You are on page 1of 27

Fire Detection Systems

Fire detection systems 8/8/06 11:46 Page 3

contents

conventional fire alarm systems 4

intelligent fire alarm systems 9

detector application guide 15


Fire detection systems 8/8/06 11:46 Page 4

conventional fire a minimum of 24 hours, dependant


on the application, in case of a
mains failure.

alarm systems Note: There are numerous suppliers


of fire control equipment and fire
detection devices. There is no
principle control panel guarantee that all panels and all
detectors are electrically
of operation The control panel drives the
detection zones and sounder
compatible. Therefore, to avoid
A conventional fire alarm system potential incompatibility issues, it is
circuits, provides LED indications
normally consists of a control panel strongly recommended to purchase
of fire, fault or normal conditions
linked to a number of lines of fire both groups of products from the
and contains switches to allow the
detectors and manual call points, same source, or to obtain
sounders to be activated or silenced
normally called detection zones, confirmation of compatibility from
and the detectors to reset following
and a number of sounder or alarm the panel manufacturer.
an alarm. The control panel is
circuits. A simple system is shown powered from the mains (230VAC)
in Figure 1. and will contain back-up batteries
to allow the system to function for fire detection
and alarm
zones
FIRE Most conventional fire alarm panels
FIRE
ALARM ALARM have several detection zones
CONTROL CIRCUIT
EOL

comprising a mixture of automatic


PANEL
fire detectors and manual call
System OK
points. In order to limit the effect of
Zone 1 Alarm
faults, and to limit the search area in
Zone 2 Alarm
the case of a fire, the size of a fire
Zone 1 Fault

Zone 2 Fault FIRE


detection zone is limited to 2000m2,
Alarm Cct Fault
DETECTION with a maximum travel distance
ZONE 1
EOL

within the zone to locate a fire of


System Reset
60m. In addition, zones should not
cover more than one storey, unless
the total floor area of the building is
FIRE
DETECTION less than 300m2. As a result unless
ZONE 2
EOL

the site is very small, the system will


comprise several detection zones.

A fire alarm (or sounder) circuit may


cover more than one detection
zone, but it must follow the
boundaries of the relevant detection
zones, and the boundaries should
Figure 1: Simple conventional fire alarm system be of fire resisting construction.

4
Fire detection systems 8/8/06 11:46 Page 5

conventional detector to limit the current draw


in alarm. Resistors fitted into the
detection line
fault monitoring
system detector base are also used in
Standard conventional systems are
some cases to distinguish between
operation a short circuit fault and an alarm.
able to monitor the zone for short
circuit, open circuit and detector
The value of the base resistor is head removal.
detection line operation dependant on the control panel,
Conventional detection systems however a typical value is 470 When a short circuit occurs on a
normally operate on a 24VDC line. Ohms. If in any doubt, contact the zone, a high current will be drawn,
In the standby condition, the control panel manufacturer who and the line voltage will be pulled
detectors will draw a low current, should be able to specify which towards zero volts. The panel
typically less than 100μA. When the detector bases should be used detects the low voltage / high
detector senses a fire, it will switch with different detector brands. current and a fault is signalled.
into the alarm condition with it's
LED illuminated, and will collapse A manual call-point consists of a In order to detect an open circuit, or
the line voltage by drawing a larger simple switch with a resistor in detector head removal, a device is
current - dependant on the series with it, usually 470 Ohms or connected across the end of the
detectors and control panel, but 680 Ohms. When the call point is zone, which can be monitored.
typically 50-80mA. The control activated, the resistor is switched This device can take various forms
panel can sense this, and activate across the line, and a current of dependant on the control panel.
the appropriate alarms. The 50-80mA, dependant on the
detector will remain latched in the control panel, is drawn.
alarm state with its LEDs
illuminated, even if the smoke or
heat is removed until it has been
reset from the panel by momentarily +24V
removing power from the line.
This allows the fire to be located
even if the signal is intermittent, or
to locate possible sources of
Resistor

Contact Closed
nuisance alarms.
when detector
inserted in base
For some control panel - detector
combinations, when a standard
base is used, there is an
incompatibility between the current
specifications of the detector and
panel, leading to incorrect reporting
by the control panel, for example
signalling a fault in place of an 0V
alarm, and in some cases damage
to the detector due to over current
in the alarm state. In these cases it
is necessary to use a base fitted
with a resistor in series with the Figure 2: Resistive end of line operation

5
Fire detection systems 8/8/06 11:46 Page 6

The simplest end of line device is removed detector, it will no longer head is removed, the diode is
a resistor, which will draw a current work, which contravenes the connected across the contact,
distinct from the quiescent and requirements of BS5839 part 1. To allowing power to continue to be
alarm currents drawn by the overcome this either all call points supplied to the remainder of the
detectors. Installation of detectors must be mounted at the start of zone, whilst still permitting the
into their bases closes a contact in each zone, or in completely removed detector to be monitored.
the base supplying the remainder of separate zones (both of these This is achieved in a number
the zone. Thus if the line is broken, solutions are often impractical and of ways.
or if a detector head is removed, too costly), or head removal
the current drawn by the zone will monitoring can be employed. An active end of line device uses a
fall, and a fault will be signalled switched resistor at the end of line
(See figure 2). Example zone current Active monitoring uses bases fitted and can thus be used with a
and voltage figures are with a diode across the contact in standard control panel. It sends a
given in figure 3. the base (fig 4). Whilst the detector periodic signal back along the
detection line, which is normally
quenched by the control panel.
Monitoring of detection line When a head is removed, the base
(example only) diode is switched into the line, and
Condition Current Voltage pulse can be seen. The Active end
of line then switches the resistor out
Open Circuit <3mA 24V
of the line, and a fault is signalled.
Normal 5mA (dependant on EOL device) 18V
Fire 50mA (dependant on control panel) 4 –15V If a capacitive end of line is used,
the panel periodically drops the line
Short Circuit High (dependant on control panel) 0V
voltage for a few milliseconds, and
Figure 3: Example resistive conventional system current and voltage figures
looks for the line voltage being held
up by the capacitor. When a head is
The problem with a simple resistive is mounted in the base, the base removed, the panel will see the line
end of line is that should a detector contact connects directly across the voltage drop immediately as the
head be removed, the remainder of diode, and links it out. There is capacitor's discharge will be
the zone beyond that detector is usually provision for manually inhibited by the diode, and thereby
lost and no alarm can be signalled linking the diode out to permit a fault can be signalled.
beyond this point. Should a call continuity testing during
point be mounted beyond the commissioning. When the detector A third type of end of line device is
a diode. With this the panel
+24V periodically reverses the line voltage
for a few milliseconds: If the line is
broken by the diode in the detector
base, then no current can flow in
E.O.L.

the reverse direction.

