You are on page 1of 167

2/10/2022 2:51:25 PM

B
C
D
E
G

A
1

of Engineers ®
US Army Corps
2
3

TRANSATLANTIC MIDDLE EAST DISTRICT


4
5
6

DETAILS
7

SFDN - STANDARD
STANDARD FACILITIES
AREA DEFENSE (THAAD) -
8

TERMINAL HIGH ALTITUDE


9

READY TIO
ADVERTISE
SUBMISSION
10

24 FEBRUARY 2022

DESIGN BY: ISSUE DATE:


VARIOUS LOCATIONS, KSA US ARMY CORPS OF ENGINEERS J. BLANCHARD
ROYAL SAUDI AIR DEFENSE FORCES (RSADF) TRANSATLANTIC MIDDLE EAST DISTRICT DRAWN BY: SOLICITATION NO.:
201 PRINCE FREDERICK DRIVE, J. HOLLAND
THAAD STANDARD FACILITIES WINCHESTER, VA 22602 CKD BY: CONTRACT NO.:
$

SA-480530
Engineers ®

E. OKES
STANDARD DETAILS SUBMITTED BY: PLOT SCALE: PLOT DATE:
A. HANKS 2/10/2022
US Army Corps of

COVER SHEET 1:1


SHEET ID

2:51:25 PM
SG001
Middle East District

SIZE: FILE NO.:


ANSI D SA-480530-1$-SG001GN.dwg
MARK DESCRIPTION DATE
1 2 3 4 5 6 7 8 9 10

INDEX OF DRAWINGS INDEX OF DRAWINGS


US Army Corps of
REV. AM/COP REV. AM/COP Engineers ®
SHT REF NO. FILE NAME NO. NO. TITLE SHT REF NO. FILE NAME NO. NO. TITLE Middle East District
G GENERAL INTERIOR
SG001 SA-480530-1$-SG001GN.dwg COVER SHEET SI501 SA-480530-1$-SI501DT.dwg TYPICAL FLOOR TRANSITION DETAILS
SG002 SA-480530-1$-SG002GN.dwg INDEX OF DRAWINGS SI502 SA-480530-1$-SI502DT.dwg TYPICAL FLOOR TRANSITION DETAILS

DATE
SG003 SA-480530-1$-SG003GN.dwg ABBREVIATIONS SI503 SA-480530-1$-SI503DT.dwg WALL BASE DETAILS
SG004 SA-480530-1$-SG004GN.dwg GENERAL SYMBOLOGY SI601 SA-480530-1$-SI601DT.dwg INTERIOR FINISH LEGEND
SI602 SA-480530-1$-SI602DT.dwg FURNITURE, FIXTURES & EQUIPMENT SCHEDULE
STRUCTURAL SI603 SA-480530-1$-SI603DT.dwg SIGNAGE MOUNTING HEIGHTS
SS001 SA-480530-1$-SS001GN.dwg STRUCTURAL GENERAL NOTES - SHEET 1 OF 3 SI604 SA-480530-1$-SI604DT.dwg SIGNAGE TYPES
SS002 SA-480530-1$-SS002GN.dwg STRUCTURAL GENERAL NOTES - SHEET 2 OF 3
SS003 SA-480530-1$-SS003GN.dwg STRUCTURAL GENERAL NOTES - SHEET 3 OF 3 FIRE PROTECTION
SS501 SA-480530-1$-SS501DT.dwg TYPICAL CONCRETE DETAILS - SHEET 1 OF 6 SF501 SA-480530-1$-SF501DT.dwg FIRE ALARM - DETAILS
SS502 SA-480530-1$-SS502DT.dwg TYPICAL CONCRETE DETAILS - SHEET 2 OF 6 SF502 SA-480530-1$-SF502SH.dwg FIRE ALARM - SITE WIDE SCHEMATIC
SS503 SA-480530-1$-SS503DT.dwg TYPICAL CONCRETE DETAILS - SHEET 3 OF 6 SF511 SA-480530-1$-SF511DT.dwg FIRE SUPPRESSION - DETAILS
SS504 SA-480530-1$-SS504DT.dwg TYPICAL CONCRETE DETAILS - SHEET 4 OF 6
SS505 SA-480530-1$-SS505DT.dwg TYPICAL CONCRETE DETAILS - SHEET 5 OF 6 PLUMBING
SS506 SA-480530-1$-SS506DT.dwg TYPICAL CONCRETE DETAILS - SHEET 6 OF 6 SP001 SA-480530-1$-SP001GN.dwg PLUMBING GENERAL NOTES

DESCRIPTION
F SS507 SA-480530-1$-SS507DT.dwg CONCRETE SLAB-ON-GROUND DETAILS - SHEET 1 OF 4 SP002 SA-480530-1$-SP002AB.dwg PLUMBING LEGEND AND ABBREVIATIONS
SS508 SA-480530-1$-SS508DT.dwg CONCRETE SLAB-ON-GROUND DETAILS - SHEET 2 OF 4 SP003 SA-480530-1$-SP003SY.dwg PLUMBING SYMBOLS
SS509 SA-480530-1$-SS509DT.dwg CONCRETE SLAB-ON-GROUND DETAILS - SHEET 3 OF 4 SP501 SA-480530-1$-SP501DT.dwg PLUMBING DETAILS
SS510 SA-480530-1$-SS510DT.dwg CONCRETE SLAB-ON-GROUND DETAILS - SHEET 4 OF 4 SP502 SA-480530-1$-SP502DT.dwg PLUMBING DETAILS
SS511 SA-480530-1$-SS511DT.dwg FOUNDATION DETAILS - SHEET 1 OF 2 SP503 SA-480530-1$-SP503DT.dwg PLUMBING DETAILS
SS512 SA-480530-1$-SS512DT.dwg FOUNDATION DETAILS - SHEET 2 OF 2 SP504 SA-480530-1$-SP504DT.dwg PLUMBING DETAILS
SS513 SA-480530-1$-SS513DT.dwg CONCRETE UNIT MASONRY DETAILS - SHEET 1 OF 4
SS514 SA-480530-1$-SS514DT.dwg CONCRETE UNIT MASONRY DETAILS - SHEET 2 OF 4 MECHANICAL
SS515 SA-480530-1$-SS515DT.dwg CONCRETE UNIT MASONRY DETAILS - SHEET 3 OF 4 SM001 SA-480530-1$-SM001GN.dwg MECHANICAL LEGEND AND GENERAL NOTES
SS516 SA-480530-1$-SS516DT.dwg CONCRETE UNIT MASONRY DETAILS - SHEET 4 OF 4 SM002 SA-480530-1$-SM002GN.dwg MECHANICAL GENERAL NOTES
SS517 SA-480530-1$-SS517DT.dwg ELECTRICAL BUSWAY SUPPORT DETAIL SM501 SA-480530-1$-SM501DT.dwg MECHANICAL - DETAILS
SM502 SA-480530-1$-SM502DT.dwg MECHANICAL - DETAILS
ARCHITECTURE SM503 SA-480530-1$-SM503DT.dwg MECHANICAL - DETAILS
SA001 SA-480530-1$-SA001GN.dwg GENERAL NOTES AND LEGENDS SM504 SA-480530-1$-SM504DT.dwg MECHANICAL - DETAILS

MARK
SA002 SA-480530-1$-SA002GN.dwg GENERAL NOTES, ARCHITECTURAL CODES AND SM505 SA-480530-1$-SM505DT.dwg MECHANICAL - DETAILS
CRITERIA FOR UNIFIED FACILITY CRITERIA FACILITIES SM506 SA-480530-1$-SM506DT.dwg MECHANICAL - DETAILS
E SA003 SA-480530-1$-SA003GN.dwg GENERAL NOTES, ARCHITECTURAL CODES AND SM507 SA-480530-1$-SM507DT.dwg MECHANICAL - DETAILS
CRITERIA FOR SAUDI BUILDING CODE FACILITIES SM508 SA-480530-1$-SM508DT.dwg MECHANICAL - DETAILS
SA005 SA-480530-1$-SA005GN.dwg TYPICAL MOUNTING HEIGHTS

PLOT SCALE: PLOT DATE:


SM509 SA-480530-1$-SM509DT.dwg MECHANICAL - DETAILS

2/9/2022 4:56:39
SA510 SA-480530-1$-SA510DT.dwg DETAILS TYPICAL STUCCO
SA511 SA-480530-1$-SA511DT.dwg DETAILS TYPICAL STUCCO ELECTRICAL

SOLICITATION NO.:

SA-480530-1$-SG002GN.dwg
SA518 SA-480530-1$-SA518DT.dwg ROOF DETAILS - RS-1 TYPICAL DETAILS

PM
SE001 SA-480530-1$-SE001LG.dwg ELECTRICAL SYMBOLS LEGEND FOR FACILITIES

CONTRACT NO.:
SA519 SA-480530-1$-SA519DT.dwg ROOF DETAILS - RS-1 TYPICAL DETAILS (SHEET 1 OF 2)

ISSUE DATE:
SA522 SA-480530-1$-SA522DT.dwg ROOF DETAILS - RS-3 TYPICAL DETAILS SE002 SA-480530-1$-SE002LG.dwg ELECTRICAL SYMBOLS LEGEND FOR FACILITIES

1:1
SA523 SA-480530-1$-SA523DT.dwg ROOF DETAILS - RS-3 TYPICAL DETAILS (SHEET 2 OF 2)
SA525 SA-480530-1$-SA525DT.dwg ROOF DETAILS - RS-5 TYPICAL DETAILS SE003 SA-480530-1$-SE003GN.dwg ELECTRICAL GENERAL NOTES FOR FACILITIES
SA526 SA-480530-1$-SA526DT.dwg ROOF DETAILS - RS-5 TYPICAL DETAILS SE501 SA-480530-1$-SE501DT.dwg EARTHING AND LIGHTNING PROTECTION DETAILS
SA530 SA-480530-1$-SA530DT.dwg EXTERIOR DOOR DETAILS, H4.1 & J4.1 SE502 SA-480530-1$-SE502DT.dwg EARTHING AND LIGHTNING PROTECTION DETAILS
SA531 SA-480530-1$-SA531DT.dwg EXTERIOR DOOR DETAILS, H1 & J1 - H2 & J2, S1, S2 SE503 SA-480530-1$-SE503DT.dwg EARTHING AND LIGHTNING PROTECTION DETAILS

FILE NO.:
SA532 SA-480530-1$-SA532DT.dwg EXTERIOR DOOR DETAILS, H3 & J3 - H4 & J4 SE510 SA-480530-1$-SE510DT.dwg EARTHING AND LIGHTNING PROTECTION DETAILS

SUBMITTED BY:
SA533 SA-480530-1$-SA533DT.dwg EXTERIOR DOOR DETAILS, H5 & J5 - H6 & J6 SE511 SA-480530-1$-SE511DT.dwg EARTHING AND LIGHTNING PROTECTION DETAILS

J. BLANCHARD
SA534 SA-480530-1$-SA534DT.dwg EXTERIOR DOOR DETAILS, H7 & J7 - H8 & J8 SE512 SA-480530-1$-SE512DT.dwg EARTHING AND LIGHTNING PROTECTION DETAILS

J. HOLLAND
DESIGN BY:

DRAWN BY:

A. HANKS
D SA535 SA-480530-1$-SA535DT.dwg EXTERIOR DOOR DETAILS, J9 - H10 & J10 SE520 SA-480530-1$-SE520DT.dwg LIGHTING DETAILS

E. OKES
CKD BY:

ANSI D
SIZE:
SA536 SA-480530-1$-SA536DT.dwg EXTERIOR DOOR DETAILS, H11 &J11 - H12 & J12 SE521 SA-480530-1$-SE521DT.dwg LIGHTING DETAILS
SA537 SA-480530-1$-SA537DT.dwg EXTERIOR DOOR DETAILS, H13 & J13 - H14 & J14 SE522 SA-480530-1$-SE522DT.dwg LIGHTING DETAILS
SA538 SA-480530-1$-SA538DT.dwg INTERIOR DOOR DETAILS, H15 & J15 - H16 & J16 SE523 SA-480530-1$-SE523DT.dwg LIGHTING DETAILS

TRANSATLANTIC MIDDLE EAST DISTRICT


SA539 SA-480530-1$-SA539DT.dwg INTERIOR DOOR DETAILS, H17 & J17 - H18 & J18 SE524 SA-480530-1$-SE524DT.dwg LIGHTING DETAILS
SA540 SA-480530-1$-SA540DT.dwg INTERIOR DOOR DETAILS, H19 & J19 - H20 & J20 SE525 SA-480530-1$-SE525DT.dwg LIGHTING DETAILS

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


SA541 SA-480530-1$-SA541DT.dwg INTERIOR DOOR DETAILS, H21 & J21 - H22 & J22 SE541 SA-480530-1$-SE541DT.dwg POWER DETAILS

WINCHESTER, VA 22602
SA542 SA-480530-1$-SA542DT.dwg INTERIOR DOOR DETAILS, H23 & J23 - H24 & J24 SE542 SA-480530-1$-SE542DT.dwg POWER DETAILS
SA543 SA-480530-1$-SA543DT.dwg INTERIOR DOOR DETAILS, H25 & J25 - H26 & J26 SE543 SA-480530-1$-SE543DT.dwg POWER DETAILS
SA544 SA-480530-1$-SA544DT.dwg INTERIOR DOOR DETAILS, H27 & J27 - H28 & J28 SE544 SA-480530-1$-SE544DT.dwg POWER DETAILS
SA545 SA-480530-1$-SA545DT.dwg DOOR DETAILS, H29 & J29 - H30 & J30 SE601 SA-480530-1$-SE601DG.dwg EARTHING RISER DIAGRAM
SA546 SA-480530-1$-SA546DT.dwg DOOR DETAILS, H31 & J31 - H32 & J32 SE602 SA-480530-1$-SE602DG.dwg EARTHING RISER DIAGRAM
SA547 SA-480530-1$-SA547DT.dwg DOOR DETAILS SE620 SA-480530-1$-SE620SC.dwg LUMINAIRE SCHEDULE FOR FACILITIES
SA559 SA-480530-1$-SA559DT.dwg EXTERIOR WALL EW2 AND EW2A WINDOW DETAILS SE640 SA-480530-1$-SE640SC.dwg POWER SCHEDULES
SA560 SA-480530-1$-SA560DT.dwg EXTERIOR WALL EW2 WINDOW DETAILS
SA561 SA-480530-1$-SA561DT.dwg EXTERIOR WALL EW2 WINDOW DETAILS TELECOMMUNICATION
C SA562 SA-480530-1$-SA562DT.dwg EXTERIOR WALL EW2 WINDOW DETAILS ST001 SA-480530-1$-ST001GN.dwg TELECOMMUNICATION LEGEND AND GENERAL NOTES
SA563 SA-480530-1$-SA563DT.dwg EXTERIOR WALL EW2A WINDOW DETAILS ST501 SA-480530-1$-ST501DT.dwg TYPICAL TELECOMMUNICATION DETAILS
SA564 SA-480530-1$-SA564DT.dwg EXTERIOR WALL EW2A WINDOW DETAILS ST502 SA-480530-1$-ST502DT.dwg TYPICAL TELECOMMUNICATION DETAILS
SA565 SA-480530-1$-SA565DT.dwg EXTERIOR WALL EW2A WINDOW DETAILS ST503 SA-480530-1$-ST503DT.dwg TYPICAL TELECOMMUNICATION DETAILS
SA566 SA-480530-1$-SA566DT.dwg EXTERIOR WALL EW2A WINDOW DETAILS ST601 SA-480530-1$-ST601SC.dwg TELECOMMUNICATION SCHEDULES
SA567 SA-480530-1$-SA567DT.dwg EXTERIOR WALL EW1 WINDOW DETAILS
SA568 SA-480530-1$-SA568DT.dwg EXTERIOR WALL EW1A WINDOW DETAILS SECURITY
SA569 SA-480530-1$-SA569DT.dwg WINDOW DETAILS TY001 SA-480530-1$-TY001GN.dwg SECURITY LEGEND AND GENERAL NOTES
SA570 SA-480530-1$-SA570DT.dwg INTERIOR WALL M8F0.1P2 WINDOW DETAILS TY501 SA-480530-1$-TY501DT.dwg SECURITY DEVICE DETAILS - 1 OF 8

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


SA596 SA-480530-1$-SA595DT.dwg LOUVER DETAILS - EW-2A TY502 SA-480530-1$-TY502DT.dwg SECURITY DEVICE DETAILS - 2 OF 8
SA597 SA-480530-1$-SA596DT.dwg LOUVER DETAILS - EW-2A TY503 SA-480530-1$-TY503DT.dwg SECURITY DEVICE DETAILS - 3 OF 8

THAAD STANDARD FACILITIES


SA598 SA-480530-1$-SA597DT.dwg LOUVER DETAILS - EW-2A TY504 SA-480530-1$-TY504DT.dwg SECURITY DEVICE DETAILS - 4 OF 8

VARIOUS LOCATIONS, KSA


SA599 SA-480530-1$-SA599DT.dwg LOUVER DETAILS TY505 SA-480530-1$-TY505DT.dwg SECURITY DEVICE DETAILS - 5 OF 8

INDEX OF DRAWINGS
STANDARD DETAILS
SA600 SA-480530-1$-SA600DT.dwg LOUVER DETAILS TY506 SA-480530-1$-TY506DT.dwg SECURITY DEVICE DETAILS - 6 OF 8
SA601 SA-480530-1$-SA601DT.dwg EXTERIOR WALL TYPES TY507 SA-480530-1$-TY507DT.dwg SECURITY DEVICE DETAILS - 7 OF 8

SA-480530
SA602 SA-480530-1$-SA602DT.dwg PARTITION TYPES TY508 SA-480530-1$-TY508DT.dwg SECURITY DEVICE DETAILS - 8 OF 8
B SA603 SA-480530-1$-SA603DT.dwg PARTITION TYPES TY601 SA-480530-1$-TY601DG.dwg IESS NETWORK LINE DIAGRAM
SA604 SA-480530-1$-SA604DT.dwg PARTITION TYPES TY602 SA-480530-1$-TY602DG.dwg IESS WIRING DIAGRAM - 1 OF 10
SA608 SA-480530-1$-SA608DT.dwg ROOF TYPE DETAIL SHEET TY603 SA-480530-1$-TY603DG.dwg IESS WIRING DIAGRAM - 2 OF 10
SA610 SA-480530-1$-SA610DT.dwg DOOR PANEL TYPES TY604 SA-480530-1$-TY604DG.dwg IESS WIRING DIAGRAM - 3 OF 10
SA611 SA-480530-1$-SA611DT.dwg DOOR FRAME TYPES TY605 SA-480530-1$-TY605DG.dwg IESS WIRING DIAGRAM - 4 OF 10
SA615 SA-480530-1$-SA615DT.dwg WINDOW TYPES, W1 - W9 TY606 SA-480530-1$-TY606DG.dwg IESS WIRING DIAGRAM - 5 OF 10
SA616 SA-480530-1$-SA616DT.dwg WINDOW TYPES, W10 - W16 TY607 SA-480530-1$-TY607DG.dwg IESS WIRING DIAGRAM - 6 OF 10
SA617 SA-480530-1$-SA617DT.dwg WINDOW TYPES, W17 - W20 TY608 SA-480530-1$-TY608DG.dwg IESS WIRING DIAGRAM - 7 OF 10
SA618 SA-480530-1$-SA618DT.dwg WINDOW TYPES, W21 - W23 TY609 SA-480530-1$-TY609DG.dwg IESS WIRING DIAGRAM - 8 OF 10
SA620 SA-480530-1$-SA620DT.dwg WINDOW TYPES, W24 - W30 TY610 SA-480530-1$-TY610DG.dwg IESS WIRING DIAGRAM - 9 OF 10
SA630 SA-480530-1$-SA630DT.dwg CEILING DETAILS TY611 SA-480530-1$-TY611DG.dwg IESS WIRING DIAGRAM - 10 OF 10
SA631 SA-480530-1$-SA631DT.dwg CEILING DETAILS
SA651 SA-480530-1$-SA651DT.dwg EXTERIOR FINISH SCHEDULE
2/9/2022 4:56:39 PM

SA701 SA-480530-1$-SA701DT.dwg CASEWORK AND MILLWORK DETAILS


SA702 SA-480530-1$-SA702DT.dwg CASEWORK AND MILLWORK DETAILS
A SHEET ID
SA703 SA-480530-1$-SA703DT.dwg CASEWORK AND MILLWORK DETAILS
SA704 SA-480530-1$-SA704DT.dwg CASEWORK AND MILLWORK DETAILS
SA705 SA-480530-1$-SA705DT.dwg CASEWORK AND MILLWORK DETAILS
$

SG002
1 2 3 4 5 6 7 8 9 10
ABBREVIATIONS ABBREVIATIONS ABBREVIATIONS ABBREVIATIONS ABBREVIATIONS ABBREVIATIONS ABBREVIATIONS
# POUND OR NUMBER CJ CONSTRUCTION JOINT EMF WALK-OFF ENTRY MAT HD HEAD, HEAT DEFLECTOR MCOV MAXIMUM CONTINUOUS OPERATING VOLTAGE PSIG POUNDS PER SQUARE INCH GAGE T.O.W TOP OF WALL
& AND CKT CIRCUIT EMT ELECTRICAL METALLIC TUBING HDPE HIGH DENSITY POLYETHLENE MCP MOTOR CIRCUIT PROTECTOR PT POINT OF TANGENT, POTENTIAL TRANSFORMER TAF TOWEL APPLIED FINISH
Ø ROUND (DIAMETER) PHASE CL CENTER LINE ENCL ENCLOSE, ENCLOSURE HDR HANDRAIL MCUCD MASTER CONTROL UNIT CONTROL DEVICE PT PORCELAIN TILE TB TILE BASE
A AMPERE, AIR COMPRESSED AIR CLF CHAIN LINK FENCE ENG ENGINE HDW HARDWARE MDP MAIN DISTRIBUTION PANEL PTB PORCELAIN TILE BASE TBB TELECOMMUNICATIONS BONDING BACKBONE US Army Corps of
A/E ARCHITECT / ENGINEER CLFA CLUB FACILITY ENGR ENGINEER HDWD HARDWOOD MECH MECHANICAL PTL PRIMARY TARGET LINE TBM TEMPORARY BENCH MARK
Engineers ®
AASHTO AMERICAN ASSOCIATION OF STATE HIGHWAY AND CLG CEILING ENT ENTERING HDWL HEADWALL MEMB MEMBRANE PTN PARTITION, PORCELAIN TILE TC TIME CLOCK, TOP OF CURB
TRANSPORTATION OFFICIALS CLJ CONTROL JOINT ENTR ENTRANCE HGR HANGER MER MAIN EQUIPMENT ROOM PUHO FIRE AND DOMESTIC PUMP HOUSE TCPL TACTICAL CHILLER PLANT Middle East District
G AB
ABT
ANCHOR BOLT
ABOUT
CLO
CLOS
CLOSET
CLOSURE
EOL
EP
END OF LINE
EXPLOSION-PROOF, EDGE OF PAVEMENT
HGT
HH
HEIGHT
HANDHOLE
MET.
MFR
METAL
MANUFACTURER
PVC
PVDF
POINT OF VERTICAL CURVE, POLYVINYL CHLORIDE
POLYVINYLIDENE FLUORIDE
TD
TDC
TRENCH DRAIN
TURNED DOWN CURB
ABUT. ABUTMENT CLPR CALIPER EPX EPOXY HM HOLLOW METAL MGD MILLION GALLONS PER DAY PVI POINT OF VERTICAL INTERSECTION TEF TELECOMMUNICATIONS ENTRANCE FACILITY
ABV ABOVE CLR CLEAR EQL EQUAL HOA HAND-OFF AUTOMATIC MH MANHOLE, MOUNTING HEIGHT, METAL HALIDE PVMT PAVEMENT TEL TELEPHONE

DATE
AC ALTERNATING CURRENT, AIR CONDITIONING UNIT, ACRE, AIR CLSD CEILING LINEAR SLOT DIFFUSER EQPT EQUIPMENT HORIZ HORIZONTAL MHz MEGAHERTZ PVR PAVER TELECOM TELECOMMUNICATIONS
COMPRESSOR CLSR CEILING LINEAR SLOT RETURN EQUIP EQUIPMENT HP HORSEPOWER, HEAT PUMP MID MIDDLE PVT POINT OF VERTICAL TANGENT, PRIVATE TEMF THAAD EQUIPMENT MAINTENANCE FACILITY
ACC AIR COOLED CHILLER CM CENTIMETER ER EXISTING TO REMAIN HPF HIGH POWER FACTOR MIN MINIMUM PWR POWER TEMP TEMPERATURE, TEMPERED, TEMPORARY
ACCS ACCESSORIES CMP CORRUGATED METAL PIPE ER EXHAUST REGISTER HPS HIGH-PRESSURE SODIUM, HIGH-PRESSURE STEAM MISC MISCELLANEOUS QT QUARRY TILE TER TERRAZZO
ACCU AIR COOLED CONDENSING UNIT CMPSN COMPOSITION ES EDGE OF SHOULDER HPT HIGH POINT MJ MECHANICAL JOINT QTZ QUARTZ TERM. TERMINAL
ACI AMERICAN CONCRETE INSTITUTE CMU CONCRETE MASONRY UNITS ESMT EASEMENT HR HOUR MK MARK R RADIUS, RIGHT, RISER TFE TETRAFLUOROETHYLENE
ACM ASBESTOS CONTAINING MATERIAL CND CONDUIT ET EXPANSION TANK HR HOSE REEL MKBD MARKER BOARD R/W RIGHT OF WAY TG TOP GRILLE
ACMU ACOUSTICAL CONCRETE MASONRY UNIT CNDCT CONDUCTIVE EV EVERGREEN HS HORIZONTAL SLOT MLO MAIN LUGS ONLY RA RETURN AIR TGB TELECOMMUNICATIONS GROUNDING BUSBAR
ACP ASBESTOS CEMENT PIPE, ACOUSTICAL CEILING PANEL CNDS CONDENSATE, CONDUITS EW EACH WAY, END WALL HSS HIGH SECURITY SWITCH mm MILLIMETERS RAD RADIUS THERM. THERMOMETER
ACS ACESS, ACCESSIBLE CO CLEANOOUT, COUNTY EWC ELECTRIC WATER COOLER HTG HEATING MO MASONRY OPENING RAF RAISED ACCESS FLOORING THK THICK
ACST ACOUSTIC, ACOUSTICAL CO2 CARBON DIOXIDE EXC EXCAVATE, EXCAVATION HTR HEATER MON MONUMENT RAS RETURN ACTIVATED SLUDGE THKNS THICKNESS
ACU AIR CONDITIONING UNIT COBU COMMUNICATIONS BUILDING EXH EXHAUST HV HIGH VOLTAGE, HEATING-VENTILATING UNIT MOSQ MOSQUE RB RUBBER BASE THR THRESHOLD
ACV ALARM CHECK VALVE COL COLUMN EXP EXPOSED HW DOMESTIC HOT WATER MOV METAL OXIDE VARISTOR RBR RUBBER, RUBBER BASE TI TEMPERATURE INDICATOR
ADA AMERICANS WITH DISABILITY ACT COMB. COMBINATION EXPN EXPANSION HWC DOMESTIC HOT WATER CIRCULATING MOV MOTOR OPERATED VALVE RCP REINFORCED CONCRETE PIPE TKBD TACKBOARD
ADD. ADDITIONAL COMM COMMUNICATION EXST EXISTING HWL HIGH-WATER LINE MP MEDIUM PRESSURE RCPT RECEPTACLE TLSD TOP LINEAR SLOT DIFFUSER
ADH ADHESIVE COMP COMPRESSION, COMPRESSED EXT EXTERIOR, EXTERNAL HX HEAT EXCHANGER MPa MEGAPASCAL RCRC RESINOUS CHEMICAL, RESISTANT COATING TLT TOILET
ADJ ADJUSTABLE, ADJACENT

DESCRIPTION
CONC CONCRETE EXTN EXTENSION HYD HYDRANT MPC MINI POWER CENTER RCRTC RESINOUS CHEMICAL RESISTANT TRAFFIC COATING TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
F ADMIN
ADO
ADMINISTRATIVE
AUTOMATIC DOOR OPENER
COND
CONN
CONDUCTOR, CONDUCTIVE, CONDENSER
CONNECT, CONNECTION
F
F TO F
FUSED, FAN
FACE TO FACE
hZ
I
HERTZ
INTERCOM
MPH
MR
MILES PER HOUR
MOP RECEPTOR, MOISTURE RESISTANT
RCVG
RCVR
RECEIVING
RECEIVER
TMV
TO.
THERMAL MIXING VALVE
TELECOMMUNICATIONS OUTLET
AFCI ARC FAULT CIRCUIT INTERRUPTER CONST CONSTRUCTION F&T FLOAT AND THERMOSTATIC IC INTERRUPTING CAPACITY, INTERMEDIATE CROSS CONNECT MSL MEAN SEA LEVEL RD ROOF DRAIN, ROAD TOC TOP OF CONCRETE
AFF ABOVE FINISH FLOOR CONT CONTINUOUS, CONTINUATION FA FIRE ALARM ID INSIDE DIAMETER MT MOUNT RDCR REDUCER TOF TOP OF FOOTING
AFFF AQUEOUS FILMM FORMING FOAM CONTR CONTRACT, CONTRACTOR FAB FABRICATE IDS INTRUSION DETECTION SYSTEM MTD MOUNTED REC RECESS TOFA THAAD OPERATIONS FACILITY
AFG ABOVE FINISH GRADE COORD COORDINATE FABL FIRE ALARM BELL IDSCD INTRUSION DETECTION SYSTEM CONTROL DEVICE MTG MOUNTING RECIR RECIRCULATING TOS TOP OF STEEL
AFMS AIRFLOW MEASURING STATION COP COPPER FACP FIRE ALARM CONTROL PANEL IEEE THE INSTITUTE OF ELECTRICAL AND ELECTRONICS MTR MOTOR RECT RECTANGLE, RECTANGULAR TOT. TOTAL
AGGR AGGREGATE COR CORNER fC FOOTCANDLE, FAN COIL UNIT, FACE OF CURB ENGINEERS MTZ MOTORIZED RED. REDUCING TP TREE PROTECTION, TOILET PARTITION
AH AIR HANDLING, AIR-HANDLING UNIT CORR CORRIDOR, CORRUGATED FCO FLOOR CLEANOUT IG ISOLATED GROUND MU MULCHING REF REFERENCE TR TOP REGISTER, TOP OF RAIL, TELECOM ROOM
AHR ANCHOR COV COVER FCU FAN COIL UNIT IMC INTERMEDIATE METAL CONDUIT MUL MULLION REFL REFLECTED TRANSV TRANSVERSE
AHU AIR HANDLING UNIT CP CEMENT PILASTER, CONDENSATE PUMP FD FLOOR DRAIN, FIRE DAMPER IN. INCH MUTCO MANUAL OF UNIFORM TRAFFIC CONTROL REFR REFRIGERATOR TRTD TREATED
AI ANALOG INPUT CPF CHEMICAL POT FEEDER FDC FIRE DEPARTMENT CONNECTION INCAND INCANDESCENT MUTOA MULTI-USER TELECOMMUNICATION OUTLET ASSEMBLY REINF REINFORCE, REINFORCEMENT, REINFORCED TS TEMPERATURE STEEL, TIME SWITCH, TAMPER SWITCH,
AIC AMPERE INTERRUPTING CAPACITY CPT CARPET FDN FOUNDATION INCL INCLUSIVE MV MEDIUM VOLTAGE REM REMAINDER TEMPORARY SWITCH, THICKENED SLUDGE, TEMPORARY
AISI AMERICAN INSTITUTE OF STEEL CONSTRUCTION INCR INCREMENT SEEDING, TRAVERSE STATION
CR CEILING REGISTER, HOT-CONDENSER WATER CONTROL FDR FEEDER MWP MEMBRANE WATERPROOFING REQD REQUIRED
AL ALUMINUM RELAY FE FIRE EXTINGUISHER IND INDUCTION N NORTH RES RESINOUS FLOORING TSD TEMPORARY SLOPE DRAIN
ALT ALTERNATE CSD CELLULAR STEL DECK FEC FIRE EXTINGUISHER CABINET INFL INFLUENT N2 NITROGEN RESIL RESILENT TSP TWISTED SHIELDED PAIR
AM AMMETER CT CERAMIC TILE, CURRENT TRANSFORMER FES FLARED END SECTION INSTL INSTALL, INSTALLATION N2O NITROGEN OXIDE REV REVISION TSPB TACTICAL SITE POWER BUILDING
AMP AMPERE CTR CENTER FFE FINISH FLOOR ELEVATION INSUL INSULATION, INSULATED, INSULATOR, INSULATING N&D NAIL & DISC RF ROOF, RADIO FREQUENCY, RESILIENT FLOOR TST TWISTED SHIELDED TRIPLE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE CTRL CONTROL INT INTEGRATED, INTERIOR TSTAT THERMOSTAT

MARK
FGL FIBERGLASS N-G NEUTRAL TO GROUND RFG ROOFING
AO AUTOMATIC OPENER, ANALOG OUTPUT CTSK COUNTERSINK FH FIRE HOSE INTMD INTERMEDIATE N.C. NORMALLY CLOSED RFH ROOF HATCH TT TEMPERATURE TRANSMITTER
AP ACCESS PANEL CTWT COUNTERWEIGHT FHC FIRE HOSE CABINET INV INVERT, INVERSE N.O. NORMALLY OPEN RFI RADIO FREQUENCY INTERFERENCE TU TERMINAL UNIT
E APPR
APROX
APPROVED
APPROXIMATE
CU
CULV
CUBIC, COPPER
CULVERT
FHYD FIRE HYDRANT IP IRON PIN, STORM DRAIN INLET PROTECTION, INTERNET
PROTOCOL
NA NOT APPLICABLE RL ROOF LEADER, REFRIGERANT LIQUID TV
TVSH
TELEVISION, TELEVISION OUTLET
TACTICAL VEHICLE SUNSHADE
FIG. FIGURE NEC NATIONAL ELECTRICAL CODE RM ROOM
APS ALARM PRESSURE SWITCH CV CONVERTER, CHECK VALVE FIN FL EL FINISH FLOOR ELEVATION IPF IRON PIN FOUND, IRON PIPE FOUND NEUT NEUTRAL RND ROUND TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR

PLOT SCALE: PLOT DATE:


ARCH ARCHITECT / ARCHITECTURAL CW DOMESTIC COLD WATER IR IRRIGATION TYP TYPICAL

2/9/2022 4:56:44
FIN. FINISH NFPA NATIONAL FIRE PROTECTION ASSOCIATION RO ROUGH OPENING
AREMA AMERICAN RAILWAY ENGINEERING AND CWB CAPILLARY WATER BARRIER FL FLOOR, FLASHING ISOL ISOLATOR NIC NOT IN CONTRACT RPBP REDUCED PRESSURE BACKFLOW PREVENTER U.S. URINAL SCREEN
MAINTENANCE-OF-WAY ASSOCIATION ºC DEGREES CELSIUS J JOULE, JUNCTION BOX UC UNDERCUT, UNDERCOUNTER
FLA FULL LOAD AMPERAGE NO. NOS NUMBER, NUMBERS RPM REVOLUTION PER MINUTE
AS AIR SEPARATOR

SOLICITATION NO.:

SA-480530-1$-SG003GN.dwg
D DEPTH, DEGREE, OF CURVE, DIMMER SWITCH, DRAINLINE, FLC FULL LOAD CURRENT JB JUNCTION BOX NOM NOMINAL RPRE RADAR PAD AND RADAR ENCLOSURE UF UNDERFLOOR

PM
ASB ASBESTOS

CONTRACT NO.:
MOUNTED IN DUCT FLEX. FLEXIBLE JC JANITOR'S CLOSET NOP NORMAL OPEN POINT RR RIPRAP, RAILROAD UFD UNDERFLOOR DUCT
ASC ABOVE SUSPENDED CEILING DB DRY BULB, DIRECT BURIAL DUCT, DEEP BANK, DECIBELS, JCT JUNCTION UG UNDERGROUND

ISSUE DATE:
FLG FLANGE NPRN NEOPRANE RR RETURN REGISTER
ASPH ASPHALT DEED BOOK, DRAINAGE BASIN JST JOIST UH UNIT HEATER
FLSH FLASHING NPW NONPOTABLE WATER RS ROLLER SHADE, ROOF SYSTEM
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS DBL DOUBLE JT JOINT UHF ULTRAHIGH FREQUENCY
FLUOR FLUORESCENT NRS NONRISING STEM RTE ROUTE

1:1
ASYM ASYMMETRICAL DC DIRECT CURRENT K KEY OPERATED, KIP NRS UL UNDERWRITERS LABORATORY
FM FLOW METER RTU ROOFTOP PACKAGED UNIT
AT AMPERE TRIP DDC DIRECT DIGITAL CONTROL kA KILOAMPERES NS NEAR SIDE ULT ULTIMATE
FMC FLEXIBLE METAL CONDUIT S SOUTH, SANITARY, SEWER, SPEAKER, SWITCH, SUPPLY
ATS AUTOMATIC TRANSFER SWITCH DEC DECIDUOUS KCM THOUSAND CIRCULAR MILS NST NONSLIP TREAD UNIF UNIFORM
FO FIBER OPTIC S/M SINGLE MODE FIBER
AUTO. AUTOMATIC DEFL DEFLECT, DEFLECTION KCP KEENE'S CEMENT PILASTER NTS NOT TO SCALE UNO UNLESS NOTED OTHERWISE
FOB FACE OF BRICK, FRONT OF BUILDING S/N SOLID NEUTRAL
AUX AUXILIARY DEG DEGREE kg KILOGRAM 02 MEDICAL OXYGEN UPS UNINTERUPTABLE POWER SUPPLY
FOR FUEL-OIL RETURN SA SUPPLY AIR
AV AIR VENT, AUDIO VISUAL, ALTITUDE VALVE, ACID VENT DEM DEMOUNTABLE kg/s KILOGRAM PER SECOND O TO O OUT TO OUT UR URINAL
FOS FUEL-OIL SUPPLY SAAS SMALL ARMS / AMMUNITION STORAGE

FILE NO.:
AVG AVERAGE DEPR DEPRESSED kHZ KILOHERTZ O.F. OUTSIDE FACE UTIL UTILITY
FOV FUEL-OIL VENT SAGF SWITCHGEAR AND GENERATOR FACILITY
AW ACID WASTE DEPT DEPARTMENT km KILOMETER OA OVERALL, OUTSIDE AIR UTP UNSHIELDED TWISTED PAIR

SUBMITTED BY:
FPM FEET PER MINUTE SAN SANITARY

J. BLANCHARD
AWG AMERICAN WIRE GAUGE DET DETAIL / DETAILS kN KILONEWTON OAMF OPERATIONS AND MAINTENANCE FACILITY V VOLTAGE, VOLT, VENT, VALVE
FR FRAME, FROM SCFA SECURITY CONTROL FACILITY

J. HOLLAND
DESIGN BY:

DRAWN BY:
AWP ACOUSTICAL WALL PANEL DF DRINKING FOUNTAIN KO KNOCKOUT OC ON CENTER VA VOLT-AMPERE
FRICT FRICTION SCFM STANARD CUBIC FEET PER MINUTE

A. HANKS
D AWS AMERICAN WELDING SOCIETY DH DUCT HEATER, DOOR HOLDER kPa KILOPASCAL VAC VACUUM VOLTS AC, MEDICAL VACUUM

E. OKES
CKD BY:
FRT FIRE RETARDANT TREATED OCPD OVER CURRENT PROTECTOR SERVICE SCHED SCHEDULE

ANSI D
AWWA AMERICAN WATER WORKS ASSOCIATION DI DROP INLET,DUCTILE IRON, DEIONIZED WATER KSF KIPS PER SQUARE FOOT OD OUTSIDE DIAMETER VAR VOLT-AMPERE REACTIVE

SIZE:
FRZR FREEZER SCONC/SC SEALED CONC
B BATTERY DI DIGITAL INPUT KSI KIPS PER SQUARE INCH OFBA OFFICER'S BARRACKS VAV VARIABLE AIR VOLUME
FS FAR SIDE, FULL SIZE, FLOW SWITCH, FLOOR SINK, FUSE SIZE SD STORM DRAIN, SMOKE DETECTOR
B TO B BACK TO BACK DIA DIAMETER kV KILOVOLT OFCI OWNER FURNISHED CONTRACTOR INSTALLED VB VAPOR BARRIER
FSCP FLAME SAFEGUARD CONTROL PANEL SDF STATIC DISSIPATIVE FLOORING
B&B BALL & BURLAP DIAG DIAGRAM, DIAGONAL kVA KILOVOLT-AMPERE OFOI OWNER FURNISHED OWNER INSTALLED VC VERTICAL CURVE
FSS FUSED SAFETY SWITCH SDMH STORM DRAIN MANHOLE
B.O.W BOTTOM OF WALL DIFA DINING FACILITY

TRANSATLANTIC MIDDLE EAST DISTRICT


FT FOOT kVAR KILOVOLT-AMPERE REACTIVE OH OVERHEAD, OPPOSITE HAND SDT STATIC DISSIPATIVE TILE VCP VITRIED CLAY PIPE
BAHE BATTERY HEADQUARTERS DIFF DIFFUSER kW KILOWATT OP OUTLET PROTECTION VCT VINYL COMPOSITION TILE
FTG FOOTING SEC SECONDARY

US ARMY CORPS OF ENGINEERS


BAL BALANCE DIM DIMENSION kWH KILOWATT HOUR OPNG OPENING VD VOLUME DAMPER

201 PRINCE FREDERICK DRIVE,


FUFA FUEL FARM SECT SECTION
BC BOLT CIRCLE, BOTTOM OF CURB, BARE COPPER DIP. DUCTILE IRON PIPE L LEFT, LENGTH OF CURVE, LONG OPP OPPOSITE VDC VOLTS DC
FUR FURRED, FURRING SEMF SMP EQUIPMENT MAINTENANCE FACILITY
BD BOARD DIR DIRECTION, DIRECT, DEIONIZED WATER RETURN

WINCHESTER, VA 22602
FURN FURNISH L-G LINE TO GROUND OS&Y OUTSIDE SCREW AND YOKE SF SILT FENCE, SQUARE FEET VEL VELOCITY
BDL BUNDLE DISC. DISCONNECT L-L LINE TO LINE OSP OUTSIDE PLANT VENT VENTILATE / VENTILATION
FUST FUEL STATION SFDN STANDARD DETAILS
BEJ BRICK EXPANSION JOINT DISCH DISCHARGE L-N LINE TO NEUTRAL OVHD OVERHEAD VERT VERTICAL
FUT FUTURE SFM SEWER FORCE MAIN
BET. BETWEEN DISP DISPENSER L.W.T LEAVING WATER TEMPERATURE OZ OUNCE VEST VESTIBULE
FVNR FULL VOLTAGE NON-REVERSING SFP SPRAYED FIRE PROTECTION
BF BLIND FLANGE DIST DISTRIBUTION, DISTANCE L/S LITERS PER SECOND P POLE, POWER, PUMP VFD VARIABLE FREQUENCY DRIVE
FWC FABRIC WALL COVERING SH SHEET
BG BOTTOM GRILLE DIV DIVISION LA LIGHTENING ARRESTER P.F. POWER FACTOR VHF VERY HIGH FREQUENCY
FWP FABRIC WRAPPED PANEL SHV SHELVING
BIM BUILDING INFORMATION MODEL DK DECK LAB LABORATORY P.R.S PRESSURE REDUCING STATION VIB VIBRATION
FXTR FIXTURE SIM SIMILAR
BITUM BITUMINOUS DL DEAD LOAD LAM LAMINATE PA PIPE ANCHOR, PUBLIC ADDRESS VIF VERIFY IN FIELD
ºF DEGREES FAHRENHEIT SK SKETCH
BL BUILDING LINE, BASE LINE DL DRUM LOUVER LAN LOCAL AREA NETWORK Pa PASCAL VIS VINYL STAIR TREADS AND RISERS
G GAS MAIN OR SERVICE LINE, NATURAL GAS PIPE SLP SLOPE
BLDG BUILDING DMH DROP MANHOLE LAPA LAUNCHER PAD PB PUSH BUTTON, PANEL BOARD, PULL BOX VLT VAULT
GA GAGE, GAUGE SM SQUARE METERS
BLK BLOCK, BLOCKING DML DEMOLITION, DEMOLISH LAT LATTITUDE, LATERAL PBSS PALLET BUILD SUNSHADE VM VOLTMETER
GAFF GRANDSTAND AND FITNESS FIELD SMBU SEC METERING BUILDING
BLW BELOW DMPR DAMPER LAV LAVATORY PC POINT OF CURVE VOL VOLUME
GAHO GATE HOUSE SMH SEWER MANHOLE
C BM BEAM, BENCH MARK, SOIL STABILIZATION BLANKET &
MATTING
DN
DO
DOWN
DIGITAL OUTPUT
GAL GALLON LB POUND PCC POINT OF COMPOUND CURVE, PRECAST CONCRETE, SMR SURFACE METAL RACEWAY VR VAPOR RETARDER
GALV GALVANIZE, GALVANIZED LCG LACING PORTLAND CEMENT CONCRETE SNT SEALANT VS VERTICAL SLOT
BMS BUILDING MANAGEMENT AND CONTROL SYSTEM DP DISTRIBUTION PANEL LCP LIGHTING CONTROL PANEL PCP PRECAST CONCRETE PANEL VSS SHOCK SENSOR
GC GROUND COUNTERPOISE SOBA SOLDIER'S BARRACKS
BOL BEGINNING OF LINE DPT DIFFERENTIAL PRESSURE TRANSMITTER LDG LOADING PCSP PRECAST CONCRETE SANDWICH PANEL VT VINYL TILE
GCMU GLAZED CONCRETE MASONRY UNIT SOG SLAB ON GRADE
BOT BOTTOM DR DOOR, DRIVE LED LIGHT EMITTING DIODE PD PRESSURE DROP VTR VENT THRU ROOF
GCP GLYCOL COOLANT PUMP SP SPACE, SPACES, STATIC PRESSURE, SERVICE PROVIDER
BP BASE PLATE, BACKFLOW PREVENTER, BEARING PLATE DS DOWNSPOUT, DRIP STATION, DIGESTED SLUDGE, LF LINEAR FOOT, LINEAR FEET PDS PROTECTED DISTRIBUTION SYSTEM W WEST, WIDTH/WIDE
DISCONNECT SWITCH GCR GLYCOL COOLANT RETURN SPD STATIC PRESSURE DROP, SURGE PROTECTION DEVICE
BR BARE ROOT, BOTTOM REGISTER LFMC LIQUID LIGHT FLEXIBLE METAL CONDUIT PDU POWER DISTRIBUATION UNIT W/ WITH
GCS GLYCOL COOLANT SUPPLY SPEC SPECIFICATIONS
BRG BEARING DSD DUCT SMOKE DETECTOR LG LENGTH, LONG PED PEDESTAL W/O WITHOUT
GDR GUARDRAIL SPKR SPEAKER
BRK BRICK DTWH DUAL TEMP WALL HYDRANT LI LONG TIME INSTANTANEOUS PEJ PREMOLDED EXPANSION JOINT WA WAINSCOT
GEN GENERATOR SPMR SINGLE-PLY MEMBRANE ROOF
BRKT BRACKET DUP DUPLICATE LIQ LIQUID PEMB PRE-ENGINEERED METAL BUILDING WAGD WASTE ANESTHESIA DISPOSAL
GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED SPR SPRINKLER
BSMT BASEMENT DV DRAIN VALVE LKR LOCKER PET PROTECTED ENTRANCE TERMINAL WAS WASTE ACTIVATED SLUDGE
GFE GOVERNMENT FURNISHED EQUIPMENT, GROUND FLOOR SPRT SUPPORT
BT BUFFER TANK DVTL DOVETAIL

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


ELEVATION LL LIVE LOAD PF POROUS FILL SPS STATIC PRESSURE SENSOR WATO WATCH TOWER
BTU BRITISH THERMAL UNIT DW DUMBWAITER, DISHWASHER LLH LONG LEG HORIZONTAL PG PIPE GUIDE, PAGE, PRESSURE GAUGE WB WET BULB, WIND BEAM
GFECI GOVERNMENT FURNISHED EQUIPMENT CONTRACTOR SPWA SMP PARTS WAREHOUSE
BTUH BTU PER HOUR DWD DRINKING WATER DISPENSER INSTALLED LLV LONG LEG VERTICAL PH PHASE, PENTHOUSE WC WATER CLOSET, WALL COVERING, WINDOW COVERING
SQ SQUARE
BU BUILT-UP DWEL DWELLING GFGI GOVERNMENT FURNISHED GOVERNMENT INSTALLED LOC LOCATE PHR PREHEAT RETURN WC VINYL WALL COVERING
SR SUPPLY REGISTER

