, 9999 9999
selection 0 to 8, 10 to 14,
MRS terminal 16, 24, 25, 37, selection
187 function selection 62, 64 to 67,
24 0 to 100s,
STOP terminal 9999 250 Stop selection 1000 to 1100s, 9999
188 function selection
25 8888, 9999
RES terminal Output phase loss
189 62 251 protection selection
0, 1 1
function selection
RUN terminal 252 Override bias 0 to 200% 50%
190 function selection
0 to 5, 7, 8, 0
253 Override gain 0 to 200% 150%
10 to 19, 25, 26,
45 to 47, 64, Life alarm status
SU terminal function 255 (0 to 15) 0
191 selection 70 to 78, 90 to 1 display
96, 98, 99, Inrush current limit
256 circuit life display
(0 to 100%) 100%
IPF terminal 100 to 105, 107,
192 function selection
2
Control circuit
108, 110 to 116,
125, 126, 257 capacitor life (0 to 100%) 100%
OL terminal function 145 to 147, 164, display
193 selection
3
170, 190 to 196, Main circuit
198, 199, 9999 258 capacitor life (0 to 100%) 100%
FU terminal function
194 selection *1 4 display
13
F700_kaigaidoukon_EC.book 14 ページ 2008年7月28日 月曜日 午前10時32分
PARAMETER LIST
14
F700_kaigaidoukon_EC.book 15 ページ 2008年7月28日 月曜日 午前10時32分
PARAMETER LIST
589
Auxiliary motor 3
0 to 400Hz 0Hz 896 Power unit cost 0 to 500, 9999 9999
stopping frequency
Power saving 0, 1 to 1000h,
Auxiliary motor start 897 monitor average time 9999
9999
590 detection time
0 to 3600s 5s
Power saving
Auxiliary motor stop 898 cumulative monitor 0, 1, 10, 9999 9999
591 detection time
0 to 3600s 5s
clear
Traverse function Operation time rate 0 to 100%,
592 selection
0, 1, 2 0 899 9999
(estimated value) 9999
Maximum amplitude
593 0 to 25% 10% C0 CA terminal
amount
(900) calibration
Amplitude
compensation C1 AM terminal
594 0 to 50% 10%
amount during (901) calibration
deceleration Terminal 2
C2
Amplitude frequency setting 0 to 400Hz 0Hz
compensation (902) bias frequency
595 amount during
0 to 50% 10%
Terminal 2
acceleration C3
frequency setting 0 to 300% 0%
Amplitude (902) bias
596 acceleration time
0.1 to 3600s 5s
Terminal 2
125
Amplitude frequency setting 0 to 400Hz 50Hz
597 deceleration time
0.1 to 3600s 5s (903) gain frequency
Acceleration time at 0 to 3600s, Terminal 2
611 5/15s *1 C4
a restart 9999 frequency setting 0 to 300% 100%
(903) gain
867 AM output filter 0 to 5s 0.01s
Terminal 4
869 Current output filter 0 to 5s 0.02s C5
frequency setting 0 to 400Hz 0Hz
Input phase loss (904) bias frequency
872 protection selection
0, 1 0
Terminal 4
C6
Regeneration frequency setting 0 to 300% 20%
882 avoidance operation 0, 1, 2 0 (904) bias
selection Terminal 4
126
Regeneration frequency setting 0 to 400Hz 50Hz
883 avoidance operation 300 to 800V 760VDC (905) gain frequency
level Terminal 4
C7
Regeneration frequency setting 0 to 300% 100%
avoidance at (905) gain
884 deceleration
0 to 5 0
C8 Current output bias
detection sensitivity 0 to 100% 0%
(930) signal
Regeneration
avoidance 0 to 10Hz, C9 Current output bias
885 6Hz 0 to 100% 0%
compensation 9999 (930) current
frequency limit value C10 Current output gain
Regeneration 0 to 100% 100%
(931) signal
886 avoidance voltage 0 to 200% 100%
gain C11 Current output gain
0 to 100% 100%
(931) current
888 Free parameter 1 0 to 9999 9999
989
Parameter copy
10/100 *1 10/100 *1
alarm release
990 PU buzzer control 0, 1 1
889 Free parameter 2 0 to 9999 9999
PU contrast
991 adjustment 0 to 63 58
Cumulative power
891 monitor digit shifted 0 to 4, 9999 9999 Pr.CL Parameter clear 0, 1 0
times
ALLC All parameter clear 0, 1 0
892 Load factor 30 to 150% 100%
Er.CL Faults history clear 0, 1 0
LD/SLD
Energy saving value of PCPY Parameter copy 0, 1, 2, 3 0
0.1 to 55kW/
893 monitor reference applied
0 to 3600kW *1 motor
(motor capacity)
capacity
Control selection
during commercial
894 power-supply
0, 1, 2, 3 0
operation
*1 The setting depends on capacities. (01160 or less/01800 or more)
15
F700_kaigaidoukon_EC.book 16 ページ 2008年7月28日 月曜日 午前10時32分
TROUBLESHOOTING
7 TROUBLESHOOTING
When a fault occurs in the inverter, the inverter trips and the PU display automatically changes to any of the
following fault or alarm indications.
