. 20
EYER IMENT
Pump motor characteristics
OBJECTIVES
1, Understanding the dead-range effect in a DC motor.
2. Studying effects of the dead range on control operation.
3. To study a method for solving the problem of dead range.
REQUIRED EQUIPMENT
See page 25
PREREQUISITES
- Knowledge of constant-f1eld DC motor operation.
THEORETICAL BACKGROUND
The armature of the constant-field DC motor used in the experimental setup
receives its current through carbon brushes. ‘The torque available at the
motor shaft is proportional to the armature current.
To overcome internal mechanical friction, and start rotation, a certain
initial current must be supplied. Therefore, if the voltage applied to the DC
motor is slowly increased from zero, the motor will not rotate until a certain
minimum voltage value is reached. The range below this level is called the
“dead range”.
The “dead-range” effect is non-linear in nature and causes instability in the
closed-loop behaviour. For example when a deviation between the measured and
the reference level is detected, an instruction may be given by the control to
312
actuate the pump, but to no effect; the motor will start’ only at a certain
higher deviation and will stop before the entire deviation has disappeared. |
The experiment studies this case and the curative measures required. :
Before starting, fill the lower tank (reservoir) with water up to about Sem
from its top edge, and then f{11 tank A with water up to the manual valve
level.
PROCEDURE OF THE EXPERIMENT
1. Open the manual valve in tank A, to the maximum (0°).
“On the control unit, set the POWER switch to ON, Set switch S1 and $3 to
OFF, and switch S2-to A.
Adjust level reference output for a reading of 1V on voltmeter M2.
Connect level reference output to the power buffer input (see Fig. 15).
5. Increase level reference output voltage slowly and record the voltage at
which the motor starts rotating. This voltage is 6V.
‘ pottTtaO 7 4 SONS, nour |
pioirat
CONTROL,
FIGURE 15: Measurement of Motor Operating Voltage
6. Restore level reference output voltage to OV and repeat step 5.
7. Restore level reference output voltage to OV.
Disconnect the level reference output from the power buffer input.
329%
10.
le
12.
13.
la,
15.
16.
22
Connect level reference output to the pump interface input (see Fig. 16).
Lever
REFERENCE
tr
VREF
biairat
conTrow,
FIGURE 16: Measurement of Pump Interface Characteristic
Using the external DMM, measure the pump interface output voltage.
Increase the level reference output voltage as per Table 1 and record,
the pump interface output voltage.
9
Restore level reference output to OV.
Connect pump interface output to pump power buffer.
Slowly increase level reference output and record the initial voltage at
which the motor starts rotating. This voltage is 0.5V.
a
Disconnect all connections made on the control unit.
Set the POWER switch to OFF.
Level reference Output (Vy) {0 ]1]2|/3]/4]5]6]7)8]9] 10
Pump Interface
Output (V)
TABLE 1: Pump Interface Output as Function of Level Reference Voltage
3323
ANALYSIS OF RESULTS
Draw a diagram of pump interface output as a function of the input.
Pump
INTERFACE
OUTPUT 4
ww)
i oy _ piouteur
° wv)
FIGURE 17: Pump Interface Output Voltage vs Input Voltage
J
QUESTIONS
1. What is the dead range of the pump motor?
2. How can this range be reduced?
3
34
Does the pump interface cancel the dead range?|
axPaRlualy 2
Pump characteristics
OBJECTIVES
Precise measurement of liquid flow rate.
2, Establishment of the pump calibration diagram.
Evaluation of pump gain from the static characteristic.
REQUIRED EQUIPMENT
See page 25
PREREQUISITES
- Knowledge of the meaning of static gain and its evaluation from the
static characteristics of an element.
THEORETICAL BACKGROUND
Liquid flow rate is the volume of liquid passing a pipe cross-section for one
time unit. The flow rate is measured in volume unit per time units, eg
m/sec.
There are several methods of measuring flow rate, some direct and some
indirect.
One of the most accurate methods is to measure the time required to fill a
tank of known volume with the flowing liquid. The ratio of volume to time
will give the average flow rate during this time.
If the tank has a constant cross-section A, the rate of height change may be
3525
measured instead. Using this value and the known cross-section area, the flow
rate may be calculated.
PROCEDURE OF THE EXPERIMENT
1, Turn off the output valve of tank A.
2. On the control unit, connect the level reference output to the pump
interface.
3, Set the POWER switch to ON. Set switches S1 and $3 to OFF, and S2 to "A".
4, Adjust level reference for 1V on M2.
5. Connect the pump interface output to the power buffer input (see Fig. 18).
The pump now starts filling the tank.
