Professional Documents
Culture Documents
Extruder control
MacromateXX professional S7
Siemens Panel PC Touch
1 General information............................................................................................ 4
2 System hardware description ............................................................................ 5
3 Screen layout ...................................................................................................... 6
4 Functions ............................................................................................................ 7
5 ON/OFF buttons .................................................................................................. 8
6 Screen selection buttons ................................................................................. 11
7 Password protection ........................................................................................ 12
8 Operation / Screens .......................................................................................... 13
8.1 Overview (Screen 10) ............................................................................................16
8.2 Report-Screen ........................................................................................................17
8.3 Analog values display (Screen 11) .......................................................................18
8.4 Alarm screens ........................................................................................................19
8.4.1 Currently active alarms (Screen 20) ............................................................................ 19
8.4.2 Alarm history (Screen 21) ............................................................................................. 20
8.5 Temperature control ..............................................................................................21
8.5.1 Temperature controllers 1 – 16 (Screen 30) ................................................................ 21
8.5.2 Temperature limits (Screen 32) .................................................................................... 22
8.5.3 Automatic heat up (Screen 33) ..................................................................................... 23
8.5.4 Screen saver (Screen 34) .............................................................................................. 24
8.6 Charts (Screens 60…66) .......................................................................................25
8.6.1 Chart 1 (Screen 60) ........................................................................................................ 26
8.6.2 Chart 2 (Screen 61) ........................................................................................................ 26
8.6.3 Chart 3 (Screen 62) ........................................................................................................ 26
8.6.4 Chart 4 (Screen 63) ........................................................................................................ 26
8.6.5 Chart 5 (Screen 64) ........................................................................................................ 27
8.6.6 Chart 6 (Screen 65) ........................................................................................................ 27
8.6.7 Chart 6 (Screen 66) ........................................................................................................ 27
8.7 Limits for analog inputs (Screen 67) ....................................................................28
8.8 Melt pressure /melt temperature limits (Screen 68) ............................................29
8.9 Recipes User data (Screen70) ..............................................................................30
8.10 Process data logging (Screen 71) ........................................................................35
8.10.1 Temperature logging selection (Screen 72) ................................................................ 37
8.10.2 Process data logging selection (Screen 73) ............................................................... 38
8.11 Start automatic ......................................................................................................39
8.11.1 Start automatic analog values (Screen 80) ................................................................. 39
8.11.2 Start automatic feeders (Screen 81) ............................................................................ 41
8.11.3 Stop automatic (Screen 82) .......................................................................................... 42
8.12 Option – Brabender RC4, LM3 odder OP5 feeders ..............................................43
8.12.1 Brabender Feeder Status (Screen 40).......................................................................... 43
8.12.2 Brabender Feeder configuration (Screen 41) ............................................................. 45
8.13 Option – Brabender OP1 feeder (Screen 47)........................................................47
8.14 Option – K-Tron Feeders .......................................................................................48
8.14.1 K-Tron Feeder status (Screen 42) ................................................................................ 48
8.14.2 K-Tron Feeder configuration (Screen 43) .................................................................... 50
8.15 Option – Colortronic / Scholz feeders ..................................................................52
8.15.1 Colortronic Feeder Status (Screen 44) ........................................................................ 52
Edition 02/2012 for SW Version 10.1
Doku_MacromateXX_professional_S7_english_10_1.doc Page 2 of 98
8.15.2 Colortronic/Scholz Feeder configuration 1 (Screen 45 ) ........................................... 54
8.15.3 Colortronic / Scholz Feeder configuration 2 (Screen 46) .......................................... 56
8.16 -Option- Underwater pelletizer ..............................................................................58
8.16.1 Underwater pelletizing operator (UWP) (Screen 90) ................................................. 58
8.16.2 Underwater pelletizing (UWP) technician (Screen 91) ............................................... 61
8.17 -Option- Melt pump ................................................................................................63
8.17.1 Melt pump (Screen 94) .................................................................................................. 63
8.17.2 Melt pump Parameter (Screen 95) ................................................................................ 65
8.18 -Option- Roving-monitoring (Screen 97) .............. Fehler! Textmarke nicht definiert.
