A consistent design of offers from All Merlin Gerin offers are designed according to
Medium Voltage to Ultra terminal electrical, mechanical and communication
consistency rules.
The products express this consistency by their
overall design and shared ergonomics.

Electrical consistency:

Each product complies with or enhances system performance at co-


ordination level: breaking capacity, Isc, temperature rise, etc. for
more safety, continuity of supply (discrimination) or economic
optimisation (cascading).
The leading edge technologies employed in Merlin Gerin’s
Guiding System ensure high performance levels in discrimination
and cascading of protection devices, electrodynamic withstand of
switches and current distributors, heat loss of devices, distribution
blocks and enclosures.
Discrimination guarantees co-ordination between the operating
Likewise, inter-product ElectroMagnetic Compatibilty (EMC) is
characteristics of serial-connected circuit-breakers. Should a guaranteed.
fault occurs downstream, only the circuit-breaker placed
immediately upstream from the fault will trip.

Mechanical consistency:

Each product adopts dimensional standards simplifying and


optimising its use within the system.
It shares the same accessories and auxiliaries and complies with
global ergonomic choices (utilisation mode, operating mode, setting
and configuration devices, tools, etc.) making its installation and
operation within the system a simpler process.

Prefabricated and tested solutions, upstream and downstream


from the device complying with the IEC 60439-1 switchboard
standard.

Communication consistency:

Thanks to the use of standard Web technologies, you can offer Each product complies with global choices in terms of
your customers intelligent Merlin Gerin switchboards allowing communication protocols (Modbus, Ethernet, etc.) for simplified
easy access to information: follow-up of currents, voltages,
powers, consumption history, etc.
integration in the management, supervision and monitoring
systems.

Guiding Tools
for more efficient design
and implementation
of your installations.

1
0

SM6 Sepam Masterpact


Medium voltage switchboard Protection relays Protection switchgear
system from 1 to 36 kV from 100 to 6300 A

Trihal
MV/LV dry cast resin
transformer
from 160 to 5000 kVA

Evolis
MV vacuum
switchgear and
components
from 1 to 24 kV.

The Technical guide CAD software and tools

These technical guides help you comply with The CAD software and tools enhance
installation standards and rules i.e.: productivity and safety.
The electrical installation guide, the They help you create your installations
protection guide, the switchboard by simplifying product choice through
implementation guide, the technical booklets easy browsing in the Guiding System
and the co-ordination tables all form genuine offers.
reference tools for the design of high- Last but not least, they optimise
performance electrical installations. use of our products while also complying
For example, the LV protection co-ordination with standards and proper procedures.
guide - discrimination and cascading -
optimises choice of protection and
connection devices while also increasing
markedly continuity of supply in the
installations.

2
0

Compact Multi 9 Prisma Plus


Protection switchgear system Modular protection switchgear Functional system for electrical
from 100 to 630 A system up to 125 A distribution switchboards
up to 3200 A

Pragma Canalis
Enclosures for Prefabricated Busbar
distribution Trunking
switchboards from 25 to 4000 A
up to 160 A

PowerLogic
Power
management

Training

Training allows you to acquire the Merlin


Gerin expertise (installation design, work
with power on, etc.) for increased efficiency
and a guarantee of improved customer
service.
The training catalogue includes beginner’s
courses in electrical distribution, knowledge
of MV and LV switchgear, operation and
maintenance of installations, design of LV
installations to give but a few examples.

3
LF and SF circuit breakers 0

Two ranges of comprehensive and proven LF circuit breakers from 7.2 kV to 17.5 kV
three-pole circuit breaker units for indoor
installation using SF6 technology.

PE55761
Both compact and dependable, they are
ideally suited to the most demanding
applications and integrate perfectly
in the Merlin Gerin Guiding System.
Both of these circuit breaker ranges
meet IEC standard 62271-100.

SF circuit breakers from 17.5 kV to 40.5 kV


PE55762

4
General contents 0

Presentation 6

Panorama 14

LF circuit breakers 17

SF circuit breakers 29

5
Presentation LF circuit breakers 0

General

Description of the device


The LF circuit breaker comprises a basic fixed version:
PE55761

b 3 poles integrated in a “sealed pressure system” type insulating enclosure.


The sealed assembly is filled with SF6 gas at low relative pressure
(0.15 Mpa/1.5 bars) and equipped with a pressure switch
b an RI stored energy electrical operating mechanism.
This gives the device an opening and closing speed that is independent
of the operator, for both electrical and manual orders. It enables reclosing cycles
to be carried out
b a front panel housing the manual operating mechanism and status indicators
b upstream and downstream terminals for the power circuit connection
b a terminal block for connection of external auxiliary circuits.
Each device can also be fitted with the following options:
b a supporting frame equipped with rollers and ground fixing brackets for fixed
LF1 - LF2 - LF3 circuit breakers installation
b circuit breaker locking in the open position by a keylock installed on the front plate
of the operating mechanism
b a 42-pin Harting type LV connector.
PE55763

Applications
LF circuit breakers are three-pole indoor MV circuit breakers.
They are mainly used for operation and protection of public, industrial and tertiary
distribution networks from 7.2 to 17.5 kV.
Through their anti-seismic qualification, they are particularly well suited to nuclear
or thermal power production installations and applications in heavy industries
such as the petrochemical industry.
Through their compact dimensions and harmonized range, LF circuit breakers
are positioned very favorably on the retrofit market.
With self expansion, the breaking technique used in these circuit breakers,
all current types, capacitive and inductive, can be made or broken without
generating overvoltage which could damage your installation.
The LF circuit breaker is therefore ideally suited to operating capacitor banks.

LF circuit breakers for a fixed installation

6
Presentation LF circuit breakers 0

General (cont.)

Breaking principle: self expansion


LF circuit breakers use the SF6 gas self expansion technique.
This technique is the result of many years’ experience in SF6 technology and major
research work.
It combines the effect of thermal expansion with a rotating arc to create arc blowing
and quenching conditions.
The result is reduced control energy requirements and arcing contact erosion;
this increases mechanical and electrical endurance.
The operating sequence of a self-expansion breaking chamber, whose moving part
is driven by the mechanical operating mechanism, is as follows:

b the circuit breaker is closed

DE51242

b on opening of the main contacts (a) the current


DE51243

is shunted into the breaking circuit (b)

b on separation of the arcing contacts, an electrical arc


DE51244

appears in the expansion volume (c). The arc rotates


under the effect of the magnetic field created by the coil
(d) through which flows the current to be broken:
the overpressure created by the temperature build-up
of the gas in the expansion volume (c ) causes a gaseous
flow blowing the arc inside the tubular arcing contact (e),
resulting in arc quenching when the current passes
through the zero point

b the circuit breaker is open.


