DESIGN OF PASSIVE SOLAR-ENERGY HEATING SYSTEMS
FOR BUILDINGS
‘A south-facing passive solar collector will be designed for a one-story residence in Denver, CO.
Determine the area of collector required to maintain an average inside temperature of 70°F (21°C)
on a normal clear winter day for a comer room 15 ft (4.6 m) wide, 14 f€(4.3 m) deep, and 8 ft
(2.4 m) high. The collector is located on the 15+ft (4.6-m) wide wall facing south, and the 14-f
(G.3-m) sidewall contains a 12-f? (L.L1 m®) window. The remaining two walls adjoin heated space
and so do not transfer heat, Find the volume and surface area of thermal storage material needed
to prevent an unsuitable daytime temperature increase and to store the solar gain for nighttime
heating. Estimate the passive solar-heating contribution for an average heating season.
Calculation Procedure:
1, Compute the heat loss
The surface areas and the coefficients of heat transmission of collector, windows, doors, walls, and
roofs must be known to calculate the conductive heat losses of a space. The collector area can be
estimated for purposes of heat-loss calculations from Table 8.
Table 8 lists ranges of the estimated ratio of collector area to floor area, g, of a space for latitudes
36°N or 48°N based on 4°F (2.2°C) intervals of average January temperature and on various types
of passive solar collectors. Average January temperatures ean be selected from government weather
data. Denver has an average January temperature of 32°F (0°C). Choosing a direct-gain system for
this installation, read down to the horizontal line for 1, = 32°F (0°C), and then read right to the col-
umn for a direct-gain system. To find the estimated ratio of collector area to floor area, use a linear
interpolation. Thus for Denver, which is located at approximately 40°N, interpolate between 48°N
and 36°N values. Or, (0.24 — 0.20/12 x (40 ~ 36) + 0.20 = 0.21, where 0.24 and 0.20 ate the ratios
at 48°N and 36°N, respectively; 12 is a constant derived from 48 — 36; and 40 is the latitude for
which a ratio is sought.
TABLE 8 Estimated Ratio of Collector Area to Floor Area,
1 (65 ~ tf, for 36 to 48° North Latitude”
Average January
temperature —-Dieot gain Water wall Masonry wall
1,°BCC) 8 8 8
20(-6.2) 027-032 OSH064 069-081
24-44) 025-029 049-058 0.63-0.74
28 (-2.2) 022-027 0440.52 0.56-0.67
32 (0) 020-024 = 030.047 0 50-0.60
3642.2) 017-021 035-041 044-053
40.4.4) 015-018 = 030-035 0.38-0.45
HON 013-015 025-030 032-038
Far Sl temperature, use the relation g =f, 18.38 ~ 1 ie
“Bred ona heat loss of 8 Btuiday ft -"F 1058 Wik? KD},Next, find the collector area by using the relation A, = (g)(A,), where A, = collector aren,
FE (m2); g= ratio of collector area to floor area, expressed as a decimal; and A, =floor area, f(r")
Therefore, A, = (0.21)(2.10) = 44 ft? (4.1 m?).
To compute the conductive heat loss through a surface, use the general relation He = UA Ay
where H, = conductive heat toss, Brush (W); U = overall coefficient of heat transmission of the
surface, Bru/(h - £2 . °F)[Wi(m? - KJ; A = area of heat transmission surface, £2 (m®); and At
temperature difference, °F = 65 ~1, (°C = 18.33 —1,), where , = average monthly temperature, *F CC’,
The U values of materials can be found in ASHRAE and atchitectural handhooks.