8.19 Technician configuration (Screen 100) ................................................................67
8.19.1 Machine configuration (Screen 110) ............................................................................ 68
8.19.2 Button positions (Screen 111) ...................................................................................... 69
8.19.3 Maintenance list (Screen 112) ...................................................................................... 70
8.19.4 Positions analog displays (Screen 113) ...................................................................... 71
8.19.5 Control parameters (Screen 120) ................................................................................. 72
8.19.6 Heating optimisation 1 – 8 / 9 – 16 (Screen 122 / 123 ) ............................................. 75
8.19.7 Heat current monitoring (Screen 121) ......................................................................... 77
8.19.8 Scaling analog outputs (Screen 130) ........................................................................... 78
8.19.9 Scaling analog inputs (Screen 131) ............................................................................. 79
8.19.10 Scaling analog inputs MT/MD (Screen 132) ................................................................ 80
8.19.11 PLC (Screen 140) ........................................................................................................... 81
8.19.12 PLC Diagnosis (Screen 141) ......................................................................................... 82
8.19.13 - Option- Diverter valve operation (Screen 145) ......................................................... 83
8.19.14 User administration (Screen 150) ................................................................................. 84
8.19.15 System settings (Screen 151) ....................................................................................... 86
8.19.16 Machine settings (Screen 152) ..................................................................................... 87
9 Alarm display and operation ........................................................................... 88
9.1 Alarm list ................................................................................................................89
The instructions given in this manual cannot replace sufficient technical understanding.
Never open the controller and touch electronic components while energised.
Work on electronic components may only be conducted by specially trained experts.
Never use petrol, thinner or cleaner containing solvents to clean the controller. Only clean the
operating unit with a neutral cleaner and a soft cloth.
Do not press the keys of the touch-screen with a pointy object (biro, pencil).
Keep the USB-socket closed to provide dust inlet
Switching on
To boot the control the main switch must be on and all emergency-stop buttons must be released.
The Windows operating system and the HMI-Runtime application program on the operating unit are
started automatically. (That may take ca. 3 minutes)
This schematic description not necessarily consists in reality of these displayed units.
Operation panel
Siemens Panel PC
Profibus DP
Feeder
controller
converter
8-chanel
Temp.controller KS 800
S7-300 ET200s
I/O-Unit
Permanent area
Screen content
Touch buttons
Permanent area The content of the permanent area is similar on all screen pages. Up to 8 actual
values can be displayed numerically and by a bar chart. Configuration of this is
performed on Technicians screen 131 and 132.
If there is no connection to the control unit (S7-PLC) the upper right dot does not
blink green and grey. So there is no operation possible.
Screen content The screen content pane is screen specific, so it is different on all the screens.
Screen cleaning
To clean the screen manually during operation to avoid any operation this
button calls a clean-screen.
Log-in/off
(incl. Display of the current level)
If a user is logged in this button leads to log-of (level 0)
Calculator
Launches the Windows-calculator
Hardcopy
The current screen will be saved as a graphic file
The setting at the “Hardcopy-program” is the second USB interface.
Attention: To save the screen, press the button two times!
Report-Screen
Report of current actual values and setpoints
A hardcopy file can be stored on USB-stick
The frame and inner filling display the status of the specific unit.
Heating/ Cooling
Heating OFF
Pelletizer ON/OFF
Login screen:
No access to the system without password
Password entry
The structure of the sections and screen selection are illustrated in the table below.
Alarms
21 Alarm history
Overview
10 Overview
Temperature control
30 Temperature controllers 1 – 16
31 Temperature controllers 17 – 32
32 Temperature limits
33 Automatic heat up
34 Screen saver
Feeders
40 Feeder status
41 Feeder configuration
60 Chart 1
61 Chart 2
62 Chart 3
63 Chart 4
64 Chart 5
65 Chart 6
66 Chart 7
Start automatic
Technician configuration
gravimetric
feeders
acknowledge alarm,
Status: quit alarm
K = alarm occurred
G = alarm gone
Q = alarm acknowledged
Status:
K = alarm occurred
G = alarm gone
Q = alarm acknowledged
heating active
Cooling active
Set Setpoints
The set temperatures are entered in °C. The individual heat zones are heated up to
these specified values when the heating is switched on.
Copies Setpoint 1 to all other zones
Act. The actual temperatures are current temperatures of the individual heat zones
Output The output is a measure in percent for the heating capacity of the heat zones. When a
zone is initially heated up, this measure is 100 %. As the actual value approaches the
setpoint, the switch-on time decreases in order to optimally reach the selected setpoint. A
positive output indicates that the zone is being heated. A negative output is indicative of
the zone being cooled.
The individual heat zones can be switched on or off with the I/O pre-selection. The set or
decrease temperatures and the limits are not taken into account for switched-off zones.
Limit entry
On this screen the upper and lower temperature value limits for the heat can be entered. The tempera-
ture differences of the heat zones are displayed as numerical values and as bar graphs. With the pre-
selection Alarm I/O the limit-value fault messages of the individual heat zones can be switched on and
off.
The temperature limit values are relative values used for limit value monitoring of the respective heat
zone. A tolerance range can be set for each heat zone. The violation of the tolerance range triggers an
alarm.