6. Watch the water level closely. When the level has reached 4,5 cm, start
the stop watch and measure the time required to raise the level up to 17
cm. Record the result in Table 2.
Pune
Hv POWER
IWTERF ACE: fOrren rue
Leven,
REFERENCE
et
By)
=~ 1
74 f°
is
. Te
oisirat,
conTROL,
Yaer
+2av
pioiraL
CONTROL
FIGURE 18: Pump Characteristics
7. Disconnect the interface output from the pump buffer and turn the output
valve on, letting the water level drop down to 4-5 cm.
Turn the output valve off.
9. Repeat steps 5-8 for all voltages listed in Table 2, and record the
results.
10. Set the POWER switch to OFF.
11, Disconnect all connections made to the control unit.
364
|
i
26
Pump Voltage Filling Volume Filling Time Pump Flow Rate
Ww) (m3) (sec) (em3/sec)
0.5
i
rs
TABLE 2: Flow Rate as a Function of Pump Voltage
ANALYSIS OF RESULTS
1. Fill all columns of Table 2.
2. Draw the pump calibration diagram in Fig. 19.
3. Evaluate the pump static gain from the calibration diagram.
QUESTIONS
how can it be improved?
What are the factors affecting the flow rate measurement precision and
What are the units in which the pump's static gain is measured?
3738
caw
mae
lomirs0c)
24
80}
rH
a
7 PUMP
VOLTAGE
mw
FIGURE 19: Pump Calibration Diagram
eran neenmenenanmeneastne en
emeorneen28
SUP UWE :
Characteristics of the level
measuring unit
OBJECTIVES
1+ Measurement of the level sensor calibration diagram.
2. Evaluation of the level sensor gain from the static characteristics.
REQUIRED EQUIPMENT
See page 25
PREREQUISITES
> Knowledge of principles of floating bodies.
~ Understanding of rotary potentiometer operation.
THEORETICAL BACKGROUND
The float is a widely used element in level measurements. Its principle of
operation, Archimedes Law, is based on the fact that a body floating in a
jpautd loses part of its weight equal to the weight of the liquid volume it
displaces. This principle also determines how deep the body submerges - just
enough to displace its own weight of liquid. The float will always follow the
liquid surface, whether rising or falling since its submersion is invariable
and is independent of the liquid level.
To make usé of the float for level measurement, a wire {s wound around a
pulley, and one end is connected to the float. A counterweight 1s connected
tes other end of the wire. The weight must be lighter than the float, and
tts function is to keep the wire under tension. The pulley rotates
potentiometer which has a constant DC voltage actoss its outer terminals. The
potentiometer then produces a variable voltage at its middle terminal
according to the float position (see Fig. 20).
3927
input ourpuT =
VOLTAGE VOLTAGE
FIGURE 20: Rotary Potentiometer
The level sensor is an element of the control loop. Since its response ts
essentially instantaneous, only its static gain must be known. The static
gain can be determined from the characteristic diagram obtained in this
experiment.
PROCEDURE OF THE EXPERIMENT
1. Set the POWER switch to ON.
2. Open the output tap of tank A and drain off the water.
Close the tap.
4. Set switches $1 and $3 to OFF and switch $2 to (analog)
Adjust level reference for a reading of 12V on M2.
6. Connect the elements of the control unit according to Fig. 21:
- Connect the output of the level sensor buffer to the external Di.
= Connect the output of level reference jack to the input of the pump
interface.
- Connect the pump interface output to the input of the power buffer.
+ When the water level in tank A reaches 10 cm, disconnect the pump
interface output from the input of the power buffer.
. If the water level exceeds 10 cm, open the output tap of the tank and
drain off the excess water.
9. Read the output voltage of the level sensor potentiometer by means of the
external DMM.
The output voltage should be 6V. If it differs from this value, lif
4010.
i.
12:
13.
30
v
teve
SENSO"
1 extenwat
- oun = i
pune Power rump
INTERFACE. BurFeR ae
tiey
ever
REFERENCE
¥
aa)
FIGURE 21: Measurement of Level Sensor Characteristic
counter-veight and rotate the pulley to obtain the required voltage.
Connect the pump interface output to the power buffer. Wait until the
water level reaches 21 cm, then disconnect the previously-made connection.
C WRN)
Open the output tap of the tank and slowly drain off the water, until the
level is exactly 20 cm. Make sure that the water level does not fall
below this value.
Read the output voltage of the level sensor potentiometer and record its
value in Table 3.
Level (cm) 20} 18] 16] 14] 12] 1] 8 | ofa fe
Level sensor
voltage
TABLE 3: Level Sensor Characteristic
Drain off water until the level decreases by 2 cm and record in Table 3
the level sensor voltage.