Since a direct-gain system was selected, the total area of glazing is the sum of the collector and
noncoliector glazing 44 £2 (4.1 m2) + 12 ft? (1.1 m?)=56 ft (5.2 m*), Double glazing is recommended
in ail passive solar designs and is found to have a U valuc of 0.42 Buu/(h - ft? - °F} [2.38 WA(m? - K)|
in winter. Thus, the conductive heat loss through the glazing is H,.= UA Ar = (0.42)(56)(65 ~ 32)
716 Bulb (227.4 W).
‘The area of opaque wall surface subject to heat loss can be estimated by multiplying the wall
height by the total wall Jength and then subtracting the estimated glazed areas fom the total exterior
wall area, Thus, the opaque wall area of this space is (8)(15 + 14) ~ 56 = 176 f (16.3 m2), Use the
same general relation as above, substituting the U value and area of the wall. Thus, U = 0.045 Buu/
(2: £8 *F) [0.26 W/m? - K)], and A = 176 £2 (16.3 m?), Then H..= UA Ar = (0.045\(176)(65 ~ 32) =
261 Btw (76.5 W),
‘To determine the conductive heat loss of the roof, use the same general relation as above, sub-
stituting the U value and area of the roof. Thus, U = 0.029 Btu/(h - ft? °F) (0.16 Wm? K)} and
A= 210 fe (19.5 m2), Then H, = UA Ar= (0.029)(210)(65 — 32) = 201 Btu/h (58.9 W).
‘To calculate infiltcation heat loss, use the relation 1, = Vi AWS5, where V= volume of heated
Space, f¢° (ms); n = number of air changes per hour, selected from Table 9. The volume for this space
is V= (15)(14)(8) = 1680 16 (47.6 mm). Entering Table 9 at the lett for the physical description of the
space, tead (0 the right for 1, the number of air changes per hour. This space has windows on {wo
walls, so n= 1. Thus, H,= (1680\(1)(65 — 32)/55 = 1008 Btuh (295.4 W)
TABLE 9 Air Changes per Hour for Well-Insulated Spaces"
OO
‘Number of air changes
Description of space per hour n
No windows or exterior doors 0.33
Windows or exterior doors on one side as?
Windows or exterior doors on two sides 10
Windows or exterior doors on three sides 1.33,
"Thove figures are based on spaces with weatherstripped doors and windows
‘or sates with storm windows or doors. I the space docs not have these feat,
increase the value listed for n by 50%.
The total heat loss of the space is the sum of the individual heat losses of glass, wall, roof, and
infiltration. Therefore, the total heat loss for this space is H, = 776 + 261 + 201 + 1008 = 2246 Btu/h
(658.3 W). Convert the total hourly heat loss to daily heat loss, using the relation H,, = 2441, where
Hy = total heat loss per day, Bludday (W), Thus, H,, = 24(2246) = 53,904 Buu/day (658.3 W).
2. Determine the daily insolation transmitted through the collector
Use government data or ASHRAE clear-day insolation tables. ‘The latitude of Denver is 39°S0'N.
Since the minutes are greater than 30, or one-half of a degree, the ASHRAE table for 40°N is used.
The collector is oriented dve south. Hence, the average daily insolation transmitted through vertical
south-facing single glazing for a clear day in January is i, = 1626 Bawft? (5132 Wim), or double
the half-day total given in the ASHRAE table, Since double glazing is used, correct the insolation
transmitted through single glazing by a factor of 0.875. Thus, i, = (1626)(0.875) = 1423 Biu/(day - fi?)
(4490 Winn?) of collector.3, Compute the area of unshaded collector required
Determine the area of unshaded collector needed to heat this space on an average clear day in
January. An average clear day is chosen because sizing the collector for extreme or cloudy conditions
wouid cause space overheating on clear days. January is used because it generally has the highest
heating load of all the months.
‘To compute the collector arca, use the relation A. = H.p/(EM,). where E = a rule of thumb for
energy absorptance efficiency of the passive solar-heating system used, expressed as a decimal,
Enter Table 10 for a ditect gain system to find £ = 0.91. Therefore, A, = 53,904/(0.91\ 1423) = 42 ft
G9 m’).
TABLE 10 Enemy Absorptance Efficiency of Passive
Solar Heating Systems
System Efficiency E
Direct gain 091
‘Water thermal storage wall or roof pond 0.6
Masonry thermal storage wall 0.36
Attached greenhouse os
If the area of unshaded collector computed in this step varies by more than 10 percent from the
area of the coltector estimated for heat loss calculations in step 1. the heat loss should be recomputed
with the new areas of collector and opaque wall. In this example, the computed and estimated col-
lector ateas are within 10 percent of each other, making a second computation of the collector area
‘unnecessary.
