This drawing is the property of L&T Construction, B&F-EDRC and must not be passed on to any person or body not authorised by
us to receive it nor be copied or otherwise made use either in full or in part by such person or body without our prior permission

EPI-C-10-LMSDB
M
LOC : ELEC. ROOM (C.E.10) 230V AC I/P M
POWER SUPPLY

address:

___.______

L N PE MTN6725-0004

1/9 2/10 3/11 4/12

KNX DALI-Gateway
Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG

UPS 230V 1A
230V AC I/P POWER SUPPLY
address: address: address:

___.______ ___.______ ___.______

L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12

KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway


Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

address: address: address: address: address: 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

___.______ ___.______ ___.______ ___.______ ___.______

L L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L

address: address: address:

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 L N PE
___.______

MTN6725-0004 L N PE
___.______

MTN6725-0004 L N PE
___.______

MTN6725-0004

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12

KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway

KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG address:

___.______
address:

___.______
address:

___.______

L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12

KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway


Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

K K

2C OF 1.5 Sq.mm PVC INSULATED FRLS Cu.

EPI/C/10/DALI ZONE-15

EPI/C/10/DALI ZONE-16
WIRE IN 20mm DIA MS/PVC CONDUIT

EPI/C/10/DALI ZONE-1

EPI/C/10/DALI ZONE-4

EPI/C/10/DALI ZONE-2

EPI/C/10/DALI ZONE-5

EPI/C/10/DALI ZONE-3

EPI/C/10/DALI ZONE-6

EPI/C/10/DALI ZONE-7

EPI/C/10/DALI ZONE-8
INTERNAL VIEW FRONT VIEW
A9HFD456
EPI-C-10-LMSDB-1

CAT6 CABLE FROM


NEAREST DATA POINT
J J

L N + + - - address: address: address: address: address: address:

___.______ ___.______ ___.______ ___.______ ___.______ ___.______


Input Output
100-240VAC 24VDC 0.6A L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004
address:

___.______

ABLM1A24004 L N PE MTN6725-0004

1/9 2/10 3/11 4/12

KNX DALI-Gateway
Basic REG-K/2/16/64

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG

KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway
Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.
L N + + - -

Input Output
100-240VAC 24VDC 0.6A
ABLM1A24004

H H
D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG
FRLS Cu. WIRE IN 20mm DIA MS/PVC

EPI/C/10/DALI ZONE-14

EPI/C/10/DALI ZONE-13

EPI/C/10/DALI ZONE-12

EPI/C/10/DALI ZONE-11

EPI/C/10/DALI ZONE-10
2C OF 1.5 Sq.mm PVC INSULATED

EPI/C/10/DALI ZONE-17
EPI/C/10/DALI ZONE-9
SPARE
SPARE

SPARE

SPARE

SPARE
NOTE:

1. FOR UPS POWER SOCKET REFER DRAWING NO: GHIAL-LNT-W-PTB-E-73-2020 TO


GHIAL-LNT-W-PTB-E-73-2023
G G
2. FOR DATA POINT REFER LATEST IT ENDPOINT DRAWING
CONDUIT

DATA POINT REQUIRED 3. FOR ELECTRICAL EQUIPMENT LAYOUT REFER DRAWING NO: GHIAL- LNT- W- PTB- E- 71- 2020
TO GHIAL- LNT- W- PTB- E- 71- 2023

FIELD DEVICES 4.FOR LIGHTING LAYOUT DALI LOOPING REFER DRAWING NO: GHIAL-LNT-D-PTB-E-72-2303

INTERNAL VIEW FRONT VIEW 5.FOR LIGHTING LAYOUT REFER DRAWING NO: GHIAL- LNT- W- PTB- E- 72- 2020 TO
A9HFD456 GHIAL- LNT- W- PTB- E- 72- 2023
EPI-C-10-LMSDB-2
EPI-C-26-LMSDB S.NO. SYMBOL DESCRIPTION QTY
F F
EPI/C/DS2
1.
2P MCB

2P MCB --
GENERAL ARRANGEMENT DRAWING
2. iPRD40 2P
Surge Arrester

SURGE ARRESTER --
+ - + - + -
DLS 4KP 4KP 3.
address:

___.______
POWER SUPPLY-1280mA 01
L N PE MTN6725-0004

EPI/C/DS1 EPI/C/10/KP1 EPI/C/10/KP2 1/9 2/10 3/11 4/12

DALI MODULE 11
6.
KNX DALI-Gateway
Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG

7. LOGIC CONTROLLER 01
L N + + - -

E POWER SUPPLY FOR LOGIC E


Input Output
100-240VAC 24VDC 0.6A
ABLM1A24004

8. CONTROLLER
01

LEVEL E 9. 4KP 4 FOLD KEYPAD 02


DALI TYPE-2
E
N
DALI TYPE-2
E
N
7.500 mFFL
Driver-3
L
D1 Driver-4
L
D1
EN15 E15 EN16 10. DLS DAYLIGHT SENSOR *
H
D2 D2

11. KNX/EIB CABLE --


EAF LCP/PTB/EPI/C/011/F
12. 3Rx1.5SQMM FRLS CU. WIRE --
E E
N N
DALI TYPE-2 L DALI TYPE-2 L
Driver-2 D1
D2
Driver-5 D1
D2
900 1000
13. 2C x 1.5 SQMM DALI CABLE --
D D

14. CAT6 CABLE --


450

CAT6 TO DATA PORT (CABLE TO BE LAYED


300MM
0

AWAY FROM OTHER SERVICES


143

CONDUIT/RACEWAY AND TO BE DONE


1535

E E
460

DALI TYPE-2 N
DALI TYPE-2 N AS PER SITE CONDITION.)
L L 108 750
Driver-1 Driver-45 0 TRAFO-03
D1
D2
D1
D2 EPI-C-10-LMSDB-1
RTU PANEL
EPI-C-10-LMSDB-2 A 200x100mm RACEWAY (TYP)
1000
650

2Cx1.5SQ.MM. 510 600


FRLS Cable MAIN HT PANEL
400

address:

___.______
C-NELDB-6
0

L N PE MTN6725-0004
117

3500
‎3100

2100

E
C 1/9 2/10 3/11 4/12
N
C-EPDB-2 C
L SOURCE FROM LDB(LIGHTING DB)
200

KNX DALI-Gateway
Basic REG-K/2/16/64
E ABS PAPR RMK SMS/VSN
N
0 ISSUED FOR APPROVAL
L
C-NEPDB-2 ABS 19.07.2022 PAPR 20.07.2022 RMK 21.07.2022 SMS/VSN 22.07.2022

7350
5/13 6/14 7/15 8/16 Man.

150X100mm Cable tray


900

REV.NO. DESCRIPTION DESIGNED DRAWN CHECKED APPROVED


D1+ D1- D2+ D2- KNX / PRG

REVISIONS
C-EMLDB-2

2600
200

CHECKED BY SIGN DATE CHECKED BY SIGN DATE CHECKED BY SIGN DATE


3440 1850 2000
C-UDB-2 ARCHITECTURE HVAC GIS
900

TENANT PANEL
2850 CIVIL & STRUCTURAL FPS GEOTECH
C-NELDB-2
200

2Cx1.5SQ.MM. FIRE MODE VENTILATION PANEL-1 ELECTRICAL PIPING AIRPORT SYSTEMS


2715

FRLS Cable
ELV SYSTEM PHE VHT
C-ELDB-2 C-ELECTRICAL 200x100mm
0
117

3000

DALI TYPE-2
D2
D1
DALI TYPE-2
D2
D1
ROOM - 2 RACEWAY
L L
Driver-1 Driver-45 6000 2065
B
N
E
N
E
200 1170 200 900 200 900 200 1170 200200 650 B
A

CLIENT : GMR HYDERABAD CONCEPT:

EPI-C-10-LMSDB-1
5

535
155

INTERNATIONAL AIRPORT LIMITED. Mechanical, Electrical, Civil, Structural, Geotechnical


1250

EARTH BUS
LMSDB-1
1700

2065 500 PROJECT: O18151 - EXPANSION OF RAJIV GANDHI PROJECT Engineering Design and Research Center (EDRC),
DALI TYPE-2
D2
D1
DALI TYPE-2
D2
D1
C-NELDB-2 INTERNATIONAL AIRPORT. CONSULTANT: L&T Construction - Buildings & Factories.
L L
Driver-2 N Driver-5 N
E E SUPPLIER / CONTRACTOR : Larsen & Toubro Limited, Construction, Buildings & Factories
0
112

APFC-1 SECTION/
JOB No : O18151 TITLE:

2000
1440

ELEVATION

EPI-C-10-LMSDB-2
MAIN LT PANEL SL NAME SIGN DATE EXPANSION OF RAJIV GANDHI INTERNATIONAL AIRPORT MARKING
1000

SPF LCP/PTB/EPI/C/001/F LPF LCP/PTB/EPI/C/001/F C-NELDB-2 LMSDB-2


DSGN ABS ABS 19.07.2022
4KP 4KP DRAWING
DRWN PAPR PAPR 20.07.2022 EAST PIER - LEVEL C (BULB PORTION) NUMBER
D'
D2 D2
DALI TYPE-2 D1
DALI TYPE-2 D1
CHKD RMK RMK 21.07.2022 LIGHTING LMS DB SCHEMATIC DRAWING SCALE
L L
Driver-3 N Driver-4 N
As indicated
A E E
APPD SMS/VSN SMS/VSN 22.07.2022 A
C-EMLDB-2 C-EPDB-2 PROJECTION
E15 EN15 LMS DB LOCATION DETAIL ELEC. ROOM-2 EN16 C-UDB-2 C-NEPDB-2
C-NELDB-6
LEVEL C DRAWING No. GHIAL-LNT-D-PTB-E-72-2302
SIZE