Example: Set temp. = 200 °C
+ Alarm Max. = 15 °K
- Alarm Min. = -20 °K
|
215 °C |------------------------- + Alarm Max.
| +15 °K
200 °C |------------------------- Setpoint
| -20 °K
180 °C |------------------------- - Alarm Min.
|
Violation of the tolerance range triggers an alarm. When the temperature lies within the tolerances again
the fault message disappears.
If a setpoint or decrease value is changed, the tolerances are automatically adapted taking the limit value
into account. While the system heats up, all heat zones must reach the lower minimum alarm limit before
the main motor can be started.
Activate each desired day of week by button I/0: green background means activated status
The copy-button enables to copy the start time of Monday to all other days
This page avoids operation of the machine while the PC is on (password protection)
Selection of
other trends
The scaling of the value-axis can be set as desired from –999 to 9999.
Shortcut Value
n Ext Actual speed of extruder screw
M Ext Actual load of the extruder
MD 1 Melt pressure 1
MT Melt temperature
Dos Total throughput feeder line
Vacu Vacuum pressure
SB 1 Feed rate/speed of side feeder 1
SB 2 Feed rate/speed of side feeder 2
Shortcut Value
Dos 1 Throughput feeder 1
Dos 2 Throughput feeder 2 (if available)
Dos 3 Throughput feeder 3 (if available)
Dos 4 Throughput feeder 4 (if available)
Dos 5 Throughput feeder 5 (if available)
Dos 6 Throughput feeder 6 (if available)
Dos 7 Throughput feeder 7 (if available)
Dos 8 Throughput feeder 8 (if available)
Shortcut Value
HZ 1 Actual temperature of Heat Zone 1
HZ 2 Actual temperature of Heat Zone 2
HZ 3 Actual temperature of Heat Zone 3
Dos 4 Actual temperature of Heat Zone 4
HZ 5 Actual temperature of Heat Zone 5
HZ 6 Actual temperature of Heat Zone 6
HZ 7 Actual temperature of Heat Zone 7
HZ 8 Actual temperature of Heat Zone 8
Shortcut Value
HZ 9 Actual temperature of Heat Zone 9
HZ 10 Actual temperature of Heat Zone 10
HZ 11 Actual temperature of Heat Zone 11
HZ 12 Actual temperature of Heat Zone 12
HZ 13 Actual temperature of Heat Zone 13
HZ 14 Actual temperature of Heat Zone 14
HZ 15 Actual temperature of Heat Zone 15
HZ 16 Actual temperature of Heat Zone 16
Shortcut Value
HZ 17 Actual temperature of Heat Zone 17
HZ 18 Actual temperature of Heat Zone 18
HZ 19 Actual temperature of Heat Zone 19
HZ 20 Actual temperature of Heat Zone 20
HZ 21 Actual temperature of Heat Zone 21
HZ 22 Actual temperature of Heat Zone 22
HZ 23 Actual temperature of Heat Zone 23
HZ 24 Actual temperature of Heat Zone 24
Shortcut Value
HZ 25 Actual temperature of Heat Zone 25
HZ 26 Actual temperature of Heat Zone 26
HZ 27 Actual temperature of Heat Zone 27
HZ 28 Actual temperature of Heat Zone 28
HZ 29 Actual temperature of Heat Zone 29
HZ 30 Actual temperature of Heat Zone 30
HZ 31 Actual temperature of Heat Zone 31
HZ 32 Actual temperature of Heat Zone 32
Shortcut Value
n Gran Speed pelletizer
M Gran Load pelletizer
P AnfW Melt pressure diverter valve
MT Melt pressure 1
T AnfW Temperature diverter valve
T LP Temperature plate
T Tank Temperature water tank
T Rohr Temperature water pipe
This screen contains all important analog limit values used for system monitoring and protection.
These parameters are only to be entered by the authorised personnel with the corresponding care.
An upper and a lower limit value can be defined for each measured value. The corresponding alarms are
switched on or off with the pre-selection I/O.
This screen contains melt pressure and melt temperature values to be configured. These parameters are
only to be entered by the authorised personnel with the corresponding care.
Recipe handling:
The current control data are read from the controller to the visualization
system
The current control data are read from the controller to the visualization sys-
tem
Message
Message
Important:
All recipes are always transferred from the internal memory to the USB-Stick or vice versa. This
means that the above transfer actions overwrite recipes of the same name without asking for confir-
mation. This problem can be remedied by using different USB-Sticks (exactly dated backup cop-
ies).
One file can store 50 000 values. Once a file reached 200MB, the system creates a new one automat-
ically. A total of 40 files can be created.
These files are stored at USB at E:\Arch\...
The archive files start with the name Archiv0.csv, Archiv1.csv, Archiv2.csv, ..., Archiv40.csv.