DE51245

Electrical arc in a self-expansion breaking chamber


PE55764

7
Presentation SF circuit breakers 0

General

Equipment description
The SF circuit breaker comprises a basic fixed version with:
PE55765

b 3 main independent poles, that are mechanically linked and each comprising
a “sealed pressure system” type insulating enclosure. The sealed enclosure is filled
with low pressure SF6 gas.
b a stored energy operating mechanism of:
v of manual RI type (that can be electrically operated as an option) for SF1 and
SFset circuit breakers
v of electrical GMH type for SF2 circuit breakers.
v The circuit breaker’s stored energy operating mechanism gives the device a making
and breaking speed that is independent of the operator, whether the order is electrical
or manual. When equipped with an electrical operating mechanism, the circuit breaker
can be remotely controlled and it is possible to carry out reclosing cycles.
b a front panel with the manual operating mechanism and the indicators
b upstream and downstream terminals for connection of power circuits
b a terminal for connection of external auxiliary circuits.
SF1 circuit breakers with an RI type operating mechanism
Each device can be optionally equipped with:
b an electrical operating mechanism for SF1 and SFset
b a support frame fitted with rollers and floor securing brackets for a fixed installation
b locking of the circuit breaker in the open position by a keylock installed on the
PE55766

control panel
b a pressure switch for the high performance versions
b a Harting 42-pin type LV connector.
The SFset includes an independent protection chain
The SFset is provided with a fully autonomous integrated protection chain
(with a VIP type control unit) operating without an auxiliary power source.
The VIP protection unit exists in two models: VIP300P and VIP300LL.
kA
25
DE55730

20 VIP300LL

16

12,5 VIP300P - VIP300LL


SFset circuit breakers with an RI type operating mechanism
0 17,5 24 kV
Depending on the model, the unit provides protection against phase over-currents
and earthing faults.
PE55767

VIP protection units are associated with functional current sensors.


Two interchangeable sensors, CSa and CSb, are sufficient to cover all requirements
from 10 to 1250 A.
SFset is delivered equipped and cabled with its protection chain, this simplifies panel
builders’ installation work.
DE55710

SF1

Mitop

CS VIP
SF2 circuit breakers with a GMH type operating mechanism

SFset schematic diagram

Applications
SF circuit breakers are 3-pole MV circuit breakers for indoor installation. They are
mainly used for switching and protection of networks from 17.5 to 40.5 kV in primary
and secondary power distribution.
Because the SFset protection chain is autonomous in terms of power, this circuit
breaker is particularly suited to certain dispersed installations on the network.
The autocompression breaking technique used in these circuit breakers means that
making or breaking all types of compacitive or inductive currents can be achieved
without dangerous overvoltages for the switchgear connected to the network.
The SF6 circuit breaker is therefore well suited to operating capacitor banks.

8
Presentation SF circuit breakers 0

General (cont.)

Breaking technique: autocompression


SF circuit breakers use the SF6 autocompression technique.
This technique involves cooling and extinguishing the electrical arc when the current
passes through the zero point by blowing gas compressed by a piston connected to
a moving contact. The gas is guided through an insulating nozzle towards tubular
arcing contacts which are used to evacuate the gases.
This breaking technique is used for high performance (40.5 kV – 31.5 kA) in which
we have 35 years’ experience.
The operating sequence in the autocompression breaking chamber, whose mobile
part is displaced by the mechanical operating mechanism, is as follows:

b the circuit breaker is closed

DE51238

b following an opening order, the main contacts begin


DE51239

to open (a) and the current is shunted into the breaking


circuit (b)

b when the contact separate, an electrical arc forms


DE51240

which is extinguished when the current passes


through the zero point by the blowing resulting from
compression of the gas in the piston (c) which is guided
by the isolating nozzle (d)

b the circuit breaker is open


DE51241

9
Presentation LF and SF circuit breakers 0

The advantages of proven


technology

With over 35 years’ industrial experience in Safety


SF6 techniques and over 250,000 installed The breaking medium is sulfur hexafluoride (SF6) used at low pressure.
devices throughout the world, Merlin Gerin The insulating enclosure containing the circuit breaker pole(s) is equipped with
a safety membrane.
is today one of the foremost manufacturers In addition, the rated characteristics, breaking the rated current under the rated
of SF6 switchgear. voltage, are generally maintained at zero relative bars of SF6.
Merlin Gerin has developed a wide range
of high performance and reliable devices
operating faultlessly on all 5 continents. Reliability
The motor-charged spring stored energy operating mechanism is a key factor
Continuously increasing its performance, of device reliability: Merlin Gerin cumulates 35 years’ experience with this type
the company maintains a very high level of mechanism, 250,000 of which are already in operation.
of innovation in its offer. Merlin Gerin’s mastery of design and the testing of sealed systems guarantees
sustained device performance for at least 30 years.

Increased endurance
61051N

The mechanical and electrical endurance of Merlin Gerin SF6 breaking devices
are in conformity with the most demanding specifications recommended by the IEC.
These devices therefore meet requirements for even the most exposed of networks.

Less maintenance
Throughout the device’s service life, which in normal operating conditions may be
at least 30 years, the only maintenance required is on the mechanical operating
mechanism, once every 10 years or every 10,000 operations.
Although no maintenance is performed on poles, a diagnosis is possible:
b contact wear can be checked by external pole measurement
b SF6 pressure can be continually monitored by a pressure switch.

Environmentally-friendly
Merlin Gerin devices have been designed to ensure protection of the environment:
b the materials used, both insulating and conductive, are identified and easy
to separate and recycle,
b the SF6 gas is under control from production through to the circuit breaker’s end
of life. In particular it can be recovered at the end of the circuit breaker’s life and
re-used after treatment in line with the new European directive,
b an end of life manual for the product details procedures for dismantling and
recycling components.

Quality Assurance
During production, each circuit breaker undergoes systematic routine tests
in order to check quality and conformity:
b pole sealing check
b checking the correct mechanical operation of the device,
plus its associated locking mechanisms
b checking simultaneous closing of contacts
b checking power frequency insulation level
b checking main circuit resistance
b checking auxiliary circuit insulation
b checking auxiliary circuit electrical resistance
b checking switching speeds
b checking the switching cycle
b measuring the switching times.
The results are recorded on the test certificate for each device
which is initialed by the quality control department.

10
Presentation LF and SF circuit breakers 0

The advantages of proven


technology (cont.)

Certification
The quality system for the design and production of LF and SF range circuit breakers
is certified in conformity with ISO 9001: 2000 quality assurance standard requirements.

DE55745
The environmental management system adopted by Merlin Gerin production sites
for the production of LF and SF range circuit breakers has been assessed and
judged to be in conformity with requirements in standard ISO 14001.
DE55746

11
Presentation LF circuit breakers 0

Example of integration in an
MCset cubicle
PE55754

12
Presentation SF circuit breakers 0

Example of integration in an
SM6 cubicle
PE55755

13
LF and SF circuit breakers Panorama 0

Circuit breakers
LF range circuit breakers SF range circuit breakers

LF1-LF2-LF3 LFP SF1 SFset


Front operating mechanism Front operating mechanism Side or front operating mechanism Side or front operating mechanism
(only fixed installation) with integrated VIP
Rated voltage Ur (kV, 50/60 Hz)

Rated short-circuit breaking current (Isc)


from 25 to 50 kA from 25 from 40 from 25 from 12.5 to 25 kA from 12.5 to 25 kA
to 40 kA to 50 kA to 31.5 kA
Rated current (Ir)
from 630 to 3150 A 5000 A from 400 to 1250 A from 400 to 1250 A

14
LF and SF circuit breakers Panorama (cont.) 0

Protection, monitoring and control


SFset circuit breakers LF/SF1-SF2 circuit breakers

MERLIN GERIN ext 0 off I on Trip


1 > 51 1 > >51 1o > 51 1o > >51
Sepam on

I1 = 165A RMS
I2 = 166A RMS
I3 = 167A RMS

SF2 VIP300P Sepam series 20


Front operating mechanism for phase protection for normal applications
VIP300LL Sepam series 40
for phase and for demanding applications
earthing protection Sepam series 80
for customized applications