The type of end of line monitoring


used on a system will depend
Contact Closes
when detector on the control panel. However it
0V inserted in base is important, particularly when
Figure 4: Active end of line monitoring circuit using active end of line monitoring

6
Fire detection systems 8/8/06 11:46 Page 7

to ensure that the detectors wires, see figure 5. In this instance, relay contacts are wired in series
are compatible with the type a base incorporating a change over with the normally closed contacts of
of monitoring being used. relay is used. This configuration is the detector relay base(s). Thus in
Reference must be made to known as a four-wire system, and is the normal state the detection
the panel manufacturer to often seen when a fire zone is circuit is closed; in the case of fire
ensure compatibility. integrated into a security panel. or power failure the relevant relay
contacts will open.
Figure 5 shows the simplest form of
remote LEDs four-wire system, as used with most Normally after an alarm, the
Most system smoke detectors are security panels. This is used where detectors are reset by disconnecting
equipped with a terminal to allow the monitor line is able only to the power to the relevant zone for a
the connection of a remote LED. register an open or closed circuit - short period by pressing a central
Remote LEDs are often used there is no distinction between a panel reset button. Fire panels have
outside bedroom doors in hotels so fault and a fire. By using a normally this facility built in, however many
that in case of a fire, it is easy for closed relay at the end of the power security panels are unable to do this
the fire brigade to identify the line, it is possible to monitor for a without turning the entire panel off.
location of the fire without needing power failure to the detectors. The Therefore to allow the use of
to enter every room in the building.
They may also be used where a - 24VDC
+ 24VDC
POWER SUPPLY
END OF LINE
RELAY COIL

detector is located in a hidden


position, such as a floor or roof void
+24VDC IN

+24VDC IN
- 24VDC OUT

- 24VDC OUT
- 24VDC IN

- 24VDC IN
+ 24VDC OUT

+ 24VDC OUT

or cable tunnel, for example, to


provide a visual indication that the BEAM DETECTOR #1 BEAM DETECTOR #2
MAINTENANCE

MAINTENANCE
RELAY (N/O)

RELAY (N/O)
RELAY (N/C)

RELAY (N/C)
RELAY (N/C)

RELAY (N/C)

detector is in an alarm state.


ALARM

ALARM
FAULT

FAULT

four-wire system operation


In some cases it is necessary that
the power to the detectors and the
Resistor

Resistor

EOL

DETECTION CIRCUIT
fire detection signal be on separate

Figure 6: 4-wire system with full monitoring

detectors with security panels,


non-latching versions of the relay
Detection Line bases are usually made available,
(Open Circuit for
Alarm and Fault)
which automatically isolate the
FIRE detector from the supply every few
ALARM seconds. Thus once the fire
CONTROL
PANEL End of Line condition has passed the detector
Monitoring Relay

C NO NC C NO NC
will automatically reset (note that
Power Supply
(Nominal 12V
or 24V System)
the alarm condition should be
latched at the control panel.)

Four-wire type systems are also


often used with devices such as
Figure 5: Typical 4 wire system wiring
beam detectors where an auxiliary

7
Fire detection systems 8/8/06 11:46 Page 8

power supply may be required. In 470 Ohms is placed in series with to operate when a voltage is applied
this case if the device is connected each alarm contact as indicated in in one direction, but not when the
to a fire control panel, able to order to shunt the detector zone. voltage is reversed. When the
distinguish between different Note that a separate reset signal system is in standby, the panel
detector states, the circuit can be may be required to reset some applies a voltage in the 'wrong'
routed to provide full monitoring for beam detectors direction, so that the sounders do
alarm and fault. Figure 6 shows not operate and do not draw any
typical wiring for a beam detector, current. An end-of-line resistor
which includes it's own internal
fire alarm (sounder) draws a constant monitoring
maintenance and fault monitoring. zone operation current, which allows the panel to
With this layout all fault and Similarly to detection lines, it is verify that the wiring is intact.
maintenance contacts are wired in important to monitor fire alarm Should the panel sense that no
series, and all alarm contacts in zones to ensure that the cable has current is being drawn, it signals an
parallel with the end of line device. not been broken, disconnected or open circuit fault. In the case of a
In the case of a fault or shorted. However the operation of short circuit, a high current is drawn
maintenance signal, the end of line alarm zones is different from from the zone, the voltage drops
will be disconnected, and a fault detection lines. towards zero and a fault condition
can be signalled at the panel. To is shown. To activate the sounders,
distinguish between an alarm and Fire alarm sounders contain a the control panel reverses the
short circuit, a resistor, typically polarising diode, which allows them polarity of the voltage to the zone.

Standby
24VDC
EOL

Alarm
24VDC

Figure 7: Conventional fire alarm sounder circuit

8
Fire detection systems 8/8/06 11:47 Page 9

intelligent fire Figure 8 demonstrates an example


of a single loop intelligent fire
system layout. The wiring is looped,

alarm systems and connects to the control panel at


each end. All detectors, call points,
sounders and interface modules are
wired directly to the loop, each
introduction pair of wires to be used to connect
a large number of devices to the having its own address.
Conventional fire alarm systems system, allowing cost savings in the
provide an adequate and cost wiring of large systems. In larger The control panel communicates
effective fire alarm system for many installations, the benefits of with each device on the loop, and if
small buildings. In larger, more improved maintenance and reduced an alarm or fault condition is
complex buildings however, more cabling cost are overwhelming. signalled, or if communications are
sophisticated ‘intelligent’ fire alarm Currently, the point at which an lost with one or more detectors, the
systems tend to be used. These intelligent system becomes appropriate response is triggered.
systems offer benefits in speed of economical is around 6 zones The loop can be powered from each
detection, identification of the in the UK. end so that if the loop is broken at
location of a fire and easier any point, no devices are lost. In
maintenance. Intelligent systems This guide is intended as an addition the use of short circuit
also offer tolerance to faults in the introduction to the technology used isolators minimises the area of
system wiring, which allows a single in intelligent fire alarm systems. coverage lost in the case of a
short circuit.