If there are created more than 40 files the system will continue to overwrite the oldest files beginning
with the file Archiv0.csv.
The files are .csv formatted, so it is possible to open and handle them with e.g. MS Excel
Copy all logging files Archiv0.csv to Archiv40.csv to the second USB-stick (F:\)
activated no logging
logging
activated no logging
logging
Example:
Step
after 6 s start
with 400 U/min
“Hold times” and “total throughput in kg/h” belong to the previous screen “Start automatic analog val-
ues“.
Feeders are not switched off, even there is in the upper row a „O“ setting
Pressing this button initiates the stop automatic to switch off all devices automatically.
Drives interlocked: Feeders are able to run only with running extruder
According to the projected number of feeders the data lines are displayed.
Status
grey: feeder off, green: feeder on
Total setpoint Group-Mode: Display and entry of the total throughput setpoint of all feeders
in kg/h.
Single-Mode: Display of the total throughput setpoint of all feeders in kg/h.
Total actual value Display of the actual total throughput of all feeders in kg/h.
Bulk densi- Entry of product weight in kg/l to calculate the fill level.
ty kg/l Entry is only possible at stopped feeder.
Check max.
Maximum output in kg/h :
output kg/h
Entry is only possible in turned off mode of each feeder. (blue displayed values)
Level min. Fill level, which enables the controller to switch from feeder mode to refill mode.
% Entry in %, related to the useable weight range.
Level max. Fill level, which enables the controller to switch from refill mode to stabilization time.
% Entry in %, related to the useable weight range.
All configuration data of that screen will be written (transferred) to the feeder controller.
Push button "write values" to write these data to the feeder controller!
MAN: Reaching the minimum level an alarm appears to do a manual refill at the specif-
ic feeder hopper.
Selection:
grey: only alarm message
red: cut off
Characters a – m:
Correlation to possible alarms
If the selected feeder is off, all others are not able to run
To enable the communication via Profibus to the PLC following settings has to be done at the feeder
controller:
Host comp operation
Host computer Parameter
Throughput Act
Actual Throughput
Drives interlocked: Feeders are able to run only with running extruder
According to the projected number of feeders the data lines are displayed.
Status
grey: feeder off, green: feeder on
Total setpoint Group-Mode: Display and entry of the total throughput setpoint of all feeders
in kg/h.
Single-Mode: Display of the total throughput setpoint of all feeders in kg/h.
Total actual value Display of the actual total throughput of all feeders in kg/h.
Name
Name entry (max 12 characters)
The initial value must be adapted to the mean value in order to regulate the meter-
Feed factor Ini-
ing unit after switching on in order to ensure that it settles at the desired set value.
tial kg/h
Calibration
Cal
Starts determining maximum output.
Hopper weight
Actual hopper weight
kg
Level min. Fill level, which enables the controller to switch from feeder mode to refill mode.
kg Entry in kg
MAN: Reaching the minimum level an alarm appears to do a manual refill at the
specific feeder hopper.
Selection:
grey: only alarm message
red: cut off
Characters a – m:
Correlation to possible alarms
If the selected feeder is off, all others are not able to run.
Drives interlocked: Feeders are able to run only with running extruder
Status
grey: feeder off, green: feeder on
Total setpoint Group-Mode: Display and entry of the total throughput setpoint of all feeders
in kg/h.
Single-Mode: Display of the total throughput setpoint of all feeders in kg/h.
Total actual value Display of the actual total throughput of all feeders in kg/h.
Calibration
Cal
Starts determining maximum output.
Hopper weight
Actual hopper weight
kg
Level min. Fill level, which enables the controller to switch from feeder mode to refill mode.
kg Entry in kg
Level max. Fill level, which enables the controller to switch from refill mode to gravimetric
kg mode. Entry in kg
MAN: Reaching the minimum level an alarm appears to do a manual refill at the
specific feeder hopper.
Within active communication to the feeder controller these values overwrite automatically always the
values at the feeder controller. So, these values needs to be entered only at the Panel PC
All other parameters are only available and accessible at the feeder controller
Selection:
grey: only alarm message
red: cut off
Characters a – k:
Correlation to possible alarms
If the selected feeder is off, all others are not able to run.
ON-/OFF-Status
Status
Status Pelletizer:
dismounted
mounted
Operation of the UWP system by buttons:
Pelletizer
Pre-automatic / automatic
Pushing the button „Pelletizer“ or time delayed, Mode “blade adjustment” run-
blade adjustment will end ning
3. Operation production:
Button Condition, status, operation Status text
Start diverter valve (automatic) Start delay time position change diverter valve
In "AUTO mode" the pressure is controlled by varying the melt pump speed with a pressure setpoint
entry in bar.