Separate catalogue

from 12.5 to 40 kA 31.5 kA

from 630 to 3150 A from 1250


to 2500 A

15
0

16
LF and SF circuit breakers LF circuit breakers 0

Presentation 6
Panorama 14
General characteristics 18
Description of functions 20
Opening circuit 20
Remote control 21
Indication and locking/interlocking 22
Wiring diagram for auxiliary contacts 23
Dimensions 24
Order form 25
Offer structure 26
SF circuit breakers 29

17
LF circuit breakers General characteristics 0

Electrical characteristics according to IEC 62271-100


PE55761

Circuit breakers LF1 LF2 LF3


Ur 7.2 kV Isc Ir
Ud 20 kV 50 Hz, 1 min (*) 25 kA 630 A b
Up 60 kV peak 1250 A b
2500 A b
31.5 kA 630 A b
1250 A b
2500 A b
3150 A b
40 kA 630 A b
1250 A b
2000 A b
2500 A b
3150 A b
50 kA 630 A b
1250 A b
2000 A b
2500 A b
3150 A b
Ur 12 kV Isc Ir
Ud 28 kV 50 Hz, 1 min (*) 25 kA 630 A b
Up 75 kV peak 1250 A b
2500 A b
31.5 kA 630 A b
1250 A b
2500 A b
3150 A b
40 kA 630 A b
1250 A b
2000 A b
2500 A b
3150 A b
50 kA 1250 A b
2500 A b
3150 A b
Ur 17.5 kV Isc Ir
Ud 38 kV 50 Hz, 1 min (*) 25 kA 630 A b
Up 95 kV peak 1250 A b
2000 A b
2500 A b
3150 A b
31.5 kA 630 A b
1250 A b
2000 A b
2500 A b
3150 A b
40 kA (**) 1250 A b
2500 A b
3150 A b

(*) Ud 42 kV 50 Hz, 1 min possible.


(**) Switching sequence: O-3 min-CO-3 min-CO.

18
LF circuit breakers General characteristics (cont.) 0

Additional characteristics according to IEC 62271-100


Service temperature T –25° to 40°C
Rated frequency fr (Hz) 50/60
Short time withstand current Ik/tk (kA) Isc/3 s
Permissible peak current Ip peak (kA) 2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
Making capacity peak (kA) 2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
Switching sequence O-0.3 s-CO-15 s-CO
O-0.3 s-CO-3 min-CO
O-3 min-CO-3 min-CO
Operating times Opening 48 ms
Breaking 70 ms
Making 65 ms
Mechanical endurance Class M2
Number of switching 10000
operations
Electrical endurance Class E2
Current breaking capacity Class C2

Specific applications
Protection of generators and power station auxiliaries
All circuit breakers in the LF range break short circuit currents with an asymmetry
of at least 30%.
In cases where the network constant X/R is greater than 45 ms, the asymmetry
to be broken is higher; this is often the case of circuit breakers protecting nuclear
or thermal power station auxiliaries or circuit breakers that are close to generator sets
or large transformers.
Specific tests have been carried out:
Circuit breakers kV kA Asymmetry
LF2 7.2 43.5 50%
LF3 7.2 43.5 50%
12 40 50%
17.5 25 100%
Switching and protection of capacitor banks
LF range circuit breakers are particularly well suited to switching and protection
of capacitor banks; they are classed C2 according to standard IEC 62271-100.
Tests carried out according to the standard for breaking at 400 A with making
and breaking cycles in case of a capacitor bank with a making current of 20 kA.
Additional tests have been carried out: please consult us.

19
LF circuit breakers Description of functions 0

Opening circuit

Composition
DE55701EN

The opening circuit can be produced using the following components:


b shunt opening release (on energizing) (YO1)
b second shunt opening release (on energizing) (YO2)
b undervoltage release (YM)
b low energy release (Mitop).
(2) (1) or (3)
Note: see the table of possible combinations, page 25.

Shunt opening release (YO1 and YO2)


Energizing this unit causes instant opening of the circuit breaker.
Characteristics
Power supply See page 25
Threshold V AC 0.85 to 1.1 Un
V DC 0.7 to 1.1 Un
Consumption V AC 160 VA
V DC 50 W

Operating device
Undervoltage release (YM)
This release unit causes the systematic opening of the circuit breaker when its
DE60094

supply voltage drops below a value less than 35% of the rated voltage, even if this
drop is slow and gradual. It can open the circuit breaker between 35% and 70% of
its rated voltage. If the release unit is not supplied power, manual or electrical closing
of the circuit breaker is impossible. Closing of the circuit breaker is compulsory when
the supply voltage of the release unit reaches 85% of its rated voltage.
Shunt opening release (1)
Characteristics
Power supply See page 25
DE60089

Threshold Opening 0.35 to 0.7 Un


Closing 0.85 Un
Consumption Triggering V AC 400 VA
V DC 100 W
Latched V AC 100 VA
V DC 10 W
Undervoltage release (2)

Low energy release (Mitop)


DE60091

This specific release unit comprises a low consumption unit and is specifically used
for Sepam 100LA self-powered relays.
Characteristics
Power supply Direct current
Low energy release (3) Threshold 0.6 A < I < 3 A
Any tripping due to the Mitop release unit is momentarily indicated by an SDE type
changeover contact.

20
LF circuit breakers Description of functions 0

Remote control

(6) (5)
Function
DE55702

Remote control enables the remote opening and closing of the circuit breaker.

Composition
The remote control mechanism comprises:
b an electrical motor with gearing
b a shunt closing release (YF) combined with an anti-pumping device
b an operation counter.

Electrical motor with gearing


The electrical motor arms and re-arms the stored energy unit as soon as the circuit
breaker is closed. This allows the instant closing of the device after opening.
The arming lever is only used as a back-up operating mechanism in the case of any
auxiliary power supply.
The M3 contact indicates the end of arming operations.
Characteristics
(4) Power supply See page 25
Threshold V AC/V DC 0.85 to 1.1 Un
Consumption V AC 380 VA
V DC 380 W
Operating mechanism

Shunt closing release (YF)


DE60093

This allows the remote closing of the circuit breaker when the operating mechanism
is armed.
Characteristics
Power supply See page 25
Electrical motor and gearing (4) Threshold V AC 0.85 to 1.1 Un
V DC 0.85 to 1.1 Un
DE60151

Consumption V AC 160 VA
V DC 50 W
The anti-pumping relay enables the guaranteeing of opening priority in the case
of a permanent closing order. This therefore avoids the device being caught
in a uncontrolled opening-closing loop.

Shunt closing release (5)

Operation counter
DE60087

The operation counter is visible on the front panel.


It displays the number of switching cycles (CO) that the device has carried out.

