ﺘﺭﺸﻴﺩ ﺍﻟﻁﺎﻗﺔ ﻓﻰ ﻋﻤﻠﻴﺎﺕ ﺘﻜﻴﻴﻑ ﺍﻟﻬﻭﺍﺀ
ﺘﺘﻁﻠﺏ ﺃﺴﺱ ﺍﻟﺘﺼﻤﻴﻡ ﻭﻤﻭﺍﺼﻔﺎﺕ ﺒﻨﻭﺩ ﺍﻷﻋﻤﺎل ﻭﺃﺼﻭل ﺍﻟﺼﻨﺎﻋﺔ ﺍﻻﻟﺘﺯﺍﻡ ﺒﺎﺴﺘﺨﺩﺍﻡ ﺍﻟﺤﺩ ﺍﻷﺩﻨـﻰ ﻤـﻥ
ﺍﻟﻁﺎﻗﺔ ﻟﺘﺸﻐﻴل ﻨﻅﻡ ﺘﻜﻴﻴﻑ ﺍﻟﻬﻭﺍﺀ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻭﺘﻜﻭﻥ ﺃﺴﺱ ﺍﻟﻤﻔﺎﻀﻠﺔ ﺒﻴﻥ ﺍﻟﻨﻅﻡ ﺍﻟﻤﺨﺘﻠﻔﺔ ﺒﺈﻋﺘﺒﺎﺭ ﺍﺴﺘﻬﻼﻙ ﺍﻟﻁﺎﻗـﺔ
ﺍﻟﻨﻭﻋﻰ ﻭﺘﺤﺩﺩ ﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻌﺎﻟﻤﻴﺔ ﻜﻔﺎﺀﺓ ﺍﻟﺘﺸﻐﻴل ﺍﻷﺩﻨﻰ ﺍﻟﻤﺴﻤﻭﺡ ﺒﻬﺎ ﻭﻤﻌـﺎﻤﻼﺕ ﺍﻷﺩﺍﺀ ﺒﺎﻟﻨـﺴﺒﺔ ﻟﻭﺤـﺩﺍﺕ
ﺘﻜﻴﻴﻑ ﺍﻟﻬﻭﺍﺀ ﺍﻟﻘﺎﺌﻤﺔ ﺒﺫﺍﺘﻬﺎ ﻭﻭﺤﺩﺍﺕ ﺍﻟﺘﺒﺭﻴﺩ ﺍﻟﺘﺒﺨﻴﺭﻯ ﻭﺨﻼﻓﺔ ﻭﺍﻟﺠﺩﺍﻭل ﺃﺭﻗﺎﻡ ) ( 1-6ﺍﻟﻰ ) ( 8-6ﺘﻭﻀﺢ ﺍﻟﻘﻴﻡ
ﺍﻟﻤﻭﺼﻰ ﺒﻬﺎ ﻋﻨﺩ ﺍﺴﺘﺨﺩﺍﻡ ﺃﻱ ﻤﻥ ﺍﻟﻨﻅﻡ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻭﻓﻘﹰﺎ ﻟﻠﻜﻭﺩ ﺍل ﻋﺭﺒﻰ ﻭﺘﻌﻠﻴﻤﺎﺕ ﺠﻤﻌﻴﺔ ﺍﻟﺘﺒﺭﻴﺩ ﺍﻟﻌﺎﻟﻤﻴﺔ.
