You are on page 1of 3

GUARANTEED TECHNICAL PARTICULAR

Customer : HPCL
Project : HPCL-LPG CAVERN AT MANGLORE LPG IMPORT FACILITY
Ref No. : SEPL/KM/HPCL/GTP/23-24/9092
Manufacturer : Suyog Electricals Ltd. Rev.03.Dt.24.07.2023
SR
Description Unit 1Pair x 1.5mm2 2Pair x 1.5mm2 3Pair x 1.5mm2 4Pair x 1.5mm2
No.
1 MAKE SEPL
2 Type of Cables(size) 1P x 1.5mm2 2P x 1.5mm2 3P x 1.5mm2 4P x 1.5mm2
3 No of Element P 1P 2P 3P 4P
4 Voltage Grade V 650/1100 V
5 Screening Type Overall Screening Individual & Overall Screening
6 Conductor Material Annealed Stranded Bare Copper as per IS :8130
7 Insulation material Extruded XLPE As per IS : 7098 P1
8 Pair Identification Black & Blue Black & Blue with number identification on Tape or Insulation
9 Insulation Thickness (Nominal) mm 0.6
10 No of twist/mtr twst/mtr Min 10
11 a) Al. Myler Thickness - Individual shield mm NA 0.05
b) Al. Myler Thickness - Overall shield mm 0.05 0.075
12 Drain Wire mm2 ATC - 0.5mm2
13 Communication Pair NA Provided (Green & Red)
14 Rip Cord Provided
15 INNER SHEATH
a) Material Extruded FR PVC TYPE ST-2 as per IS:5831
b) Thickness of sheath (min) mm 0.3
c) Colour Black
d) Dia over inner sheath (+/- 2mm) mm 7.1 12 12.8 13.9
16 ARMOUR
a) Material G.S Round Wire G.S Flat Strip
b) Armour Size (Nominal) mm 1.4 4.0 x 0.8
c) Dia over armour (+/- 2mm) mm 9.8 14.7 15.6 15.5
17 OUTER SHEATH
a) Material Extruded FRLS PVC TYPE ST-2 as per IS:5831
b) Thickness (min) mm 1.24 1.4
c) Colour Black
d) Tolerance on Overall Diameter (+/-2mm)
e) Overall dia of cable (+/-2mm) mm 12.6 17.5 18.7 18.6
f) Net weight of cable (Approx) kg/km 282 540 600 570
18 FRLS PROPERTIES
a) Oxygen Index(test as per ASTM-D2863) % 29% (min)
b) Temperature Index Test ( ASTM-D2863) Deg. C. 250 Deg.C (min)
c) Smoke Density(test as per ASTM-D2843) % 60% (max) SDAR
d) Acid gas emission(test as per IEC-754(I)) % 20% (max)
19 ELECTRICAL PARAMETERS
1 High Voltage test
Between Conductor 2 KV - AC / 1 Minute
Bet,Core & Screen 1 KV - AC / 1 Minute
2 Resistance Test at 20 'C
Conductor Ω/km 12.3 Max
Drain wire Ω/km 30 Max
3 Mutual Capacitance core to core at 1kHz pF/mtr 100 (max)
4 Capacitance Pair to Screen pF/mtr 400 (max)
5 L/R Ratio µH/Ω 40 (max)
6 Insulation resistance MΩ/km 1000 (min)
20 Marking on cable (Printing) SEPL 650/1100V Instrumentation Cable FRLS , Cable Size , Year , Seq Mark
21 Standard Drum Length mtr 500/1000 mtr/PO Qty (± 3%)
NOTE :-
1 The Data specified above are based on IS specification and in case of any dispute or typographical error,
interpretation of IS specification shall prevail.
2 The conductor diameter are indicative and shall confirm to meet the IS requirements of conductor resistance
3 The packing drum dimension and weight are approximate and may vary.
4 Non standard length shall be limited to 10% of the ordered quantity.
GUARANTEED TECHNICAL PARTICULAR