Operation counter (6)

21
LF circuit breakers Description of functions 0

Indication and locking/interlocking

“Open/closed” auxiliary contacts


DE55703

The number of contacts available depends on the options chosen on the operating
mechanism.
In the basic configuration, the circuit breaker’s operating mechanism comprises
a total of:
b 6 normally closed contacts (NC)
b 6 normally open contacts (NO)
b 1 changeover contact (CHG).
The usage procedure for auxiliary contacts is given in the following table:
Options
NC contact NO contact
Remote control 1 1
(7) Shunt opening release (each one) 0 1
Undervoltage release 0 0
Mitop low energy release 0 0
In order to know the final number of available contacts, you must deduct the total
number of contacts included in the circuit breaker (6 NC + 6 NO + 1 CHG),
the number of contacts used given in the table below.
E.g: a circuit breaker equipped with a remote control and a shunt trip unit has
the following available contacts:
Operating mechanism 5 NC + 4 NO + 1 CHG.
With a undervoltage release instead of the shunt trip, this circuit breaker would have
the following available contacts:
DE60124

5 NC + 5 NO + 1 CHG.

Locking the circuit breaker in the “open” position


This key-operated device allows the circuit breaker to be locked in the “open” position.
The circuit breaker is locked in the open position by blocking the opening push button
in the “engaged” position.
Locking is achieved using a Profalux or Ronis captive key type keylock.

Keylocking kit (7)

22
LF circuit breakers Description of functions 0

Wiring diagram for auxiliary contacts

Wiring diagram for auxiliary contacts (principle)


DE55747EN

Close CB

Open CB

M3

YF + YO1 MITOP
anti-pumping or YM
YO2

Motor Shunt closing “Control Shunt Under- Low energy Changeover NO NC


release mechanism opening voltage release contact contacts contacts
+ anti-pumping armed” release release (MITOP)
system indicator contact

Remote control

23
LF circuit breakers Dimensions 0

LF1, LF2, LF3 circuit breakers

Device
Basic fixed
50 50 connection 50 270
LF1 LF2 LF3 35 25

DE55704EN
A 493 554 728

weight (kg) 106 128 149.5

on
off
330
on
off
590

A 536 34

Fixed with a support frame

LF1 LF2 LF3


DE55705

B 542 602 776


weight (kg) 124 148 168
on
off
330
on
off

995

555

B 539 34

Connections
Direct to the device Connection on pads
b LF1 b LF2: b LF3
b LF2 < 2000 A < 95 kV impulse v 2000 A v 2500 A/95 kV impulse
b LF3 < 2500 A and < 95 kV impulse v 1250 A/95 kV impulse v 3150 A/95 kV impulse
v 630 A/95 kV impulse
b LF3: 1250 A/95 kV impulse
63 20 15 52 128
DE55706EN

DE55707

DE55708

3 x 40 8 Ø 12,2
11 11 32
3 x 30
20 40
40
C E
15

60
D E

22,5 4 x ø12
7,5 66 40
3 x 2M10 x 26 (effective length)

LF1 LF2 LF3 Note:


C 160 180 240 b recommended connection screw M10 class 8.8.
Tightening torque: 50 Nm with contact washer.
D 145 165 225
b connectors delivered mounted on the device
E 145 165 225 b for more details refer to the dimensional drawings

24
LF circuit breakers Order form 0

LF1, LF2, LF3 fixed


up to 17.5 kV

Only one of the boxes (ticked X or filled by Basic fixed circuit breaker Quantity
the needed value) have to be considered between each
horizontal line. Rated voltage Ur (kV)
Orange box X corresponds to none priced functions.
Impulse voltage Up (kVbil)

Breaking current Isc (kA)

Rated current Ir (A)

Frequency 50 Hz 60 Hz

Colour for push buttons and indicators IEC standard ANSI standard

Push buttons open/close: Red/black

Indicator open/close: Black/white Green/red

Operating mechanism charged/discharged: White/yellow Charge/discharge

Circuit breaker options


1st opening release (see possible choices in combination table below)
Shunt opening release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
Undervoltage release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
MITOP (not available with sismic version)
Without contact With contact

2nd opening release (see possible choices in combination table below)


Shunt opening release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
Undervoltage release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
MITOP (not available with sismic version)
Without contact With contact

Remote control
Electric motor - MCH 24…32 Vdc 110…127 Vdc/ac
48…60 Vdc/ac 220…250 Vdc/ac
Shunt closing release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)

Low voltage wiring connection Male plug (1.2 m) Female socket (2 m)


Locking C.B. in open position Ronis Profalux
Sismic version (consult us)
Support frame
Leaflets language French English

Different releases combinations


Shunt opening release 1 2 1 1
Undervoltage release 1 1 1
MITOP 1 1 1

25
LF circuit breakers Offer structure 0

LF1, LF2, LF3 fixed


up to 17.5 kV

The basic fixed circuit breaker includes:


b an electrical operating mechanism with remote control (electrical motor,
gear reducer, shunt closing release, antipumping relay and operation counter)
b 1 shunt opening release
b 1 block of 8 to 11 auxiliary contacts (according to options).
The circuit breaker can receive options.

Basic fixed circuit breaker LF1 LF2 LF3


7.2 kV-60 kVpeak 25 kA 630 A b
DE55731

1250 A b
2500 A b
31.5 kA 630 A b
1250 A b
2500 A b
3150 A b
40 kA 630 A b
1250 A b
2000 A b
2500 A b
3150 A b
50 kA 630 A b
1250 A b
2000 A b
2500 A b
3150 A b
12 kV-75 kVpeak 25 kA 630 A b
1250 A b
2500 A b
31.5 kA 630 A b
1250 A b
2500 A b
3150 A b
40 kA 630 A b
1250 A b
2000 A b
2500 A b
3150 A b
50 kA 1250 A b
2500 A b
3150 A b
17.5 kV-95 kVpeak 25 kA 630 A b
1250 A b
2000 A b
2500 A b
3150 A b
31.5 kA 630 A b
1250 A b
2000 A b
2500 A b
3150 A b
40 kA 1250 A b
2500 A b
3150 A b

26
LF circuit breakers Offer structure 0

LF1, LF2, LF3 fixed


up to 17.5 kV (cont.)

Circuit breaker options


Remote control (see possible choices in combination table)
1st opening release
Shunt opening release
Undervoltage release
Low energy release MITOP
2nd opening release
Shunt opening release
Undervoltage release
Low energy release MITOP
Sismic version (consult us)

Different releases combinations


Shunt opening release 1 2 1 1
Undervoltage release 1 1 1
MITOP 1 1 1

Low voltage wiring connection


1.2 m - male plug (Harting)
2 m - female socket (Harting)

Locking, interlocking
Locking circuit breaker in open position (Ronis or Profalux)

Accessories
Support frame (kit)
DE55732

27
0

28
LF and SF circuit breakers SF circuit breakers 0

Presentation 6
Panorama 14
LF circuit breakers 17
General characteristics 30
SF1 and SFset circuit breakers 30
SF2 circuit breakers 31
Other characteristics 32
Description of functions 33
Opening circuit 33
Remote control 34
Indication and locking/interlocking 35
Wiring diagram for auxiliary contacts 36
Protection, monitoring and control 37
VIP300 protection unit 37
Trip curves for VIP300P and VIP300LL 38
Current sensors and test unit for VIP300 39
Dimensions 40
SF1 and SFset circuit breakers 40
SF2 circuit breakers 43
Order form 44
SF1 circuit breakers 44
SFset circuit breakers 45
SF2 circuit breakers 46
Offer structure 47
SF1 circuit breakers 47
SFset circuit breakers 48
SF2 circuit breakers 49