ISOLATOR intelligent
FIRE ALARM SYSTEM OK
28 January 2004
14:01
system types
SYSTEM OK There are two methods commonly
FIRE ALARM
FAULT used for implementing intelligent
CONTROL fire systems:
EOL

SYSTEM RESET
MODULE

CONVENTIONAL
INTELLIGENT ALARM ZONE The most common type of system is
FIRE ALARM
CONTROL “Analogue”. In this case the detector
PANEL
(or sensor) returns a value to the
ISOLATOR
panel representing the current state
MONITOR
of its sensing element(s).
EOL

MODULE

CONTACT The control panel compares this


(E.G. SPRINKLER
SWITCH value with the alarm threshold in
order to make the decision as to
whether a fire is present. Note that
ISOLATOR
the term analogue, used to describe
these systems does not refer to the
Figure 8: Intelligent fire alarm systems
communication method (indeed
many “analogue” fire systems use

9
Fire detection systems 8/8/06 11:47 Page 10

digital communications) but to the manufacturer to manufacturer, but • Analogue Signal - i.e. the
variable nature of the response from generally comprises switching of the current sensor value
the detector to the control panel. 24V supply voltage to other voltage
• Alarm Signal if
levels to achieve communication.
appropriate
In “Addressable” type intelligent
systems, mainly used to meet the A typical basic protocol comprises • Status of module output
requirements of the French market, two main parts (See Fig 9): A query
• Remote test status
detector sensitivity is programmed or poll of a device by the control
to each device by the control panel panel including the device address • Manufacturer code
or is preset in the factory. and control information, and a
Most commonly, each device on the
response from the device giving its
loop will be polled in turn, however
The detector compares its current status and other information.
to increase speed around a loop,
sensor value with the configured Precise details of the information
some protocols allow polling of
threshold to make the alarm transferred will depend on the
groups of devices on a single
decision, which is then transmitted manufacturer, but normally will
communication.
to the panel when the sensor is include:
interrogated.
Note that since different
manufacturers have their own
In many systems the features Poll: Control Panel to device: protocols, it is important to
offered by the two detection
• Device address ensure compatibility between the
techniques are so similar that it is
detectors and control panel you
not particularly relevant which • Control of device LED - intend to use. Some detector
technique is used to make the alarm blink to indicate polling, manufacturers produce intelligent
decision. It is better to select a switch on when device is detectors with different
system based on the features in alarm communication protocols for
offered by the system as a whole. different customers, so two
• Control of device self-test detectors which look virtually
• Control of module output identical in appearance may not

communication • Error detection for


be compatible. Always check
with the manufacturer of the
protocol example parity bit or
checksum
control panel.

Intelligent systems use the same


Response: Device to
pair of wires both to supply power
to the loop, and to communicate Control Panel addressing
with devices on the loop. • Device type (e.g. optical methods
detector, heat detector, Different manufacturers of intelligent
The communication language, or multi-sensor detector, systems use a number of different
protocol used varies from module) methods of setting the address of
a device, including:
+24V
Panel to detector Detector Response
4 5 4 5
Error Check

3 6 3 6
Test Status

Detector Device Sensor Other Info 2 7 2 7


Control
Address Type Value e.g. drift 1 8 1 8
status 0 9 0 9
TENS UNITS

Figure 10: Decade address switches


Figure 9: Typical protocol configuration address 03 selected

10
Fire detection systems 8/8/06 11:47 Page 11

• 7-bit binary or sounders, input and output In order to give tolerance against
hexadecimal DIL switch modules) may be connected to short circuits on the loop, short
a loop. circuit isolators are placed at
• Dedicated address
intervals on the loop. Should a short
programmer
circuit occur on the loop (Figure 12)
• Automatic, according to
physical position on the
system fault the isolators directly on either side
of the fault will isolate that section.
loop tolerance The panel will detect the loss of the
• Binary ‘address card’ devices, signal a fault and drive the
Due to the looped wiring method
fitted in the detector base loop from both ends, thereby
used for analogue systems, they are
enabling the remainder of the loop
• Decimal address switches more tolerant to open and short
to operate correctly and ensuring
circuit wiring faults than minimum loss of coverage.
Using the Decimal Address Method conventional systems.
differences in the protocol between Short circuit isolators are available
detectors and modules allow them Under normal conditions, the loop as separate modules and
to have the same address without will typically be driven only from one incorporated into a detector base.
interfering with each other, and end. If the loop is broken (See figure
normally address 00 (the factory 11.), the panel will detect the loss of Some products have isolators built
default setting) is not used within communications with the detectors into each of the loop devices. With
a system so that the panel can beyond the break, signal a fault, and this configuration, since only the
identify if a device address has not switch to drive the loop from both section of wiring between the two
been set: Hence a total of up to ends. The system therefore remains adjacent devices is isolated there
198 devices - 99 detectors and 99 fully operational, and can possibly will be no loss of coverage should
modules (including call points, even indicate the area of the break. a short circuit occur.

Isolating
Impedance

24V
Line break
24V Isolators on either side of
SYSTEM FAULT: OPEN CIRCUIT:
Zone 2 Module 01 SYSTEM FAULT: SHORT CIRCUIT:
the short circuit switch an
FIRST FLOOR CANTEEN
Panel detects the loss of Zone 2 DETECTOR 03
FIRST FLOOR CANTEEN
impedance onto the line
SYSTEM OK to isolate it.
devices after the break, SYSTEM OK
FIRE ALARM signals a fault and powers FIRE ALARM Devices between the two
FAULT from both ends of the loop FAULT isolators are lost,
to retain full coverage. Short Circuit however the remainder of
SYSTEM RESET SYSTEM RESET
the circuit still operates
INTELLIGENT correctly.
INTELLIGENT
FIRE ALARM FIRE ALARM Isolators automatically
CONTROL PANEL CONTROL reset the line when the
short circuit is removed
PANEL 24V
24V

Isolating
Impedance

Figure 11: Open circuit fault Figure 12: Short circuit fault

11
Fire detection systems 8/8/06 11:47 Page 12

drift a “drift compensation” function,


included in either the detector or the
This “Pre-Alarm” can be signalled
at the panel and can therefore be
compensation control panel algorithms. These
functions use algorithms that
investigated to check if there is a
real fire, or if it is caused by other
and monitor the sensitivity of a detector, signals, for example steam or dust

maintenance and modify its response to


compensate for a build up of dust in
from building work. This can avoid
the inconvenience and expense of
alarm the chamber over time. Once the
detector reaches the “drift limit”
evacuating a building or calling out
the fire brigade unnecessarily
The sensitivity of a smoke detector when the dirt build up can no longer because of a nuisance alarm. The
tends to change as it becomes be compensated for, a fault can be Pre-Alarm Threshold is typically
contaminated with dirt or dust (see signalled. Some systems also set at 80% of the alarm threshold.
figure 13). As contamination builds incorporate a warning to signal
up, it usually becomes more that a detector is approaching
sensitive, leading to the risk of a
false alarm, but in some cases can
its compensation limit and
requires cleaning.
fire alarms
When a fire is detected, the control
panel indicates an alarm by
activating the fire indicator for the
relevant zone on the control panel,
Threshold
increased to sending a command to the relevant
compensate for
increased chamber detector to illuminate its LED and
clean air value.
activate alarm signals to start
Chamber Value