4. Compute the insolation stored for nighttime heating
To compute the insolation to be stored for nighttime heating, the total daily insolation must be
determined. Use the relation ip = (A-Mé(E), where fp = total daily insolation collected, Btu (1).
Therefore, ip = (42)(1423)(0.91) = 54,387 Bm (57.4 Kd).
‘Typically 35 percent of the total space heat gein is used 1 offset daytime heat losses, requiring
65 percent (o be stored for nighttime heating. Therefore, i, = (0.65)i,, where i= insolation stored,
Bru (). Thus, i, = (0.65)(54.387) = 35,352 Buu (37.3 kd). This step is not required for the design of
thermal-storage wall systems since the siorage system js integrated within the collector.
5. Compute the volume of thermal storage material required
For a direct-gain system, use the formula V,, = i,/(d)(c, MAt MC), where ¥,, = volume of thermal
storage material, 18 (in); d = density of storage matecial, 1b/t dkg/m); c-"= speciic heat of the
material, Bru/(lb °F) [KJickg - KY]; fy = temperature increase of the material, °F (°C); and, C, =
fraction of insolation absurbed by the material due to color, expressed as a decimal.
Select concrete as the thetmal storage matetial. Entering Table 11, we find the density and specific
heat of concrete to be 144 Ib/* (2306.7 ky/m*) and 0.22 Biul(Ib - °F) (0.921 ki/(kg - K)], respectively.
TABLE 11 Properties of Theemal Storage Materials
Density d Specific best 6, Heat capacity
Material Tot? kgfn® Baw °F) Ekg “K)— Bu “F) Km K)
Water 6249990 1.00 62.40 41808
Rock 153 2449.5 022 33.66 2255.2
Concrete 144 23054 023 31.68 21226
Brick 123 1969.2 022 27.06 18130
Adobe 108 1729.1 024 25.92 17366
Oak 48 768.5 037 27.36 1833.1
Pine 3 496.3 067, 20.71 1391.6A suitable temperature increase of the storage material ina TABLE 12_Insolation Absomption
direct-gain systems is At, = + 15°F (48.3°C). A range of +10 Factors for Thermal Storage Matertal
to 420°F (45.6 to 111°C) can be used with smaller increases Based on Color
being more suitable. Select from Table 12. In this space, thermal
‘energy will be stored in floors and wails, resulting ina weighted — _Color/Material Factor Cy
average of C, = 0.60. Thus, Vy, = 35,352/(144)(0.22(15) Black, matte 095
(0.60) = 124 ft (3.5m). Dark blue 091
As a rule of thumb for thermal-storage wall systems, pro- Slat, dark gray 089
vide a minimum of Lf (0.30 m°) of dark-colored thermal stor- Dark green 0.88
age material per square foot (meter) of collector for masonry Brown 079
walls or 0.5 £13 (0.15 m?) of water per square foot (meter) of Gray 075
collector for a water wall. This will provide enough thermal Quarry tile 069
storage material to maintain the inside space temperature fluc- Red brick 0.68,
tation within 15°F (8,33°C) picky Ale, tae
6. Determine the surface area of storage material for a direct- oo ‘060
gain space oe Dark red 0s7
In adircet-gain system, the insolation must he spread over the Limestone, dark 030
surface area of the storage material to prevent overheating. Limestone, light 035
Generally, the larger the surface area of material, the lower Yellow 033
the inside temperature fluctuation, and thus the space is more White 08
comfortable, To determine this area, enter Fig. 15 atthe lower
axis 10 select an aeceptable space temperature fluctuation.
Project vertically to the curve, and read left to the Ay/4, ratio. Ths is the ratio of thermal storage
material surface to collector area, where A, = surface of storage material receiving direct, diffused
or reflected insolation, ft (m). In this example, 15°F (8.33°C) is selected, requiring AslAe = 6.8.
‘Thus, A, = (6.8)(42) = 286 22 (26.5 m’).