2
ﺠﺩﻭل ) ( 1-6
ﻭﺤﺩﺍﺕ ﺘﻜﻴﻴﻑ ﺍﻟﻬﻭﺍﺀ ﻭﻭﺤﺩﺍﺕ ﺍﻟﺘﻜﺜﻴﻑ ﺍﻟﺘﻰ ﺘﻌﻤل ﺒﺎﻟﻜﻬﺭﺒﺎﺀ
ﺍﻟﺤﺩ ﺍﻷﺩﻨﻰ ﻟﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﻜﻔﺎﺀﺓ
3
ﺠﺩﻭل ) ( 2-6
ﺍﻟﻤﻀﺨﺎﺕ ﺍﻟﺤﺭﺍﺭﻴﺔ ﺍﻟﺘﻰ ﺘﻌﻤل ﺒﺎﻟﻜﻬﺭﺒﺎﺀ
ﺍﻟﺤﺩ ﺍﻷﺩﻨﻰ ﻟﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﻜﻔﺎﺀﺓ
ﺍﻻﺨﺘﺒﺎﺭ ﺃﺩﻨﻰ ﻜﻔﺎﺀﺓ ﺍﻟﺘﺼﻨﻴﻑ ﺍﻟﺴﻌﻪ ﻨﻭﻉ ﺍﻟﻤﻌﺩﺓ
2.93 SCOP ﻨﻅﺎﻡ ﻤﻨﻔﺼل > 19ﻜﻴﻠﻭﻭﺍﺕ
)(1
2.84 SCOP ﻭﺤﺩﺓ ﻤﺠﻤﻌﺔ ﻤﻔﺭﺩﺓ
ARI 210/240
2.96 COP ﻨﻅﺎﻡ ﻤﻨﻔﺼل < 19ﻜﻴﻠﻭﻭﺍﺕ
3.05 IPLV ﻭﻭﺤﺩﺓ ﻤﺠﻤﻌﺔ ﻤﻔﺭﺩﺓ > 40ﻜﻴﻠﻭﻭﺍﺕ
ﺍﻟﻤﺒﺭﺩﺓ ﺒﺎﻟﻬﻭﺍﺀ )ﺤﺎﻟﻪ ﺍﻟﺘﺒﺭﻴﺩ(
2.72 COP ﻨﻅﺎﻡ ﻤﻨﻔﺼل < 40ﻜﻴﻠﻭﻭﺍﺕ
2.78 IPLV ﻭﻭﺤﺩﺓ ﻤﺠﻤﻌﺔ ﻤﻔﺭﺩﺓ > 70ﻜﻴﻠﻭﻭﺍﺕ
ARI 340/360
2.64 COP ﻨﻅﺎﻡ ﻤﻨﻔﺼل
< 70ﻜﻴﻠﻭﻭﺍﺕ
2.70 IPLV ﻭﻭﺤﺩﺓ ﻤﺠﻤﻌﺔ ﻤﻔﺭﺩﺓ
3.52 COP 29.4ﺱ Oﺍﻟﻤﻴﺎﻩ ﺍﻟﺩﺍﺨﻠﺔ
> 19ﻜﻴﻠﻭﻭﺍﺕ
3.81 COP 23.9ﺱ Oﺍﻟﻤﻴﺎﻩ ﺍﻟﺩﺍﺨﻠﺔ
ARI 320 ﺍﻟﻤﺼﺩﺭ ﺍﻟﻤﻴﺎﻩ )ﺤﺎﻟﺔ ﺍﻟﺘﺒﺭﻴﺩ(
3.52 COP 29.4ﺱ Oﺍﻟﻤﻴﺎﻩ ﺍﻟﺩﺍﺨﻠﺔ < 19ﻜﻴﻠﻭﻭﺍﺕ
3.81 COP 23.9ﺱ Oﺍﻟﻤﻴﺎﻩ ﺍﻟﺩﺍﺨﻠﺔ > 40ﻜﻴﻠﻭﻭﺍﺕ
3.96 COP 21.1ﺱ Oﺍﻟﻤﻴﺎﻩ ﺍﻟﺩﺍﺨﻠﺔ
ARI 325 > 40ﻜﻴﻠﻭﻭﺍﺕ ﺍﻟﻤﺼﺩﺭ ﺍﻟﻤﻴﺎﻩ ﺍﻟﺠﻭﻓﻴﺔ )ﺤﺎﻟﺔ ﺍﻟﺘﺒﺭﻴﺩ(
4.40 COP 10ﺱ Oﺍﻟﻤﻴﺎﻩ ﺍﻟﺩﺍﺨﻠﺔ
3.63 COP 25ﺱ Oﺍﻟﺒﺭﺍﻴﻥ ﺍﻟﺩﺍﺨل
ARI 330 > 40ﻜﻴﻠﻭﻭﺍﺕ ﺍﻟﻤﺼﺩﺭ ﺍﻷﺭﻀﻰ )ﺤﺎﻟﺔ ﺍﻟﺘﺒﺭﻴﺩ(