A0
REV

0
0.150 mFFL SHEET: FIRST ANGLE

GENERAL WIRING SCHEME FOR DALI


PRELIMINARY TENDER INFORMATION APPROVAL CONSTRUCTION
SECTION-"AA" RELEASED FOR

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
16 15 14 13 12 11 10 9 8 7 6 5 4
This drawing is the property of L&T Construction, B&F-EDRC and must not be passed on to any person or body not authorised by
us to receive it nor be copied or otherwise made use either in full or in part by such person or body without our prior permission

EPI-C-26-LMSDB

M
LOC : ELEC. ROOM (C.E.26) 230V AC I/P
POWER SUPPLY M

address: address: address:

___.______ ___.______ ___.______

L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12

KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway


Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

UPS 230V 1A
230V AC I/P POWER SUPPLY L N PE
address:

___.______

MTN6725-0004 L N PE
address:

___.______

MTN6725-0004 L N PE
address:

___.______

MTN6725-0004

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12

KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway


Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

address: address: address: address: address: address: address:

___.______ ___.______ ___.______ ___.______ ___.______ ___.______ ___.______


address: address: address:

___.______ ___.______ ___.______

L L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004


L

1/9
N PE

2/10 3/11
MTN6725-0004

4/12
L

1/9
N PE

2/10 3/11
MTN6725-0004

4/12
L

1/9
N PE

2/10 3/11
MTN6725-0004

4/12
L
KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway
Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12

FROM EPI/C/DS1 KNX DALI-Gateway


Basic REG-K/2/16/64
KNX DALI-Gateway
Basic REG-K/2/16/64
KNX DALI-Gateway
Basic REG-K/2/16/64
KNX DALI-Gateway
Basic REG-K/2/16/64
KNX DALI-Gateway
Basic REG-K/2/16/64
KNX DALI-Gateway
Basic REG-K/2/16/64
KNX DALI-Gateway
Basic REG-K/2/16/64
address: address: address:

___.______ ___.______ ___.______

L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.
KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway
Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

INTERNAL VIEW FRONT VIEW


K K
A9HFD456
2C OF 1.5 Sq.mm PVC INSULATED FRLS Cu.

EPI-C-26-LMSDB-1

EPI/C/26/DALI ZONE-12
EPI/C/26/DALI ZONE-10

EPI/C/26/DALI ZONE-12
EPI/C/26/DALI ZONE-11

EPI/C/26/DALI ZONE-13
WIRE IN 20mm DIA MS/PVC CONDUIT

EPI/C/26/DALI ZONE-1

EPI/C/26/DALI ZONE-8

EPI/C/26/DALI ZONE-2

EPI/C/26/DALI ZONE-9

EPI/C/26/DALI ZONE-3

EPI/C/26/DALI ZONE-4

EPI/C/26/DALI ZONE-5

EPI/C/26/DALI ZONE-6

EPI/C/26/DALI ZONE-7
address:

___.______

L N PE MTN6725-0004

1/9 2/10 3/11 4/12

KNX DALI-Gateway
Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG

J J

address: address: address: address: address: address:

___.______ ___.______ ___.______ ___.______ ___.______ ___.______

L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12

KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway
Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

H D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG H

FRONT VIEW
FRLS Cu. WIRE IN 20mm DIA MS/PVC

INTERNAL VIEW
EPI/C/26/DALI ZONE-19

EPI/C/26/DALI ZONE-18

EPI/C/26/DALI ZONE-17

EPI/C/26/DALI ZONE-16

EPI/C/26/DALI ZONE-14
EPI/C/26/DALI ZONE-15
2C OF 1.5 Sq.mm PVC INSULATED

EPI/C/26/DALI ZONE-21

EPI/C/26/DALI ZONE-20
SPARE

SPARE

SPARE

SPARE
A9HFD456
EPI-C-26-LMSDB-2 NOTE:

1. FOR UPS POWER SOCKET REFER DRAWING NO: GHIAL-LNT-W-PTB-E-73-2020 TO


GHIAL-LNT-W-PTB-E-73-2023
G G
CONDUIT

2. FOR DATA POINT REFER LATEST IT ENDPOINT DRAWING


GENERAL ARRANGEMENT DRAWING
3. FOR ELECTRICAL EQUIPMENT LAYOUT REFER DRAWING NO: GHIAL- LNT- W- PTB- E- 71- 2020
TO GHIAL- LNT- W- PTB- E- 71- 2023