Chart display:
MP1 : act. mass pressure 1
MP2 : act. mass pressure 2
MP3 : act. mass pressure 3
P diff : act. differential pressure
M: act. load of melt pump motor
n: act. speed of melt pump
Q: act. gravimetric throughput in kg/h
Output melt
In AUTO-mode the speed of the melt pump is controlled automatically by the PID-
pump
pressure controller
Speed melt
pump
Actual speed of the melt pump
M melt
pump
Actual load of the melt pump
Once the low value is reached, or the set time is reaches the alarm is
Alarm delay activated.
Low pressure limits If now the low pressure value is reached (with hysteresis) the pump will
be switched off
P-gain is calculated in linear ratio to the actual pressure control deviation (bar):
In the control deviation range from 0 to Deviation max. , P-gain will be calculated in a linear way
between P-gain max. and P-gain min.
Exceeding control deviation Deviation. max. , P-gain max. is used
Pdevi.
Pgain
Pmin. Pmin
Ti Integration time
Functionality:
With activated alarms and reached alarm value the melt pump and the extruder is shut off.
Low limit:
Once the low value is reached, or the set time is reaches the alarm is activated.
If now the low pressure value is reached (with hysteresis) the pump will be switched off
(Alarm delay time on screen 95)
Drives interlocked: auxiliary devices are able to run only with running extruder
Drives not interlocked: auxiliary devices are able to run without extruder.
The extruder cannot be started
Feeder type No grav. Feeders, Brabender CS (OP1), Brabender RC4, LM3, OP5
K-Tron, Colortronic, Scholz
Number of feeders Number of gravimetric feeders 1…8
Granulator Type of pelletizers
Activation/deactivation of devices and signals
(at deactivated device all belonging alarms and functions are reactive)
The controller parameters for the 8-channel temperature controllers are entered on this screen.
Pushing this button transmits the settings for the currently selected control-
ler to the corresponding controller with a Profibus telegram. As long as the
transmission is running, the "Controller" field flashes (approx. 3 seconds).
Auto tuning Selection of whether the heat zone is used for group optimisation
Integral Time TN Value range for integral time (Ti) 0 to 3276.7 s. If a value of 0 is set, the inte-
(Heating/cooling) gral time is deactivated
Differential Time TV Value range for the differential time (Td) 0 to 3276.7 s. If a value of 0 is set,
(Heating/cooling) the differential time is deactivated
Proportional Band XP Proportional gain for heating/cooling. Value range 0.1 to 999.9
(Heating/cooling)
Heat Current Cycle Here the time between 2 heat current measurements is set for each regulator.
The factor is a multiple of 2.25 sec. The value is pre-set to 5 -> for 8 planned
controllers on a device the heat current is measured every 5 x 8 x 2.25 sec. =
90 sec.
Multiplier heat current Here it is specified which heat current (in A) actually flows when the current
converter outputs 30 mA.
Pushing this button transmits all regulator settings to the two regulator
units via Profibus telegram. During transmission (approx. 3 minutes) the
input fields of this screen are inactive.
If the heating will be switched off during waiting time, the standby time will
be started. If during that time the heating will be switched on again the wait-
Heat up standby timet ing time continues to run.
in minutes
If the heating will be switched off, heated up, this time also starts.
The controller self-optimisation is a process for determining optimised controller parameters for the
respective heating and cooling segments. In the program it is possible to optimise the individual zones
separately or to combine certain control zones in groups and to optimise them together. A group may
consist of a maximum of 8 controllers, as only the respective controllers of a device can be optimised
together.
Before beginning with self-optimisation, the following conditions must exist:
1. The temperature setpoints of the heat zones to be optimised must be at least 180°C.
2. The machine must be cold (actual temperatures less than 40°C).
3. Actual temperature value may not fluctuate.
Select and press the Start button in the upper right field (Group self-
optimisation). All selected regulator zones (LED lights up green) are
switched on and the <Cancel> button appears. Pressing the <Cancel>
button cancels the self-optimisation process once. Now all regulator zones
to be optimised are switched on. Pressing the Start button again starts the
optimisation process once and for all.
The current state of optimisation can be output per regulator via the selection
field at the left in the lower right screen area.
Self-optimisation de- If a fault occurs while running the self-optimisation, the system ends the pro-
fective cess and a corresponding fault text appears in the two status fields:
The control zone to be optimised is selected with the "Regulator 1" field in
the upper left screen area (Single self-optimisation). The single optimisa-
tion is started with the Start button.
Regulator state The current state of regulator optimisation is output in the lower left screen
area.
Self-optimisation Self-optimisation is finished when the message "Self-optimisation success-
finished fully finished" appears in the two output fields. The optimised regulator pa-
rameters are automatically put in the parameter list on screen 7110 by the
system. Following optimisation the heat zone remains switched on and con-
tinues to operate in the normal regulator mode. Therefore, the heating should
be switched off by the user with the <Heater On/Off> button.