THAAD STANDARD FACILITIES


BUR BUILT-UP ROOF(ING), BURIED DWG DRAWING GFI GROUND FAULT INTERRUPTER LONG. LONGITUDINAL PHS PREHEAT SUPPLY WD WOOD, WIDTH

VARIOUS LOCATIONS, KSA


SRV SURGE RELIEF VALVE
BVMF BATTERY VEHICLE MAINTENANCE FACILITY DWLS DOWELS GFM GOVERNMENT FURNISHED MATERIAL LP LIQUIEFIED PROPANE PI POINT OF INTERSECTION WDO WINDOW
SS SANITARY SEWER, SOLID SURFACE, SAFETY SWITCH
BW BOTH WAYS DWV DRAIN WASTE AND VENT

STANDARD DETAILS
GFRC GLASS-FIBER REINFORCED CONCRETE LPS LOW PRESSURE SODIUM, LIGHTING PROTECTION SYSTEM PI PRESSURE INDICATOR SSD SUBSURFACE DRAIN, SECONDARY STORM DRAIN WFD WATERFLOW DETECTOR
C COURSE, CONVECTOR, CENTER, CONDUIT DX DUPLEX, DIRECT EXPANSION,

ABBREVIATIONS
GHSA GUARD HOUSE WITH SITTING AREA LPS LITERS PER SECOND PIV POST INDICATOR VALVE SSK SOIL STACK WG WALL GUARD, WATER GAGE
C TO C CENTER TO CENTER E EAST, EMERGENCY (CIRCUIT), ELECTRIC, ELECTRICAL GHZ GIGAHERTZ LPT LOW POINT PL PLATE, PROPERY LINE WH WALL HYDRANT

SA-480530
SSMR STANDING SEAM METAL ROOF
C&G CURB & GUTTER E TO E END TO END GI GALVANIZED IRON LR LONG RADIUS, LINEAR REGISTER PLAM PLASTIC LAMINATE WHA WATER HAMMER ARRESTER
SST STAINLESS STEEL
B C&R
C.O.G
CUT & REPLACE
CHANGE OF GRADE
E.A.T
E.W.T
ENTERING AIR TEMPERATURE
ENTERING WATER TEMPERATURE
GL GLASS LS LUMP SUM, LIMIT SWITCH, LONG TIME SHORT TIME PLAS PLASTER ST STREET, STORY, STEAM, SEDIMENT TRAP, STONE WHS WELDED HEAD STUD
GND GROUND LSG LONG TIME SHORT TIME GROUND FAULT PLATF PLATFORM STA STATION WI WROUGHT IRON
CA COMPRESSED AIR EA EACH GOVT GOVERNMENT LSI LONG TIME SHORT TIME INSTANTANEOUS PLF POUNDS PER LINEAR FOOT WL WIND LOAD, WATER LINE
STD STANDARD
CAB. CABINET EC EMPTY CONDUIT, ELECTRICAL CONTRACTOR GPH GALLON PER HOUR LSIG LONG TIME SHORT TIME INSTANTANEOUS GROUND FAULT PLVS PARKING LOT VEHICLE SUNSHADE WM WATER METER
STER STERLIZER
CANTIL. CANTILEVER ECB ENCLOSED CIRCUIT BREAKER GPM GALLONS PER MINUTE LT LIGHT PLYWD PLYWOOD WP WORKING POINT, WATERPROOF
STIF STIFFENER
CAP. CAPACITY ECC EARTH CONTINUITY CONDUCTOR GPU GLYCOL INJECTION PUMP AND TANK LTG LIGHTING PNL PANEL WP WALL PROTECTION
STIR. STIRRUP
CATV CABLE TELEVISION ECL EMERGENCY CRITICAL LIGHTING GPWA GENERAL PURPOSE WAREHOUSE LV LOW VOLUME PNLBD PANELBOARD WPF WATERPROOFING
STL STEEL
CB CATCH BASIN, CIRCUIT BREAKER ECMT ENCASEMENT GR GRADE LVR LOUVER PNT PAINT, PAINTED WS WATERSURFACE, WATERSTOP
STOR STORAGE
CCFC CLOSED-CIRCUIT FLUID COOLER ECP EMERGENCY CRITICAL POWER GRAD GRADUATED LVT LUXURY VINYL TILE POB POINT OF BEGINNING WS WINDOW SHADE
STP SHIELDED TWISTED PAIR
CCTV CLOSED CAPTION TELEVISION ECPO ENTRY CONTROL POINT GRL GRILLE LW LONG WAY, LIMIT OF WORK POL POLISH, POINT ON LINE WST WASTE
STR STRAIGHT, STARTER
CD CEILING DIFFUSER, ROCK CHECK DAMN EDB ELECTRIC DUCT BANK GRS GALVANIZED RIGID STEEL LWC LIGHTWEIGHT CONCRETE PP POWER POLE WT WEIGHT, WINDOW TREATMENT
STRL STRUCTURAL
CE CONSTRUCTION ENTRANCE EES EARTH ELECTRODE SYSTEM GRT GROUT LWL LOW-WATER LINE PPH POUNDS PER HOUR WTGS WASTEWATER TREATMENT - GREY STORAGE
STRUC STRUCTURE
CEM CEMENT EF EACH FACE GSU GLAZED STRUCTURAL UNITS lx LUX PPM PIXELS PER METER WTPF WATER TREATMENT AND PUMP FACILITY
SUBSTA SUSPENDED
CENT. CENTRIFUGAL EF EXHAUST FAN GT GLASS TILE M MICROPHONE, MANUAL PR PAIR WTR WATER
SUP SUPPLY
CF CELLULAR FLOOR, CUBIC FOOT EFF EFFLUENT GTB GROUND TERMINAL BOX m METER PRC POINT OF REVERSE CURVE WTS WELDED THREADED STUD
SURF. SURFACE
CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED EG ELECTRIC GROUND GTV GATE VALVE M/G MOTORGENERATOR PREFIN PREFINISHED WV WATER VALVE, WOOD VENEER
SUSP SUSPENDED
CFM CUBIC FEET PER MINUTE EGB ELECTRIC GROUND BUS GUHO GUARD HOUSE MACH MACHINE PRESS. PRESSURE WWR WELDED WIRE FABRIC (WELDED WIRE REINFORCEMENT)
SV SHEET VINYL, STEAM VENT
CFS CUBIC FEET PER SECOND EGH ELECTRIC GLYCOL HEATER
2/9/2022 4:56:44 PM

GV GAS VALVE MAG MAGNETIC PRI PRIMARY SVCE SERVICE XARM CROSS ARM
CG CORNER GUARD, CHANGE OF GRADE EIFS EXTERIOR INSULATION AND FINISH SYSTEM GVL GRAVEL MATL MATERIAL PRL PARALLEL XFMR TRANSFORMER
SVSW SMP VEHICLE STORAGE WAREHOUSE
A CH
CHAM
CABINET HEATER, CHORD
CHAMFER
EJ
EL
EXPANSION JOINT
ELEVATION
GWB
GYP
GYPSUM WALLBOARD
GYPSUM
MATV
MAX
MASTER ANTENNA TELEVISION
MAXIMUM
PROP.
PROV
PROPOSED
PROVIDED
SW SHORT WAY, SWITCH, SIDEWALK XFR
XMIT
TRANSFER
TRANSMITTER SHEET ID
SWBD SWITCHBOARD
CHEM CHEMICAL ELEC ELECTRIC, ELECTRICAL H HIGH MBH 1000 BTU PER HOUR PRV PRESSURE REDUCING VALVE, POWER ROOF VENTILATION XP EXPLOSION PROOF
SWGR SWITCHGEAR
CHIS
CHWP
CHISELED
CHIILLED WATER PUMP
ELEV
ELL
ELEVATOR, ELEVATION
EMERGENCY LIFE SAFETY LIGHTING
H.I.D HIGH-INTENSITY DISCHARGE MBR MEMBER PS PRESSURE SWITCH, PERMANENT SEEDING, POINT OF
SWITCH
SYMM SYMMETRICAL YD YARD $
HAST HAZMAT STORAGE MC MAIN CROSS CONNECT SYS SYSTEM YHYD YARD HYDRANT
CI CAST IRON ELP EMERGENCY LIFE SAFETY POWER PSC PRESTRESSED CONCRETE
SG003
HB HOSE BIB MCB MAIN CIRCUIT BREAKER T TREAD, TOP, TANGENT, TELEPHONE, THICKNESS
CIP CAST IN PLACE, CULVERT INLET PROTECTION, CAST IRON EM EXPANDED METAL HBD HARDBOARD MCC MOTOR CONROL CENTER PSF POUNDS PER SQUARE FOOT
PIPE T&B TOP AND BOTTOM
EMER EMERGENCY HC HANDICAPPED, HORIZONTAL CROSS CONNECT MCCB MOTOR CASE CIRCUIT BREAKER PSI POUNDS PER SQUARE INCH
CIRC CIRCULAR, CIRCUMFERENCE T&G TOUNGE AND GROVE
1 2 3 4 5 6 7 8 9 10

SHEET NUMBERING SYMBOLOGY


US Army Corps of
DISCIPLINE DESIGNATION Engineers ®
(1 OR 2 CHARACTERS) SHEET TYPE
Middle East District
G 0
PLAN SHEET
COLUMN BUBBLE AND GRIDLINE
CALLOUT NUMBER
KEY PLAN AREA

DATE
AD101A AE401 EL. 52.50'
EL. 15'-6"
CALLOUT REF
LEVEL NAME 1
SEQUENCE BOUNDARY
LEVEL OR FLOOR 15'-6" AE101
DISCIPLINE DESIGNATION

SITE ELEVATION LEVEL ELEVATION SPOT ELEVATION

SHEET FILE DISCIPLINE DESIGNATORS SHEET DRAWN

G- GENERAL AE ARCHITECTURAL ELEMENTS ES ELECTRICAL SITE


GI GENERAL INFORMATION AI ARCHITECTURAL INTERIORS EG ELECTRICAL GROUNDING ROOM NAME

DESCRIPTION
ROOM TAG
F H HAZARDOUS MATERIALS AF ARCHITECTURAL FINISHES EI ELECTRICAL INSTRUMENTATION 101
HA ASBESTOS ABATEMENT ID INTERIORS DEMOLITION EL ELECTRICAL LIGHTING
SPACE NUMBER REFERENCE
V- SURVEY I- INTERIORS EP ELECTRICAL POWER
B- GEOTECHNICAL IN INTERIOR DESIGN ET ELECTRICAL TELECOMMUNICATIONS FLOOR NUMBER
REFERENCE
BB BORING LOGS IF INTERIOR FURNISHINGS EY ELECTRICAL AUXILIARY SYSTEMS 1
CD CIVIL DEMOLITION IG INTERIOR GRAPHICS TD TELECOMMUNICATIONS DEMOLITION REF

REF
C- CIVIL QF FOOD SERVICE T- TELECOMMUNICATIONS SIM
CC CIVIL EROSION AND SEDIMENT FD FIRE PROTECTION DEMOLITION TA AUDIO VISUAL 1 1 AE101 1
CONTROL TC CLOCK AND PROGRAM
____________________________________________________

F- FIRE PROTECTION 1 1 AE101

REF
KEYNOTE
CE CIVIL EXISTING FA FIRE ALARM TI INTERCOM SHEET DRAWN
CS CIVIL SITE FA FIRE ALARM TM MONITORING REF
SHEET DRAWN 1
CG CIVIL GRADING FX FIRE PROTECTION/SUPPRESSION TN DATA NETWORKS
CP CIVIL PAVING PD PLUMBING DEMOLITION TT TELEPHONE
P- PLUMBING TY SECURITY EXTERIOR ELEVATION REFERENCE INTERIOR ELEVATION REFERENCE
CU CIVIL UTILITIES
TS SCADA

MARK
LD LANDSCAPE DEMOLITION PS PLUMBING SITE
POINT OF CONNECTION (NEW TO EXISTING)
L- LANDSCAPE PL PLUMBING FIXTURES
E LS LANDSCAPE SITE PP PLUMBING PIPING
LL LANDSCAPE LIGHTING PQ PLUMBING EQUIPMENT
LP LANDSCAPE PLANTING DQ MATERIAL HANDLING

PLOT SCALE: PLOT DATE:


REFERENCE

2/9/2022 4:56:48
SD STRUCTURAL DEMOLITION MD MECHANICAL DEMOLITION
POINT BETWEE EXISTING WORK TO
S- STRUCTURAL M- MECHANICAL
REMAIN AND EXISTING WORK TO REMOVE

SOLICITATION NO.:

SA-480530-1$-SG004GN.dwg
SS STRUCTURAL SITE MH MECHANICAL HVAC SIM

PM
CONTRACT NO.:
SB STRUCTURAL SUBSTRUCTURE MI MECHANICAL INSTRUMENTATION 1 ARROW AND TAIL INDICATE

ISSUE DATE:
SF STRUCTURAL FRAMING MP MECHANICAL PIPING
____________________________________________________

DIRECTION OF SECTION
AE101
MS MECHANICAL SITE

1:1
SC STRUCTURAL COMPONENTS
SR STRUCTURAL REINFORCEMENT MY MECHANICAL HYDRAULIC SYSTEMS
SHEET DRAWN
AD ARCHITECTURAL DEMOLITION MW MECHANICAL DISTRIBUTED ENERGY
A- ARCHITECTURAL ED ELECTRICAL DEMOLITION
SECTION REFERENCE SHEET FOR
AS ARCHITECTURAL SITE E- ELECTRICAL CONTINUATION

FILE NO.:
SUBMITTED BY:
J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:
MATCH LINE SEE A101B

A. HANKS
D SHEET TYPE DESIGNATORS

E. OKES
CKD BY:

ANSI D
PIPE BREAK FOR SINGLE LINE PIPE BREAK FOR DOUBLE LINE

SIZE:
0 GENERAL (SYMBOLS LEGEND, NOTES, ETC.) BREAKLINE MATCHLINE

TRANSATLANTIC MIDDLE EAST DISTRICT


1 PLANS (HORIZONTAL VIEWS)
2 ELEVATIONS AND PROFILES (VERTICAL VIEWS)

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


3 SECTIONS (SECTIONAL VIEWS, CROSS-SECTIONS, ETC.)
N

WINCHESTER, VA 22602
4 LARGE SCALE VIEWS (ENLARGED PLANS AND ELEVATIONS) LW LW LW
5 DETAILS LIMITS OF WORK
6 SCHEDULES AND DIAGRAMS PLAN NORTH/TRUE NORTH/MECCA
PN
7 USER DEFINED
8 USER DEFINED M
BUILDING LIMITS OF WORK CIVIL LIMITS OF WORK
9 3D REPRESENTATIONS (PERSPECTIVES AND PHOTOGRAPHS)

PLAN OR TYPICAL
DETAIL TITLE
C BUILDING MATERIALS
1
View Name
1 : 100 REVISION NUMBER
EARTH PLYWOOD

DRAWING SCALE

CRUSHED STONE PLASTER OR GWB LIMITS OF REVISION

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


DRAWING REVISION
CONCRETE BATT INSULATION REFERENCE LOCATION SECTION OR

THAAD STANDARD FACILITIES


DETAIL TITLE

VARIOUS LOCATIONS, KSA

GENERAL SYMBOLOGY
STANDARD DETAILS
STEEL RIGID INSULATION
View Name
A1

SA-480530
B 1 : 100

CONCRETE MASONRY UNITS COMPRESSIBLE FILLER DRAWING SCALE

BRICK SAND

ACOUSTICAL TILE

ROUGH WOOD
2/9/2022 4:56:48 PM

A FINISH WOOD SHEET ID


$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SG004
1 2 3 4 5 6 7 8 9 10

GENERAL STRUCTURAL NOTES FOUNDATIONS CAST-IN-PLACE CONCRETE (CONT) STRUCTURAL STEEL


1. THE PROJECT SPECIFICATIONS ARE A PART OF THE CONTRACT DOCUMENTS. 1. PROVIDE SHEETING, BRACING, AND DEWATERING, AS REQUIRED. 15. NO CONCRETE MUST BE CAST BEFORE REVIEW AND APPROVAL OF THE REINFORCING 1. STRUCTURAL STEEL MUST CONFORM TO THE FOLLOWING, UNLESS OTHERWISE NOTED:
US Army Corps of
AND EMBEDDED ITEMS SHOP DRAWINGS HAS BEEN OBTAINED FROM THE CONTRACTING A. WIDE-FLANGE AND TEE SHAPES: ASTM A992, GRADE 50,
2. THE CONTRACTOR MUST EXAMINE THE STRUCTURAL DRAWINGS AND MUST NOTIFY THE 2. PRIOR TO CONCRETE PLACEMENT, WATER PRESENT MUST BE PUMPED OUT FROM THE OFFICER. Engineers ®
MINIMUM Fy = 345 MPa
CONTRACTING OFFICER OF DISCREPANCIES BEFORE PROCEEDING WITH WORK. BOTTOM OF EXCAVATIONS TO A LEVEL APPROVED BY THE GEOTECHNICAL ENGINEER. B. CHANNEL SHAPES: ASTM A36, MINIMUM Fy = 250 MPa Middle East District
G FOUNDATIONS MUST NOT BE PLACED IN WATER. 16. NO HORIZONTAL CONSTRUCTION JOINTS MUST BE MADE IN BEAMS AND PILE CAPS, C. ANGLE SHAPES: ASTM A36, MINIMUM Fy = 250 MPa
3. THE DRAWINGS AND SPECIFICATIONS REPRESENT THE COMPLETED STRUCTURE. THEY UNLESS SHOWN SPECIFICALLY ON DRAWINGS. FOR VERTICAL CONSTRUCTION JOINTS, D. RECTANGULAR HSS SECTIONS: ASTM A500, GRADE C,
DO NOT INDICATE THE METHOD OF CONSTRUCTION. PROVIDE MEASURES AND MEANS 3. PROVIDE A WELL COMPACTED SELECT GRAVEL BASE COURSE CONFORMING TO THE REFER TO ACI 318, SECTION 6.4 AND TYPICAL DETAILS. MINIMUM Fy = 345 MPa
NECESSARY TO PROTECT PERSONS AND STRUCTURES DURING CONSTRUCTION. SUCH SPECIFICATIONS UNDER SLABS-ON-GROUND AND PER THE DETAILS SHOWN IN THE E. BARS, RODS AND PLATES: ASTM A572, GRADE 50,

DATE
MEASURES MUST INCLUDE, BUT NOT BE LIMITED TO BRACING, SHORING, ETC. DRAWINGS. 17. LOCATE CONSTRUCTION JOINTS IN FLOORS AND ROOFS NEAR THE MIDDLE OF THE SPANS MINIMUM Fy = 345 MPa
OBSERVATIONS BY THE ARCHITECT, ENGINEER, OR CONTRACTING OFFICER DOES NOT OF SLABS AND BEAMS, UNLESS OTHERWISE INDICATED ON THE PLANS. IF A BEAM F. BASE PLATES: ASTM A572, GRADE 50,
INCLUDE THE REVIEW OF THESE MEASURES. 4. REQUIRED INSERTS SLEEVES, CONDUITS, EMBEDMENT AND PENETRATIONS MUST BE INTERSECTS A GIRDER AT THIS LOCATION, OFFSET THE CONSTRUCTION JOINT IN THE MINIMUM Fy = 345 MPa
VERIFIED WITH RESPECTIVE TRADE BEFORE CONCRETE PLACEMENT. GIRDER A DISTANCE EQUAL TO TWICE THE WIDTH OF THE BEAM. SUBMIT DRAWINGS G. CONVENTIONAL HIGH-STRENGTH BOLTS: ASTM F3125, GRADE A325 TC
4. SPECIFICATIONS TAKE PRECEDENCE OVER GENERAL NOTES AND DETAILS ON THE SHOWING INTENDED PLACING SEQUENCES AND LOCATIONS OF CONSTRUCTION JOINTS H. STAINLESS STEEL BOLTS: ASTM F593
STRUCTURAL DRAWINGS IN CASE OF A CONFLICT. TYPICAL DETAILS MUST BE USED 5. DOWELS FROM FOOTINGS INTO PIERS, COLUMNS, BUTTRESSES, OR WALLS MUST BE THE AND GRADE BEAM JOINTS TO THE ENGINEER FOR APPROVAL. I. ANCHOR RODS: ASTM F1554, GRADE 55
WHENEVER APPLICABLE, EXCEPT WHERE NOTED OTHERWISE. SAME SIZE AND NUMBER AS REINFORCEMENT IN PIERS, COLUMNS, BUTTRESSES, OR WALLS J. THREADED RODS: ASTM A36, MINIMUM Fy = 250 MPa
ABOVE, EXCEPT AS OTHERWISE SHOWN. 18. CAST SLABS AND BEAMS MONOLITHICALLY, UNLESS OTHERWISE INDICATED. K. HEADED SHEAR STUDS: ASTM A108 / AWS D1.1, TYPE B
5. WORK NOT DETAILED OR NOTED MUST BE CONSTRUCTED IN ACCORDANCE WITH L. WELD ELECTRODES: E70XX
OTHER SIMILAR WORK SHOWN ON THE DRAWINGS AND TYPICAL DETAILS. DIMENSIONS 6. PROVIDE CONTINUOUS DRAINAGE TO CONTROL SURFACE WATER, AS REQUIRED DURING 19. SHEAR KEYS MUST BE 50 mm x 100 mm (NOMINAL) UNLESS SHOWN OTHERWISE ON M. HARDENED WASHERS: ASTM F436M
MUST TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. DRAWINGS CONSTRUCTION. DRAWINGS. N. HEAVY HEX NUTS: ASTM A563M
MUST NOT BE SCALED FOR CONSTRUCTION PURPOSES. O. STAINLESS STEEL STRUCTURAL SHAPES: ASTM A276, 304 STAINLESS STEEL
7. FOOTINGS MUST BE CENTERED UNDER SUPPORTED MEMBERS, UNLESS NOTED OTHERWISE 20. EXPOSED EDGES OF CONCRETE ELEMENTS, SUCH AS COLUMNS, PILASTERS, BEAMS,
6. NO PIPES OR DUCTS ARE TO BE PLACED IN OR PENETRATE THROUGH STRUCTURAL ON PLANS. CURBS AND EQUIPMENT PADS WILL HAVE 20 mm CONCRETE CHAMFER, UNO. 2. EACH WELDER, TACKER, AND WELDING OPERATOR MUST BE CERTIFIED BY TEST WITHIN THE
MEMBERS UNLESS SPECIFICALLY DESIGNED AND DETAILED OR PERMITTED AS PER THE PAST SIX MONTHS TO PERFORM THE TYPE OF WORK REQUIRED IN CONFORMANCE WITH THE

DESCRIPTION
F TYPICAL DETAILS. 8. DO NOT PLACE BACKFILL AGAINST WALLS UNTIL SLABS AND WALL BRACING ARE IN-PLACE 21. NOT ALL OPENINGS THROUGH CONCRETE SLABS AND WALLS ARE SHOWN ON AWS D1.1 – STRUCTURAL WELDING CODE.
AND AFTER CONCRETE HAS ATTAINED DESIGN STRENGTH. SHORE AND / OR BRACE WALLS AS STRUCTURAL DRAWINGS. OPENINGS INDICATED, OR ANY ADDITIONAL OPENINGS OR
7. REFER TO ARCHITECTURAL DRAWINGS FOR THE FOLLOWING: REQUIRED IF BACKFILLING OPERATIONS ARE TO BE CARRIED OUT PRIOR TO PLACEMENT OF INSERTS REQUIRED, MUST BE VERIFIED WITH RESPECTIVE TRADES BEFORE CONCRETE 3. CONNECTIONS MUST BE BOLTED WITH HIGH-STRENGTH BOLTS OR WELDED IN ACCORDANCE
A. SIZE AND LOCATION OF DOOR AND WINDOW OPENINGS; EXCEPT AS NOTED ON FLOOR SLABS. PLACEMENT. PROVIDE OPENINGS THROUGH FOUNDATION WALLS AS REQUIRED BY TO AWS D1.1 – STRUCTURAL WELDING CODE AND WITH THE AISC MANUAL REQUIREMENTS,
THESE DRAWINGS. MECHANICAL TRADES. REQUIRED INSERTS, SLEEVES, CONDUITS, EMBEDMENTS, AND UNLESS OTHERWISE NOTED.
B. SIZE AND LOCATION OF INTERIOR AND EXTERIOR NON-BEARING PARTITIONS. 9. WHERE BACKFILL WILL BE PLACED ON BOTH SIDES OF FOUNDATION WALLS, PROVIDE A PENETRATIONS MUST BE VERIFIED WITH RESPECTIVE TRADES BEFORE CONCRETE
C. SIZE AND LOCATION OF CURBS, FLOOR DRAINS, SLOPES, DEPRESSED AREAS, BALANCED BACKFILL AGAINST FOUNDATION WALLS TO ELIMINATE LATERAL LOAD EFFECTS, PLACEMENT. 4. SHOP CONNECTIONS MAY BE BOLTED WITH HIGH STRENGTH BOLTS OR WELDED IN
CHANGES IN LEVEL, RAMPS, CHAMFERS, GROOVES, INSERTS, ETC. OR PROVIDE NECESSARY TEMPORARY LATERAL SUPPORT TO THE TOP OF THE WALL UNTIL ACCORDANCE WITH AWS D1.1 – STRUCTURAL WELDING CODE, UNLESS THE CONNECTION
D. SIZE AND LOCATION OF FLOOR AND ROOF OPENINGS; EXCEPT AS NOTED ON PERMANENT SUPPORT IS PROVIDED. 22. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY EXACT SIZES AND LOCATIONS METHOD IS SPECIFICALLY INDICATED ON THE STRUCTURAL DRAWINGS.
THESE DRAWINGS. OF OPENINGS, CONCRETE PADS OR CURBS, WELDING PLATES, WITH THE APPROPRIATE
E. FLOOR AND ROOF FINISHES. 10. BACKFILL MATERIAL MUST BE COMPACTED TO 95% OF MAXIMUM DENSITY, AS DETERMINED BY SUBCONTRACTORS WELL IN ADVANCE, SO THAT ADJUSTMENTS IN REINFORCING OR 5. SUPPLY PLATES, CLIPS, SEAT ANGLES, ANGLE BRACKETS, CONNECTIONS, ETCETERA, AS
F. STAIR FRAMING AND DETAILS; EXCEPT AS NOTED ON THESE DRAWINGS. THE MODIFIED PROCTOR METHOD (ASTM D1557), IN LIFTS NOT EXCEEDING 200 mm. LOCATION MAY BE MADE WITHOUT INTERRUPTION OF THE WORK SCHEDULE. REQUIRED FOR COMPLETION OF THE STRUCTURE, EVEN IF SUCH ITEMS ARE NOT EXPLICITLY
G. DIMENSIONS NOT SHOWN ON THESE DRAWINGS. CALLED FOR ON THE ARCHITECTURAL OR STRUCTURAL DRAWINGS.
11. FOUNDATIONS, INCLUDING SLAB-ON-GRADE, MUST BE POURED ON TOP OF A 100 mm-THICK 23. PIPES, CONDUITS, ETC. MUST NOT BE EMBEDDED IN CAST IN PLACE CONCRETE UNLESS
8. REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR THE FOLLOWING: BLINDING CONCRETE SLAB. SPECIFICALLY NOTED ON THE STRUCTURAL DRAWINGS. 6. PROVIDE EMBEDDED PLATES, SLEEVES, BOX OUTS, CONDUITS, ETCETERA, AS REQUIRED BY
A. PIPE RUNS. SLEEVES, HANGERS, EQUIPMENT, AND SLAB OPENINGS; EXCEPT AS OTHER TRADES IN THE CONCRETE STRUCTURE.
NOTED ON THESE DRAWINGS. 12. FOOTING EXCAVATIONS MUST BE INSPECTED AND APPROVED BY THE CONTRACTING 24. REFER TO ARCHITECTURAL DRAWINGS FOR FINISHES, DEPRESSIONS, REGLETS, NOTCHES

MARK
B. ELECTRICAL CONDUIT, BOXES, OUTLETS. OFFICERS REPRESENTATIVE PRIOR TO PLACING CONCRETE. AND OTHER ARCHITECTURAL FEATURES. 7. PROVIDE ONE HARDENED WASHER AND HEAVY HEX NUT WITH STRUCTURAL CONNECTION
C. CONCRETE INSERTS FOR ELECTRICAL, MECHANICAL, AND PLUMBING FIXTURES. BOLTS AND ANCHOR BOLTS, UNLESS OTHERWISE INDICATED ON THE DRAWING.
D. SIZE AND LOCATION OF MACHINE AND EQUIPMENT BASES. 13. SOIL MOISTURE CONTENT FOR BACKFILL SOILS AT THE TIME OF COMPACTION MUST BE 25. PROVIDE SEALANT JOINT FOR EXPOSED TO VIEW CONSTRUCTION JOINTS, CONTROL
E WITHIN PLUS OR MINUS TWO PERCENT OF THE OPTIMUM MOISTURE CONTENT, AS JOINTS AND SHEAR KEYS. 8. PROVIDE ANCHOR BOLTS, SETTING PLATES AND EMBEDDED PLATES TO BE SET BY OTHERS.
9. COORDINATE OPENINGS IN CONCRETE SLABS OR WALLS WITH ARCHITECTURAL, PRESCRIBED BY GEOTECHNICAL REPORT.
MECHANICAL, ELECTRICAL, PLUMBING DRAWINGS. ENSURE OPENING SIZES MEET 26. SET ANCHOR BOLTS AND EMBEDDED PLATES REQUIRED FOR CONNECTION OF WORK BY 9. PROVIDE 6 mm THICK LEVELING PLATES FOR USE IN ALIGNING AND SETTING ANCHOR BOLTS

PLOT SCALE: PLOT DATE:


MANUFACTURER REQUIREMENTS FOR PRODUCTS SELECTED AND NOTIFY THE OTHER TRADES/ERECTORS/MANUFACTURERS. AND BASE PLATES, UNLESS OTHERWISE NOTED.

9:07:27 AM
2/22/2022
CONTRACTING OFFICER OF ANY PROPOSED ADJUSTMENTS TO OPENING SIZES.
CAST-IN-PLACE CONCRETE

SOLICITATION NO.:

SA-480530-1$-SS001GN.dwg
27. PROVIDE CONCRETE PADS FOR MECHANICAL EQUIPMENT ACCORDING TO THE 10. TOP-OF-STEEL ELEVATIONS INDICATED ON THE DRAWINGS REFER TO TOP OF BEAM TOP

CONTRACT NO.:
10. REFER TO APPLICABLE BUILDING CODE FOR ASTM REFERENCES, REVISIONS AND ISSUE, REQUIREMENTS OF THE MANUFACTURER AND IN ACCORDANCE WITH THE TYPICAL FLANGE, UNLESS OTHERWISE NOTED.

ISSUE DATE:
UNLESS OTHERWISE NOTED. DETAILS. ALWAYS PROVIDE MINIMUM SHRINKAGE REINFORCEMENT PER ACI 318-14 FOR
1. CONCRETE QUALITY IN ACCORDANCE WITH THE REQUIREMENTS OF THESE DRAWINGS AND PADS, UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH MECHANICAL 11. PROVIDE NECESSARY TEMPORARY GUYING AND BRACING REQUIRED TO ERECT AND HOLD

1:1
11. INVESTIGATE THE SITE DURING CLEARING. UNCONSOLIDATED AND UNDOCUMENTED SPECIFICATIONS IS ESSENTIAL TO THE STRUCTURAL PERFORMANCE OF THE STRUCTURE. DRAWINGS. FRAME FOR WIND AND CONSTRUCTION LOADS.
FILLS, BURIED STRUCTURES, UTILITIES, ETC. IMMEDIATELY NOTIFY THE CONTRACTING CONCRETE THAT IS NOT IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS WILL
OFFICER OF SITE CONDITIONS NOT REFLECTED ON THE DRAWINGS, OR DIFFERENCES NOT BE ACCEPTED. 28. PROVIDE CONDENSATE PITS AND OTHER DEPRESSIONS OR CURBS AS REQUIRED FOR 12. MAKE SHOP AND FIELD CONNECTIONS, UNLESS WELDED, WITH 20 mm MINIMUM DIAMETER
FROM MAXIMUM OR MINIMUM DIMENSIONS INDICATED, INCLUDING CONFLICT IN GRADES, COMPLETION OF THE MECHANICAL WORK. HIGH STRENGTH BOLTS; AND UNLESS SPECIFICALLY INDICATED OTHERWISE IN THE
ADVERSE SOIL CONDITIONS, GROUND WATER PRESENT, DEEPENED FOOTINGS, 2. CONCRETE MUST BE NORMAL-WEIGHT CONCRETE, UNLESS OTHERWISE NOTED, MIXED AND STRUCTURAL DRAWINGS, IN STANDARD HOLES. PROVIDE ONE HARDENED WASHER UNDER

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


UNCOVERED AND UNEXPECTED UTILITY LINES, ETC. PLACED UNDER THE SUPERVISION OF AN APPROVED CONCRETE TESTING AGENCY. 29. EMBEDDED PLATES AND ANCHOR BOLTS MUST BE SET WITHIN 3 mm TOLERANCE IN ANY THE ELEMENT TURNED IN TIGHTENING.

FILE NO.:
CONCRETE MUST BE STONE AGGREGATE, UNLESS OTHERWISE NOTED, AND MUST DEVELOP DIRECTION. USE TEMPLATES TO PLACE ANCHOR BOLTS AND PROVIDE THE MINIMUM
12. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE STABILITY OF THE STRUCTURE WHILE PROJECTION SHOWN ON THE DRAWINGS. 13. BOLTED MOMENT CONNECTIONS AT CANTILEVERS AND BACKSPANS MUST USE SLIP-

SUBMITTED BY:
THE FOLLOWING 28-DAY COMPRESSIVE STRENGTHS (f’c):
UNDER CONSTRUCTION. CONSTRUCTION MATERIALS MUST BE SPREAD OUT IF PLACED CRITICAL BOLTS WITH "CLASS B" SURFACE, UNLESS OTHERWISE NOTED.

A. ALHMOOD
A. FOOTINGS AND MAT SLABS 35 MPa

DESIGN BY:

DRAWN BY:
ON STRUCTURAL FRAME SUCH THAT THE LOADING DOES NOT EXCEED THE DESIGN LIVE 30. PROVIDE POCKETS OR RECESSES IN CONCRETE WORK FOR STEEL COLUMNS AND BEAMS

A. HANKS
D B. GRADE BEAMS 35 MPa

CKD BY:
LOADS. PROVIDE SHORING AND BRACING WHERE DESIGN STRENGTH HAS NOT BEEN AS REQUIRED AND / OR CALLED FOR BY THE SPECIFICATIONS EVEN IF IT IS NOT SHOWN 14. EXPOSED, EXTERIOR STEEL MUST BE GALVANIZED AS PER SPECIFICATION 05 12 00 AND

ANSI D
C. FOUNDATION WALLS 35 MPa

SIZE:
ATTAINED AND/OR STRUCTURE IS NOT COMPLETE. D. SLABS-ON-GROUND 31 MPa ON THE DRAWINGS. PROVIDE CONCRETE FILL AFTER STEEL ERECTION TO COMPLETE THEN COATED WITH HIGH-PERFORMANCE COATING PER SPECIFICATION 09 96 00, UNLESS
E. STRUCTURAL SLABS 35 MPa SEAL OF EXPOSED OPENINGS OR RECESSES. OTHERWISE NOTED.
13. DETERMINE THE LOCATION OF UTILITY SERVICES IN AREAS TO BE EXCAVATED BEFORE F. WALLS, COLUMNS AND BEAMS 35 MPa
BEGINNING EXCAVATION. NOTIFY UTILITIES THREE DAYS PRIOR TO DEMOLITION AND 31. INCLUDE IN THE ESTIMATES AN ALLOWANCE FOR DEFLECTION AND OTHER FACTORS THAT 15. BRACING MEMBERS MUST BE DETAILED TO AVOID ECCENTRIC CONNECTIONS.

TRANSATLANTIC MIDDLE EAST DISTRICT


G. EXTERIOR CONCRETE 31 MPa
EXCVAVATION AND PROVIDE CONTACT INFORMATION. EXERCISE CAUTION IN H. BLINDING SLABS 15 MPa MAY CONTRIBUTE TO CONCRETE QUANTITY.

US ARMY CORPS OF ENGINEERS


EXCAVATING AND TRENCHING. 16. COLUMN END SPLICES MUST BE MILLED IN ACCORDANCE WITH THE TYPICAL DETAILS.

201 PRINCE FREDERICK DRIVE,


I. LIGHTWEIGHT CONCRETE 21 MPa
32. BOLTS, INSERTS, PLATES AND STEEL PIECES WHICH ARE EXPOSED TO WEATHER MUST BE

WINCHESTER, VA 22602
14. STRUCTURAL DRAWINGS MUST BE USED IN CONJUNCTION WITH ARCHITECTURAL 3. CONCRETE MUST REACH THE FOLLOWING PERCENTAGES OF ITS 28-DAY COMPRESSIVE GALVANIZED. 17. BEAMS MUST BE FABRICATED WITH NATURAL CAMBER UP.
DRAWINGS. STRENGTH (f'c) BEFORE FORMS OR SHORES MAY BE REMOVED:
A. WALLS 40% 33. SUBMIT DRAWINGS SHOWING INTENDED PLACING SEQUENCES AND LOCATIONS OF 18. STIFFENER PLATES MUST BE PROVIDED IN PAIRS, EACH SIDE OF BEAM OR COLUMN WEB,
15. THE PROJECT UNITS ARE METRIC UNITS UNLESS OTHERWISE NOTED. B. SLABS, BEAMS 70% CONSTRUCTION JOINTS TO THE CONTRACTING OFFICER FOR APPROVAL. UNLESS OTHERWISE NOTED.

16. BUILDING ELEVATIONS ARE GIVEN AS REFERENCE ELEVATIONS TO THE REFERNCE 4. STEEL REINFORCEMENT MUST CONFORM TO THE FOLLOWING, UNLESS OTHERWISE NOTED: 34. AT LOCATIONS WHERE ANCHOR REINFORCEMENT IS REQUIRED PER THE DETAILS, IT 19. PRIOR TO DETAILING STRUCTURAL STEEL, THE FABRICATOR MUST SUBMIT PLANS FOR EACH
POINT GRADE ELEVATION. A REFERENCE GRADE ELEVATION OF 0.00 mm IS USED. A. DEFORMED REINFORCING BARS ASTM A615, GRADE 420, MUST BE PLACED AS CLOSE TO THE ANCHORS AS PRACTICABLE AND AS CLOSE TO LEVEL AND CONFIRM DIMENSIONS. THE DETAILS ON THESE DRAWINGS DO NOT SHOW
MINIMUM Fy = 420 MPa CONCRETE SURFACE AS POSSIBLE WHILE OBSERVING CONCRETE COVER ERECTION AIDS. PROVIDE ERECTION AIDS AS REQUIRED AND REMOVE THEM AFTER WORK
17. REPRODUCTION OF CONTRACT DRAWINGS MUST NOT BE USED AS SHOP DRAWINGS B. WELDED WIRE REINFORCEMENT ASTM A1064, GRADE 450, REQUIREMENTS. IS COMPLETE, IF EXPOSED TO VIEW.
WITHOUT WRITTEN APPROVAL OF THE CONTRACTING OFFICER'S REPRESENTATIVE. MINIMUM Fy = 450 MPa
35. WELDING OF REINFORCEMENT IS NOT PERMITTED. 20. NO STEEL GRADE SUBSTITUTION IS ACCEPTABLE WITHOUT THE APPROVAL OF THE
C 18. DIMENSIONS SHOWN ARE TO STRUCTURAL ELEMENTS AND DO NOT INCLUDE 5. STEEL REINFORCEMENT MUST HAVE THE FOLLOWING CONCRETE COVER, UNLESS CONTRACTING OFFICER.
ARCHITECTURAL TREATMENTS SUCH AS PLASTER FINISH OR SPRAY-ON FIRE OTHERWISE NOTED: 36. PROVIDE 13 mm JOINT FILLER MATERIAL WHERE SLABS-ON-GRADE ABUT VERTICAL
PROOFING. CONCRETE AND MASONRY OPENINGS THAT ARE INDICATED ON THE A. FOUNDATIONS AND SURFACES PLACED IN CONTACT WITH SURFACES. 21. IF ELEMENTS ARE SPECIFIED AS GALVANIZED, REPAIR DAMAGE TO GALVANIZING COATINGS
FACILITY DRAWINGS MAY VARY WITH THE EQUIPMENT PROVIDED. COORDINATE THE GROUND 75 mm USING ASTM A780/A780M ZINC RICH PAINT FOR GALVANIZING DAMAGED BY HANDLING
OPENING REQUIREMENTS WITH ALL TRADES. B. FORMED SURFACE EXPOSED TO GROUND OR WEATHER 50 mm 37. ALL EMBEDDED ITEMS MUST BE PROPERLY PLACED, ACCURATELY POSITIONED, AND TRANSPORTING, CUTTING, WELDING, OR BOLTING PER SPECIFICATION 05 12 00.
C. WALLS 50 mm MAINTAINED SECURELY IN PLACE PRIOR TO AND DURING CONCRETE PLACEMENT.
19. IMPLEMENTATION OF JOB SITE SAFETY IS THE SOLE RESPONSIBILITY OF THE D. SLABS 20 mm 22. PROJECT WAS DEVELOPED WITH USE OF BIM MODEL. CONTRACTOR MAY REQUEST USE OF
CONTRACTOR. E. PIERS AND COLUMNS 40 mm 38. REINFORCING STEEL MUST BE SPREAD AT SLEEVES, TIEBACKS RECESSES AND OTHER BIM MODEL FOR STEEL AND OTHER DETAILING SOFTWARE, PROVIDE A REQUEST TO
F. BEAMS 40 mm EMBEDDED ITEMS UNLESS OTHERWISE INDICATED. REINFORCEMENT MUST NOT BE CUT CONTRACTING OFFICER.
20. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING AND COORDINATING TO FACILITATE PLACEMENT OF EMBEDDED ITEMS.

STRUCTURAL GENERAL NOTES - SHEET 1 OF 3


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
DIMENSIONS AND INSTALLATION DETAILS FOR PURCHASED EQUIPMENT WITH THE 6. REINFORCEMENT FOR BURIED CONCRETE ELEMENTS/STRUCTURES MUST BE ZINC-COATED
SUPPORTING STRUCTURE. CONFLICT BETWEEN THESE ITEMS AND THE BUILDING (GALVANIZED) AS PER ASTM A767M -19 DUE TO SOIL CHLORIDE CONTENT. REFER TO 39. CONCRETE MUST NOT BE PLACED UNTIL THE CONTRACTING OFFICERS REPRESENTATIVE
STRUCTURE MUST BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICERS SPECIFICATION 03 30 00. HAS INSPECTED EMBEDDED WORK, INCLUDING REINFORCEMENT.
REPRESENTATIVE FOR RESOLUTION.

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
7. USE TYPE V SULFATE RESISTANT CEMENT FOR CONCRETE IN CONTACT WITH SOIL. 40. ALUMINUM MUST NOT BE PLACED IN DIRECT CONTACT WITH CONCRETE UNLESS
21. FOR STRUCTURE DESIGN CRITERIA, REFER TO DRAWINGS FOR SPECIFIC STRUCTURES. EFFECTIVELY COATED OR COVERED TO PREVENT ALUMINUM-CONCRETE REACTION AND

STANDARD DETAILS
8. DESIGN AND CONSTRUCTION OF FORMWORK MUST COMPLY WITH ACI 318-14 AND ELECTROLYTIC ACTION BETWEEN ALUMINUM AND STEEL.
22. FOR ADDITIONAL REQUIREMENTS FOR STRUCTURES DESIGNED UNDER UNIFIED ACI-347R-14 – GUIDE TO FORMWORK FOR CONCRETE.

