Option_1 Transfo

Summary of Cables

Description KW

Main Cable from T/F to New Proposed Room


2550
Near HFO Room

New Thermal/Steam Boiler 400

RO Plant 20

New Compressor Room near new Boilers

HDI Section

HDT Section

H2 Section

ISS Section
PSA Section

Make Up Section

ARU Section

OSBL Saf

Raw Material Tank Load Pump A

Raw Material Tank Load Pump B

Raw Material Tank UnLoad Pump C

Raw Material Tank Unload Pump D

Raw Material Tanks transfer pump E


Raw Material Tanks transfer pump F

Bio Napht Tank Load Pump A

Bio Napht Tank Load Pump B

Bio Napht Tank Unload Pump C

Bio Napht Tank Unload Pump D

Bio Napht Tank Transfer Pump E

Bio Napht Tank Transfer Pump F

SAF Storage Tank Load Pump A

SAF Storage Tank Load Pump B


SAF Storage Tank Unload Pump C

SAF Storage Tank Unload Pump D

SAF Storage Tank Transfer Pump A

SAF Storage Tank Transfer Pump A

SAF Product Tank Load Pump A

SAF Product Tank Load Pump B

SAF Product Tank Unload Pump C

SAF Product Tank Unload Pump D

SAF Product Tank Transfer Pump E


SAF Product Tank Transfer Pump F

UG Methanol Tank Load Pump A

UG Methanol Tank Load Pump B

UG Methanol Tank Unload Pump C

UG Methanol Tank Unload Pump D

UG Methanol Tank Transfer Pump E

UG Methanol Tank Transfer Pump F

Fire Water ponds A

Fire Water ponds B


Fire Water Tank A

Fire Water Tank B

Lighting Cables

Lighting Cables

Lighting Cables

Earthing cable

Earthing cable

Building Rooms Cables

Building Rooms Cables


BOQ-Ex
Category
Title

Sr No.

1
2

10

11

12

13

14
15

16
tion_1 Transformer Room to HFO New Room

Cable Size Route

14C X 630mm² Via OSBL SAF/Bio Plant Boundary


Core: Single Core
Type: Cu/PVC/PVC to HFO New room

4C X 185mm²
Core: Four Core New LT room to Boiler Control room
Type: Cu/PVC/PVC

4C X 16mm²
Core: Four Core New LT room to RO room
Type: Cu/PVC/PVC

4C X 50mm²
Core: Four Core New LT room to New Compressor
Type: Cu/PVC/PVC

4C X 95mm²
Core: Four Core New Lt room to HDI
Type: Cu/PVC/PVC

4C X 95mm²
Core: Four Core New LT room to HDT
Type: Cu/PVC/PVC

4C X 10mm²
Core: Four Core New LT room to H²
Type: Cu/PVC/PVC

4C X 95mm²
Core: Four Core New Lt room to ISS
Type: Cu/PVC/PVC
4C X 95mm²
Core: Four Core New Lt room to PSA
Type: Cu/PVC/PVC

4C X 95mm²
Core: Four Core New Lt room to Make Up
Type: Cu/PVC/PVC

4C X 400mm² New Lt room to ARU


Core: Four Core
Type: Cu/PVC/PVC (Note: if VFD installed at compressor)

4C X 120mm²
Core: Four Core Old Lt room to OSBL
Type: Cu/PVC/PVC

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF
3C X 10mm² Via trench from new control room OSBL
Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Four Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Four Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Four Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF
3C X 10mm² Via trench from new control room OSBL
Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Four Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Four Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF
3C X 10mm² Via trench from new control room OSBL
Core: Four Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF
3C X 10mm² Via trench from new control room OSBL
Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

4C X 6mm² Via trench and cable tray if require at OSBL


Core: Four Core
Type: Cu/PVC/PVC Saf

4C X 6mm²
Core: Four Core VIA Trench and GI pipe at ISBL SAF
Type: Cu/PVC/PVC

3C X 1.5mm²
Core: 3 Main cable to each 320 lights
Type: Cu/PVC/PVC

1C X 70mm²
Core: 1 VIA trench to Earthing Pits
Type: Rope

1C X 16mm² VIA Cable Trench In interconnection with


Core 1
Type: CU/PVC/PVC Rope

For new LT HFo room


7/29
New OSBl room
Core: 1
new SCADA room
Type: Cu/PVC
For new Boiler control and office
red: 6, Black:6 Green: 4 Blue: 3
For new LT HFo room
7/36
New OSBl room
Core: 1
new SCADA room
Type: Cu/PVC
For new Boiler control and office
red: 4, Black:4 Green: 1
Power and Control Cables for OSBL SAF Palnt
Project
OSBL SAF