This Step is not required for the design of thermal-storage wall systems in which Ay
As /Ac ratio
anusaareaod
® 10 15 20 25 30 35 40
‘Space temperature fluctuation At, °F
bit
28 66 83 Nl B9 167 19.4 22.2
Space temperature fluctuation At,°C
FIGURE 15 Ratio of mass surface area to collector area, (Based on
dasa in DOBICS-D127-2 Passive Solar Design Handhook, vel. 2.)7. Determine the average daily inside temperatures
To verify that the collector and thermal storage material are correctly sized, the average inside
temperature must be determined. Use 1)= 1, + 5+ (ip N65 ~ 1,/Hpy where 1, = avornge daily inside
temperature, °F (°C), and 5°F (2.8°C) is att assumed inside temperature increase owing to intetnal
heat generation such as lights, equipment, and people. Thus, z,= 32 + 5 + (54,387)(65 ~ 32)/53,90 =
T03°F (21.27°O),
To determine the average daily low and high temperatures, use f, = #,—A1/2.5, am 1, f+ Ad/1.67,
where 1, = minimum average space temperature, °F (°C); ty = maximum average space (empervhure,
°F (°C); und At= inside space temperature fluctuation used in step 6. Thus, t, =70.3-- 15/25: 61.31
(17.9°C), and fy = 70.3 + 15/1.67 = 79.3°F (26.27°C).
8. Estimate the passive solar-heating contribution
‘To estimate the passive solar-heating contribution (SHC) for an average month, use SHC, 1004i))
(Dy Hp, where SHC,, = solar-heating contribution of the total monthly space-heating feeds, pet
cent, and p = an insolation factor based on the percentage of clear days, expressed as a deci
‘The value of p = 0.30 + 0,65(S/100), where $= average sunshine for the month, percent, from an
ASHRAE or government map of sunshine for each month. ‘The average January sunshine for Denver is
67 percent. Hence, p = 0.30 + 0,65(67/100) = 0.74. Tlaus for this room in January, SHC,, = 100(54,387)
(0.74Y53,904 = 74.7 percent of the total average space-heating needs are provided by the passive solar-
heating system.
‘To estimate the average annual solar-healing contribution for a building, repeat steps 1. 2, and 7 for
each space for each month of the heating season. Use the collector area computed in step 3 for an aver-
age clear day in January to determine ip for each month unless part of the collector is shaded (in which
case, determine the unshaded area and use that figure). Use SHC, = 100E U,\pXDYEH)(D), where
SHC, = annual passive solar-heating contribution, percent, and D = number of days of the month, The
summation of the heat gains for each space for each month of the heating season is divided by the sum-
mation of the heat losses for each space for each month,
Related Calculations. These design procedures ace suitable for buildings with skin-dominated heat
loads such as heat losses through walls, roofs, perimeters, and infiltration, They are cot applicable
to buildings which have internal heat loads or buildings which are so deep that itis difficult to col-
lect solar heat. Therefore, these procedures generally should be limited to small- and medium-size
buildings with good solar access.
‘These procedures use en average clear-day method as a basis for sizing a passive solar-heating
system. Average monthly and yearly data also are used, If the aciusl weather conditions vary sub-
stantially from the average, the performance of the system will vary. For instance, if a winter day is
unseasonably warm, the passive solar-heating system will collect more heat than is required to offset
the heut loss on that day, possibly causing space overheating. Since passive solar-heating systems
rely on natural phenomena, temperature fluctuation and variability in performance are inherent in the
system, Adjustable shading, reflectors, movable insulation, venting mechanisms, and backup heating
systems are often used to stabilize system performance.
Since passive systems collect, store, and distribute heat through natural physical means, the sys-
tem must be integrated with the architectural design. The actual efficiency of the system is highly
variable and dependent on this integration within the architectural design, Efficiency ratings given in
this procedure are rules of thumb, Detailed analyses of many variables and how they affect system
performance can be found in DOE/CS-0127-2 and 3, Passive Solar Design Handbook, volumes 2
and 3, available from the National Technical Information Service, Alexandria, VA, 22312. The
Passive Solar Energy Book, by Eéward Mazria, available from Rodale Press, Emmaus, PA, examines
various architectural concepts and how they can be utilized to maximize system performance.