Smoke required to evacuation. Most intelligent fire


reach alarm
threshold reduces - system control panels include
Detector sensitivity
increases
alphanumeric displays enabling
them to show information on the
source of the alarm. This may
simply be a zone and detector
address, or could be more
descriptive for example “Smoke
Time Detector, Bedroom 234”. The
Clean Air Uncompensated Uncompensated Compensated
control panel may also use control
Value Alarm Threshold Chamber Value Threshold modules to operate additional
Figure 13: Chamber contamination and drift compensation
electrical equipment such as air
conditioning units and door
become less sensitive, so delaying releases to prevent the spread of
the alarm if a fire is detected. To pre-alarm smoke and fire.
counter this, if a detector drifts
outside its specification, a
facility The alarm signals can either be a
maintenance signal may be sent to One advantage of intelligent type zone of conventional sounders and
the panel warning that the detector systems is that since the data sent strobes activated via control
needs cleaning. by a detector to the panel varies modules on the loop or directly from
with the local environment, it can be the control panel, or addressable
To further increase the maintenance used to detect when the device is loop powered devices connected on
interval, many systems incorporate approaching an alarm condition. the same loop as the detectors and

12
Fire detection systems 8/8/06 11:47 Page 13

activated by direct command from connected on one circuit. Although therefore recommends the division
the panel. Loop powered sounders intelligent systems allow the precise of the loop as to limit the effect of a
tend to have lower wiring costs, device that initiated an alarm to be short circuit with the use of short
however the number permissible identified, zones are still used in circuit isolators. The placement of
on the loop may be restricted by order to make programming the these isolators should typically limit
current limitations. system and interpreting the location the loss of coverage to less than
of a fire easier. The control panel 2,000 m2 nor more than one floor
On larger sites, it may be desirable may have individual fire indicators (figure 14). Allowances are made for
to use zoned alarms. This allows a for each zone on the system, and the floor above and below but this
phased evacuation to be carried the control panel response to an is limited as not to affect more than
out, with areas at most immediate alarm is often programmed five devices on these floors.
risk being evacuated first, then less according to the zone of the
endangered areas later. device in alarm rather than its
individual address. remote LED’s
Most system smoke detectors are
The division of a loop into zones is
fire system achieved within the panel software,
equipped with a terminal to allow
the connection of a remote LED.
zones however, as multiple zones are
physically connected onto the same
Remote LEDs are often used outside
Conventional fire alarm systems bedroom doors in hotels so that in
cable, a short circuit can affect the
group detectors into ‘zones’ for case of a fire, it is easy for the fire
operation of a large area of
faster location of a fire, with all the brigade to identify the location of
detection devices unlike a
detectors in a particular zone being the fire without the need to enter
conventional system. BS5839 part 1
every room in the building. They
may also be used where a detector
is concealed in loft space, for example,
to provide a visual indication that
the detector is in an alarm state.

interface
modules
Input and Output modules can be
used to provide an interface
between a fire loop and a variety of
types of electrical equipment.
Output or control modules can be
used to operate sounders or shut
down electrical equipment by
command from the panel in case of
a fire. Input or monitor modules are
used to monitor volt-free switch
contacts, for example from a
sprinkler supervisory switch or an
Figure 14: Intelligent system fire zones
existing conventional fire panel.

13
Fire detection systems 8/8/06 11:47 Page 14

Conventional zone monitor modules Other optional features may also be the location of a fire to be
are also available, providing an programmed using the keypad. The precisely located from the
interface between a zone of sensitivity of each detector on the control panel
conventional detectors and an system can be configured for high
• The use of looped wiring
analogue fire detection loop, and sensitivity if the detector is installed
allows the system to
are often used when existing in a clean smoke-free area, or for function normally even
conventional systems are upgraded. low sensitivity if the area is subject with an open circuit in the
to cigarette smoke, for example. loop wiring
Complex intelligent systems offer
• The use of short circuit
programming many user-programmable features
that can be time-consuming to enter isolators allows correct
of intelligent manually using the keypad. In this
case, many panels have the facility
operation of most, if not
all of the system even
fire alarm to connect a portable PC by means with a short circuit in the
loop wiring
panels of a serial data link.
• Detectors are constantly
Most small intelligent systems can The user is supplied with a monitored for correct
be programmed with ease without specialised piece of software, which operation
the need for any specialised enables the entire configuration of
the system to be programmed into
• The use of a ‘pre-alarm’
equipment. The control panel has an
the PC, away from site if necessary.
feature alerts staff to
alphanumeric keypad, which is used
check whether a fire
to enter data into the system. It is then a simple matter of
condition exists before
Typically a password is required to temporarily connecting the PC to
the alarm is raised
set the panel to ‘engineering mode’, the control panel and downloading
allowing the panel to be the system configuration to the • Different detector
programmed. Many control panels panel. Once the information has sensitivities can be used
have an ‘auto-learn’ facility, been downloaded, it is permanently for diverse applications
whereby the control panel polls stored in the control panel, and the
• The use of addressable
every address on the system, and PC can be removed.
loop-powered sounders
detects which addresses have been allows the same wiring to
used, and what type of detector or be used for sensors, call
module has been connected to each
address. As a default, the panel will
advantages of points and sounders

usually programme all the devices


on the loop into the same zone.
intelligent • The use of monitor
modules allows contacts
systems from sprinkler switches,
existing fire alarm
The user can then customise the
system by entering how the zones • The wiring cost of a systems, fire dampers etc.
are configured. The panel may give system can be reduced by to be monitored using
the use of a single pair of detector loop wiring
the user an option of how modules
wires for many devices
are to be configured - for example • The use of control
including smoke and heat
whether an input module should modules allows sounder
detectors, call points,
trigger an alarm or a fault when lines, air conditioning
beam detectors, input and
operated and whether the wiring systems, lifts etc. to be
output modules.
is to be monitored for open controlled or shut down
circuit faults. • Intelligent Systems allow using detector loop wiring

14
Fire detection systems 8/8/06 11:47 Page 15

detector category L systems Protection should be as for category


L4 with the addition of smoke or
Category L systems are automatic
application fire detection systems intended to heat detectors in rooms opening
onto escape routes.
guide protect life. The category is further
subdivided as follows:
Canteen Kitchen Pantry
fire system categories
category L5: In a category L5
Before a fire protection system can system certain areas within a
be designed, it is necessary to building, defined by the fire system
define the main objectives of the specification, are protected by

down
system. This is normally determined automatic fire detection in order to Paper
Store Office Office

by a fire risk assessment, and reduce the risk to life. This category
should be provided as part of the of system may also include manual
fire system specification. BS5839 fire protection.
Part 1: 2002 defines three basic
categories of fire detection system. Canteen Kitchen Pantry category L2: Objectives are similar
to category L3, however additional
protection is provided for rooms at
category M systems
higher risk. Protection should be as
Category M systems rely on human for category L3 plus smoke
down

intervention, and use only manually Paper


Store
Office Office detectors in specified rooms at
operated fire detection such as high risk
break glass call points. A category
M system should only be employed
Example L5 System: L4 protection plus areas of high risk Kitchen
Canteen Pantry
if no one will be sleeping in the
building, and if a fire is likely to be category L4: Designed to offer
detected by people before any protection to the escape routes
escape routes are affected. Any from a building. The system should
alarm signals given in a category M
down

comprise Category M plus smoke


system must be sufficient to ensure detectors in corridors and stairways
Paper
Store
Office Office

that every person within the alarm


area is warned of a fire condition.
Canteen Kitchen Pantry

Canteen Kitchen Pantry


category L1: The highest category
for the protection of life. Intended to
down

Paper
Store Office Office give the earliest possible notification
of a fire in order to allow maximum
down

time for evacuation. Automatic and


Paper
Office Office manual fire detection installed
Store
throughout all areas of the building.
category L3: Intended to offer Smoke detectors should be
early enough notification of a fire to employed wherever possible to
allow evacuation before escape protect rooms in which people can
routes become smoke logged. be expected to be present.

15
Fire detection systems 8/8/06 11:47 Page 16

Similarly to class M systems, all detectors should be installed Manual call points should be
alarm signals given in a category L throughout a building. mounted on all escape routes, and
system must be sufficient to warn at all exit points from the floors of a
all those people for whom the In a category P system, unless building and to clear air. It should
alarm is intended to allow for a combined with category M, it may not be possible to leave the floor of
timely evacuation. be adequate for alarm signals a building without passing a manual
simply to allow fire fighting action to call point, nor should it be
Kitchen
Canteen Pantry
be taken, for example a signal to necessary to deviate from any
alert a responsible person to call the escape route in order to operate a
fire brigade. manual call point. Call points
mounted at the exits from a floor
Electrical Plant Materials
may be mounted within the
down

Storage
Paper Office
Store
Office
accommodation or on the stairwell.
In multiple storey buildings where
phased evacuation is to be used
call points should be mounted
down

Computer
Equipment
within the accommodation to
category P systems
avoid activation of call points on
Category P systems are automatic lower levels by people leaving
fire detection systems whose the building.
primary objective is to protect
manual call points
property. The category is subdivided In order to provide easy access, call
as follows: People can often still detect a fire points should be mounted between
long before automatic fire detectors; 1.2 and 1.6m from the floor, and
category P2: Intended to provide hence manual call points are should be clearly visible and
early warning of fire in areas of high important components of fire identifiable. The maximum distance
hazard, or to protect high-risk detection systems in occupied anyone should have to travel in
property. Automatic fire detection buildings to ensure timely order to activate a manual call point
should be installed in defined areas evacuation in the case of fire. All is 45m, unless the building is
of a building. call points should be approved to occupied by people having limited
EN54-11, and should be of type A, mobility, or a rapid fire development
Electric Plant Materials
that is once the frangible element is is likely, in which case the maximum
Storage
broken or displaced the alarm travel distance should be reduced
condition is automatic. to 20m. Call points should also be

Pantry
down

Kitchen
Computer Canteen
Equipment

MAX DISTANCE 45M


1.2 to 1.6m

category P1: The objective of a


Office Office
category P1 system is to reduce to
a minimum the time from the
ignition of a fire to the arrival of the
fire brigade. In a P1 system, fire Figure 15: Intelligent system fire zones

16
Fire detection systems 8/8/06 11:47 Page 17

sited in close proximity to specific


hazards, for example kitchens or
paint spray booths.

selection of automatic fire


detectors
Smoke detectors are the most
sensitive automatic means of
detecting a fire and should be
used wherever conditions allow.

ionisation smoke
detectors Without smoke: Chamber is designed so that light from the IR-LED
does not reach the receiver
Ionisation smoke detectors use a
weak radioactive source to ionise
the air between two electrodes,
creating positive and negative ions
and so allowing a small current to
flow across the chamber. Smoke
particles attract these ionised
particles, and allow positive and
negative ions to recombine, thus
reducing the number of ions and
hence the current flow.

Environmental regulations
concerning the radioactive source
used in ion detectors means that
Smoke present: Light from the IR-LED is reflected off the smoke particles
they are now becoming obsolete,
onto the receiver, triggering an alarm signal
and most major manufacturers are
no longer including ionisation Figure 16: Operation of optical chamber
detectors in new ranges.
figure 16). They are now largely choice in an environment where a
replacing ionisation detectors as a slow burning fire could be expected,
photoelectric smoke
general purpose detector. such as a room containing modern
detectors fabrics and furnishings.
Photoelectric or optical smoke Photoelectric smoke detectors are
detectors work by generating pulses tested across the complete range of
of infra red light and measuring any EN54 fires, however they are most
multi-criteria detectors
diffracted light. If smoke is present sensitive to smoke containing large Multi-criteria detectors comprise two
in the sensing chamber, the light is particles from around 0.4 to 10 or more sensors within the same
diffracted by the smoke particles microns, such as that given off by housing, integrated by the detector
onto a photodiode, which senses smouldering fires. A photoelectric electronics or software to give a
the presence of the smoke (see detector would therefore be a good rapid response to a broader range

17
Fire detection systems 8/8/06 11:47 Page 18

Multi-Criteria reaches a set threshold. This type of


Alarm Optical detector would be the first choice in
Alarm
an environment where a smoke
Chamber Value

detector could not be used.