FIELD DEVICES (1750mmX300mm) ELECTRICAL E26 4.FOR LIGHTING LAYOUT DALI LOOPING REFER DRAWING NO: GHIAL-LNT-D-PTB-E-72-2303
CUTOUT @ LEVEL C CEILING TO 5.FOR LIGHTING LAYOUT REFER DRAWING NO: GHIAL- LNT- W- PTB- E- 72- 2020 TO
RISE / DROP THE ELECTRICAL GHIAL- LNT- W- PTB- E- 72- 2023
CABLE
400 1800
F S.NO. SYMBOL DESCRIPTION QTY F
EPI-C-34-LMSDB

300
BMU PANEL 1. 2P MCB

2P MCB --

550 150

300
2. SURGE ARRESTER --
+ - + - + -
iPRD40 2P

SE
Surge Arrester

GI EARTH BUS

1512
DLS 4KP 4KP SH 1750
3. POWER SUPPLY-1280mA --

300
EPI/C/DS2 EPI/C/26/KP1 EPI/C/26/KP2 150 1688 450 1138 L N PE
address:

___.______

MTN6725-0004

1/9 2/10 3/11 4/12

DALI MODULE 13
6.
KNX DALI-Gateway
Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man.

C-EMLDB-3 D1+ D1- D2+ D2- KNX / PRG

C-IT UDB - 3 7. LOGIC CONTROLLER --

900
E L N + + - - E
POWER SUPPLY FOR LOGIC
Input Output
100-240VAC 24VDC 0.6A
ABLM1A24004

8. --
CONTROLLER
CEILING SLAB

200
E E
9. 4KP 4 FOLD KEYPAD 02
N N
DALI TYPE-2 DALI TYPE-2

VENTILATION FAN PANEL-1


L L

2900
Driver-3 D1 Driver-4 D1
D2 D2
10. DAYLIGHT SENSOR

SUB NORMAL MODE


DLS 01
C-NELDB-3

1170
11. KNX/EIB CABLE --
FRONT
E E C-NELDB-3 12. 3Rx1.5SQMM FRLS CU. WIRE --
N N
150X100mm Cable tray

DALI TYPE-2 L DALI TYPE-2 L


Driver-2 D1 Driver-5 D1

13.

200
D
D2 D2
2C x 1.5 SQMM DALI CABLE -- D

C-EPDB-3 14. CAT6 CABLE --


X

900
DALI TYPE-2
E
N
L DALI TYPE-2
E
N
L
C-NEPDB-3
Driver-1 D1 Driver-45 D1
D2 D2

300
200
2Cx1.5SQ.MM.
FRLS Cable

address:
150

___.______

L N PE MTN6725-0004

1170
EPI-C-26-LMSDB-1

EPI-C-26-LMSDB-2

E
C 1/9 2/10 3/11 4/12
C
N
L SOURCE FROM LDB(LIGHTING DB) C-ELDB-3

2900
KNX DALI-Gateway
Basic REG-K/2/16/64
E ABS PAPR RMK SMS/VSN
N
0 ISSUED FOR APPROVAL
L C-UDB-3 ABS 19.07.2022 PAPR 20.07.2022 RMK 21.07.2022 SMS/VSN 22.07.2022

SUB NON-ESEENTIAL LTG


5

5/13 6/14 7/15 8/16 Man.

1688 REV.NO. DESCRIPTION DESIGNED DRAWN CHECKED APPROVED


741

& POWER PANEL-1


D1+ D1- D2+ D2- KNX / PRG

200
REVISIONS
SIGN DATE SIGN DATE DATE
FRONT EPI-C-26-LMSDB-1 CHECKED BY CHECKED BY CHECKED BY SIGN

436
ARCHITECTURE HVAC GIS
CIVIL & STRUCTURAL FPS GEOTECH

900
2Cx1.5SQ.MM. C-IT UDB - W ELECTRICAL PIPING AIRPORT SYSTEMS
FRLS Cable
ELV SYSTEM PHE VHT
EPI-C-26-LMSDB-2
1200

DALI TYPE-2
D2
D1
DALI TYPE-2
D2
D1
B

1253
L L
Driver-1 N
E
Driver-45 N
E
436 436
B B

C-IT UDB - S

1050
CLIENT : GMR HYDERABAD CONCEPT:
INTERNATIONAL AIRPORT LIMITED. Mechanical, Electrical, Civil, Structural, Geotechnical

450 PROJECT: O18151 - EXPANSION OF RAJIV GANDHI PROJECT Engineering Design and Research Center (EDRC),
D2 D2 BMU PANEL INTERNATIONAL AIRPORT. CONSULTANT: L&T Construction - Buildings & Factories.
DALI TYPE-2 D1
DALI TYPE-2 D1
L L
Driver-2 Driver-5