The single or group optimisation can be cancelled at any time with the
<Reset> button.
Option at up to 24 controllers
Optimisation controllers 17 – 24 (Screen 124 )
Option at up to 32 controllers
Optimisation controllers 25 – 32 (Screen 125 )
The heat current monitoring of the individual controllers is parameterised and activated on this screen.
Actual Actual value display of the last heat current measurement in amps.
Min.-Alarm Limit value which the heat current must exceed with the solid-state relay
switched through. If this value is not exceeded, an alarm message is output.
If the value 0 is entered here, the heat current measurement is deactivated.
Multiplier The heating current multiplier adapts the heat current detection to 2 and 3-
phase systems and to real measured values
Setpoint
Initial = 0 Starts the device with setpoint 0
Initial = HMI Starts with a preset initial setpoint
Initial =Setp. The latest setpoint is stored and the device will start with that setpoint
Display
+/- Step to in-or decrease the setpoint by +/- pushbuttons at screen “Analog values dis-
Step play” Screen 11
Display
Position Position settings of values in the upper permanent area:
Permanent Position 1 Position 5
area Position 2 Position 6
Position 3 Position 7
Position 4 Position 8
Begin Initial display value setting
Unit rpm, bar, mbar, A, kg/h, l/m, l/h, %, °C, °F, psi, m/min
Value
Begin % Lower value of the analog signal
These settings are available for values configured at „Machine configuration“ 110.
Display
Position Position settings of values in the upper permanent area:
Permanent Position 1 Position 5
area Position 2 Position 6
Position 3 Position 7
Position 4 Position 8
Begin Initial display value setting
Unit rpm, bar, mbar, A, kg/h, l/m, l/h, %, °C, °F, psi, m/min
Value
Begin % Lower value of the analog signal
For service :
Access to the PLC
Status display
After reaching the both end positions of the diverter valve the sole-
noid valves remain for this time longer open and also the hydraulic
Hydraulic pump off delay
pump runs that time longer, to be sure to open or close the diverter
valve fully.
Max. movement time diverter The maximum running time for the hydraulic pump diverter valve. Is
valve one end position not reached within this time, an alarm appears.
At undefined position, e.g. after emergency off, the diverter valve will be moved in bypass position with
the button “Heating on”
.
Level Authorization
Level 0 All screens, but settings in the technician configuration are selectable.
No user No entry ore change of values are allowed
Level 1 Switch on/off devices
Operator Change of process values, e.g. temperature setpoints, speeds, throughput, …
Create, change or delete users only can be done within „Administrator level“.
Therefore select the desired row and do the action.
Automatic log-on:
To enable the operator immediately to start at screen “Overview” 10 and log-on automatically, the
function Auto log-on can be activated
After system start, screen „Overview“ 10 is called and user with level 1 to operate will be logged in
automatically.
e.g. User: 111 das Password: 111.
The actions to handle the data records are similar to the user recipe handling described an screen 70
Alarm indicator The alarm indicator is a graphic symbol displayed on the screen when a fault
message is received. The symbol flashes as long as fault messages are pre-
sent.
The number below the triangle indicates how many fault messages are currently
active.
Message window Each fault or system message is displayed in its own message window on the
screen when a message is received. It is output in a message window with the
character set of the current language.
State:
K = alarm received (currently active)
G = alarm gone
Q = alarm acknowledged
Acknowledge alarms
Miscellaneous alarms :
Fault text Cause Remedy
Error chiller cabinet or operation panel electrical contact open Check chiller, check circuit breaker
Error 24V DC current surveillance electrical contact open Check to shortcut 24V DC
Error circuit breaker 230V cooling valves electrical contact open Check valves, check circuit breaker
Error chiller cabinet +S1 electrical contact open Check chiller, fuse or circuit breaker
Error chiller operation panel electrical contact open Check chiller, fuse or contact
Drives interlock "off", first interlock "on" Drive not interlocked Interlock at screen 100 „on“= „green“
at technician page !
Error Profibus: ET200s at cabinet +S1 no BUS connection Check PROFIBUS plugs, termination switch, ad-
dress-setting, cable
Error Profibus: ET200s at terminal box no BUS connection Check PROFIBUS plugs, termination switch, ad-
+K1 dress-setting, cable
Error heat exchanger Failure, electrical contact open Check reason at device (LED), e.g. Water min.