3.75 COP 21.1ﺱ Oﺍﻟﺒﺭﺍﻴﻥ ﺍﻟﺩﺍﺨل
1.99 COP ﻨﻅﺎﻡ ﻤﻨﻔﺼل > 19ﻜﻴﻠﻭﻭﺍﺕ
1.93 COP ﻭﺤﺩﺓ ﻤﺠﻤﻌﺔ ﻤﻔﺭﺩﺓ )ﺴﻌﺔ ﺍﻟﺘﺒﺭﻴﺩ(
)(2
ARI 210/240 3.2 COP 8.3ﺱ Oﺩ.ﺝ6.1/ﺱ Oﺩ.ﻁ ﺍﻟﻬﻭﺍﺀ ﺍﻟﺨﺎﺭﺠﻰ < 19ﻜﻴﻠﻭﻭﺍﺕ
8.3-ﺱ ﺩ.ﺝ9.4-/ﺱ ﺩ.ﻁ ﺍﻟﻬــــــﻭﺍﺀ > 40ﻜﻴﻠﻭﻭﺍﺕ
ﺍﻟﻤﺒﺭﺩﺓ ﺒﺎﻟﻬﻭﺍﺀ )ﺤﺎﻟﺔ ﺍﻟﺘﺴﺨﻴﻥ(
O O
2.2 COP
)(2
ﺍﻟﺨﺎﺭﺠﻰ )ﺴﻌﺔ ﺍﻟﺘﺒﺭﻴﺩ(
)(2
3.1 COP 8.3ﺱ Oﺩ.ﺝ6.1/ﺱ Oﺩ.ﻁ ﺍﻟﻬﻭﺍﺀ ﺍﻟﺨﺎﺭﺠﻰ < 40ﻜﻴﻠﻭﻭﺍﺕ
ARI 340/360 2.0 COP 8.3-ﺱ ﺩ.ﺝ9.4-/ﺱ ﺩ.ﻁ ﺍﻟﻬــــــﻭﺍﺀ
O O
)ﺴﻌﺔ ﺍﻟﺘﺒﺭﻴﺩ(
)(2
ﺍﻟﺨﺎﺭﺠﻰ
4.1 COP 21.1ﺱ ﺍﻟﻤﻴﺎﺓ ﺍﻟﺩﺍﺨﻠﺔ
O
> 40ﻜﻴﻠﻭﻭﺍﺕ
ARI 320 ﺍﻟﻤﺼﺩﺭ ﺍﻟﻤﻴﺎﻩ )ﺤﺎﻟﺔ ﺍﻟﺘﺴﺨﻴﻥ(
4.2 COP 23.9ﺱ ﺍﻟﻤﻴﺎﺓ ﺍﻟﺩﺍﺨﻠﺔ
O
)ﺴﻌﺔ ﺍﻟﺘﺒﺭﻴﺩ(
3.9 COP 21.1ﺱ Oﺍﻟﻤﻴﺎﺓ ﺍﻟﺩﺍﺨﻠﺔ > 40ﻜﻴﻠﻭﻭﺍﺕ ﺍﻟﻤــﺼﺩﺭ ﺍﻟﻤﻴــﺎﻩ ﺍﻟﺠﻭﻓﻴــﺔ )ﺤﺎﻟــﺔ
ARI 325
10ﺱ ﺍﻟﻤﻴﺎﺓ ﺍﻟﺩﺍﺨﻠﺔ )ﺴﻌﺔ ﺍﻟﺘﺒﺭﻴﺩ(
ﺍﻟﺘﺴﺨﻴﻥ(
O
3.4 COP
4
ﺠﺩﻭل ) ( 3-6
ﻭﺤﺩﺍﺕ ﺇﻨﺘﺎﺝ ﺍﻟﻤﻴﺎﻩ ﺍﻟﻤﺜﻠﺠﺔ ﺍﻟﻤﺠﻤﻌﺔ
ﺍﻟﺤﺩ ﺍﻷﺩﻨﻰ ﻟﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﻜﻔﺎﺀﺓ
5
ﺠﺩﻭل ) ( 4-6
ﻭﺤﺩﺍﺕ ﺘﻜﻴﻴﻑ ﺍﻟﻬﻭﺍﺀ ﺍﻟﻁﺭﻓﻴﺔ ﻭﺍﻟﻤﻀﺨﺎﺕ ﺍﻟﺤﺭﺍﺭﻴﺔ ﻭﺍﻟﺘﻰ ﺘﻌﻤل ﺒﺎﻟﻜﻬﺭﺒﺎﺀ
ﻭﺤﺩﺍﺕ ﺘﻜﻴﻴﻑ ﻫﻭﺍﺀ ﺍﻟﻐﺭﻑ ﻭﺍﻟﻤﻀﺨﺎﺕ ﺍﻟﺤﺭﺍﺭﻴﺔ ﻭﺍﻟﺘﻰ ﺘﻌﻤل ﺒﺎﻟﻜﻬﺭﺒﺎﺀ