Tf thermal collection and storage to provide heating on cloudy days is desired, the collector area
can be oversized by 10 percent. This necessitates the oversizing of the thermal storage material (0
store 75 percent of the total daily heat gain rather than 65 percent, as used in step 4. Oversizing
the system will increase the average inside temperature. Step 7 should be used to verify that this
higher average temperature is acceptable, Oversizing the system for cloudy-day storage is not rec~
ommended for excessively hazy or cloudy climates. Cloudy climates do not have enough cleardays in a row to accumulate resesve heat for cloudy-day heating. This increased collector area may
increase heat load in these climates. Cloudy-day storage should be considered only for climates with
a ratio of several clear days to each cloudy day.
‘Passive solar-heating systems may overheat buildings if insolation reaches the collector during
seasons when heating loads are low or nonexistent. Shading devices are recommended in passive
solar-heated buildings to contro} unwanted heat, Shading devices should allow low-angle winter
jnsolation to penetrate the collector but block higher-angle summer insolation, The shading device
should allow enough insolation to penetrate the collector to heat the building during the Lower-heating-
Toad seasons of autumn and spring without overheating spaces. If shading devices are used, the area
of unshaded collector must be calculated for each month to determine ,. Methods to calculate the
‘area of unshaded collector can be found in The Passive Solar Energy Book and in Solar Control and
Shading Devices, by V. and A. Olgyay, available from Princeton University Press.
Passive solar-heating systems should be considered only for tightly constructed, well-insulated
buildings, The cost of a passive system is gencrally higher than that of insulating and weathesstrip-
ping a building, A building that has a relatively small heat load will require a smaller collection and
Storage system and so will have a lower construction cost. The cost-effectiveness of a passive solar-
heating system is inversely related to the heat losses of the building. Systems which have a smaller
ratio of collector area {0 floor area ate generally more efficient.
‘gnificant decreases in the size of the colicctor can be achieved by placing movable insulation
over the collector at night. This is especially recommended for extremely cold climates in more north-
tern latitudes, If night insulation is used, calculate heat loss for the uninsulated collector for 8 hours
with the daytime average temperature and for the insulated collector for 16 hours with the aighttime
average temperature.
“Table & is based on a heat loss of 8 Btu/(day - 1°) of floor area per °F [Wimn? - K)]. Total building
heat loss will increase with the increase in the ratio of collector to floor area because of the larger areas
of glazing. However, itis assumed that this inerease in heat loss will be offset by providing higher insu-
jation values in noncollector surfaces. The tabulated values correspond to a residence with a compact
plan, 8-ft-high ceilings, R-30 roof insulation, R-19 wail insulation, R-10 perimeter insulation, double
lazing, and one air change por hour. It is provided for estimating purposes only. Ifthe structure under
consideration differs, the ratio of collector area to floor area, g, can be estimated for heat-loss calcula~
tions by using g = h(65 ~ 1,)iy, where hy, = estimated heat loss, Btu/(dlay » ft» °F) {W/n? + K)],
Passive solar heating is nonpolluting znd is environmentally altractive, Other than the pollution
(aig, steeam, and soil) possibly ereated in manufacturing the components of a passive solar heating
system, this method of space heating is highly desirable from an environmental standpoint
Solar heating does not provide carbon dioxide, as does the combustion of coal, gas, oil, and wood.
“Thos, there is no accumulation of carbon dioxide in the atmosphere from solar heating, It is the
accumulated carbon dioxide in the earth’s atmosphere that traps heat from the sun's rays and earth
reradiation that leads to global warming.
Computer models of the earth’s atmosphere and the warming that might be caused by excessive
accumulation of carbon dioxide show that steps must be taken (0 control pollution. Although there is
some disagreement about the true effect of carbon dioxide on global warming, most scientists believe
that efforts to reduce carbon dioxide emissions ate worthwhile, Both a United Nations seientifi
panel ond research groups associated with the National Academy of Setences recommend cxreful
study and tracking of the possibility of global warming,
For these reasons solar heating will receive more attention from designers. With more attention
being paid to the environment, solar heating offers a nonpolluting alternative that can easily be
incorporated in the design of most buildings.