SA-480530
FACILITIES CRITERIA (UFC), REFER TO FACILITY SPECIFIC GENERAL NOTES. 41. WHEN SPECIFIED REINFORCING BAR IS NOT AVAILABLE, THE NEXT LARGER (DIAMETER)
B 9. PROVIDE CLASS B SPLICES FOR CONTINUOUS REINFORCEMENT, UNLESS OTHERWISE SIZE BAR MAY BE SUBSTITUTED AS LONG AS MINIMUM SPACING BETWEEN REBAR IS
23. FOR ADDITIONAL REQUIREMENTS FOR STRUCTURES DESIGNED UNDER SAUDI BUILDING INDICATED. MINIMUM ANCHORAGE AND SPLICE REQUIREMENTS FOR REINFORCING BARS MUST MAINTAINED FOR THE SUBSTITUTED REINFORCING BAR SIZE.
CODE (SBC), REFER TO FACILITY SPECIFIC GENERAL NOTES. BE ACCORDING TO ACI 318-14.
42. CONCRETE SLABS MUST BE CURED BY METHOD COMPATIBLE WITH SPECIFIED FLOOR
SPECIAL INSPECTIONS 10. IN SLABS AND BEAMS, LAP CONTINUOUS BOTTOM REINFORCEMENT AT SUPPORTS AND FINISH. WHERE ACCEPTABLE USE A LIQUID MEMBRANE-CURING COMPOUND AT THE
MANUFACTURER'S RECOMMENDED COVERAGE.
CONTINUOUS TOP REINFORCEMENT AT THE CENTER OF A SPAN, UNLESS OTHERWISE
1. SPECIAL INSPECTIONS MUST BE PERFORMED AND DOCUMENTED AS SPECIFIED IN THE INDICATED. PROVIDE STANDARD HOOKS FOR TOP BARS AT DISCONTINUOUS ENDS.
43. SLOPE SLABS-ON-GROUND TO DRAIN AS PER THE DRAWINGS. MAINTAIN MINIMUM DESIGN
STATEMENT OF SPECIAL INSPECTIONS AND SCHEDULE OF SPECIAL INSPECTIONS.
11. WHERE COLUMNS ARE INTEGRAL WITH WALLS, EXTEND COLUMN REINFORCEMENT (TIES AND THICKNESS INDICATED.
REFER TO SPECIFICATION 01 45 35.
LONGITUDINAL BARS) AS INDICATED.
44. REFER TO HOT WEATHER SECTION IN SPECIFICATION 03 30 00 FOR REQUIREMENTS.
2. DIRECTLY EMPLOY, WITH THE APPROVAL OF THE CONTRACTING OFFICER, THE SPECIAL
INSPECTOR TO PERFORM THE REQUIREMENTS OF THE SPECIAL INSPECTIONS. 12. PROVIDE BAR SUPPORTS, SPACERS AND ACCESSORIES RECOMMENDED IN THE ACI DETAILING
MANUAL 2004, PUBLICATION SP-66. REINFORCEMENT DETAILING, LAP SPLICES AND 45. NON-SHRINK CEMENT BASED GROUT WILL BE REQUIRED FOR STRUCTURAL AND
EMBEDMENT MUST CONFORM TO THIS MANUAL. ACCESSORIES, SUCH AS SLAB BOLSTERS AND EQUIPMENT GROUTING.
BEAM AND SLAB CHAIRS IN CONTACT WITH EXPOSED SURFACES MUST BE PLASTIC COATED.
46. SLAB-ON-GROUND CONTROL JOINT (CJ) INDICATED IN PLANS CAN BE SUBSTITUTED WITH
2/22/2022 9:07:27 AM

13. DETAILING OF REINFORCEMENT MUST BE ACCORDING TO THE LATEST EDITION OF ACI 315 CONSTRUCTION JOINTS (CTJ) AS NEEDED, FOLLOWING THE PROVIDED TYPICAL DETAILS.
A "MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES".
47. CONCRETE BEAM DEPTH LISTED IN CONCRETE BEAM SCHEDULES INCLUDES SLAB SHEET ID
14. PROVIDE DOWELS IN FOOTING TO MATCH CAST-IN-PLACE WALL REINFORCEMENT. SET AND TIE THICKNESS.
REINFORCEMENT BEFORE PLACING CONCRETE. SETTING DOWELS AND REINFORCEMENT INTO $
WET CONCRETE IS PROHIBITED. 48. REINFORCEMENT OF PARAPETS SHALL BE FULLY DEVELOPED EITHER INTO THE
SPANDREL/WALL BELOW. DEVELOPMENT CAN BE EITHER BY USING A STRAIGHT OR
HOOKED REBAR. REFER TO TABLES ON SS-002. UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS001
1 2 3 4 5 6 7 8 9 10

STEEL DECKS CONCRETE UNIT MASONRY (CONT.) METAL BUILDING SYSTEMS DEVELOPMENT LENGTH DEVELOPMENT LENGTH SCHEDULE NOTES:
1. CASES FOR STRAIGHT BARS IN TENSION
FOR STRAIGHT DEFORMED BARS IN TENSION ARE DEFINED AS FOLLOWS:
1. STEEL DECKS MUST HAVE A MINIMUM YIELD STRENGTH OF 275 MPa. 16. REFER TO PLANS AND DETAILS FOR BONDED JOINT REQUIREMENTS AT WALL CORNERS 1. THE PRE-ENGINEERED METAL BUILDING (PEMB) MANUFACTURER MUST DESIGN AND US Army Corps of
AND INTERSECTIONS. WHERE INDICATED ON DRAWINGS, INTERLOCK WALLS WITH DETAIL A METAL BUILDING MEETING THE DESIGN CRITERIA LISTED, AS WELL AS ALL 31 MPa NORMAL-WEIGHT CONCRETE CASE 1A: CLEAR SPACING, CS, Engineers ®
2. PROVIDE STEEL DECK WITH DEPTH AND MINIMUM THICKNESS INDICATED ON THE METAL TIES, ANCHORS, OR PREFABRICATED JOINT REINFORCEMENT, UNLESS OTHER REQUIREMENTS OF THE CONTRACT DOCUMENTS, DRAWINGS, AND GALVANIZED ASTM A615 GRADE 420 STEEL BETWEEN BARS BEING DEVELOPED OF LAP Middle East District
CONTRACT DOCUMENTS. OTHERWISE NOTED. SPECIFICATIONS. THE MANUFACTURER MUST SUBMIT FOR APPROVAL DESIGN SPLICED IS GREATER THAN OR EQUAL TO
G CALCULATIONS AND ERECTION SHOP DRAWINGS SEALED BY A PROFESSIONAL CASE 1A/1B1 CASE 21 BAR DIAMETER CLEAR COVER, CC, IS
3. PROVIDE CHECKED SHOP DRAWINGS SHOWING EXACT LAYOUT OF COMPOSITE BEAM 17. CONCRETE UNIT MASONRY IN NON-LOAD BEARING AND BACKUP WALLS MUST BE ENGINEER. SHOP DRAWINGS AND CALCULATIONS SUBMITTED FOR APPROVAL MUST BE
DEFORMED
BAR SIZE TOP2 ALL OTHER TOP2 ALL OTHER GREATER THAN OR EQUAL TO BAR
SHEAR CONNECTIONS FOR EACH BEAM, SPAN, AND DECK TYPE. BRACED DURING CONSTRUCTION UNTIL PERMANENT RESTRAINTS HAVE BEEN 100% COMPLETE, INCLUDING DETAILING. INCOMPLETE SHOP DRAWINGS SUBMITTED DIAMETER STIRRUPS OR TIES THROUGH
Ld Ld Ld Ld

DATE
PROVIDED. FOR APPROVAL WILL NOT BE REVIEWED BY THE ARCHITECT OR STRUCTURAL Ldh ARE PRESENT AND NOT LESS THAN
4. NO LOADS EXCEEDING 0.2 kN WILL BE PERMITTED TO BE HUNG FROM COMPOSITE ENGINEER. (mm ) (mm) (mm) (mm) CODE MINIMUM
DECKING HANGER TABS. HANGER LOADS MUST BE DISTRIBUTED SUCH THAT THE 18. GROUT CMU CELLS AT LADDER SUPPORTS AND WHERE EXPECTED TO HAVE EXPANSION
RESULTING UNIFORM TRIBUTARY LOAD FOR EACH HANGER DOES NOT EXCEED 0.25 ANCHORS. 2. METAL BUILDINGS MUST BE DESIGNED, DETAILED, FABRICATED, AND ERECTED IN ⌀ 10 470 360 705 540 CASE 1B: CLEAR SPACING, CS,
MPa. ACCORDANCE WITH REQUIREMENTS OF THE LOCAL BUILDING CODES, AISC, AISI, AWS,
AND LATEST EDITION OF THE METAL BUILDING MANUFACTURERS ASSOCIATION
⌀ 12 565 435 845 650 BETWEEN BARS BEING DEVELOPED OF LAP
SPLICED IS GREATER THAN OR EQUAL TO
⌀ 14
5. STEEL DECK MUST BE WELDED TO THE SUPPORTING STEEL MEMBERS AT A MAXIMUM
OF 300 mm ON CENTER, USING 20mm PUDDLE WELDS, AND SIDE LAP FASTENERS NOT
POST-INSTALLED ANCHORS PUBLICATION TITLED “METAL BUILDING SYSTEMS MANUAL”.
⌀ 16
655
750
505
575
985
1125
755
865
TWICE BAR DIAMETER CLEAR COVER, CC,
IS GREATER THAN OR EQUAL TO BAR
EXCEEDING 300 mm ON CENTER, UNLESS OTHERWISE NOTED. POWDER ACTUATED 3. PROVIDE LATERAL BRACING FOR BOTH FLANGES OF GIRTS WITH SUPPORTING DIAMETER
FASTENERS MAY BE USED IF APPROVED BY THE STRUCTURAL ENGINEER. FOLLOW THE 1. POST-INSTALLED ANCHORS MUST CONFORM WITH REQUIREMENTS OF ACI 318-14 - CALCULATIONS. FLANGES CONNECTED TO WALL PANELS MUST NOT BE ASSUMED TO ⌀ 18 845 650 1265 970
MANUFACTURERS GUIDELINES FOR INSTALLATION PROCEDURE, PROPERTIES, AND
CAPACITIES. SUBMIT CALCULATIONS FOR APPROVAL.
BUILDING CODE REQUIREMENTS OF STRUCTURAL CONCRETE. BRACE THE OPPOSITE FLANGE OF THE GIRT.
⌀ 20 1155 890 1785 1375 CASE 2: ALL OTHER CASES
2. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING ANCHOR LOCATIONS, AS 4. MEMBER SIZES MUST BE SHOWN ON THE SUBMITTED SHOP DRAWINGS. ⌀ 25 1445 1110 2230 1715 2. "TOP" STRAIGHT BARS IN TENSION ARE
REQUIRED.
6. DECKING MUST BE WELDED TO STRUCTURAL STEEL BY QUALIFIED WELDERS USING
PRE-QUALIFIED PROCEDURES. THE ERECTOR MUST ESTABLISH A WELDING PROCEDURE 5. REGARDLESS OF MANUFACTURER’S TEST DATA, STANDING SEAM ROOF PANELS WILL
⌀ 32 1850 1420 2855 2195 DEFINED AS HORIZONTAL REINFORCING
BARS WITH MORE THAN 300mm OF FRESH

DESCRIPTION
FOR THE WELD OF THE STEEL DECKING TO THE STRUCTURAL STEEL FOR EACH GAGE 3. POST INSTALLED ANCHORS CAPACITY IS DEPENDENT ON THE SELECTED NOT BE CONSIDERED EFFECTIVE TO PROVIDE LATERAL BRACING TO PURLINS, JOISTS, CONCRETE PLACED BELOW Ldh OR Lst.
F USED. PRIOR TO THE START OF ERECTION OF THE STEEL DECK, EACH WELDED MUST MANUFACTURER/PRODUCT. ALL POST INSTALLED ANCHORS SHALL MEET THE MINIMUM ROOF BEAMS, AND ROOF GIRDERS. THE STANDING SEAM ROOF MUST NOT BE DEVELOPMENT LENGTH
BE QUALIFIED USING THIS PROCEDURE AS WITNESSED BY THE OWNER'S TESTING AND DESIGN LOADS LISTED IN DRAWINGS AND DETAILS, AND THE CONTRACTOR SHALL CONSIDERED EFFECTIVE TO PROVIDE DIAPHRAGM ACTION IN THE PLANE OF THE ROOF. FOR STRAIGHT DEFORMED BARS IN TENSION
INSPECTION SERVICE. CONFORM WITH DESIGN CALCULATIONS THAT THE PRODUCT SELECTED MEETS OR CROSS BRACING, OR SUPPLEMENTAL FRAMING MUST BE PROVIDE LATERAL STABILITY
EXCEEDS THE MINIMUM CAPACITIES LISTED IN DETAILS. AND DIAPHRAGM ACTION IN THE PLANE OF THE ROOF. 35 MPa NORMAL-WEIGHT CONCRETE
7. OPENINGS LARGER THAN 150 mm THROUGH STEEL ROOF DECK MUST BE FRAMED WITH GALVANIZED ASTM A615 GRADE 420 STEEL
STEEL SUPPORT MEMBERS AS SHOWN ON THE CONTRACT DOCUMENTS. ACTUAL SIZE 4. ALL POST INSTALLED ANCHORS SHALL MEET THE MINIMUM DESIGN LOADS LISTED IN 6. THE MANUFACTURER MUST SUBMIT FRAME REACTIONS TO THE STRUCTURAL ENGINEER
AND LOCATION OF OPENINGS MUST BE COORDINATED WITH OTHER TRADES. THE DRAWINGS AND DETAILS, AND SHALL BE DESIGNED BY THE CONTRACTOR'S OF RECORD. THESE REACTIONS MUST INCLUDE THE BASIC LOAD CASES AS WELL AS CASE 1A/1B1 CASE 21
ENGINEER CONFORMING TO THE PRODUCT AND MANUFACTURER SELECTED BY THE THE APPLICABLE LOAD COMBINATIONS FROM THE APPLICABLE BUILDING CODE. IN CASE DEFORMED
CONTRACTOR. PROVIDE SIGNED AND SEALED CALCULATIONS FOR REVIEW AND BAR SIZE TOP2 ALL OTHER TOP2 ALL OTHER
8. PROVIDE DECK AND INSTALL DECK ENDS OVER SUPPORTING FRAME WITH A MINIMUM THOSE COLUMN REACTIONS EXCEED THOSE LISTED IN THE DRAWINGS, SUBMIT A
OF 40 mm. LAP END JOINTS 50 mm MINIMUM. APPROVAL. ANCHOR SIZES SHOWN IN DRAWINGS ARE SUGGESTIONS ONLY. REVISED DESIGN AND SHOP DRAWINGS FOR THE FOUNDATIONS TO SUPPORT THE Ld Ld Ld Ld
HIGHER LOADS. (mm ) (mm) (mm) (mm)
9. WELDING OF STEEL DECK MUST PENETRATE ALL LAYERS OF DECK MATERIAL AT END 5. FOR OVERHEAD APPLICATION OR ANCHOR WITH PERMANENT TENSION EXPOSED TO
LAPS AND SIDE JOINTS AND HAVE GOOD FUSION TO THE SUPPORTING STEEL MEMBERS. DYNAMIC LOAD SUCH AS FATIGUE, IMPACT, SHOCK LOAD: HEAVY DUTY EXPANSION 7. BOLTS MUST BE HIGH-STRENGTH AND MUST BE TIGHTENED ACCORDING TO AISC AND ⌀ 10 440 340 660 510
ANCHORS MUST BE USED FOR LOADS LESS THAN 2 kN; UNDERCUT ANCHORS MUST BE MBMA SPECIFICATIONS.
10. UNLESS OTHERWISE NOTED, STEEL DECKING MUST HAVE A GALVANIZED COATING USED FOR LOADS IN EXCESS OF 2 kN. THE USE OF ADHESIVE ANCHORS IS NOT ⌀ 12 530 410 795 610
CONFORMING TO ASTM A653, Z275. ALLOWED. 8. LOADS FROM SPRINKLER PIPING MUST BE COORDINATED WITH THE FIRE PROTECTION ⌀ 14 620 475 925 710
ENGINEER AND/OR CONTRACTOR PRIOR TO THE DESIGN OF THE METAL BUILDING
⌀ 16 705 545 1055 815

MARK
11. ASSURE THAT OPENINGS PENETRATING ROOF DECKS ARE SHOWN ON THE SHOP 6. THE DESIGN OF STRAIGHT POST-INSTALLED REINFORCING BARS TO CONCRETE MUST SYSTEM. THE DESIGN LOADS ASSUME A UNIFORM 14Kg/m2 LOAD FOR SPRINKLER PIPES
DRAWINGS PRIOR TO SUBMITTING FOR REVIEW. OPENINGS MUST BE LOCATED TO BE PERFORMED PER THE DEVELOPMENT AND SPLICE REQUIREMENTS OF ACI 318-14 LESS THAN OR EQUAL TO 50 mm IN DIAMETER. ⌀ 18 795 610 1190 915
E CLEAR WALLS, STEEL JOISTS OR STEEL BEAMS, AND OPENINGS 150 mm x 150 mm OR "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE". THE POST-INSTALLED
⌀ 20 1090 840 1680 1295
LARGER WILL REQUIRE STRUCTURAL FRAME AS SHOWN ON THE CONTRACT REINFORCING BAR SYSTEM IS AN ALTERNATIVE TO CAST-IN-PLACE REINFORCING BARS 9. METAL PANELS ARE CONSIDERED STRUCTURAL COMPONENTS AND MUST NOT BE CUT
DOCUMENTS. IF OPENINGS REDUCE STRUCTURAL CAPACITY, ADJUST OPENINGS AND GOVERNED BY ACI 318-14 AND IBC CHAPTER 19. PROVIDE SIGNED AND SEALED WITHOUT WRITTEN APPROVAL FROM THE PRE-ENGINEERED METAL BUILDING ⌀ 25 1360 1045 2100 1615

PLOT SCALE: PLOT DATE:


ADD STRUCTURAL ELEMENTS OR OTHER MEASURES AS DIRECTED BY CONTRACTING CALCULATIONS SEALED BY A REGISTERED STRUCTURAL ENGINEER. THE EPOXY ENGINEER. DOOR AND WINDOW LOCATIONS MUST NOT DEVIATE FROM THE DRAWINGS
SYSTEM MUST BE TESTED IN ACCORDANCE WITH THE ICC-ES ACCEPTANCE CRITERIA ⌀ 32 1740 1340 2685 2070

2:28:09 PM
OFFICER'S REPRESENTATIVE. CARE MUST BE EXERCISED IN CUTTING OPENINGS, WHEN WITHOUT WRITTEN APPROVAL.

2/11/2022
APPROVED, TO PROVIDE A NEAT EDGE, FREE FROM SPILLS, SHARP FRAGMENTS OR FOR POST-INSTALLED EPOXY ANCHORS IN CONCRETE ELEMENTS (AC308), TABLE 3.8.

SOLICITATION NO.:

SA-480530-1$-SS002GN.dwg
OTHER DEFECTS. ACTUAL SIZE AND LOCATION OF OPENINGS MUST BE COORDINATED TECHNICAL DATA MUST BE PUBLISHED IN AN ICC-ES EVALUATION SERVICE REPORT 10. ROOFS PURLINS AND METAL PANELS OF METAL BUILDINGS MUST BE DESIGNED TO

CONTRACT NO.:
WITH OTHER TRADES. SHOWING COMPLIANCE WITH IBC. ENSURE THAT WHEN THE ROOF IS DEFLECTED UNDER DEAD PLUS LIVE LOADS OR

ISSUE DATE:
DEAD, A NEGATIVE GRADIENT OF THE ROOF SLOPE IS NOT ESTABLISHED. MAXIMUM
CONCRETE UNIT MASONRY 7. CONTINUOUSLY THREADED CARBON STEEL ANCHOR ELEMENTS MUST BE ASTM F1554 DEFLECTIONS MUST BE BASED ON SHEETS TWO OR MORE SUPPORTS WITH SHEETS

1:1
COMPLIANT. UNFASTENED AND FREE TO DEFLECT.
1. CONCRETE UNIT MASONRY IN NON-LOAD BEARING AND BACKUP WALLS MUST CONFORM 8. PROVIDE ANCHORS AND INSTALL PER THE MANUFACTURER INSTRUCTIONS, AS 11. PROVIDE BRACING OF PURLIN COMPRESSION FLANGES AS REQUIRED TO RESIST
TO THE FOLLOWING, UNLESS OTHERWISE NOTED: INCLUDED IN THE ANCHOR PACKAGING. APPLIED LOADING.
A. CONCRETE UNITS/BLOCKS ASTM C90, NORMALWEIGHT, MINIMUM 28-

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


DAY COMPRESSIVE STRENGTH 9. DRILL HOLES WITH ROTARY IMPACT HAMMER DRILLS USING CARBIDE-TIPPED DRILL BIT,

FILE NO.:
12. FRAMED OPENINGS MUST BE DESIGNED STRUCTURALLY.
(f’c) = 6.89 MPa FOR TYPE S OR HOLLOW DRILL BIT WITH INTEGRAL VACUUM CLEAN AS PERMITTED BY ICC-ESR. USE

SUBMITTED BY:
B. MORTAR ASTM C270, TYPE S PORTLAND OF DIAMOND CORE BIT WITH ROUGHENING TOOL WILL BE PERMITTED AFTER 13. ROOF DECKING MUST BE DESIGNED TO SUPPORT, IN ADDITION TO OTHER LOAD

A. ALHMOOD
CEMENT / LIME ONLY BY PROPORTION ENGINEERS OF RECORD APPROVAL. UNLESS OTHERWISE SHOWN ON THE DRAWINGS,

DESIGN BY:

DRAWN BY:
REQUIREMENTS, A 0.2 kN CONCENTRATED LOAD AT MID-SPAN ON A 300 mm WIDE

A. HANKS
C. GROUT ASTM C476, BY PROPORTION, NON-SHRINK
D HOLES MUST BE DRILLED PERPENDICULAR TO THE CONCRETE SURFACE. SECTION OF DECK.

CKD BY:
CLASS B LAP SPLICE LENGTH LAP SPLICE LENGTH SCHEDULE NOTES:

ANSI D
CEMENT BASED, MINIMUM 28-DAY

SIZE:
COMPRESSIVE STRENGTH (f’g) = 10.34 MPa 1. UNLESS OTHERWISE NOTED, FOR LAP
A. DEFORMED REINFORCING BARS ASTM A615, GRADE 420,
10. ARRANGE AN ANCHOR MANUFACTURER’S REPRESENTATIVE TO PROVIDE ONSITE 14. IF USED AS A DIAPHRAGM, ROOF DECKS MUST BE DESIGNED IN ACCORDANCE WITH THE FOR STRAIGHT DEFORMED BARS IN TENSION SPLICES USE CLASS B LAP SPLICE
INSTALLATION TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS SPECIFIED. LATEST EDITION OF THE STEEL DECK INSTITUTE DIAPHRAGM DESIGN MANUAL (SDI- LENGTH FOR STRAIGHT BARS IN
MINIMUM Fy = 420 MPa DDM). 31 MPa NORMAL-WEIGHT CONCRETE TENSION.

TRANSATLANTIC MIDDLE EAST DISTRICT


B. JOINT REINFORCEMENT ASTM A951, MINIMUM Fy = 485 MPa, LADDER 11. INSTALLATION OF ADHESIVE ANCHORS HORIZONTALLY OR UPWARDLY INCLINED TO
TYPE WITH CROSS RODS @ 400 mm ON SUPPORT SUSTAINED TENSION LOADS MUST BE PERFORMED BY PERSONNEL CERTIFIED FLOOR FLATNESS AND LEVELNESS GALVANIZED ASTM A615 GRADE 420 STEEL

US ARMY CORPS OF ENGINEERS


2. CASES FOR STRAIGHT BARS IN

201 PRINCE FREDERICK DRIVE,


CENTER BY AN APPLICABLE CERTIFICATION PROGRAM. CERTIFICATION MUST INCLUDE WRITTEN CASE 1A/1B2 CASE 22 TENSION AND "TOP" STRAIGHT BARS IN
AND PERFORMANCE TESTS IN ACCORDANCE WITH THE ACI/CRSI ADHESIVE ANCHOR DEFORMED
TOP2 TOP2

WINCHESTER, VA 22602
1. MINIMUM COMPRESSIVE STRENGTH OF MASONRY ASSEMBLAGE (f’m) MUST BE 6.90 MPa, INSTALLER CERTIFICATION PROGRAM, OR EQUIVALENT. 1. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR FLOOR FINISH AREAS, TYPES, AND BAR SIZE ALL OTHER ALL OTHER TENSION ARE AS DEFINED FOR
UNLESS OTHERWISE NOTED, VERIFIED BY THE UNIT STRENGTH METHOD IN REQUIREMENTS. DEVELOPMENT OF REINFORCEMENT.
Lst Lst Lst Lst
ACCORDANCE WITH THE ABOVE REFERENCED STANDARDS. 12. ANCHOR CAPACITY IS DEPENDENT UPON SPACING BETWEEN ADJACENT ANCHORS AND
PROXIMITY OF ANCHORS TO EDGE OF CONCRETE. PROVIDE ANCHORS IN ACCORDANCE 2. CONSTRUCT SLABS-ON-GROUND IN ACCORDANCE WITH ONE OF THE METHODS (mm ) (mm) (mm) (mm) 3. WHERE BARS OF DIFFERENT SIZE ARE
LAPPED IN TENSION, Lst MUST BE THE
2. PROVIDE MORTAR TYPES PER THE FOLLOWING: WITH SPACING AND EDGE CLEARANCES INDICATED ON THE DRAWINGS. RECOMMENDED IN ACI 302.1R-15, TABLE 10.15.3a - "SLABS-ON-GROUND ⌀ 10 610 470 915 705 GREATER OF Ld FOR THE LARGER BAR
A. EXTERIOR AND INTERIOR WALLS TYPE S FLATNESS/LEVELNESS CONSTRUCTION GUIDE" FOR THE FOLLOWING SPECIFIED
13. REINFORCEMENT MUST NOT BE CUT FOR ANCHORS. UNDERTAKE TO LOCATE THE REQUIREMENTS: ⌀ 12 730 565 1095 845 AND Lst OF THE SMALLER BAR.
3. MORTAR AND GROUT PRODUCTS MUST NOT CONTAIN CALCIUM CHLORIDE. POSITION OF THE REINFORCING BARS AT THE LOCATIONS OF THE CONCRETE FLOOR FINISH COMPOSITE MINIMUM LOCAL ⌀ 14 855 655 1280 985
ANCHORS, BY GPR, X-RAY OR OTHER NON-DESTRUCTIVE MEANS.
4. PROVIDE FULL FACE SHELL MORTAR COVERAGE ON MASONRY UNIT HORIZONTAL AND
OVERALL
FF FL FF FL
⌀ 16 975 750 1460 1125
C VERTICAL (BED AND HEAD) FACE SHELL JOINTS. 14. ADHESIVE ANCHORS MUST BE DRILLED AT LEAST 21 DAYS AFTER FRESHLY PLACED ⌀ 18 1095 845 1640 1265
⌀ 20
CONCRETE. MECHANICAL ANCHORS MUST BE DRILLED AT LEAST 7 DAYS AFTER THICK-SET / SEALED CONCRETE 20 15 17 15
5. LAY MASONRY UNITS IN RUNNING BOND, UNLESS OTHERWISE NOTED, WITH UNITS FRESHLY PLACED CONCRETE. AT MECH. AND UTILITY AREAS
1505 1155 2320 1785
DESIGNED TO ALIGN WITH WEBS IN EACH COURSE. ⌀ 25 1880 1445 2900 2230
15. PROVIDE TO THE CONTRACTING OFFICER DOCUMENTED CONFIRMATION THAT THE
6. GROUT SOLID CELLS WITH DEFORMED REINFORCING BARS, AND GROUT SOLID CELLS IN CONTRACTOR'S PERSONNEL WHO ARE INSTALLING ANCHORS ARE TRAINED PRIOR TO
CARPET / RESILIENT
FLOORING / RUBBER TILES
25 20 24 17
⌀ 32 2400 1850 3710 2855
BELOW GRADE CONSTRUCTION WHERE MASONRY IS IN CONTACT WITH SOIL. CELLS THE COMMENCEMENT OF INSTALLING ANCHORS.
WITH DEFORMED REINFORCING BARS MUST BE CLEAR OF JOINT MORTAR DROPPINGS, SEALED CONCRETE 35 25 35 24 CLASS B LAP SPLICE LENGTH
PRIOR TO GROUTING.
3. CONSTRUCT ELEVATED CONCRETE FLOOR SLABS IN ACCORDANCE WITH ONE OF THE FOR STRAIGHT DEFORMED BARS IN TENSION
7. PLACE GROUT BY THE LOW-LIFT METHOD. MAXIMUM GROUT POUR MUST BE 1200 mm. METHODS RECOMMENDED IN ACI 302.1R-15, TABLE 10.15.3b - "SUSPENDED SLAB 35 MPa NORMAL-WEIGHT CONCRETE

STRUCTURAL GENERAL NOTES - SHEET 2 OF 3


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
EACH LIFT OF GROUT MUST BE KEYED INTO THE PREVIOUS COURSES OF MASONRY STANDARD HOOK GEOMETRY FOR DEVELOPMENT FLATNESS/LEVELNESS CONSTRUCTION GUIDE" FOR THE FOLLOWING SPECIFIED
BELOW A MINIMUM OF 75 mm. REQUIREMENTS: GALVANIZED ASTM A615 GRADE 420 STEEL
OF DEFORMED BARS IN TENSION
CASE 1A/1B2 CASE 22
DEFORMED

THAAD STANDARD FACILITIES


8. JOINT REINFORCEMENT WIRE SIZES MUST CONFORM TO THE FOLLOWING, UNLESS FLOOR FINISH COMPOSITE MINIMUM LOCAL
TOP2 TOP2

VARIOUS LOCATIONS, KSA


OTHERWISE NOTED: TYPE OF MINIMUM INSIDE STRAIGHT DEVELOPMENT OVERALL BAR SIZE ALL OTHER ALL OTHER
BAR SIZE

STANDARD DETAILS
A. SIDE RODS W1.7 (9 GAGE) STANDARD BEND DIAMETER EXTENSION LENGTH FF FL5 FF FL5 Lst Lst Lst Lst
B. CROSS RODS W1.7 (9 GAGE)
HOOK db (mm) (mm) ℓext (mm) ℓdh(mm) THICK-SET / SEALED CONCRETE 20 15 17 15 (mm ) (mm) (mm) (mm)

SA-480530
B
9. JOINT REINFORCEMENT MUST BE COATED PER THE FOLLOWING;
⌀ 10 THROUGH ⌀ 25 6db AT MECH. AND UTILITY AREAS ⌀ 10 575 445 860 665
A. EXTERIOR WALLS ASTM A153, HOT-DIP 90° HOOK 12db
GALVANIZED, CLASS B-2 ⌀ 32 8db GREATER OF CARPET / RESILIENT 25 20 24 15 ⌀ 12 690 530 1030 795
B. INTERIOR WALLS ASTM A641, MILL GALVANIZED
⌀ 10 THROUGH ⌀ 25 6db GREATER OF 8db AND 150 mm FLOORING / RUBBER TILES ⌀ 14 805 620 1200 925
C. INTERIOR WALLS EXPOSED TO HIGH HUMIDITY ASTM A153, HOT DIP 180° HOOK
GALVANIZED, CLASS B-2 ⌀ 32 8db 4db AND 65 mm
SEALED CONCRETE 35 20 35 15 ⌀ 16 920 705 1375 1060
4. FLOOR LEVELNESS CRITERIA DOES NOT APPLY TO UNSHORED SLABS-ON-DECK.
⌀ 18 1030 795 1545 1190
10. FOR SINGLE-WYTHE WALLS, PROVIDE LADDER TYPE JOINT REINFORCEMENT WITH STANDARD HOOK GEOMETRY ⌀ 20 1415 1090 2185 1680
SINGLE PAIR OF SIDE RODS. FOR MULTI-WYTHE WALLS, PROVIDE LADDER TYPE JOINT
FOR STIRRUPS, TIES, AND HOOPS
REINFORCEMENT WITH ADJUSTABLE (TWO-PIECE) DESIGN, WITH SEPARATE DOUBLE- 5. COMPLIANCE WITH THE SPECIFIED COMPOSITE OVERALL VALUES MUST BE
DETERMINED IN ACCORDANCE WITH ASTM E1155. COMPLIANCE TESTING AND
⌀ 25 1770 1360 2730 2100
EYE BUTT WELDED TO SIDE RODS AT 400 mm ON CENTER; DOUBLE HOOK TIES THAT
ENGAGE EYES WELDED TO REINFORCEMENT AND RESIST MOVEMENT PERPENDICULAR TYPE OF MINIMUM INSIDE STRAIGHT DEVELOPMENT IDENTIFICATION OF DEFECTIVE AREAS SHOULD BE COMPLETED WITHIN 24 HOURS OF ⌀ 32 2260 1740 3495 2690
TO WALL. HOOK TIE LENGTH MUST BE SUFFICIENT TO EXTEND 12 mm MINIMUM INTO BAR SIZE CONCRETE PLACEMENT.
OUTER FACE SHELL FOR HOLLOW UNITS AND 40 mm MINIMUM INTO SOLID UNITS, BUT
STANDARD BEND DIAMETER EXTENSION LENGTH
WITH A MINIMUM OF 16 mm COVER AT OUTSIDE FACE. HOOK db (mm) (mm) ℓext (mm) ℓdh(mm) 6. REFER TO SPECIFICATION 03 30 00 FOR ADDITIONAL REQUIREMENTS.
GREATER OF
⌀ 10 THROUGH ⌀ 16
2/11/2022 2:28:09 PM

11. LAP JOINT REINFORCEMENT BY AT MINIMUM OF 150 mm. 4db 6db AND 75 mm
90° HOOK
A 12. PROVIDE PRE-FORMED T AND L SHAPED JOINT REINFORCING AT WALL INTERSECTIONS.
⌀ 18 THROUGH ⌀ 25 6db 12db SHEET ID
GREATER OF
13. WHERE STRAP ANCHORS ARE REQUIRED BY DRAWINGS OR SPECIFICATIONS, LOCATE
135° HOOK ⌀ 10 THROUGH ⌀ 16 4db GREATER OF
8db AND 150 mm
STRAPS AT DIFFERENT BEDS THAN THOSE RECEIVING JOINT REINFORCEMENT.
⌀ 18 THROUGH ⌀ 25 6db 6db AND 75 mm $
⌀ 10 THROUGH ⌀ 16 4db GREATER OF
14. PROVIDE CONTROL JOINTS IN CMU WALLS AT EVERY 6000mm ON CENTER, AT
PILASTERS, WALL HEIGHT CHANGE, ADJACENT TO LINTELS, OR AS NOTED ON THE
DRAWINGS.
180° HOOK
⌀ 18 THROUGH ⌀ 25 6db 4db AND 65 mm UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS002
1 2 3 4 5 6 7 8 9 10
JST JOIST
STRUCTURAL ABBREVIATIONS K, KIP(S) THOUSAND POUNDS
STRUCTURAL LEGEND
# NUMBER KIP-FT THOUSAND POUND-FEET (MOMENT / TORQUE) TOS = +XX = TOP OF STEEL ELEVATION MEASURED FROM REFERENCED
& AND KSI THOUSAND POUNDS PER SQUARE INCH PLAN ELEVATION = 0
= EQUAL, EQUALS US Army Corps of
@ AT L LENGTH / ANGLE TOC = +XX = TOP OF CONCRETE ELEVATION MEASURED FROM REFERENCED Engineers ®
A/C AIR CONDITIONING LAST LOWEST ANTICIPATED SERVICE TEMPERATURE PLAN ELEVATION = 0 Middle East District
AB ANCHOR BOLT LB POUND
G ACI AMERICAN CONCRETE INSTITUTE LB-FT POUND-FEET (MOMENT / TORQUE) BOD = +XX = BOTTOM OF DECK ELEVATION MEASURED FROM REFERENCED
ACIP AUGER CAST-IN-PLACE PILE / AUGER CAST GROUT PILE Ld TENSION DEVELOPMENT LENGTH FOR STRAIGHT BARS PLAN ELEVATION = 0
ADDL ADDITIONAL Ldc COMPRESSION DEVELOPMENT LENGTH FOR STRAIGHT BARS

DATE
ADJ ADJACENT Ldh TENSION DEVELOPMENT LENGTH FOR STANDARD HOOKS
AFF ABOVE FINISHED FLOOR LFRS LATERAL FORCE RESISTING SYSTEM
AH, AHU AIR HANDLING UNIT LG LONG = FLOOR / ROOF OPENING
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION LL LIVE LOAD
ALT ALTERNATE LLH LONG LEG HORIZONTAL
APA AMERICAN PLYWOOD ASSOCIATION LLV LONG LEG VERTICAL
LOC LOCATE / LOCATION TOSL XX = TOP OF SLAB ELEVATION MEASURED FROM REFERENCED
APPROX APPROXIMATELY
ARCH ARCHITECTURAL LONG LONGITUDINAL PLAN ELEVATION = 0
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS LP LOW POINT
AT/FP ANTI-TERRORISM / FORCE PROTECTION Lst TENSION SPLICE LENGTH
AWS AMERICAN WELDING SOCIETY Lsc COMPRESSION SPLICE LENGTH = CHANGE IN ELEVATION - REFER TO CIVIL DRAWINGS
LW LIGHT-WEIGHT
BET BETWEEN
BLDG BUILDING MAS MASONRY = SLOPE DOWN
BLW BELOW MAX MAXIMUM

DESCRIPTION
BM BEAM MB MACHINE BOLT
F BN BOUNDARY NAIL MBR MEMBER = SLOPE UP
BOC BOTTOM OF CONCRETE MECH MECHANICAL
BOD BOTTOM OF DECK MED MEDIUM
BOF BOTTOM OF FOOTING MEZZ MEZZANINE X = COLUMN GRID MARK
BOPC BOTTOM OF PILE CAP MF MOMENT FRAME
BOT / B BOTTOM MFG MANUFACTURING
BRG BEARING MFR MANUFACTURER XX = DECK SPAN
MIN MINIMUM
C CHANNEL MO MASONRY OPENING
CANT CANTILEVER / CANTILEVERED MOD MODIFY / MODIFIED SECTION / DETAIL NUMBER / LETTER
CE CARBON EQUIVALENT X
CENT CENTERED N NORTH = SECTION / DETAIL MARK
N/A NOT APPLICABLE XX
CFMF COLD-FORMED METAL FRAMING
CIP CAST-IN-PLACE NF NEAR FACE SHEET NUMBER WHERE SECTION / DETAIL MARK IS DRAWN
CJ CONTROL JOINT NOM NOMINAL
CTJ CONSTRUCTION JOINT NS NEAR SIDE
= INDICATES COLUMN OR POST STARTING ON THIS FLOOR AND EXTENDING DOWN ONLY

MARK
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE OC ON CENTER
CLR CLEAR OD OUTSIDE DIAMETER
E CMU CONCRETE MASONRY UNIT / CONCRETE UNIT MASONRY OH OPPOSITE HAND / OVERHEAD
COL COLUMN OWSJ OPEN WEB STEEL JOIST = INDICATES COLUMN OR POST STARTING ON THIS FLOOR AND EXTENDING UP ONLY
CONC CONCRETE

PLOT SCALE: PLOT DATE:


COND CONDITION P/C PIN CONNECTED

2:28:10 PM
PAR PARALLEL = INDICATES TWO COLUMNS OR POSTS STARTING ON THIS FLOOR AND EXTENDING UP

2/11/2022
CONN CONNECT / CONNECTION
PCC PRECAST CONCRETE

SOLICITATION NO.:
AND DOWN AT THE SAME LOCATION

SA-480530-1$-SS003GN.dwg
CONST CONSTRUCTION
PCF POUNDS PER CUBIC FOOT

CONTRACT NO.:
CONT CONTINUOUS, CONTINUED
PCRS PROGRESSIVE COLLAPSE RESISTING SYSTEM

ISSUE DATE:
CONTR CONTRACTOR
COORD COORDINATE PEN PENETRATION = MOMENT CONNECTION
PEMB PRE-ENGINEEREED METAL BUILDING

1:1
COR CORNER
CWB CAPILLARY WATER BARRIER PFJ PERIMETER FELT JOINT
PL PLATE = CANTILEVER MOMENT CONNECTION
D DEEP / DEPTH PLYWD PLYWOOD
DEG DEGREE PNL PANEL

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


DEG-F DEGREES FAHRENHEIT PSF POUNDS PER SQUARE FOOT = FULLY RESTRAINED MOMENT SPLICE
PSI POUNDS PER SQUARE INCH

FILE NO.:
DEM DEMOLISH / DEMOLITION
DEP DEPRESSED PT PRESSURE TREATED / POINT / PRETENSIONED

SUBMITTED BY:
DET DETAIL PVMT PAVEMENT

A. ALHMOOD
= HORIZONTAL BRIDGING

DESIGN BY:

DRAWN BY:
DIA DIAMETER

A. HANKS
D

CKD BY:
DIAG DIAGONAL

ANSI D
REINF REINFORCING / REINFORCED

SIZE:
DL DEAD LOAD = CROSS BRIDGING
DO DITTO REQ REQUIRED
DOR DESIGNER RET RETURN / RETAINING
DT DRAG TRUSS REV REVISION / REVISED

TRANSATLANTIC MIDDLE EAST DISTRICT


RF ROOF SLAB-ON-GROUND ISOLATION JOINT (IJ)
DWG(S) DRAWING(S)
RFT RAFTER

US ARMY CORPS OF ENGINEERS


DWL DOWEL

201 PRINCE FREDERICK DRIVE,


RPM REVOLUTIONS PER MINUTE SLAB-ON-GROUND CONTRACTION/CONSTRUCTION JOINT (CJ)
RS ROUGH SAWN

WINCHESTER, VA 22602
E EAST
EA EACH RT ROOF TRUSS
EF EACH FACE
S SECTION MODULUS / SOUTH DROP PANEL BOTTOM REINFORCEMENT
ELEC ELECTRICAL
ELEV/EL ELEVATION SC SLIP CRITICAL
EMBED EMBEDMENT, EMBEDDED SCBRW SEGMENTAL BLOCK RETAINING WALL
EN EDGE NAIL SCHED SCHEDULE FX
EQN EQUATION SDI STEEL DECK INSTITUTE EL. -YYYY
EQUIP EQUIPMENT SECT SECTION
ES EACH SIDE SEIS SEISMIC FX = FOOTING MARK
SEOR STRUCTURAL ENGINEER CX
EW EACH WAY EL. -YYYY TOP OF FOOTING ELEVATION
C EXIST EXISTING SEP
SFRS
SEPARATION
SEISMIC FORCE RESISTING SYSTEM
EXT EXTERNAL / EXTERIOR CX = COLUMN MARK
SHT SHEET
f'c SPECIFIED MINIMUM COMPRESSIVE STRESS SIM SIMILAR PX PX = PIER MARK (WHERE APPLICABLE)
FF FAR FACE SJI STEEL JOIST INSTITUTE
FFE FINISH FLOOR ELEVATION SOG SLAB-ON-GROUND
FG FINISH GRADE SPEC(S) SPECIFICATION(S)
FJ FLOOR JOIST SPRT SUPPORT PLAN VIEW
FMG FRAMING SQ SQUARE
FN FIELD NAIL SS STAINLESS STEEL
BEAM SIZE NUMBER OF SHEAR STUDS
STRUCT STRUCTURAL / STRUCTURE

STRUCTURAL GENERAL NOTES - SHEET 3 OF 3


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
FND FOUNDATION AISC SHAPE ADDITIONAL DESCRIPTION ON BEAM POSITION
FOC FACE OF CONCRETE SUSP SUSPENDED
FOM FACE OF MASONRY SYM SYMMETRICAL W150x18 XX (X) [X]
FOS FACE OF STUD = STEEL BEAM/GIRDER TAG NOTATION

THAAD STANDARD FACILITIES


T TOP [+/- X]

VARIOUS LOCATIONS, KSA


FS FAR SIDE
FT, ' FOOT T&G TONGUE AND GROOVE

STANDARD DETAILS
FTG FOOTING TGB TOP OF GRADE BEAM DEVIATION FROM PLAN TOP
Fy SPECIFIED MINIMUM YIELD STRESS THK THICK / THICKNESS OF STEEL ELEVATION
TL TOTAL LOAD BEAM CAMBER

SA-480530
TN TOE NAIL
B GA GAGE
TOB TOP OF BEAM
BEAM POSITION LEGEND:
[S] INDICATES MEMBER IS SLOPED, REFER TO SECTIONS AND DETAILS.
GLB GLUE LAMINATED BEAM
GT GIRDER TRUSS TOC TOP OF CONCRETE
GUSS GUSSET TOF TOP OF FOOTING [LO]: XX mm
GW GALVANIZED STEEL WELDED GRATING TOS TOP OF STEEL
GYP BD GYPSUM BOARD TOSL TOP OF SLAB [HI]: XX mm
TOW TOP OF WALL
HD HOLD DOWN TYP TYPICAL
HDR HEADER
HGR HANGER UFC UNITED FACILITIES CRITERIA
HK HOOK UNO UNLESS NOTED OTHERWISE, UNLESS OTHERWISE NOTED
HORIZ HORIZONTAL UON UNLESS OTHERWISE NOTED
HP HIGH POINT
HSS HOLLOW STRUCTURAL SECTION VB VAPOR BARRIER
HT HEIGHT VERT VERTICAL
HVAC HEATING / VENTILATION / AIR CONDITIONING
2/11/2022 2:28:10 PM

W WIDTH / WEST / WIDE FLANGE


I SECOND AREA MOMENT OF INERTIA w/ WITH
A IBC INTERNATIONAL BUILDING CODE WF WIDE FLANGE
SHEET ID
ICF INSULATED CONCRETE FORM WFRS WIND FORCE RESISTING SYSTEM
WPT WORKING POINT
ID
IJ
INSIDE DIAMETER
ISOLATION JOINT WT WEIGHT / TEE SECTION $
IN, " INCH WWF WELDED WIRE FABRIC
INCL
INFO
INCLUDE
INFORMATION
WWR WELDED WIRE REINFORCEMENT
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS003
INS INSULATED / INSULATION x BY / TIMES
1 2 3 4 5 6 7 8 9 10

FIRST PLACEMENT SECOND PLACEMENT


US Army Corps of
Engineers ®
CORNER BAR SIZE TO MATCH U-BAR SIZE TO MATCH CENTERLINE JOINT
LARGER OF HORIZONTAL LAP SPLICE (TYP) Middle East District
LARGER OF HORIZONTAL
G WALL REINFORCEMENT (TYP) WALL REINFORCEMENT (TYP) CLEAN AND ROUGHEN SURFACE TO 6mm
90-DEGREE BEND (TYP) 38 AMPLITUDE AND APPLY EPOXY BONDING AGENT
90-DEGREE BEND (TYP) PRIOR TO SECOND CONCRETE PLACEMENT (TYP)

DATE
EQ EQ EQ
THICKNESS
T

(T)
S (TYP) S (TYP)
VERTICAL WALL
REINFORCEMENT (TYP) CONC WALL HORIZ REINF CONTINUOUS THROUGH JOINT
VERTICAL WALL

LAP SPLICE
REINF (TYP) (PROVIDE MATCHING DOWELS WITH FULL

LAP SPLICE
S/2 MAX (TYP) S/2 MAX (TYP) REINFORCEMENT (TYP) LAP SPLICES EACH SIDE OR MECHANICAL
NOTE: COUPLERS)
REINF DETAILED TO

DESCRIPTION
F 0 (TYP) DEVELOP FULL MOMENT TYPICAL VERTICAL CONSTRUCTION JOINT
TRANSFER CAPACITY 0 (TYP)

HORIZONTAL WALL HORIZONTAL WALL


REINFORCEMENT (TYP) CENTERLINE JOINT CENTERLINE JOINT
REINFORCEMENT (TYP)

T/6 (TYP)
150 150
75 75
TYP TYP 13mm PREMOLDED JOINT TYP TYP
SEALANT
T T FILLER

THICKNESS

THICKNESS
WALLS WITH TWO LAYERS OF REINFORCEMENT WALLS WITH TWO LAYERS OF REINFORCEMENT (ALTERNATE) 13

(T)

(T)
T/2

T/2
CORNER BAR SIZE TO MATCH

MARK
LARGER OF HORIZONTAL
WALL REINFORCEMENT 300mm LONG GREASED DOWEL 300mm LONG GREASED DOWEL
LAP SPLICE (TYP) CONC WALL CONC WALL
SIZE AND SPACING TO MATCH SIZE AND SPACING TO MATCH HORIZ REINF
E (ALTERNATE DIRECTION) REINF (TYP) HORIZ REINF REINF (TYP) 20
90-DEGREE BEND

PLOT SCALE: PLOT DATE:


STOP HORIZ REINF AT JOINT STOP HORIZ REINF AT JOINT

2:28:11 PM
2/11/2022
TYPICAL VERTICAL EXPANSION JOINT TYPICAL VERTICAL CONTRACTION JOINT

SOLICITATION NO.:

SA-480530-1$-SS501DT.dwg
T

CONTRACT NO.:
ISSUE DATE:
NOTES:
1. JOINTS NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS MUST
S (TYP)

1:1
BE APPROVED BY THE STRUCTURAL ENGINEER OF RECORD.
VERTICAL WALL
LAP SPLICE

S/2 MAX (TYP) REINFORCEMENT (TYP) 2. REFER TO PLAN FOR WALL REINF SIZE AND SPACING.

