You are on page 1of 9

Apartment, Belgaum, Bangalore.

PROJECT: M/S APARTMENT, BELGAUM, BANGALORE.


SCHEDULE OF QUANTITIES FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF SOLAR & LOW SIDE ELECTRICAL WORKS
QUANTITY SUPPLY IN INR ITC IN INR
S.NO DESCRIPTION UNIT
STILT GF TERRACE TOTAL RATE AMOUNT RATE AMOUNT
A LT PANELS
Supply, Installation, Testing and Commissioning of Indoor type Fully type
1.00 tested LT Switchboards, Floor mounting type, 4b Design construction,
Bottom/Top entry. Refer enclosed SLD.

Refer standard: IEC 61439-1 &2 And Internal Arc 61641.


Enclosure: Compartmentalized Single front CRCA
Doors: 2mm, Body: 2mm, Gland: 3mm covers and partitions: 1.6mm, Base
Channel: 3mm (Floor Mounting)
IP class: IP52 for Indoor & IP55 for Outdoor
Connectivity: Below 100A, PVC insulated flexible copper cable, 100A and
above busbar.

Bus bars: Electrolytic grade conductivity as per standard IS 5082

Busbar Material: As per SLD (0.7A/Sqmm for Al & 1.7A/Sqmm for Copper)

Bus bar supports: DMC/FRP/SMC


Bus bar joints: Shrouded/Tinned
Breakers: Microprocessor based is 250 A Adjustable overload and
Adjustble short circuit with time dealy /Thermal Magnetic up to 200A
Protection releases: As per SLD (Adjustable over current & short circuit
unless otherwise specified)
Ics=Icu for all breakers
Utilization category: All MCCB/ACB's shall be Cat: A except ACB's for Ltg
& raw power input distribution panel shall be with Cat: B.
Louvers: Busbar chamber shall have louvers with fine mesh inside
Shade: Epoxy powder coated RAL 7032, Coating Thickness should be
above 80micron.
Design: Modular type
Cable entry: As per site condition
SPD: As per SLD
Note:1) All the breakers shall have spreaders/phase
separators/RHOM/Pad lock/Door lock/trip free 2)Breakers shall have
provision to add shunt trip 3) Shunt trip for the breakers to be provided
wherever shown 4) Insulated shrouding shall be provided for live parts 5)
FRLS PVC copper wires shall be used for control wiring 6) CT's shall be
provided with shorting terminals 7) All ACB's, MCCB's and MCB's Should
be as per LOTO Requirement

1.01 LT Metering Panel Nos 1 1


A) Incomer :
100Amps TPN Variable Type MCCB with Manual Closing Mechanism of 25
kA Short Circuit Rating with Thermal Magnetic O/L, S/C, - 1 No
B) Busbar :
1 Set of 100A, TPN Aluminium Busbar for the entire length of the Panel as
per specification
C) Outgoings :
20Amps DP C-Curve MCB with 16 kA Short Circuit Rating - 9 Nos
20Amps DP Fuse Link - 9 Nos with terminal Block
Provision for Single Phase KWH Meter - 9 Nos
25Amps FP C-Curve MCB with 16 kA Short Circuit Rating - 2 Nos
25Amps FP Fuse Link - 2 Nos with terminal Block
Provision for Three Phase KWH Meter - 2 Nos
D) Indications :
LED ON/OFF/ TRIP indication for incomer control through MCB
LED R,Y & B Phase indication for incomer control through MCB
E) CT's :
100/5A, Class-I, 5VA burden moulded CT's - 3 Nos
F) Metering :
3 phase, 4 wire, Digital flush type Class-I accuracy VRF meter with RS
485, 100/5A, Class-I, 5VA burden moulded CT's. - 1 No
G) SPD :
25KA SPD, B+C class, 3Phase with 32A TPN C-MCB - 1 No
H) Accessories :
1No - Earth Leakage Relay

Sub Total (A)

B LT CABLES

Supply, Laying, Testing and Commissioning of multi stranded XLPE / PVC


insulated, Armoured / Unarmoured / Flexible, Aluminium / Copper
2.00
conductor, laid over in already laid cable tray / fixing on walls including
Galvanized clamping support to the cable as per approved installation dwg.

Referer Indian standard


Specification: IS 1554, 7098, 5831, 3975, 694
Installation: IS1255
Multicore/Single core Armoured/Un-armoured cable
Voltage grade:1100Volts
Armoure: Galvanized Steel strip 16 Sq.mm and above / Wire for multicore
upto 10 Sq.mm
Non Magnetic Aluminum Wire/Strip for Single core
Aluminium / Copper Armoured Power Cables
2.01 3.5Cx50 Sq.mm A2XFY Mtrs 55 55

Page 1 of 9
Apartment, Belgaum, Bangalore.