1199

1211
N N
E E SUPPLIER / CONTRACTOR : Larsen & Toubro Limited, Construction, Buildings & Factories

1000
523
600 PMS
JOB No : O18151 TITLE:
SECTION/
ELEVATION
MARKING
NAME SIGN DATE EXPANSION OF RAJIV GANDHI INTERNATIONAL AIRPORT
DSGN ABS ABS 19.07.2022

150
FLOOR SLAB 4KP 4KP
DALI TYPE-2
D2
D1
L
DALI TYPE-2
D2
D1
L
D' D' DRWN

CHKD
PAPR

RMK
PAPR

RMK
20.07.2022

21.07.2022
EAST PIER - LEVEL C (BULB PORTION)
LIGHTING LMS DB SCHEMATIC DRAWING
DRAWING
NUMBER
SCALE
Driver-3 N Driver-4 N
As indicated
A E E
APPD SMS/VSN SMS/VSN 22.07.2022 A

150 LMS DB LOCATION DETAIL ELEC. ROOM-2 DRAWING No. GHIAL-LNT-D-PTB-E-72-2302


PROJECTION SIZE

A0
REV

0
SHEET:

E26
FIRST ANGLE

GENERAL WIRING SCHEME FOR DALI


SECTION-"BB" RELEASED FOR PRELIMINARY TENDER INFORMATION APPROVAL CONSTRUCTION

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
16 15 14 13 12 11 10 9 8 7 6 5 4
This drawing is the property of L&T Construction, B&F-EDRC and must not be passed on to any person or body not authorised by
us to receive it nor be copied or otherwise made use either in full or in part by such person or body without our prior permission

M M

EPI-C-34-LMSDB
LOC : ELEC. ROOM - (C.E.34) EPI/E/28/DS3

UPS 230V 1A
230V AC I/P POWER SUPPLY
L UPS 230V 1A L
230V AC I/P POWER SUPPLY address:

___.______
address:

___.______
address:

___.______

L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12

KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway


Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

address: address: address: address: address: address:


address: address: address:

___.______ ___.______ ___.______

___.______ ___.______ ___.______ ___.______ ___.______ ___.______ L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12

KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway


Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12

K KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway K
Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

EPI/C/DS2 D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

INTERNAL VIEW FRONT VIEW


A9HFD456
EPI-C-34-LMSDB-1
2C OF 1.5 Sq.mm PVC INSULATED FRLS Cu.

J J

EPI/C/34/DALI ZONE-10
WIRE IN 20mm DIA MS/PVC CONDUIT

EPI/C/34/DALI ZONE-1

EPI/C/34/DALI ZONE-7

EPI/C/34/DALI ZONE-2

EPI/C/34/DALI ZONE-8

EPI/C/34/DALI ZONE-3

EPI/C/34/DALI ZONE-9

EPI/C/34/DALI ZONE-4

EPI/C/34/DALI ZONE-5

EPI/C/34/DALI ZONE-6
SPARE

SPARE
GENERAL ARRANGEMENT DRAWING

H H

NOTE:

FIELD DEVICES 1. FOR UPS POWER SOCKET REFER DRAWING NO: GHIAL-LNT-W-PTB-E-73-2020 TO
GHIAL-LNT-W-PTB-E-73-2023
G G
2. FOR DATA POINT REFER LATEST IT ENDPOINT DRAWING

3. FOR ELECTRICAL EQUIPMENT LAYOUT REFER DRAWING NO: GHIAL- LNT- W- PTB- E- 71- 2020
TO GHIAL- LNT- W- PTB- E- 71- 2023
EPI-C-36-LMSDB
4.FOR LIGHTING LAYOUT DALI LOOPING REFER DRAWING NO: GHIAL-LNT-D-PTB-E-72-2303
EPI/C/DS7 5.FOR LIGHTING LAYOUT REFER DRAWING NO: GHIAL- LNT- W- PTB- E- 72- 2020 TO

+ - + - + - + - + - + - 900X300mm LEVEL C CELING CUT OUT TO


E35 GHIAL- LNT- W- PTB- E- 72- 2023

DLS DLS DLS DLS 4KP 4KP RISE / DROP OF ELECTRICAL CABLE GI EARTH BUS S.NO. SYMBOL DESCRIPTION QTY
F F

EPI/C/DS3 EPI/C/DS4 EPI/C/DS5 EPI/C/DS6 EPI/C/34/KP1 EPI/C/34/KP2 1. 2P MCB

2P MCB --

2. iPRD40 2P
Surge Arrester

SURGE ARRESTER --

300
SE 3. POWER SUPPLY-1280mA --
150
SL 900
address:

___.______

L N PE MTN6725-0004

SH 6.
1/9

5/13
2/10

6/14
3/11

7/15
4/12

KNX DALI-Gateway
Basic REG-K/2/16/64

8/16 Man.
DALI MODULE 06

1205
D1+ D1- D2+ D2- KNX / PRG

200
LOGIC CONTROLLER --
CEILING SLAB 7.
E
600 L N

Input
100-240VAC
+ +

Output
24VDC 0.6A
- -

ABLM1A24004

POWER SUPPLY FOR LOGIC E


8. --
CONTROLLER
C-EMLDB-4
9. 4KP 4 FOLD KEYPAD 02

900
E E
N N
DALI TYPE-2 L DALI TYPE-2 L
Driver-3 D1
D2
Driver-4 D1
D2 10. DLS DAYLIGHT SENSOR 04

11.