Customer : HPCL
Project : HPCL-LPG CAVERN AT MANGLORE LPG IMPORT FACILITY
Ref No. : SEPL/KM/HPCL/GTP/2023/9092
Manufacturer : Suyog Electricals Ltd. Rev.03.Dt.24.07.2023
SR
Description Unit 6Pair x 1.5mm2 7Pair x 1.5mm2 10Pair x 1.5mm2 12Pair x 1.5mm2 24Pair x 1.5mm2
No.
1 MAKE SEPL
2 Type of Cables(size) 6P x 1.5mm2 7P x 1.5mm2 10P x 1.5mm2 12P x 1.5mm2 24P x 1.5mm2
3 No of Element P 6P 7P 10P 12P 24P
4 Voltage Grade V 650/1100 V
5 Screening Type Individual & Overall Screening
6 Conductor Material Annealed Stranded Bare Copper as per IS :8130
7 Insulation material Extruded XLPE As per IS : 7098 P1
8 Pair Identification Black & Blue with number identification on Tape or Insulation
9 Insulation Thickness (Nominal) mm 0.6
10 No of twist/mtr twst/mtr Min 10
11 a) Al. Myler Thickness - Individual shield mm 0.05
b) Al. Myler Thickness - Overall shield mm 0.075
12 Drain Wire mm2 ATC - 0.5mm2
13 Communication Pair Provided (Green & Red)
14 Rip Cord Provided
15 INNER SHEATH
a) Material Extruded FR PVC TYPE ST-2 as per IS:5831
b) Thickness of sheath (min) mm 0.3
c) Colour Black
d) Dia over inner sheath (+/- 2mm) mm 17.1 17.6 20.3 21.4 28.9
16 ARMOUR
a) Material G.S Flat Strip
b) Armour Size (Nominal) mm 4.0 x 0.8
c) Dia over armour (+/- 2mm) mm 18.7 19.2 21.9 24 31.4
17 OUTER SHEATH
a) Material Extruded FRLS PVC TYPE ST-2 as per IS:5831
b) Thickness (min) mm 1.4 1.56
c) Colour Black
d) Tolerance on Overall Diameter (+/-2mm)
e) Overall dia of cable (+/-2mm) mm 21.8 22.3 25 27.1 34.9
f) Net weight of cable (Approx) kg/km 780 820 1045 1140 1880
18 FRLS PROPERTIES
a) Oxygen Index(test as per ASTM-D2863) % 29% (min)
b) Temperature Index Test ( ASTM-D2863) Deg. C. 250 Deg.C (min)
c) Smoke Density(test as per ASTM-D2843) % 60% (max) SDAR
d) Acid gas emission(test as per IEC-754(I)) % 20% (max)
19 ELECTRICAL PARAMETERS
1 High Voltage test
Between Conductor 2 KV - AC / 1 Minute
Bet,Core & Screen 1 KV - AC / 1 Minute
2 Resistance Test at 20 'C
Conductor Ω/km 12.3Max
Drain wire Ω/km 30 Max
3 Mutual Capacitance core to core at 1kHz pF/mtr 100 (max)
4 Capacitance Pair to Screen pF/mtr 400 (max)
5 L/R Ratio µH/Ω 40 (max)
6 Insulation resistance MΩ/km 1000 (min)
20 Marking on cable(Printing) SEPL 650/1100V Instrumentation Cable FRLS , Cable Size , Year , Seq Mark
21 Standard Drum Length mtr 500/1000 mtr/PO Qty (± 3%)
NOTE :-
1 The Data specified above are based on IS specification and in case of any dispute or typographical error,
interpretation of IS specification shall prevail.
2 The conductor diameter are indicative and shall confirm to meet the IS requirements of conductor resistance
3 The packing drum dimension and weight are approximate and may vary.
4 Non standard length shall be limited to 10% of the ordered quantity.
GUARANTEED TECHNICAL PARTICULAR

Customer : HPCL
Project : HPCL-LPG CAVERN AT MANGLORE LPG IMPORT FACILITY
Ref No. : SEPL/KM/HPCL/GTP/2023/9092
Manufacturer : Suyog Electricals Ltd. Rev.03.Dt.24.07.2023
SR
Description Unit 1Triad x 1.5mm2
No.
1 MAKE SEPL
2 Type of Cables(size) 1T x 1.5mm2
3 No of Element P 1T
4 Voltage Grade V 650/1100 V
5 Screening Type Overall Screening
6 Conductor Material Annealed Stranded Bare Copper as per IS :8130
7 Insulation material Extruded XLPE As per IS : 7098 P1
8 Pair Identification Blue , Black & Brown
9 Insulation Thickness (Nominal) mm 0.6
10 No of twist/mtr twst/mtr Min 10
11 a) Al. Myler Thickness - Individual shield mm NA
b) Al. Myler Thickness - Overall shield mm 0.05
12 Drain Wire mm2 ATC - 0.5mm2
13 Rip Cord Provided
14 INNER SHEATH
a) Material Extruded FR PVC TYPE ST-2 as per IS:5831
b) Thickness of sheath (min) mm 0.3
c) Colour Black
d) Dia over inner sheath (+/- 2mm) mm 8.2
15 ARMOUR
a) Material G.S Round Wire
b) Armour Size (Nominal) mm 1.4
c) Dia over armour (+/- 2mm) mm 10.9
16 OUTER SHEATH
a) Material Extruded FRLS PVC TYPE ST-2 as per IS:5831
b) Thickness (min) mm 1.24
c) Colour Black
d) Tolerance on Overall Diameter (+/-2mm)
e) Overall dia of cable (+/-2mm) mm 13.7
f) Net weight of cable (Approx) kg/km 367
17 FRLS PROPERTIES
a) Oxygen Index(test as per ASTM-D2863) % 29% (min)
b) Temperature Index Test ( ASTM-D2863) Deg. C. 250 Deg.C (min)
c) Smoke Density(test as per ASTM-D2843) % 60% (max) SDAR
d) Acid gas emission(test as per IEC-754(I)) % 20% (max)
18 ELECTRICAL PARAMETERS
1 High Voltage test
Between Conductor 2 KV - AC / 1 Minute
Bet,Core & Screen 1 KV - AC / 1 Minute
2 Resistance Test at 20 'C
Conductor Ω/km 12.3 Max
Drain wire Ω/km 30 Max
3 Mutual Capacitance core to core at 1kHz pF/mtr 100 (max)
4 Capacitance Pair to Screen pF/mtr 400 (max)
5 L/R Ratio µH/Ω 40 (max)
6 Insulation resistance MΩ/km 1000 (min)
19 Marking on cable (Printing) SEPL 650/1100V Instrumentation Cable FRLS , Cable Size , Year , Seq Mark
20 Standard Drum Length mtr 500/1000 mtr/PO Qty (± 3%)
NOTE :-
1 The Data specified above are based on IS specification and in case of any dispute or typographical error,
interpretation of IS specification shall prevail.
2 The conductor diameter are indicative and shall confirm to meet the IS requirements of conductor resistance
3 The packing drum dimension and weight are approximate and may vary.
4 Non standard length shall be limited to 10% of the ordered quantity.

You might also like