ﺍﻟﺤﺩ ﺍﻷﺩﻨﻰ ﻟﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﻜﻔﺎﺀﺓ
6
ﺠﺩﻭل ) ( 5-6
ﺃﻓﺭﺍﻥ ﺘﺴﺨﻴﻥ ﺍﻟﻬﻭﺍﺀ ﻭﺍﻟﻭﺤﺩﺍﺕ ﺍﻟﻤﺠﻤﻌﺔ ﻟﺘﻜﻴﻴﻑ ﺍﻟﻬﻭﺍﺀ ﻭﺃﻓﺭﺍﻥ ﺘﺴﺨﻴﻥ ﺍﻟﻬﻭﺍﺀ
ﺃﻓﺭﺍﻥ ﺘﺴﺨﻴﻥ ﻤﺠﺎﺭﻯ ﺍﻟﻬﻭﺍﺀ ﻭﻭﺤﺩﺍﺕ ﺘﺴﺨﻴﻥ ﺍﻟﻬﻭﺍﺀ
ﺍﻟﺤﺩ ﺍﻷﺩﻨﻰ ﻟﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﻜﻔﺎﺀﺓ
7
ﺠﺩﻭل ) ( 6-6
ﺍﻟﻤﺭﺍﺠل ﺍﻟﻐﺎﺯﻴﺔ ﻭﺫﺍﺕ ﺍﻟﻭﻗﻭﺩ ﺍﻟﺴﺎﺌل
ﺍﻟﺤﺩ ﺍﻷﺩﻨﻰ ﻟﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﻜﻔﺎﺀﺓ
ﺍﻻﺨﺘﺒﺎﺭ ﺃﺩﻨﻰ ﻜﻑﺀﺓ ﺍﻟﺘﺼﻨﻴﻑ ﺍﻟﺴﻌﺔ ﻨﻭﻉ ﺍﻟﻤﻌﺩﺓ
DOE 10 CFR
80% AFUE ﻤﺎﺀ ﺴﺎﺨﻥ > 88ﻜﻴﻠﻭﻭﺍﺕ
Part 430 75% AFUE ﺒﺨﺎﺭ
75% Et )(a
ﺃﻗﺼﻰ ﻜﻔﺎﺀﺓ < 88ﻜﻴﻠﻭﻭﺍﺕ
)(a
ﺃﺩﻨﻰ ﻜﻔﺎﺀﺓ > 733ﻜﻴﻠﻭﻭﺍﺕ ﺍﻟﻤﺭﺍﺠل ﻭﻗﻭﺩ ﻏﺎﺯﻯ
d
H.I.Htg Boiler Std 86
78% Et ﻤﺎﺀ ﺴﺎﺨﻥ < 733ﻜﻴﻠﻭﻭﺍﺕ
78% Et ﺒﺨﺎﺭ < 733ﻜﻴﻠﻭﻭﺍﺕ
DOE 10 CFR 80% AFUE > 88ﻜﻴﻠﻭﻭﺍﺕ
Part 430
78% Et )(a
ﺃﻗﺼﻰ ﻜﻔﺎﺀﺓ < 88ﻜﻴﻠﻭﻭﺍﺕ
)(a
ﺃﺩﻨﻰ ﻜﻔﺎﺀﺓ > 733ﻜﻴﻠﻭﻭﺍﺕ ﺍﻟﻤﺭﺍﺠل ﻭﻗﻭﺩ ﺯﻴﺕ
d
H.I.Htg Boiler Std 86
81 % Et ﻤﺎﺀ ﺴﺎﺨﻥ < 733ﻜﻴﻠﻭﻭﺍﺕ
81 % Et ﺒﺨﺎﺭ < 733ﻜﻴﻠﻭﻭﺍﺕ
78 % Et )(a
ﺃﻗﺼﻰ ﻜﻔﺎﺀﺓ < 88ﻜﻴﻠﻭﻭﺍﺕ
)(a
ﺃﺩﻨﻰ ﻜﻔﺎﺀﺓ > 733ﻜﻴﻠﻭﻭﺍﺕ
H.I.Htg Boiler Std 86 d
ﻭﻗﻭﺩ ﺯﻴﺕ )ﻤﺨﻠﻔﺎﺕ(
81 % Et ﻤﺎﺀ ﺴﺎﺨﻥ < 733ﻜﻴﻠﻭﻭﺍﺕ
81 % Et ﺒﺨﺎﺭ < 733ﻜﻴﻠﻭﻭﺍﺕ
)(a
ﺍﻟﻤﻌﺩﻻﺕ ﺍﻟﻘﺼﻭﻯ ﻭﺍﻟﺩﻨﻴﺎ ﻫﻰ ﺍﻟﻤﺴﻤﻭﺡ ﺒﻬﺎ ﺒﻭﺍﺴﻁﺔ ﻭﺍﻟﻤﺘﻌﻠﻘﺔ ﺒﺄﺠﻬﺯﺓ ﺘﺤﻜﻡ ﺍﻟﻭﺤﺩﺓ
) (b
Ecﻜﻔﺎﺀﺓ ﺍﻻﺤﺘﺭﺍﻕ ) %100ﺃﻗل ﻤﻔﺎﻗﻴﺩ ﻋﺎﺩﻡ( .ﺃﻨﻅﺭ ﺨﻁﻭﺍﺕ ﺍﻻﺨﺘﺒﺎﺭ ﻟﻠﻤﻨﺎﻗﺸﺔ ﺍﻟﻤﻁﻭﻟﺔ
)(C
Etﺍﻟﻜﻔﺎﺀﺓ ﺍﻟﺤﺭﺍﺭﻴﺔ .ﺃﻨﻅﺭ ﺨﻁﻭﺍﺕ ﺍﻻﺨﺘﺒﺎﺭ ﻟﻠﻤﻨﺎﻗﺸﺔ ﺍﻟﻤﻁﻭﻟﺔ
)(d
ﺨﻁﻭﺍﺕ ﺍﻻﺨﺘﺒﺎﺭ ﺍﻟﺒﺩﻴل ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻜﻌﺭﺽ ﺍﺨﺘﻴﺎﺭﻯ ﻟﻠﻤﺼﻨﻊ ﻫﻰ ANSI Z21.31ﻭﻜﺫﻟﻙ ASME PTC-4.1ﻟﻠﻭﺤﺩﺍﺕ ﺫﺍﺕ ﻗﺩﺭﺍﺕ ﺍﻟﺩﺨﻭل ﺃﻜﺒﺭ
ﻤﻥ 1465ﻜﻴﻠﻭﻭﺍﺕ
8
ﺠﺩﻭل ) ( 7-6
ﻤﺘﻁﻠﺒﺎﺕ ﺍﻷﺩﺍﺀ ﻟﻤﻌﺩﺍﺕ ﻁﺭﺩ ﺍﻟﺤﺭﺍﺭﺓ )ﺃﺒﺭﺍﺝ ﺍﻟﺘﺒﺭﻴﺩ(
ﺍﻻﺨﺘﺒﺎﺭ a,b
ﺃﺩﻨﻰ ﻜﻔﺎﺀﺓ ﺍﻟﺘﺼﻨﻴﻑ ﺍﻟﺴﻌﺔ ﻨﻭﻉ ﺍﻟﻤﻌﺩﺓ
35ﺱ ﺍﻟﻤﻴﺎﻩ ﺍﻟﺩﺍﺨﻠﻪ
o
ﺍﺒﺭﺍﺝ ﺍﻟﺘﺒﺭﻴﺩ ﺫﺍﺕ ﺍﻟﺭﻓﺎﺹ ﺃﻭ ﺍﻟﻤـﺭﺍﻭﺡ
CTI ATC-105 3.23 L / s.kW ﺍﻟﻜل 29ﺱ oﺍﻟﻤﻴﺎﻩ ﺍﻟﺨﺎﺭﺠﺔ ﺍﻟﻤﺤﻭﺭﻴﺔ
24ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺭﻁﺒﺔ ﻫﻭﺍﺀ ﺨﺎﺭﺠﻰ
35ﺱ oﺍﻟﻤﻴﺎﻩ ﺍﻟﺩﺍﺨﻠﻪ ﺃﺒﺭﺍﺝ ﺍﻟﺘﺒﺭﻴـﺩ ﺫﺍﺕ ﺍﻟﻤـﺭﺍﻭﺡ ﺍﻟﻁـﺎﺭﺩﺓ
CTI ATC-105 1.7 L / s.kW ﺍﻟﻜل 29ﺱ ﺍﻟﻤﻴﺎﻩ ﺍﻟﺨﺎﺭﺠﺔ
o
ﺍﻟﻤﺭﻜﺯﻴﺔ
24ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺭﻁﺒﺔ ﻫﻭﺍﺀ ﺨﺎﺭﺠﻰ
52ﺱ oﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﺘﻜﺜﻴﻑ – ﻤﺎﺌﻊ ﺍﻻﺨﺘﺒﺎﺭ ﺍﻟﻤﻜﺜﻔﺎﺕ ﺍﻟﻤﺒﺭﺩﺓ ﺒﺎﻟﻬﻭﺍﺀ
R22
ARI 460 69 COP ﺍﻟﻜل 88ﺱ oﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﻐﺎﺯ ﺍﻟﺩﺍﺨل
8ﺱ oﺘﺒﺭﻴﺩ ﺯﺍﺌﺩ
35ﺱ oﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﺠﺎﻓﺔ ﺍﻟﺩﺍﺨﻠﻪ
ﻷﻏﺭﺍﺽ ﺍﺴﺘﺨﺩﺍﻡ ﻫﺫﺍ ﺍﻟﺠﺩﻭل ،ﻴﻌﺭﻑ ﺃﺩﺍﺀ ﺒﺭﺝ ﺍﻟﺘﺒﺭﻴﺩ ﺒﺄﻗﺼﻰ ﻤﻌﺩل ﺘﺼﺭﻴﻑ ﻟﻠﺒﺭﺝ ﻤﻘﺴﻭﻤﹰﺎ ﻋﻠﻰ ﻗﺩﺭﺓ ﺍﻟﺘﺸﻐﻴل ﻟﻤﻭﺘﻭﺭ ﺍﻟﻤﺭﻭﺤـﺔ ﺍﻟﻤﺩﻭﻨـﺔ )(a
ﻋﻠﻴﻪ.
ﻷﻏﺭﺍﺽ ﺍﺴﺘﺨﺩﺍﻡ ﻫﺫﺍ ﺍﻟﺠﺩﻭل ،ﻴﻌﺭﻑ ﺃﺩﺍﺀ ﺍﻟﻤﻜﺜﻑ ﺍﻟﻤﺒﺭﺩ ﺒﺎﻟﻬﻭﺍﺀ ﺒﺄﻨﻪ ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻤﻁﺭﻭﺩﺓ ﻤﻥ ﻤﺎﺌﻊ ﺍﻟﺘﺒﺭﻴﺩ ﻤﻘﺴﻭﻤﺔ ﻋﻠﻰ ﻗﺩﺭﺓ ﺍﻟﺘﺸﻐﻴل ﻟﻤﻭﺘﻭﺭ )(b
9
ﺠﺩﻭل ) ( 8-6
ﻤﺘﻁﻠﺒﺎﺕ ﺍﻷﺩﺍﺀ ﻟﻤﻌﺩﺍﺕ ﺘﺴﺨﻴﻥ ﺍﻟﻤﻴﺎﻩ
ﺍﻻﺨﺘﺒﺎﺭ ﺃﺩﻨﻰ ﻜﻔﺎﺀﺓ ﺍﻟﺘﺼﻨﻴﻑ ﺍﻟﺴﻌﺔ ﻨﻭﻉ ﺍﻟﻤﻌﺩﺓ
DOE 10 CFR ﻤﻘﺎﻭﻤﺔ > 12ﻜﻴﻠﻭﻭﺍﺕ
0.93-0.005V EF
Part 430
ASHRAE 118.1 5.9 + 5.3 V ﻤﻘﺎﻭﻤﺔ < 12ﻜﻴﻠﻭﻭﺍﺕ
ﺴﺨﺎﻨﺎﺕ ﺍﻟﻤﻴﺎﻩ ﺍﻟﻜﻬﺭﺒﻴﺔ
ﻤﻀﻐﻪ ﺤﺭﺍﺭﻴﺔ > 24ﺃﻤﺒﻴﺭ
DOE 10 CFR
0.93-0.005V EF > 250ﻓﻭﻟﺕ
Part 430
DOE 10 CFR < 75.7ﻟﺘﺭ > 22.98ﻜﻴﻠﻭﻭﺍﺕ
0.62-0.0072V EF
Part 430
80 % Et > 309.75ﻭﺍﺕ/ﻟﺘﺭ < 22.98ﻜﻴﻠﻭﻭﺍﺕ
)( Q / 799 + 16.6 V > 45.43ﻜﻴﻠﻭﻭﺍﺕ
ﺴﺨﺎﻨﺎﺕ ﺍﻟﻤﻴﺎﻩ ﺍﻟﺘﺨﺯﻴﻨﻴﺔ ﺍﻟﻐﺎﺯﻴﺔ
ASHRAE 118.1
80 % Et > 309.75ﻭﺍﺕ/ﻟﺘﺭ < 45.43ﻜﻴﻠﻭﻭﺍﺕ
)( Q / 799 + 16.6 V
10