Check electrical connection
Error Profibus: heat exchanger no BUS connection Check PROFIBUS plugs, termination switch, ad-
dress-setting, cable
Error metal separator XX failure contact open Check or reset device, connection
Heating / Temperatures
Fault text Cause Remedy
Heat zone XX lower temperature limit Temperature too low Increase heat-up time, check solenoid valve
exceeded respective temperature zone, prevent energy loss
Heat zone XX Upper temperature limit Temperature too high Switch on cooling unit, open throttle valve of
exceeded temperature control zone if present, excessive
melt friction
Heat zone XX Heater current alarm Current too low Heating element defective or cable break, fuse
defective, semiconductor defective
Heat zone XX temperature sensor failure no electrical contact, Check sensor for proper seating, replace defec-
sensor failure tive sensor, and check electrical connection
Melt temperature XX sensor failure no electrical contact, Check sensor for proper seating, replace defec-
sensor failure tive sensor, and check electrical connection
Extruder temperatures are still too low ! One or more temperatures too Wait to reach the temperatures
low
Error Profibus: Multitemperature control- no BUS connection Check PROFIBUS plugs, termination switch,
ler XX address-setting, cable
Error heating-current short circuit con- At least one semiconductor Heating unit XX – XX semiconductor defective
troller XX relay is defective
Heat zone XX Failure output tempera- Output of controller defective Eliminate fault in controller output, replace con-
ture controller troller if necessary
Main drive :
Fault text Cause Remedy
Error lower limit speed extruder Minimum limit reached Set reasonable limit value
Check main drive functionality
Error upper limit speed extruder Maximum limit reached Set reasonable limit value
Check main drive functionality
Error low motor load extruder Minimum limit reached Do not run the extruder too long without material,
Set reasonable minimum load limit value
Error upper limit extruder load Maximum limit reached Set reasonable limit value
Reduce material throughput,
increase extruder speed,
increase temperature profile
Error circuit breaker main drive controller electrical contact open, Check setting at circuit breaker, check converter
power supply overcurrent
(DC-motor)
Error field current supervision main drive electrical contact open, Check fuse, check cooling, check converter
(DC-motor) overcurrent
Error tach main motor no electrical contact, Check connection, check sensor and connection
(DC-motor) overcurrent
Error power converter main drive failure See failure display at converter, e.g. overload
Error overtemperature main motor electrical contact open Check cooling, check thermosensor connection
Error circuit breaker cooling fan main electrical contact open, Check setting at circuit breaker,
drive overcurrent Check mechanical movement
Error Profibus: Converter main drive no BUS connection Check PROFIBUS plugs, termination switch,
address-setting, cable
Extruder cuts off, because of low motor lower limit reached Extruder more than one minute in low motor load
load
Error cooling water flow meter main electrical contact open Check water flow, check monitoring device, check
drive connection, check filter
First, turn on main drive, or Interlock At first start main drive.
drives off ! At Screen 100 Interlock „off“.
Start main drive first ! At first start main drive.
Cover clutch demounted electrical contact open Mount cover, check electrical contact
Error lower limit feeder XX Limit reached Set reasonable limit value at creed 67
Check drive functionality
Error upper limit feeder XX Limit reached Set reasonable limit value at creed 67
Check drive functionality
Error Profibus: feeder XX converter no BUS connection Check PROFIBUS plugs, termination switch, ad-
dress-setting, cable
General error feeder -> Feeder line off electrical contact open Check feeder
Feeder XX refill manually !
Feeders Brabender CS / RC4, OP5 :
Fault text Cause Remedy
General error feeder electrical contact open See feeder controller
Error Profibus: Feeder controller RC4 no BUS connection Check PROFIBUS plugs, termination switch, ad-
dress-setting, cable
Feeder XX load cell signal error no electrical signal Restart system, check connection, check interface,
check or change weight cell module
Feeder XX refill error Maximum level within set time Check refilling, check refill contact and connection,
not reached set reasonable refill levels and refill time
Feeder XX underload Underload level reached Check refilling, set reasonable limit, correct tara
value
Feeder XX overload Overload level reached Rise value between overload and max. level,
reduce mechanical material flow
Feeder XX control deviation negative Time delayed deviation Correct control parameter, check screw size and
material, avoid external mechanical vibration
Feeder XX control deviation positive Time delayed deviation Correct control parameter, check screw size and
material, avoid external mechanical vibration
Feeder XX speed minimum Limit reached Reduce parameter, check rpm detection, check
control parameter, check screw size
Feeder XX AV-error (filter violation) Increase filter parameter, avoid external vibration,
correct control parameter settings
Feeder XX CM-error (check max.) Wrong calculated value See Brabender manual
Feeder XX FC-error (frequency convert- overload Release mechanical blocking of the screw, check
er) converter