Description Technical Details

Size: 14C X 630mm²


Power Cable Core: Single Core
Type: Cu/PVC?PVC
Size:4C X 500mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size:4C X 95mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size:4C X 50mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size:4C X 95mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size: 4C X 95mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Szie:4C X 10mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size:4C X 95mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size:4C X 95mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size:4C X 95mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size:4C X 400mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size: 4C x 120mm²
Power Cable
Type: CU/PVC/PVC

Size:3C x 10mm ²
Power Cable Type: CU/PVC/PVC
Colour: Red, Yellow,Blue

Size:3C x 1.5mm ²
Control Cable Type: CU/PVC/PVC
Colour: Red, Yellow,Blue
Size:1C X 16mm²
Earth Cable Type: CU/PVC

Size:1C X 70mm²
Earth Cable Type: Rope
Units Quantity Remarks

For Main Power Supply


Mtr 3374
One core required 241Meter

For Air Compressor


Mtr 80
500mm2 cable take load of

Mtr 52 For RO Plant room

Mtr 37 For New Compressor Room

Mtr 230 For HDI Section input supply

Mtr 260 For HDT Section input supply

Mtr 182 For H2 Plant input supply

Mtr 201 For ISS Section input supply


Mtr 150 For PSA Section input supply

Mtr 226 For Make-up Section input supply

Mtr 176 For ARU Section input supply

Mtr 100 For OSBLSection input supply

For motor Input from New Control room


Mtr 60 OSBL
Tab-4 details attached

For motor Input from New Control room


Mtr 60
OSBL

For motor Input from New Control room


Mtr 60
OSBL

For motor Input from New Control room


Mtr 60
OSBL

For motor Input from New Control room


Mtr 60
OSBL
For motor Input from New Control room
Mtr 60
OSBL

For motor Input from New Control room


Mtr 70
OSBL

For motor Input from New Control room


Mtr 70
OSBL

For motor Input from New Control room


Mtr 70
OSBL

For motor Input from New Control room


Mtr 70
OSBL

For motor Input from New Control room


Mtr 70
OSBL

For motor Input from New Control room


Mtr 70
OSBL

For motor Input from New Control room


Mtr 85
OSBL

For motor Input from New Control room


Mtr 85
OSBL
For motor Input from New Control room
Mtr 85
OSBL

For motor Input from New Control room


Mtr 85
OSBL

For motor Input from New Control room


Mtr 85
OSBL

For motor Input from New Control room


Mtr 85
OSBL

For motor Input from New Control room


Mtr 35
OSBL

For motor Input from New Control room


Mtr 35
OSBL

For motor Input from New Control room


Mtr 35
OSBL

For motor Input from New Control room


Mtr 35
OSBL

For motor Input from New Control room


Mtr 35
OSBL
For motor Input from New Control room
Mtr 35
OSBL

For motor Input from New Control room


Mtr 50
OSBL

For motor Input from New Control room


Mtr 50
OSBL

For motor Input from New Control room


Mtr 50
OSBL

For motor Input from New Control room


Mtr 50
OSBL

For motor Input from New Control room


Mtr 50
OSBL

For motor Input from New Control room


Mtr 50
OSBL

For motor Input from New Control room


Mtr 80
OSBL

For motor Input from New Control room


Mtr 80
OSBL
For motor Input from New Control room
Mtr 80
OSBL

For motor Input from New Control room


Mtr 80
OSBL

Mtr 900 From New Control Room OSBL SAF

Mtr 550 From New Boiler room ISBL Saf

New Lights activation from main cable


Mtr 1600
Estimated for each light is 5meter

Mtr 300 For Motor Earthing

For motor connection with Rope 10 meter


Mtr 340
required for each

for rom led Lights, fans,


Coil 19
and UPS connections

for rom led Lights, fans,


Coil 10
and UPS connections
al Details Unit Qty

Mtr 3374
Mtr 80

Mtr 52

Mtr 37

Mtr 230

Mtr 260

Mtr 182

Mtr 201

Mtr 150

Mtr 226

Mtr 176

Mtr 100

Mtr 2120

Mtr 2120
Mtr 340

Mtr 300
Description

Main Cable from T/F room and Hfo to


New Boiler Control Room

New Boiler

RO Plant

New Compressor Room

HDI Section

HDT Section

H² Section

ISS Section
PSA Section

Make Up Section

ARU Section

OSBL Saf

Raw Material Tank Load Pump A

Raw Material Tank Load Pump B

Raw Material Tank UnLoad Pump C

Raw Material Tank Unload Pump D

Raw Material Tanks transfer pump E