29
SF circuit breakers General characteristics 0

SF1 and SFset circuit breakers

Electrical characteristics according to IEC 62271-100


PE55765

SF1 circuit breakers


Phase to phase distance (mm) 220 280 350(*) 380
Ur 17.5 kV Isc Ir
Ud 38 kV 50 Hz, 1 min 12.5 kA 1250 A b
Up 95 kV peak 20 kA 400 A b
630 A b
1250 A b
25 kA 630 A b
1250 A b
Ur 24 kV Isc Ir
Ud 50 kV 50 Hz, 1 min 12.5 kA 400 A b
Up 125 kV peak 630 A b
1250 A b
SF1 circuit breakers 16 kA 400 A b
630 A b
1250 A b
20 kA 630 A b
1250 A b
PE55766

25 kA 630 A b
1250 A b
Ur 36 kV Isc Ir
Ud 70 kV 50 Hz, 1 min 12.5 kA 400 A b b
Up 170 kV peak 630 A b b
20 kA 630 A b b
1250 A b b
25 kA 630 A b b
1250 A b b
SFset circuit breakers
Phase to phase distance (mm) 220 280
Ur 17.5 kV Isc Ir
Ud 38 kV 50 Hz, 1 min 12.5 kA 1250 A b
Up 95 kV peak 20 kA 400 A b
SFset circuit breakers 630 A b
1250 A b
25 kA 630 A b
1250 A b
Ur 24 kV Isc Ir
Ud 50 kV 50 Hz, 1 min 12.5 kA 400 A b
Up 125 kV peak 630 A b
1250 A b
16 kA 400 A b
630 A b
1250 A b
20 kA 630 A b
1250 A b
25 kA 630 A b
1250 A b

(*) only front operating mechanism

30
SF circuit breakers General characteristics 0

SF2 circuit breakers

Electrical characteristics according to IEC 62271-100


PE55767

SF2 circuit breakers


Phase to phase distance (mm) 300 400 457
Ur 24 kV Isc Ir
Ud 50 kV 50 Hz, 1 min 12.5 kA 2500 A b
Up 125 kV peak 25 kA 2500 A b
31.5 kA 630 A b
1250 A b
2500 A b
40 kA (**) 630 A b
1250 A b
2500 A b
3150 A b
Ur 36 kV Isc Ir
Ud 70 kV 50 Hz, 1 min 25 kA 2500 A b
Up 170 kV peak 31.5 kA (*)(**) 630 A b
1250 A b
2500 A b
40 kA (**) 630 A b
1250 A b
2500 A b
3150 A b
Ur 40.5 kV Isc Ir
Ud 95 kV 50 Hz, 1 min 31.5 kA (*)(**) 2500 A b
Up 185 kV peak

Switching sequences:
b O-0.3 s-CO-15 s-CO
b O-0.3 s-CO-3 min-CO (*)
b O-3 min-CO-3 min-CO (**).
All switching sequences are possible for values without an asterisk.

31
SF circuit breakers General characteristics 0

SF1, SFset and SF2 circuit breakers

Additional characteristics according to IEC 62271-100


SF1 and SFset circuit breakers
Service temperature T –25° to 40°C
Rated frequency fr (Hz) 50/60
Short time withstand current Ik/tk (kA) Isc/3 s
Permissible peak current Ip peak (kA) 2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
Making capacity Peak (kA) 2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
Switching sequence O-0.3 s-CO-15 s-CO
O-0.3 s-CO-3 min-CO
O-3 min-CO-3 min-CO
Operating times Opening < 50 ms
Breaking < 60 ms
Making < 65 ms
Mechanical endurance Class M2
Number of switching 10000
operations
Electrical endurance Class E2
Capacitive current breaking capacity Class C2
SF2 circuit breakers
Service temperature T –25° to 40°C
Rated frequency fr (Hz) 50/60
Short time withstand current Ik/tk (kA) Isc/3 s
Permissible peak current Ip peak (kA) 2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
Making capacity Peak (kA) 2.5 Isc (50 Hz)
2.6 Isc (60 Hz)
Operating sequence O-3 min-CO-3 min-CO
(according to performance levels) O-0.3 s-CO-15 s-CO
O-0.3 s-CO-3 min-CO
Operating times Opening < 50 ms
Breaking < 60 ms
Making < 65 ms
Mechanical endurance Class M2
Number of switching 10000
operations
Electrical endurance Class E2
Capacitive current breaking capacity Class C2

Specific applications
Capacitor bank protection and switching
SF range circuit breakers are particularly well suited to switching and protection
of capacitor banks; they are classed C2 according to standard IEC 62271-100.
Tests carried out according to the standard break at 400 A and have making and
breaking cycles in the case of the capacitor bank with a making capacity of 20 kA.
Additional tests have been carried out: please consult us.

32
SF circuit breakers Description of functions 0

Opening circuit

Composition
DE55701EN

The opening circuit can be produced using the following components:


b shunt opening release (on energizing) (YO1)
b second shunt opening release (on energizing) (YO2)
b undervoltage release (YM)
b low energy release (Mitop).
(2) (1) or (3)
Note: see the table of possible combinations, page 44.

Shunt opening release (YO1 and YO2)


Energizing this unit causes instant opening of the circuit breaker.
Characteristics
Power supply See page 44
Threshold V AC 0.85 to 1.1 Un
V DC 0.7 to 1.1 Un
Consumption V AC 160 VA
V DC 50 W

Operating mechanism
Undervoltage release (YM)
This release unit causes the systematic opening of the circuit breaker when
DE60094

the supply voltage drops below a value of less than 35% of the rated voltage,
even if the drop is slow and gradual. It can open the circuit breaker between 35%
and 70% of the rated voltage. If the release is not supplied power, manual or electrical
closing of the circuit breaker is impossible. Closing of the circuit breaker is compulsory
when the supply voltage to the release unit reaches 85% of its rated voltage.
Shunt opening release (1)
Characteristics
Power supply See page 44
DE60089

Threshold Opening 0.35 to 0.7 Un


Closing 0.85 Un
Consumption Triggering V AC 400 VA
V DC 100 W
Latched V AC 100 VA
V DC 10 W
Undervoltage release (2)

Low energy release (Mitop)


DE60091

This specific release unit comprises a low power consumption unit and is specifically
used for Sepam 100LA, self-powered relays or VIP relays in the case of SFset.
Characteristics
Power supply Direct current
Low energy release (3) Threshold 0.6 A < I < 3 A
Any tripping due to the Mitop release unit is momentarily signaled by an SDE type
changeover contact.

33
SF circuit breakers Description of functions 0

Remote control

(6) (5)
Function
DE55702

Remote control enables the remote opening and closing of the circuit breaker.

Composition
The remote control comprises:
b an electric motor with gearing
b a shunt closing release (YF) associated with an anti-pumping device
b an operation counter.

Electrical motor with gearing


The electrical motor arms and re-arms the stored energy mechanism as soon as
the circuit breaker is closed. This allows instant closing of the device after opening.
The arming lever is only used as a backup control in the case of the absence
of the auxiliary power supply.
The M3 contact indicates the end of the arming operation.
Characteristics
(4) Power supply See page 44
Threshold V AC/V DC 0.85 to 1.1 Un
Consumption V AC 380 VA
V DC 380 W
Operating mechanism
DE60093

Shunt closing release (YF)


This allows the remote closing of the circuit breaker when the control mechanism
is armed.
Characteristics
Power supply See page 44
Electrical motor and gearing (4)
Threshold V AC 0.85 to 1.1 Un
V DC 0.85 to 1.1 Un
DE60151

Consumption V AC 160 VA
V DC 50 W
The anti-pumping relay enables priority to be given to opening in the case
of a permanent closing order. This thus avoids the device being locked in
an uncontrolled opening-closing cycle.

Shunt closing release (5)


DE60087

Operation counter
The operation counter is visible on the front panel.
It displays the number of switching cycles (CO) that the device has carried out.

Operation counter (6)

34
SF circuit breakers Description of functions 0

Indication and locking/interlocking

“Open/closed” auxiliary contacts


DE55703

The number of contacts available depends on the options chosen on the operating
mechanism.
In its basic configuration, the circuit breaker operating mechanism comprises
a total of:
b 6 normally closed contacts (NC)
b 6 normally open contacts (NO)
b 1 changeover contact (CHG).
The usage mode for auxiliary contacts is given in the following table:
Options
NC contact NO contact
Remote control 1 1
(7) Shunt opening release (each one) 0 1
Undervoltage release 0 0
Mitop low energy release 0 0
To know the final number of available contacts, the number of contacts used
indicated in the table below must be deducted from the total number of contacts
included in the circuit breaker (6 NC + 6 NO + 1 CHG).
E.g: a circuit breaker equipped with a remote control and a shunt trip
has the following number of contacts available:
Operating mechanism 5 NC + 4 NO + 1 CHG.
With an undervoltage release instead of a shunt trip unit, this circuit breaker
has the following available contacts:
DE60124

5 NC + 5 NO + 1 CHG.

Locking of the circuit breaker in the “open” position


This keylocking device allows the circuit breaker to be locked in the “open” position.
The circuit breaker is locked in the “open” position by blocking the opening push button
in the “engaged” position.
Locking is achieved using a Profalux or Ronis captive key type keylock.

Keylocking kit (7)

35
SF circuit breakers Description of functions 0

Wiring diagram for auxiliary contacts

Wiring diagram for auxiliary contacts (principle)


DE55747EN

Close CB

Open CB

M3

YF + YO1 MITOP
anti-pumping or YM
YO2

Motor Shunt closing “Control Shunt Under- Low energy Changeover NO NC


release mechanism opening voltage release contact contacts contacts
+ anti-pumping armed” release release (MITOP)
system indicator contact

Remote control

36
SF circuit breakers Protection, monitoring and control 0

VIP300 protection relay

The SFset circuit breaker has an integrated and independent


PE55766

protection system
The SFset circuit breaker comprises an SF1 into which is integrated a protection
system comprising:
b a set of current sensors installed on the lower current terminals of the pole units.
Two interchangeable sensors, CSa and CSb, sufficient to cover all requirements
from 10 A to 1250 A.
b mounted on the control unit.
b a “Mitop” low consumption, release unit installed on the switching device.
The unit is fully independent and functions without an auxiliary power supply.
Operating principle
The protection system is supplied power by sensors which supply:
b the “current” information”, processed by the protection unit
b the electrical power required for the whole protection system to operate;
VIP unit and Mitop release.
SFset with a VIP protection unit installed on the front panel
All settings are visible and accessible from the front of the device.
PE55772

VIP300P and VIP300LL independent protection unit


The VIP300 unit is intended to be installed on distribution networks. It can be used
to protect an MV/LV transformer, to protect the head of an industrial installation,
but also to protect a branch.
The VIP300 provides protection against phase-to-phase faults and against earthing
faults. The choice of trip curves and the large number of settings enable it to be used
in a large number of discrimination arrangements.
The VIP300 is an independent unit supplied power from the current sensors;
it does not require an auxiliary power supply. It activates a Mitop release unit.
The VIP300 exists in 2 models:
b VIP300P: phase protection
b VIP300LL: phase and earthing protection.
DE55725

DE55726

t
VIP300LL protection unit
Mitop

VIP300
t>

t >>
I
1,2 Is 10 Is I >>
Simplified connection arrangement Phase and earthing protection curve

Phase protection (VIP300P, VIP300LL)


Phase protection has two independently adjustable thresholds:
b the lower threshold can be chosen to be either definite time or inverse definite time.
It can be executed according to the RI curve.
b the upper threshold is inverse definite time.
The definite time curves are in conformity with standard IEC 60255-3.
They are either of type inverse (SI), very inverse (VI) and extremely inverse (EI).
Earthing protection (VIP300LL)
Earthing full protection functions with the measurement of residual current:
this is carried out based on the sum of secondary currents in the sensors.
As for phase protection, earthing protection has two independently adjustable
thresholds.
Indication
Two indicators show the origin of the release (phase or earth).
They stay in position after breaking the release unit power supply.
Two LED indicator lights (phase and earth) show that the lower threshold
has been exceeded and that the time delay has been started.

37
SF circuit breakers Protection, monitoring and control 0

Trip curves
VIP300P and VIP 300LL

Trip curves
DE55727

t> t>

t >> t >>

Is 1.2 Is 10 Is I >> Is I> I >>


With a definite time lower threshold With an inverse definite time lower threshold

Definite time curves


t (s) t (s)
DE55728

100 100

10 10
6 6
4
3 4
2 3
1.5 2
1 1 1 1.5
1
0.6
0.4 0.6
0.3 0.4
0.2 0.3
0.15 0.2
0.1 0.1 0.1 0.15
0.07 0.1
0.05 0.07
0.05

I/Is I/Is
0.01 0.01
1 10 100 1 1.2 Is 10 100
RI curve SI curve

t (s) t (s)
DE55729

1000 1000

100 100

10 10

6
4
3 6
1 2 1 4
1.5 3
1 2
0.6 1.5
0.4 1
0.3 0.6
0.1 0.2 0.1 0.4
0.15 0.3
0.1 0.2
0.07 0.15
0.05 0.1
I/Is 0.07 I/Is
0.01 0.01 0.05
1 1.2 Is 10 100 1 1.2 Is 10 100
VI curve EI curve

38
SF circuit breakers Protection, monitoring and control 0

Current sensors and test unit


for VIP300

CSa and CSb current sensors for the VIP300


PE55773

In order to achieve the specified performance levels, the VIP300 protection unit must
be used with the specified sensors. The combination of the unit/sensor is essential
in order to comply with characteristics and in particular with:
b operation throughout the whole range
b response time
b accuracy
b short circuit thermal withstand.
Two interchangeable sensors, CSa and CSb, suffice to cover all requirements
from 10 A to 1250 A.
Sensor selection Service current (Is)
CSa 10 A to 200 A
CSb 63 A to 1250 A

Cs type current sensors


VAP6 test unit
VIP type protection units have a “test”, socket to connect a VAP6 test unit.
This portable unit with its own power supply enables the correct functioning
PE55774

of the protection unit to be checked.

VAP6 test unit

39
SF circuit breakers Dimensions 0

SF1 and SFset circuit breakers

Basic fixed unit


Operating mechanism on the right hand side
SF1 and SFset SF1 SFset
E E P/D P/D
DE55711

350 350

L/W 270

Operating mechanism on the left hand side


SF1 SFset SF1, SFset
P/D P/D E E
DE55712

350 350

270 L/W

Operating mechanism on the front


SF1, SFset SF1 SFset
E E P/D 270 P/D 270
DE55713

345 345

L/W

Dimensions and weights


SF1 SFset
Rated voltage (kV) Dimensions (mm) Weight Dimensions (mm) Weight
H W D E (kg) H W D E (kg)
Operating mechanism on the right or left
17.5 750 993 290 220 78 750 993 420 220 88
24 750 1143 290 280 80 750 1143 420 280 90
36 750 1560 365 380 88
Operating mechanism on the front
17.5 745 766 490 220 78 745 766 620 220 88
24 745 886 490 280 80 745 886 620 280 90
36 745 927 559 350 85
36 745 1260 565 380 88

40
SF circuit breakers Dimensions 0

SF1 and SFset circuit breakers (cont.)

Fixed unit with support frame


Operating mechanism on the right hand side
SF1, SFset SF1 SFset

E E P/D P/D
DE55718

H (1)

775 (1) 775 (1)

L/W

Operating mechanism on the left hand side


SF1 SFset SF1, SFset
P/D P/D E E
DE55719

H (1)

775 (1) 775 (1)

L/W

Operating mechanism on the front


SF1, SFset SF1 SFset

E E P/D P/D
DE55720

H (1)

775 (1) 775 (1)

L/W

Dimensions and weights


SF1 SFset
Rated voltage (kV)Dimensions (mm) Weight Dimensions (mm) Weight
H W D E (kg) H W D E (kg)
Operating mechanism on the right or left hand side
17.5 1175 1065 600 220 103 1175 1065 600 220 103
24 1175 1215 600 280 105 1175 1215 600 280 105
36 1175 632 600 380 113
Operating mechanism on the front
17.5 1175 853 600 220 103 1175 853 649 220 103
24 1175 973 600 280 105 1175 973 649 280 105
36 1175 1347 600 380 113
(1) Additional holes, provided on the fixed support frame allow the device to be positioned 215 mm lower.

41
SF circuit breakers Dimensions 0

SF1 and SFset circuit breakers (cont.)

Connection
Top
SF1, SFset (A) SF1, SFset (B)
20 Ø 24 M8 kA 20 Ø 40 M8
DE55714-A

DE55714-B
DE55709
25

20 (B)
56 56
16 20

17 17
8 13 +0.2
0 12,5 (A) 8 +0.2
13 0

0 17,5 24 36 kV

Bottom
SF1, insulation y 125 kV impulse SF1, insulation y 170 kV impulse SFset
25 ± 0,5
DE55715

DE55716

DE55717
2 Ø M8 2 Ø 10,5 52 2 Ø M8

10
20

18 Ø 40 60 Ø 40
20 20
75

Note: recommended connection screw M8 class 8.8.


Tightening torque: 28 Nm with contact washer.

42
SF circuit breakers Dimensions 0

SF2 circuit breakers

Basic fixed unit


P/D 300
E E 190
DE55722

372

L/W

Fixed unit with a support frame


P/D 300
E E
190
DE55721

630

L/W 644

Connection
630, 1250 A 2500, 3150 A 2000 A (*)

32,5 35 78 2 Ø M12
DE55723

DE55724

10 70 30
100
90 30 20 Ø 60
35
8 Ø13 49,5
18,5 90

63 70

26 Note: recommended connection screw M12 class 8.8.


26 47 10 117 Tightening torque: 75 Nm with contact washer.

Dimensions and weights


Basic fixed unit Fixed unit with support frame
Rated current (A) Rated voltage (kV) Dimensions (mm) Weight Dimensions (mm) Weight
H W D E (kg) H W D E (kg)
630, 1250 24 825 910 750 300 159 1030 910 750 300 179
36 825 1110 750 400 212 1030 1110 750 400 239
40.5 825 1224 750 457 242 1030 1224 750 457 272
2500, 3150 24 942 910 777 300 174 1147 910 777 300 194
36 942 1110 777 400 227 1147 1110 777 400 254
40.5 942 1224 777 457 242 1147 1224 777 457 272
(*) This connector is specific for the 2000 A rated current, “ANSI standard”.

43
SF circuit breakers Order form 0

SF1 frontal/lateral fixed


up to 36 kV

Only one of the boxes (ticked X or filled by Basic fixed circuit breaker Quantity
the needed value) have to be considered between each
horizontal line. Rated voltage Ur (kV)
Orange box X corresponds to none priced functions.
Impulse voltage Up (kVbil)

Breaking current Isc (kA)

Rated current Ir (A)

Frequency 50 Hz 60 Hz

Operating mechanism position A1 B1 C1

Colour for push buttons and indicators IEC standard ANSI standard

Push buttons open/close: Red/black

Indicator open/close: Black/white Green/red

Operating mechanism charged/discharged: White/yellow Charge/discharge

Circuit breaker options


1st opening release (see possible choices in combination table below)
Shunt opening release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
Undervoltage release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
MITOP Without contact With contact

2nd opening release (see possible choices in combination table below)


Shunt opening release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
Undervoltage release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
MITOP Without contact With contact

Remote control
Electric motor - MCH 24…32 Vdc 110…127 Vdc/ac
48…60 Vdc/ac 220…250 Vdc/ac
Shunt closing release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)

Low voltage wiring connection Male plug (1.2 m) Female socket (2 m)


Locking C.B. in open position Ronis Profalux
Pressure switch option (not available for all electrical characteristics)
Support frame Low (560 mm) High (775 mm)
Leaflets language French English Spanish

Different releases combinations


Shunt opening release 1 2 1 1
Undervoltage release 1 1 1
MITOP 1 1 1

44
SF circuit breakers Order form 0

SFset frontal/lateral fixed


up to 24 kV

Only one of the boxes (ticked X or filled by Basic fixed circuit breaker Quantity
the needed value) have to be considered between each
horizontal line. Rated voltage Ur (kV)
Orange box X corresponds to none priced functions.
Impulse voltage Up (kVbil)

Breaking current Isc (kA)

Rated current Ir (A)

Frequency 50 Hz 60 Hz

Operating mechanism position A1 B1 C1

Colour for push buttons and indicators IEC standard ANSI standard

Push buttons open/close: Red/black

Indicator open/close: Black/white Green/red

Operating mechanism charged/discharged: White/yellow Charge/discharge

Control unit and sensors


Available in 2005
VIP 300P
(not available for all CSa 200/1 Is = 10 to 50 A Is = 40 to 200 A
electrical characteristics) CSb1250/1 Is = 63 to 312 A Is = 250 to 1250 A
VIP 300LL
CSa 200/1 Is = 10 to 50 A Is = 40 to 200 A
CSb1250/1 Is = 63 to 312 A Is = 250 to 1250 A

Circuit breaker options


2nd opening release (see possible choices in combination table below)
Shunt opening release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
Undervoltage release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)

Remote control
Electric motor - MCH 24…32 Vdc 110…127 Vdc/ac
48…60 Vdc/ac 220…250 Vdc/ac
Shunt closing release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
30 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)

Low voltage wiring connection Male plug (1.2 m) Female socket (2 m)


Locking C.B. in open position Ronis Profalux
Pressure switch option (not available for all electrical characteristics)
Support frame Low (560 mm) High (775 mm)
Test box (VAP 6)
Leaflets language French English Spanish

Different releases combinations


MITOP 1 1 1
Shunt opening release 1
Undervoltage release 1

45
SF circuit breakers Order form 0

SF2 frontal fixed


up to 40.5 kV

Only one of the boxes (ticked X or filled by Basic fixed circuit breaker Quantity
the needed value) have to be considered between each
horizontal line. Rated voltage Ur (kV)
Orange box X corresponds to none priced functions.
Impulse voltage Up (kVbil)

Breaking current Isc (kA)

Rated current Ir (A)

Frequency 50 Hz 60 Hz

Colour for push buttons and indicators IEC standard ANSI standard

Push buttons open/close: Red/black

Indicator open/close: Black/white Green/red

Operating mechanism charged/discharged: White/yellow Charge/discharge

Circuit breaker options


1st opening release (see possible choices in combination table below)
Shunt opening release
24 Vdc 60 Vdc 220 Vdc 250 Vac (50 Hz)
32 Vdc 100-109 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 100-127 Vdc 220 Vac (50 Hz) 240 Vac (60 Hz)
Undervoltage release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
32 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
MITOP Without contact With contact

2nd opening release (see possible choices in combination table below)


Shunt opening release
24 Vdc 60 Vdc 220 Vdc 250 Vac (50 Hz)
32 Vdc 100-109 Vdc 110 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 100-127 Vdc 220 Vac (50 Hz) 240 Vac (60 Hz)
Undervoltage release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
32 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)
MITOP Without contact With contact

Remote control
Electric motor - MCH 24…32 Vdc 110…127 Vdc/ac
48…60 Vdc/ac 220…250 Vdc/ac
Shunt closing release
24 Vdc 60 Vdc 220 Vdc 220 Vac (50 Hz)
32 Vdc 110 Vdc 48 Vac (50 Hz) 120 Vac (60 Hz)
48 Vdc 125 Vdc 110 Vac (50 Hz) 240 Vac (60 Hz)

Low voltage wiring connection Male plug (1.2 m) Female socket (2 m)


Locking C.B. in open position Ronis Profalux
Pressure switch option
Support frame
Leaflets language French English

Different releases combinations


Shunt opening release 1 2 1 1
Undervoltage release 1 1
MITOP 1 1

46
SF circuit breakers Offer structure 0

SF1 frontal/lateral fixed


up to 36 kV

The basic fixed circuit breaker includes:


b a manual operating mechanism (spring type)
b 1 shunt opening release
b 1 block of 8 to 11 auxiliary contacts (according to options).
The circuit breaker can receive options.

Basic fixed circuit breaker


Phase distance (mm) 220 280 350 380
DE55734
DE55733

Operating mechanism position A1, B1, C1 A1, B1, C1 C1 A1, B1, C1


17.5 kV-95 kVpeak 12.5 kA 1250 A b
20 kA 400/630 A (*) b
1250 A b
25 kA 630 A b
1250 A b
24 kV-125 kVpeak 12.5 kA 400/630 A (*) b
1250 A b
16 kA 400/630 A (*) b
A1 B1 1250 A b
20 kA 630 A b
DE55735

1250 A b
25 kA 630 A b
1250 A b
36 kV-170 kVpeak 12.5 kA 400/630 A (*) b b
20 kA 630 A b b
C1 1250 A b b
25 kA 630 A b b
1250 A b b

Circuit breaker options


Remote control (see possible choices in combination table)
1st opening release
Shunt opening release
Undervoltage release
Low energy release MITOP
2nd opening release
Shunt opening release
Undervoltage release
Low energy release MITOP
Remote control including:
Electrical motor, gear reducer, shunt closing release, operation counter

Different releases combinations


Shunt opening release 1 2 1 1
Undervoltage release 1 1 1
MITOP 1 1 1

Low voltage wiring connection


1.2 m - male plug (Harting)
2 m - female socket (Harting)

Locking, interlocking
Locking circuit breaker in open position (Ronis or Profalux)

Pressure switch
Option not available for (*) characteristics

Accessories
Support frame (kit)
DE55736

47
SF circuit breakers Offer structure 0

SFset frontal/lateral fixed


up to 24 kV

The basic fixed circuit breaker includes:


b a manual operating mechanism (spring type)
b 1 low energy release MITOP
b 1 block of 8 to 11 auxiliary contacts (according to options)
b Control unit and sensors.
The circuit breaker can receive options.

Basic fixed circuit breaker


Phase distance (mm) 220 280
DE55738
DE55737

Operating mechanism position A1, B1, C1 A1, B1, C1


17.5 kV-95 kVpeak 12.5 kA 1250 A b
20 kA 400/630 A (*) b
1250 A b
25 kA 630 A b
1250 A b
24 kV-125 kVpeak 12.5 kA 400/630 A (*) b
1250 A b
16 kA 400/630 A (*) b
DE55739

A1 B1 1250 A b
20 kA 630 A b
1250 A b
25 kA 630 A b
1250 A b

C1

Control unit and sensors


VIP300P With 2 sensors CSa
DE55741

only for (*) characteristics


VIP300LL With 3 sensors CSa/CSb

Circuit breaker options


Remote control (see possible choices in combination table)
2nd opening release
Shunt opening release
Undervoltage release
Remote control including:
Electrical motor, gear reducer, shunt closing release, operation counter

Different releases combinations


MITOP 1 1 1
Shunt opening release 1
Undervoltage release 1

Low voltage wiring connection


1.2 m - male plug (Harting)
2 m - female socket (Harting)

Locking, interlocking
Locking circuit breaker in open position (Ronis or Profalux)

Pressure switch
Option not available for (*) characteristics

Accessories
Support frame (kit) (fig. 1)
DE55736

DE55744

Test box (VAP 6) (fig. 2)

Fig. 1 Fig. 2

48
SF circuit breakers Offer structure 0

SF2 frontal fixed


up to 40.5 kV

The basic fixed circuit breaker includes:


b an electrical operating mechanism with remote control
(electrical motor, gear reducer, shunt closing release and operation counter)
b 1 shunt opening release
b 1 block of 8 to 11 auxiliary contacts (according to options).
The circuit breaker can receive options.

Basic fixed circuit breaker


Phase distance (mm) 300 400 457
DE55735

24 kV-125 kVpeak 12.5 kA 2500 A b


25 kA 2500 A b
31.5 kA 630 A b
1250 A b
2500 A b
40 kA 630 A b
1250 A b
2500 A b
C1
3150 A b
36 kV-170 kVpeak 25 kA 2500 A b
31.5 kA 630 A b
1250 A b
2500 A b
40 kA 630 A b
1250 A b
2500 A b
3150 A b
40.5 kV-185 kVpeak 31.5 kA 2500 A b

Circuit breaker options


Remote control (see possible choices in combination table)
1st opening release
Shunt opening release
Undervoltage release
Low energy release MITOP
2nd opening release
Shunt opening release
Undervoltage release
Low energy release MITOP

Different releases combinations


Shunt opening release 1 2 1 1
Undervoltage release 1 1
MITOP 1 1

Low voltage wiring connection


1.2 m - male plug (Harting)
2 m - female socket (Harting)

Locking, interlocking
Locking circuit breaker in open position (Ronis or Profalux)

Pressure switch

Accessories
Support frame (kit)
DE55736

49