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN

FILE NO.:
TYPICAL CONCRETE WALL VERTICAL JOINT DETAILS

SUBMITTED BY:
A. ALHMOOD
D7

DESIGN BY:

DRAWN BY:

A. HANKS
D 0 (TYP) 1 : 12

CKD BY:

ANSI D
SIZE:
HORIZONTAL WALL

TRANSATLANTIC MIDDLE EAST DISTRICT


REINFORCEMENT (TYP)

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
T

WALLS WITH SINGLE LAYER OF REINFORCEMENT

LAP SPLICE COVER + 50 LAP SPLICE COVER + 50 LAP SPLICE


C CORNER BAR SIZE TO MATCH CORNER BAR SIZE TO MATCH
LARGER OF HORIZONTAL LARGER OF HORIZONTAL U-BAR SIZE TO MATCH
WALL REINFORCEMENT WALL REINFORCEMENT (TYP) LARGER OF HORIZONTAL
WALL REINFORCEMENT (TYP)
90-DEGREE BEND 90-DEGREE BEND 90-DEGREE BEND (TYP)
T

STANDARD 90-DEGREE

T
HOOK (TYP)
0 (TYP)
S (TYP)

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)

TYPICAL CONCRETE DETAILS - SHEET 1 OF 6


VERTICAL WALL
LAP SPLICE

S/2 MAX (TYP) REINFORCEMENT (TYP) S (TYP) S (TYP)

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
VERTICAL WALL VERTICAL WALL
LAP SPLICE

LAP SPLICE
S/2 MAX (TYP) REINFORCEMENT (TYP) S/2 MAX (TYP) REINFORCEMENT (TYP)

STANDARD DETAILS
SA-480530
B 0 (TYP) 0 (TYP) 0 (TYP)

HORIZONTAL WALL HORIZONTAL WALL HORIZONTAL WALL


REINFORCEMENT (TYP) REINFORCEMENT (TYP) REINFORCEMENT (TYP)

T T T

WALLS WITH SINGLE LAYER OF REINFORCEMENT WALLS WITH TWO LAYERS OF REINFORCEMENT WALLS WITH TWO LAYERS OF REINFORCEMENT (ALTERNATE)
2/11/2022 2:28:11 PM

A SHEET ID
TYPICAL CONCRETE WALL AND CURB CORNER REINFORCING DETAILS
A1 1 : 12 $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS501
1 2 3 4 5 6 7 8 9 10

(1) D16 CONT @ TOP OF WALL SEE WALL ELEVATIONS FOR


TYPICAL REINFORCEMENT

US Army Corps of
Engineers ®
Middle East District

50.00 CLR (TYP)


G
NOTE 5

DATE
NOTE 3
FINISHED FLOOR
SEE PLAN

TENSION

TENSION

LAP
LAP

NOTE 1

DESCRIPTION
F VERIFY ROUGH
OPENING
AND LOCATIONS NOTE 2
WITH
ARCHITECTURAL
DRAWING

TENSION

LAP

MARK
TENSION

LAP

PLOT SCALE: PLOT DATE:


FINISHED FLOOR

2:28:12 PM
SEE PLAN

2/11/2022
SOLICITATION NO.:

SA-480530-1$-SS502DT.dwg
CONTRACT NO.:
TENSION

ISSUE DATE:
NOTE 6
NOTE 4 LAP

1:1
K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN

FILE NO.:
SUBMITTED BY:
A. ALHMOOD
DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
SIZE:
(2) D16 @ TOP AND BOTTOM OF OPENING
(TYP) LAP WITH TYPICAL HORIZONTAL
REINFORCING

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
(2) D16 UNO @ JAMB (TYP)

C DOWELS TO MATCH WALL


REINFORCING SIZE AND
SPACING WITH 90 DEG HOOK
BOTT

TO FOUNDATION
SEE PLAN

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)

TYPICAL CONCRETE DETAILS - SHEET 2 OF 6


THAAD STANDARD FACILITIES
VARIOUS LOCATIONS, KSA

STANDARD DETAILS
SA-480530
FOUNDATION SYSTEM SEE STEP WALL WITH
B PLAN STEPPED FOOTING OR
GRADE BEAM

NOTES:
1. OPENINGS FOR PIPES AND MISCELLANEOUS OPENINGS LESS THAN 200mm MAY BE MADE WITHOUT MODIFYING REINFORCEMENT. CORES MUST BE
OUTSIDE OF SPECIAL REINFORCEMENT AROUND OPENINGS.
2. PROVIDE (2) D16 DIAGONAL BARS AT CORNERS OF WALL AND OPENINGS CAN'T EXTEND FOR TENSION LAP LENGTH PROVIDE 90 DEG HOOK.
3. WHERE WALL DOES NOT CONTINUE INTO WALL ABOVE PROVIDE 90 DEG HOOKED BAR WITH SIZE AND SPACING TO MATCH TYPICAL WALL VERTICAL
REINFORCING. CENTER HORIZONTAL LEG OF DOWEL IN SLAB ABOVE, TURNED PERPENDICULAR TO THE WALL WHEN POSSIBLE.
4. WHERE BOTTOM OF WALL OCCURS AT AN ELEVATED SLAB PROVIDE DOWELS TO WALL VERTICAL REINFORCING PER CUT DETAILS, MINIMUM MATCH
WALL VERTICAL REINFORCING AND SPACING. PLACE HORIZONTAL LEG AT BOTTOM OF SLAB, TURNED PERPENDICULAR TO WALL WHEN POSSIBLE.
5. WHERE TOP OF WALL OCCURS AT AN ELEVATED SLAB PROVIDE DOWELS TO WALL VERTICAL REINFORCING PER CUT DETAILS, MINIMUM MATCH
2/11/2022 2:28:12 PM

WALL VERTICAL REINFORCING AND SPACING. PLACE HORIZONTAL LEG AT TOP OF SLAB, TURNED PERPENDICULAR TO WALL WHEN POSSIBLE.
A 6. PROVIDE ADDITIONAL DOWELS FROM SLAB TO WALL BELOW WHERE INDICATED.
SHEET ID
TYPICAL CONCRETE WALL REINFORCING $
DIAGRAM SS502
A1 NTS
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

25 CLR TOP AT PARKING/


PROVIDE 180º HOOKS AT ALL US Army Corps of
L'n SUPPORT Ln (CLEAR SPAN) SUPPORT

20 CLR TOP, UNO

OUTSIDE SLABS
DISCONTINUOUS ENDS Engineers ®

TYPICAL CONTINUOUS TOP BAR Middle East District


G SPLICE LOCATION C OF SPLICE
L SLAB EDGE
GREATER OF L'n/3 OR Ln/3 GREATER OF L'n/3 OR Ln/3 Ln/2

DATE
EXTEND ALL CONTINUOUS
CONTINUOUS REINFORCING TOP ADDITIONAL TOP REINFORCING AT CANTILEVER
AND BOTTOM EACH WAY REINFORCING

50 CLR
20 CLR BOTTOM HOOK BOTTOM BARS AT EXTERIOR
(2) MIN CONTINUOUS BOTTOM (TYP) SUPPORT
ADDITIONAL BOTTOM
BARS THROUGH SUPPORT CORE, REINFORCING

DESCRIPTION
50 CLR
EACH WAY
F

CONTINUOUS BOTTOM BAR SPLICE PERMITED IN THIS REGION CANTILEVER

NOTES:
1. SPLICES MUST BE TENSION SPLICES (TYPICAL) PER SCHEDULE.
2. ADDITIONAL TOP BARS MUST BE PLACED EQUALLY ABOUT SUPPORT IN THE TRANSVERSE DIRECTION AND SPACED AT THE SAME SPACING AS CONTINUOUS
REINFORCING TO ACHEVE A SPACING OF 1/2 THAT OF THE CONTINUOUS BARS.
3. ADDITIONAL BOTTOM BARS MUST BE SPACED EQUALLY ABOUT SPAN END SUPPORTS IN THE TRANSVERSE DIRECTION AND SPACED AT THE SAME SPACING AS
CONTINUOUS REINFORCING TO ACHEVE A SPACING OF 1/2 THAT OF THE CONTINUOUS BARS.

MARK
4. BAR PLACEMENT ORDER: BOTTOM TRUE NORTH/SOUTH, BOTTOM TRUE EAST/WEST, CENTER BARS NORTH/SOUTH, CENTER BARS EAST/WEST, TOP TRUE
EAST/WEST, TOP TRUE NORTH/SOUTH.
5. REFER TO PLANS FOR CONTINUOUS REINFORCING (TOP AND BOTTOM) AND ADDITIONAL REINFORCING (TOP AND BOTTOM).
E 6. SHOP DRAWINGS FOR SLAB REINFORCING MUST CLEARLY INDICATE BAR SIZE, SPACING, SPLICE POINT, LENGTHS, CLEARANCES, HOOKS, BAR SUPPORTS, ETC
REQUIRED FOR FIELD INSTALLATION OF REINFORCING. PROVIDE SEPARATE SHOP DRAWINGS FOR BOTTOM AND TOP SLAB REINFORCING.
7. COORIDINATE CLOSELY SLAB REINFORCING PLACED LOCAL TO STUD RAILS, WHERE CONFLICTS OCCUR, OFFSET SLAB REINFORCING TO GET THRU STUD

PLOT SCALE: PLOT DATE:


RAILS.

2:28:13 PM
2/11/2022
SOLICITATION NO.:

SA-480530-1$-SS503DT.dwg
CONTRACT NO.:
ISSUE DATE:

1:1
TYPICAL TWO WAY FRAMED SLAB
ELEVATION
D1

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


NTS

FILE NO.:
CANTILEVER

SUBMITTED BY:
BUILDING LINE AT CANTILEVER ZONES, FOR SIZE & REINF OF COLUMN AND BUILDING LINE

A. ALHMOOD
DESIGN BY:

DRAWN BY:
PROVIDE 90º HOOK AT TOP MIDDLE STRIP BARS, SEE FRAMING

A. HANKS
D

CKD BY:
BARS PLANS

ANSI D
SIZE:
PROVIDE HOOKS IN BOTTOM
CORNER BARS FOR A DISTANCE
Ln/5 IN BOTH DIRECTIONS BARS IN THE CORNER MUST
EXTEND A MINIMUM OF Ln/5

TRANSATLANTIC MIDDLE EAST DISTRICT


CS

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


CS
CS CS
EDGE OF SLAB EDGE OF SLAB

WINCHESTER, VA 22602
MS
CS

CS
FOR MIN LENGTH OF TOP BARS SEE

MS
MS DETAIL E1 THIS SHEET
MS
CONTINOUS BOTTOM BAR ADD'L BOTTOM BARS
TENSION SPLICES PERMITTED SHOWN ON FRAMING

CS
IN THIS REGION (2xLnxWIDTH OF PLAN STRESS LINE (TYP) MS STRESS LINE (TYP)

FRAMING
COLUMN)

PLAN
SEE
CS

MS
SUPPORT (TYP)
C CS BARS

UNO
EQ
HOOK 90º (2) MIN BOTTOM BARS
WITHIN EXTENT OF COLUMN ZONE CONTINUOUS
(TYP) TOP BAR

UNO
EQ

CS
PROVIDE 90º HOOK AT 50% OF

CS
CS MS CS MS CS MS
CS MS MIDDLE STRIP TOP BARS

MS

CS
MS
PROVIDE 90º HOOK AT COLUMN

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)

TYPICAL CONCRETE DETAILS - SHEET 3 OF 6


CS

CS
STRIP TOP BARS
CS

THAAD STANDARD FACILITIES


(2) MIN CONT BOTTOM BARS

VARIOUS LOCATIONS, KSA


THROUGH COLUMN ZONE EACH

STANDARD DETAILS
WAY (TYP)

SA-480530
MS
B COLUMN (TYP)

FOR SIZE AND SPACING OF CONTINUOUS 50% OF BOTTOM MIDDLE STRIP BARS MUST BE SPLICED 150mm
FOR MIN LENGTH OF TOP BARS SEE
BOTTOM AT REINF SEE PLAN NOTES ON (MIN). BALANCE OF BARS WAY STOP AT 0.15LN OF OPPOSITE SIDE
DETAIL E1 THIS SHEET
FRAMING PLAN OF STRESS LINE

BOTTOM BARS (PLAN VIEW) TOP BARS (PLAN VIEW)


NOTES:
NOTES:
1. FOR BALANCE OF NOTES AND INFORMATION SEE DETAIL A5 THIS SHEET. 1. FOR BALANCE OF NOTES AND INFORMATION SEE DETAIL A1 THIS SHEET.
2. CS = COLUMN STRIP REINFORCING. 2. CS = COLUMN STRIP REINFORCING.
MS = MIDDLE STRIP REINFORCING. MS = MIDDLE STRIP REINFORCING.
2/11/2022 2:28:13 PM

A SHEET ID
TYPICAL FLAT PLATE REINFORCING PLAN TYPICAL FLAT PLATE REINFORCING PLAN
$
DETAIL FOR BOTTOM BARS DETAIL FOR TOP BARS
A1 NTS A5 NTS UNLESS OTHERWISE NOTED, LINEAR SS503
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®

EXTERIOR WALL INTERIOR WALL Middle East District


G OR BEAM OR BEAM

DATE
SPAN SPAN

SPAN / 2 SPAN / 2 SPAN / 2 SPAN / 2


ACI
STD END TOP BARS TOP BAR "T" BARS TOP BAR
HOOK SEE WALL SECTION LAP SPLICE LAP SPLICE DIRECTION OF
SLAB SPAN

DESCRIPTION
F 600 600 600
TEMP REINF "B" BARS BOT BARS "B"
SEE PLANS REINF CONC BEAM SEE PLANS MIN, UNO MIN, UNO MIN, UNO
SEE SCHED FOR SIZE & REINF
(OR CONC WALL)
CONC WALL ADD'L T12@
TYP END SPAN TYP INTERIOR SPAN 300 T, MIN
(OR CONC BEAM)
SEE PLAN
ADD'L REINF
Ø12@300 T,
NOTES:
MIN
1. DETAIL TRANSVERSE BARS SIMILAR TO MAIN SPAN BARS.
2. PLACE SPAN REINFORCING AT MIDSLAB FOR ONE-WAY SLABS
CONTAINING ONE LAYER OF REINFORCING.

ADDITIONAL ONE-WAY SLAB REINFORCING

MARK
E ONE-WAY SLAB REINFORCING DIAGRAM PERPENDICULAR TO MAIN
E1 NTS E6 NTS

PLOT SCALE: PLOT DATE:


2:28:14 PM
2/11/2022
SOLICITATION NO.:

SA-480530-1$-SS504DT.dwg
CONTRACT NO.:
ISSUE DATE:

1:1
K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN

FILE NO.:
VARIES

SUBMITTED BY:
A. ALHMOOD
1400 MAX

DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
SIZE:
CL SUPPORT CL SUPPORT NOTES:
75 1. CONSTRUCTION JOINTS ARE PERMITTED AT ANY POINT 1200

TRANSATLANTIC MIDDLE EAST DISTRICT


ADD REINF AREA= MIN. AWAY FROM OPENINGS AND IN THE MIDDLE THIRD OF
(2) T16X1200 AT MID- 0.3% X BEAM GROSS Ld Ld THE CLEAR SPAN.

US ARMY CORPS OF ENGINEERS


38

201 PRINCE FREDERICK DRIVE,


DEPTH OF SLAB, TYP AREA 2. NO CONSTRUCTION JOINTS ARE PERMITTED IN TRANSFER
GIRDERS WHERE INDICATED ON PLAN.

WINCHESTER, VA 22602
SPAN/5

D/3
3. SUBMIT CONSTRUCTION JOINT LOCATIONS TO OWNER FOR
APPROVAL.
(2) BARS TO MATCH SLAB 4. SPLICE TOP & BOTTOM BARS WITH TENSION LAP SPLICE PER
REINF, SIZE & SPACING GENERAL NOTES ON SS002, UNO.

EDGE OF SLAB
1400 MAX

D
VARIES

1/3 't'
C JOINT
WHERE NO TOP BARS
ARE SHOWN ADD
Ø12X1200 @300
ALLOWED
OPENING SQUARE
RECTANGULAR OR 3L/8 L/4 3L/8

't'
ROUND 0
30 HOOK DOWEL

SPAN/5
@ BAR END L

SECOND POUR FIRST POUR CONSTRUCTION JOINT BOTTOM BARS CONT.

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)

TYPICAL CONCRETE DETAILS - SHEET 4 OF 6


SECOND POUR FIRST POUR

BEAM SLAB

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA

STANDARD DETAILS
(3) BARS TO MATCH SLAB

SA-480530
REINF, SIZE & SPACING
B
TYP CONSTRUCTION JOINT IN ELEVATED
NOTES:
ADD'L REINFORCEMENT AT CORNERS SLAB/BEAM
1. TOP& BOTT. SLAB BARS INTERRUPTED BY THE OPENING MUST BE
REPLACED WITH ADDITIONAL REINF EQUAL TO THAT INTERRUPTED. B4 1 : 16 B6 NTS
PLACE HALF OF THE ADDITIONAL REINF ON EACH SIDE OF OPENING
AND EXTEND IT A DEVELOPMENT LENGTH BEYOND EDGE OF
OPENING.
2. BOXED OUT OPENINGS RECESSED BOXES & PIPE SLEEVE CLUSTERS
MUST BE TREATED AS SLAB OPENINGS.
2/11/2022 2:28:14 PM

A ADD'L REINFORCEMENT AT OPENING


A1 1 : 16
SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS504
1 2 3 4 5 6 7 8 9 10

ONE-HALF REGULAR SPACING


CONCRETE SLAB OR BEAM
(REINFORCEMENT NOT SHOWN FOR CL COL CL

THROUGHOUT LAP
PROVIDE TIES AT
CLARITY)
SPAN L1 US Army Corps of
Engineers ®
L1/2 L1/2 L2/2 Middle East District
G
CL LAP SPLICE

EQ

DATE
SLAB WHERE
SPLICE
EQ

OCCURS
LAP

CONC
'T' BARS TOP BARS TOP BARS
50
150

ACI STD 90°


HOOK
PROVIDE ADDITIONAL
SLOPE 1:6
COLUMN TIE AT TOP OF
MAX
COLUMN
BOT BARS
SEE NOTE 2 ROUNDED CONC @

DESCRIPTION
75
TOP (TYP)
F STIRRUPS 150 BOT BARS SEE 200ø STD PIPE (TYP)
TYP NOTE 3

Ø12@75
TYPICAL TIE SPACING

50 STIRRUP SPACING FILL W/ CONC


TYP PER SCHEDULE BOT
BARS
C4 BASE PL: 350 x 25 x 350

900
COL TIE SETS COL VERT REINF SS505 CONC COLUMN W/ (4) 20ø EPOXY
ONE-HALF REGULAR SPACING

ADHESIVE
ANCHORS REINF CONC
(200 EMBED, MIN) A SLAB-ON-GRADE
THROUGHOUT LAP
PROVIDE TIES AT

NOTES: 5. (X) LOCATED WITH LONGITUDINAL REINF. INDICATES RE: PLAN


LAP SPLICE

T/SLAB
1. WORK THIS REINFORCING DIAGRAM WITH CONCRETE REQUIRED NUMBER OF LAYERS. USE 1 LAYER U.N.O.
TENSION

BEAM SCHEDULE. LAYERS MUST CONTAIN EQUAL NUMBERS OF BARS RE: PLAN
CONCRETE SLAB OR BEAM 2. EXTEND AT LEAST 25% OF BOT STEEL AREA INTO WHERE POSSIBLE. WHERE IT IS NOT POSSIBLE,
(REINFORCEMENT NOT SHOWN FOR SUPPORT W/ STD HOOK (MIN 2 BARS). STAGGER LAYERS OF EVEN AND ODD NUMBER.
CLARITY) 3. EXTEND AT LEAST 25% OF GREATER BOT STEEL AREA 6. FOR 2-PIECE STIRRUP TIES, PLACE 90º HOOK
(1) - ø12 HAIRPIN
THRU SUPPORT INTO ADJACENT SPAN (MIN 2 BARS). AT TOP INSIDE CORNER OF SPANDREL (EDGE) BEAMS.
@ EACH ANCHOR (2) - ADDL ø12 T & B

MARK
SEPARATE STRAIGHT BARS MAY BE PROVIDED IN LIEU ALTERNATE SIDES AT OTHER BEAMS.
GROUP
7. AT INSIDE CORNER COLUMNS, EXTEND BEAM TOP
50

OF EXTENDED BOT BARS. PROVIDE TENSION LAP SPLICE.


4. BARS MUST EXTEND PAST EACH SIDE OF THE SUPPORT BARS INTO SLAB BY DEVELOPMENT LENGTH. NOTES:
E AS INDICATED ON DIAGRAM. 1. RE: ARCH FOR FINISH REQUIREMENTS.
2. HAIRPIN AND ADDITIONAL BARS APPLICABLE

PLOT SCALE: PLOT DATE:


AT EDGE CONDITION WHERE DISTANCE "A"
FROM EDGE OF BASE PLATE TO EDGE OF

2:28:16 PM
TYP CONC BEAM & COL REINFORCING

2/11/2022
CONCRETE IS GREATER THAN 400mm.

SOLICITATION NO.:

SA-480530-1$-SS505DT.dwg
CONTRACT NO.:
DIAGRAM MOUNTED ON SLAB-ON-GRADE

ISSUE DATE:
D4 NTS
75

OFFSET VERTICAL REINFORCING OF LOWER

1:1
Ø12@75

COLUMN VERTICALS AS NEEDED FOR LAP SPLICE


WITH VERTICAL REINFORCING OF COLUMN ABOVE

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


OFFSET TIES FROM FOUNDATION 50 TYP INTERIOR FACILITY BOLLARD DETAIL

FILE NO.:
INSIDE OF COLUMN VERTICALS
SLAB WHERE
OCCURS D8 NTS

SUBMITTED BY:
TOP BARS

A. ALHMOOD
DESIGN BY:

DRAWN BY:
DOWELS TO MATCH SIZE AND

A. HANKS
D QUANTITY OF COLUMN VERTICAL

CKD BY:
SIDE REINF

ANSI D
REINFORCING

SIZE:
'D'
TYPICAL TIE SPACING

TRANSATLANTIC MIDDLE EAST DISTRICT


STIRRUPS
PROVIDE (2) ADDITIONAL TIES

US ARMY CORPS OF ENGINEERS


WITHIN COLUMN REINFORCING

201 PRINCE FREDERICK DRIVE,


TOP BARS
SPLICE
'W'

WINCHESTER, VA 22602
LAP SPLICE
TENSION

NOTE: REFER TO BEAM SCHEDULE FOR REINFORCEMENT.


CONCRETE SLAB OR BEAM
(REINFORCEMENT NOT SHOWN FOR ROUNDED CONC @
CLARITY) SECTION TOP (TYP)
C4 NTS
50

200ø STD PIPE (TYP)


FILL W/ CONC
C SLOPE AWAY FROM
BOLLARD (TYP)

1260
500ø (TYP)
PROVIDE ADDITIONAL SLAB
PROVIDE TIES AROUND FOUNDATION DOWELS, REINFORCEMENT
MATCH COLUMN TIES ABOVE TOP OF FOUNDATION

STEP RE: PLAN


AND AN ADDITIONAL TIE AT TOP & BOTTOM OF
GRADE BEAM. PLACE 90 DEGREE HOOK ON BOTTOM ISOLATION REINF CONC
AT BOTTOM OF BEAM OR PILE CAP JOINT SLAB-ON-GRADE
LAP SPLICE RE: PLAN

75
T/SLAB

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)

TYPICAL CONCRETE DETAILS - SHEET 5 OF 6


TOP BARS RE: PLAN
TOP BARS

75

THAAD STANDARD FACILITIES


CONC

VARIOUS LOCATIONS, KSA


ENCASEMENT

STANDARD DETAILS
Ø10 @ 300 OC
(4) Ø16 VERT T/FTG

SA-480530
1400
RE: PLAN
B
FOOTING
RE: PLAN
STIRRUPS BOT BARS
BASE PL: 300 x20 x 300

75
TYPICAL CONCRETE COLUMN DETAIL NOTES: W/ (4) 20ø ADHESIVE

B1 COL TIE SETS 1. COORDINATE WITH CIVIL FOR BOLLARDS ANCHORS (125

150
NTS NOT IMMEDIATELY ADJACENT TO, OR EMBED, MIN) @ 225
INTERIOR OF, BUILDING STRUCTURES. EW
COL VERT REINF
500ø (TYP) 2. RE: ARCH FOR FINISH REQUIREMENTS.

AT SLAB-ON-GRADE OR PAVEMENT AT FOOTING


2/11/2022 2:28:16 PM

A SHEET ID
TYP STEP IN CONCRETE BEAM TYP EXTERIOR FACILITY BOLLARD DETAIL $
A4 NTS A7 NTS

UNLESS OTHERWISE NOTED, LINEAR


DIMENSIONS ARE IN MILLIMETERS
SS505
1 2 3 4 5 6 7 8 9 10

Ø12@300mm CORING AND CUTTING THROUGH Ø12@300mm Ø12@300mm CORING AND CUTTING THROUGH Ø12@300mm
2 HORIZONTAL REINFORCEMENT IS NOT 2 HORIZONTAL FACE OF EQUIPMENT (TYP) PROVIDE ADHESIVE ANCHORS W/
2 HORIZONTAL REINFORCEMENT IS NOT 2 HORIZONTAL
BARS MINIMUM ALLOWED USE EMBED PLATES BARS MINIMUM EMBED, QTY & DIA AS REQD BY
BARS MINIMUM ALLOWED USE EMBED PLATES BARS MINIMUM
Ø12@300mm OC EW EQUIP MFR
US Army Corps of
HOOK IN PLANE OF CURB (T&B IF THICKNESS > 200mm)
WIDTH WIDTH WIDTH WIDTH Engineers ®
Ø12 DOWELS @ 300mm
150 Ø12@300mm OC EW Middle East District
OC ALL AROUND
Ø12@300mm OC DRILLED (T&B IF THICKNESS > 200mm)
G IN WITH ADHESIVE MIN
CONTRACTOR
ANCHORS 76mm MINIMUM Ø10@150mm Ø12 DOWELS @ 300mm HAS OPTION TO
EMBED OC OC ALL AROUND DRILL AND

DATE
GROUT DOWELS

500mm MAX
ROOF SLAB, AS ALTERNATIVE
KEYWAY OR

HEIGHT
EQ EQ EQ EQ
SEE PLAN

76
INTENTIONALLY Ø12@300mm

MIN
150
ROUGHEN SURFACE OC
SLOPE

125
SLOPE T/ROOF SLAB SLOPE
T/ROOF SLAB
EL VARIES EL VARIES

CLEAN AND ROUGHEN SURFACE TO 6mm


AMPLITUDE PRIOR TO CONC PLACEMENT

DESCRIPTION
F
CURB WIDTH - 76mm MINIMUM TO 180mm MAX CURB WIDTH OVER 180mm CURB WIDTH - 76mm MINIMUM TO 180mm MAX CURB WIDTH OVER 180mm EQUIPMENT PAD ON SLOPED ROOF SLAB
NOTES:
POST-INSTALLED CAST-IN-PLACE 1. COORDINATE EQUIPMENT PAD REQUIREMENTS WITH
MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS.
NOTES: NOTES: 2. FOR TOP OF PAD ELEVATIONS, COORDINATE WITH EQUIPMENT
1. FOR SIZE AND LOCATION SEE ARCHITECTURE, MEP, OR STRUCTURAL DRAWINGS 1. FOR SIZE AND LOCATION SEE ARCHITECTURE, MEP, OR STRUCTURAL DRAWINGS MANUFACTURERS.
2. FOR TOP OF CURB ELEVATIONS, COORDINATE WITH EQUIPMENT MANUFACTURERS. 2. FOR TOP OF CURB ELEVATIONS, COORDINATE WITH EQUIPMENT MANUFACTURERS.
3. ROUGHEN SURFACE OF SLAB TO 6mm AMPLITUDE CLEAN THOROUGHLY AND APPLY 3. SEE ARCH DRAWINGS FOR EMBEDDED PLATES AND BLOCKOUTS REPLACE
BONDING AGENT IMMEDIATELY BEFORE CASTING CURB REINFORCEMENT INTERRUPTED BY BLOCKOUTS.
4. SEE ARCH DRAWINGS FOR EMBEDDED PLATES AND BLOCKOUTS REPLACE 4. AT CONTRACTOR'S OPTION, POST-INSTALLED DOWELS MAY BE USED IN PLACE OF
REINFORCEMENT INTERRUPTED BY BLOCKOUTS. CAST IN PLACE DOWELS.
5. AT CONTRACTOR'S OPTION, CAST IN PLACE DOWELS MAY BE USED IN PLACE OF
POST-INSTALLED.
TYPICAL CONCRETE EQUIPMENT PAD ON SLOPING ROOF SLAB
E7

MARK
1 : 12

E TYP CONC CURB DETAIL ON SLOPING SLAB


E2 NTS

PLOT SCALE: PLOT DATE:


SEE PLAN

2:28:17 PM
2/11/2022
SOLICITATION NO.:

SA-480530-1$-SS506DT.dwg
CONTRACT NO.:
ISSUE DATE:
ADDITIONAL TOP DROP TOP SLAB REINFORCEMENT,
Ø12@150mm
PANEL REINFORCEMENT, SEE PLAN
2 HORIZONTAL LW CONCRETE

1:1
SEE PLAN
BARS MINIMUM CURB
13 mm IJ
200 Ø12@300mm OC DRILLED IN WITH
LW CONCRETE
ADHESIVE ANCHORS 75mm

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


SCREED MAX MINIMUM EMBED

FILE NO.:
T/CURB

SUBMITTED BY:
T/CONC. TPNG

A. ALHMOOD
DESIGN BY:

DRAWN BY:
INTENTIONALLY

PLAN
SEE

A. HANKS
D ROUGHEN SURFACE TO

CKD BY:
BOTTOM SLAB REINFORCEMENT,

ANSI D
5mm AMPLITUDE

SIZE:
SEE PLAN
T/ROOF SLAB
EL VARIES

TRANSATLANTIC MIDDLE EAST DISTRICT


DROP PANEL

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


BOTTOM REINFORCEMENT

WINCHESTER, VA 22602
CONC COLUMN

TYP CONC CURB DETAIL ON FLAT SLAB TYPICAL DROP PANEL DETAIL
C C1 NTS C6 NTS

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)

TYPICAL CONCRETE DETAILS - SHEET 6 OF 6


THAAD STANDARD FACILITIES
VARIOUS LOCATIONS, KSA

STANDARD DETAILS
SA-480530
B
2/11/2022 2:28:17 PM

A SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS506
1 2 3 4 5 6 7 8 9 10

13mm PREMOLDED JOINT FILLER


TOP OF SLAB ELEVATION ISOLATION JOINT (IJ)
REFER TO PLAN
REFER TO PLAN FOR SLAB-ON-
GROUND REINFORCEMENT, SIZE US Army Corps of
AND SPACING. CMU WALL OPENING CMU WALL OPENING Engineers ®

t/3
REFER TO ARCH REFER TO ARCH Middle East District
G Ø20@300mm, 400mm LONG SMOOTH
BAR ONE END MUST BE GREASED.

SEE PLAN
CONTRACTION/CONSTRUCTION JOINT
AT NON-BRG CMU WALL (CJ) STAGGERED BETWEEN REBAR TOP OF SLAB ELEVATION

DATE
t
REFER TO PLAN

TOP OF SLAB ELEVATION


LAP SPLICE (4)Ø16

100
REFER TO PLAN (2)Ø16

SEE PLAN

SEE PLAN
CONTINUOUS VAPOR

t
300

300
BARRIER,

100

100
REFER TO SPECS

BLINDING CONCRETE
LAYER BELOW SOG BLINDING CONCRETE 1 1 BLINDING CONCRETE 1 1
LAYER BELOW SOG LAYER BELOW SOG
3 3 3 3

DESCRIPTION
200 500 200 500
F
AGGREGATE
BOTTOM REINFORCMENT WHERE
APPLICABLE, REFER TO PLANS.
WITH CONTRACTION/CONSTRUCTION JOINT WITHOUT CONTRACTION/CONSTRUCTION JOINT
NOTE: THICKENED SLAB TO EXTEND A MIN OF 300mm AT EACH END OF CMU WALL
TYPICAL SLAB-ON-GROUND ISOLATION JOINT SECTION SOG DETAIL @ NON-BRG CMU WALL OPENING
F1 1:8 F5 1 : 16

MARK
TOP OF SLAB ELEVATION SAWCUT
REFER TO PLAN 6
E REFER TO PLAN FOR SLAB-ON-
GROUND REINFORCEMENT, SIZE
CONTROL JOINT (CJ)
AND SPACING.
t/3 CLR

PLOT SCALE: PLOT DATE:


t/4

2:28:18 PM
2/11/2022
200mm CMU WALL

SOLICITATION NO.:
200mm CMU WALL

SA-480530-1$-SS507DT.dwg
REFER TO ARCH

SEE PLAN

CONTRACT NO.:
REFER TO ARCH
CLR

Ø20@150mm, 400mm LONG SMOOTH

ISSUE DATE:
75

BAR ONE END MUST BE GREASED.

t
CONTRACTION/CONSTRUCTION JOINT

t/2
AT NON-BRG CMU WALL (CJ) STAGGERED BETWEEN REBAR

1:1
TOP OF SLAB ELEVATION
REFER TO PLAN

100
TOP OF SLAB ELEVATION
REFER TO PLAN (2)Ø16 (4)Ø16

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


CONTINUOUS VAPOR LAP SPLICE

FILE NO.:
SEE PLAN
BARRIER,

SEE PLAN
REFER TO SPECS

SUBMITTED BY:
t

A. ALHMOOD
300

DESIGN BY:

DRAWN BY:
300
100

A. HANKS
D

100

CKD BY:

ANSI D
BLINDING CONCRETE

SIZE:
LAYER BELOW SOG

1 1
BLINDING CONCRETE BLINDING CONCRETE 1 1

TRANSATLANTIC MIDDLE EAST DISTRICT


LAYER BELOW SOG 3 3 LAYER BELOW SOG
200 500 3 3

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WHEN SOG THICKNESS "t" IS LARGER 200 500
THAN 150 MM, PROVIDE Ø20@300mm, BOTTOM REINFORCMENT WHERE

WINCHESTER, VA 22602
400mm LONG SMOOTH BAR ONE END AGGREGATE APPLICABLE, REFER TO PLANS.
MUST BE GREASED. STAGGERED
BETWEEN REBARS WITH CONTRACTION/CONSTRUCTION JOINT WITHOUT CONTRACTION/CONSTRUCTION JOINT
NOTE: DOWELS ONLY APPLICABLE FOR SLAB THICKNESS GREATER THAN 150 mm.
NOTE: THICKENED SLAB TO EXTEND A MIN OF 300mm AT EACH END OF CMU WALL

TYPICAL SLAB-ON-GROUND CONTROL JOINT SECTION SOG DETAIL @ NON-BRG CMU WALL
C1 1:8 C5 1 : 16
C

Ldowel

(TYP)

REFER TO PLAN FOR SLAB-ON-GROUND

CONCRETE SLAB-ON-GROUND DETAILS - SHEET 1


CONSTRUCTION JOINT (CJ)
t/3 CLR

TOP OF SLAB ELEVATION REINFORCEMENT, SIZE AND SPACING

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


REFER TO PLAN CONTRACTION /
CONSTRUCTION JOINT
(CJ) (TYP)
300mm (TYP)

THAAD STANDARD FACILITIES


SEE PLAN

VARIOUS LOCATIONS, KSA


CLR
75

STANDARD DETAILS
t
t/2

SA-480530
100

OF 4
CONTINUOUS VAPOR
BARRIER,
REFER TO SPECS STOP DOWELS AT DISTANCE
EQUAL TO 1.25 Ldowel OR
Ldowel/2 + 76mm;
WHICHEVER IS GREATER
DOWEL BAR (TYP)
BLINDING CONCRETE REFER TO TYPICAL
LAYER BELOW SOG CONTRACTION AND
TYPICAL CONSTRUCTION
JOINT DETAILS
WHEN SOG THICKNESS "t" IS LARGER
THAN 150 MM, PROVIDE Ø20@300mm, AGGREGATE BOTTOM REINFORCMENT WHERE
400mm LONG SMOOTH BAR ONE END APPLICABLE, REFER TO PLANS.
MUST BE GREASED. STAGGERED
2/11/2022 2:28:18 PM

BETWEEN REBARS

A
NOTE: DOWELS ONLY APPLICABLE FOR SLAB THICKNESS GREATER THAN 150 mm.
SLAB-ON-GROUND DETAIL AT CONTRACTION/CONSTRUCTION JOINT
SHEET ID
TYPICAL SLAB-ON-GROUND CONSTRUCTION JOINT SECTION INTERSECTION
A1 1:8 A5 1 : 16
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS507
1 2 3 4 5 6 7 8 9 10

LARGER OF ADDITIONAL BARS AT EACH LAYER LARGER OF


L+LTS (SIZE TO MATCH INTERRUPTED BARS) L+LTS US Army Corps of
OR 2 x Ld ADD 1/2 THE NUMBER OF BARS OR 2 x Ld Engineers ®
TYPICAL W INTERRUPTED BY OPENING +1 W CLEAR DISTANCE TO
TYPICAL Middle East District
ON EACH SIDE OF OPENING ADJACENT OPENING
G LESS THAN 300mm
1Ø12mm TOP
AND BOTTOM

DATE
500mm
TYPICAL
TYPICAL SLAB
OR HOOK REINFORCEMENT
1-Ø12 TOP AND BOTTOM STANDARD HOOK
(TYP)

900mm
75mm 75mm

MAX.
TYPICAL TYP 1Ø12mm TOP

900mm
CLEAR DISTANCE TO
ADJACENT OPENING

MAX.
LESS THAN 300mm
BARS FOR

900mm
L

MAX.
OPENINGS
GREATER THAN
300mm

DESCRIPTION
F

LARGER OF

OR 2 x Ld
TYPICAL
LARGER OF

900mm 900mm

W+LTS
900mm
OR 2 x Ld
TYPICAL

SLAB
MAX MAX
W+LTS

OPENING MAX
UNINTERRUPTED 1-Ø12 TOP AND
BARS BOTTOM
OPENING SIZE FOR DETERMINING OPENING SIZE FOR DETERMINING
OPENING SIZE FOR DETERMINING SLAB REINFORCEMENT AT SLAB REINFORCEMENT AT
SLAB
INTERRUPTED SLAB REINFORCEMENT AT CLUSTERED OPENINGS CLUSTERED OPENINGS
OPENING
BARS CLUSTERED OPENINGS

MARK
ADDITIONAL TOP BARS WHERE NO TYPE 1 TYPE 2 TYPE 3
E TOP BARS ARE PRESENT SEE TYPE 1 FOR INFORMATION NOT SHOWN SEE TYPE 1 FOR INFORMATION NOT SHOWN

PLOT SCALE: PLOT DATE:


ADDITIONAL BARS WHERE BARS ARE INTERRUPTED CLUSTERED OPENING ADDITIONAL REINFORCEMENT

2:28:19 PM
2/11/2022
SOLICITATION NO.:

SA-480530-1$-SS508DT.dwg
CONTRACT NO.:
NOTES: ADDITIONAL BARS

ISSUE DATE:
1. PROVIDE ADDITIONAL BARS ON EACH SIDE OF OPENING FOR TOP AND BOTTOM BARS ADDITIONAL TOP BARS NOTES: CLUSTERED OPENINGS
1. THE REINFORCEMENT REQUIREMENTS AT CLUSTERED OPENINGS ARE IN NOTES:

1:1
THAT ARE INTERRUPTED BY OPENINGS DISTRIBUTE REPLACEMENT BARS EQUALLY TO
BOTH SIDES OF OPENING AT 76mm SPACING OPENING SIZE ADDITION TO THE TYPICAL SLAB OPENING DETAIL REQUIREMENT AROUND 1. REFER TO PLANS FOR ADDITIONAL BARS AROUND OPENINGS.
2. PROVIDE A MINIMUM OF 2 BARS EACH SIDE OF OPENING TOP AND BOTTOM WHERE NO (LARGER DIMENSION TOP BARS THE ENTIRE CLUSTER. 2. SEE STRUCTURAL DRAWINGS FOR QUANTITY AND LOCATIONS OF OPENINGS. VERIFY SIZE AND
TOP BARS ARE PRESENT, PROVIDE ADDITIONAL TOP BARS SHOWN ABOVE OF OPENING) ALL SIDES 2. FOR ONE-WAY SLABS, WHEN CLUSTERED OPENING IS GREATER THAN LOCATION OF OPENINGS WITH MEP DRAWINGS NOTIFY STRUCTURAL ENGINEER IN WRITING OF
3. AT CLUSTERED OPENINGS, PROVIDE THESE ADDITIONAL BARS AROUND THE CLUSTER 610mm, SUBMIT REINFORCEMENT PLAN TO CONTRACTING OFFICER FOR DISCREPANCIES FOR REVIEW AND APPROVAL.

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


0 to 300mm NONE
PLUS THE ADDITIONAL BARS SHOWN IN THE CLUSTERED OPENINGS DETAIL APPROVAL. 3. FOR TWO-WAY SLAB SEE TYPICAL TWO-WAY SLAB OPENING LIMITATIONS. FOR OPENING NOT

FILE NO.:
300mm to 915mm (1) Ø12 3. FOR TWO-WAY SLABS, WHEN CLUSTERED OPENING DOES NOT MEET TWO- MEETING LIMITATIONS OR GREATER THAN 915mm, SUBMIT OPENINGS TO SEOR FOR APPROVAL
WAY SLAB OPENING LIMITATIONS OR IS GREATER THAN 915mm, SUBMIT TO FOR ONE-WAY SLABS WHERE THE OPENING DIMENSION PERPENDICULAR TO THE DIRECTION OF THE

SUBMITTED BY:
SEOR FOR APPROVAL. SPAN IS GREATER THAN 610mm, SUBMIT OPENINGS TO SEOR FOR APPROVAL.

A. ALHMOOD
DESIGN BY:

DRAWN BY:
4. WHERE ADJACENT OPENINGS ARE NOT SEPARATED BY 2X THE LARGEST OPENING DIMENSION OR

A. HANKS
D

CKD BY:
WOULD INTERRUPT THE ADDITIONAL REINFORCEMENT FROM THE ADJACENT OPENING, SUBMIT

ANSI D
SIZE:
OPENINGS TO SEOR FOR APPROVAL.

ADDITIONAL REINFORCEMENT AT SLAB-ON-GROUND PENETRATIONS /

TRANSATLANTIC MIDDLE EAST DISTRICT


OPENINGS
D1

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


1 : 24

WINCHESTER, VA 22602
50 CLEAR
TOP OF SLAB ELEVATION
REFER TO PLAN (TYP)

SLAB-ON-GROUND
MATCH SLAB-ON-GROUND
REINF (TYP) (2)⌀12 T&B
150mm MAX

REINF SIZE AND SPACING


Ø12
INTERIOR CONC

610
SLAB-ON-GROUND

61
C
THICKNESS

0
(4)⌀12 TOP
(T)

61
0
100

CONC SLAB-

610
1 ON-GROUND
AR

CONCRETE SLAB-ON-GROUND DETAILS - SHEET 2


BLINDING CONCRETE 2T (300mm MIN) LE

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


2 C
LAYER BELOW SOG
50
LAP SPLICE

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
CONTINUOUS VAPOR
BARRIER,

STANDARD DETAILS
ISOLATION JOINT (IJ)
REFER TO SPECS CONTRACTION /
CONSTRUCTION JOINT (CJ)
SLAB-ON-GROUND WITHOUT TOP REINFORCEMENT

SA-480530
B

OF 4
NOTE: REENTRANT CORNERS - PLAN
REFER TO PLANS AND PLAN NOTES FOR SLAB-ON-GROUND PLAN
THICKNESS AND REINFORCEMENT. NOTE: NOTE:
REINFORCEMENT SHOWN MUST NOT CROSS NEARBY JOINTS IN REINFORCEMENT SHOWN MUST NOT CROSS NEARBY
SLAB-ON-GROUND. JOINTS IN SLAB-ON-GROUND.

TYP SLAB-ON-GROUND STEP LESS THAN 150mm ADD'L REINFORCEMENT AT DISCONTINUOUS JOINTS ADD'L REINFORCEMENT AT CORNERS
A1 1 : 12 A4 1 : 16 A8 1 : 16
2/11/2022 2:28:19 PM

A SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS508
1 2 3 4 5 6 7 8 9 10

Ø12@300mm CORING AND CUTTING THROUGH Ø12@300mm


2 HORIZONTAL REINFORCEMENT IS NOT 2 HORIZONTAL US Army Corps of
PROVIDE ADHESIVE ANCHORS W/
BARS MINIMUM ALLOWED USE EMBED PLATES BARS MINIMUM Engineers ®
EMBED, QTY & DIA AS REQD BY
FACE OF EQUIPMENT (TYP)
EQUIP MFR Middle East District
G Ø12@250mm OC EW Ø12 DOWELS @ 300mm
Ø12@300mm OC DRILLED 150 OC ALL AROUND
IN WITH ADHESIVE
Ø12@300mm OC EW

DATE
ANCHORS 76mm MINIMUM MIN
EMBED CONTRACTOR
HAS OPTION TO
DRILL AND

460mm MAX
EQ EQ KEYWAY OR GROUT DOWELS
INTENTIONALLY AS ALTERNATIVE

H
ROUGHEN SURFACE ISOLATION

75

UNO
150
JOINT (IJ) PLAN DIMENSIONS & LOCATIONS

RE: ARCH, MECH & ELEC DWGS PROVIDE ADHESIVE ANCHORS W/

100
T/SLAB ON GRADE EMBED, QTY & DIA AS REQD BY
150 MIN EQUIP MFR
EL SEE PLAN Ø16 @ 200mm

UNO
150
OC EW T&B TYP

100
FIN GRADE

DESCRIPTION
F SEE CIVIL

300 MIN
BLINDING CONCRETE
LAYER
CURB WIDTH - 76mm MINIMUM TO 180mm MAX CURB WIDTH OVER 180mm

CONC SLAB-ON-GROUND REINF CLEAN AND ROUGHEN SURFACE TO 6mm


NOTES: AMPLITUDE PRIOR TO CONC PLACEMENT BLINDING CONCRETE LAYER
1. FOR SIZE AND LOCATION SEE ARCHITECTURE, MEP, OR STRUCTURAL DRAWINGS
2. ROUGHEN SURFACE OF SLAB TO 6mm AMPLITUDE CLEAN THOROUGHLY AND APPLY 150mm EQUIPMENT PAD ON SLAB-ON-GROUND
BONDING AGENT IMMEDIATELY BEFORE CASTING CURB NOTE:
3. THIS DETAIL IS APPLICABLE AT CURBS FOR NON-STRUCTURAL ELEMENTS SUCH AS 1. COORDINATE EQUIPMENT PAD REQUIREMENTS WITH NOTES:
SKYLIGHTS, INTERIOR PARTITIONS AND INTERIOR RAILINGS MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS. 1. COORDINATE SIZE & LOCATION WITH EQUIPMENT REQUIREMENTS
4. SEE ARCH DRAWINGS FOR EMBEDDED PLATES AND BLOCKOUTS REPLACE 2. CHAMFER EDGES 25mm TYPICAL.
REINFORCEMENT INTERRUPTED BY BLOCKOUTS.
5. AT CONTRACTOR'S OPTION, CAST IN PLACE DOWELS MAY BE USED IN PLACE OF

MARK
POST-INSTALLED.

E TYPICAL CURB DETAILS (INTERIOR) TYP CONCRETE EQUIPMENT PAD ON SOG TYP CONCRETE EQUIPMENT PAD - STANDALONE
E1 1:8 E4 1 : 12 E7 NTS

PLOT SCALE: PLOT DATE:


2:28:20 PM
2/11/2022
SOLICITATION NO.:

SA-480530-1$-SS509DT.dwg
CONTRACT NO.:
ISSUE DATE:
FILTER FABRIC AROUND PIPE

1:1
SLAB ON GROUND

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN

FILE NO.:
BLINDING CONCRETE LAYER

SUBMITTED BY:
A. ALHMOOD
DESIGN BY:

DRAWN BY:

A. HANKS
D

100

CKD BY:

ANSI D
PIPE TRENCHES MUST BE LOCATED

SIZE:
SO THAT FOOTINGS WILL NOT BE

250
NO PIPE WILL PASS UNDERMINED
THROUGH THIS PORTION OF

TRANSATLANTIC MIDDLE EAST DISTRICT


FOOTING, SEE PLAN FOR SIZE PIPE SLEEVE

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
A 200mm POROUS FILL OR GRAVEL
75 MIN

UNDISTURBED SOIL ROCK, OR

150
WELL COMPACTED BACKFILL

150mm DIA PERFORATED PVC PIPE


75 MIN

250 250

C
250

UNDERSLAB DRAIN DETAIL


C7 1:8
100 MIN

CONCRETE SLAB-ON-GROUND DETAILS - SHEET 3


900 MAX

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


SLAB ON GROUND MEP CONDUIT
FOR SIZE AND LOCATION
2 MIN
SEE MEP DWGS

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
1

STANDARD DETAILS
150 MIN

SA-480530
B

OF 4
500 MIN 500
PIPE SLEEVE 50 mm LARGER CONCRETE FILL MUST BE
THAN PIPE PENETRATION PLACED PRIOR TO TYP
POURING FOOTINGS

100 MIN
1
NO PIPES PERMITTED IN OR THROUGH FOOTING. SECTION A
CONCRETE FILL MUST BE SAME WIDTH AS FOOTING PAD
AND FULL WIDTH OF PIPE TRENCH. FOOTING MUST BE 1
STEPPED PER TYPICAL STEPPED FOOTING DETAIL, SO
THAT CONCRETE FILL DOES NOT EXCEED 915mm ABOVE 100 MIN.
PIPE INSERT.
Y P.
. T
LR
2/11/2022 2:28:20 PM

C
0
10
A SHEET ID
TYPICAL PIPE AND TRENCH DETAIL
A1 1:8 TYPICAL DETAIL OF CONDUIT ENCASEMENT $
A7 1:8
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS509
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
G

DATE
CENTERLINE
COLUMN

13mm IJ 460

12mm DIA SMOOTH TYP


DOWEL AT 400mm OC,

DESCRIPTION
ISOLATION JOINT
F 300mm LONG, TYP.
150mm THICK
EXTERIOR SLAB WITH
Ø12 @ 300 EW
INTERIOR SLAB, SEE PLAN BASE PLATE

460

TYP

CENTERLINE
SLOPE BELOW STEEL COLUMN
REFER TO

COLUMN
PAVING OR FIN. GRADE SCHEDULE

SEE CIVIL
2
1
200 MIN

200 (2) Ø12, TYP

MARK
NOTE: T/FTG
E SEE ARCHITECTURE DWGS SEE PLAN
FOR PAD ELEVATIONS CONCRETE FILL
CONTRACTION/CONSTRUCTION AROUND COLUMN

PLOT SCALE: PLOT DATE:


JOINT (CJ) OR ISOLATION JOINT AFTER SLAB IS

2:28:21 PM
2/11/2022
(IJ) REFER TO PLAN (TYP) POURED

SOLICITATION NO.:

SA-480530-1$-SS510DT.dwg
CONTRACT NO.:
ISSUE DATE:

1:1
K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN

FILE NO.:
TYPICAL CONCRETE PAD AT EXTERIOR DOOR SLAB-ON-GRADE DETAIL AT STEEL COLUMN
D1 D4

SUBMITTED BY:
1 : 20 1 : 16

A. ALHMOOD
DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
US ARMY CORPS OF ENGINEERS
COL COL COL

201 PRINCE FREDERICK DRIVE,


COL

WINCHESTER, VA 22602
ADD Ø16 CENTERED EQ
IN SLAB, TYP AT
CORNERS ADD Ø16 CENTERED TYP
IN SLAB, TYP AT
TYP

60
300

ISOLATION JOINT

0
CORNERS

CONTROL R

7
CONTROL 13mm ISOLATION 13mm ISOLATION CL

5
JOINT (CJ)
C JOINT (CJ) JOINT, TYP. 4 SIDES JOINT 50
CONCRETE

TYP
EQ
13mm ISOLATION COLUMN
JOINT
CJ CJ
R
CL
50 300
TYP COL
50
C
LR

CONCRETE SLAB-ON-GROUND DETAILS - SHEET 4


COL COL COL

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


THAAD STANDARD FACILITIES
VARIOUS LOCATIONS, KSA
0
60

STANDARD DETAILS
COLUMN CONCRETE FILL

SA-480530
AROUND COLUMN
CONTRACTION/CONSTRUCTION
B

OF 4
CJ

FOUNDATION WALL FOUNDATION WALL AFTER SLAB IS


JOINT (CJ) OR ISOLATION JOINT POURED
0 (IJ) REFER TO PLAN (TYP)
ADD Ø16 CENTERED
60
IN SLAB, TYP AT RE-
COLUMN COLUMN
ENTRANT CORNERS

CORNER COLUMN EXTERIOR COLUMN INTERIOR COLUMN


2/11/2022 2:28:21 PM

A SHEET ID
TYPICAL SOG JOINT DETAILS AT CONCRETE COLUMN
A1 1 : 16 $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS510
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
G

DATE
Ø12 CONT
13mm IJ
13mm IJ
20mm DIA SMOOTH LAP SPLICE 900 MIN TO FACE L
DOWEL AT 400mm OC,
OIL/GREASE ONE END, TO COL FTG 1200 MIN TOP OF SLAB
300mm LONG (TYP) EL VARIES
CONC SHEAR WALL

SEE PLAN
600 MAX
EXTERIOR SLAB INTERIOR SLAB, SEE PLAN

T
VENEER,
SEE ARCH DOWELS TO MATCH WALL REINF SLOPE
FIN GRADE
IJ
SLAB, SEE PLAN
REINF TO MATCH

DESCRIPTION
GRADE, FTG REINF Ø12@300 EW, MID

STEP = 600 MAX


F SEE CIVIL

1000

MIN
ROUGHENED SURFACE
REINF TO MATCH
FTG REINF
FOUNDATION
REINFORCING T/FTG

(TYP)
BLINDING CONC 3-Ø16

T
BARS AND COLUMN

300
FOUNDATION SEE PLAN
BARS BELOW GRADE 1
REINFORCING T/FTG MUST BE 1
BARS AND COLUMN
SEE PLAN GALVANIZED
BARS BELOW GRADE

CLR
75
MUST BE
T
GALVANIZED 200 200 200 BLINDING CONC
(UNO ON PLAN)

MARK
E FOUNDATION DETAIL AT WALL FOUNDATION DETAIL AT OPENING TYP STEPPED FOOTING DETAIL TYPICAL RAMP WALL DETAIL
E1 NTS E3 NTS E5 NTS E8 NTS

PLOT SCALE: PLOT DATE:


2:28:22 PM
2/11/2022
SOLICITATION NO.:

SA-480530-1$-SS511DT.dwg
CONTRACT NO.:
ISSUE DATE:

1:1
25 mm RISER
SLOPE TYP

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


2 Ø12 TYP

FILE NO.:
EA NOSING
CL

SUBMITTED BY:
A. ALHMOOD
SLOPE Ø12 TYP

DESIGN BY:
T/SLAB

DRAWN BY:

A. HANKS
D EA NOSING

CKD BY:
15
SEE PLAN

ANSI D
0M

SIZE:
T/SLAB

IN
75
CL
ISOLATION JOINT ISOLATION SEE PLAN

R
JOINT

TRANSATLANTIC MIDDLE EAST DISTRICT


450

US ARMY CORPS OF ENGINEERS


T/PVMT T/PVMT

201 PRINCE FREDERICK DRIVE,


SEE ELEC/TELECOM
SEE CIVIL SEE CIVIL

600mm MIN.

WINCHESTER, VA 22602
75

VARIES
Ø16@300

CL
COLUMN PER PROVIDE TIES AROUND FOUNDATION DOWELS,

600

R
SCHEDULE MATCH COLUMN TIES ABOVE FOUNDATION LIGHTNING POLE,
SEE ELEC/TELECOM
TOP REINFORCEMENT IF NEEDED PER SCHEDULE 2
GROUND FLOOR TOC
BASE PL & ANCHORS
SEE PLANS
BY POLE MANUFACTURER
300 300 300
SECTION 1 - 1
C CHAMFER EDGE SECTION 2 - 2
NOTES:
GRADE, 1. PROVIDE 300mm GRADE BEAM EACH SIDE OF STAIR AS
FOOTING TOC REQUIRED, REINFORCED WITH (2) Ø16 T&B AND

50
SEE CIVIL

100
SEE PLAN (2) Ø16 SKIN REINF EF.
2. SEE CIVIL AND ARCHITECTURAL DRAWINGS FOR STAIR
BOTTOM REINFORCEMENT LOCATIONS.
3. COORDINATE STAIR RISE, RUN, AND NUMBER OF
FOUNDATION TREADS WITH ARCHITECTURAL AND CIVIL PLANS.
REINFORCING
75 (3) - Ø10 TIES
100

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


BARS AND COLUMN 100 100 BLINDING CONCRETE LAYER BELOW FOOTING
BARS BELOW GRADE CLR @ 75 OC AT
TYPICAL STAIRS AT GRADE

FOUNDATION DETAILS - SHEET 1 OF 2


MUST BE
GALVANIZED
ANCHOR
RODS C8 NTS

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA

STANDARD DETAILS
2000 MIN
FOOTING WIDTH PER SCHEDULE A8 (6) - Ø25 VERT BARS
W/ 90-DEG HOOKS
SS511 (6) - Ø25 VERT FOUNDATION

SA-480530
PIER
FOOTING PER PLAN AND
B SCHEDULE
SUBGRADE OR STRUCTURAL FILL MUST Ø10 TIES
BE PREPARED AND COMPACTED PER @ 300 OC
SECTION 31 00 00 - EARTHWORK
Ø10 TIES W/ LAP
CONC
FOUNDATION
NOTES: 480 LAP
1. SUBGRADES AND INITIAL BACKFILL MUST BE PREPARED IN STRICT ACCORDANCE WITH SPECIFICATION 31 00 00 - EARTHWORK.
MIN
2. FOUNDATION SUBGRADES BELOW FOOTINGS MUST BE COMPETENT TO RECEIVE ALLOWABLE BEARING PRESSURE AS ASSUMED FOR DESIGN. THE
GEOTECHNICAL ENGINEER MUST VERIFY THAT SUBGRADES ARE PREPARED TO RECEIVE THE ASSUMED DESIGN BEARING PRESSURE. SECTION A-A
600
2/11/2022 2:28:22 PM

A TYPICAL FOUNDATION DETAIL TYP LIGHTNING POLE FOUNDATION DETAIL TYP LIGHTNING POLE PIER SECTION
A1 1 : 25 A6 NTS A8 NTS
SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS511
1 2 3 4 5 6 7 8 9 10

ADDITIONAL STIRRUPS AT 76mm SPACING


(SIZE TO MATCH INTERRUPTED STIRRUPS) US Army Corps of
PLACE ONE HALF THE NUMBER OF Engineers ®
STIRRUPS INTERRUPTED BY
PENETRATION + 1 AT EACH SIDE CL CL Middle East District
G OF PENETRATION CIRCULAR
OPENING
CIRCULAR
OPENING

DATE
TOP BAR CLOSED TOP BARS SEE
SEE SCHEDULE TOP STIRRUPS BEAM SCHEDULE
SEE SCHEDULE CLOSED
T/SLAB ON GRADE TOP STIRRUPS

EL SEE PLAN
TOP BARS SEE
BEAM SCHEDULE

H/2 UON
STIRRUPS SEE

SEE BEAM SCHEDULE


TOP BARS
BEAM SCHEDULE

DESCRIPTION
F

H
CL PENETRATION

SIDE BARS SEE


BEAM SCHEDULE BOTTOM BARS
90 DEGREE HOOK
AT OPENING
BOTTOM BARS SEE
BEAM SCHEDULE

38 CLR
TYP CLOSED BOTTOM STIRRUPS
LTS DIA 38
CLOSED
200 MAX CLR W

MARK
BOTTOM BAR BOTTOM STIRRUPS BOTTOM BARS SEE
SEE SCHEDULE SEE SCHEDULE BEAM SCHEDULE
SEE BEAM SCHEDULE
E

PLOT SCALE: PLOT DATE:


2:28:23 PM
2/11/2022
SOLICITATION NO.:

SA-480530-1$-SS512DT.dwg
CONTRACT NO.:
NOTES:

ISSUE DATE:
1. BEAM PENETRATIONS MUST BE SHOWN ON THE SHOP DRAWINGS FOR REVIEW BY THE DESIGN PROFESSIONALS. NO PENETRATIONS WILL BE MADE WITHOUT PRIOR WRITTEN
APPROVAL FROM THE DESIGN PROFESSIONAL.

1:1
2. THESE DETAILS MUST BE USED IN CONJUNCTION WITH CONCRETE BEAM PENETRATION SCHEDULE.
3. THE MINIMUM CLEAR SPACE BETWEEN TWO ADJACENT PENETRATIONS MUST BE GREATER OF THE LARGEST PENETRATION DIMENSION OR TWO TIMES THE BEAM DEPTH.
4. THE MINIMUM CLEAR DIMENSION BETWEEN THE EDGE OF A PENETRATION AND THE FACE OF SUPPORT MUST BE THE DEPTH OF THE BEAM.
5. SEE STRUCTURAL DRAWINGS FOR PENETRATIONS. VERIFY QUANTITY, SIZE, AND LOCATION OF PENETRATIONS WITH MEP DRAWINGS. NOTIFY THE CONTRACTING OFFICER IN WRITING

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


OF DISCREPANCIES FOR REVIEW AND ACTION.
6. NO ADDITIONAL REINFORCEMENT IS REQUIRED FOR OPENINGS WITH 100mm DIAMETER OR SMALLER PROVIDED NO BEAM REINFORCEMENT IS INTERRUPTED AND MINIMUM CONCRETE

FILE NO.:
COVER IS PROVIDED AROUND BARS. IT IS ACCEPTABLE TO ADJUST BEAM REINFORCEMENT WITHIN MAXIMUM SPACING LIMITS FOR STIRRUPS OR SIDE BARS.

SUBMITTED BY:
A. ALHMOOD
DESIGN BY:

DRAWN BY:
TYPICAL GRADE BEAM SLEEVE - ELEVATION

A. HANKS
D

CKD BY:
D1

ANSI D
SIZE:
1 : 24

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
HEAVY HEX NUT

FIRST POUR SECOND POUR SQUARE OR ROUND PLATE BASE PLATE W/ OVERSIZED
WASHER WITH STANDARD HOLE HOLE, PER SCHEDULE A
TOP BARS SIZE AND THICKNESS PER
SEE SCHEDULE SCHEDULE A MINIMUM ANCHOR ROD
50 50 LTS PROJECTION ABOVE BASE
PLATE PER SCHEDULE A
T/SLAB ON GRADE
LEVELING NUT
BOTTOM OF BASE PLATE
C EL SEE PLAN
T/CONCRETE
EL SEE PLAN NOMINAL GROUT THICKNESS AS
ROUGHEN
CONTACT SURFACE PER DRAWINGS

50mm MIN
TO 6mm AMPLITUDE
THREAD LENGTH
MINIMUM EMBEDMENT LENGTH
AS PER DRAWINGS

100 MINIMUM

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


COVER
BOTTOM OF

FOUNDATION DETAILS - SHEET 2 OF 2


STIRRUPS
SEE SCHEDULE CONCRETE ANCHOR ROD AS PER

THAAD STANDARD FACILITIES


DRAWINGS

VARIOUS LOCATIONS, KSA

STANDARD DETAILS
HEX BOLT HEAD

SA-480530
B
BOTTOM BARS NOTE SIDE BARS
SEE SCHEDULE ADDITIONAL SEE TYPICAL SCHEDULE A
STIRRUPS BEAM SECTION
ANCHOR BASE PL MIN MIN MIN PROJ NOMINAL
ROD HOLE DIA WASHER WASHER ABOVE GROUT
DIAMETER SIZE THICKNESS BASE PL THICKNESS
(mm) (mm) (mm) (mm) (mm) (mm)
NOTES:
1. SUBMIT CONCRETE CONSTRUCTION JOINT LAYOUT FOR REVIEW AND ACTION (REFER TO GENERAL NOTES AND 19 33 51 6 76 51
SPECIFICATIONS) PRIOR TO REINFORCEMENT SUBMITTAL. 22 40 64 8 89 51
2. HORIZONTAL CONSTRUCTION JOINTS ARE NOT PERMITTED WITHOUT PRIOR WRITTEN APPROVAL FROM SEOR.
3. ACCEPTABLE TO PROVIDE CONSTRUCTION JOINT AT FACE OF PILE CAP PROVIDED TWO 50mm X 100mm 25 48 76 10 89 51
HORIZONTAL SHEAR KEYS ARE PROVIDED AND INSTALLED AT THE INTERFACE.
32 54 89 13 102 51
2/11/2022 2:28:23 PM

38 60 102 13 102 51

A TYPICAL GRADE BEAM CONSTRUCTION SHEET ID


JOINT - ELEVATION TYPICAL ANCHOR ROD DETAIL $
A1 1 : 24 A6 1:8
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS512
1 2 3 4 5 6 7 8 9 10

TYPICAL EXTERIOR NON-BEARING CMU WALL REINFORCEMENT SCHEDULE

TYP US Army Corps of


NOMINAL MAXIMUM TYPICAL WALL REINFORCEMENT
VERTICAL IN FIRST CELL D1
WALL WALL Engineers ®
OF LINTEL AT OPENING SS515 THICKNESS, t HEIGHT, H Middle East District
VERTICAL HORIZONTAL HORIZONTAL REMARKS
CONTROL JOINT TYPICAL
G (mm) (mm) JOINT BOND BEAM

200 4800 Ø16 @ 600 OC (2) W1.7 @ 400 OC (2) Ø16* *AT TOP AND BOTTOM, AND AT TOP AND BOTTOM OF OPENINGS
T/WALL

DATE
200 6300 Ø16 @ 400 OC (2) W1.7 @ 400 OC (2) Ø16* *AT TOP AND BOTTOM, AND AT TOP AND BOTTOM OF OPENINGS
NO CONTROL JOINTS
ARE TO BE LOCATED AT 250 4800 Ø16 @ 600 OC (2) W1.7 @ 400 OC (2) Ø16* *AT TOP AND BOTTOM, AND AT TOP AND BOTTOM OF OPENINGS
OPENING CORNERS,
TYPICAL 250 6300 Ø16 @ 400 OC (2) W1.7 @ 400 OC (2) Ø16* *AT TOP AND BOTTOM, AND AT TOP AND BOTTOM OF OPENINGS

TYPICAL INTERIOR NON-BEARING CMU WALL REINFORCEMENT SCHEDULE

NOMINAL MAXIMUM TYPICAL WALL REINFORCEMENT


WALL WALL
THICKNESS, t HEIGHT, H VERTICAL HORIZONTAL HORIZONTAL REMARKS
(mm) (mm) JOINT BOND BEAM

DESCRIPTION
SEE TYPICAL CMU SILL
F AND LINTEL SCHEDULE 200 4500 Ø16 @ 1200 OC (2) W1.7 @ 400 OC (2) Ø16* *AT TOP AND BOTTOM, AND AT TOP AND BOTTOM OF OPENINGS
A5 FOR REINFORCEMENT
LINTEL SCHEDULE NOTES:
UNITS 1. CELLS WITH REINFORCING BARS MUST BE FULLY GROUTED.
2. REINFORCEMENT SHOWN IN SCHEDULE IS TYPICAL. REFER TO
DETAILS FOR ADDITIONAL REQUIRED REINFORCEMENT AT WALL ENDS,

WALL HEIGHT "H"


CORNERS, INTERSECTIONS, JAMBS, PIERS, CONTROL JOINTS, DOOR
75mm MAXIMUM AT CMU LINTEL AND WINDOW OPENINGS, FRAMING ANCHORAGES, BEAM POCKETS,
(20mm CLEAR MINIMUM TO AND UTILITY PENETRATIONS, ETC.
BOTTOM SHELL)

PIER HEIGHT
TYP 20 CLEAR
A1
SS514 OPENING LENGTH L1 MASONRY UNIT

SEE LINTEL SCHEDULE AND NOTE 1 BAR CENTERED ON CELL BAR AT OUTSIDE FACES OF CELL
OPENING LENGTH L2

MARK
E
HORIZONTAL BAR (S) HORIZONTAL BAR (S)
VERTICAL IN FIRST CELL AT

PLOT SCALE: PLOT DATE:


WHERE SCHEDULED IN BOND WHERE SCHEDULED IN BOND
OPENINGS FULL HEIGHT BEAM (NOT SHOWN) BEAM (NOT SHOWN)

2:28:24 PM
2/11/2022
SEE SCHEDULE A1

SOLICITATION NO.:

SA-480530-1$-SS513DT.dwg
CONTRACT NO.:
ISSUE DATE:
ONE BAR TWO BAR
PER CELL LAYOUT PER CELL LAYOUT

1:1
SEE TYPICAL CMU NON-BEARING WALL
PLAN DETAIL AT ADJACENT WALL TYPICAL REINFORCEMENT LAYOUT
OPENING FOR JAMB AND PIER ZONE
CRITERIA

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


TYPICAL CMU NON-BEARING WALL

FILE NO.:
T/SLAB

SUBMITTED BY:
REINFORCEMENT SCHEDULE

A. ALHMOOD
DESIGN BY:

DRAWN BY:
D6

A. HANKS
D DOWELS

CKD BY:
1 : 12

ANSI D
SEE BASE OF WALL

SIZE:
JAMB ZONE PIER ZONE
DETAILS ON SS515 NOTES:
1. FOR WALL INFORMATION NOT SHOWN, SEE TYPICAL CMU NON-BEARING
PW WALL ELEVATION WITH STEEL OR PRECAST LINTELS.

TRANSATLANTIC MIDDLE EAST DISTRICT


2. SEE TYPICAL CMU SILL AND LINTEL SCHEDULE A5 FOR ADDITIONAL
PIER WIDTH

US ARMY CORPS OF ENGINEERS


INFORMATION.

201 PRINCE FREDERICK DRIVE,


3. PROVIDE CONTROL JOINTS IN CMU WALLS AT EVERY 6000mm ON CENTER,

WINCHESTER, VA 22602
AT PILASTERS, WALL HEIGHT CHANGE, ADJACENT TO LINTELS, OR AS
NOTED ON THE DRAWINGS.

TYPICAL CMU NON-BEARING WALL ELEVATION WITH CMU LINTELS


C1 1 : 12 VERTICAL REINFORCEMENT
SEE SCHEDULE

FULLY GROUT CELLS FOR FULL


C HEIGHT OF LINTEL DEPTH SCHEDULED
WALL THICKNESS

BOTTOM SHELL
SEE SCHEDULE
LINTEL DEPTH

20 CLEAR TO
MAXIMUM
MASONRY 200 mm WALL BOND BEAM AT SECOND COURSE WITH
OPENING REINFORCEMENT PER SCHEDULE. WHERE
TYPICAL NON-BEARING CMU WALL JAMB AND PIER ZONE SCHEDULE "L" LINTEL 1ST 2ND REINFORCEMENT IS NOT REQUIRED FULLY
DEPTH COURSE COURSE GROUT CELLS
NOMINAL MAXIMUM MAXIMUM JAMB AND PIER ZONE GEOMETRY REMARKS REINF REINF

CONCRETE UNIT MASONRY DETAILS - SHEET 1 OF 4


WALL WALL CLEAR BOND BEAM WITH REINFORCEMENT
THICKNESS, t HEIGHT, H OPENING, JAMB ZONE WIDTH, PIER ZONE WIDTH1 VERTICAL

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


SCHEDULE
SEE SCHEDULE AT FIRST COURSE
(mm) (mm) L1 OR L23 W1 OR W2 (mm) REINFORCING IN 1900 200 2Ø16 -
(mm) EACH CELL LINTEL
(mm)
(mm)

OPENING

THAAD STANDARD FACILITIES


3000 400 2Ø16 -

VARIOUS LOCATIONS, KSA


1220 200 400 Ø16
75 mm MAXIMUM TO CL

STANDARD DETAILS
200 6300 2130 400 400 Ø16
NOTES:

SA-480530
1. MASONRY LINTELS MUST BE SHORED DURING CONSTRUCTION AND MUST REMAIN SHORED UNTIL MASONRY
B 3660 600 600 Ø16
HAS GAINED 100% OF FULL SPECIFIED STRENGTH (f'm)
2. DESIGN BASED ON DESIGN SERVICE LOAD PRESSURE NOTED AS 1.44 kPA, UNLESS OTHERWISE NOTED
3. SEE TYPICAL CMU NON-BEARING WALL ELEVATIONS FOR ADDITIONAL INFORMATION.
SCHEDULE NOTES: BOND BEAM WITH REINFORCEMENT
1. SINGLE VALUE (X mm) REFERS TO PIER ZONE WIDTH WITH CONTINUOUS VERTICAL BARS SEE SCHEDULE AT FIRST COURSE
EXTENDING FULL HEIGHT OF WALL X mm.
DOUBLE VALUE (X mm/Y mm) REFERS TO A MINIMUM PIER OF TOTAL WIDTH Y mm (INCLUDING NON-
CONTINUOUS CELLS INTERRUPTED BY LINTELS, AND A MINIMUM PIER ZONE
WIDTH WITH CONTINUOUS BARS EXTENDING FULL HEIGHT OF WALL OF X mm.
2. JAMBS AND PIERS MUST BE FULLY GROUTED, WITH VERTICAL REINFORCING BARS IN EACH CELL.
3. AT ADJACENT OPENINGS; VALUE FOR MAXIMUM CLEAR OPENING MUST BE AT LEAST EQUAL TO THE AVERAGE WIDTH
OF ADJACENT OPENINGS.
4. AT PIERS WIDER THAN REQUIRED PER SCHEDULE, IT IS PERMITTED TO REINFORCE EDGES AS JAMB ZONES.
5. NOTIFY THE CONTRACTING OFFICER IF JAMB AND/OR PIER LENGTH NOTED CANNOT BE SATISFIED.
6. REFER TO A1/SS514 FOR W1 AND W2. TYPICAL MASONRY SECTION AT OPENING
2/11/2022 2:28:24 PM

A TYPICAL CMU SILL AND LINTEL SCHEDULE SHEET ID


TYPICAL NON-BEARING CMU WALL JAMB AND PIER ZONE SCHEDULE (NON-BEARING WALL) $
A1 1 : 12 A5 NTS
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS513
1 2 3 4 5 6 7 8 9 10

CONT HORIZONTAL REINF US Army Corps of


Engineers ®
LAP SPLICE LAP SPLICE
Middle East District

0 TYP
G (TYP)

DATE
CENTERLINE OF
(3) VERTICAL BARS (1) VERTICAL BAR (2) VERTICAL BARS
BEAM BEARING

EQ EQ

EQ EQ

EQ EQ

EQ EQ
LAP SPLICE

LAP SPLICE
90-DEGEE DOWEL BARS
TO MATCH HORIZONTAL
REINF (TYP) (2) VERTICAL BARS CENTERLINE OF
IN (2) CELLS NEAREST TO BEAM BEARING
CENTER OF BEAM BEARING
CONT CONT HORIZONTAL REINF
HORIZONTAL 0 TYP 0 TYP EQ EQ EQ EQ
REINF

DESCRIPTION
F CORNER INTERSECTION
CORNER INTERSECTION BEAM BEARING PERPENDICULAR BEAM BEARING AT END
DOWEL BARS AT
SPLICES (TYP)
GROUT SOLID (TYP)
GROUT SOLID

38
CONT HORIZONTAL

75
REINF (TYP)

CONT HORIZONTAL REINF OPEN CLOSED


BOTTOM BOTTOM NOTES:

MARK
UNIT UNIT 1. BAR SIZES TO MATCH TYPICAL WALL REINF IN SCHEDULE D6 ON SS513, UON.
2. HORIZONTAL REINF NOT SHOWN FOR CLARITY.
E TYPICAL SECTIONS 3. REFER TO TYPICAL PLAN, ELEVATION, AND SECTION DETAILS AT CMU WALL
OPENINGS FOR ADDITIONAL INFORMATION.
NOTES: 4. REFER TO ARCH FOR WALL THICKNESS, LAYOUT, AND OPENINGS.

PLOT SCALE: PLOT DATE:


1. REFER TO SCHEDULE D6 ON SS513 FOR HORIZONTAL REINF SIZE
AND QUANTITY.

2:28:25 PM
2/11/2022
2. VERTICAL REINF NOT SHOWN FOR CLARITY.

SOLICITATION NO.:

SA-480530-1$-SS514DT.dwg
3. REFER TO ARCH FOR WALL THICKNESS, LAYOUT, AND OPENINGS.

CONTRACT NO.:
ISSUE DATE:

1:1
TYPICAL CONCRETE MASONRY BOND BEAM REINFORCING DETAILS CONCRETE UNIT MASONRY (CMU) VERTICAL REINFORCING DETAILS
D1 D6

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


1 : 12 1 : 16

FILE NO.:
SUBMITTED BY:
A. ALHMOOD
DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
SIZE:
400 mm D. 400 MAX 3xD CLR MIN 400 mm

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
3 x LARGEST D CLR MIN
VERTICAL
REINF (SEE
SCHEDULE D6 ON
SS513)
C WHERE OPENING INTERRUPS
HORIZONTAL JOINT REINF, ADD
JOINT REINF ABOVE AND BELOW
OPENING
BARS AT EACH CELL BARS AT EACH CELL BAR AT EACH CELL
IN JAMB ZONE IN PIER ZONE IN JAMB ZONE

CONCRETE UNIT MASONRY DETAILS - SHEET 2 OF 4


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
PIPE PENETRATIONS

THAAD STANDARD FACILITIES


D 3 x D CLR, 200 MIN MUST NOT INTERRUPT

VARIOUS LOCATIONS, KSA


VERTICAL REINFORCEMENT

STANDARD DETAILS
OR BOND BEAMS, TYP

SA-480530
JAMB ZONE W1 L1 PIER ZONE = PIER WIDTH, PW L2 JAMB ZONE W2
CLUSTER OF
B SEE NOTE 3 CLEAR OPENING SEE NOTE 4 CLEAR OPENING SEE NOTE 3 PENETRATIONS

CMU WALL WITH LINTEL

400 MAX
NOTES:

H
1. SEE ARCHITECTURAL DRAWINGS FOR THE EXACT LOCATION OF MASONRY WALL OPENINGS.
2. W1 AND W2 REFERS TO WIDTH OF JAMB ZONE BASED ON ADJACENT CLEAR OPENING L1 AND L2,
RESPECTIVELY AS PER TYPICAL CMU NON-BEARING WALL JAMB AND PIER ZONE SCHEDULE (A1 ON SS513).
3. PIER ZONE REFERS TO MINIMUM WIDTH OF PIER AS SCHEDULED ON TYPICAL CMU NON-BEARING WALL JAMB
AND PIER ZONE SCHEDULE (A1 ON SS513).
4. SEE TYPICAL CMU NON-BEARING WALL JAMB AND PIER ZONE SCHEDULE FOR REINFORCEMENT (A1 ON SS513).

L, 400 MAX CLR DISTANCE GREATER OF


2/11/2022 2:28:25 PM

3 x L OR 3 x H MIN
A SHEET ID
TYPICAL CMU NON-BEARING WALL PLAN
$
DETAIL AT ADJACENT WALL OPENINGS TYPICAL MASONRY WALL PENETRATIONS
A1 1 : 12 A6 1 : 12 UNLESS OTHERWISE NOTED, LINEAR SS514
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

T/WALL

SEE TYPICAL BOTTOM OF SUPPORT US Army Corps of


TOP BRACE DETAIL A4 SEE PLAN Engineers ®
Middle East District
G
GROUT TOP COURSE SOLID

DATE
WALL REINFORCEMENT WALL REINFORCEMENT CL WALL/CL DOWEL UON
PROVIDE HORIZONTAL SEE SCHEDULE D6 ON SS513 SEE SCHEDULE D6 ON SS513
REINFORCMENT
BOND BEAM (SEE SCHEDULE D6 ON SS513) DOWELS TO MATCH VERTICAL
IN TOP JOINT
REINFORCEMENT SPACING
DOWELS TO MATCH VERTICAL DOWELS TO MATCH VERTICAL NOT TO EXCEED MAX DOWEL
REINFORCEMENT SPACING REINFORCEMENT SPACING SPACING PER EDGE OF SLAB
TYPICAL HORIZONTAL NOT TO EXCEED 1200 OC NOT TO EXCEED 1200 OC, DOWEL SCHEDULE
REINFORCEMENT
SEE SCHEDULE
D6 ON SS513 TYPICAL VERTICAL REINFORCEMENT
HORIZONTAL REINFORCEMENT MIN 1Ø12 CONTINUOUS NOSING BAR
SEE SCHEDULE D6 ON SS513
SEE TYPICAL CMU NON-BEARING
WALL SECTION HORIZONTAL REINFORCEMENT

DESCRIPTION
SEE NOTE 1 SEE TYPICAL CMU NON-BEARING
F WALL SECTION

LAP SPLICE

LAP SPLICE

LAP SPLICE
Ø12 CONTINUOUS Ø12 HAIRPIN
DRILLED-IN DOWELS WITH
MINIMUM Ø12@300 HOOKED BARS AT
STANDARD HOOK ADHESIVE ANCHORS
EDGE CONDITIONS

T/SLAB T/SLAB T/SLAB

100

100
EL SEE PLAN EL SEE PLAN EL SEE PLAN
SEE TYPICAL WALL ELEVATIONS FOR
CRITERIA

MARK
THICKENED SLAB THICKENED SLAB THICKENED SLAB
SLAB REINFORCEMENT SEE PLAN AT SLAB-ON-GROUND SLAB REINFORCEMENT SEE PLAN AT SLAB-ON-GROUND AT SLAB-ON-GROUND
E
CAST-IN DOWELS - OPTION 1 DRILLED-IN DOWELS - OPTION 2 TYPICAL DETAIL AT EDGE OF SLAB

PLOT SCALE: PLOT DATE:


SEE PLAN AND TYPICAL DETAILS
(INTERIOR WALL) (INTERIOR WALL)

2:28:26 PM
FOR SLAB REINFROCEMENT

2/11/2022
SOLICITATION NO.:

SA-480530-1$-SS515DT.dwg
CONTRACT NO.:
T/SLAB

ISSUE DATE:
NOTES:

1:1
1. DETAILS ONLY APPLY WHEN ALL OF THE FOLLOWING CONDITIONS ARE MET:
-VERTICALLY SPANNING NON-STRUCTURAL WALL BRACED AT TOP
- NORMAL WEIGHT CONCRETE CLASS
SEE TYPICAL BASE OF WALL DETAILS (A1 AND D4) 2. REFER TO SLAB-ON-GROUND DETAILS FOR INFORMATION AND REINFORCEMENT

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


AT THICKENED SLAB-ON-GROUND.

FILE NO.:
NOTES:

SUBMITTED BY:
1. SEE TYPICAL CMU SILL AND LINTEL SCHEDULE (NON-BEARING) FOR

A. ALHMOOD
ADDITIONAL INFORMATION ON SS513.

DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
SIZE:
TYPICAL BASE OF CMU NON-BEARING WALL
TYPICAL CMU NON-BEARING WALL SECTION DETAIL AT CONCRETE SLAB

TRANSATLANTIC MIDDLE EAST DISTRICT


D1 NTS D4 1 : 12

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
VERTICAL REINFORCEMENT
SEE SCHEDULE

200
(2) - 6mm CONCRETE SCREW (2) - 6mm CONCRETE SCREW BOND BEAM REINF WITH 2Ø16
ANCHOR W/ 75mm ANCHOR W/ 75mm
EMBEDMENT EMBEDMENT 250x200mm CIP LINTEL
C CL CMU NOTE: CL CONC

200
NOTE: BEAM BETWEEN CONC
WALL EACH SCREW MUST RESIST WALL EACH SCREW MUST RESIST
PARTITION TOP ANCHOR (PTA) W/ PARTITION TOP ANCHOR (PTA) W/ COLUMNS
3kN OF ULTIMATE LATERAL 3kN OF ULTIMATE LATERAL
9.5mm DIA X 150mm @ 1200 mm OC SHEAR LOAD. 9.5mm DIA X 150mm @ 1200 mm OC SHEAR LOAD. 2Ø16 CONT T&B DOWELED INTO
CL
GALVANIZED STEEL ROD INSERTED GALVANIZED STEEL ROD INSERTED CONCRETE COLUMNS
REINF CMU WALL, 250
INTO PARTITION TOP ANCHOR TUBE INTO PARTITION TOP ANCHOR TUBE
(PTA) W/ COMPRESSIBLE FILL. RE: ARCH DWGS FOR
(PTA) W/ COMPRESSIBLE FILL

2600 MAX
OPENING
LOCATION OF NON-LOAD Ø12@90 STIRRUPS
(PTA) TO BE PLACED WITHIN CONC BEAM BEARING CONC PARTITIONS
MORTAR JOINT CONC BEAM
40 MAX

40 MAX
25 MIN

25 MIN

CONCRETE UNIT MASONRY DETAILS - SHEET 3 OF 4


OR SLAB

LAP SPLICE

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


BOND BEAM W/ REINF, SEE SCHEDULE VERT REINF,
D6 ON SS513 AT FIRST COURSE SEE SCHEDULE
CONC SLAB ON GRADE

THAAD STANDARD FACILITIES


D6 ON SS513

VARIOUS LOCATIONS, KSA


PROVIDE HORIZONTAL JOINT PROVIDE HORIZONTAL JOINT OVER BLINDING CONC

FULLY GROUT
REINFORCEMENT IN TOP JOINT REINFORCEMENT IN TOP JOINT

STANDARD DETAILS
CELLS
400
BOND BEAM REINF WITH 2Ø16
OPEN BLOCK (HOLLOW) CMU WALL SEE TYPICAL CMU NON-BEARING WALL REINF CMU WALL

SA-480530
ELEVATIONS FOR INFORMATION
B
HOOK AS REQD. DOWELS TO MATCH SIZE
AT ELEVATED AND SPACING OF WALL
FRAMING VERTICAL REINF.
CONC FOUNDATION WALL OR
ELEVATED CONC BEAM
TYPICAL CIP LINTEL SECTION AT MASONRY WALL OPENING
TOP TOP BOTTOM
NOTES:
1. MASONRY LINTELS MUST BE SHORED DURING CONSTRUCTION AND MUST REMAIN SHORED UNTIL MASONRY
HAS GAINED 100% OF FULL SPECIFIED STRENGTH (f'm)
2. DESIGN BASED ON DESIGN SERVICE LOAD PRESSURE NOTED AS 1.44 kPA, UNLESS OTHERWISE NOTED
3. SEE TYPICAL CMU NON-BEARING WALL ELEVATIONS FOR ADDITIONAL INFORMATION.
2/11/2022 2:28:26 PM

TYPICAL CMU NON-BEARING WALL TYPICAL CMU NON-BEARING WALL CIP


A
ATTACHMENT TO CONC BEAM OR SLAB LINTEL DETAIL
SHEET ID
A3 NTS A8 NTS $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS515
1 2 3 4 5 6 7 8 9 10

10mm JOINT FILLER-SPECCHEM CONTROL JT


FIBER EXPANSION JT

US Army Corps of
Engineers ®
Middle East District
G WALL DOWELS

DATE
STEEL COLUMN IJ(TYP)
TYP
E1
SS516

T/SLAB

DESCRIPTION
TYP WALL REINF,
F DO NOT DOWEL
REBAR ACROSS JT

CMU WALL
CONTROL JT
EXTENT OF JT FILLER, SEE PLAN
EXTENT OF JT

FILLER BELOW CMU WALL JT ELEVATION @ COLUMN


LOCATION
ENLARGED TYP PLAN - CMU WALL JT @ E6 NTS
CENTERLINE JOINT
COLUMN LOCATION (CONTINUOUS WITH
E1 NTS JOINT IN WALL)

MARK
SEALANT
GROUT SOLID
E BACKER ROD

THICKNESS

PLOT SCALE: PLOT DATE:


(T)

2:28:27 PM
T/2

2/11/2022
SOLICITATION NO.:

SA-480530-1$-SS516DT.dwg
CONTRACT NO.:
CENTERLINE JOINT FOR EXTERIOR WALLS PROVIDE CONTROL

ISSUE DATE:
JOINTS AT A DISTANCE OF L/4 FROM 20 DIA x 300 LONG GREASED DOWEL
CORNERS OF EXTERIOR WALLS. HORIZONTAL AS ALTERNATIVE PROVIDE 600

1:1
GROUT SOLID REINF (TYP) LONG Ø16 REBAR; 1 END PLACED
SEALANT FOR INTERIOR WALLS, PROVIDE CONTROL STOP HORIZ
VERTICAL REINF REINF AT JOINT IN PLASTIC SLEEVE OR
JOINTS AT A DISTANCE OF L/4 FROM
BACKER ROD DEBONDED BY OTHER MEANS
INTERSECTIONS WITH EXTERIOR WALLS.
TYPICAL VERTICAL CONTROL JOINT

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


WHERE L = LENGTH OF WALL SEGMENT

FILE NO.:
NOTES:

SUBMITTED BY:
1. JOINTS NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS MUST BE APPROVED THE

A. ALHMOOD
DESIGN BY:

DRAWN BY:
STRUCTURAL ENGINEER OF RECORD. CONTROL JOINTS ARE NOT ALOWED OVER

A. HANKS
D HORIZONTAL PREFORMED GASKET OPENINGS.

CKD BY:

ANSI D
JOINT REINF (TYP) FOR 2-HOUR FIRE RATING 2. REFER TO SCHEDULE D6 ON SS513 FOR HORIZONTAL REINF SIZE AND QUANTITY.

SIZE:
3. VERTICAL REINF NOT SHOWN FOR CLARITY.
STOP HORIZ
REINF AT JOINT TYPICAL CONCRETE MASONRY BOND BEAM

TRANSATLANTIC MIDDLE EAST DISTRICT


CONTROL JOINT

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


TYPICAL VERTICAL CONTROL JOINT
C6

WINCHESTER, VA 22602
NOTES: NTS
1. JOINTS NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS MUST
BE APPROVED THE STRUCTURAL ENGINEER OF RECORD.
2. REFER TO SCHEDULE D6 ON SS513 FOR HORIZONTAL REINF SIZE
AND QUANTITY.
50
CONCRETE BEAM OR SLAB

TYPICAL CONCRETE MASONRY CONTROL


C JOINT 150 CMU
C1 NTS

GFRC, SEE
ARCH DWGS

150 LINTEL WITH (1)Ø16 CONT,

CONCRETE UNIT MASONRY DETAILS - SHEET 4 OF 4


FULLY GROUT CELL ABOVE BOND

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


BEAM

CONCRETE COLUMN

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
(2) VERTICAL BARS 200 CMU BEYOND

STANDARD DETAILS
OPENING

SA-480530
B BOND BEAM BAR (TYP)
150 BOND BEAM WITH (1)Ø16 CONT

GFRC, SEE
ARCH DWGS NOTES:
1. SEE TYPICAL CMU LINTEL SCHEDULE
FOR ADDITIONAL INFORMATION.

LAP SPLICE Ø10 BARS @


ISOLATION JOINT W/ 25 OF EA BOND BEAM
COMPRESSIBLE MATERIAL
2/11/2022 2:28:27 PM

A SHEET ID
ENLARGED TYP PLAN - CMU WALL TYPICAL RECESSED CMU SILL AND LINTEL
$
INTERSECTION AT CONCRETE COLUMN (NON-BEARING WALL)
A1 NTS A6 NTS UNLESS OTHERWISE NOTED, LINEAR SS516
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

LW CONCRETE
SCREED

US Army Corps of
Engineers ®
Middle East District
G

DATE
⌀20mm EXPANSION ANCHOR, CONCRETE
EMBEDMENT DEPTH 120mm. ROOF SLAB
NOTE:
EACH ANCHOR MUST RESIST
3kN OF ULTIMATE TENSION LOAD.

1500 MAX

DESCRIPTION
F
COORDINATE WITH EXISTING UTILITIES
1500 MAX

⌀20mm ROD @ 3000mm MAX

MARK
BUSWAY SUPPORT,
COORDINATE PER
BUSWAY
E MANUFACTURER'S
RECOMMENDATION

PLOT SCALE: PLOT DATE:


2:28:28 PM
2/11/2022
SOLICITATION NO.:

SA-480530-1$-SS517DT.dwg
CONTRACT NO.:
ISSUE DATE:
P1047 - U SHAPE FITTING

1:1
NOTES:
1. REFER TO SE003 FOR ELECTRICAL GENERAL NOTES.
2. REFER TO SE001 & SE002 FOR ELECTRICAL ABBREVIATIONS &

K. TEEMSMA & X. CHEN

K. TEEMSMA & X. CHEN


LEGEND.

FILE NO.:
3. CONTRACTOR SHALL SUBMIT BUSWAY ROUTING PLAN AND SHOP
DRAWINGS FOR GOVERNMENT SPPROVAL.

SUBMITTED BY:
4. BUSWAY SHALL BE 3200A (200KAIC), FOR 4-WIRE WITH INTEGRAL

A. ALHMOOD
DESIGN BY:

DRAWN BY:
GROUND.

A. HANKS
D

CKD BY:
2 - P5501 @ 3000mm MAX 5. CONTRACTOR SHALL SUBMIT DESIGN CALCULATIONS AND SHOP

ANSI D
SIZE:
DRAWINGS FOR BUSWAY SUPPORT. DESIGN CALCULATIONS AND
SHOP DRAWINGS SHALL BE STAMPED AND SIGNED BY THE
CONTRACTOR'S ENGINEER AND SUBMITTED FOR GOVERNMENT
APPROVAL.

TRANSATLANTIC MIDDLE EAST DISTRICT


HORIZONTAL BUSWAY SUPPORT HANGER DETAIL

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


D1 NTS

WINCHESTER, VA 22602
WALL

C ALL 4 SIDES

50

BUSWAY 25

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)

ELECTRICAL BUSWAY SUPPORT DETAIL


WALL OPENING

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA

STANDARD DETAILS
SA-480530
B

WALL FLANGE

NOTE:
1. WALL OPENINGS FOR BUSWAY SHOULD BE AT LEAST 25mm
LARGER THAN OUTSIDE DIMENSION OF BUSWAY
2/11/2022 2:28:28 PM

BUSWAY WALL PENETRATION DETAIL


A A1 NTS SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SS517
1 2 3 4 5 6 7 8 9 10

GENERAL ARCHITECTURAL NOTES: SHEETS AE150 THRU AE159 GENERAL ARCHITECTURAL NOTES: GENERAL ARCHITECTURAL NOTES
REFLECTED CEILING PLAN NOTES, LEGEND AND SYMBOLS ROOF PLAN NOTES. LEGENDS AND SYMBOLS LEGEND AND SYMBOLS NOTES US Army Corps of
Engineers ®

LEGEND AND SYMBOLS NOTES 1. REFER TO SG004 FOR, LEGENDS AND SYMBOLS. REFER TO 21. FIRE-RESISTIVE (LABELED) DOORS SHALL HAVE THE Middle East District
G NOTES SA005 FOR TYPICAL MOUNTING HEIGHTS. APPROPRIATE UL OR OTHER RATING AGENCY LABEL
ACCEPTABLE TO GOVERNMENT AUTHORITIES AFFIXED TO

XXX
1. STROBES SHALL BE LOCATED AT +2000 mm AFF. SEE 1. REFER TO MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS FOR 2. VERIFY EACH DIMENSION AND CONDITIONS IN FIELD PRIOR BOTH THE DOOR AND THE FRAME.
TO START OF WORK. NOTIFY CONTRACTING OFFICER IN

DATE
(REFERENCE RCP AND FINISH ENGINEER'S DRAWINGS FOR LOCATIONS AND ADDITIONAL ROOF ELEMENT INFORMATION. DOOR AND TAG, SEE
SPECIFICATIONS. DOOR SCHEDULE WRITING OF ANY WORK DESCRIBED IN THE CONTRACT 22. DISSIMILAR METALS SHALL BE EFFECTIVELY ISOLATED
LEGEND AND FINISH
DOCUMENTS WHICH CANNOT BE PERFORMED DUE TO FROM EACH OTHER TO AVOID GALVANIC ACTION BY
MATERIALS SCHEDULE FOR ADDITIONAL
2. STROBES TO ALIGN VERTICALLY WITH RECEPTACLES EXISTING CONDITIONS. PAINTING CONTACT SURFACE WITH MATERIALS
TYPES NOT SHOWN)
AND/OR SWITCHES BELOW WHERE OCCURS. MET. STUD / GWB PARTITION RECOMMENDED BY METAL MANUFACTURER FOR THIS
3. PRIOR TO PROCEEDING WITH ANY WORK, THE PURPOSE OR BY INSTALLING NONCONDUCTIVE SPACERS.
3. CONTRACTING OFFICER'S REPRESENTATIVE TO REVIEW CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH WHERE ALUMINUM IS IN CONTACT WITH CONCRETE OR
600 x 600 GRID AND CMU PARTITION
ALL LIGHT/CEILING FIXTURE LOCATIONS PRIOR TO EXISTING CONDITIONS. DURING THE PROCESS OF MASONRY, PROTECT AGAINST CORROSION BY PAINTING
TILE SYSTEM
INSTALLATION. CONSTRUCTION, IT SHALL BE THE CONTRACTORS SURFACES WITH BITUMINOUS PAINT.
RESPONSIBILITY TO MAINTAIN THE INTEGRITY OF EXISTING
CAST-IN-PLACE CONCRETE
4. INSTALL THE SUSPENDED CEILING GRID TO BE LEVEL WORK WHERE EXISTING WORK IS MODIFIED TO 23. CONTRACTOR SHALL PROVIDE AND COORDINATE
PARTITION
WITHIN A TOLERANCE OF 1 IN 1200 mm. ANCHOR AS ACCOMMODATE NEW CONSTRUCTION AND TO PROTECT TEMPORARY INTERIOR AND EXTERIOR BUILDING SIGNAGE
REQUIRED. FROM DAMAGE THOSE PORTIONS OF EXISTING WORK, WITH CONTRACTING OFFICER.
PXX PARTITION TYPE TAG, REFER TO SHEETS WHICH ARE TO REMAIN.
600 x 1200 GRID AND SA602, SA603, AND SA604 FOR TYPES 24. PROVIDE STEP FLASHING WITH FULL HEIGHT END DAMS
TILE SYSTEM 5. CONTRACTING OFFICER'S REPRESENTATIVE TO REVIEW
4. DO NOT SCALE THE DRAWINGS. THE DRAWINGS MAY NOT INSTALLED BETWEEN FLASHING LEVELS TO ENSURE

DESCRIPTION
LOCATIONS OF ALL SLOT DIFFUSERS, SPRINKLERS, AXX TOILET ACCESSORY TAG
F SMOKE DETECTORS, ETC. IN GYP BD CEILINGS PRIOR TO BE TO SCALE. WRITTEN DIMENSIONS SHALL TAKE CONTINUITY OF FLASHING AT GRADE CHANGES
INSTALLATION BY SHOP DRAWING REVIEW. PRECEDENCE OVER SCALED MEASUREMENTS.
GYPSUM BOARD CEILING, EQXX EQUIPMENT TAG 25. REFER TO SA651 FOR EXTERIOR FINISH LEGEND. REFER
SOFFIT AND/OR BULKHEAD 5. WORK SHOWN ON THE DRAWINGS IS ASSUMED TO BE TO SI601 FOR INTERIOR FINISH LEGEND.
6. REFLECTED CEILING PLANS INDICATED CEILING TYPE
AS INDICATED ON PLAN. NEW, FURNISHED AND INSTALLED BY THE CONTRACTOR
AND DESIGN INTENT; REFER TO MECHANICAL, PLUMBING, W# WINDOW TAG
REFER TO INTERIOR UNLESS NOTED OTHERWISE. 26. THE GROSS BUILDING AREA CALCULATION INDICATED ON
FIRE PROTECTION, TELECOM AND ELECTRICAL
FINISH LEGEND ON SHEET THE DRAWINGS INCLUDES:
DRAWINGS FOR ADDITIONAL WORK AND COORDINATE.
SI601 FOR PAINT 6. ABBREVIATION LIST, SYMBOLS LEGEND, AND MATERIAL A. THE AREA MEASURED TO THE OUTSIDE FACE OF THE
SPECIFICATIONS L# LOUVER TAG LEGEND ARE PROVIDED FOR INFORMATION ONLY - EXTERIOR WALLS, EXCLUSIVE OF VENT SHAFTS AND
7. WHERE ACOUSTICAL PANELS ARE REQUIRED TO BE
CUT, CUT THE PANELS TO MAINTAIN A SHARP AND NEAT INCLUSION OR OMISSION FROM THE LIST OR LEGENDS COURTS.
EDGE. DOES NOT IMPLY THAT THE REFERENCED ITEM(S) ARE B. THE AREA OF THE BUILDING WITHIN THE HORIZONTAL
S SMOKE PARTITION INCLUDED OR EXCLUDED FROM THE CONTRACT PROJECTION OF THE ROOF OR FLOOR ABOVE.
DECORATIVE METAL 8. INSTALL LIGHT FIXTURES IN THE CENTER OF THE DOCUMENTS AND/OR PROJECT SCOPE OF WORK.
PANEL CEILING SYSTEM. ACOUSTICAL CEILING PANEL AND/OR CENTERED IN THE FIRE BARRIER - 1/2 HR
REFER TO INTERIOR ROOM AS INDICATED, UNO. 7. WHERE SPECIFIC DIMENSIONS, DETAILS OR DESIGN
FINISH LEGEND ON SHEET FIRE BARRIER - 1 HR INTENT CANNOT BE DETERMINED, CONSULT THE
SI601. 9. ACOUSTICAL CEILING TILES TO BE INSTALLED CONTRACTING OFFICER PRIOR TO PROCEEDING WITH THE

MARK
CENTERED IN ROOMS, UNO. FIRE BARRIER - 2 HR WORK.

E 10. REFER TO FINISH SCHEDULE FOR CEILING TYPES AND 8. IF A CONFLICT EXISTS WITHIN THE DRAWINGS AND/OR
SPECIFICATIONS, THE MORE STRINGENT AND MORE
FINISHES. XXX mm FINISH FLOOR HEIGHT AS
INDICATED ON PLAN, UNO COSTLY REQUIREMENT SHALL APPLY. ITEMS SHOWN ON

PLOT SCALE: PLOT DATE:


DRAWINGS, BUT NOT SPECIFIED, SHALL APPLY AND BE

2/9/2022 4:22:22
FURNISHED AND INSTALLED BY THE CONTRACTOR. IF AN
ANNOTATIONS FIRE ALARM (REFERENCE SF001 FOR LEGEND AND SYMBOLS FD
FLOOR DRAIN, SEE ITEM IS SHOWN ON THE DRAWINGS, BUT IS NOT INCLUDED

SOLICITATION NO.:

SA-480530-1$-SA001GN.dwg
ADDITIONAL TYPES NOT SHOWN) PLUMBING IN THE SPECIFICATIONS, PROVIDE ITEM OF A QUALITY

PM
FINISHED CEILING HEIGHT AS

CONTRACT NO.:
XXX mm LEVEL CONSISTENT WITH THE GENERAL QUALITY LEVEL
INDICATED ON PLAN UNO. ELECTRIC WATER COOLER

ISSUE DATE:
OF THE CONTRACT REQUIREMENTS. BRING CONFLICTS
EXIT SIGN, ARROW INDICATES XX/1000 WITH INTEGRAL BOTTLE BETWEEN DRAWINGS AND SPECIFICATIONS TO THE
SLOPE OF ROOF FILLER, SEE PLUMBING

1:1
CEILING MATERIAL FINISH CODE PATH OF TRAVEL ATTENTION OF THE CONTRACTING OFFICER IMMEDIATELY
ACT-1 SCHEDULES FOR TYPE. FOR CLARIFICATION.
3000 HEIGHT OF CEILING MATERIAL EJ
S SMOKE DETECTOR ? TYP
EXPANSION JOINT (TYP) SIGNAGE TAG 9. WRITTEN INFORMATION TAKES PRECEDENCE OVER
DRAWN LINES. BRING CONFLICTS BETWEEN WRITTEN
LIFE ALARM SPEAKER / STROBE EXTENTS OF FINISH INFORMATION AND DRAWN LINES TO THE ATTENTION OF

FILE NO.:
c RS-X ROOF SYSTEM TYPE THE CONTRACTING OFFICER IMMEDIATELY.

SUBMITTED BY:
WALL FINISH CODE

J. BLANCHARD
S
LIFE ALARM / MASS GL-1 10. IF AN AREA OR SPACE IS SHOWN, BUT IS NOT CLEARLY

J. HOLLAND
DESIGN BY:

DRAWN BY:
NOTIFICATION SPEAKER
DEFINED OR INDICATED BY NOTES, PROVIDE THE SAME

A. HANKS
D LIGHT FIXTURES (REFERENCE SE001 FOR HEAT AND SMOKE VENT (TYP)

S. OKES
CKD BY:
MATERIALS, FINISHES AND QUALITY OF CONSTRUCTION AS

ANSI D
ADDITIONAL TYPES NOT SHOWN) CD

SIZE:
LIFE ALARM STROBE GL-1 SPECIALTY MATERIAL FINISH CODE SCHEDULED OR DETAILED FOR AREAS OF SIMILAR USE
600 x 600 RECESSED SEMI- ELSEWHERE IN THE WORK.
INDIRECT LED FIXTURE
ROOF HATCH (TYP)

TRANSATLANTIC MIDDLE EAST DISTRICT


11. NOTES ON DRAWINGS SHALL APPLY TO SIMILAR
GL-1 FLOOR MATERIAL FINISH CODE
(REFERENCE SM001 FOR CONDITIONS WHETHER REPEATED OR NOT.

US ARMY CORPS OF ENGINEERS


600 x 600 RECESSED SEMI- HVAC

201 PRINCE FREDERICK DRIVE,


INDIRECT LED FIXTURE ADDITIONAL TYPES NOT SHOWN)
12. DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER TO
(EMERGENCY)

WINCHESTER, VA 22602
OTHER TYPICAL DETAILS PROVIDED THROUGHOUT THE

?
CEILING SUPPLY DIFFUSER OR PIPE PENETRATION (TYP) CHANGE IN FLOOR FINISH DRAWING SET, EVEN IF NOT SPECIFICALLY REFERENCED.
600 x 1200 RECESSED SEMI-
13. CONTRACTOR SHALL VERIFY FLOOR ELEVATIONS PRIOR
INDIRECT LED FIXTURE FLOOR MATERIAL FINISH CODE

?
TO BEGINNING WORK. CONTRACTOR SHALL VERIFY SLAB
CEILING RETURN REGISTER POWER ROOF EXHUAST DEPRESSION REQUIREMENTS FOR FLOOR FINISHES PRIOR
TO BEGINNING WORK.
600 x 1200 RECESSED SEMI- FURNITURE ITEM CODE LISTED IN
INDIRECT LED FIXTURE COMPREHENSIVE INTERIOR DESIGN 14. REFER TO MECHANICAL, PLUMBING, FIRE PROTECTION
(EMERGENCY) (CID) PACKAGE AND ELECTRICAL DRAWINGS FOR LOCATIONS AND
CEILING EXHAUST REGISTER
DESCRIPTIONS OF ACCESS PANELS, LOUVER OPENINGS,
C 300 x 1200 RECESSED SEMI-
? (4) QUANTITY IN ROOM OR AREA
VENTILATORS, GRILLES, VALVE CABINETS, FIRE DAMPERS
INDIRECT LED FIXTURE FURNITURE ITEM VARIATION OR OTHER APPURTENANCES AFFECTING WALLS, CEILINGS
CEILING EXHAUST GRILL OR FLOORS. PROVIDE NECESSARY LINTELS, SUPPORT AND
300 x 1200 RECESSED SEMI- ROOF TOP UNIT (TYP) FURNITURE ITEM ID ANCHORAGE. SEE STRUCTURAL DRAWINGS FOR LINTEL
INDIRECT LED FIXTURE FURNITURE CATEGORY REQUIREMENTS.
(EMERGENCY)
(REFERENCE ST001 AND SY001 FOR 15. PLACEMENT OF BLOCKING AND GROUNDS IS THE
ROUND RECESSED DOWNLIGHT TELECOM RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE
ADDITIONAL TYPES NOT SHOWN)
ROUND RECESSED DOWNLIGHT CONFIRMED TO BE OF PROPER SIZE AND SECURED AT
(EMERGENCY) S1 CEILING SPEAKER APPROPRIATE LOCATIONS PRIOR TO CLOSING OF THE

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


WALLS. WOOD BLOCKING AND GROUNDS SHALL BE FIRE
RETARDANT TREATED LUMBER.
SECURITY CAMERA, FIXED

GENERAL NOTES AND LEGENDS


ROOF CONDENSING UNIT (TYP) 16. PROVIDE CONTINUOUS BLOCKING AT METAL STUD

THAAD STANDARD FACILITIES


DIRECT / INDIRECT TRI-SPOKE

VARIOUS LOCATIONS, KSA


FRAMING WITH WALL MOUNTED EQUIPMENT AND
FIXTURE PTZ SECURITY CAMERA, PAN-TILT-ZOOM CASEWORK

STANDARD DETAILS
17. MOUNT ELECTRICAL SWITCHES, THERMOSTATS AND

SA-480530
LIGHTNING PROTECTION AIR OTHER ELECTRONIC CONTROLS LOCATED IN THE SAME
B DECORATIVE WING SHAPED
FIRE PROTECTION (REFERENCE SF001 FOR
ADDITIONAL TYPES NOT SHOWN)
TERMINAL, SEE ELECTRICAL VICINITY AT THE SAME HEIGHT ABOVE FINISH FLOOR
PENDANT DRAWINGS FOR DETAILS ELEVATION IN A UNIFORM, ORDERLY FASHION UNLESS
NOTED OTHERWISE.
SPRINKLER HEAD
18. INSTALL ELECTRICAL SWITCHES, OUTLETS,
THERMOSTATS, CONTROLS, SPEAKERS AND OTHER WALL-
MOUNTED ACCESSORIES IN LOCATIONS WHICH ARE
SENSORS UNOBSTRUCTED BY CABINETS, COUNTERS, RACKS,
DISPLAY BOARDS, FIXTURES, SHELVING OR OTHER
FURNISHINGS OR EQUIPMENT DESIGNATED FOR SPACES
SHOWN ON DRAWINGS.

19. EACH APPURTENANCE BUILT INTO OR THROUGH WALLS,


SQUARE RECESSED DOWNLIGHT INCLUDING DOORS, WINDOWS, DUCTS, LOUVERS, GRILLES,
SQUARE RECESSED DOWNLIGHT PIPING, MECHANICAL WORK, ETC. SHALL FIT TIGHTLY AND
(EMERGENCY) BE THOROUGHLY SEALED AROUND PERIMETERS. USE
2/9/2022 4:22:22 PM

FIRESTOPPING SYSTEMS THAT HAVE RATINGS THAT MEET


REQUIREMENTS OF ASSEMBLIES BEING PENETRATED.
A SHEET ID
20. RATINGS ARE TO COMPLY WITH UNDERWRITERS
LABORATORIES (UL) TEST RATINGS. IN THE ABSENCE OF A $
TESTED ASSEMBLY, PROVIDE CERTIFICATE OF
EQUIVALENCY FROM UL FOR BOTH CONSTRUCTION AND
FIRE PROTECTION. SA001
1 2 3 4 5 6 7 8 9 10

ARCHITECTURAL CODES AND CRITERIA GENERAL SHEET NOTES


1. UNITED STATES ARMY CORPS OF ENGINEERS CRITERIA - DESIGN INSTRUCTION 1. REFER TO SHEET SG003 IN THE SFDN PACKAGE FOR ABBREVIATIONS.
MANUAL APRIL 2019 VERSION.
2. REFER TO SA001 IN THE SFDN PACKAGE FOR GENERAL ARCHITECTURAL US Army Corps of
2. LEADERSHIP IN ENERGY AND ENVIRONMENTAL DESIGN (LEED) - NOT NOTES, LEGEND AND SYMBOLS. Engineers ®
APPLICABLE. Middle East District
G 3. ACCESSIBILITY - PROVISIONS FOR PHYSICALLY HANDICAPPED INDVIDUALS IS
3. THIS SHEET IS SPECIFIC FOR THE FOLLOWING FACILITIES - A, B, C, D, E, F, G, AL,
AK, AM.
NOT REQUIRED. BUILDING IS DESIGNED FOR ACTIVE DUTY SERVICE MEMBERS
PER DESIGN INSTRUCTION MANUAL APRIL 2019 EDITION ARTICLE 7.1.8.

DATE
4. US DEPARTMENT OF DEFENSE CRITERIA - UNIFIED FACILITIES CRITERIA
A. 1-200-01 DOD BUILDING CODE, 8 OCT 2019 CHANGE 1, 1 OCT 2020
B. 1-202-01 HOST NATION FACILITIES IN SUPPORT OF MILITARY OPERATIONS, 01
SEP 2013
C. 3-101-01 ARCHITECTURE, 28 NOV 2011 CHANGE 5, 25 SEP 2019
D. 3-110-03 ROOFING, 1 MAY 2012 CHANGE 5, 12 JUN 2020
E. 3-120-01 DESIGN: SIGN STANDARDS, WITH CHANGE 3
F. 3-120-10 INTERIOR DESIGN, 16 MAY 2018

5. INTERNATIONAL BUILDING CODE, 2018

6. FORCE PROTECTION CRITERIA


A. 4-010-01 DOD ANTI TERRORISM STANDARDS FOR BUILDINGS

DESCRIPTION
7. LIFE SAFETY CODE - NFPA 101 LIFE SAFETY CODE.
F

MARK
E

PLOT SCALE: PLOT DATE:


2/9/2022 4:22:25
SOLICITATION NO.:

SA-480530-1$-SA002GN.dwg
PM
CONTRACT NO.:
ISSUE DATE:

1:1
FILE NO.:
SUBMITTED BY:
J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:

A. HANKS
D

S. OKES
CKD BY:

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
C

CRITERIA FOR UNIFIED FACILITY CRITERIA FACILITIES


GENERAL NOTES, ARCHITECTURAL CODES AND
ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
THAAD STANDARD FACILITIES
VARIOUS LOCATIONS, KSA

STANDARD DETAILS
SA-480530
B
2/9/2022 4:22:25 PM

A SHEET ID
$

SA002
1 2 3 4 5 6 7 8 9 10
ARCHITECTURAL CODES AND CRITERIA GENERAL SHEET NOTES
1. UNITED STATES ARMY CORPS OF ENGINEERS CRITERIA - DESIGN INSTRUCTION 1. REFER TO SHEET SG003 IN THE SFDN PACKAGE FOR ABBREVIATIONS.
MANUAL APRIL 2019 VERSION.
2. REFER TO SA001 IN THE SFDN PACKAGE FOR GENERAL ARCHITECTURAL US Army Corps of
2. BUILDING CODE - SAUDI BUILDING CODE GENERAL SBC 201 - CR CODE NOTES, LEGEND AND SYMBOLS. Engineers ®
REQUIREMENTS 2018. Middle East District
3. THIS SHEET IS SPECIFIC FOR THE FOLLOWING FACILITIES - H, I, J, K, L, M, O, P,
G 3. ENERGY CODE - SAUDI ENERGY CONSERVATION CODE BUILDING EXCEPT LOW- Q, S, T, R, U, V, W, Y, X, Z, AA, AB, AC, AD, AG, AF, AE, AH, V, AI.
RISE (RESIDENTIAL) BUILDING - SBC 601 - CR, CODE REQUIREMENTS 2018.
4. NON-STRUCTURAL COMPONENTS DO NOT REQUIRE SEISMIC BRACING.

DATE
4. LEADERSHIP IN ENERGY AND ENVIRONMENTAL DESIGN (LEED) - NOT
APPLICABLE.

5. ACCESSIBILITY - PROVISIONS FOR PHYSICALLY HANDICAPPED INDVIDUALS IS


NOT REQUIRED. BUILDING IS DESIGNED FOR ACTIVE DUTY SERVICE MEMBERS
PER DESIGN INSTRUCTION MANUAL APRIL 2019 EDITION ARTICLE 7.1.8.

6. US DEPARTMENT OF DEFENSE CRITERIA - UNIFIED FACILITIES CRITERIA ARE


NOT APPLICABLE.

7. FORCE PROTECTION CRITERIA - NOT APPLICABLE.

8. LIFE SAFETY CODE - NFPA 101 LIFE SAFETY CODE IS NOT APPLICABLE.

DESCRIPTION
F

MARK
E

PLOT SCALE: PLOT DATE:


2/9/2022 4:22:28
SOLICITATION NO.:

SA-480530-1$-SA003GN.dwg
PM
CONTRACT NO.:
ISSUE DATE:

1:1
FILE NO.:
SUBMITTED BY:
J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:

A. HANKS
D

S. OKES
CKD BY:

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
C

CRITERIA FOR SAUDI BUILDING CODE FACILITIES


GENERAL NOTES, ARCHITECTURAL CODES AND
ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
THAAD STANDARD FACILITIES
VARIOUS LOCATIONS, KSA

STANDARD DETAILS
SA-480530
B
2/9/2022 4:22:28 PM

A SHEET ID
$

SA003
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


DIMENSION DESCRIPTION / LOCATION ALTERNATE 1. COMPLY WITH ARCHITECTURAL BARRIERS ACT (ABA
W1 = 915 MIN CLEAR AMBULATORY STALL (NOTE 1) 815 MIN DOOR ACCESSIBILITY REQUIREMENTS FOR ITEMS REQUIRED TO
LOCATION BE ACCESSIBLE. US Army Corps of
W1 = 1525 MIN CLEAR WHEEL CHAIR ACCESSIBLE STALL 100 MAX 2. COORDINATE INSTALLATION OF REQUIRED ACCESSIBLE Engineers ®
1370 MIN

150 MAX
W2 = 1420 MIN CLEAR NON-ACCESSIBLE STALL BIDET HOSE ON RIGHT ITEMS WITH AUTHORITY HAVING JURISDICTION PRIOR TO
Middle East District
W2 = 1525 MIN CLEAR WHEEL CHAIR ACCESSIBLE STALL SIDE OF TOILET INSTALLATION.
G W2 = 1525 MIN CLEAR AMBULATORY
305 MAX 3. FOR ITEMS NOT SHOWN, MOUNT ACCESSIBLE FEATURE AT
380mm MINIMUM AND 1220mm MAXIMUM ABOVE FINISHED
H1 = 865 MIN - 915 MAX ACCESSIBLE GRAB BAR HEIGHT TOP OF SURFACE

100 MAX
815 MIN
FLOOR.

1525 MIN

DATE
4. WHERE DIMENSIONS ARE DEFINED BY MINIMUM AND

915 MIN
915 MIN

915 MIN

1525 MIN
CL

150 MAX
360 405-455 MAXIMUM, INSTALL AT MIDDLE OF RANGE UNLESS

405-455
BIDET HOSE ON RIGHT CL 900 CEILING INDICATED OTHERWISE.
WIDTH WIDTH SIDE OF TOILET CL 5. INSTALL ALL WALL MOUNTED ACCESSORIES, EQUIPMENT
AND OTHER WALL MOUNTED ITEMS TO PROJECT NOT MORE
(W1) (W2)
PARTITION THAN 100mm INTO CIRCULATION PATH, WHETHER OR NOT
1065 MIN

405-455
1420 MIN
BUILDING IS TO BE COMPLIANT WITH ACCESSIBLE
A19 - 1070mm SIDE 1065 CLEAR FROM 815 MIN REQUIREMENTS.
CLEAR OUTSIDE FACE OF 305 MAX
1370 MIN WALL GRAB BAR 6. MOUNTING AND CLEARANCE INFORMATION DEPICTED FOR
FLOOR ADJACENT STALL 1370 MIN
A18 - 900mm REAR SPACE FIXTURES AND DEVICES ARE FOR BASIS OF DESIGN
WALL GRAB BAR 150 GAP 305 A-05/A-11 - TOILET 1065 MIN WIDTH (W2) PRODUCTS ARE USED, CONTRACTOR TO CONFIRM

3000
MAX TISSUE DISPENSER DOOR DOOR COMPLIANT PLACEMENT REQUIREMENTS WITH AUTHORITY

20 CLEARANCE
610 305 IS FOR REF.
A19 - 1070mm SIDE HAVING JURISDICTION.
1065 MIN WIDTH (W2) CLEAR FROM OUTSIDE
WALL GRAB BAR @ 1525 MIN 7. DIMENSIONS INDICATED ARE FROM FINISHED SURFACES.
LATCH SIDE FACE OF ADJACENT REFER TO A-SERIES, I-SERIES, AND SPECIFICATIONS FOR
AMBULATORY
STALL

HEIGHT

DESCRIPTION
APPROACH ONLY WALL AND FLOOR FINISHES. IF THICKNESS OF FINISH

1220 MAX
F

(H1)
485 MIN
BIDET HOSE ON RIGHT PRODUCT SELECTED FOR INSTALLATION VARIES FROM THE

650
SIDE OF TOILET BASIS OF DESIGN FINISH PRODUCT, COORDINATE
FLOOR LEVEL NOT IN STALL STANDARD STALL STANDARD STALL LOCATIONS OF ACCESSIBLE ITEMS TO BE CONSISTENT WITH
DIMENSIONS INDICATED.

MIN
230
430 MIN /
485 MAX
WATER CLOSET IS FOR CL OPENING 8. PROVIDE GRAB BARS AT ALL WHEEL CHAIR ACCESSIBLE
REF. SEE P-SERIES FOR 405 MIN / AMBULATORY STALL TOILET PARTITION AND ABULATORY TOILET ROOMS.
TYPE 455 MAX 180 MIN / NOTES : 9. PROVIDE PLUMBING PIPE PROTECTION WRAPS /
1. AMBULATORY ACCESSIBLE COMPARTMENTS ARE REQUIRED WHEN THERE ARE 6 OR MORE WATER CLOSETS AND URINALS (BOTH 1. ATTACH TOILET PARTITIONS TO MASONRY WING
REAR WALL ELEV SIDE WALL ELEV 230 MAX COMBINED) IN A TOILET ROOM. AS WITH A WHEELCHAIR ACCESSIBLE COMPARTMENT, A 1065mm WIDE APPROACH IS REQUIRED TO AN WALLS.
UNDERLAVATORY GUARDS AT ALL SINKS AND LAVORTORIES
WITH EXPOSED PIPING.
AMBULATORY COMPARTMENT AS WELL. THE COMPARTMENT IS REQUIRED TO BE A MINIMUM OF 1525mm IN LENGTH AND 915mm WIDE.
10. REFER TO ACCESSORY SCHEDULE AND SPEC SECTIONS
FOR INFORMATION.

1500 MIN

SCHEDULED
330 330 950
MIRROR

MARK
EQ EQ A01/A10/A17

150 ABOVE

305 ABOVE
COUNTER
A16

COUNTER
A01 /A17A
E A03 A06/A20 A12

1220 MIN
A12/A13 A03 SCHEDULED

430 MIN

485 MAX
/A20 A03 AS MIRROR CLEAR

1000 MIN/MAX
A15
SCHED FLOOR

PLOT SCALE: PLOT DATE:


2/9/2022 4:22:34
A03 SCHED A13 SCHEDULED SPACE

150
150

LAV (L-4) LAV


CASEWORK

SOLICITATION NO.:

SA-480530-1$-SA005GN.dwg
1200 MAX
1000 MIN
1220 MAX
1050 TYP
1220 MAX
1065 TYP

KNEE

PM
CONTRACT NO.:
760 MIN
150
865 MAX

865 MAX

850 TYP

UNO
1025
SPACE
1015

300 415

MAX
TO BOT. OF

ISSUE DATE:
865

760
GLASS

300

1:1
FLOOR LEVEL
SCHED LAV SCHEDULED LAV
(L-1) 95 MIN 150 MAX

DESCRIPTION LAVATORY BASIN/BATHROOMS SOAP DISPENSER MIRRORS PAPER TOWEL DISPENSERS

FILE NO.:
NOTES/ 1. INSULATE OR CONCEAL ALL WATER AND DRAIN PIPES. 1. LOCATE CENTERED BETWEEN LAVS AS A01 - MIRROR 600mm X 1200mm A06 - CONCEALED PAPER TOWEL DISPENSER, REFER TO INTERIOR
ACCESSORIES : 2. FAUCET AND SOAP DISPENSER CONTROLS SHALL HAVE A REACH DEPTH OF 280 MAX INDICATED, SEE INTERIOR ELEVATIONS. A10 - MIRROR WITH SHAVER SOCKET ELEVATIONS FOR MOUNTING HEIGHT, UNO

SUBMITTED BY:
J. BLANCHARD
AND SHELF, 680mm X 980mm A12 - SURFACE MOUNTED COMBINATION PAPER TOWEL DISPENSER
A01 - MIRROR 600mm X 1000mm A13 - RECESSED PAPER TOWEL AND TRASH RECEPTACLE

J. HOLLAND
DESIGN BY:

DRAWN BY:
A16 - FULL LENGTH MIRROR AND WASTE BIN

A. HANKS
D A03 - SURFACE MOUNTED FOAM SOAP DISPENSER A15 - FREE STANDING SOAP DISPENSER A03 - SURFACE MOUNTED FOAM SOAP DISPENSER

S. OKES
CKD BY:
A17 - MIRROR 1650mm X1050mm A13 - RECESSED COMBINATION PAPER TOWEL AND WASTE RECEPTACLE

ANSI D
A12 - SURFACE MOUNTED COMBINATION PAPER TOWEL A20 - SURFACE MOUNTED PAPER TOWEL DISPENSER

SIZE:
A17A - MIRROR 2285mm X 1050mm A20 - SURFACE MOUNTED PAPER TOWEL DISPENSER
DISPENSER AND WASTE BIN
1200
1200

TRANSATLANTIC MIDDLE EAST DISTRICT


SCHEDULED WALL

US ARMY CORPS OF ENGINEERS


SHOWER SLIDE FINISH AS

201 PRINCE FREDERICK DRIVE,


W/ HAND HELD WALLS 915
SCHED
SHOWER HEAD FINISHED AS

WINCHESTER, VA 22602
CL SCHEDULED CL A09 W/ MOP CL CL
A07 HOOK A18
SCHEDULED 100 150
THERMOSTATIC CENTERED A02 - ROBE A06
SINK 50 A06
CONTROL VALVE ON SERVICE WALLS HOOK
RECEPTOR ABLUTION
3000

155

FINISHED AS

CL CL
COUNTER TOP & FAUCET
A14 SCHEDULED

375
CONTROLS CABINETS, SEE ABLUTION
A03 SOAP

1525 -1680
INTERIOR ELEV.

ACCESSIBLE

TYPICAL
DISPENSER 200
1800

FAUCET

1220 MAX
A08 400
SERVICE

550
1000

1000

A03

UNO

150

935
865
RECEPTOR
900

100
500
C

685
525
150
FLOOR LEVEL

50
400

50
FRONT WALL SIDE WALL 1433 300 530 300
SHOWER SIDE WALL SHOWER CONTROL WALL
200 100 250 260
DESCRIPTION SHOWER STALL JANITOR CLOSET COUNTER TOP SINK GARMENT HOOKS ABLUTION ROOM
NOTES/ A07 - SHOWER DOOR A09 - UTILITY SHELF W/ 3 HOOKS AND 4 HOLDERS 1. PROVIDE PLUMBING PIPE 1. PROVIDE GARMENT HOOK AT TOILET 1. PROVIDE MIN. 1433mm WIDE AREA FOR WHEEL CHAIR ACCESSIBLE
ACCESSORIES : A08 - TRIPLE SHOWER DISPENSER PROTECTION WRAPS/ UNDER STALL DOORS AT TYPICAL MOUNTING ABLUTION SEAT
A14 - SHOWER SOAP BASKET LAVATORY GUARDS AT SINKS HEIGHT. AT ACCESSIBLE TOILET STALL

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


AND LAVATORIES WITH DOORS, PROVIDE TWO, PROVIDE ONE A03 - SURFACE MOUNTED FOAM SOAP DISPENSER
EXPOSED PIPING. AT BOTH THE TYPICAL AND ACCESSIBLE A06 - CONCEALED PAPER TOWEL DISPENSER
MOUNTING HEIGHTS. A19 - 1070mm GRAB BAR
2. LOCATE AS INDICATED ON DRAWINGS.

THAAD STANDARD FACILITIES

TYPICAL MOUNTING HEIGHTS


VARIOUS LOCATIONS, KSA
ACCESSORY LEGEND

STANDARD DETAILS
COUNTER/DESK
250 ABOVE

EO
TV CODE DESCRIPTION

SA-480530
FA MKBD / TKBD
B COAX/
CL

TV VD A01 MIRROR 600mm X 1000mm


DATA
TV EO ALIGN W/ DOOR A02 DOUBLE ROBE HOOK
HARDWARE OR OTHER
CL

CL
MAX OF 2440

A03 SURFACE MOUNTED FOAM SOAP DISPENSER


CL

ADJACENT DEVICES
PS A04 SQUARE PEDAL BIN
450 AFF
1250 MAX

EO A05 RECESSED TOILET TISSUE DISPENSER


VARIES

1200 MAX

1525

VD A06 CONCEALED PAPER TOWEL DISPENSER


A07 SHOWER DOOR
CL

A08 TRIPLE SHOWER SOAP DISPENSER


FLOOR LEVEL
A09 UTILITY SHELF
ALIGN LIFE SAFETY DEVICES VERTICALLY CENTERED A10 MIRROR WITH SHELF 600mm x 915mm
ABOVE LIGHT SWITCH, SIGNS, ELECTRICAL AND/OR A11 SURFACE MOUNTED TOILET TISSUE DISPENSER
MECHANICAL DEVICES OR FEC BELOW. A12 SURFACE MOUNTED COMBINATION PAPER TOWEL DISPENSER AND WASTE BIN
A13 RECESSED COMBINATION PAPER TOWEL AND WASTE RECEPTACLE
DESCRIPTION TELEVISION (810-812) OUTLETS FIRE ALARM (FA) MARKERBOARD / TACKBOARD (MKBD AND TKBD)
2/9/2022 4:22:34 PM

A14 SHOWER SOAP BASKET


NOTES/ 1. REFER TO IF SERIES DWGS 1. MOUNT HEIGHTS SHOWN FOR ABOVE 1. FIRE ALARM* (FA) 1. REFER TO IN SERIES DWGS FOR LOCATIONS A15 FREE STANDING SOAP DISPENSER
A ACCESSORIES : FOR LOCATIONS FLOOR AND ABOVE COUNTER UNO., 2. PULL STATION (PS) A16 FULL LENGTH MIRROR SHEET ID
REFER TO ELEVATIONS FOR 3. REFER TO FA501 FOR TOP AND BOTTOM OF FA LENSE
LOCATIONS. A17 NOT USED
2. ELECTRICAL OUTLET (EO)
REQUIREMENTS
A18 900mm GRAB BAR $
3. VOICE/DATA OUTLET (VD) A19 1070mm GRAB BAR
* INCLUDES WALL MOUNTED STROBE , SPEAKER AND/OR HORN. A20 SURFACE MOUNTED PAPER TOWEL DISPENSER UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA005
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


4.002 - 200 mm CONCRETE MASONRY 3.007 - REINFORCED CAST-IN-PLACE
UNIT CONCRETE WALL, SEE STRUCTURAL
1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
DRAWINGS
4.040 - PREMOLDED JOINT FILLER US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
4.040 - PREMOLDED JOINT FILLER SYMBOLS.
Middle East District
G 7.060 - BACKER ROD AND JOINT 7.060 - BACKER ROD AND JOINT 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.
SEALANT SEALANT

DATE
15 15

DESCRIPTION
F

25 25
4.005 - MASONRY VENEER 4.005 - MASONRY VENEER
9.107 - CASING BEAD FOR STUCCO 9.107 - CASING BEAD FOR STUCCO
SYSTEM SYSTEM
7.188 - SEALANT 7.188 - SEALANT
7.251 - SEALANT AND AIR BARRIER 7.251 - SEALANT AND AIR BARRIER
TRANSITION MEMBRANE AT JOINT IN TRANSITION MEMBRANE AT JOINT IN

MARK
SUBSTRATE SUBSTRATE
9.115 - METAL LATH FOR STUCCO
9.115 - METAL LATH FOR STUCCO
E SYSTEM
SYSTEM
9.009 - 25 mm THICK THREE COAT
9.009 - 25 mm THICK THREE COAT

PLOT SCALE: PLOT DATE:


STUCCO SYSTEM

2/9/2022 4:23:04
STUCCO SYSTEM

SOLICITATION NO.:

SA-480530-1$-SA510DT.dwg
PM
CONTRACT NO.:
PLAN DETAIL AT EW-1 PLAN DETAIL AT EW-1A

ISSUE DATE:
E3 1:5 E6 1:5

1:1
SEE STRL DRAWINGS
4.006 - CONCRETE MASONRY SEE STRL DRAWINGS

FILE NO.:
3.001 - REINFORCED
7.016 - FLUID-APPLIED MEMBRANE

SUBMITTED BY:
CAST-IN-PLACE CONCRETE 4.006 - CONCRETE MASONRY
AIR BARRIER 3.001 - REINFORCED

DESIGN BY:

DRAWN BY:
S. MURPHY

A. HANKS
D CAST-IN-PLACE CONCRETE

A. ORTIZ
3.124 - PREMOLDED JOINT 7.016 - FLUID-APPLIED MEMBRANE

S. OKES
CKD BY:
9.009 - 25 mm THICK THREE COAT

ANSI D
FILLER STRIP AIR BARRIER

SIZE:
STUCCO SYSTEM 3.124 - PREMOLDED JOINT
FILLER STRIP

9.009 - 25 mm THICK THREE COAT 7.251 - SEALANT AND AIR

TRANSATLANTIC MIDDLE EAST DISTRICT


30mm UNO SEE STRL DRAWINGS
STUCCO SYSTEM BARRIER TRANSITION

US ARMY CORPS OF ENGINEERS


MEMBRANE AT JOINT IN

201 PRINCE FREDERICK DRIVE,


9.115 - METAL LATH FOR STUCCO 7.251 - SEALANT AND AIR
9.115 - METAL LATH FOR STUCCO SUBSTRATE
SYSTEM BARRIER TRANSITION

WINCHESTER, VA 22602
MEMBRANE AT JOINT IN SYSTEM 9.107 - CASING BEAD FOR
9.107 - CASING BEAD FOR STUCCO SUBSTRATE STUCCO SYSTEM
SYSTEM 9.107 - CASING BEAD FOR STUCCO
9.107 - CASING BEAD FOR SYSTEM 7.016 - FLUID-APPLIED
7.188 - SEALANT STUCCO SYSTEM
MEMBRANE AIR BARRIER
7.188 - SEALANT
4.006 - CONCRETE MASONRY
9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM 7.016 - FLUID-APPLIED 9.009 - 25 mm THICK THREE COAT
MEMBRANE AIR BARRIER STUCCO SYSTEM
9.115 - METAL LATH FOR STUCCO
SYSTEM
C 25mm UNO
30mm UNO

PLAN DETAIL PLAN DETAIL


C3 1:5 C6 1:5

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


SEE STRL DRAWINGS

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA

DETAILS TYPICAL STUCCO


7.251 - SEALANT AND AIR BARRIER 7.016 - FLUID-APPLIED MEMBRANE
AIR BARRIER 3.001 - REINFORCED

STANDARD DETAILS
TRANSITION MEMBRANE AT JOINT IN
SUBSTRATE CAST-IN-PLACE CONCRETE
9.115 - METAL LATH FOR STUCCO

SA-480530
SYSTEM
B 3.001 - REINFORCED CAST-IN-PLACE
7.251 - SEALANT AND AIR
BARRIER TRANSITION
CONCRETE 9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM MEMBRANE AT JOINT IN
SUBSTRATE
9.107 - CASING BEAD FOR STUCCO
SYSTEM 7.246 - PACK JOINT WITH
GRAPHIC SCALES
MINERAL WOOL INSULATION
9.107 - CASING BEAD FOR STUCCO
SYSTEM
25mm UNO SEE STRL DRAWINGS
9.009 - 25 mm THICK
7.188 - SEALANT THREE COAT STUCCO 7.188 - SEALANT 4.006 - CONCRETE MASONRY
SYSTEM
9.107 - CASING BEAD FOR STUCCO 9.107 - CASING BEAD FOR STUCCO
SYSTEM SYSTEM
2/9/2022 4:23:04 PM

25mm UNO
A 0 100 200 400
SHEET ID
SCALE: 1:5 $
PLAN DETAIL SECTION DETAIL
A3 1:5 A6 1:5
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA510
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

DATE
3.001 - REINFORCED
CAST-IN-PLACE CONCRETE

7.016 - FLUID-APPLIED
MEMBRANE AIR BARRIER

DESCRIPTION
F CONCRETE OR CONCRETE MASONRY 9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM

9.115 - METAL LATH FOR STUCCO


SYSTEM

9.106 - CORNER BEAD FOR


STUCCO SYSTEM

9.115 - METAL LATH FOR STUCCO 7.016 - FLUID-APPLIED MEMBRANE 7.016 - FLUID-APPLIED MEMBRANE 9.115 - METAL LATH FOR STUCCO
SYSTEM AIR BARRIER AIR BARRIER SYSTEM

9.009 - 25 mm THICK THREE COAT 9.009 - 25 mm THICK THREE COAT


STUCCO SYSTEM 9.116 - CONTROL JOINT BEAD FOR STUCCO SYSTEM
STUCCO SYSTEM

MARK
E

PLOT SCALE: PLOT DATE:


2/9/2022 4:23:40
PLAN DETAIL PLAN DETAIL

SOLICITATION NO.:

SA-480530-1$-SA511DT.dwg
E3 E6

PM
CONTRACT NO.:
1:5 1:5

ISSUE DATE:

1:1
FILE NO.:
SUBMITTED BY:
7.016 - FLUID-APPLIED MEMBRANE

DESIGN BY:

DRAWN BY:
S. MURPHY

A. HANKS
AIR BARRIER
D 3.001 - REINFORCED

A. ORTIZ

S. OKES
CKD BY:
3.001 - REINFORCED

ANSI D
CAST-IN-PLACE CONCRETE

SIZE:
CAST-IN-PLACE CONCRETE

9.009 - 25 mm THICK THREE COAT


STUCCO SYSTEM

TRANSATLANTIC MIDDLE EAST DISTRICT


9.115 - METAL LATH FOR STUCCO

US ARMY CORPS OF ENGINEERS


7.016 - FLUID-APPLIED MEMBRANE

201 PRINCE FREDERICK DRIVE,


AIR BARRIER SYSTEM

WINCHESTER, VA 22602
7.016 - FLUID-APPLIED
9.115 - METAL LATH FOR STUCCO 7.016 - FLUID-APPLIED 9.106 - CORNER BEAD FOR STUCCO MEMBRANE AIR BARRIER
SYSTEM MEMBRANE AIR BARRIER SYSTEM
9.009 - 25 mm THICK THREE COAT 9.115 - METAL LATH FOR STUCCO 9.009 - 25 mm THICK THREE COAT 9.115 - METAL LATH FOR STUCCO
STUCCO SYSTEM SYSTEM STUCCO SYSTEM SYSTEM
9.106 - CORNER BEAD FOR STUCCO
9.009 - 25 mm THICK THREE COAT
SYSTEM
STUCCO SYSTEM

PLAN DETAIL PLAN DETAIL


C3 1:5 C6 1:5

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


7.016 - FLUID-APPLIED
MEMBRANE AIR BARRIER

THAAD STANDARD FACILITIES


3.001 - REINFORCED CAST-IN-PLACE 9.009 - 25 mm THICK THREE COAT
CONCRETE OR CONCRETE MASONRY

VARIOUS LOCATIONS, KSA

DETAILS TYPICAL STUCCO


CONCRETE STUCCO SYSTEM

STANDARD DETAILS
9.115 - METAL LATH FOR STUCCO

100, TYP UNO


SYSTEM

SA-480530
7.016 - FLUID-APPLIED MEMBRANE
B AIR BARRIER 3.001 - REINFORCED CAST-IN-PLACE
CONCRETE GROUND LEVEL
9.115 - METAL LATH FOR STUCCO
SYSTEM EL 150
9.107 - CASING BEAD FOR 9.108 - DRIP SCREED FOR GRAPHIC SCALES
9.009 - 25 mm THICK THREE COAT STUCCO SYSTEM STUCCO SYSTEM
7.016 - FLUID-APPLIED MEMBRANE
STUCCO SYSTEM
AIR BARRIER
9.115 - METAL LATH FOR STUCCO
9.009 - 25 mm THICK THREE COAT SYSTEM 9.093 - ELASTOMERIC COATING
9.116 - CONTROL JOINT BEAD FOR STUCCO SYSTEM
STUCCO SYSTEM 7.001 - ELASTOMERIC SHEET 3.128 - BROOM FINISH
WATERPROOFING WITH CAST-IN-PLACE CONCRETE
PROTECTION BOARD APRON. CONSTRUCT APRON
WITH CONTRACTION JOINTS TO
3.098 - PREMOLDED JOINT FILLER DIVIDE THE SURFACE INTO
2/9/2022 4:23:40 PM

STRIP EXTENDING FULL DEPTH OF RECTANGULAR AREAS. SPACE


SLAB CONTRACTION JOINTS EQUAL
A TO THE APRON WIDTH. FORM
0 100 200 400
SHEET ID
APRON CONTRACTION JOINTS IN
THE SAME MANNER AS SCALE: 1:5 $
SECTION DETAIL PLAN DETAIL SECTION DETAIL SIDEWALK CONTRACTION
JOINTS
A1 1:5 A3 1:5 A6 1:5
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA511
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


DETAIL NOTE: LOCATE
CENTERLINE OF PENETRATION 1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
450 mm MINIMUM AWAY FROM US Army Corps of
BACK SIDE OF PARAPET AND 450 2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
mm MINIMUM FROM OTHER 7.261 - FLANGED CABLE SYMBOLS.
PENETRATION ALUMINUM Middle East District
PENETRATIONS.
G FLASHING FOR FLEXIBLE 3. REFER TO SHEET SA608 FOR ROOF SYSTEM DETAILS.
CONDUIT AND CABLES

DATE
7.188 - SEALANT DETAIL NOTE: LOCATE CENTERLINE PIPE OR CONDUIT PENETRATION
OF PENETRATION 450 mm MINIMUM
7.262 - EPDM END CAP SEAL, AWAY FROM BACK SIDE OF PARAPET 7.188 - SEALANT
7.101 - STAINLESS STEEL AND 450 mm MINIMUM FROM OTHER
FRICTION FIT
CLAMPING RING PENETRATIONS. 7.101 - STAINLESS STEEL
CLAMPING RING
7.103 - EPDM MEMBRANE FLASHING
7.252 - STONE BALLAST 7.252 - STONE BALLAST
7.103 - EPDM MEMBRANE FLASHING
7.189 - 50 mm PRECAST 7.189 - 50 mm PRECAST
7.078 - GEOTEXTILE FABRIC MAT CONCRETE BALLAST PAVERS 7.078 - GEOTEXTILE FABRIC MAT CONCRETE BALLAST PAVERS

200 MIN

200 MIN
7.010 - LOOSE-LAID

DESCRIPTION
7.010 - LOOSE-LAID
F POLYSTYRENE BOARD POLYSTYRENE BOARD
ROOF INSUL, RSI=4.40 ROOF INSUL, RSI=4.40
ROOF TYPE RS-1

ROOF TYPE RS-1


(R-25) MIN (R-25) MIN
7.025 - LOOSE-LAID BALLASTED
EPDM SHEET ROOFING TOP OF ROOF SLAB TOP OF ROOF SLAB
7.025 - LOOSE-LAID BALLASTED
3.016 - LIGHTWEIGHT CONCRETE EPDM SHEET ROOFING 3.016 - LIGHTWEIGHT CONCRETE
TOPPING, MIN 50 mm THICK AND TOPPING, MIN 50 mm THICK AND
MAX 150 mm THICK, SLOPE 2% MAX 150 mm THICK, SLOPE 2%
MINIMUM TOWARD ROOF DRAINS MINIMUM TOWARD ROOF DRAINS

3.115 - REINFORCED 3.115 - REINFORCED


CAST-IN-PLACE CONCRETE CAST-IN-PLACE CONCRETE
ROOF SLAB, SEE STRUCTURAL ROOF SLAB, SEE STRUCTURAL
DRAWINGS DRAWINGS

MARK
7.188 - SEALANT 7.188 - SEALANT 7.188 - SEALANT
7.188 - SEALANT
E

PLOT SCALE: PLOT DATE:


2/9/2022 4:24:12
RS-1 SECTION DETAIL FLANGED CABLE PENETRATION RS-1 SECTION DETAIL AT PIPE PENETRATION

SOLICITATION NO.:

SA-480530-1$-SA518DT.dwg
E1 E5

PM
CONTRACT NO.:
1 : 10 1 : 10

ISSUE DATE:

1:1
FILE NO.:
M. CUNNINGHAM
SUBMITTED BY:
DESIGN BY:

DRAWN BY:
S. MURPHY

A. HANKS
D

A. ORTIZ
CKD BY:

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
5.187 - SAFETY RAILING SYSTEM
SELF CLOSING SWING GATE

EQL

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


5.169 - SAFETY RAILING SYSTEM

WINCHESTER, VA 22602
23.001 - ROOFTOP MECHANICAL
7.081 - NEOPRENE FILLER AND/OR EQUIPMENT, SEE MECHANICAL 5.163 - METAL ROOF HATCH
GASKET
7.263 - FLASHING RECEIVER CL
23.004 - GALVANIZED STEEL

1068 MIN
INSULATED PREFABRICATED CURB 7.264 - COUNTER FLASHING 5.190 - GALVANIZED STEEL 7.103 - EPDM MEMBRANE
FOR ROOF TOP EQUIPMENT. ATTACH LADDER BRACKETS AND 12 mm FLASHING
CURB TO CONCRETE SLAB PER 7.103 - EPDM MEMBRANE (MIN) EXPANSION ANCHORS FOR
7.252 - STONE BALLAST

EQL
EQUIPMENT MFR RECOMMENDATION FLASHING FASTENING INTO MASONRY AND
C CONCRETE SUBSTRATES
7.252 - STONE BALLAST 7.189 - 50 mm PRECAST
5.222 - LADDER SAFETY POST CONCRETE BALLAST PAVERS
7.189 - 50 mm PRECAST
CONCRETE BALLAST PAVERS

7.078 - GEOTEXTILE FABRIC MAT


5.189 - GALVANIZED STEEL
300 UNO

CL LADDER RUNGS 7.078 - GEOTEXTILE FABRIC MAT


7.010 - LOOSE-LAID 5.188 - GALVANIZED STEEL

300 UNO

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


POLYSTYRENE BOARD ROOF LADDER STRINGER (SIDE RAILS)
7.010 - LOOSE-LAID POLYSTYRENE
INSUL, RSI=4.40 (R-25) MIN

ROOF DETAILS - RS-1 TYPICAL DETAILS


BOARD ROOF INSUL, RSI=4.40 (R-25)
ROOF TYPE RS-1

MIN

THAAD STANDARD FACILITIES


7.010 - LOOSE-LAID

250 UNO

ROOF TYPE RS-1

VARIOUS LOCATIONS, KSA


3.016 - LIGHTWEIGHT CONCRETE POLYSTYRENE BOARD ROOF

300 UNO
TOP OF ROOF SLAB INSUL, RSI=4.40 (R-25) MIN

STANDARD DETAILS
TOPPING, MIN 50 mm THICK AND MAX
150 mm THICK, SLOPE 2% MINIMUM
TOWARD ROOF DRAINS 7.025 - LOOSE-LAID BALLASTED TOP OF ROOF SLAB

SA-480530
EPDM SHEET ROOFING
B 3.098 - PREMOLDED JOINT
3.115 - REINFORCED CAST-IN-PLACE
FILLER STRIP EXTENDING FULL 7.025 - LOOSE-LAID BALLASTED
CONCRETE ROOF SLAB, SEE
DEPTH OF SLAB EPDM SHEET ROOFING
STRUCTURAL DRAWINGS
7.329 - CRICKET AT EQUIPMENT
3.016 - LIGHTWEIGHT CONCRETE
GRAPHIC SCALES
3.098 - PREMOLDED JOINT FILLER CURB. INSTALL MECHANICAL 7.330 - CRICKET AT ROOF HATCH.
INSTALL MECHANICAL FASTENED TOPPING, MIN 50 mm THICK AND
STRIP EXTENDING FULL DEPTH OF FASTENED TAPERED
TAPERED POLYSTYRENE ROOF MAX 150 mm THICK, SLOPE 2%
SLAB 200 UNO POLYSTYRENE ROOF BOARD TO
BOARD TO FORM CRICKET. MINIMUM MINIMUM TOWARD ROOF DRAINS
FORM CRICKET. MINIMUM
SEE STRL CRICKET LENGTH TO WIDTH RATIO
CRICKET LENGTH TO WIDTH 3.098 - PREMOLDED JOINT
RATIO OF 3:1 OF 3:1
200 UNO 190 200 UNO FILLER STRIP EXTENDING FULL
DEPTH OF SLAB
SEE STRL UNO 3.098 - PREMOLDED JOINT SEE STRL
FILLER STRIP EXTENDING FULL
DEPTH OF SLAB
3.115 - REINFORCED
2/9/2022 4:24:12 PM

CAST-IN-PLACE CONCRETE
A ROOF SLAB, SEE STRUCTURAL 0 200 400 800
SHEET ID
DRAWINGS

SCALE: 1:10 $
RS-1 SECTION DETAIL AT METAL CURB RS-1 SECTION DETAIL AT ROOF HATCH
A1 1 : 10 A5 1 : 10
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA518
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
COL SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA608 FOR ROOF SYSTEM DETAILS.
7.261 - FLANGED CABLE
PENETRATION ALUMINUM

DATE
FLASHING FOR FLEXIBLE
CONDUIT AND CABLES

7.188 - SEALANT
7.262 - EPDM END CAP SEAL,
7.016 - FLUID-APPLIED MEMBRANE FRICTION FIT
AIR BARRIER 7.101 - STAINLESS STEEL
CLAMPING RING
9.009 - 25 mm THICK THREE COAT COL
STUCCO SYSTEM 7.103 - EPDM MEMBRANE FLASHING
7.252 - STONE BALLAST
9.108 - DRIP SCREED FOR STUCCO 7.078 - GEOTEXTILE FABRIC MAT
SYSTEM
7.038 - EXTEND EPDM
MEMBRANE ON VERTICAL FACE

200 MIN
7.179 - CAST IN PLACE REGLET AND 3.073 - CONCRETE PARAPET, 7.189 - 50 mm PRECAST CONCRETE OF PARAPET UP TO 750 mm

DESCRIPTION
COUNTER FLASHING SEE STRUCTURAL DRAWINGS BALLAST PAVERS
F ABOVE TOP OF ROOF SLAB TO
TERMINATION BAR, UNO
7.010 - LOOSE-LAID
POLYSTYRENE BOARD 3.098 - PREMOLDED JOINT
FILLER STRIP EXTENDING FULL

ROOF TYPE RS-1


ROOF INSUL, RSI=4.40
(R-25) MIN DEPTH OF SLAB
7.189 - 50 mm PRECAST CONCRETE
BALLAST PAVERS 7.038 - EXTEND EPDM TOP OF ROOF SLAB
MEMBRANE ON VERTICAL FACE 7.025 - LOOSE-LAID BALLASTED
7.078 - GEOTEXTILE FABRIC MAT
OF PARAPET UP TO 750 mm EPDM SHEET ROOFING
7.010 - LOOSE-LAID POLYSTYRENE ABOVE TOP OF ROOF SLAB TO 65 MIN SEE STRUCTURAL DRAWINGS

800 TYP, UNO


BOARD ROOF INSUL, RSI=4.40 (R-25) TERMINATION BAR, UNO
MIN
7.025 - LOOSE-LAID BALLASTED
7.188 - SEALANT
EPDM SHEET ROOFING
3.016 - LIGHTWEIGHT CONCRETE 3.116 - REINFORCED
3.098 - PREMOLDED JOINT TOPPING, MIN 50 mm THICK AND MAX CAST-IN-PLACE CONCRETE

MARK
3.016 - LIGHTWEIGHT CONCRETE FILLER STRIP EXTENDING FULL 150 mm THICK, SLOPE 2% MINIMUM BEAM, SEE STRUCTURAL
TOPPING, MIN 50 mm THICK AND MAX DEPTH OF SLAB TOWARD ROOF DRAINS DRAWINGS
150 mm THICK, SLOPE 2% MINIMUM
E TOWARD ROOF DRAINS 7.246 - PACK JOINT WITH
3.115 - REINFORCED CAST-IN-PLACE
CONCRETE ROOF SLAB, SEE MINERAL WOOL INSULATION

PLOT SCALE: PLOT DATE:


TOP OF ROOF SLAB

2/9/2022 4:24:35
STRUCTURAL DRAWINGS
9.123 - 25 mm WIDE STUCCO
3.115 - REINFORCED CAST-IN-PLACE CONTROL JOINT WITH SEALANT.

SOLICITATION NO.:

SA-480530-1$-SA519DT.dwg
CONCRETE ROOF SLAB, SEE 7.188 - SEALANT

PM
REFER TO SHEET SA510

CONTRACT NO.:
STRUCTURAL DRAWINGS

ISSUE DATE:
9.009 - 25 mm THICK THREE COAT
26.024 - FLEXIBLE CONDUIT OR STUCCO SYSTEM
CABLE. SEE ELECTRICAL DRAWINGS

1:1
12
7.297 - LOOSE-LAID EW-2
POLYSTYRENE BOARD RIGID 7.016 - FLUID-APPLIED
INSUL ON CONC RF DECK IN 75 MEMBRANE AIR BARRIER
mm THICK LAYERS TO LIMIT
LIGHTWEIGHT CONCRETE TO 150

FILE NO.:
mm THICK

M. CUNNINGHAM
SUBMITTED BY:
DESIGN BY:

DRAWN BY:
S. MURPHY

A. HANKS
D

A. ORTIZ
7.016 - FLUID-APPLIED

CKD BY:

ANSI D
MEMBRANE AIR BARRIER

SIZE:
9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM

TRANSATLANTIC MIDDLE EAST DISTRICT


RS-1 SECTION DETAIL AT PARAPET 9.108 - DRIP SCREED FOR

US ARMY CORPS OF ENGINEERS


D1

201 PRINCE FREDERICK DRIVE,


STUCCO SYSTEM
1 : 10

WINCHESTER, VA 22602
9.093 - ELASTOMERIC COATING
7.188 - SEALANT
3.128 - BROOM FINISH
CAST-IN-PLACE CONCRETE
APRON. CONSTRUCT APRON
9.097 - WALL BASE AS EW-2
WITH CONTRACTION JOINTS TO
ROOFTOP MECHNICAL OR SCHEDULED DIVIDE THE SURFACE INTO
ELECTRICAL SUPPORT. SEE
RECTANGULAR AREAS. SPACE
MECHANICAL AND ELECTRICAL 9.110 - SCHEDULED FLOORING, CONTRACTION JOINTS EQUAL
DRAWINGS FOR SUPPORTS AND REFER TO IN SERIES DRAWINGS FOR TO THE APRON WIDTH. FORM
C SUPPORT LOCATIONS FINISH PLANS APRON CONTRACTION JOINTS IN
7.188 - SEALANT THE SAME MANNER AS
SIDEWALK CONTRACTION
7.101 - STAINLESS STEEL 9.111 - FLOORING SETTING BED, JOINTS GROUND FLOOR
7.103 - EPDM CLAMPING RING REFER TO IN SERIES DRAWINGS FOR
MEMBRANE FLASHING FINISH PLANS
7.252 - STONE BALLAST
3.006 - REINFORCED CONCRETE
7.078 - GEOTEXTILE SLAB, SEE STRUCTURAL DRAWINGS
7.189 - 50 mm PRECAST

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


FABRIC MAT CONCRETE BALLAST PAVERS
200 MIN

3.098 - PREMOLDED JOINT

ROOF DETAILS - RS-1 TYPICAL DETAILS


FILLER STRIP EXTENDING FULL
3.139 - UNDER SLAB VAPOR BARRIER DEPTH OF SLAB

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
7.010 - LOOSE-LAID 3.098 - PREMOLDED JOINT 31.005 - GRAVEL BASE COURSE,
POLYSTYRENE BOARD FILLER STRIP EXTENDING FULL 3.024 - BLINDING CONCRETE, SEE SEE STRUCTURAL DRAWINGS

STANDARD DETAILS
ROOF INSUL, RSI=4.40 DEPTH OF SLAB STRUCTURAL DRAWINGS
7.001 - ELASTOMERIC SHEET
ROOF TYPE RS-1

(R-25) MIN 31.005 - GRAVEL BASE COURSE, SEE WATERPROOFING WITH

SA-480530
7.025 - LOOSE-LAID STRUCTURAL DRAWINGS PROTECTION BOARD
B BALLASTED EPDM TOP OF ROOF SLAB
SHEET ROOFING 3.098 - PREMOLDED JOINT FILLER
STRIP EXTENDING FULL DEPTH OF 26.024 - FLEXIBLE CONDUIT OR
3.098 - PREMOLDED
JOINT FILLER STRIP 3.016 - LIGHTWEIGHT CONCRETE
TOPPING, MIN 50 mm THICK AND
SLAB CABLE. SEE ELECTRICAL
DRAWINGS
GRAPHIC SCALES
EXTENDING FULL 7.001 - ELASTOMERIC SHEET
DEPTH OF SLAB MAX 150 mm THICK, SLOPE 2%
MINIMUM TOWARD ROOF DRAINS WATERPROOFING WITH 3.007 - REINFORCED
PROTECTION BOARD CAST-IN-PLACE CONCRETE
3.115 - REINFORCED
WALL, SEE STRUCTURAL
CAST-IN-PLACE CONCRETE
DRAWINGS
200 UNO ROOF SLAB, SEE STRUCTURAL
SEE STRL DRAWINGS
2/9/2022 4:24:35 PM

A 0 200 400 800


SHEET ID
SCALE: 1:10 $
RS-1 SECTION DETAIL AT EQUIPMENT SUPPORT RS-1 SECTION DETAIL AT LIGHTNING PROTECTION RISER
A1 1 : 10 A5 1 : 10 UNLESS OTHERWISE NOTED, LINEAR SA519
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA608 FOR ROOF SYSTEM DETAILS.

7.296 - CONDUIT SUPPORT MAX 3000

DATE
mm. REFER TO ELECTRICAL AND
TELECOM DRAWINGS FOR LAYOUT
7.290 - ATTACHMENT CLIP

7.131 - ALUMINUM STRUCTURAL


STANDING SEAM METAL ROOFING

7.291 - ROOF SYSTEM RS-3

EQ
7.285 - 1070 mm GALVANIZED

DESCRIPTION
F STEEL GUARDRAIL

1068
7.288 - GALVANIZED
STEEL GRATING

7.286 - 150 mm TOE KICK

EQ
7.287 - GALVANIZED STEEL
BRACKET
7.289 - GRATING CLIP RS-3 CONDUIT BRACKET ATTACHMENT
7.290 - ATTACHMENT CLIP
E5 1:5
7.131 - ALUMINUM STRUCTURAL
STANDING SEAM METAL

MARK
ROOFING

250 MIN.
E

PLOT SCALE: PLOT DATE:


2/9/2022 4:24:35
7.173 - NON-PENETRATING

SOLICITATION NO.:
STANDING SEAM FALL

SA-480530-1$-SA522DT.dwg
PM
CONTRACT NO.:
PROTECTION ANCHOR

ISSUE DATE:
7.195 - STRUCTURAL

1:1
STANDING SEAM ROOF
HALTER CLIPS
7.131 - ALUMINUM
STRUCTURAL
STANDING SEAM METAL
ROOFING

FILE NO.:
7.291 - ROOF SYSTEM RS-3

M. MacEACHERN
SUBMITTED BY:
W. RODRIGUEZ
C. SCORZELLI
7.291 - ROOF SYSTEM RS-3

DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
SIZE:
RS-3 GUARDRAIL DETAIL @ WALKWAY
D1

TRANSATLANTIC MIDDLE EAST DISTRICT


1 : 10

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
RS-3 SECTION DETAIL @ FALL PROTECTION
C5 1:5
47

4.041 - PRECAST CONCRETE SPLASH


BLOCK 7.293 - CONDUIT PENETRATION TO
BE CENTERED ON THE FLAT PART
OF THE ROOF
C
7.294 - SEAL AT TOP PER PIPE BOOT
305

406

MANUF'S RECOMMENDATION AND


INSTALLATION GUIDELINES

7.131 - ALUMINUM STRUCTURAL


STANDING SEAM METAL ROOFING
47

7.257 - RUBBER PIPE BOOT

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)

ROOF DETAILS - RS-3 TYPICAL DETAILS


7.295 - EPDM PIPE BOOT SET IN

THAAD STANDARD FACILITIES


CONT BEAD OF SEALANT AND

VARIOUS LOCATIONS, KSA


FASTENED TO SSMR

STANDARD DETAILS
610

SA-480530
B

GRAPHIC SCALES
51
127

127
102

610 305 0 200 400 800

SCALE: 1:10
2/9/2022 4:24:35 PM

A 0 100 200 400


SHEET ID
SCALE: 1:5 $
SPLASH BLOCK RS-3 CONDUIT PENETRATION
A1 1:5 A5 1:5 UNLESS OTHERWISE NOTED, LINEAR SA522
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10
CL
DETAIL NOTE: LOCATE
GENERAL SHEET NOTES
CENTERLINE OF PENETRATION 7.261 - FLANGED CABLE
450 mm MINIMUM AWAY FROM PENETRATION ALUMINUM 1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
BACK SIDE OF PARAPET AND 450 FLASHING FOR FLEXIBLE
CONDUIT AND CABLES US Army Corps of
mm MINIMUM FROM OTHER 2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
PENETRATIONS. SYMBOLS.
7.225 - STAINLESS STEEL Middle East District
G CLAMPING RING 3. REFER TO SHEET SA608 FOR ROOF SYSTEM DETAILS.
7.223 - MEMBRANE FLASHING
COLLAR, LAP WITH
7.262 - EPDM END CAP SEAL, WATERPROOF MEMBRANE

DATE
FRICTION FIT 7.131 - ALUMINUM STRUCTURAL
7.226 - CONTINUOUS BEAD OF STANDING SEAM METAL
SEALANT ROOFING
7.224 - EPDM RUBBER PIPE BOOT 7.204 - REINFORCED
WITH CLAMP POLYETHYLENE AIR AND VAPOR
BARRIER
7.103 - EPDM MEMBRANE FLASHING 7.195 - STRUCTURAL STANDING
SEAM ROOF HALTER CLIPS

CL

DESCRIPTION
F
7.222 - REFER TO STRUCTURAL
DRAWING FOR ANTENNA/AIR
TERMINAL SUPPORT DETAILS
7.226 - CONTINUOUS BEAD OF 7.225 - STAINLESS STEEL
SEALANT CLAMPING RING
7.224 - EPDM RUBBER PIPE BOOT 7.223 - MEMBRANE FLASHING
WITH CLAMP COLLAR, LAP WITH
WATERPROOF MEMBRANE
7.131 - ALUMINUM STRUCTURAL 7.188 - SEALANT 7.188 - SEALANT
STANDING SEAM METAL
ROOFING
7.204 - REINFORCED
POLYETHYLENE AIR AND VAPOR
BARRIER

RS-3 SECTION DETAIL @ FLANGED CABLE PENETRATION

MARK
7.195 - STRUCTURAL STANDING

E
SEAM ROOF HALTER CLIPS
F5 1 : 10

COL

PLOT SCALE: PLOT DATE:


7.209 - ALUMINUM VERGE CLIP

2/9/2022 4:24:43
7.131 - ALUMINUM STRUCTURAL
STANDING SEAM METAL ROOFING
7.195 - STRUCTURAL STANDING

SOLICITATION NO.:
275

SA-480530-1$-SA523DT.dwg
7.196 - GALV STEEL HAT CHANNELS SEAM ROOF HALTER CLIPS

PM
CONTRACT NO.:
ISSUE DATE:
7.207 - MINERAL FIBER BLANKET 7.229 - ALUMINUM FASCIA TRIM,
INSULATION, RSI=3.52 (R-20) MIN 75 TO MATCH COLOR AND FINISH

1:1
OF SSMR PANELS. SUPPORT
7.204 - REINFORCED POLYETHYLENE
ATTACHMENT TO BE FIXED AT
AIR AND VAPOR BARRIER
BENT PL
7.221 - CENTER PANELS 5.173 - 10 GA, 6 mm CONTINUOUS
ON ROOF, TYP. BENT PL, REFER TO
STRUCTURAL

FILE NO.:
M. MacEACHERN
SUBMITTED BY:
W. RODRIGUEZ
C. SCORZELLI
7.215 - ALUMINUM SOFFIT TO

DESIGN BY:

DRAWN BY:
MATCH COLOR AND FINISH OF

A. HANKS
D

CKD BY:
SSMR PANELS

ANSI D
RS-3 SECTION DETAIL @ AIR TERMINAL SUPPORT

SIZE:
D1 1 : 10
7.228 - "J TRIM, TO MATCH
COLOR AND FINISH OF SSMR
PANELS

TRANSATLANTIC MIDDLE EAST DISTRICT


5.200 - PAINTED CONTINUOUS 9.103 - ALUMINUM REGLET

US ARMY CORPS OF ENGINEERS


GALVANIZED STEEL ANGLE. SEE

201 PRINCE FREDERICK DRIVE,


9.009 - 25 mm THICK
STRUCTURAL FRAMING PLAN
THREE COAT STUCCO

WINCHESTER, VA 22602
SYSTEM

4.033 - 100 mm CONCRETE


MASONRY UNIT

COL 7.267 - RIGID BOARD WALL


INSULATION, RSI=2.29 (R-13)
7.195 - STRUCTURAL STANDING MINIMUM
SEAM ROOF HALTER CLIPS
7.131 - ALUMINUM RS-3 SECTION DETAIL @ RAKE
C STRUCTURAL
STANDING SEAM METAL C5 1 : 10
ROOFING

7.217 - EAVE TRIM


7.230 - ALUMINUM RIDGE FLASHING
7.220 - GUTTER STRAP
7.195 - STRUCTURAL STANDING
SEAM ROOF HALTER CLIPS
7.231 - RIDGE 'Z' SUPPORT

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


7.207 - MINERAL FIBER

ROOF DETAILS - RS-3 TYPICAL DETAILS


BLANKET INSULATION,
7.229 - ALUMINUM FASCIA TRIM, RSI=3.52 (R-20) MIN

THAAD STANDARD FACILITIES


TO MATCH COLOR AND FINISH 7.131 - ALUMINUM

VARIOUS LOCATIONS, KSA


OF SSMR PANELS. SUPPORT STRUCTURAL STANDING

STANDARD DETAILS
ATTACHMENT TO BE FIXED AT SEAM METAL ROOFING
BENT PL 90
200 7.196 - GALV STEEL HAT

SA-480530
7.228 - "J TRIM, TO MATCH CHANNELS
B COLOR AND FINISH OF SSMR
PANELS
7.215 - ALUMINUM SOFFIT TO
MATCH COLOR AND FINISH OF
SSMR PANELS 5.003 - STEEL ROOF
GRAPHIC SCALES
DECK, SEE
7.033 - PREFINISHED METAL STRUCTURAL
DOWNSPOUT, 100 mm x 100 mm DRAWINGS

9.009 - 25 mm THICK THREE COAT


STUCCO SYSTEM

4.033 - 100 mm CONCRETE


MASONRY UNIT
2/9/2022 4:24:43 PM

A 0 200 400 800


SHEET ID
SCALE: 1:10 $
RS-3 SECTION DETAIL @ EAVE RS-3 SECTION DETAIL @ RIDGE
A1 1 : 10 A5 1 : 10 UNLESS OTHERWISE NOTED, LINEAR SA523
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


COL 1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA608 FOR ROOF SYSTEM DETAILS.

3.114 - REINFORCED

DATE
7.060 - BACKER ROD CAST-IN-PLACE CONCRETE
AND JOINT SEALANT EW - 1
COLUMN, SEE STRUCTURAL
7.009 - COMPRESSIBLE DRAWINGS
FILLER
3.022 - PRECAST 3.007 - REINFORCED
ARCHITECTURAL CAST-IN-PLACE CONCRETE
CONCRETE COPING WALL, SEE STRUCTURAL COL
DRAWINGS

485
E5
7.331 - CONTINUOUS
SA525 SLOPE LEAD-COATED COPPER
3.022 - PRECAST FLASHING SET IN BED

DESCRIPTION
ARCHITECTURAL OF SEALANT WITH
F CONCRETE COPING SEALED PENETRATIONS

150
125

25
485

COL T.O.W.
3.120 - DRIP GROOVE
SLOPE EL VARIES
7.060 - BACKER ROD
AND JOINT SEALANT 7.060 - BACKER ROD
AND JOINT SEALANT
9.107 - CASING BEAD 25
60
FOR STUCCO SYSTEM 9.018 - STUCCO

25
CONTROL JOINT, TYP
3.043 - SST DOWEL OR
UNO. REFER TO SHEET
EW - 1 GRAVITY CONNECTOR
SA511
BY PRECAST MFR
9.107 - CASING BEAD

MARK
1200 15
9.009 - 25 mm THICK FOR STUCCO SYSTEM
7.016 - FLUID-APPLIED
TYP THREE COAT STUCCO
MEMBRANE AIR 4.034 - CMU CELL
E BARRIER
SYSTEM
GROUT SOLID -
NON-SHRINK, TYP
7.267 - RIGID BOARD EW - 1A

PLOT SCALE: PLOT DATE:


2/9/2022 4:25:24
WALL INSULATION, 9.009 - 25 mm THICK
RSI=2.29 (R-13) MINIMUM THREE COAT STUCCO
SYSTEM

SOLICITATION NO.:

SA-480530-1$-SA525DT.dwg
PM
CONTRACT NO.:
9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM

ISSUE DATE:

1:1
RS-5 PLAN DETAIL AT PRECAST COPING & EXTERIOR WALL RS-5 SECTION DETAIL AT PRECAST COPING
E1 1 : 10 E5 1:5

FILE NO.:
M. MacEACHERN
SUBMITTED BY:
W. RODRIGUEZ
C. SCORZELLI
DESIGN BY:

DRAWN BY:
COL

A. HANKS
D

CKD BY:

ANSI D
SIZE:
9.009 - 25 mm THICK THREE COAT COL
STUCCO SYSTEM

TRANSATLANTIC MIDDLE EAST DISTRICT


9.027 - WEEP SCREED, TYP

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


9.009 - 25 mm THICK THREE COAT

WINCHESTER, VA 22602
7.067 - TERMINATION BAR AND STUCCO SYSTEM
SEALANT, FASTEN AT 200 mm OC
MAX 9.027 - WEEP SCREED, TYP
7.179A - STUCCO TYPE REGLET AND 7.067 - TERMINATION BAR AND
COUNTERFLASHING SEALANT, FASTEN AT 200 mm OC EW - 1A
MAX
7.038 - EXTEND EPDM MEMBRANE ON EW - 1A
VERTICAL FACE OF PARAPET UP TO 7.179A - STUCCO TYPE REGLET AND
750 mm ABOVE TOP OF ROOF SLAB COUNTERFLASHING
TO TERMINATION BAR, UNO 4.012 - SCREW TYPE VENEER
ANCHORS. REFER TO
C 7.259 - ROOF TYPE RS-5 -
7.025 - LOOSE-LAID BALLASTED
EPDM SHEET ROOFING SPECIFICATION SECTION 04 20
PROTECTED MEMBRANE ROOF 00 FOR SPACING
ASSEMBLY; SEE ROOF SYSTEM 7.253 - SET SCUPPER IN
DETAILS FULL BED OF MASTIC 9.107 - CASING BEAD FOR
STUCCO SYSTEM
7.259 - ROOF TYPE RS-5 -
PROTECTED MEMBRANE ROOF 7.188 - SEALANT
7.189 - 50 mm PRECAST
ASSEMBLY; SEE ROOF SYSTEM
750 mm

CONCRETE BALLAST 7.280 - 200 mm HIGH X 300 mm


DETAILS
PAVERS SLOPE, SEE WIDE METAL THRU-WALL
SLOPE, SEE 7.189 - 50 mm PRECAST CONCRETE SCUPPER AS OVERFLOW
ROOF PLAN SLOPE, SEE

200

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


ROOF PLAN BALLAST PAVERS DRAINAGE, MOUNT 200 mm
ROOF PLAN

ROOF DETAILS - RS-5 TYPICAL DETAILS


ABOVE TOP OF ROOF SLAB LOW
POINT

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
7.188 - SEALANT

200

STANDARD DETAILS
T.O. ROOF SLAB T.O. ROOF SLAB

SA-480530
3.136 - SLOPING ROOF
B SLAB, SEE STRUCTURAL 6.008 - 2X PRESSURE TREATED
DRAWINGS WOOD NAILER
9.009 - 25 mm THICK THREE COAT
3.115 - REINFORCED STUCCO SYSTEM
CAST-IN-PLACE 4.033 - 100 mm CONCRETE GRAPHIC SCALES
CONCRETE ROOF SLAB, MASONRY UNIT
3.136 - SLOPING ROOF SEE STRUCTURAL 7.267 - RIGID BOARD WALL
SLAB, SEE STRUCTURAL DRAWINGS INSULATION, RSI=2.29 (R-13)
DRAWINGS MINIMUM
3.115 - REINFORCED 3.116 - REINFORCED CAST-IN-PLACE
7.016 - FLUID-APPLIED
CAST-IN-PLACE CONCRETE BEAM, SEE STRUCTURAL
MEMBRANE AIR BARRIER
CONCRETE ROOF SLAB, DRAWINGS
SEE STRUCTURAL 0 100 200 400
DRAWINGS
7.328 - SLOPE LIGHTWEIGHT SCALE: 1:5
2/9/2022 4:25:24 PM

CONCRETE TOPPING TO FORM


CRICKET. MINIMUM CRICKET LENGTH
A TO WIDTH RATIO OF 3:1. 0 200 400 800
SHEET ID
SCALE: 1:10 $
RS-5 SECTION DETAIL - SADDLES AND CRICKETS AT PARAPETS RS-5 SECTION DETAIL AT OVERFLOW SCUPPER UNLESS OTHERWISE NOTED, LINEAR SA525
A1 1 : 10 A5 1 : 10 DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


22.002 - PRIMARY ROOF 22.003 - SECONDARY OVERFLOW 1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
DRAIN, SEE PLUMBING ROOF DRAIN WITH WATER DAM, US Army Corps of
SEE PLUMBING 2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
31.012 - LOOSE ROCK SYMBOLS.
BALLAST 7.024 - 2-PLY MODIFIED BITUMEN Middle East District
G ROOFING MEMBRANE SYSTEM 3. REFER TO SHEET SA608 FOR ROOF SYSTEM DETAILS.
7.259 - ROOF TYPE RS-5 WITH GRANULAR CAP SHEET
- PROTECTED 7.189 - 50 mm PRECAST

DATE
MEMBRANE ROOF CONCRETE BALLAST PAVERS
ASSEMBLY; SEE ROOF CL CL
SYSTEM DETAILS SLOPE, SEE SLOPE, SEE
ROOF PLAN ROOF PLAN

DESCRIPTION
F
3.136 - SLOPING ROOF
SLAB, SEE STRUCTURAL SEE PLUMBING
DRAWINGS
3.115 - REINFORCED
CAST-IN-PLACE 22.013 - 14 GA
CONCRETE ROOF SLAB, GALVANIZED SUMP PAN
SEE STRUCTURAL
DRAWINGS

RS-5 SECTION DETAIL AT ROOF DRAINS/SUMP PAN


F4 1 : 10
7.188 - SEALANT

MARK
7.101 - STAINLESS
STEEL CLAMPING RING 23.006 - MECHANICAL EQUIPMENT
E ROOF CURB WITH FLASHING BY MFR
7.338 - PRE-MOLDED EPDM PIPE 23.007 - MECHANICAL EQUIPMENT

PLOT SCALE: PLOT DATE:


2/9/2022 4:26:00
23.022 - GALVANIZED STEEL FLASHING ROOF CURB SECURED TO STRUCT
INSULATED PREFABRICATED CURB ROOF DECK
WITH PRE-CUT HOLES CURB COVER

SOLICITATION NO.:
7.103 - EPDM MEMBRANE

SA-480530-1$-SA526DT.dwg
FOR MECH. PIPE PENETRATION. 7.115 - PACK ANNULAR SPACE WITH

PM
CONTRACT NO.:
FLASHING MINERAL WOOL BATT INSULATION, 7.137 - LIQUID-APPLIED
ATTACH CURB TO CONCRETE SLAB

ISSUE DATE:
PER MFR RECOMMENDATION SEAL TOP AND BOTTOM WITH REINFORCED FLASHING SYSTEM
RESILIENT SILICONE BASED

1:1
7.252 - STONE BALLAST SEALANT
7.259 - ROOF TYPE RS-5 -
PROTECTED MEMBRANE ROOF
ASSEMBLY; SEE ROOF SYSTEM 7.189 - 50 mm PRECAST 2% SLOPE
400 MIN.

DETAILS CONCRETE BALLAST PAVERS

300 MIN

FILE NO.:
M. MacEACHERN
SUBMITTED BY:
W. RODRIGUEZ
C. SCORZELLI
TOP OF ROOF SLAB

DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
SIZE:
TOP OF ROOF SLAB

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


3.115 - REINFORCED CAST-IN-PLACE

WINCHESTER, VA 22602
CONCRETE ROOF SLAB, SEE
STRUCTURAL DRAWINGS

3.115 - REINFORCED CAST-IN-PLACE 23.008 - VEHICLE EXHAUST HOSE


CONCRETE ROOF SLAB, SEE REEL
7.188 - SEALANT
STRUCTURAL DRAWINGS

RS-5 SECTION DETAIL AT MULTIPLE PIPE PENETRATIONS RS-5 SECTION DETAIL AT EXHAUST FAN
D1 1 : 10 D5 1 : 10
C

5.261 - MECHANICAL PIPE


PIPE OR CONDUIT PENETRATION
7.025A - FULLY SUPPORT POST, SEE
ADHERED EPDM SHEET STRUCTURAL DRAWINGS
ROOFING
7.103 - EPDM MEMBRANE FLASHING 7.188 - SEALANT

7.259 - ROOF TYPE RS-5 7.252 - STONE BALLAST 7.101 - STAINLESS STEEL
- PROTECTED 7.078
7.010 - GEOTEXTILE
LOOSE-LAID FABRIC MAT

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


CLAMPING RING
MEMBRANE ROOF POLYSTYRENE BOARD

ROOF DETAILS - RS-5 TYPICAL DETAILS


ROOF INSUL, RSI=4.40
600 MIN.

ASSEMBLY; SEE ROOF


SYSTEM DETAILS 7.189 - 50 mm PRECAST (R-25) MIN

THAAD STANDARD FACILITIES


CONCRETE BALLAST PAVERS

VARIOUS LOCATIONS, KSA


7.025 - LOOSE-LAID BALLASTED

STANDARD DETAILS
EPDM SHEET ROOFING 7.189 - 50 mm PRECAST
CONCRETE BALLAST PAVERS

SA-480530
B

TOP OF ROOF SLAB


TOP OF ROOF SLAB
GRAPHIC SCALES

3.115 - REINFORCED
3.115 - REINFORCED
CAST-IN-PLACE CONCRETE
CAST-IN-PLACE CONCRETE
ROOF SLAB, SEE STRUCTURAL
ROOF SLAB, SEE STRUCTURAL
2/9/2022 4:26:00 PM

DRAWINGS
DRAWINGS
A 7.188 - SEALANT 7.188 - SEALANT 0 200 400 800
SHEET ID
SCALE: 1:10 $
RS-5 SECTION DETAIL AT EQUIPMENT SUPPORT RS-5 SECTION DETAIL AT PIPE PENETRATION
A1 1 : 10 A5 1 : 10 UNLESS OTHERWISE NOTED, LINEAR SA526
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
G

DATE
PROVIDE BULLET RESISTANT COMPONENTS AT
OPENING LOCATIONS IDENTIFIED IN DOOR
SCHEDULES TO BE BULLET RESISTANT.

DESCRIPTION
F PROVIDE RABBET AND STOP IN WIDTH AND
DEPTHS TO ACCOMODATE BULLET RESISTANT
COMPONENTS.

7.016 - FLUID-APPLIED
EW-2A MEMBRANE AIR BARRIER
9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM
7.248 - AIR BARRIER TRANSITION
MEMBRANE. LAP MEMBRANE
OVER STUCCO DRIP FLASHING

MARK
BY 50 mm MIN.
8.079 - FILL FRAME WITH
MINERAL WOOL 9.113 - METAL DRIP FLASHING
E INSULATION FOR STUCCO SYSTEM

PLOT SCALE: PLOT DATE:


2/9/2022 4:26:22
16 UNO 50

SOLICITATION NO.:
8.111 - PAINTED

SA-480530-1$-SA530DT.dwg
PM
CONTRACT NO.:
GALVANIZED STEEL
DOOR FRAME, UNO

ISSUE DATE:
49 7.188 - SEALANT
UNO

1:1
275 150
425

FILE NO.:
INTERIOR EXTERIOR

SUBMITTED BY:
W. LOCKWOOD
J. BLANCHARD
DESIGN BY:

DRAWN BY:

A. HANKS
D

S. OKES
CKD BY:

ANSI D
SIZE:
HEAD DETAIL H4.1
D6

TRANSATLANTIC MIDDLE EAST DISTRICT


1 : 10

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
EXTERIOR

9.107 - CASING BEAD


FOR STUCCO SYSTEM
50 16 UNO

C 9.009 - 25 mm THICK
THREE COAT STUCCO
SYSTEM

8.035 - JAMB ANCHOR

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


150
UNO
49

EXTERIOR DOOR DETAILS, H4.1 & J4.1


THAAD STANDARD FACILITIES
425

VARIOUS LOCATIONS, KSA

STANDARD DETAILS
275

SA-480530
B
EW-2A

GRAPHIC SCALES

INTERIOR

PROVIDE BULLET RESISTANT COMPONENTS AT


OPENING LOCATIONS IDENTIFIED IN DOOR
SCHEDULES TO BE BULLET RESISTANT.
PROVIDE RABBET AND STOP IN WIDTH AND
DEPTHS TO ACCOMODATE BULLET RESISTANT
2/9/2022 4:26:22 PM

COMPONENTS.
A 0 200 400 800
SHEET ID
SCALE: 1:10 $
JAMB DETAIL J4.1 SA530
A6 1 : 10
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

DATE
5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

DESCRIPTION
F

COL
COL

EXT. WALL ASSEMBLY EXT. WALL ASSEMBLY


SEE FLOOR PLAN 9.009 - 25 mm THICK THREE COAT SEE FLOOR PLAN
STUCCO SYSTEM

MARK
225 225
7.267 - RIGID BOARD WALL 4.033 - 100 mm CONCRETE
MASONRY UNIT
E INSULATION, RSI=2.29 (R-13)
MINIMUM 7.267 - RIGID BOARD WALL
3.007 - REINFORCED 7.016 - FLUID-APPLIED INSULATION, RSI=2.29 (R-13)

PLOT SCALE: PLOT DATE:


COL

2/9/2022 4:27:05
CAST-IN-PLACE MEMBRANE AIR BARRIER MINIMUM
SEE FLOOR PLAN FOR WALL TYPE CONCRETE WALL, SEE 7.016 - FLUID-APPLIED
4.012 - SCREW TYPE VENEER

SOLICITATION NO.:

SA-480530-1$-SA531DT.dwg
STRUCTURAL MEMBRANE AIR BARRIER
ANCHORS. REFER TO

PM
CONTRACT NO.:
DRAWINGS
200 SPECIFICATION SECTION 04 20 4.012 - SCREW TYPE VENEER

ISSUE DATE:
8.076 - DOOR AND 8.135 - THRESHOLD AS 00 FOR SPACING ANCHORS. REFER TO
FRAME AS SCHEDULED SCHEDULED - SET IN SEALANT SPECIFICATION SECTION 04 20

1:1
7.039 - STRIP TRANSITION 00 FOR SPACING
7.060 - BACKER ROD AND JOINT MEMBRANE ONTO FLASHING TO
SEALANT MAINTAIN AIR BARRIER 7.039 - STRIP TRANSITION
3.124 - PREMOLDED JOINT CONTINUITY MEMBRANE ONTO FLASHING TO
12.021 - WALK-OFF ENTRY MAT. FILLER STRIP 4.013 - CAVITY NET / MORTAR MAINTAIN AIR BARRIER
COORDINATE SLAB DEPRESSION CONTROL DEVICE CONTINUITY

FILE NO.:
DEPTH WITH APPROVED WALK-OFF EXTERIOR

M. MacEACHERN
4.013 - CAVITY NET / MORTAR

SUBMITTED BY:
ENTRY MAT

W. RODRIGUEZ
7.042 - THRU-WALL FLASHING

C. SCORZELLI
GROUND FLOOR WITH WEEP VENTILATORS AT CONTROL DEVICE

DESIGN BY:

DRAWN BY:
25

A. HANKS
600 mm OC, TYP
D 7.042 - THRU-WALL FLASHING

CKD BY:
9.011 - 20 mm THICK

ANSI D
WITH WEEP VENTILATORS AT

SIZE:
9.024 - J-MOLD AROUND GYPSUM PLASTER
600 mm OC, TYP
OPENING, TYP
T.O. OPENING T.O. OPENING
50 13

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


7.084 - STAINLESS STEEL DRIP 7.084 - STAINLESS STEEL DRIP
305 +/- EDGE SET IN BED OF SEALANT
EDGE SET IN BED OF SEALANT 3.014 - GROUT SOLID,

WINCHESTER, VA 22602
NON-SHRINK GROUT, 5.220 - EXPOSED HOT DIPPED
5.220 - EXPOSED HOT DIPPED TYP GALVANIZED LINTEL TO BE
GALVANIZED LINTEL TO BE PAINTED TO MATCH COLOR OF
8.001 - HOLLOW METAL 200 200 PAINTED TO MATCH COLOR OF 200 200
DOOR AND FRAME STUCCO FINISHING SYSTEM
STUCCO FINISHING SYSTEM
7.063 - 13 mm BACKER ROD AND
7.063 - 13 mm BACKER ROD AND SEALANT EACH SIDE
SEALANT EACH SIDE

C
SILL DETAIL S2 HEAD DETAIL H2 HEAD DETAIL H1
D1 1 : 10 D4 1 : 10 D7 1 : 10

EXTERIOR DOOR DETAILS, H1 & J1 - H2 & J2, S1, S2


7.267 - RIGID BOARD 7.267 - RIGID BOARD
9.009 - 25 mm THICK

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


WALL INSULATION, WALL INSULATION,
RSI=2.29 (R-13) MINIMUM THREE COAT STUCCO 9.009 - 25 mm THICK
RSI=2.29 (R-13) MINIMUM
COL SYSTEM THREE COAT STUCCO
8.076 - DOOR AND FRAME AS 7.016 - FLUID-APPLIED 7.016 - FLUID-APPLIED SYSTEM

THAAD STANDARD FACILITIES


SEE FLOOR PLAN FOR WALL TYPE MEMBRANE AIR MEMBRANE AIR

VARIOUS LOCATIONS, KSA


SCHEDULED
BARRIER 7.060 - BACKER ROD AND JOINT BARRIER 7.060 - BACKER ROD AND JOINT

STANDARD DETAILS
SEALANT SEALANT
200
8.108 - METAL THRESHOLD AS

EXT. WALL ASSEMBLY

SA-480530
SCHEDULED

SEE FLOOR PLAN


200

200
EXT. WALL ASSEMBLY

225

225
B
SEE FLOOR PLAN

9.092 - FINISH FLOOR AS


COL

COL
SCHEDULED 200
EXTERIOR
GRAPHIC SCALES
200

200
7.060 - BACKER ROD AND JOINT
SEALANT

GROUND FLOOR

8.001 - HOLLOW METAL DOOR 9.011 - 20 mm THICK 8.001 - HOLLOW METAL DOOR
13 50
AND FRAME GYPSUM PLASTER AND FRAME
3.007 - REINFORCED
13 50 8.037 - ANCHORS, MIN 3 PER
CAST-IN-PLACE 8.037 - ANCHORS, MIN 3 PER
CONCRETE WALL, SEE JAMB JAMB
3.124 - PREMOLDED JOINT STRUCTURAL
FILLER STRIP DRAWINGS
2/9/2022 4:27:05 PM

A 0 200 400 800


SHEET ID
$
SILL DETAIL S1 JAMB DETAIL J2 JAMB DETAIL J1 SCALE: 1:10
A1 1 : 10 A4 1 : 10 A7 1 : 10
UNLESS OTHERWISE NOTED, LINEAR SA531
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

DATE
5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

PROVIDE BULLET RESISTANT COMPONENTS AT PROVIDE BULLET RESISTANT COMPONENTS AT


OPENING LOCATIONS IDENTIFIED IN DOOR OPENING LOCATIONS IDENTIFIED IN DOOR

DESCRIPTION
SCHEDULES TO BE BULLET RESISTANT. SCHEDULES TO BE BULLET RESISTANT.
F PROVIDE RABBET AND STOP IN WIDTH AND PROVIDE RABBET AND STOP IN WIDTH AND
DEPTHS TO ACCOMODATE BULLET RESISTANT DEPTHS TO ACCOMODATE BULLET RESISTANT
COMPONENTS. COMPONENTS.

EW-2
EW-2A
7.016 - FLUID-APPLIED
7.016 - FLUID-APPLIED MEMBRANE AIR BARRIER
MEMBRANE AIR BARRIER 9.107 - CASING BEAD
9.107 - CASING BEAD FOR STUCCO FOR STUCCO SYSTEM 9.009 - 25 mm THICK THREE COAT
SYSTEM 9.009 - 25 mm THICK THREE COAT STUCCO SYSTEM
STUCCO SYSTEM 8.079 - FILL FRAME WITH

MARK
MINERAL WOOL 9.106 - CORNER BEAD FOR
8.079 - FILL FRAME WITH 9.106 - CORNER BEAD FOR INSULATION STUCCO SYSTEM
MINERAL WOOL STUCCO SYSTEM
E INSULATION 4.018 - BOND BEAM, SEE
STRUCTURAL

(100 @ MOSQ)
DRAWINGS

(100 @ MOSQ)

PLOT SCALE: PLOT DATE:


2/9/2022 4:27:50
50
7.188 - SEALANT

16 UNO

50
16 UNO

SOLICITATION NO.:
7.188 - SEALANT

SA-480530-1$-SA532DT.dwg
PM
CONTRACT NO.:
8.111 - PAINTED 8.111 - PAINTED 49

ISSUE DATE:
GALVANIZED STEEL 49 GALVANIZED STEEL UNO
DOOR FRAME, UNO 9.108 - DRIP SCREED FOR DOOR FRAME, UNO 9.108 - DRIP SCREED FOR

1:1
UNO
STUCCO SYSTEM 105 150 75 STUCCO SYSTEM
100 150
7.188 - SEALANT
7.188 - SEALANT 330

FILE NO.:
SUBMITTED BY:
INTERIOR EXTERIOR INTERIOR EXTERIOR

DESIGN BY:

DRAWN BY:
S. MURPHY

A. HANKS
D

A. ORTIZ

E. OKES
CKD BY:

ANSI D
SIZE:
HEAD DETAIL H4 HEAD DETAIL H3
D3 D6

TRANSATLANTIC MIDDLE EAST DISTRICT


1 : 10 1 : 10

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
EXTERIOR EXTERIOR

9.107 - CASING BEAD FOR STUCCO 9.107 - CASING BEAD FOR STUCCO
C SYSTEM SYSTEM
50 16 UNO

9.009 - 25 mm THICK THREE COAT 50 16 UNO 9.009 - 25 mm THICK THREE COAT


STUCCO SYSTEM 9.106 - CORNER BEAD FOR STUCCO SYSTEM
STUCCO SYSTEM 9.106 - CORNER BEAD
7.016 - FLUID-APPLIED MEMBRANE FOR STUCCO SYSTEM
7.016 - FLUID-APPLIED MEMBRANE 7.188 - SEALANT AIR BARRIER
AIR BARRIER 7.188 - SEALANT
8.111 - PAINTED GALVANIZED
STEEL DOOR FRAME, UNO 8.035 - JAMB ANCHOR 8.111 - PAINTED GALVANIZED
8.035 - JAMB ANCHOR STEEL DOOR FRAME, UNO

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)

EXTERIOR DOOR DETAILS, H3 & J3 - H4 & J4


66
75

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
UNO

150
150
UNO

316
49
325
49

STANDARD DETAILS
SA-480530
100
100

B
7.016 - FLUID-APPLIED MEMBRANE
7.016 - FLUID-APPLIED MEMBRANE AIR BARRIER 8.079 - FILL FRAME WITH
AIR BARRIER 8.079 - FILL FRAME WITH MINERAL WOOL INSULATION
EW-2A
MINERAL WOOL INSULATION
EW-2
GRAPHIC SCALES
7.188 - SEALANT
7.188 - SEALANT
INTERIOR INTERIOR

PROVIDE BULLET RESISTANT COMPONENTS AT PROVIDE BULLET RESISTANT COMPONENTS AT


OPENING LOCATIONS IDENTIFIED IN DOOR OPENING LOCATIONS IDENTIFIED IN DOOR
SCHEDULES TO BE BULLET RESISTANT. SCHEDULES TO BE BULLET RESISTANT.
PROVIDE RABBET AND STOP IN WIDTH AND PROVIDE RABBET AND STOP IN WIDTH AND
DEPTHS TO ACCOMODATE BULLET RESISTANT DEPTHS TO ACCOMODATE BULLET RESISTANT
2/9/2022 4:27:50 PM

COMPONENTS. COMPONENTS.
A 0 200 400 800
SHEET ID
JAMB DETAIL J4 JAMB DETAIL J3 SCALE: 1:10 $
A3 1 : 10 A6 1 : 10
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA532
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

DATE
5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

DESCRIPTION
F

MARK
INTERIOR EXTERIOR

E 3.007 - REINFORCED
INTERIOR EXTERIOR CAST-IN-PLACE CONCRETE
WALL, SEE STRUCTURAL

PLOT SCALE: PLOT DATE:


2/9/2022 4:28:27
9.011 - 20 mm THICK GYPSUM DRAWINGS
PLASTER 7.015 - FLUID-APPLIED, VAPOR

SOLICITATION NO.:
9.009 - 25 mm THICK THREE COAT

SA-480530-1$-SA533DT.dwg
4.002 - 200 mm CONCRETE RETARDING AIR BARRIER

PM
CONTRACT NO.:
MASONRY UNIT STUCCO SYSTEM
EW-4A

ISSUE DATE:
4.024 - MASONRY
LINTEL, SEE EW-5 9.009 - 25 mm THICK THREE COAT
STRUCTURAL STUCCO SYSTEM

1:1
7.015 - FLUID-APPLIED, VAPOR 7.060 - BACKER ROD AND JOINT
DRAWINGS
RETARDING AIR BARRIER SEALANT

15
9.113 - METAL DRIP
7.060 - BACKER ROD AND JOINT FLASHING FOR STUCCO

50
SEALANT 9.113 - METAL DRIP SYSTEM

FILE NO.:
FLASHING FOR STUCCO

50 15

SUBMITTED BY:
SYSTEM 6.015 - SHIM AS REQUIRED

J. BLANCHARD

J. BLANCHARD
7.063 - 13 mm BACKER ROD AND

DESIGN BY:

DRAWN BY:
SEALANT EACH SIDE

A. HANKS
3.014 - GROUT SOLID,
D

CKD BY:
Checker
7.060 - BACKER ROD AND JOINT

ANSI D
NON-SHRINK GROUT, TYP

SIZE:
8.001 - HOLLOW METAL DOOR SEALANT 8.001 - HOLLOW METAL DOOR
AND FRAME AND FRAME

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


150 70

WINCHESTER, VA 22602
185 75

HEAD DETAIL H6 HEAD DETAIL H5


C3 1 : 10 C6 1 : 10

9.009 - 25 mm THICK THREE COAT


STUCCO SYSTEM EXTERIOR
EXTERIOR

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


9.009 - 25 mm THICK THREE COAT

EXTERIOR DOOR DETAILS, H5 & J5 - H6 & J6


7.015 - FLUID-APPLIED, VAPOR
STUCCO SYSTEM
RETARDING AIR BARRIER
8.001 - HOLLOW METAL 7.060 - BACKER ROD AND JOINT
3.007 - REINFORCED

THAAD STANDARD FACILITIES


DOOR AND FRAME SEALANT

VARIOUS LOCATIONS, KSA


CAST-IN-PLACE
EW-5 6.015 - SHIM AS REQUIRED CONCRETE WALL, SEE

STANDARD DETAILS
EW-4A 8.001 - HOLLOW METAL DOOR
8.037 - ANCHORS, MIN 3 STRUCTURAL AND FRAME
PER JAMB DRAWINGS

SA-480530
70

75
50
150

GRAPHIC SCALES

185
5 50

4.002 - 200 mm CONCRETE 50


8.037 - ANCHORS, MIN 3
MASONRY UNIT PER JAMB
9.011 - 20 mm THICK GYPSUM
4.026 - CMU JAMBS TO BE FULLY PLASTER
GROUTED WITH VERTICAL
INTERIOR REINFORCING BARS IN EACH
CELL. REFER TO STRUCTURAL 7.060 - BACKER ROD AND JOINT
SEALANT
2/9/2022 4:28:27 PM