QUANTITY SUPPLY IN INR ITC IN INR


S.NO DESCRIPTION UNIT
STILT GF TERRACE TOTAL RATE AMOUNT RATE AMOUNT
2.02 4Cx6 Sq.mm AYWY Mtrs 10 10
2.03 4Cx4 Sq.mm AYWY Mtrs 132 132

Copper Flexible cables (Confirm to as per IS 694) with Metalic


Flexible conduits.
Note: Outer sheath for power cable shall be black color
Note: Outer sheath for earthing cable shall be green color
Note: innersheath is not required
Insulation: Class A PVC
2.04 3Cx4 Sq.mm YY Mtrs 35 35 70
2.05 1Cx4 Sq.mm YY Mtrs 8 8

SUB TOTAL (B)

C LT CABLE TERMINATION
Supply, Installation, Testing and Commissioning of Compression type
cable gland, copper sockets for copper cables, insulation tape, anti
3.00
corrosive paste, brass clamps for gland earthing with 14 SWG copper wire
to connect to nearest earth flat.
Refer Standard: IS 12943 for single compression, BS 6121 for Double
compression
Gland type: Brass with nickel plated for Armoured cables and PVC for
copper flexible cables.
Compression: Single for Indoor, Double for Outdoor
Sealing Ring: Natural rubber for indoor, Neoprene for Outdoor

Aluminium / Copper Armoured Power Cables


3.01 3.5Cx50 Sq.mm A2XFY- Single Compression Nos. 2 2
3.02 4Cx6 Sq.mm AYWY- Single Compression Nos. 2 2
3.03 4Cx4 Sq.mm AYWY - Single Compression Nos. 12 12

Copper Flexible cables (Confirm to as per IS 694).


3.04 3Cx4 Sq.mm YY - Single Compression Nos. 6 4 10
3.05 1Cx4 Sq.mm YY - Single Compression Nos. 4 4

SUB TOTAL (C)

D DISTRIBUTION BOARDS
Supply, Installation, Testing and Commissioning of MCB Distribution board
4.00
as per approved installation dwgs.
All the Swithgear should be LOTO compatible
Standard Reference: IS 8623
Enclosure: 1.2mm CRCA Sheet Steel, Powder Coated
Door: Double Door
Protection: IP 42
Cable Entry: Top & Bottom
For UPS distribution ELCB/RCBO/RCCB's shall be harmonic resistant
Bus bar: Shall be tinned Copper and 200% rating for UPS DB Neutral Link
MCB's: 25/16/10kA 'C' Curve for Lighting & Raw power, 16/10kA 'D' Curve
for UPS Distribution

Note: 1)
Separate Earth bus/Neutral bus for each phase. 2) Each Circuit shall have
yellow ferrules with circuit number. 3) Accessories required for installation
of DB's on Wall/Column/Gyp Board shall be considered. 4) DB's shall be
covered with powder coated (paint should match with DB Color) wire ways
all around and up to ceiling to receive incoming circuits, how ever raceway
shall be considered as a separate items & same shall be paid under
raceway item. 5) Laminated A3 OR A4 size SLD & Control drawing copy
shall be pasted inside DB door 6) Safe shroud for Neutral link shall be
provided. 7) SPD should be part of Integral of DB and should not be install
outside of the DB. 8) All DB doors are metal door only unless otherwise
specified. 9) All MCB's Should be as per LOTO Requirement

4.01 Common Area 8Way VTPN PDB Set 1 1


Supply, erection, testing and commissioning of three phase, DB 8 way
VTPN MCB DB double door type, IP42 powder coated comprising of "C"
curve MCB's
Incomer:
1 No - 25A TPN MCB
1 No - 16KA B+C Type SPD with 20A TPN MCB
Outgoings
6 Nos - 16A TP MCB
4 Nos - 20A SP MCB
2 Nos - 16A SP MCB
Including all interconnections & accessories etc. as reqd
4.02 Common Area, 16Way SPN LDB Set 1 1
Supply, erection, testing and commissioning of MCB DB double door type,
IP42 powder coated 16 Way DB comprising of "C" curve MCB's for
Lighting DB.
Incommer
1 No - 16A DP MCB
1 No - 16KA B+C Type SPD with 16A DP MCB
Outgoings
8 Nos - 6A SP MCB
3 Nos - DUMMY
Including all interconnections & accessories etc. as reqd

Page 2 of 9
Apartment, Belgaum, Bangalore.

QUANTITY SUPPLY IN INR ITC IN INR


S.NO DESCRIPTION UNIT
STILT GF TERRACE TOTAL RATE AMOUNT RATE AMOUNT

4.03 Flat, 2 Row 14 Module Flexy PDB - 1 & 2 Set 2 2


Supply, erection, testing and commissioning of MCB DB double door type,
IP42 powder coated 2 Row 14 Module Flexy DB comprising of "C" curve
MCB's for Lighting & Power DB.
Incommer
1 No - 20A DP MCB
1 No - 16KA B+C Type SPD with 16A DP MCB
Outgoings
13 Nos - 16A SP MCB
6 Nos - 6A SP MCB
4 Nos - Dummy
Including all interconnections & accessories etc. as reqd

Sub Total (D)

E WIRING AND CONDUITS


Supply, Laying, Testing and Commissioning of copper wires, including
5.00 termination on both ends with copper lugs in existing Wire
ways/Conduits/Flexible
Refer standard: IS 694
Voltage Grade:660/1100V
Conductor: Multistrand Copper
Insulation: PVC
Outrsheath: FRLS PVC only for multicore cable
Note: 1) There shall not be any joints except at the equipment end. 2)
Individual UPS and Raw power points shall have yellow ferrules for circuit
identification.
Supply & Laying of 2R 1C 4 Sq.mm + 1R 1CX2.5Sq.mm PVC insulated
FRLS flexible unarmoured multistrand copper wire with 25mm dia medium
5.01 class FRLS PVC Conduit in the ceiling/floor in the ceiling/floor with all Mtrs 15 250 15 280
accessories as reqd (Raw power 16/20A Sockets).- Primary Point (Raw
Power)
Supply & Laying of 2R 1C 2.5 Sq.mm + 1R 1CX1.5Sq.mm PVC insulated
FRLS flexible unarmoured multistrand copper wire with 25mm dia medium
5.02 class FRLS PVC Conduit in the ceiling/floor in the ceiling/floor with all Mtrs 5 500 10 515
accessories as reqd (Raw power 16/20A Sockets). Secondary Point (Raw
Power)

Supply, Erection, Testing and commissioning of insulated 3runs 1.5 sqmm


PVC insulated FRLS copper wire with 25mm dia medium class FRLS PVC
5.03 Mtrs 215 480 95 790
Conduit in the ceiling/floor along with other associated accessories as
required as per the site conditions. (Functional lighting)

Supply, Erection , Testing and commissioning of Cat 6 insulated FRLS


5.04 Mtrs 100 100
copper wire
Supply, Erection , Testing and commissioning of 2Pair insulated FRLS
5.05 Mtrs 100 100
copper wire

Supply, Laying, Testing & commissioning of Medium Duty Class MS,


PVC, GI Conduit on Ceiling, Wall, In floor etc. for Power wiring and
any other control wiring

NOTE:
1) Conduits running above false ceiling in multiples shall be supported by
Slotted GI 'C' channel at distance not more than 0.5mtrs intervals. OR else
with spacers & saddles at an intervals of 0.5mtrs. 2) Accessories shall
includes Bends, Collars, junction boxes, Spacers, saddles, screws,
Flexibles (all are MS, PVC, GI). 3) Conduits shall be Medium duty & ISI
marked. 4) The number of wires drawn in each conduit shall be as per IS
694 code. 5) No different phases shall be drawn in same conduit.

5.06 32mm dia Medium Class PVC FRLS Conduit Mtrs Rate
5.07 25mm dia Medium Class PVC FRLS Conduit Mtrs Rate
5.08 19mm dia Medium Class PVC FRLS Conduit Mtrs Rate
5.09 100mm dia Medium Class GI Conduit Mtrs 10 10
5.10 32mm dia Medium Class GI Conduit Mtrs 5 5
5.11 32mm dia Medium Class MS Conduit Mtrs Rate
5.12 25mm dia Medium Class MS Conduit Mtrs 10 10
5.13 19mm dia Medium Class MS Conduit Mtrs Rate
Supply,Installation, Testing & commissioning of GI Back box on
Ceiling, Wall, In floor etc. for Power wiring and any other control
wiring
5.14 1M Switch Plate with GI Back Box Nos 4 4
5.15 2M Switch Plate with GI Back Box Nos 26 1 27
5.16 3M Switch Plate with GI Back Box Nos 26 26
5.17 4M Switch Plate with GI Back Box Nos 1 2 3
5.18 6M Switch Plate with GI Back Box Nos 10 10
5.19 8M Switch Plate with GI Back Box Nos 2 2
5.20 9M Switch Plate with GI Back Box Nos 2 2
5.21 12M (2*6) Switch Plate with GI Back Box Nos 4 4
5.22 16M (2*8) Switch Plate with GI Back Box Nos 2 2

SUB TOTAL (E)

F SWITCHES AND SOCKETS


Supply, Installation, Testing and Commissioning of the following
6.00 Modular/Industrial Switch, sockets with modular front plate, with suitable
GI back box accessories as per the site conditions.
Refer Standard: BS 1363, IS 3864, IS 1293
Terminal: Phosphor bronze
Enclosure for Current carrying part; Thermoplastic/ABS plastic complying
to environment recycling
Frontplate: Thermoplastic /Polycarbonate complying to environmental
recycling
IP Class for Modular sockets: IP20
Note: Safety shutters to prevent accidental contact with live parts shall be
provided. No indicator shall be provided for switches

Page 3 of 9
Apartment, Belgaum, Bangalore.

QUANTITY SUPPLY IN INR ITC IN INR


S.NO DESCRIPTION UNIT
STILT GF TERRACE TOTAL RATE AMOUNT RATE AMOUNT
Supply, Installation, testing and commissioning of 3 Nos of 6A Round pin
Socket suitable for round pins controlled by 1 nos 16A switch in a single
modular plate with suitable GI back box and fixing the same for a single
6.01 location with a dummy if necessary and other associated accessories in the Nos 1 6 7
work station as required as per the site conditions. Color of the switches,
sockets and front plates would be as per Client approval. (For TV & CCTV
)
Supply, installation, testing and commissioning of 6A Round 5 pin Socket
6.02 Nos 1 34 35
controlled by 6A switch along with GI Boxes
Supply, installation, testing and commissioning of 6/16A Round 5 pin
6.03 Nos 3 30 1 34
Socket controlled by 16A switch along with GI Boxes
6.04 Supply, installation, testing and commissioning of 6A One Way Switch Nos 4 58 2 64

6.05 Supply, installation, testing and commissioning of 16A One Way Switch Nos 12 12

6.06 Supply, installation, testing and commissioning of 6A Two Way Switch Nos 12 12
Supply, installation, testing and commissioning of 10 A Bell Push With
6.07 Nos 2 2
Indicator
6.08 Supply, installation, testing and commissioning of 1M Fan Regulator Nos 10 10
6.09 Supply, installation, testing and commissioning of Call Bell Nos 2 2
Supply, installation, testing and commissioning of RJ45 Socket along with
6.10 Nos 2 2
GI Backbox
Supply, installation, testing and commissioning of RJ11 Socket along with
6.11 Nos 2 2
GI Backbox
Supply, installation, testing and commissioning of TV Outlet Point along
6.12 Nos 2 2
with GI Backbox
Supply, installation, testing and commissioning of Mechanical Limit Switch- Plunger
6.13 Type ( 1NO ,1NC WITH SPDT ACTION)
Nos 6 6
Industrial Sockets / Isolators
Terminal : Phosphor bronze
Enclosure: Polycarbonate upto 125A, MS Powder Coated above 125A.
IP Class :IP44 (Indoor), IP55 (Outdoor)
Note: The enclosure color of socket shall be different for different Source

Supply, erection, testing and commissio`ning of 16A FP MCB(C-Curve)


with IP44 enclosure concealed in wall with sufficient space for cable
6.14 Nos 3 3
termination as required at site including providing necessary earthing
provisions.

SUB TOTAL (F)

G EARTHING SYSTEM
7.00 EARTHSTRIPS
Supply, Installation on trays/in ground/on wall/in trench etc, Testing and
Commissioning of the Earth strips as per installation standard IS 3043
Strips above ground: GI
Strips below groung: MS
Accessories: Welding for GI/MS, Brazing for Copper, GI nut bolts for
connection at eqpt end/PVC sleeves for copper strips/Epoxy Insulated
mounts shall be considered
7.01 50 x 6 mm - GI strip Mtrs Rate
7.02 25 x 3 mm - GI strip Mtrs 10 10
7.03 25 x 3 mm - CU strip Mtrs 5 5
7.04 SITC of 8SWG Cu Wire Mtrs 30 10 40

600(W)x600(L)x450(D)mm Chamber Size. Chemical Earthing with


4.5meter long GI Pipe with funnel and All required Accessories for System
7.05 Nos 2 2
Earth pit. NOTE:The rate shall include Boring for installation of electrode
and other civil works associated.

SUB TOTAL (G)

H CABLE TRAYS AND RACEWAYS


Supply and Installation of the following sizes of Cable trays suspended
8.00
from the ceiling or Along the wall or in trench or on floor,
Refer standard: IS 1079 & 513
Material: Mild steel
Finish: Hot dip galvanized for Outdoor / Pre galvanized for indoor
Thickness: 0.9mm
Type: Ladder or Perforated/Solid
Rung Spacing:300mm
Rung width:35mm
Supports: MS angle supports with anticorrosive paint at an intervals of
500mm.
Accessories: Couplers, Bends, Reducers, Tees & Cross junctions shall be
considered.
Two cable joints to be connected with Angle coupler or Joint connectors
The trays installed on floor shall be mounted on 'C' clamp
The Verticla drop of trays installed on I Beam Secton shall be mounted on
Slotted Channel Bracket Support
CABLE TRAYS
100 mm x 60mm x 0.6mm thickness Perforated type with 2R 25 x 3 mm -
8.01 Mtrs Rate
GI strip
150 mm x 60mm x 0.7mm thickness Perforated type with 2R 25 x 3 mm -
8.02 Mtrs 40 10 50
GI strip
200 mm x 60mm x 0.7mm thickness Perforated type with 2R 25 x 3 mm -
8.03 Mtrs Rate
GI strip
300 mm x 60mm x 1mm thickness Perforated type with 2R 25 x 3 mm - GI
8.04 Mtrs 5 5
strip
450 mm x 60mm x 1.2mm thickness Perforated type with 2R 25 x 3 mm -
8.05 Mtrs 10 5 5 20
GI strip

SUB TOTAL (H)

I LIGHT FIXTURES

Page 4 of 9
Apartment, Belgaum, Bangalore.

QUANTITY SUPPLY IN INR ITC IN INR


S.NO DESCRIPTION UNIT
STILT GF TERRACE TOTAL RATE AMOUNT RATE AMOUNT
Supply, Installation, testing & commisioning of 40W 4Feet Endura LED
Light Fixture with CCT-4000K, CRI>80, UGR<19 and 2.5KV Surge
9.01 Nos 12 14 1 27
Protection LED Driver. MAKE : PHILIPS, MODEL NO:BN 108C LED 40S
PSU CDL WH or Equivalent.
Supply, Installation, testing & commisioning of 20W 2Feet Endura LED
Light Fixture with CCT-4000K, CRI>80, UGR<19 and 2.5KV Surge
9.02 Nos 2 5 2 9
Protection LED Driver. MAKE : PHILIPS, MODEL NO:BN108C LED 20S
PSU CDL WH or Equivalent.
Supply, Installation, testing & commisioning of 10W Bulk Head LED Light
9.03 Fixture with 2.5KV Surge Protection LED Driver. MAE: BAJAJ, MODEL Nos 7 7
NO: BIBWP 10W LED or Equivalent.

Supply, Installation, testing & commisioning of 100W Street Light LED Light
9.04 Fixture with Cross Aarm & 2.5KV Surge Protection LED Driver. MAKE: Nos 1 1
BAJAJ, MODEL NO: BRTFG 100W LED CR LED or Equivalent.

Supply, Installation, testing & commisioning of 10W Gate & Compound


9.05 Nos 9 9
Wall Decorative LED Light Fixture with 2.5KV Surge Protection LED Driver.

Supply, Installation, testing & commisioning of 1200mm dia Brushless DC


9.06 Nos 10 10
Motor Ceiling Fan
Supply, Installation, testing & commisioning of 10W Mirror LED Light
9.07 Nos 6 6
Fixture with 2.5KV Surge Protection LED Driver.

Supply, Installation, testing & commisioning of 10W Home Decorative Wall


9.08 Nos 22 22
Mounted LED Light Fixture with 2.5KV Surge Protection LED Driver.

Supply, Installation, testing & commisioning of 15W Surface Mounted


9.09 Nos 4 4
Round LED Light Fixture with 2.5KV Surge Protection LED Driver.

Supply, Installation, testing & commisioning of 2W Recess Mouted LED


9.10 Light Fixture with 2.5KV Surge Protection LED Driver. Make: Philips, Model Nos 12 12
No: Astra Spot

9.11 Supply, Installation, testing & commisioning of 4W Foot Lamp Nos 4 4

SUB TOTAL (I)

J SOLAR SYSTEM & MISCELLANEOUS

10.01 SITC of 16A DP Manual Change over Switch with necessary accessories. Nos 1 1

Supply, Installation, Testing & Commissing of 395Wp Monocrystalline Solar


10.02 Nos 6 6
Modules (10 Years Product Warranty) Make: Waaree / Renewsys

Supply, Installation, Testing & Commissing of 2kW, 230V Output, IP66,


10.03 Hybrid Inverter ( 5 Years Product Warranty) Make: Luminous, Model NO: Nos 1 1
Solar Nxt
Supply, Installation, Testing & Commissing of 150Ah Battery ( 5 Years
10.04 Product Warranty)Make: Luminous, Model NO: Luminous Solar LPTT Nos 2 2
12150H 150 AH C10 Tall Tubular battery
Supply, Installation, Testing & Commissing of Solar 2 row Design 3 Panel
10.05 Nos 1 1
Stand 395 watt

Supply, Installation, Testing & Commissing of 1C x 4Sqmm Cu DC Flexible


10.06 Mtrs 40 40 80
cable XLPO UV Red & Black for DC Cabling Module to Inverter

Supply, Installation, Testing & Commissing of DC Cabling accessories


(12Nos. 4sqmm Pin type copper lugs for DC Cabling Module to Inverter, 3
10.07 Lot 1 1
Panel MC4 Connectors pair, 3 Wire In, 1 Wire Out & 2 Nos UV Resistant
Junction Box / Connecting Box for Solar Panel Interconnection )

SUB TOTAL (J)

K SAFETY ITEMS
11.00 For Metering Panel etc
2mm thick Fire Rated PVC Insulated rubber Mats (Class A) 3.3KV grade
11.01 Sqm 1 1
(As per IS: 15652:2006)
11.02 Approved plant SLD duly Framed Nos 1 1

SUB TOTAL (K)

TOTAL
Add: SGST 9%
Add: CGST 9%
GRAND TOTAL

Page 5 of 9
Sl No
Apartment, Belgaum, Bangalore.

PROJECT: M/S APARTMENT, BELGAUM, BANGALORE.


SCHEDULE OF QUANTITIES FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF SOLAR & LOW SIDE ELECTRICAL WORKS
QUANTITY SUPPLY IN INR ITC IN INR
S.NO DESCRIPTION UNIT
GF RATE AMOUNT RATE AMOUNT
Copper Flexible cables (Confirm to as per IS 694) with Metalic
1
Flexible conduits.
Note: Outer sheath for power cable shall be black color
Note: Outer sheath for earthing cable shall be green color
Note: innersheath is not required
Insulation: Class A PVC
1.01 3Cx4 Sq.mm YY Mtrs 18 52 910

C LT CABLE TERMINATION
Supply, Installation, Testing and Commissioning of Compression type
cable gland, copper sockets for copper cables, insulation tape, anti
2.00
corrosive paste, brass clamps for gland earthing with 14 SWG copper wire
to connect to nearest earth flat.
Refer Standard: IS 12943 for single compression, BS 6121 for Double
compression
Gland type: Brass with nickel plated for Armoured cables and PVC for
copper flexible cables.
Compression: Single for Indoor, Double for Outdoor
Sealing Ring: Natural rubber for indoor, Neoprene for Outdoor
Copper Flexible cables (Confirm to as per IS 694).
2.01 3Cx4 Sq.mm YY - Single Compression Nos. 2 120 240

D DISTRIBUTION BOARDS
Supply, Installation, Testing and Commissioning of MCB Distribution board
3.00
as per approved installation dwgs.
All the Swithgear should be LOTO compatible
Standard Reference: IS 8623
Enclosure: 1.2mm CRCA Sheet Steel, Powder Coated
Door: Double Door
Protection: IP 42
Cable Entry: Top & Bottom
For UPS distribution ELCB/RCBO/RCCB's shall be harmonic resistant
Bus bar: Shall be tinned Copper and 200% rating for UPS DB Neutral Link
MCB's: 25/16/10kA 'C' Curve for Lighting & Raw power, 16/10kA 'D' Curve
for UPS Distribution

Note: 1)
Separate Earth bus/Neutral bus for each phase. 2) Each Circuit shall have
yellow ferrules with circuit number. 3) Accessories required for installation
of DB's on Wall/Column/Gyp Board shall be considered. 4) DB's shall be
covered with powder coated (paint should match with DB Color) wire ways
all around and up to ceiling to receive incoming circuits, how ever raceway
shall be considered as a separate items & same shall be paid under
raceway item. 5) Laminated A3 OR A4 size SLD & Control drawing copy
shall be pasted inside DB door 6) Safe shroud for Neutral link shall be
provided. 7) SPD should be part of Integral of DB and should not be install
outside of the DB. 8) All DB doors are metal door only unless otherwise
specified. 9) All MCB's Should be as per LOTO Requirement

3.01 Flat, 2 Row 14 Module Flexy PDB - 1 & 2 Set 1 3500 3500
Supply, erection, testing and commissioning of MCB DB double door type,
IP42 powder coated 2 Row 14 Module Flexy DB comprising of "C" curve
MCB's for Lighting & Power DB.
Incommer
1 No - 20A DP MCB
1 No - 16KA B+C Type SPD with 16A DP MCB
Outgoings
13 Nos - 16A SP MCB
6 Nos - 6A SP MCB
4 Nos - Dummy
Including all interconnections & accessories etc. as reqd

E WIRING AND CONDUITS


Supply, Laying, Testing and Commissioning of copper wires, including
4.00 termination on both ends with copper lugs in existing Wire
ways/Conduits/Flexible
Refer standard: IS 694
Voltage Grade:660/1100V
Conductor: Multistrand Copper
Insulation: PVC
Outrsheath: FRLS PVC only for multicore cable
Note: 1) There shall not be any joints except at the equipment end. 2)
Individual UPS and Raw power points shall have yellow ferrules for circuit
identification.
Supply & Laying of 2R 1C 4 Sq.mm + 1R 1CX2.5Sq.mm PVC insulated
FRLS flexible unarmoured multistrand copper wire with 25mm dia medium
4.01 class FRLS PVC Conduit in the ceiling/floor in the ceiling/floor with all Mtrs 125 65 8125
accessories as reqd (Raw power 16/20A Sockets).- Primary Point (Raw
Power)
Supply & Laying of 2R 1C 2.5 Sq.mm + 1R 1CX1.5Sq.mm PVC insulated
FRLS flexible unarmoured multistrand copper wire with 25mm dia medium
4.02 class FRLS PVC Conduit in the ceiling/floor in the ceiling/floor with all Mtrs 250 52 13000
accessories as reqd (Raw power 16/20A Sockets). Secondary Point (Raw
Power)

Supply, Erection, Testing and commissioning of insulated 3runs 1.5 sqmm


PVC insulated FRLS copper wire with 25mm dia medium class FRLS PVC
4.03 Mtrs 240 45 10800
Conduit in the ceiling/floor along with other associated accessories as
required as per the site conditions. (Functional lighting)

Page 7 of 9
Apartment, Belgaum, Bangalore.

QUANTITY SUPPLY IN INR ITC IN INR


S.NO DESCRIPTION UNIT
GF RATE AMOUNT RATE AMOUNT
Supply, Erection , Testing and commissioning of Cat 6 insulated FRLS
4.04 Mtrs 50 18 900
copper wire
Supply, Erection , Testing and commissioning of 2Pair insulated FRLS
4.05 Mtrs 50 12 600
copper wire
Supply, Laying, Testing & commissioning of Medium Duty Class MS,
PVC, GI Conduit on Ceiling, Wall, In floor etc. for Power wiring and
any other control wiring

NOTE:
1) Conduits running above false ceiling in multiples shall be supported by
Slotted GI 'C' channel at distance not more than 0.5mtrs intervals. OR else
with spacers & saddles at an intervals of 0.5mtrs. 2) Accessories shall
includes Bends, Collars, junction boxes, Spacers, saddles, screws,
Flexibles (all are MS, PVC, GI). 3) Conduits shall be Medium duty & ISI
marked. 4) The number of wires drawn in each conduit shall be as per IS
694 code. 5) No different phases shall be drawn in same conduit.

4.06 32mm dia Medium Class PVC FRLS Conduit Mtrs 45 0


4.07 25mm dia Medium Class PVC FRLS Conduit Mtrs 200 40 8000
4.08 19mm dia Medium Class PVC FRLS Conduit Mtrs 200 35 7000
4.09 100mm dia Medium Class GI Conduit Mtrs 210 0
4.10 32mm dia Medium Class GI Conduit Mtrs 120 0
4.11 32mm dia Medium Class MS Conduit Mtrs 120 0
4.12 25mm dia Medium Class MS Conduit Mtrs 100 0
4.13 19mm dia Medium Class MS Conduit Mtrs 80 0
Supply,Installation, Testing & commissioning of GI Back box on
Ceiling, Wall, In floor etc. for Power wiring and any other control
wiring
4.14 1M Switch Plate with GI Back Box Nos 2 55 110
4.15 2M Switch Plate with GI Back Box Nos 13 55 715
4.16 3M Switch Plate with GI Back Box Nos 13 55 715
4.17 4M Switch Plate with GI Back Box Nos 1 65 65
4.18 6M Switch Plate with GI Back Box Nos 5 95 475
4.19 8M Switch Plate with GI Back Box Nos 1 110 110
4.20 9M Switch Plate with GI Back Box Nos 1 110 110
4.21 12M (2*6) Switch Plate with GI Back Box Nos 2 135 270
4.22 16M (2*8) Switch Plate with GI Back Box Nos 1 160 160

F SWITCHES AND SOCKETS


Supply, Installation, Testing and Commissioning of the following
5.00 Modular/Industrial Switch, sockets with modular front plate, with suitable
GI back box accessories as per the site conditions.
Refer Standard: BS 1363, IS 3864, IS 1293
Terminal: Phosphor bronze
Enclosure for Current carrying part; Thermoplastic/ABS plastic complying
to environment recycling
Frontplate: Thermoplastic /Polycarbonate complying to environmental
recycling
IP Class for Modular sockets: IP20
Note: Safety shutters to prevent accidental contact with live parts shall be
provided. No indicator shall be provided for switches
Supply, Installation, testing and commissioning of 3 Nos of 6A Round pin
Socket suitable for round pins controlled by 1 nos 16A switch in a single
modular plate with suitable GI back box and fixing the same for a single
5.01 location with a dummy if necessary and other associated accessories in the Nos 3 280 840
work station as required as per the site conditions. Color of the switches,
sockets and front plates would be as per Client approval. (For TV & CCTV
)
Supply, installation, testing and commissioning of 6A Round 5 pin Socket
5.02 Nos 17 35 595
controlled by 6A switch along with GI Boxes
Supply, installation, testing and commissioning of 6/16A Round 5 pin
5.03 Nos 15 55 825
Socket controlled by 16A switch along with GI Boxes
5.04 Supply, installation, testing and commissioning of 6A One Way Switch Nos 29 12 348