Feeder XX communication error ISC failure ISC-bus Configure ID-No. of ISC-CM
Check ISC-CM supply, check ISC-BUS connection
Feeder XX weight below 2% Underload level reached Check refilling, set reasonable limit, correct tara
value
Feeder XX overload Overload level reached Rise value between overload and max. level,
reduce mechanical material flow
Feeder XX refill timeout has occurred Maximum level within set time Check refilling, check refill contact and connection,
not reached set reasonable refill levels and refill time
Feeder XX actual value is too high Maximum speed level reached Check max. value and alarm limit , check screw,
check refilling, check initial feed factor
Feeder XX actual value is too low Minimum speed level reached Check min. value and alarm limit , check screw,
check refilling, check initial feed factor
Feeder XX motor speed is too high Limit reached Check max. value and alarm limit , check screw,
check refilling, check initial feed factor
Feeder XX motor speed is too low Limit reached Check min. value and alarm limit , check screw,
check refilling, check initial feed factor
Feeder XX weight processor failed no electrical signal Restart system, check connection, check interface,
check or change weight cell module
Feeder XX MDU failure No speed response Check rpm detection, check screw
Error Profibus: Feeder controller K-Tron no BUS connection Check PROFIBUS plugs, termination switch, ad-
dress-setting, cable
Feeder XX refill manually ! Minimum level reached Refill hopper manually
With automatic refilling set button to “AUTO”
Feeder XX actual value is too high Maximum reached Check max. value and alarm limit , check screw,
check refilling, check initial feed factor
Feeder XX actual value is too low Minimum reached Check min. value and alarm limit , check screw,
check refilling, check initial feed factor
Feeder XX motor speed is too high Maximum speed level reached Check max. value and alarm limit , check screw,
check refilling, check initial feed factor
Feeder XX motor speed is too low Minimum speed level reached Check min. value and alarm limit , check screw,
check refilling, check initial feed factor
Feeder XX weight processor failed no electrical signal Restart system, check connection, check interface,
check or change weight cell module
Feeder XX motor failure no speed response Czech gear cover, safety switch, rpm detector,
screw
Feeder XX feeder error Feeder is on and Pert-value is Check mechanical movement of motor, refill flap
higher than Pertlimit-value closed, too high Setpoint change, avoid external
vibration
General error pelletizer -> Extruder off failure Check connection and contacts, circuit breaker
Error lower limit speed pelletizer Lower limit reached Set reasonable limit value at creed 67
Check drive functionality
Error upper limit speed pelletizer Upper limit reached Set reasonable limit value at creed 67
Check drive functionality
Error frequency converter pelletizer Failure, e.g. overload See failure display at converter,
check connection
Error overload pelletizer Pelletizer blocked Check material parameters
Error circuit breaker pellet drier electrical contact open Check setting at circuit breaker, mechanical
movement
Error cover pellet drier open electrical contact open Close cover, check limit switch and connection
Vacuum pump:
Fault text Cause Remedy
Error lower limit "vacuum" Lower limit reached Set reasonable limit value at creed 67
Check drive functionality and pipes
Error upper limit "vacuum" Upper limit reached Set reasonable limit value at creed 67
Check drive functionality and pipes
Error vacuum pump electrical contact open Check setting at circuit breaker, mechanical
movement of drive
Melt pump :
Error agglomerate screen UWG Limit switch not reached Check valves and hydraulic, check limit switches
Error water level water tank UWP Water level to low Check refill parameter, check refilling, check
sensors
Error water flow rate UWP Water flow rate too low Check water flow, min. setting, sensor or device
Error safety switch pellet dryer UWP Safety key not in right position Key switch to “on”
Error speed pellet dryer UWP No speed signal Check drive (belt), monitoring unit
Error frequency converter pelletizer Failure, e.g. overload See failure display at converter,
UWP check connection
Error circuit breaker fan pellet dryer electrical contact open Check setting at circuit breaker, mechanical
UWP movement of drive
Error circuit breaker dryer UWP electrical contact open Check setting at circuit breaker, mechanical
movement of drive
Error circuit breaker process water pump electrical contact open Check setting at circuit breaker, mechanical
UWP movement of drive
Error circuit breaker water pump pellet electrical contact open Check setting at circuit breaker, mechanical
filter UWP movement of drive
Error circuit breaker hydraulic pump electrical contact open Check setting at circuit breaker, mechanical
diverter valve movement of drive
Error limit switch valve filter UWP Wrong position Check mechanic, clean, check limit switch
Bypass solenoids not in bypass position Limit switch not reached, Check valves and air, check monitoring time
UWP Monitor time too short
Bypass solenoids not in production Limit switch not reached, Check valves and air, check monitoring time
position UWP Monitor time too short
Error Profibus: ET200-Station pelletizing no BUS connection Check PROFIBUS plugs, termination switch,
system address-setting, cable
MacromateXX professional S7
Notes:
Passwords: