You are on page 1of 4

ISD 80/83/95/96/110 K-DN (c/w SAT-2 Controller)

Ducted Split System Installation &


Indoor Units Maintenance
Fig. 1 Dimensions (mm) ISD 80K, 83K, 95K, 96K, 110K GENERAL
These ISDSK-DN indoor units are designed
PROJECTION Not to Scale MODEL A B C D E F to be coupled with the OSASRK outdoor
D ISD 80K 570 125 747 805 835 190 units. The '-DN' indicates the unit is supplied
ISD 83/95K 660 175 836 895 925 230 complete with SAT-2 room temperature
controller and safety drain tray.
ISD 96/110K 787 240 962 1020 1050 290
C Units must be installed in accordance with
FIXED MTG CTRS
50 all national and local safety codes.
REFRIGERANT
CONNECTIONS Combinations
Net Weight
One ISD 80K with one OSA 80RKSH
ISD 80K 36 kg
One ISD 83K with one OSA 83RKSH
500 MIN. CLEARANCE

500 MIN. CLEARANCE

ISD 83/95K 39 kg
One ISD 95K with one OSA 95RKSH
ISD 96K 40 kg
482 ELECTRICAL One ISD 96K with one OSA 95RKSH
MOUNTING BOX ISD 110K 40 kg
CENTRES One ISD 110K with one OSA 110RKSH
One ISD 110K with one OSA 110RKTH
Options
FAN ACCESS VIA 1. Filter Box c/w polypropylene net filter
REMOVEABLE BASE
& DRAIN TRAY
2. Spring Mounting Kit
B 400 F 3. Electric Heater Box
ELECTRICAL 4. Supply & Return Air Plenums
ELECTRICAL BOX
ACCESS
CONDUIT HOLE 60 60 5. SAT-2 Accessories (refer overleaf).
PANEL 30 30
(BOTH ENDS)

225 SAFETY DRAIN TRAY


420 OA 335
The unit is supplied with a safety drain tray
170
to protect your ceiling against accidental
60 damage. The safety drain tray is best
secured to the ISD unit after the unit has
DRAIN 19 OD
E been suspended in the ceiling, however it
OVERALL 650 OA
is possible to fit it before if circumstances
make this easier.

