You are on page 1of 2

Linea Modulex3 MX3EG1A

Numerical module for automatic synchronising of generator 90f - 90U - 25

Functions Measurement functions


• The device performs frequency • Voltage and frequency busbar side.
and voltage regulation of a • Voltage and frequency generator
generator, thereafter it executes side.
automatic paralleling with a live • Phase-displacement.
bus-bar (already supplied bus-bar). • Primary voltage values.
Alternatively it permits the
regulation at optimal frequency Recording functions
and voltage values, then executes • Record of the last events (last
automatic paralleling with a dead eight, parallel executed, failed,
bus-bar (non supplied bus-bar). reason) with date and time
For synchronisation, (YY/MM/DD - hh:mm:ss.mmm)
MX3EG1A sends controls that and fault values.
operate on the turbine speed and • Record of the logical status change
on the generator field. (last 32) representing the parallel
When the parallel conditions are sequences, digital inputs included,
positively checked, MX3EG1A with date and time (YY/MM/DD
controls the circuit breaker. - hh:mm:ss.mmm)
• Two inputs, supplied from • Disturbance recording with
generator and bus-bar voltages, record of all input signals and
permit measurement of respective Communication
correlated logical status;
voltages, frequencies and • Rear serial port for connection to
possibility to choose the cause
phase-displacement. Lonwork™ network at 1.25 Mbit/s.
determining trigger and define
• It is possible to configure the logic • Alternatively: serial port RS485
the recording time before and
inputs to receive: synchronisation and Modbus protocol.
after trigger (for a total recording
and parallel requests (with Live-bus time of 2.5 s).
Start_LB or Dead-bus Start_DB), Human Machine Interface
• Record on counters and LED's.
Stop control, circuit breaker • Local HMI with keyboard,
closed (CB52), anomalies, etc. backlit LCD display, 12 LED's,
• The device includes two setting Monitoring and control: 8 of which are freely assignable
groups, switch in operation of digital inputs and outputs to the functions.
groups: from HMI, Digital input • 5 freely assignable inputs (controls, • Local HMI by PC connected
or Communication. blocks, setting group switch). to the front serial port.
• 6 output relays one of which is for • Remote interface by the Local
diagnostic and 5 freely assignable Area Network.
to the functions.
Characteristics Auxiliary supply Output relay contacts
Bus-bar side rated voltage Uaux: 19 to 100 Vd.c. Rated current 5A
Ubn 40 to 130 V or: 19 to 72 Va.c. Breaking
Generator side rated voltage Uaux: 64 to 300 Vd.c. 0.3 A @ 110 Vd.c., L/R=40 ms
Ugn 40 to 130 V or: 64 to 275 Va.c. Make and carr y 30 A for 0.5 s
Bus-bar side line VT's rated Burden: 5 W/10 W d.c. Mechanical life 106 operations
voltage 0.1 to 1000 kV 10VA/20VA a.c.
Generator side line VT's rated Standards
voltage 0.1 to 1000 kV EN 60255-6 IEC 255
Rated frequency fn 50/60 Hz

Closing pulse duration


tc 0.10 to 9.99 s
Closing delay tr 0.02 to 0.99 s
Maximum parallel attempts
Ns 1 to 10
Minimum interval
twc 0.10 to 9.99
Maximum sequence duration
ts 1 to 30 min
Stability verification time
td 0.10 to 10 s
Max busbar frequency deviation
Dfb 1 to 5 %
Max generator frequency deviation
Dfg 1 to 20 %
Max busbar voltage deviation
DUb 1 to 5 %
Max generator voltage deviation
DUg 70 to 85 %
Live Bus mode Norm/Sub/Super
Max difference in frequency
Df 0.02 to 0.50 Hz
Max difference in voltage
DU 1 to 30 %
Max phase-displacement
Dp 1 to 30°

Dead Bus Mode


OFF/ON/ON_CHECK
"Dead bus" voltage threshold
Ud 0.10 to 0.30 Ubn
Frequency regulation mode
CPf CONT/PULSE
Pulse duration tfpu 0.10 to 9.99 s
Minimum interval tfpa 1.00 to 9.99
s
Max. interval tfpm 10.00 to 99.99
s
START LB: Live bus synchronisation and paralleling request
Load pulse mode LP ON/OFF
START DB: Dead bus synchronisation and paralleling request.
Pulse duration tlp 0.10 to 9.99 s STOP: Sequence stop control.
Voltage regulation mode CB52: Paralleling CB's auxiliary contact.
CPU CONT/PULSE
tupu 0.10 to 9.99 s
tupa 0.10 to 9.99 s

ALSTOM FIR S.p.A. - via Viscardi,5 - 24016 SAN PELLEGRINO T. - BG - ITALIA


Tel. ++39 0345 28111 - Fax ++39 0345 22590 - Telex 301152 FIR I - E-mail: alstom.fir@tde.alstom.com