You are on page 1of 3
Graphic 3 oer) EyEy E R410A Graphic 1 @. cane Discharge tube - horizontal ine 24 EL JUNIFLAIR™ Graphic 2 Discharge tube - vertical line ® Liat S ‘S WAX \\ VW \\\ \ TA .|\ WW 8 25 Conforming to the Standards EN 14276-1 and EN 14276-2 the minimum recommended thickness for the gas supply pipe where bends are made for the air cooled units with R410A refrigerant, must be equal othe values presentin the attached table below, The value "R' refers tothe minimum allowed radius of the bend, External diameter] Radius of the bend | Thickness De (mm) + [mm] Umm] 28 100) 12 22 66 4 o a 18 27 1 16 26 1 12 20 1 Line sizing R07 ¥ ¥ . ¥ fp egrets EXAMPLE - Choosing the diameter of the discharge tube with R407C refrigerant Conditioner selected: TDARO721A Cooling capacity per circuit: 24 Kw Discharge line: vertical Equivalent length of the line: 20 m 1) Graphic 2: Operating at 100% (2 compressors - cooling capacity per circult = 24KW) possible diameters: 20mm DPIL= 1,8 Kpalm ‘@mm DP/L= 3,0 Kpaim 1mm DP/L= 6,0 Kpaim 26 ‘14mm _DPIL= 11,5 Kpalm Operating at 50% (1 compressor - cooling capacity per circuit = 12 KW): possible diameters: 7 Kpaim 2) Graphic 3: Operating at 100% (2 compressors) Diameter 16mm 6,0Kpalm Allowed Diameter 14mm 11,5 Kpaim Not allowed ‘The advised diameteris 16mm

You might also like