Fig. 2 Spring Mounting Fig. 3 Solid Mounting


AIR FILTRATION / FILTER BOX (Option)
MOUNTING ROD Tighten As air filtration requirements vary, filters are
LOCKNUTS not supplied with the unit. Filters should
FOR
STRENGTH ideally be installed on the return air side of
the unit, no closer than 500mm from the
back of the unit and easily accessible for
MOUNTING
RECOMMENDED BRACKETS cleaning. To maximise the efficiency of air
MOUNTING SUPPLIED flow, the return air filter should be twice the
SYSTEM
(OPTIONAL area of the ISD unit's return air spigot/s. If
EXTRA) efficiency is less of a concern a Filter Box is
available.
The Filter Box is installed by unscrewing
the return air spigot and replacing it with
the Filter Box's filter-integrated spigot. The
filter may be accessed from either side of
this spigot. This new spigot has a depth of
135 mm, instead of 60 mm.
Fig. 4 Condensate Drain
100 mm VENT PIPE Note: The Safety Drain Tray
APPROX. FOR LONG
CONDENSATE does not require trapping. ELECTRIC HEATER BoX (Option)
UNIT DRAIN RUNS The Electric Heater Box is installed by
50 mm unscrewing the supply air spigot and
100 mm
MINIMUM MINIMUM replacing it with the Electric Heat Box's
APPROX. SLOPE element-integrated spigot. This new spigot
20 mm PER m
(1 IN 50) has a depth of 195 mm, instead of 60 mm.
OPEN A separate page of installation instructions is
'U' TRAP
DRAIN supplied with the Kit.
INSTALLATION Electrical WIRING 6. Check the wall where the Wall Control
Positioning & Mounting The electrical supply required (via the plaque is to be located is flat before
Provide 500 mm minimum clearance to both Outdoor Unit) is specified on the Outdoor fastening the wall mounting plate.
ends of the unit. Unit's wiring diagram. Alternatively, the mounting plate can
If the Electric Heater Box or Filter Box be screwed to a standard wall socket
Electrical work must be carried out by a mounted horizontally.
options are to be used, allow adequate qualified electrician in accordance with local
clearance for servicing. Note: Use low profile (mush) headed
supply authority regulations and the wiring screws to prevent contact with the PCB
If low noise is a critical factor in the diagram. board. Fixing the plate to a distorted
installation, refer to Figure 6 for noise surface may damage the control.
In a free blow or low resistance application,
isolation recommendations. 7. Drill hole in wall to allow cable entry.
beware of exceeding the fan motor's full
It is recommended that the unit be mounted load amp limit (refer Outdoor Unit's wiring 8. Connect the interface lead's lugs to the
using the spring mounting system, supplied diagram). Wall Control board as per the wiring
as an optional extra (Fig.2). This system diagram overleaf.
minimises transfer of vibration into the Note: The SAT-2 Controller automatically
9. Ensure the interface lead is run
building structure. switches the indoor fan off during de-ice,
separately and away from main
therefore no additional wiring is required to
If a more rigid installation can be tolerated, power supply wires, including the
achieve this result.
then suspend the unit from four threaded interconnecting cable. When installing
rods (not supplied) attached to the ceiling. cabling, trim any excess length to suit
INDOOR FAN SPEED
Four 'L' shaped brackets are supplied on the your location.
The fan speed can be set to LOW, MED, or
unit to facilitate this method. These brackets 10.Fill around the interface lead with foam
HIGH - whichever best suits the application.
must first be unscrewed, reversed and or cover hole with PVC tape to prevent
If the air returning to the indoor unit is draft from wall cavity affecting control
resecured to enable rod attachment.
regularly expected to be above 50%RH, operation. Do not use aluminium duct tape.
The unit has a built-in sloping drain tray, then the coil face velocity should be limited 11. Secure the Wall Control body to the
therefore mount it level. to be 2.5 m/s or less (refer Air Handling mounting plate by replacing the locking
When finally positioned, tighten the lock graph in Technical Data pamphlet). screw removed earlier.
nuts on the mounting rods from above and High humidity levels can occur in tropical or 12.Replace the ISD electrical box cover.
below the mounting flange to give a firm subtropical conditions, and/or when heavily
installation (see Fig. 3). moisture laden fresh air is introduced. Select Remote Air Temperature Sensor/s
a fan speed that avoids water carry-over (option)
Condensate Drain problems. The air temperature sensor is by default
The condensate drain should be trapped located in the Wall plaque. Optional remote
outside the unit cabinet. The trap should air temperature sensors are available so that
have a vertical height of at least 50 mm. SAT-2 CONTROLLER the measurement of the room temperature
The drain should have a slope of at least The following components are supplied in a can be taken away from the wall plaque,
1 in 50 and must not be piped to a level box taped inside the return air spigot: eg. elsewhere in the room or in the return
above the unit drain tray. (Refer Fig.4). 1. SAT-2 Wall Control plaque, including wall air duct.
For long condensate pipe runs, fit a vent mounting plate. Remote sensor's can be plugged directly
pipe near the drain trap. The top of the vent 2. 10 m interface lead (electrical box-to- into the Controller board (PCB). This
pipe must be at least 100 mm above the ISD plaque). board accepts up to four sensors which
unit's drain tray. 3. User's Operating Instructions booklet. are designated as 'zones' one to four. The
4. Lithium CR2032 battery (3V). first return air sensor will automatically
It is essential that the drainage system
Optional replace the Wall Control sensor and should
for the evaporator is checked by pouring
1. Remote return air sensor (in box). be located in the same room as the Wall
water in the drain tray and seeing that it
2. Remote return air temperature sensor Control. The Controller will always use the
discharges at the end of the drain and does
lead; 1.5, 6, 12 or 25 m. average of the zones selected. Refer to the
not overflow the drain tray.
3. 20 m extended interface lead separate installation instructions supplied
Note: The built-in drain tray can be (electrical box-to-plaque). with the PCB for further details.
removed for cleaning (or fan access) by first 4. ISD indoor unit–to–OSA outdoor Ensure all remote sensor wires are run
removing the unit's base. unit interconnecting lead; separately and away from main power
12.5 m or 25 m; 7 core. supply wires, including the interconnecting
INDOOR–OUTDOOR UNIT 5. SAT-2 Zone Control PCB. cable.
Connections 6. Zone Control 24V transformer.
Refer to the relevant OSA Outdoor Unit 7. Additional SAT-2 Wall Control plaque.
'Installation & Maintenance' pamphlet for 8. Infra red remote control.
piping instructions. For wiring connections, SAFETY DRAIN TRAY
refer to the Outdoor Unit wiring diagram in The safety drain tray is best secured to the
Installation ISD unit after the unit has been suspended
conjunction with the ISD wiring diagram in The SAT-2 Controller PCB is supplied pre-
this pamphlet. in the ceiling, however it is possible to fit it
installed in the ISD unit's electrical box. before if circumstances make this easier.
1. Isolate the ISD unit from power supply, 1. Unscrew the supporting brackets from
REFRIGERATION PIPING
then remove electrical box cover. their temporary shipping position, inside
Pipe Connection Sizes (mm OD) & Type
2. Remove the SAT-2 box supplied taped the drain tray, and retain the screws.
Model Liquid Suction inside the return air spigot. 2. The drain tray has pre-drilled holes
ISD 80K 10 (3/8") sweat 16 (5/8") sweat 3. Remove the Wall Control's interface designed to align with the screws on the
lead from this box and connect the bare unit. One at a time, remove a screw from
ISD 83/95K 10 (3/8") sweat 16 (5/8") sweat
wired end of the interface lead to the each bottom corner of the ISD unit and fit
ISD 96/110K 10 (3/8") sweat 19 (3/4") sweat terminal block on the SAT-2 Controller a bracket using the same screws.
board (refer wiring diagram). Trace the 3. Position the drain tray’s pipe exit so it is
The ISD is shipped from the factory with
remaining length of the lead to the Wall at the same end as the ISD unit’s drain
a pressurised holding charge of nitrogen.
Control's intended location. pipe exit.
Immediately before removing any brazed
4. Remove the Wall Control's backing plate
pipe connection's seal, reduce the holding 4. Supporting the drain tray from
by using a small screw driver to remove
charge to atmospheric pressure. underneath, then secure the drain tray to
the single screw at the bottom edge of
Warning: Failure to do so may cause injury. each bracket using the supplied screws.
the plaque.
cont'd...
Refer to the Outdoor Unit 'Installation & 5. Install the Lithium battery, supplied loose,
Maintenance' pamphlet for evacuation positive (+) side up in the Wall Control's
procedure and piping requirements. battery holder.
5. Connect the drain pipe to a suitable 2. Check that the air filter (if fitted) is clean. Six Monthly
drain line with an appropriate slope to 3. Check that the fan runs freely without 1. Check condensate drain and safety drain
allow free drainage. This drain line does vibration. tray for free drainage.
not require trapping. Test the drain with 4. Check condensate drain and safety 2. Check heat exchanger coil; vacuum or
water to ensure it clears safely. drain tray for free drainage. brush clean as necessary.
DO NOT let the ISD unit’s condensate drain 3. Check the tightness of the fan.
Refer to Outdoor Unit Installation
exit into this safety drain tray. 4. Check that fan motor is free running.
Instructions in order to complete the start-
5. Check tightness of electrical connections.
up and commissioning procedure for the
ISD/OSA Systems 6. Check air supply at diffuser outlets.
complete air conditioning system.
with Electric Heater BOX
Demonstrate the SAT-2 Wall Control to the WARNING
Replace the systems external fuse with
owner/user, after having first thoroughly This unit is designed for use ONLY with the
the size recommended in the table on the
familiarised yourself with the User's refrigerant HFC­-410A (R410A). The use
Outdoor Unit's wiring diagram.
Operating Instructions. This page is to of other refrigerants is NOT authorised or
Note: Tandem indoor units with electric heat remain with the owner/user. approved by the manufacturer and may
may require greater fuse sizes on the power
cause operational problems such as poor
supply. MAINTENANCE performance and efficiency, loss of capacity,
DIP switch 2 on the SAT-2 Controller PCB, Weekly For First Four Weeks degradation of materials and refrigerant
located in the ISD electrical box, must be 1. Check air filter (if fitted); vacuum clean as leaks.
set to 'On' (refer wiring diagram). necessary. The use of flammable or explosive
2. Check condensate drain for free materials as a refrigerant creates the
COMMISSIONING drainage. additional risks of fire and explosion
Indoor Unit Monthly which may result in property damage,
1. Check that the thermostat is Check air filter (if fitted); vacuum clean as personal injury or death.
correctly wired and set at the desired necessary.
temperature.

Fig. 5 SAT-2 Control Wiring 1.5, 6, 12 m or


25 m LEAD SAT-2 Note
OPTIONAL ROOM WALL The manufacturer reserves
REMOTE CONTROL
RETURN AIR the right to change
SENSOR specifications at any time
10 m or
OSA
20 m LEAD
without notice or obligation.
OUTDOOR UNIT Certified dimensions
available on request.
ELECTRICAL
BOX

ISD INDOOR UNIT This pamphlet replaces the


Refer back page for
previous issue no. 3266
full wiring diagram.
12.5 or 25 m LEAD dated 11/09. ISD 83/96K
added; wiring H.
POWER SUPPLY

Fig. 6 Application Considerations


Recommendations for Noise Isolation FLEXIBLE
- particularly for high static installations: CONNECTION FLEXIBLE CONNECTION
1. Avoid installing units, with non-ducted return air, directly
above spaces where noise is critical.
RETURN
2. Use flexible connections between unit and rigid ducting. AIR DUCT
3. Use generously sized acoustically lined ducts. SUPPLY UNIT
4. If generous duct size is not possible, use turning vanes on AIR DUCT (PLAN VIEW)
bends to reduce air turbulence (regenerated noise).
5. Use 90° bends in ducting to significantly assist in noise
reduction. TURNING
VANES
MINIMUM OF 1 m
25 mm INSULATED DUCT

FLEXIBLE CONNECTION

LINE SUPPLY DUCT WITH SPRING DO NOT ATTACH CEILING WIRES


ACCOUSTIC INSULATION MOUNTING TO OR THROUGH DUCT
FOR NOISE CONTROL SYSTEM
ALTERNATIVE
RETURN AIR BOOT
FOR SAME EFFECT
INSTALL INSULATED
NOISE ISOLATION
BOOT & FILTER WHERE
SOUND IS CRITICAL
SUPPLY AIR DUCT UNIT
DOUBLE LAYER OF
PLASTER BOARD

SUSPENDED CEILING
SUPPLY AIR RETURN AIR GRILLE LOCATED ALTERNATIVE FILTER LOCATION
GRILLE AWAY FROM UNIT TO MINIMISE WITH SWING OPENING GRILLE
NOISE TRANSMISSION FOR EASY SERVICING
01/10 Pamphlet No. 3292 © temperzone limited 2009

You might also like