Professional Documents
Culture Documents
Design Options- I
Emerson Confidential
Agenda
Flow Direction
o Cage Guiding
o Post Guiding
Plug Guiding methods
Cage guiding
Post guiding
Unbalanced Plug
o Provides tight shutoff
oPrimary leakage path only
o Suitable for high temperature
applications
o Preferred in smaller valve sizes with low
pressure drop
o More actuator force required in high
pressure drop applications
Types of Plugs
Balanced Plug
o Holes drilled through the plug
o Eliminates plug instability
o Lesser actuator force is required compared to
unbalanced type
o Secondary leakage path between valve plug
and cage
Flow Direction
Unbalanced – Flow Up (PTTO)
o PTTO – Pressure Tends To
Open
oPreferred Flow direction
o PTTC – Pressure Tends To
Close
Flow Up PTTO
Unbalanced
Plug Flow Down PTTC
ED – Seal ring
Solid Graphite seal / piston ring - Standard
Fisher easy-e valves - ED
ED – C-seal for Class V Shutoff (up to 593 deg C)
Fisher easy-e valves - ED
ED – C-seal for Class V Shutoff (up to 593 deg C)
Fisher easy-e valves - Summary
EZ ES ET ED
Type Globe Globe & Angle Globe & Angle Globe & Angle
Size 0.5 to 4 Inch 1 to 8 Inch 1 to 8 Inch 1 to 8 Inch
Rating 125, 150, 300 &
150, 300 & 600 150, 300 & 600 150, 300 & 600
600
Guiding Post Cage Cage Cage
Plug Unbalanced Unbalanced Balanced Balanced
Flow Direction
Up Up Down Down
(PTTO)
Shutoff Class
Standard Class IV Class IV Class IV Class II
Optional Class V & VI Class V & VI Class V & VI Class III, IV & V
Parts Interchangeability
Bellows Seals
Packing
Bonnets
Gaskets
Stem
Valve Plug
Cage
Seat Ring
Bodies