You are on page 1of 5

Environmental and wetstock

management solutions

Magnetostrictive
PROBES
Filling stations
and fuel depots
Magnetostrictive liquid level ATEX, CE, IP protection, Magnetostrictive level probe Main features
gauges OIML compliance Operating principle Supports tele-diagnostic/maintenance functions.
Internal sensor replacement without removing rod from
The operation of Magnetostrictive Level Probe is based
with rigid stainless steel shaft up to 5,5 meters • intrinsically safe or explosion proof on the principle denominated Wiedemann effect and the tank. Remote configuration of operation parameters.
suitable for gasoline, gasoil, LPG, adblue, solvents, versions allows a continuous and highly accurate reading of the Connection to the tank: fixed or adjustable thread flanged/
with multipoint technology. level of liquids inside a tank. inside riser.
• submersible IP68 protection certified
The level transmitter XMT consists of an electronic circuit Stainless Steel AISI 304/316 shaft
• metrological certification:
Different versions for different with microprocessor located in the head and of a stainless Measuring range from 500 mm. up to 5.500 mm
- OIML R85 for fixed tanks. steel rod housing a wave guide located inside the tank. Calculation of data relating to:
applications A high frequency electric impulse is generated by the - Product level in 0,01 mm
electronic device. - Interface level in 0,01 of mm. (water presence detection)
• radio wireless, battery powered
In the exact point of intersection with the magnetic field - Product mean temperature up to max. 5 integrated
• wired with RS485 communication generated by the permanent magnet housed in the float, digital sensors
• wired RS485 LOG: tank measure recording a mechanical impulse caused by the magnetostrictive Standard measuring accuracy: +/- 0,5 mm
if power and communication are lost. torsional deformation is generated. Standard resolution: +/- 0,01 mm
The mechanical impulse travels at the speed of sound Temperature accuracy range -20 +70 °C: +/- 0,2 °C
in the wave guide up to the detector located in the Temperature resolution: ± 0,0625 °C
measuring housing.
By measuring of the time elapsed between the sending
of the initial signal and its return the exact position of the
floats along the rod is defined with 0,01 mm. resolution.

I.S. wireless probes XMT-SI-RF “Multipoint” wiring for wired probes


New generation of magnetostrictive wireless level gauge with the ultimate low frequency wireless technology

Advantages Features
• Avoid expensive costs for digging, wiring and cables. • Wireless transmission to the RF receiver up to 2 Km.
• Low power consumption with save energy management. line of sight.
• Long life lithium battery up to 5 years. • RF repeater for difficult environmental application.
• Wake up on radio function.
Stainless steel IP68 compact version:
• Battery and antenna embedded inside the probe. • Power up 500 mW adjustable.
• Suitable for underground and above ground tanks. • Signal measurement and display.
• Reliable and guaranteed data transmission in harsh
conditions (metallic lid cover, concrete sump). MAGLINK
console
MAGLINK
console Discriminating sensor

RF rece
iver
Junction box

Modem wireless

Magnetostrictive
level probe
Magnetostrictive probes
PATENTED
I.S. probes XMT-SI-485/RF Series Black Seal XMT LOG Black Seal main features
Intrinsecally safe version.
- Stainless Steel Enclosure Ø 50 mm IP68
theft-proof with memory Bend-proof, strong 2" stainless steel shaft.
Integrated floats: preventing theft attempts, suitable for
Certifications
This Magnetostrictive XMT-SI-LOG smart-probe belongs to
(submersible up to 1,2 m per 24 hours) the same family as XMT-SI but with data logger function turbulent flowing liquids. Explosion proof ATEX certifications
- In 2” riser installation and with floats (fuel and water) integrated in a 2" stainless Memory: data saving in case of power failure; should INERIS 06ATEX0051 II 1/2 GD Ex d IIA T6
- 7/8” circular connector with standard cable length 2 m. steel shaft up to 5,5 meters, suitable for gasoline and cable be cut or removed, data are saved in probe internal
Ex tD A21 IP66/68 T85 °C Tamb: -20 °C to 60 °C
Ø 9 mm, hydrocarbon resistant in according ENI specification diesel fuel. memory.
- Power supply: 12 VDC Supports tele-diagnostic /maintenance functions, CESI 06ATEX 020 II 1/2 G Ex db II 2 Ex tb IIIC
remote configuration of operation parameters.
- RS485 serial port / antenna Different versions for different Connection to the tank: inside riser
T 85 °C IP67
- I.S. circuits to wire to an intrinsically safe barrier active
(BRA-SI) or passive (BRA-SIP) (only for RS485 Series)
applications: Circular connection Intrinsically safe ATEX certifications
• radio wireless, battery powered Power supply: 12 VDC / battery
CEC 09 ATEX131 Rev. 4 II 1G Ex ia IIB T4 Ga
I.S. probes XMT-SI-485 LOG Series • wired RS485 LOG: tank level data saving in case RS485 serial port / antenna.
II 1D Ex ta IIIC T 135 °C Da IP66/68
of power failure, 1 month of memory. IP68 protection (submersible up to 1,2 m. per 24 hours)
This Magnetostrictive probe belongs to the same family of FISCO Field Device Ex ta IIC T4
XMT-SI-485 with data logger functionality which Calculation of data relating to:
is automatically activated when the external power supply - Product level in 0,01 mm
and/or data is off. - Interface level in 0,01 of mm. (water presence detection) Metrological certifications
- Product mean temperature up to max. 5 integrated digital OIML R85/2008-CZ-11.03 of 29.06.2011
LOG operating mode sensors for fixed tanks
When external power supply is present, as the normal case, Standard measuring accuracy: +/- 0,5 mm
the probe works as usual replying to the polling protocol. Standard resolution: +/- 0,01 mm
When the power/data is off, an internal battery Temperature accuracy range -20 +70 °C: +/- 0,2 °C
is automatically connected to the electronics to store
Temperature resolution: ± 0,0625 °C
movement data in its internal memory which is available
for download when the power is restored.
This option is available both for new probes and existing
probes as a retrofit.

Probes XMT

XMT-Exd

XMT-SI-RS485

Black Seal LOG


XMT-SI-RF
Fuel quality analisys and product identification
Certifications
• Fuel Density ρ (kg/m³) • Temperature (°C) CEC 13 ATEX 051
• Fuel Viscosity µ (cp) • Multi-parametric II 1 G Ex ma IIC T5/T3 Ga IP66/68.

• Fuel Dielectric constant ɛ calculation

DVD description DVD features Fuel types


The DVD TUNING FORK sensor directly and simultaneously • Patented Tuning Fork Technology with high accuracy Simultaneous measurement with DVD sensor for three
measures the viscosity, density, dielectric constant, • Static and direct measurement, no moving parts, physical properties enables absolute fuel fingerprint
temperature of fuels. resistant to turbulence analysis to confirm fuel type.
Relying on patented tuning fork technology, the sensor • Rugged construction for high pressure
monitors the direct and dynamic relationship between and high flow environments
multiple physical properties to determine the quality, • Proprietary corrosion and contaminant resistant
condition and contaminant loading of fuels such as coating for wetted parts
diesel biodiesel, gasoline, Jet fuel, kerosene, biodiesel
• On-board microprocessor for real-time data analysis
concentration and urea quality.
• Highly reliable and long term stability
The multi-parametric analysis capability improves fluid
• ATEX Compliance, suitable for 0 zone.
characterization algorithms.
Circular connector
The DVD provides in-line monitoring of fluids for a wide
range of applications including fuel tanks, process lines DVD application version
and pressurized high flow conduits.
• Density solution for retail and depots automation
A digital serial compliant protocol provides easy to connect • Real time fuel quality
interface to Consoles controller.
• Biodiesel in diesel concentration

PATENTED • Anti-crossover fuels detection


• Sump and interstitial sensors with liquid
discriminating (empty status / type of fuel / water).

Cable gland
version

Black Seal DVD

Fuel quality sensor software

In-line, continuous process In tank density meter


density monitoring for pipe up to 20 meters
installations
Tokheim ProGauge
Via Pola, 6
20813 Bovisio Masciago (MB)
Italy
www.tokheimprogauge.com

You might also like