5.05 Supply, installation, testing and commissioning of 16A One Way Switch Nos 6 12 72

5.06 Supply, installation, testing and commissioning of 6A Two Way Switch Nos 6 12 72
Supply, installation, testing and commissioning of 10 A Bell Push With
5.07 Nos 1 12 12
Indicator
5.08 Supply, installation, testing and commissioning of 1M Fan Regulator Nos 5 25 125
5.09 Supply, installation, testing and commissioning of Call Bell Nos 1 110 110
Supply, installation, testing and commissioning of RJ45 Socket along with
5.10 Nos 1 25 25
GI Backbox
Supply, installation, testing and commissioning of RJ11 Socket along with
5.11 Nos 1 25 25
GI Backbox
Supply, installation, testing and commissioning of TV Outlet Point along
5.12 Nos 1 15 15
with GI Backbox
Supply, installation, testing and commissioning of Mechanical Limit Switch- Plunger
5.13 Type ( 1NO ,1NC WITH SPDT ACTION)
Nos 3 35 105

G EARTHING SYSTEM
6.00 EARTHSTRIPS
Supply, Installation on trays/in ground/on wall/in trench etc, Testing and
Commissioning of the Earth strips as per installation standard IS 3043
Strips above ground: GI
Strips below groung: MS
Accessories: Welding for GI/MS, Brazing for Copper, GI nut bolts for
connection at eqpt end/PVC sleeves for copper strips/Epoxy Insulated
mounts shall be considered
6.01 SITC of 8SWG Cu Wire Mtrs 5 18 90

CABLE TRAYS
150 mm x 60mm x 0.7mm thickness Perforated type with 2R 25 x 3 mm -
7.01 Mtrs 5 145 725
GI strip
450 mm x 60mm x 1.2mm thickness Perforated type with 2R 25 x 3 mm -
7.02 Mtrs 2.5 280 700
GI strip

Page 8 of 9
Apartment, Belgaum, Bangalore.

QUANTITY SUPPLY IN INR ITC IN INR


S.NO DESCRIPTION UNIT
GF RATE AMOUNT RATE AMOUNT

I LIGHT FIXTURES
Supply, Installation, testing & commisioning of 40W 4Feet Endura LED
Light Fixture with CCT-4000K, CRI>80, UGR<19 and 2.5KV Surge
9.01 Nos 7 140 980
Protection LED Driver. MAKE : PHILIPS, MODEL NO:BN 108C LED 40S
PSU CDL WH or Equivalent.
Supply, Installation, testing & commisioning of 20W 2Feet Endura LED
Light Fixture with CCT-4000K, CRI>80, UGR<19 and 2.5KV Surge
9.02 Nos 2.5 110 275
Protection LED Driver. MAKE : PHILIPS, MODEL NO:BN108C LED 20S
PSU CDL WH or Equivalent.
Supply, Installation, testing & commisioning of 1200mm dia Brushless DC
9.03 Nos 8 140 1120
Motor Ceiling Fan
Supply, Installation, testing & commisioning of 10W Mirror LED Light
9.04 Nos 3 80 240
Fixture with 2.5KV Surge Protection LED Driver.

Supply, Installation, testing & commisioning of 10W Home Decorative Wall


9.05 Nos 11 110 1210
Mounted LED Light Fixture with 2.5KV Surge Protection LED Driver.

Supply, Installation, testing & commisioning of 15W Surface Mounted


9.06 Nos 2 110 220
Round LED Light Fixture with 2.5KV Surge Protection LED Driver.

Supply, Installation, testing & commisioning of 2W Recess Mouted LED


9.07 Light Fixture with 2.5KV Surge Protection LED Driver. Make: Philips, Model Nos 6 60 360
No: Astra Spot

9.08 Supply, Installation, testing & commisioning of 4W Foot Lamp Nos 2 110 220

SUB TOTAL (J)

K SAFETY ITEMS
11.00 For Metering Panel etc
2mm thick Fire Rated PVC Insulated rubber Mats (Class A) 3.3KV grade
11.01 Sqm
(As per IS: 15652:2006)
11.02 Approved plant SLD duly Framed Nos

SUB TOTAL (K) 65114

TOTAL
Add: SGST 9%
Add: CGST 9%
GRAND TOTAL

Page 9 of 9