Chamber
Response
In some environments, such as
boiler rooms, fast rates of rise of
temperature can be expected
normally, meaning that there would
Alarm be a risk of false alarms when using
Threshold a rate-of-rise device. In this case a
fixed temperature detector would be
Heat suitable. As their name implies,
Response
fixed temperature detectors give an
alarm once the temperature has
Time reached a preset threshold, most
Figure 17: Photo-thermal detector response commonly 58°C or 78°C for EN54-5
Class AS or BS respectively.
of fires and greater immunity to environments where a smoke
nuisance alarms. The most common detector might generate false
type at present is a combination of alarms, for example kitchens or
optical beam detectors
optical and rate of rise heat shower rooms. Optical beam detectors work on the
sensors, which can give a response principle of projecting a beam of
to fast flaming fires similar to that of Rate of Rise heat detectors will light across a room, which is
ionisation detectors. Other sensor alarm if the temperature rises very attenuated when smoke is present
combinations are also available. quickly, or if the temperature thus allowing an alarm to be given

CO detectors Up to 100M

A recent addition to BS5839 is CO


detectors. These generally use an
electro-chemical sensor to detect
carbon monoxide given off by
Beam
incomplete combustion. They attenuated by
Reflector
Combined smoke plume
provide reliable detection of
Up to 25m height

Emitter /
Receiver Unit
incipient fires whilst giving good
assurance against nuisance alarms.
However the chemical cells used in
these detectors have a limited life
span, and they cannot detect fast
burning fires due to the low CO
levels produced.

heat detectors
Heat detectors are normally used in Figure 18: Operation of reflective type optical beam smoke detector

18
Fire detection systems 8/8/06 11:47 Page 19

(Figure 18). There are two forms of Since an optical beam detector arenas, warehouses and
beam detector: emitter and receiver senses smoke across the entire shopping malls.
separate (single path), requiring smoke plume, it tends to be less
separate wiring both to the emitter affected by smoke dilution as the Beam detectors are more complex
and receiver, and reflective in which ceiling height increases than point to install than ordinary point smoke
the emitter and receiver are type smoke detectors. In addition, a detectors and it is advisable to
mounted in the same box, and the single beam detector can protect a consult an application guide for the
beam is shone onto a reflective large area; hence they are use of projected beam smoke
material at the far side of the room particularly suitable for protecting detectors before considering the
(dual path). large high rooms such as sports use of these detectors.

Detector type Application Not suitable for

Ionisation smoke General purpose smoke detector Areas subject to smoke, steam,
detector – better for fast flaming fires dust or dirt during normal use

Optical smoke General purpose smoke detector Areas subject to smoke, steam,
detector – better for smouldering fires dust or dirt during normal use

Photo-thermal multi- General purpose detector – good Areas subject to smoke, steam,
criteria detector for smouldering and fast flaming fires dust or dirt during normal use

Optical beam smoke Large and high rooms Areas subject to smoke, steam,
dust or dirt during normal use

Rate of rise heat Areas subject to smoke, steam, dust Areas subject to rapid changes
detector of dirt during normal use of temperature or temperature
over 43ºC

Fixed temperature Areas subject to smoke, steam, dust Areas subject to temperatures
detector (58ºC) or dirt and rapid changes of over 43ºC
temperature during normal use

High temperature Areas subject to smoke, steam, dust Areas subject to temperatures
fixed detector (78ºC) or dirt and temperatures over 43ºC over 70ºC
during normal use

Figure 19: Selection of fire detectors

19
Fire detection systems 8/8/06 11:47 Page 20

location and spacing of


automatic fire detectors
5.3
m It is important to consult applicable
m
7.5
local and national standards when
choosing the spacing and location
of fire detectors. The following
information is intended only as a
guide to the location and spacing
of detectors. There is currently no
European standard available;
hence this guide is based on
7.5m 3.7m
BS5839 part 1, 2002.

5.3m 10.5m location and spacing of


Standard Smoke Detector Spacing Standard Heat Detector
Spacing
point fire detectors on
flat ceilings
Figure 20: Simple spacing plans for smoke and heat detectors
On a flat ceiling with no
obstructions, the radius of
protection of fire detectors is 7.5m
for a smoke detector and 5.3m for a
heat detector, and detectors should
13m be mounted a minimum of 0.5m
from a wall. Some analogue
multi-criteria detectors have a heat
sensor only function, switched by
the control panel, typically used to
reduce the possibility of false
alarms during daytime when a
building is occupied, reverting to
11.25m

multi-sensor operation at night time.


If this type of operation is
employed, the radius of protection
for a heat sensor should be used.
Figure 20 gives a simple spacing
60 ° plan based on these figures,
however it should be noted that this
might not be the most efficient
60 ° layout for a given site; for example
in larger areas, it is also possible to
use a staggered layout, see figure
21, which may reduce the number
of detectors required. In practice,
the layout of the room must be
Figure 21: Alternate smoke detector spacing plan for protecting large areas considered to obtain the most
efficient detector layout.

20
Fire detection systems 8/8/06 11:47 Page 21

ceiling height requirement is met, but care needs If the depth of an obstruction such
Smoke or heat detectors can only to be taken if the detectors are to as a beam is less than 10% of the
detect fires once a certain amount be stood away from the roof, for height of the ceiling, but greater
example mounting on an open than 250mm deep, then detectors
of smoke or heat has reached the
lattice suspended ceiling. should not be mounted any closer
sensor. As the height of a ceiling
than 500mm to the obstruction.
increases, the time taken for smoke
or heat to reach a sensor will Another problem that should be
considered is the possibility of Where an obstruction such as a
increase, and it will become diluted
stratification of the air in a room into beam or a light fitting is less than
with clean, cool air. As a result,
hot and cold layers, causing the 250mm in depth, detectors should
maximum ceiling heights are limited
smoke or heat to stop at the not be mounted any closer to the
as indicated in figure 22 below.
boundaries. This particularly affects obstruction than twice its depth
Detector type Maximum high rooms or atria, where beam (see figure 23)
ceiling detectors are often used.
height Stratification is very difficult to Where a ceiling comprises a series
predict, and can vary, even within of small cells, for example a
Point smoke
the same room as environmental honeycomb ceiling, or a series of
detector
conditions change. closely spaced beams, for example
conforming to
floor of ceiling joists, the
EN54–7 10.5m
recommended spacing and siting of
Heat detector ceiling obstructions detectors changes further,
conforming to Ceiling obstructions such as beams dependant on the ceiling height and
EN54–5 Class A1 greater than 10% of the ceiling height the depth and spacing of the
(threshold 58ºC) 9m should be treated as a wall, and will beams. Reference should be made
thus divide a room. Detectors to relevant standards for details (in
High temperature
should not be mounted within the UK BS5839 Part 1: 2002, 22.3.k
heat detector
500mm of such an obstruction. figure 3 and 19).
conforming to
En54–5 Class B
(threshold 78ºC) 6m >10% of Ceiling Height