Raw Material Tanks transfer pump F

Bio Napht Tank Load Pump A

Bio Napht Tank Load Pump B

Bio Napht Tank Unload Pump C

Bio Napht Tank Unload Pump D

Bio Napht Tank Transfer Pump E

Bio Napht Tank Transfer Pump F

SAF Storage Tank Load Pump A

SAF Storage Tank Load Pump B


SAF Storage Tank Unload Pump C

SAF Storage Tank Unload Pump D

SAF Storage Tank Transfer Pump A

SAF Storage Tank Transfer Pump A

SAF Product Tank Load Pump A

SAF Product Tank Load Pump B

SAF Product Tank Unload Pump C

SAF Product Tank Unload Pump D

SAF Product Tank Transfer Pump E


SAF Product Tank Transfer Pump F

UG Methanol Tank Load Pump A

UG Methanol Tank Load Pump B

UG Methanol Tank Unload Pump C

UG Methanol Tank Unload Pump D

UG Methanol Tank Transfer Pump E

UG Methanol Tank Transfer Pump F

Fire Water ponds A

Fire Water ponds B


Fire Water Tank A

Fire Water Tank B

Lighting Cables

Lighting Cables

Lighting Cables

Earthing cable

Earthing cable

Building Rooms Cables

Building Rooms Cables


BOQ-Ex
Category
Title
Sr No.

2
3

10

11

12

13

14

15
16
Option_2 Transformer to New Boiler Room
Summary of Cables

Cable Size Route

14C X 630mm² Via OSBL saf Plant Boundary


Core: Single Core
Type: Cu/PVC?PVC to HFO New Lt room

4C X 500mm²
Core: Four Core New LT room to Boiler Control room
Type: Cu/PVC/PVC

4C X 16mm²
Core: Four Core New LT room to RO room
Type: Cu/PVC/PVC

4C X 50mm²
Core: Four Core New LT room to New Compressor
Type: Cu/PVC/PVC

4C X 95mm²
Core: Four Core New Lt room to HDI
Type: Cu/PVC/PVC

4C X 95mm²
Core: Four Core New LT room to HDT
Type: Cu/PVC/PVC

4C X 10mm²
Core: Four Core New LT room to H²
Type: Cu/PVC/PVC

4C X 95mm²
Core: Four Core New Lt room to ISS
Type: Cu/PVC/PVC
4C X 95mm²
Core: Four Core New Lt room to PSA
Type: Cu/PVC/PVC

4C X 95mm²
Core: Four Core New Lt room to Make Up
Type: Cu/PVC/PVC

4C X 400mm²
Core: Four Core New Lt room to ARU
Type: Cu/PVC/PVC

4C X 120mm²
Core: Four Core Old Lt room to OSBL
Type: Cu/PVC/PVC

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF
3C X 10mm² Via trench from new control room OSBL
Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF
3C X 10mm² Via trench from new control room OSBL
Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF
3C X 10mm² Via trench from new control room OSBL
Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF
3C X 10mm² Via trench from new control room OSBL
Core: Three Core
Type: Cu/PVC/PVC SAF

3C X 10mm² Via trench from new control room OSBL


Core: Three Core
Type: Cu/PVC/PVC SAF

4C X 6mm²
Core: Four Core Via trench and cable tray if require at OSBL Saf
Type: Cu/PVC/PVC

4C X 6mm²
Core: Four Core VIA Trench and GI pipe at ISBL SAF
Type: Cu/PVC/PVC

3C X 1.5mm²
Core: 3 Main cable to each 320 lights
Type: Cu/PVC/PVC

1C X 70mm²
Core: 1 VIA trench to Earthing Pits
Type: Rope

1C X 16mm²
Core 1 VIA Cable Trench In interconnection with Rope
Type: CU/PVC/PVC

For new LT HFo room


7/29
New OSBl room
Core: 1
new SCADA room
Type: Cu/PVC
For new Boiler control and office
red: 6, Black:6 Green: 4 Blue: 3
For new LT HFo room
7/36
New OSBl room
Core: 1
new SCADA room
Type: Cu/PVC
For new Boiler control and office
red: 4, Black:4 Green: 1
Power and Control Cables for OSBL SAF Palnt
Project
OSBL SAF
Description Technical Details
Size: 14C X 630mm²
Power Cable Core: Single Core
Type: Cu/PVC?PVC

Size:4C X 500mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC
Size:4C X 95mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size:4C X 50mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size:4C X 95mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size: 4C X 95mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Szie:4C X 10mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size:4C X 95mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size:4C X 95mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size:4C X 95mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size:4C X 400mm²
Power Cable Core: Four Core
Type: Cu/PVC/PVC

Size: 4C x 120mm²
Power Cable
Type: CU/PVC/PVC

Size: 3C x 10mm²
Power Cable
Type: CU/PVC/PVC

Size:3C x 1.5mm ²
Control Cable Type: CU/PVC/PVC
Colour: Red, Yellow,Blue

Size:1C X 70mm²
Earth Cable Type: Rope
Size:1C X 16mm²
Earth Cable Type: CU/PVC
Room

Unit Quantity Remarks

For Main Power Supply


Mtr 3248
One core required 232Meter

For Air Compressor


Mtr 20
500mm2 cable take load of

Mtr 60 For RO Plant room

Mtr 70 For New Compressor Room

Mtr 130 For HDI Section input supply

Mtr 160 For HDT Section input supply

Mtr 90 For H2 Plant input supply

Mtr 110 For ISS Section input supply


Mtr 50 For PSA Section input supply

Mtr 135 For Make-up Section input supply

Mtr 80 For ARU Section input supply

Mtr 100 For OSBLSection input supply

For motor Input from New Control room


Mtr 60
OSBL

For motor Input from New Control room


Mtr 60
OSBL

For motor Input from New Control room


Mtr 60
OSBL

For motor Input from New Control room


Mtr 60
OSBL

For motor Input from New Control room


Mtr 60
OSBL
For motor Input from New Control room
Mtr 60
OSBL

For motor Input from New Control room


Mtr 70
OSBL

For motor Input from New Control room


Mtr 70
OSBL

For motor Input from New Control room


Mtr 70
OSBL

For motor Input from New Control room


Mtr 70
OSBL

For motor Input from New Control room


Mtr 70
OSBL

For motor Input from New Control room


Mtr 70
OSBL

For motor Input from New Control room


Mtr 85
OSBL

For motor Input from New Control room


Mtr 85
OSBL
For motor Input from New Control room
Mtr 85
OSBL

For motor Input from New Control room


Mtr 85
OSBL

For motor Input from New Control room


Mtr 85
OSBL

For motor Input from New Control room


Mtr 85
OSBL

For motor Input from New Control room


Mtr 35
OSBL

For motor Input from New Control room


Mtr 35
OSBL

For motor Input from New Control room


Mtr 35
OSBL

For motor Input from New Control room


Mtr 35
OSBL

For motor Input from New Control room


Mtr 35
OSBL
For motor Input from New Control room
Mtr 35
OSBL

For motor Input from New Control room


Mtr 50
OSBL

For motor Input from New Control room


Mtr 50
OSBL

For motor Input from New Control room


Mtr 50
OSBL

For motor Input from New Control room


Mtr 50
OSBL

For motor Input from New Control room


Mtr 50
OSBL

For motor Input from New Control room


Mtr 50
OSBL

For motor Input from New Control room


Mtr 80
OSBL

For motor Input from New Control room


Mtr 80
OSBL
For motor Input from New Control room
Mtr 80
OSBL

For motor Input from New Control room


Mtr 80
OSBL

Mtr 900 From New Control Room OSBL SAF

Mtr 550 From New Boiler room ISBL Saf

New Lights activation from main cable


Mtr 1600
Estimated for each light is 5meter

Mtr 300 For Motor Earthing

For motor connection with Rope 10 meter


Mtr 340
required for each

for rom led Lights, fans, earh


Coil 19
and UPS connections

Coil 10 for Room Power Plugs and Air Conditioners


nical Details Unit Qty

Mtr 232

Mtr 20
Mtr 60

Mtr 70

Mtr 130

Mtr 160

Mtr 90

Mtr 110

Mtr 50

Mtr 135

Mtr 80

Mtr 100

Mtr 2120

Mtr 2120

Mtr 300
Mtr 340
Lights Summary
Sr No. Discription Tech. Detail Total lights Watts
200Watts
Flood Lights
1 IP:67 100 20000
OSBL SAF

Street Light/ 120Watts


2 Boundary Wall Lights OSBL IP:67 116 13920
Saf
LED lights Pump
3 12 Watts 50 288
OSBL SAF
120Watts
Flood Lights
4 IP:67 30 3600
SAF Plant Side OSBL

Street Light/ 120Watts


5 Boundary Wall Lights SAF IP:67 60 7200
ISBL
LED Lights for Workshops
6 12 Watts 120 1440
New Control And offices

Total Watts 46448


Air Conditioners Summary
Sr No. Discription Tech.Detail KW
For new Pump Size: 1.5 Tons
1 Room OSBL BTU: 18000 1.8
SCADA/Power Watts: 1.8 KW

Size: 1.5 Tons


For New LT room
2 BTU: 18000 1.8
HFO
Watts: 1.8 KW

Size: 1.5 Tons


New Boiler
3 BTU: 18000 1.8
Room
Watts: 1.8 KW

Size: 1.5 Tons


Boiler office
4 BTU: 18000 1.8
Room
Watts: 1.8 KW
Total Load of Air Conditioners 2.4
QTY

1
Sr No Discription
1 Motors
2 Lights OSBL
3 Lights SAF
Total
Quantity KWs for Each
34 15
216 0.12
110 0.12
Total
Total KWS
510
25.92
13.2
549.12