41Bi
14, Repeat step 13 for each level given in Table 3.
15. Set the POWER switch to OFF.
16. Disconnect all connections made on the control unit.
ANALYSIS OF RESULTS
1. Draw the level sensor characteristic in Fig. 22.
LeveL y
SENSOR
VOLTAGE
mw
/ >
° LEVEL (em)
FIGURE 22: Level Measuring Unit Characteristic Diagram
2, Evaluate the static gain of the level sensor from Fig. 22.
QUESTIONS
1, What will be the effect of adding liquid on the float level?
2. Will the liquid temperature affect measurement precision in the float
method?
'
42—
i
i
smsvenene 32
EXERT IMENT |
Measurement of the static
process characteristics
OBJECTIVES
1. Analysis of turbulent flow.
2. Measurement of the liquid level static control characteristic ‘in a tank
Measurement of the static gain of a non-linear system by linearization
around the operating point. eet sbvanes
che
np
REQUIRED EQUIPMENT
See page 25
PREREQUISITES 7
- Knowledge of basic Liquid flow principles.
- Understanding hydraulic resistance and its experimental evaluation:
THEORETICAL BACKGROUND
In a Liquid flow system, wherein liquid flows out of a tank and the output
flow, qo, passes through a constriction, R, (see Fig. 23), the liquid
level in the tank, h, as a function of inflow rate depends on the head losses
along the constriction. Since water flow in non-capillary pipes is turbulent,
these losses are non-linear.
As derived in the literature, the flow rate ist
ay = k Via (40)
43—)
a
Where:
a
hb
k
8
For
32
FIGURE 23:
Container Liquid
Level System
—>
flow rate within the constriction
liquid level in the tank
- a constant depending on constriction shape and dimensions.
- gravitational acceleration on earth.
control purposes, Linearization around the operating point is required.
The static gain, R, is defined as R = h/q, namely, the ratio between level and
constriction flow rate.
ast
For the purpose of linearization, R will be defined
R = bh/Aq (a)
which is the ratio between the level change and the resulting flow rate change
in the constriction at the operating point.
PROCEDURE. OF THE EXPERIMENT
44
Adjust the tank's output valve for maximum opening.
On the control
unit, connect level reference output to the pump
interface, and the output of the pump interface - to the input of the
power buffer. Also connect the level sensor buffer output to external
DMM (see Fig. 24).
On the control unit, Set the POWER switch to ON, $1 to OFF, S2 to A, and
83 to OFF.
Adjust level reference for a reading of 12V on M2.
Wait about 10 minutes for the level to stabilize. Measure and record the
level in Table 4,
Level changes may also be observed by observing the3%
changes in the voltmeter reading.
wv aurren
beven Wvsl.e7em
Sengon 4
exrenwar
(°) 0 pee
Levew iP O .
it t
REFERENCE
sz
=
2 Re ihe
overrat
mn consi
we] od
oierrat
CONTROL
FIGURE 24: Measurement of the Static Process Characteristics Experiment
6. The level should stabilize in the range of 17 to 20 cm. If the level
exceeds 20 cm; reduce the tap angle by 5°. Conversely, if the level
stabilizes below 17 cm, increase the angle by 5°.
If necessary, continue changing the tap position until a position is
found at which the level stabilizes within the required range. Do not
change the tap position in the following experiments
7. Repeat steps 4,5 for all voltages listed tn Table 4.
8. On the control unit, set the POWER switch to OFF.
9. Disconnect all connections made on the control unit.
ANALYSIS OF RESULTS
1. Fil all columns of Table 4.
2. Draw the process characteristic diagram in Fig. 25.
3. Calculate the static gain in the operating range of 10-14 cm.
453S
Punp interface Input
voltage (V)
Flow rate as per pump
calibration diagram
(cm3/sec)(ftom Table 2)
Final level
(cm)
|
12
TABLE 4: Stable Level as a Function of Pump Voltage
Lever
(em) 4 t
20
=I.
15}
10. +
5
LLL, 1
+
FIGURE 25:
46
oo
ab 80 5
|
80
Process Characteristic Diagram
FLOW RATE
(em3/aec)i
BE
QUESTIONS
is
as
Prove that Ris the static process gain, using both the static gain
definition and the liquid level behavior tn a tank.
In liquid level measurements, a 0,2m level was obtained from a 0.04m?/sec
flow rate.
Evaluate:
a. The constriction constant, k, from the turbulent flow equation.
b. The hydraulic resistance, if the flow rate changes in the range
of 0.10 ~ 0.12 m/sec.
Klom’} = 42)
9800 cm/sec”
47