Optical beam Minimum


500mm
detectors 25m Treat as separate room

Figure 22: Maximum ceiling height for


different types of detector
>250mm
Often, a boundary layer can form <10% of Ceiling Height Minimum
500mm
close to the ceiling, which is free of
smoke and remains cool. To avoid
Normal Detector Spacing, eg. 10.5m max
this, and maximise the probability of for “simple” layout.

detection, smoke detectors should


normally be mounted with their
smoke entry 25mm-600mm below Height < 250mm
Minimum 2 x
the ceiling, and heat detectors height

should be mounted with their heat


element 25mm-150mm below the Normal Detector Spacing, eg. 10.5m max
for “simple” layout.
ceiling. Detector design normally
ensures that the minimum Figure 23: Detector spacing around isolated ceiling obstructions

21
Fire detection systems 8/8/06 11:47 Page 22

partitions and racking sloping ceilings used, in this example 10.5m +18%.
Where the gap between the top of a Where the ceiling is pitched or Where the slope finishes within the
partition or section of racking and sloping, the slope of the roof tends adjusted detection radius, the
the ceiling is greater than 300mm, it to speed the rise of smoke or heat standard distance to the next row of
may be ignored. If the gap is less to the apex, hence reducing the detectors, 10.5m, should be used.
than 300mm it should be treated delay before the detectors are Care must be taken when placing
as a wall. triggered. For sloped roofs with a the next row that no gaps are left in
pitch height greater than 600mm for detection coverage.
To maintain a free flow of smoke smoke detectors, or 150mm for heat
and heat to the detector, a clear detectors, a row of detectors should corridors
space should be maintained for be placed within a maximum vertical
In corridors less than 2m wide,
500mm in all directions below distance of 600mm or 150mm for
detectors should be spaced at a
the detector. smoke or heat detectors
distance of 15m for smoke
respectively from the roof apex.
detectors and 10.6m for heat
Sloped roofs rising less than 600mm
detectors, with the maximum
Max 600mm for smoke detectors or 150mm for
15m dimension to a wall at the end
heat detectors may be treated as a
40°
of the corridor being 7.5m and
18° flat ceiling.
5.3m respectively.
%

Since the smoke or heat tends to


+ m
25
7. .35
9

In narrow rooms and corridors


5
5m

rise faster up the slope, it is


=
7.

permissible to use a greater spacing greater than 2m wide, due to the


for the row of detectors mounted in way that the coverage radii of
=10.5 + 18%

detectors intersect with the walls of


10.5m

12.39m

the apex of the roof: For each


degree of slope of the roof, the the corridor, the spacing between
spacing may be increased by 1% detectors will increase. Figure 25
up to a maximum of 25%. Where, shows how, for a room 6m wide, the
%
+ m

spacing for smoke detectors can be


.5 85
18

as in figure 24, the roof slopes are


=7 8.

unequal the spacing down the increased from the standard 10.5m.
slopes can be unequal, however
Figure 24: Spacing of smoke detectors along the roof apex spacing the
under a pitched roof
stairwells and lift shafts
lesser of the two figures should be
Internal stairwells and lift shafts and
6.88m 13.75m other vertical service ducts through
a building provide a clear path for
smoke to pass between floors of a
building as if they were chimneys.
It is therefore important to
protect these, preferably using
6m

7.5
smoke detectors.
m

All vertical shafts through a building


must be protected by a smoke or
heat detector at the top of the shaft,
Note: Detectors are mounted in the centre line of the room and by a detector within 1.5m of
Figure 25: Smoke detector spacing in corridors greater than 2m wide each opening onto the shaft.

22
Fire detection systems 8/8/06 11:47 Page 23

In internal stairways, a detector extensively through the voids before maintenance intervals, and possible
should be mounted on each main detection, or unless the fire risk in nuisance alarms.
landing (Figure 26). In addition, if the void is such as to warrant
the detectors on the landings are protection. Use of heat and smoke Detectors above a false ceiling may
separated by more than 10.5m, detectors in voids greater than be used to protect the area below it,
intermediate detectors should be 800mm high is dependant on if the false ceiling is perforated
mounted on the underside of the protection category, and fire uniformly across the complete area
the stairs. risk assessment. of the ceiling, with the holes making
up over 40% of the ceiling surface
Detectors should also be fitted into Where they are installed into voids, area, having a minimum size of
any room opening directly onto a a detector's sensing element should 10mm and the false ceiling having a
stairway other than a WC cubicle. be mounted either in the top 10% or thickness of less than three times
the top 125mm of the void space the dimensions of the perforations.
whichever is greater. Although it can
voids and false ceilings
be difficult to install detectors the In all other cases, the areas above
Detectors need not normally be correct way up in void spaces, care and below a false ceiling should be
installed in voids less than 800mm should be taken as incorrect treated as separate, and thus should
deep, unless on the basis of a fire orientation of a detector can lead be protected separately with detectors
risk assessment it is thought that to increased ingress of dirt and below the ceiling, and if necessary
fire or smoke could spread dust, leading to reduced in the void above the ceiling.

1.5M
1.5M
< 10.5M

Figure 26: Detector in stairwells Figure 27: Protecttion of vertical shafts

23
Fire detection systems 8/8/06 11:47 Page 24

lantern lights detector should not be closer than


500mm to any obstruction. Similar
alarm signals
A detector should be mounted in
any lantern light used for ventilation recommendations to above apply to audible alarm signals
or having a height exceeding the application of beam detectors
Audible fire alarm signals must
800mm. The temperature in lantern with sloped ceilings, voids, false
provide a clear warning of a fire to
lights can change rapidly owing to ceilings, walls and partitions and
all those for whom the signal is
heating by sunlight, which means ceiling obstructions.
intended. For category M and L
that rate-of-rise heat detectors
systems this would normally imply
should not be used and heat Where it is likely that people will be
detectors should be protected from all occupants of a building, however
present in an area protected by beam
direct sunlight. in some sites this may not apply, for
detectors, the detectors must be
example in hospitals or rest homes,
mounted at a minimum height of residents might need assistance to
location and spacing 2.7m, and consideration must also evacuate, in which case it may be
of optical be given to the possibility of other sufficient to alert staff.
beam detectors temporary obstructions to the beam
Generally, for an optical beam such as forklift trucks. The general requirement for the
detector mounted within 600mm of volume of audible alarm signals is
a ceiling, the fire detection coverage For further information on the use that they should provide a Sound
is up to 7.5m either side of the beam and mounting of beam detectors, Pressure Level (SPL) of at least
(Figure 28). The beam of the see Beam Detector Guide. 65dB(A), but not more than

Maximum 100m

Maximum
Minimum 7.5m
500mm

Transmitter or
Receiver or
Transmitter/Receiver
Reflector

Maximum
15m

Transmitter or Receiver or
Transmitter/Receiver Reflector

Figure 28: Smoke detector spacing in corridors greater than 2m wide

24
Fire detection systems 8/8/06 11:47 Page 25

Minimum Where it is not possible to place a


65dB(A) sounder within a room, there will be
a loss of approximately 20dB(A)
through a standard door, and
Minimum Minimum 30dB(A) through a fire door.
65dB(A) 65dB(A)

Volume at
Minimum Bed Head
75dB(A)
65dB(A) down

Minimum Minimum
Min 60dB(A)
Area < 60m²

65dB(A) 65dB(A)

Stairwell Warning: Volumes greater than


Min 60dB(A) 120dB(A) will cause damage to
hearing.
Figure 29: General fire alarm sound pressure levels

SOUND REDUCTION AGAINST DISTANCE


120dB(A) throughout all accessible Based on a sounder rated at 1m
0
areas of a building. See figure 29. Sounder
Minimum
85dB(A) -5 dB(A) Reduction
Sound reduction (dB(A)

Exceptions to this general rule are Machinery -10


Generating
as follows: 80dB(A)
-15

-20
• In stairways the SPL may
-25
be reduced to 60dB(A)
-30
0 5 10 15 20
• Enclosures less than 60m2 Distance (Metres)

may be reduced to
Where the alarm is intended to
60dB(A) In open space, as the distance from
wake people, an SPL of 75dB(A) is
a sounder doubles, the sound level
• There is no minimum required at the bed head. Generally
will be reduced by 6dB(A), as
for enclosed areas less this will require a sounder to be
shown.
than 1m2 placed within the room.
• At specific points of It is preferable to use multiple
limited extent the SPL quieter sounders to achieve the
may be reduced to required sound level, rather than a
60dB(A) smaller number of loud devices.
This is to prevent points of
Where a continuous background excessive volume, which may lead
Fire Door Standard Door
noise level greater than 60dB(A) is Reduces by Reduces by to disorientation or damage to
30dB(A) 20dB(A)
present the fire alarm signal should hearing. Two sounders providing
Sounder
be 5dB above the ambient, but not Volume 115 - 30 = 85 - 20 = equal sound levels will combine to
115dB(A) 85dB(A) 65dB(A)
greater than 120dB(A). add 3dB(A) to the SPL.

25
Fire detection systems 8/8/06 11:47 Page 26

visual alarm signals however the build up can still lead


to a risk of false alarms or change in
the detector sensitivity.
25m
The frequency of maintenance
-16dB -23dB 69dB(A) requirements on a detector will
depend on site conditions,
m obviously the dirtier the site the
14 more frequent maintenance will be
required. The optimum frequency for
a given site should be determined
12.6m

over a period of time after the


63 + 3
0dB 85dB(A) commissioning of the fire system.
= 66dB(A)
Some detectors (smoke, heat, or
m multi-criteria) are designed such
14 that they can be easily dismantled
for maintenance. Normally it is
sufficient to use compressed air or
62 + 3
a vacuum cleaner to remove dust
-16dB = 65dB(A) 69dB(A) from the detector chamber.
Note: dB(A) figures are for example only. Left side represents attenuation;
right side indicates typical sound pressure level Once maintenance on a fire
detection system has been
Visual alarms are required in order to positioned so that any alarm is completed, it should be re-tested.
satisfy the Disability Discrimination clearly visible from all locations
Act (DDA) as well as being used in within the area protected.
areas of high background noise routine
where hearing protection is likely to
be worn. Just as audible alarms maintenance functional
should be placed throughout all
accessible areas of a building, of fire testing of fire
visual alarms should be placed such detectors
that they can be seen in order to detectors BS5839 Part 1: 2002 gives a
alert the hearing impaired. Caution: Prior to carrying out any range of recommendations
maintenance or testing on a fire alarm regarding routine testing of a
Visual alarms should be clearly system, the relevant authorities and fire detection system.
distinguishable from other warning staff should be notified.
lights, preferably red and should A weekly test should be carried out
flash at a rate of 30 to 130 flashes Over time, the sensitivity of a smoke on a fire detection system by
per minute. The recommended detector can change owing to a activating a manual call point to
mounting height is above 2.1m, build-up of dirt in the detector ensure that all fire alarm signals
however they should not be chamber. In most modern detectors operate correctly, and that the
mounted closer than 150mm from this effect is slowed by the inclusion appropriate alarm signals are clearly
the ceiling. They should be of drift compensation functions, received. This test should be carried

26
Fire detection systems 8/8/06 11:47 Page 27

out at approximately the same time


each week, using a different call
point in rotation.

In order to comply with BS5839 Part


1: 2002, periodic inspections,
servicing and functional tests of the
fire alarm system should be carried
out at intervals determined by an
assessment of the site and type of
system installed, not normally
greater than six months.

It is recommended to perform
regular functional tests on all fire
detectors annually. These annual
tests may be carried out over the
course of two or more service visits
during the twelve-month period.

Codes and standards (in the UK


BS5839 Part 1:2002, Section 6) now
require functional tests to introduce
smoke through the smoke detector
vents and into the sensing chamber.
It also calls for heat detectors to be
tested by means of a suitable heat
source, and not by a live flame. CO
fire detectors now also need to be
functionally tested by a method that
confirms that carbon monoxide can
enter the chamber.

Many installers use a set of


equipment that consists of a
complete range of test tools that
locate on the end of the pole in
order to aid compliance with codes.
Tools exist for testing smoke, heat,
and CO fire detectors, whilst also
enabling them to be accessed and
removed at height.

Using functional test equipment,


along with those maintenance tools
should ensure that the system
remains at its optimum operation for
many years.

27
Fire Systems

Safety, Integrity and Heritage


manufactured to meet every major
largest manufacturer and supplier of solutions. These include everything from international approval, including LPCB,
VdS, UL, ULC and BOSEC/ANPI.
400 Engineered Systems Distributors
worldwide, and regional support on addressable systems, to advanced
network and integration packages. As a
manufacturing leader, serving customers
to meet our customers’ requirements.
With over 50 years of experience, we is dedicated to the highest standards
have the reassurance of working with a
offer unrivalled specialist knowledge and of service and product quality. Our
company of global standing that provides
products designed to meet all needs. operations are accredited to ISO 9001
and our products are designed and

Charles Avenue T: +44 (0) 1444 230 300


Burgess Hill F: +44 (0) 1273 376 894
W. Sussex
RH15 9UF

local distributor

You might also like