SUB UPS SMALL POWER PANEL-1


KNX/EIB CABLE --

150
12. 3Rx1.5SQMM FRLS CU. WIRE --
DALI TYPE-2
E
N
DALI TYPE-2
E
N
C-NELDB-4 B
150X100mm CABLE TRAY

L L
Driver-2 D1
D2
Driver-5 D1
D2 13. 2C x 1.5 SQMM DALI CABLE --
D D

1170
14. CAT6 CABLE --

C-IT-UDB-4 FRONT B
X

E E
DALI TYPE-2 N
L DALI TYPE-2 N
L
LCS
Driver-1 D1 Driver-45 D1
D2 D2

150

6A
2
2Cx1.5SQ.MM.
FRLS Cable

C-NEPDB-4
address:

450
___.______

L N PE MTN6725-0004
EPI-C-34-LMSDB-1

900
C 1/9 2/10 3/11 4/12
E
N
L SOURCE FROM LDB(LIGHTING DB)
C-EPDB-4 C
KNX DALI-Gateway
ABS PAPR RMK SMS/VSN

4KP 4KP
E
150

Basic REG-K/2/16/64
N
L
0 ISSUED FOR APPROVAL
5/13 6/14 7/15 8/16 Man. ABS 19.07.2022 PAPR 20.07.2022 RMK 21.07.2022 SMS/VSN 22.07.2022
REV.NO. DESCRIPTION DESIGNED DRAWN CHECKED APPROVED
EPI-C-34-LMSDB-1

150
D1+ D1- D2+ D2- KNX / PRG
REVISIONS

955
ACS CHECKED BY SIGN DATE CHECKED BY SIGN DATE CHECKED BY SIGN DATE
5

C-ELDB-4 ELEC. ARCHITECTURE HVAC GIS


741

CIVIL & STRUCTURAL FPS GEOTECH


C.E.34 ELECTRICAL PIPING AIRPORT SYSTEMS

D' D'
2Cx1.5SQ.MM.

1170
FRLS Cable 2

6A
ELV SYSTEM PHE VHT
D2 D2
DALI TYPE-2 D1
DALI TYPE-2 D1
L L
Driver-1 N Driver-45 N

135
E E
B B
C-UDB-4 2

2
2
6A
436 CLIENT : GMR HYDERABAD CONCEPT:

DDC
ACS
6A 6A INTERNATIONAL AIRPORT LIMITED. Mechanical, Electrical, Civil, Structural, Geotechnical
PMS

150
D2 D2
PMS 150 PROJECT: O18151 - EXPANSION OF RAJIV GANDHI
INTERNATIONAL AIRPORT.
PROJECT Engineering Design and Research Center (EDRC),
CONSULTANT: L&T Construction - Buildings & Factories.
1200

DALI TYPE-2 D1
DALI TYPE-2 D1
L L
Driver-2 N Driver-5 N
E E SUPPLIER / CONTRACTOR : Larsen & Toubro Limited, Construction, Buildings & Factories
SECTION/
JOB No : O18151 TITLE: ELEVATION
NAME SIGN DATE EXPANSION OF RAJIV GANDHI INTERNATIONAL AIRPORT MARKING

DSGN ABS ABS 19.07.2022

D2 D2
268 600 DRWN PAPR PAPR 20.07.2022 EAST PIER - LEVEL C (BULB PORTION) DRAWING
NUMBER
DALI TYPE-2 D1
DALI TYPE-2 D1
21.07.2022
LIGHTING LMS DB SCHEMATIC DRAWING
L L CHKD RMK RMK SCALE
Driver-3 N Driver-4 N
As indicated
A E E
A

E35
APPD SMS/VSN SMS/VSN 22.07.2022

FLOOR SLAB DRAWING No. GHIAL-LNT-D-PTB-E-72-2302


PROJECTION SIZE REV

A0 0
SHEET: FIRST ANGLE

GENERAL WIRING SCHEME FOR DALI


SECTION-"CC" RELEASED FOR PRELIMINARY TENDER INFORMATION APPROVAL CONSTRUCTION

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
16 15 14 13 12 11 10 9 8 7 6 5 4
This drawing is the property of L&T Construction, B&F-EDRC and must not be passed on to any person or body not authorised by
us to receive it nor be copied or otherwise made use either in full or in part by such person or body without our prior permission

EPI-C-36-LMSDB
LOC : ELEC. ROOM (C.E.36)
M M

UPS 230V 1A
230V AC I/P POWER SUPPLY

address: address: address: address: address: address: address:


EPI/E/28/DS3
___.______ ___.______ ___.______ ___.______ ___.______ ___.______ ___.______

L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004

L 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 UPS 230V 1A L
230V AC I/P POWER SUPPLY
KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway
Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

EPI/C/DS6
address: address: address:

___.______ ___.______ ___.______

L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. KNX DALI-Gateway
Basic REG-K/2/16/64
KNX DALI-Gateway
Basic REG-K/2/16/64
KNX DALI-Gateway
Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

address: address: address:

___.______ ___.______ ___.______

L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12

KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway


Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG
2C OF 1.5 Sq.mm PVC INSULATED FRLS Cu.

K K

EPI/C/36/DALI ZONE-12
EPI/C/36/DALI ZONE-10

EPI/C/36/DALI ZONE-12
EPI/C/36/DALI ZONE-11

EPI/C/36/DALI ZONE-13
WIRE IN 20mm DIA MS/PVC CONDUIT

EPI/C/36/DALI ZONE-1

EPI/C/36/DALI ZONE-8

EPI/C/36/DALI ZONE-2

EPI/C/36/DALI ZONE-9

EPI/C/36/DALI ZONE-3

EPI/C/36/DALI ZONE-4

EPI/C/36/DALI ZONE-5

EPI/C/36/DALI ZONE-6

EPI/C/36/DALI ZONE-7
INTERNAL VIEW FRONT VIEW
A9HFD456
address: address: address: address: address: EPI-C-34-LMSDB-1
J ___.______ ___.______ ___.______ ___.______ ___.______
J

L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004 L N PE MTN6725-0004

1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12 1/9 2/10 3/11 4/12
GENERAL ARRANGEMENT DRAWING
KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway KNX DALI-Gateway
Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64 Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man. 5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG D1+ D1- D2+ D2- KNX / PRG

H H
FRLS Cu. WIRE IN 20mm DIA MS/PVC

EPI/C/36/DALI ZONE-18

EPI/C/36/DALI ZONE-17

EPI/C/36/DALI ZONE-16

EPI/C/36/DALI ZONE-14
EPI/C/36/DALI ZONE-15
2C OF 1.5 Sq.mm PVC INSULATED

EPI/C/36/DALI ZONE-20

EPI/C/36/DALI ZONE-19
SPARE

SPARE

SPARE
NOTE:
CONDUIT

1. FOR UPS POWER SOCKET REFER DRAWING NO: GHIAL-LNT-W-PTB-E-73-2020 TO


GHIAL-LNT-W-PTB-E-73-2023
G G
2. FOR DATA POINT REFER LATEST IT ENDPOINT DRAWING
FIELD DEVICES 3. FOR ELECTRICAL EQUIPMENT LAYOUT REFER DRAWING NO: GHIAL- LNT- W- PTB- E- 71- 2020
TO GHIAL- LNT- W- PTB- E- 71- 2023

4.FOR LIGHTING LAYOUT DALI LOOPING REFER DRAWING NO: GHIAL-LNT-D-PTB-E-72-2303


FROM EPI/C/DS2 5.FOR LIGHTING LAYOUT REFER DRAWING NO: GHIAL- LNT- W- PTB- E- 72- 2020 TO
GHIAL- LNT- W- PTB- E- 72- 2023

S.NO. SYMBOL DESCRIPTION QTY


F F
+ - + - + - + - + - + - + - 1.
2P MCB

2P MCB --
DLS DLS DLS DLS DLS 4KP 4KP
2. iPRD40 2P
Surge Arrester

SURGE ARRESTER --
EPI/C/DS7 EPI/C/DS8 EPI/C/DS9 EPI/C/DS10 EPI/C/DS11 EPI/C/36/KP1 EPI/C/36/KP2

3. POWER SUPPLY-1280mA --
address:

___.______

L N PE MTN6725-0004

1/9 2/10 3/11 4/12

DALI MODULE 12
6.
KNX DALI-Gateway
Basic REG-K/2/16/64

5/13 6/14 7/15 8/16 Man.

D1+ D1- D2+ D2- KNX / PRG

7. LOGIC CONTROLLER --
CEILING SLAB
E L N + + - -

E
POWER SUPPLY FOR LOGIC
Input Output
100-240VAC 24VDC 0.6A
ABLM1A24004

8. --
CONTROLLER

DALI TYPE-2
E
N
DALI TYPE-2
E
N
PMS
E34 C-IT UDB - S C-IT UDB - W
9. 4KP 4 FOLD KEYPAD 02
Driver-3
L
D1 Driver-4
L
D1
PMS PMS PMS
D2 D2
10. DLS DAYLIGHT SENSOR 05

11. KNX/EIB CABLE --


150

150
150

6/1
6A
E E 600 300 600 300 600 300 600 900 150 900 12. 3Rx1.5SQMM FRLS CU. WIRE --

E
N N
GE
DALI TYPE-2 DALI TYPE-2
1030

L L
N
Driver-2 Driver-5

880
876

D1 D1
1080

D2 D2

D 13. 2C x 1.5 SQMM DALI CABLE -- D


150X100mm Cable tray

14. CAT6 CABLE --


SUB NORMAL MODE

650
2

CS SUB EMERGENCY
CS

6A
450

E E
DALI TYPE-2 N
DALI TYPE-2 N
VENTILATION FAN PANEL-2
X

Driver-1
L
D1 Driver-45
L
D1 LIGHTING PANEL
D2 D2

0
T
ACS

ON
220
2
2Cx1.5SQ.MM.

6A
FR
FRLS Cable
FRONT FRONT
2D SUB TENANT PANEL-2
address:

___.______
1010 2200 200 3600 ACS
L N PE MTN6725-0004
ELEC.
2000

2000

2000

C 1/9 2/10 3/11 4/12


E
N
C.E.36 C
L SOURCE FROM LDB(LIGHTING DB)
150

KNX DALI-Gateway
Basic REG-K/2/16/64
E ABS PAPR RMK SMS/VSN
N
0 ISSUED FOR APPROVAL
5/13 6/14 7/15 8/16 Man.
L
1360 2900 200 3600 ABS 19.07.2022 PAPR 20.07.2022 RMK 21.07.2022 SMS/VSN 22.07.2022

67 450
EPI-C-36-LMSDB-1

EPI-C-36-LMSDB-2

FRONT REV.NO. DESCRIPTION DESIGNED DRAWN CHECKED APPROVED


D1+ D1- D2+ D2- KNX / PRG FRONT 10
REVISIONS
CHECKED BY SIGN DATE CHECKED BY SIGN DATE CHECKED BY SIGN DATE
5

ARCHITECTURE HVAC GIS


741

SUB ESSENTIAL LTG & POWER


450

650

CIVIL & STRUCTURAL FPS GEOTECH


4KP 4KP

PANEL-1
SUB IT OUTGOING PANEL ELECTRICAL PIPING AIRPORT SYSTEMS
2Cx1.5SQ.MM.
LCS
2

FRLS Cable
ELV SYSTEM PHE VHT
646

646

200
2
ACS

6A
6A

D2 D2
DALI TYPE-2
Driver-1
D1
L
DALI TYPE-2
Driver-45
D1
L
D
N N
2
2956A

E E
B B
1696

1496
1200

PMS
CLIENT : GMR HYDERABAD CONCEPT:
436 436 PMS D INTERNATIONAL AIRPORT LIMITED.
800
600

Mechanical, Electrical, Civil, Structural, Geotechnical

1200 1170 200 1170 200 900 200 900 797 PROJECT: O18151 - EXPANSION OF RAJIV GANDHI PROJECT Engineering Design and Research Center (EDRC),
D2 D2
DALI TYPE-2 D1
DALI TYPE-2 D1 INTERNATIONAL AIRPORT. CONSULTANT: L&T Construction - Buildings & Factories.
Driver-2 L
Driver-5 L
150
150

150

N N
E E SUPPLIER / CONTRACTOR : Larsen & Toubro Limited, Construction, Buildings & Factories
577

SECTION/
JOB No : O18151 TITLE: ELEVATION
NAME SIGN DATE EXPANSION OF RAJIV GANDHI INTERNATIONAL AIRPORT MARKING

DSGN ABS ABS 19.07.2022

C-EPDB-5 DRWN PAPR PAPR 20.07.2022 EAST PIER - LEVEL C (BULB PORTION) DRAWING
D2 D2 EARTH BUS C-NELDB-5 C-NEPDB-5 NUMBER
DALI TYPE-2 D1
DALI TYPE-2 D1 LIGHTING LMS DB SCHEMATIC DRAWING
C-ELDB-5 CHKD RMK RMK 21.07.2022 SCALE
E34
L L
Driver-3 N Driver-4 N
C-IT-UDB-5 C-UDB-5 As indicated
A E E
APPD SMS/VSN SMS/VSN 22.07.2022 A
C-EMLDB-5 PROJECTION SIZE REV

FLOOR SLAB DRAWING No. GHIAL-LNT-D-PTB-E-72-2302 A0 0


SHEET: FIRST ANGLE

GENERAL WIRING SCHEME FOR DALI


SECTION-"DD" RELEASED FOR PRELIMINARY TENDER INFORMATION APPROVAL CONSTRUCTION

16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1