If the fault does not correspond to any of the following faults or if you have any other problem, please contact your
sales representative.
z Retention of fault output signal........... When the magnetic contactor (MC) provided on the input side of the
inverter is opened when a fault occurs, the inverter's control power will be
lost and the fault output will not be held.
z Fault or alarm indication ..................... When a fault or alarm occurs, the operation panel display automatically
switches to the fault or alarm indication.
z Resetting method ............................... When a fault occurs, the inverter output is kept stopped. Unless reset,
therefore, the inverter cannot restart. (Refer to page 16.)
z When any fault occurs, take the appropriate corrective action, then reset the inverter, and resume operation.
Not doing so may lead to the inverter fault and damage.
Operation 1: ..... Using the operation panel, press to reset the inverter.
(This may only be performed when a fault occurs (Refer to the Instruction
Manual for fault.))
OFF
Operation 3: ..... Turn on the reset signal (RES) for more than 0.1s. (If the RES signal is
kept on, "Err." appears (flickers) to indicate that the inverter is in a reset Inverter
status.)
RES
PC
16
F700_kaigaidoukon_EC.book 17 ページ 2008年7月28日 月曜日 午前10時32分
TROUBLESHOOTING
FN Fan fault E. 6 /
/ E. 7 / CPU fault
Overcurrent trip during E.CPU
E.OC1
acceleration
Overcurrent trip during constant Operation panel power supply
E.OC2 E.CTE short circuit, RS-485 terminal
speed
Overcurrent trip during power supply short circuit
E.OC3
deceleration or stop E.P24 24VDC power output short circuit
Regenerative overvoltage trip
E.OV1 Output current detection value
during acceleration E.CDO*
exceeded
Regenerative overvoltage trip
E.OV2 E.IOH* Inrush current limit circuit fault
during constant speed
Fault
E.IPF Instantaneous power failure * If an error occurs when using the FR-PU04, "Fault 14" is displayed
on the FR-PU04.
E.UVT Undervoltage
17
F700_kaigaidoukon_EC.book 18 ページ 2008年7月28日 月曜日 午前10時32分
Fan Fan
Fan
18
F700_kaigaidoukon_EC.book 19 ページ 2008年7月28日 月曜日 午前10時32分
FR-F740--EC 01800 02160 02600 03250 03610 04320 04810 05470 06100 06830 07700 08660 09620 10940 12120
Rated fuse voltage(V) 500V or more
Fuse Without power
factor improving
Maximum reactor
allowable
With power factor
rating (A)* improving reactor 300 350 400 500 600 700 800 900 1000 1100 1200 1350 1500 1800 2000
19
F700_kaigaidoukon_EC.book 20 ページ 2008年7月28日 月曜日 午前10時32分
70 30Hz or more* 3
60
20Hz
10Hz
10Hz Range on the right
characteristic curve
of
1) Set "1" in Pr. 71. (This provides a 100% continuous torque
6Hz
6Hz
0.5Hz
Non-operation range
Range on the left of characteristic in the low-speed range.)
50 0.5Hz characteristic curve
2) Set the rated current of the motor in Pr. 9.
Characteristic when
electronic thermal relay
240
(s) unit display in this range
120 *1 When a value 50% of the inverter rated output current (current
Electronic thermal relay
value) is set in Pr. 9
60 function for transistor *2 The % value denotes the percentage to the inverter rated output current.
protection It is not the percentage to the motor rated current.
52.5% 105% *3 When you set the electronic thermal relay function dedicated to the
50 100 120 150 Mitsubishi constant-torque motor, this characteristic curve applies
Inverter output current (%)
(% to the rated output current) to operation at 6Hz or higher.
CAUTION
⋅ Protective function by electronic thermal relay function is reset by inverter power reset and reset signal input. Avoid
unnecessary reset and power-off.
⋅ When multiple motors are operated by a single inverter, protection cannot be provided by the electronic thermal relay function.
Install an external thermal relay to each motor.
⋅ When the difference between the inverter and motor capacities is large and the setting is small, the protective characteristics of
the electronic thermal relay function will be deteriorated. In this case, use an external thermal relay.
⋅ A special motor cannot be protected by the electronic thermal relay function. Use the external thermal relay.
⋅ Electronic thermal relay does not function when 5% or less of inverter rated current is set to electronic thermal relay setting.
20
F700_kaigaidoukon_EC.book 21 ページ 2008年7月28日 月曜日 午前10時32分
MEMO
21
F700_kaigaidoukon_EC.book 22 ページ 2008年7月28日 月曜日 午前10時32分
REVISIONS
*The manual number is given on the bottom left of the back cover.
22