INTERIOR
A 0 200 400 800
SHEET ID
$
JAMB DETAIL J6 JAMB DETAIL J5 SCALE: 1:10
A3 1 : 10 A6 1 : 10
UNLESS OTHERWISE NOTED, LINEAR SA533
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

DATE
5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

DESCRIPTION
F

COL

MARK
E EXT. WALL ASSEMBLY
SEE FLOOR PLAN
4.033 - 100 mm CONCRETE

PLOT SCALE: PLOT DATE:


2/9/2022 4:28:49
MASONRY UNIT
7.267 - RIGID BOARD WALL

SOLICITATION NO.:

SA-480530-1$-SA534DT.dwg
PM
INSULATION, RSI=2.29 (R-13)

CONTRACT NO.:
MINIMUM

ISSUE DATE:
7.016 - FLUID-APPLIED
MEMBRANE AIR BARRIER

1:1
4.012 - SCREW TYPE VENEER
ANCHORS. REFER TO
SPECIFICATION SECTION 04 20
00 FOR SPACING

FILE NO.:
7.039 - STRIP TRANSITION
MEMBRANE ONTO FLASHING TO

M. MacEACHERN
SUBMITTED BY:
W. RODRIGUEZ
MAINTAIN AIR BARRIER

C. SCORZELLI
DESIGN BY:

DRAWN BY:
CONTINUITY

A. HANKS
D

CKD BY:
4.013 - CAVITY NET / MORTAR

ANSI D
SIZE:
CONTROL DEVICE
7.042 - THRU-WALL FLASHING
9.011 - 20 mm THICK WITH WEEP VENTILATORS AT
GYPSUM PLASTER

TRANSATLANTIC MIDDLE EAST DISTRICT


600 mm OC, TYP

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


T.O. OPENING

WINCHESTER, VA 22602
7.084 - STAINLESS STEEL DRIP
EDGE SET IN BED OF SEALANT
8.013 - ALUMINUM
FRAMED ENTRANCE 5.155 - GALVANIZED STEEL
DOOR SUPPORT ANGLE WITH SLOTTED
200
CONNECTIONS, ANCHORED TO
CMU WALL
7.063 - 13 mm BACKER ROD AND
SEALANT EACH SIDE
C

HEAD DETAIL H8
D4 1 : 10

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)

EXTERIOR DOOR DETAILS, H7 & J7 - H8 & J8


4.033 - 100 mm CONCRETE

THAAD STANDARD FACILITIES


MASONRY UNIT

VARIOUS LOCATIONS, KSA


7.267 - RIGID BOARD

STANDARD DETAILS
WALL INSULATION,
RSI=2.29 (R-13) MINIMUM 9.009 - 25 mm THICK
THREE COAT STUCCO

SA-480530
7.016 - FLUID-APPLIED SYSTEM
B MEMBRANE AIR
BARRIER 7.060 - BACKER ROD AND JOINT
SEALANT

GRAPHIC SCALES
EXT. WALL ASSEMBLY
SEE FLOOR PLAN

225

COL

9.011 - 20 mm THICK
2/9/2022 4:28:49 PM

GYPSUM PLASTER 8.013 - ALUMINUM FRAMED


A ENTRANCE DOOR 0 200 400 800
SHEET ID
JAMB DETAIL J8 SCALE: 1:10 $
A4 1 : 10
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA534
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

DATE
5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

DESCRIPTION
F

COL

4.033 - 100 mm CONCRETE


EXT. WALL ASSEMBLY MASONRY UNIT
7.016 - FLUID-APPLIED
SEE FLOOR PLAN 9.009 - 25 mm THICK THREE COAT EW-2A MEMBRANE AIR BARRIER
STUCCO SYSTEM
3.007 - REINFORCED 9.009 - 25 mm THICK THREE COAT
CAST-IN-PLACE 7.267 - RIGID BOARD WALL
STUCCO SYSTEM
CONCRETE WALL, SEE INSULATION, RSI=2.29 (R-13)
STRUCTURAL MINIMUM 7.248 - AIR BARRIER TRANSITION

MARK
DRAWINGS 7.016 - FLUID-APPLIED MEMBRANE. LAP MEMBRANE
MEMBRANE AIR BARRIER OVER STUCCO DRIP FLASHING
E 8.079 - FILL FRAME WITH
BY 50 mm MIN.
8.009 - INSULATED 4.012 - SCREW TYPE VENEER
ANCHORS. REFER TO MINERAL WOOL 9.113 - METAL DRIP FLASHING
OVERHEAD COILING

PLOT SCALE: PLOT DATE:


INSULATION FOR STUCCO SYSTEM

2/9/2022 4:29:22
DOOR SPECIFICATION SECTION 04 20
00 FOR SPACING

SOLICITATION NO.:

SA-480530-1$-SA535DT.dwg
7.039 - STRIP TRANSITION

100

PM
CONTRACT NO.:
MEMBRANE ONTO FLASHING TO
7.188 - SEALANT

ISSUE DATE:
MAINTAIN AIR BARRIER
CONTINUITY

16
8.111 - PAINTED

1:1
4.013 - CAVITY NET / MORTAR GALVANIZED STEEL
CONTROL DEVICE 7.188 - SEALANT
DOOR FRAME, UNO
49
7.042 - THRU-WALL FLASHING 175 150
WITH WEEP VENTILATORS AT
600 mm OC, TYP 325

FILE NO.:
M. MacEACHERN
9.024 - J-MOLD AROUND

SUBMITTED BY:
W. RODRIGUEZ
C. SCORZELLI
OPENING, TYP

DESIGN BY:

DRAWN BY:

A. HANKS
D T.O. OPENING INTERIOR EXTERIOR

CKD BY:

ANSI D
SIZE:
7.084 - STAINLESS STEEL DRIP
EDGE SET IN BED OF SEALANT

TRANSATLANTIC MIDDLE EAST DISTRICT


5.191 - CONT GALVANIZED STEEL
HEAD DETAIL H9

US ARMY CORPS OF ENGINEERS


D6

201 PRINCE FREDERICK DRIVE,


SHELF ANGLE ANCHORED TO
CONC. WALL, SEE STRUCTURAL 1 : 10

WINCHESTER, VA 22602
DRAWINGS

HEAD DETAIL H10


D4 1 : 10

C
4.033 - 100 mm
CONCRETE MASONRY
UNIT
7.267 - RIGID BOARD 9.009 - 25 mm THICK
WALL INSULATION, THREE COAT STUCCO
RSI=2.29 (R-13) MINIMUM SYSTEM

7.016 - FLUID-APPLIED 5.037 - 75X75X8 mm GALVANIZED


MEMBRANE AIR STEEL ANGLE ANCHORED TO

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


BARRIER BACK-UP WALL - PAINTED

EXTERIOR DOOR DETAILS, J9 - H10 & J10


THAAD STANDARD FACILITIES
VARIOUS LOCATIONS, KSA
5.036 - 6 mm THICK GALVANIZED
EXT. WALL ASSEMBLY

STEEL PLATE WELDED TO

STANDARD DETAILS
SEE FLOOR PLAN

ANGLES - PAINTED

SA-480530
COL

8.009 - INSULATED OVERHEAD


GRAPHIC SCALES
COILING DOOR

3.007 - REINFORCED
CAST-IN-PLACE
CONCRETE WALL, SEE
STRUCTURAL
DRAWINGS
8.034 - OVERHEAD COILING
DOOR TRACK
2/9/2022 4:29:22 PM

A 0 200 400 800


SHEET ID
SCALE: 1:10 $
JAMB DETAIL J10
A4 1 : 10 UNLESS OTHERWISE NOTED, LINEAR SA535
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

DATE
5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

DESCRIPTION
F INTERIOR EXTERIOR
INTERIOR EXTERIOR

EW-2A
9.009 - 25 mm THICK
THREE COAT STUCCO 9.009 - 25 mm THICK 9.009 - 25 mm THICK
EW-5 THREE COAT STUCCO EW-2
SYSTEM THREE COAT STUCCO
8.009 - INSULATED SYSTEM SYSTEM
OVERHEAD COILING 8.009 - INSULATED 8.009 - INSULATED
DOOR 7.016 - FLUID-APPLIED OVERHEAD COILING 7.016 - FLUID-APPLIED 7.016 - FLUID-APPLIED
OVERHEAD COILING
MEMBRANE AIR DOOR MEMBRANE AIR MEMBRANE AIR
DOOR
BARRIER BARRIER BARRIER

4.002 - 200 mm 4.002 - 200 mm


3.007 - REINFORCED
CONCRETE MASONRY CONCRETE MASONRY
CAST-IN-PLACE
UNIT UNIT
CONCRETE WALL, SEE
STRUCTURAL

MARK
4.024 - MASONRY 4.024 - MASONRY
DRAWINGS
LINTEL, SEE LINTEL, SEE
E STRUCTURAL
DRAWINGS
STRUCTURAL
9.113 - METAL DRIP 9.113 - METAL DRIP DRAWINGS
9.113 - METAL DRIP
FLASHING FOR STUCCO FLASHING FOR STUCCO FLASHING FOR STUCCO

PLOT SCALE: PLOT DATE:


2/9/2022 4:30:21
SYSTEM SYSTEM SYSTEM

SOLICITATION NO.:

SA-480530-1$-SA536DT.dwg
75

75

PM
75
T.O. OPENING

CONTRACT NO.:
T.O. OPENING

ISSUE DATE:

1:1
225 7.062 - CONTINUOUS 7.062 - CONTINUOUS 7.062 - CONTINUOUS
SEALANT, TYP 215 SEALANT, TYP 215 SEALANT, TYP
8.034 - OVERHEAD 8.034 - OVERHEAD
8.034 - OVERHEAD COILING DOOR TRACK
5.210 - PAINTED 10 mm 5.210 - PAINTED 10 mm COILING DOOR TRACK
COILING DOOR TRACK 5.210 - PAINTED 10 mm
THICK STEEL BENT THICK STEEL BENT THICK STEEL BENT
PLATE W/ (2) 13 DIA, PLATE W/ (2) 13 DIA,

FILE NO.:
PLATE W/ (2) 13 DIA,
POST-INSTALLED POST-INSTALLED POST-INSTALLED

M. CUNNINGHAM
SUBMITTED BY:
EPOXY ANCHORS AT

J. BLANCHARD
EPOXY ANCHORS AT EPOXY ANCHORS AT
450 OC, 125 MIN EMBED

J. HOLLAND
DESIGN BY:

DRAWN BY:
450 OC, 125 MIN EMBED 450 OC, 125 MIN EMBED

A. HANKS
D

CKD BY:

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
HEAD DETAIL H12 HEAD DETAIL H11A HEAD DETAIL H11

US ARMY CORPS OF ENGINEERS


D1 D4 D6

201 PRINCE FREDERICK DRIVE,


1 : 10 1 : 10 1 : 10

WINCHESTER, VA 22602
C
EXTERIOR
EXTERIOR
9.009 - 25 mm THICK
THREE COAT STUCCO 9.009 - 25 mm THICK 9.009 - 25 mm THICK
SYSTEM THREE COAT STUCCO THREE COAT STUCCO
9.107 - CASING BEAD SYSTEM 9.107 - CASING BEAD SYSTEM 9.107 - CASING BEAD
7.016 - FLUID-APPLIED FOR STUCCO SYSTEM FOR STUCCO SYSTEM FOR STUCCO SYSTEM
MEMBRANE AIR 7.016 - FLUID-APPLIED 7.016 - FLUID-APPLIED
BARRIER MEMBRANE AIR MEMBRANE AIR
3.007 - REINFORCED BARRIER BARRIER

EXTERIOR DOOR DETAILS, H11 &J11 - H12 & J12


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
CAST-IN-PLACE 7.062 - CONTINUOUS 7.062 - CONTINUOUS 7.062 - CONTINUOUS
75 4.002 - 200 mm 75 75
CONCRETE WALL, SEE SEALANT, TYP SEALANT, TYP 4.002 - 200 mm SEALANT, TYP
STRUCTURAL CONCRETE MASONRY CONCRETE MASONRY
UNIT 5.210 - PAINTED 10 mm UNIT

THAAD STANDARD FACILITIES


DRAWINGS
THICK STEEL BENT

VARIOUS LOCATIONS, KSA


5.210 - PAINTED 10 mm PLATE W/ (2) 13 DIA,

STANDARD DETAILS
POST-INSTALLED 5.210 - PAINTED 10 mm
THICK STEEL BENT
EPOXY ANCHORS AT THICK STEEL BENT
PLATE W/ (2) 13 DIA,
215

SA-480530
PLATE W/ (2) 13 DIA,

215
225

POST-INSTALLED 450 OC, 125 MIN EMBED


B EPOXY ANCHORS AT
POST-INSTALLED
EPOXY ANCHORS AT
450 OC, 125 MIN EMBED 8.009 - INSULATED
OVERHEAD COILING 450 OC, 125 MIN EMBED
DOOR
EW-5 GRAPHIC SCALES
EW-2A EW-2
8.009 - INSULATED
8.009 - INSULATED
OVERHEAD COILING
8.034 - OVERHEAD 8.034 - OVERHEAD 8.034 - OVERHEAD OVERHEAD COILING
DOOR
COILING DOOR TRACK COILING DOOR TRACK COILING DOOR TRACK DOOR
INTERIOR (BY OVERHEAD DOOR MFR) (BY OVERHEAD DOOR MFR) INTERIOR
(BY OVERHEAD DOOR MFR)
2/9/2022 4:30:21 PM

A 0 200 400 800


SHEET ID
JAMB DETAIL J12 JAMB DETAIL J11A JAMB DETAIL J11
A1 1 : 10 A4 1 : 10 A6 1 : 10 SCALE: 1:10 $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA536
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


240 1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
HEAD CONDITION AT SIDELIGHT HEAD CONDITION AT SIDELIGHT
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
3.007 - REINFORCED SYMBOLS.
EW-2 7.016 - FLUID-APPLIED Middle East District
CAST-IN-PLACE CONCRETE MEMBRANE AIR BARRIER
G 9.011 - 20 mm THICK GYPSUM WALL, SEE STRUCTURAL 8.079 - FILL FRAME WITH
3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.
PLASTER DRAWINGS MINERAL WOOL 9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM 4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.
9.011 - 20 mm THICK GYPSUM INSULATION

DATE
9.042 - CASING BEAD GYPSUM PLASTER
4.018 - BOND BEAM, SEE 9.106 - CORNER BEAD FOR 5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.
PLASTERING SYSTEM 9.042 - CASING BEAD GYPSUM STUCCO SYSTEM
PLASTERING SYSTEM STRUCTURAL
7.188 - SEALANT DRAWINGS

50
50
7.188 - SEALANT
8.113 - PAINTED GALVANIZED 7.188 - SEALANT
BULLET RESISTANT STEEL DOOR

16
16
FRAME 8.111 - PAINTED 9.108 - DRIP SCREED FOR
8.078 - FIELD APPLIED STEEL GALVANIZED STEEL STUCCO SYSTEM
GLAZING STOP DOOR FRAME, UNO 100 150
49 142 49
8.077 - GLAZING AS SCHEDULED, 7.188 - SEALANT
240 REFER TO DOOR SCHEDULE 325

49 52 49

DESCRIPTION
8.077 - GLAZING AS SCHEDULED, 8.078 - FIELD APPLIED STEEL 8.077 - GLAZING AS SCHEDULED,
F REFER TO DOOR SCHEDULE GLAZING STOP REFER TO DOOR SCHEDULE
8.078 - FIELD APPLIED STEEL

16
16
GLAZING STOP
8.113 - PAINTED GALVANIZED

50
8.111 - PAINTED GALVANIZED

50
BULLET RESISTANT STEEL DOOR STEEL DOOR FRAME, UNO
FRAME

16
16
8.078 - FIELD APPLIED STEEL
GLAZING STOP 8.078 - FIELD APPLIED STEEL
GLAZING STOP
49 142 49 8.077 - GLAZING AS SCHEDULED, 8.077 - GLAZING AS SCHEDULED,
REFER TO DOOR SCHEDULE 150 REFER TO DOOR SCHEDULE
240 HEAD CONDITION AT DOOR
HEAD CONDITION AT DOOR

240 EW-2A

MARK
7.016 - FLUID-APPLIED
3.007 - REINFORCED MEMBRANE AIR BARRIER
9.011 - 20 mm THICK GYPSUM CAST-IN-PLACE
E PLASTER
3.007 - REINFORCED
CAST-IN-PLACE CONCRETE CONCRETE WALL, SEE 9.009 - 25 mm THICK THREE COAT
WALL, SEE STRUCTURAL STRUCTURAL STUCCO SYSTEM
DRAWINGS

PLOT SCALE: PLOT DATE:


DRAWINGS

2/9/2022 4:31:04
9.042 - CASING BEAD GYPSUM 9.106 - CORNER BEAD FOR
8.079 - FILL FRAME WITH
PLASTERING SYSTEM 9.011 - 20 mm THICK GYPSUM STUCCO SYSTEM
MINERAL WOOL

SOLICITATION NO.:
PLASTER

SA-480530-1$-SA537DT.dwg
INSULATION

PM
CONTRACT NO.:
50
7.188 - SEALANT
9.042 - CASING BEAD GYPSUM

ISSUE DATE:
50
PLASTERING SYSTEM

1:1
7.188 - SEALANT

16
7.188 - SEALANT

16
8.111 - PAINTED 100 150 9.108 - DRIP SCREED FOR
8.113 - PAINTED GALVANIZED
GALVANIZED STEEL STUCCO SYSTEM
49 142 49 BULLET RESISTANT STEEL DOOR
DOOR FRAME, UNO 325
FRAME 7.188 - SEALANT

FILE NO.:
240

M. CUNNINGHAM
SUBMITTED BY:
J. BLANCHARD
INTERIOR PROTECTED ROOM INTERIOR
INTERIOR EXTERIOR

J. HOLLAND
DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
SIZE:
HEAD DETAIL H14 HEAD DETAIL H13

TRANSATLANTIC MIDDLE EAST DISTRICT


D3 D6

US ARMY CORPS OF ENGINEERS


1 : 10 1 : 10

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
INTERIOR EXTERIOR
7.188 - SEALANT
9.042 - CASING BEAD GYPSUM
PLASTERING SYSTEM 8.113 - PAINTED GALVANIZED 9.106 - CORNER BEAD
BULLET RESISTANT STEEL DOOR FOR STUCCO SYSTEM
C 9.011 - 20 mm THICK GYPSUM FRAME 7.188 - SEALANT
PLASTER 9.107 - CASING BEAD
8.078 - FIELD APPLIED STEEL FOR STUCCO SYSTEM
8.035 - JAMB ANCHOR GLAZING STOP 8.079 - FILL FRAME WITH
MINERAL WOOL INSULATION
8.077 - GLAZING AS SCHEDULED, 9.009 - 25 mm THICK
3.007 - REINFORCED THREE COAT STUCCO
CAST-IN-PLACE REFER TO DOOR SCHEDULE 8.111 - PAINTED GALVANIZED
SYSTEM STEEL DOOR FRAME, UNO
CONCRETE WALL, SEE
STRUCTURAL 8.078 - FIELD APPLIED STEEL 7.016 - FLUID-APPLIED 50 16
GLAZING STOP 16 50 16
DRAWINGS MEMBRANE AIR

EXTERIOR DOOR DETAILS, H13 & J13 - H14 & J14


BARRIER

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


49
49

8.035 - JAMB ANCHOR


142
240
240

142
240

8.111 - PAINTED GALVANIZED

THAAD STANDARD FACILITIES


STEEL DOOR FRAME, UNO

VARIOUS LOCATIONS, KSA


49
49
49

STANDARD DETAILS
150

150
52
325

SA-480530
B 9.011 - 20 mm THICK GYPSUM
PLASTER

100

49
8.079 - FILL FRAME WITH
9.042 - CASING BEAD GYPSUM 7.016 - FLUID-APPLIED MINERAL WOOL INSULATION
PLASTERING SYSTEM MEMBRANE AIR
50 16 16 50 16
BARRIER 8.078 - FIELD APPLIED STEEL GRAPHIC SCALES
7.188 - SEALANT GLAZING STOP
EW-2A 8.077 - GLAZING AS SCHEDULED,
REFER TO DOOR SCHEDULE
INTERIOR PROTECTED ROOM 8.078 - FIELD APPLIED STEEL
GLAZING STOP

7.188 - SEALANT

INTERIOR
2/9/2022 4:31:04 PM

A 0 200 400 800


SHEET ID
SCALE: 1:10 $
JAMB DETAIL J14 JAMB DETAIL J13
A3 1 : 10 A6 1 : 10 UNLESS OTHERWISE NOTED, LINEAR SA537
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA602, SA603 AND SA604 FOR INTERIOR PARTITION TYPES.

4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

DATE
5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

DESCRIPTION
F

240
9.011 - 20 mm THICK GYPSUM CL
PLASTER
4.018 - BOND BEAM, SEE
STRUCTURAL DRAWINGS 4.002 - 200 mm CONCRETE

MARK
MASONRY UNIT
9.042 - CASING BEAD GYPSUM
PLASTERING SYSTEM 9.011 - 20 mm THICK GYPSUM 9.011 - 20 mm THICK GYPSUM
E PLASTER PLASTER
7.188 - SEALANT
9.042 - CASING BEAD GYPSUM

50
4.022 - CONCRETE MASONRY

PLOT SCALE: PLOT DATE:


2/9/2022 4:31:48
PLASTERING SYSTEM PARTITION AS SCHEDULED
7.188 - SEALANT

SOLICITATION NO.:
4.024 - MASONRY LINTEL, SEE

SA-480530-1$-SA538DT.dwg
PM
16

CONTRACT NO.:
STRUCTURAL DRAWINGS
8.111 - PAINTED GALVANIZED

ISSUE DATE:
49 142 49 STEEL DOOR FRAME, UNO 6.015 - SHIM AS REQUIRED

1:1
AS SCHED
50 OR 100
240

FILE NO.:
INTERIOR INTERIOR 7.060 - BACKER ROD
7.060 - BACKER ROD AND JOINT

M. MacEACHERN
AND JOINT SEALANT

SUBMITTED BY:
W. RODRIGUEZ
SEALANT

C. SCORZELLI
DESIGN BY:

DRAWN BY:
8.001 - HOLLOW METAL DOOR

A. HANKS
D

CKD BY:
EQ EQ AND FRAME

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
HEAD DETAIL H16 HEAD DETAIL H15

US ARMY CORPS OF ENGINEERS


D3 D7

201 PRINCE FREDERICK DRIVE,


1 : 10 1 : 10

WINCHESTER, VA 22602
INTERIOR

C 9.042 - CASING BEAD GYPSUM


PLASTERING SYSTEM

9.011 - 20 mm THICK GYPSUM 7.188 - SEALANT


PLASTER

8.035 - JAMB ANCHOR 8.111 - PAINTED


GALVANIZED STEEL
4.002 - 200 mm DOOR FRAME, UNO
4.022 - CONCRETE MASONRY

INTERIOR DOOR DETAILS, H15 & J15 - H16 & J16


CONCRETE MASONRY

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


PARTITION AS SCHEDULED
UNIT
6.015 - SHIM AS REQUIRED
8.001 - HOLLOW METAL

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
49

DOOR AND FRAME

STANDARD DETAILS
8.037 - ANCHORS, MIN 3
240

142
240

PER JAMB

SA-480530
B
49

EQ
CL
9.011 - 20 mm THICK GYPSUM
GRAPHIC SCALES

EQ
PLASTER

9.042 - CASING BEAD GYPSUM


PLASTERING SYSTEM 7.063 - 13 mm BACKER ROD AND
SEALANT EACH SIDE
7.188 - SEALANT 50 16
4.026 - CMU JAMBS TO BE FULLY
GROUTED WITH VERTICAL
REINFORCING BARS IN EACH
CELL. REFER TO STRUCTURAL

9.011 - 20 mm THICK GYPSUM


INTERIOR
2/9/2022 4:31:48 PM

PLASTER
A 0 200 400 800
SHEET ID
SCALE: 1:10 $
JAMB DETAIL J16 JAMB DETAIL J15
A3 1 : 10 A7 1 : 10 UNLESS OTHERWISE NOTED, LINEAR SA538
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA602, SA603 AND SA604 FOR INTERIOR PARTITION TYPES.

4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

DATE
5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

DESCRIPTION
F

240
9.011 - 20 mm THICK GYPSUM
PLASTER

CL 4.018 - BOND BEAM, SEE


STRUCTURAL DRAWINGS 4.002 - 200 mm CONCRETE
MASONRY UNIT
9.042 - CASING BEAD GYPSUM
9.011 - 20 mm THICK GYPSUM
PLASTERING SYSTEM 9.011 - 20 mm THICK GYPSUM
PLASTER
PLASTER
4.002 - 200 mm CONCRETE 7.188 - SEALANT
9.042 - CASING BEAD GYPSUM

100

MARK
MASONRY UNIT PLASTERING SYSTEM

7.188 - SEALANT
E 4.024 - MASONRY LINTEL, SEE
STRUCTURAL DRAWINGS
8.111 - PAINTED GALVANIZED

16
STEEL DOOR FRAME, UNO

PLOT SCALE: PLOT DATE:


2/9/2022 4:32:23
7.060 - BACKER ROD 7.060 - BACKER ROD AND JOINT
49 142 49
AND JOINT SEALANT SEALANT

SOLICITATION NO.:

SA-480530-1$-SA539DT.dwg
8

PM
CONTRACT NO.:
240

50

ISSUE DATE:
8.001 - HOLLOW METAL DOOR AND

1:1
FRAME INTERIOR INTERIOR

230

FILE NO.:
M. CUNNINGHAM
SUBMITTED BY:
J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
SIZE:
HEAD DETAIL H18 HEAD DETAIL H17

TRANSATLANTIC MIDDLE EAST DISTRICT


D3 1 : 10 D6 1 : 10

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
C 4.002 - 200 mm CONCRETE MASONRY
UNIT

7.060 - BACKER ROD AND JOINT


SEALANT

8.037 - ANCHORS, MIN 3 PER JAMB


8 50

INTERIOR DOOR DETAILS, H17 & J17 - H18 & J18


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
8.001 - HOLLOW METAL
DOOR AND FRAME

THAAD STANDARD FACILITIES


230

VARIOUS LOCATIONS, KSA


CL

STANDARD DETAILS
8.037 - ANCHORS, MIN 3

SA-480530
PER JAMB
B
7.060 - BACKER ROD AND JOINT
SEALANT

4.026 - CMU JAMBS TO BE FULLY GRAPHIC SCALES


GROUTED WITH VERTICAL
REINFORCING BARS IN EACH CELL.
REFER TO STRUCTURAL

9.011 - 20 mm THICK GYPSUM


PLASTER
2/9/2022 4:32:23 PM

A 0 200 400 800


SHEET ID
HEAD DETAIL J18 $
A3 1 : 10
SCALE: 1:10

UNLESS OTHERWISE NOTED, LINEAR


DIMENSIONS ARE IN MILLIMETERS
SA539
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA602, SA603 AND SA604 FOR INTERIOR PARTITION TYPES.

4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

DATE
5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

235
9.011 - 20 mm THICK GYPSUM
PLASTER

4.024 - MASONRY LINTEL, SEE


STRUCTURAL DRAWINGS
7.060 - BACKER ROD AND JOINT
SEALANT

DESCRIPTION
7.060 - BACKER ROD AND JOINT
F SEALANT
8.118 - INTEGRAL COILING
COUNTER DOOR HOOD

8.117 - INTEGRAL COILING


COUNTER DOOR FRAME

CLEAR OPNG HEIGHT


8.032 - NON-INSULATED

MARK
OVERHEAD COILING 4.002 - 200 mm
DOOR CONCRETE MASONRY
8.120 - INTEGRAL COILING
E UNIT
COUNTER DOOR SILL

PLOT SCALE: PLOT DATE:


2/9/2022 4:33:07
SOLICITATION NO.:
7.060 - BACKER ROD AND JOINT

SA-480530-1$-SA540DT.dwg
4.024 - MASONRY

PM
CONTRACT NO.:
SEALANT
LINTEL, SEE 7.060 - BACKER ROD AND JOINT

ISSUE DATE:
STRUCTURAL 4.002 - 200 mm CONCRETE SEALANT
DRAWINGS MASONRY UNIT

1:1
7.062 - CONTINUOUS 9.011 - 20 mm THICK GYPSUM
SEALANT, TYP PLASTER

75
T.O. OPENING

FILE NO.:
M. CUNNINGHAM
SUBMITTED BY:
J. BLANCHARD
215

J. HOLLAND
DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
5.210 - PAINTED 10 mm THICK

SIZE:
8.034 - OVERHEAD
COILING DOOR TRACK
STEEL BENT PLATE W/ (2) 13 DIA,
HEAD/SILL DETAIL H19
POST-INSTALLED EPOXY
ANCHORS AT 450 OC, 125 MIN C6 1 : 10

TRANSATLANTIC MIDDLE EAST DISTRICT


EMBED

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
HEAD DETAIL H20
C4 1 : 10 8.117 - INTEGRAL COILING
COUNTER DOOR FRAME

8.120 - INTEGRAL COILING


C 7.060 - BACKER ROD AND JOINT COUNTER DOOR SILL
SEALANT
8.119 - INTEGRAL COILING COUNTER
9.011 - 20 mm THICK GYPSUM DOOR CURTAIN
PLASTER

7.062 - CONTINUOUS
SEALANT, TYP

INTERIOR DOOR DETAILS, H19 & J19 - H20 & J20


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
5.210 - PAINTED 10 mm THICK

235
4.002 - 200 mm STEEL BENT PLATE W/ (2) 13 DIA,
75

THAAD STANDARD FACILITIES


CONCRETE MASONRY POST-INSTALLED EPOXY

VARIOUS LOCATIONS, KSA


UNIT ANCHORS AT 450 OC, 125 MIN

STANDARD DETAILS
EMBED

SA-480530
B 8.032 - NON-INSULATED CLEAR OPNG WIDTH
215

OVERHEAD COILING DOOR 4.002 - 200 mm CONCRETE MASONRY


UNIT

7.060 - BACKER ROD AND JOINT GRAPHIC SCALES


SEALANT

8.034 - OVERHEAD
COILING DOOR TRACK
(BY OVERHEAD DOOR MFR)
2/9/2022 4:33:07 PM

A 0 200 400 800


SHEET ID
JAMB DETAIL J20 JAMB DETAIL J19
A4 1 : 10 A6 1 : 10
SCALE: 1:10 $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA540
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA602, SA603 AND SA604 FOR INTERIOR PARTITION TYPES.

4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

DATE
5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

DESCRIPTION
F

240
9.011 - 20 mm THICK GYPSUM
PLASTER
4.018 - BOND BEAM, SEE
STRUCTURAL DRAWINGS 4.002 - 200 mm CONCRETE
MASONRY UNIT
9.042 - CASING BEAD GYPSUM
PLASTERING SYSTEM 9.011 - 20 mm THICK GYPSUM

MARK
PLASTER
7.188 - SEALANT
9.042 - CASING BEAD GYPSUM

50
E PLASTERING SYSTEM

7.188 - SEALANT

PLOT SCALE: PLOT DATE:


2/9/2022 4:33:32
16
8.112 - STAINLESS STEEL DOOR

SOLICITATION NO.:
FRAME WITH TERMINATED

SA-480530-1$-SA541DT.dwg
49 142 49

PM
CONTRACT NO.:
STOPS

ISSUE DATE:
240

1:1
INTERIOR INTERIOR

FILE NO.:
M. CUNNINGHAM
SUBMITTED BY:
J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
SIZE:
HEAD DETAIL H22

TRANSATLANTIC MIDDLE EAST DISTRICT


D3

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


1 : 10

WINCHESTER, VA 22602
INTERIOR

9.042 - CASING BEAD GYPSUM


C PLASTERING SYSTEM

9.011 - 20 mm THICK GYPSUM 7.188 - SEALANT


PLASTER
8.112 - STAINLESS
8.035 - JAMB ANCHOR STEEL DOOR FRAME
WITH TERMINATED
4.002 - 200 mm STOPS
CONCRETE MASONRY
UNIT

INTERIOR DOOR DETAILS, H21 & J21 - H22 & J22


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
49

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
240

142
240

STANDARD DETAILS
49

SA-480530
B
9.011 - 20 mm THICK GYPSUM
PLASTER

9.042 - CASING BEAD GYPSUM GRAPHIC SCALES


PLASTERING SYSTEM

7.188 - SEALANT 50 16

INTERIOR
2/9/2022 4:33:32 PM

A 0 200 400 800


SHEET ID
JAMB DETAIL J22 SCALE: 1:10 $
A3 1 : 10
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA541
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA602, SA603 AND SA604 FOR INTERIOR PARTITION TYPES.

4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

DATE
5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

DESCRIPTION
F

4.024 - MASONRY
LINTEL, SEE
STRUCTURAL
DRAWINGS 4.002 - 200 mm CONCRETE
MASONRY UNIT
7.188 - SEALANT 9.011 - 20 mm THICK GYPSUM
PLASTER

9.042 - CASING BEAD GYPSUM

50
PLASTERING SYSTEM

MARK
7.188 - SEALANT

16
49 142 49 8.001 - HOLLOW METAL DOOR
E AND FRAME
3.014 - GROUT SOLID,
NON-SHRINK GROUT,

PLOT SCALE: PLOT DATE:


2/9/2022 4:33:59
TYP
240

SOLICITATION NO.:

SA-480530-1$-SA542DT.dwg
INTERIOR INTERIOR

PM
CONTRACT NO.:
ISSUE DATE:

1:1
FILE NO.:
M. CUNNINGHAM
SUBMITTED BY:
J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:
HEAD DETAIL H24

A. HANKS
D

CKD BY:

ANSI D
D6

SIZE:
1 : 10

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
C
9.042 - CASING BEAD GYPSUM
PLASTERING SYSTEM INTERIOR

9.011 - 20 mm THICK GYPSUM


7.188 - SEALANT
PLASTER

4.002 - 200 mm 8.001 - HOLLOW METAL

INTERIOR DOOR DETAILS, H23 & J23 - H24 & J24


CONCRETE MASONRY

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


DOOR AND FRAME
UNIT

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
4.026 - CMU JAMBS TO

49
BE FULLY GROUTED

STANDARD DETAILS
WITH VERTICAL

142

240
REINFORCING BARS IN

SA-480530
EACH CELL. REFER TO
B STRUCTURAL

49
8.037 - ANCHORS, MIN 3
PER JAMB 3.014 - GROUT SOLID,
GRAPHIC SCALES
NON-SHRINK GROUT, TYP
7.188 - SEALANT
50 16

INTERIOR
2/9/2022 4:33:59 PM

A 0 200 400 800


SHEET ID
$
JAMB DETAIL J24 SCALE: 1:10
A6 1 : 10
UNLESS OTHERWISE NOTED, LINEAR SA542
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA602, SA603 AND SA604 FOR INTERIOR PARTITION TYPES.

4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

DATE
5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

PROVIDE BULLET RESISTANT COMPONENTS AT


OPENING LOCATIONS IDENTIFIED IN THE DOOR
SCHEDULES TO BE BULLET RESISTANT. PROVIDE
RABBET AND STOP IN WIDTHS AND DEPTHS TO
ACCOMMODATE BULLET RESISTANT COMPONENTS.

240 240

DESCRIPTION
F 20 200 20 20 200 20
3.007 - REINFORCED
CAST-IN-PLACE CONCRETE
9.011 - 20 mm THICK GYPSUM 3.007 - REINFORCED 9.011 - 20 mm THICK GYPSUM WALL, SEE STRUCTURAL
PLASTER CAST-IN-PLACE CONCRETE PLASTER DRAWINGS
WALL, SEE STRUCTURAL
9.042 - CASING BEAD GYPSUM DRAWINGS 9.042 - CASING BEAD GYPSUM
PLASTERING SYSTEM PLASTERING SYSTEM 9.011 - 20 mm THICK GYPSUM
PLASTER
9.011 - 20 mm THICK GYPSUM
7.188 - SEALANT PLASTER 7.188 - SEALANT
9.042 - CASING BEAD GYPSUM

50
100
PLASTERING SYSTEM
9.042 - CASING BEAD GYPSUM
PLASTERING SYSTEM
7.188 - SEALANT

16
7.188 - SEALANT
8.111 - PAINTED GALVANIZED

16
8.111 - PAINTED GALVANIZED 49 142 49 STEEL DOOR FRAME, UNO

MARK
49 142 49 STEEL DOOR FRAME, UNO
240
E 240

PLOT SCALE: PLOT DATE:


2/9/2022 4:34:35
INTERIOR INTERIOR INTERIOR INTERIOR

SOLICITATION NO.:

SA-480530-1$-SA543DT.dwg
PM
CONTRACT NO.:
ISSUE DATE:

1:1
FILE NO.:
SUBMITTED BY:
DESIGN BY:

DRAWN BY:
S. MURPHY

A. HANKS
D

A. ORTIZ

E. OKES
CKD BY:

ANSI D
SIZE:
HEAD DETAIL H26 HEAD DETAIL H25

TRANSATLANTIC MIDDLE EAST DISTRICT


D3 1 : 10 D6 1 : 10

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
PROVIDE BULLET RESISTANT COMPONENTS AT
OPENING LOCATIONS IDENTIFIED IN THE DOOR
SCHEDULES TO BE BULLET RESISTANT. PROVIDE
RABBET AND STOP IN WIDTHS AND DEPTHS TO
ACCOMMODATE BULLET RESISTANT COMPONENTS.

C
INTERIOR

9.042 - CASING BEAD GYPSUM


PLASTERING SYSTEM
7.188 - SEALANT
8.035 - JAMB ANCHOR

9.011 - 20 mm THICK GYPSUM 8.111 - PAINTED


PLASTER GALVANIZED STEEL

INTERIOR DOOR DETAILS, H25 & J25 - H26 & J26


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
DOOR FRAME, UNO
3.007 - REINFORCED CAST-IN-PLACE
CONCRETE WALL, SEE STRUCTURAL
DRAWINGS

THAAD STANDARD FACILITIES


49

VARIOUS LOCATIONS, KSA

STANDARD DETAILS
SA-480530
240

142
240
B

GRAPHIC SCALES

49
9.011 - 20 mm THICK GYPSUM
PLASTER

9.042 - CASING BEAD GYPSUM


PLASTERING SYSTEM 50 16

7.188 - SEALANT

INTERIOR
2/9/2022 4:34:35 PM

A 0 200 400 800


SHEET ID
SCALE: 1:10 $
JAMB DETAIL J25
A6 1 : 10 UNLESS OTHERWISE NOTED, LINEAR SA543
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA602, SA603 AND SA604 FOR INTERIOR PARTITION TYPES.

4. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

DATE
5. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

DESCRIPTION
F

MARK
E

PLOT SCALE: PLOT DATE:


2/9/2022 4:35:01
SOLICITATION NO.:

SA-480530-1$-SA544DT.dwg
PM
CONTRACT NO.:
ISSUE DATE:
CL

1:1
INT. WALL ASSEMBLY
SEE FLOOR PLAN

FILE NO.:
M. MacEACHERN
SUBMITTED BY:
W. RODRIGUEZ
C. SCORZELLI
DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
3.007 - REINFORCED

SIZE:
CAST-IN-PLACE CONCRETE
WALL, SEE STRUCTURAL
DRAWINGS

TRANSATLANTIC MIDDLE EAST DISTRICT


AS SCHED
50 OR 100

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
9.011 - 20 mm THICK GYPSUM
7.063 - 13 mm BACKER PLASTER
ROD AND SEALANT
EACH SIDE 6.015 - SHIM AS REQUIRED

8.001 - HOLLOW METAL DOOR


EQ EQ AND FRAME

C
HEAD DETAIL H28
D4 1 : 10

INTERIOR DOOR DETAILS, H27 & J27 - H28 & J28


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
9.011 - 20 mm THICK GYPSUM

THAAD STANDARD FACILITIES


PLASTER

VARIOUS LOCATIONS, KSA


3.007 - REINFORCED

STANDARD DETAILS
CAST-IN-PLACE CONCRETE
WALL, SEE STRUCTURAL

SA-480530
DRAWINGS
B 8.001 - HOLLOW METAL
DOOR AND FRAME

GRAPHIC SCALES
EQ
CL

EQ

8.037 - ANCHORS, MIN 3


PER JAMB
6.015 - SHIM AS REQUIRED
7.063 - 13 mm BACKER ROD AND
2/9/2022 4:35:01 PM

SEALANT EACH SIDE


A 0 200 400 800
SHEET ID
JAMB DETAIL J28 SCALE: 1:10 $
A4 1 : 10
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA544
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA602, SA603 AND SA604 FOR INTERIOR PARTITION TYPES.

DATE
5. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

6. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

DESCRIPTION
F

CL

INT. WALL ASSEMBLY

MARK
SEE FLOOR PLAN

E
8.044 - GLAZING AS SCHEDULED,
REFER TO WINDOW SCHEDULE
7.188 - SEALANT

PLOT SCALE: PLOT DATE:


2/9/2022 4:35:55
8.071 - ALUMINUM CURTAIN WALL
MULLION

SOLICITATION NO.:
8.114 - ALUMINUM STOREFRONT

SA-480530-1$-SA545DT.dwg
3.007 - REINFORCED

PM
CONTRACT NO.:
DOOR FRAME CAST-IN-PLACE CONCRETE

ISSUE DATE:
WALL, SEE STRUCTURAL
7.188 - SEALANT
100 DRAWINGS

1:1
AS SCHED
50 OR 100
7.063 - 13 mm BACKER ROD AND
SEALANT EACH SIDE
INTERIOR EXTERIOR 6.015 - SHIM AS REQUIRED
8.001 - HOLLOW METAL DOOR

FILE NO.:
AND FRAME

SUBMITTED BY:
J. BLANCHARD
DESIGN BY:

DRAWN BY:

A. HANKS
D

A. ORTIZ

S. OKES
CKD BY:

ANSI D
EQ EQ

SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
HEAD DETAIL H30 HEAD DETAIL H29

US ARMY CORPS OF ENGINEERS


D3 D7

201 PRINCE FREDERICK DRIVE,


1 : 10 1 : 10

WINCHESTER, VA 22602
C

INTERIOR

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


8.114 - ALUMINUM STOREFRONT 7.188 - SEALANT 3.007 - REINFORCED
CAST-IN-PLACE CONCRETE

DOOR DETAILS, H29 & J29 - H30 & J30


DOOR FRAME
WALL, SEE STRUCTURAL

THAAD STANDARD FACILITIES


DRAWINGS

VARIOUS LOCATIONS, KSA


8.044 - GLAZING AS SCHEDULED,
REFER TO WINDOW SCHEDULE 8.001 - HOLLOW METAL

STANDARD DETAILS
DOOR AND FRAME
100

SA-480530
6.015 - SHIM AS REQUIRED
B
7.188 - SEALANT

EQ
8.071 - ALUMINUM CURTAIN WALL

CL
MULLION
GRAPHIC SCALES

EQ
8.037 - ANCHORS, MIN 3
PER JAMB
EXTERIOR 7.063 - 13 mm BACKER ROD AND
SEALANT EACH SIDE
2/9/2022 4:35:55 PM

A 0 200 400 800


SHEET ID
JAMB DETAIL J30 JAMB DETAIL J29
A3 1 : 10 A7 1 : 10
SCALE: 1:10 $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA545
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA602, SA603 AND SA604 FOR INTERIOR PARTITION TYPES.

DATE
5. REFER TO SHEET SA610 FOR DOOR PANEL TYPES.

6. REFER TO SHEET SA611 FOR DOOR FRAME TYPES.

DESCRIPTION
F

EW-2
7.016 - FLUID-APPLIED
MEMBRANE AIR BARRIER
9.107 - CASING BEAD 9.011 - 20 mm THICK GYPSUM 4.002 - 200 mm CONCRETE
FOR STUCCO SYSTEM 9.009 - 25 mm THICK THREE COAT PLASTER 240 MASONRY UNIT
STUCCO SYSTEM
4.018 - BOND BEAM, SEE 9.011 - 20 mm THICK GYPSUM
4.018 - BOND BEAM, SEE 9.106 - CORNER BEAD FOR
STRUCTURAL DRAWINGS PLASTER
STRUCTURAL STUCCO SYSTEM
DRAWINGS 9.042 - CASING BEAD GYPSUM 9.042 - CASING BEAD GYPSUM

MARK
PLASTERING SYSTEM PLASTERING SYSTEM

E 7.188 - SEALANT 7.188 - SEALANT


7.188 - SEALANT
9.108 - DRIP SCREED FOR

50

50

PLOT SCALE: PLOT DATE:


2/9/2022 4:37:00
STUCCO SYSTEM
8.114 - ALUMINUM
STOREFRONT DOOR

SOLICITATION NO.:

SA-480530-1$-SA546DT.dwg
7.188 - SEALANT

PM
FRAME

CONTRACT NO.:
8.127 - STAINLESS STEEL C
325

ISSUE DATE:
CHANNEL FRAME WRAP FOR
DOUBLE ACTION TRAFFIC DOOR
325

1:1
INTERIOR EXTERIOR

FILE NO.:
INTERIOR INTERIOR

SUBMITTED BY:
DESIGN BY:

DRAWN BY:
S. MURPHY

A. HANKS
D

A. ORTIZ

S. OKES
CKD BY:

ANSI D
SIZE:
HEAD DETAIL H32 HEAD DETAIL H31

TRANSATLANTIC MIDDLE EAST DISTRICT


D3 D6

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


1 : 10 1 : 10

WINCHESTER, VA 22602
EXTERIOR INTERIOR
C
9.107 - CASING BEAD
FOR STUCCO SYSTEM

9.009 - 25 mm THICK 7.188 - SEALANT


THREE COAT STUCCO
9.106 - CORNER BEAD 9.042 - CASING BEAD GYPSUM
SYSTEM 8.127 - STAINLESS STEEL C CHANNEL
FOR STUCCO SYSTEM PLASTERING SYSTEM
50 FRAME WRAP FOR DOUBLE ACTION
7.016 - FLUID-APPLIED TRAFFIC DOOR

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


MEMBRANE AIR 7.188 - SEALANT 9.011 - 20 mm THICK GYPSUM
BARRIER

DOOR DETAILS, H31 & J31 - H32 & J32


PLASTER

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA

STANDARD DETAILS
4.002 - 200 mm
CONCRETE MASONRY

SA-480530
240
325

325

UNIT
B

9.011 - 20 mm THICK GYPSUM


GRAPHIC SCALES
8.114 - ALUMINUM STOREFRONT PLASTER
DOOR FRAME
EW-2 9.042 - CASING BEAD GYPSUM 50
7.188 - SEALANT PLASTERING SYSTEM

7.188 - SEALANT

INTERIOR INTERIOR
2/9/2022 4:37:00 PM

A 0 200 400 800


SHEET ID
SCALE: 1:10 $
JAMB DETAIL J32 JAMB DETAIL J31
A3 1 : 10 A6 1 : 10 UNLESS OTHERWISE NOTED, LINEAR SA546
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

7.267 - RIGID BOARD WALL


INSULATION, RSI=2.29 (R-13)
MINIMUM
CONTINUE TO STL LINTEL EXT. WALL ASSEMBLY US Army Corps of
SEE FLOOR PLAN Engineers ®
4.033 - 100 mm CONCRETE MASONRY 3.007 - REINFORCED
UNIT Middle East District
CAST-IN-PLACE
G CONCRETE WALL, SEE
9.009 - 25 mm THICK THREE COAT STRUCTURAL
STUCCO SYSTEM DRAWINGS

DATE
100mm SOLID CMU

STAINLESS STEEL
WEEP SCREED
9.011 - 20 mm THICK
THRU-WALL FLASHING GYPSUM PLASTER
W/CELL VENTS AT 400mm OC
EXTEND CELL VENTS TO PLASTER FINISH
FACE OF STUCCO -RETURN TO DOOR
FRAME
BACKER ROD AND
SEALANT BOTH SIDES PLASTIC SHIM

DOOR AND FRAME AS SCHEDULED STEEL LINTEL, PAINT


-GROUT FRAME SOLID SEE STRUCT

DESCRIPTION
F 80
EXTERIOR INTERIOR

HEAD DETAIL AT SMBU DOOR


F6 1 : 10
3.007 - REINFORCED CAST-IN-PLACE
EXT. WALL ASSEMBLY 495 50
CONCRETE WALL, SEE STRUCTURAL
DRAWINGS SEE FLOOR PLAN
EXTERIOR EXT WALL ASSEMBLY INTERIOR
7.016 - FLUID-APPLIED MEMBRANE SEE FLOOR PLAN
9.011 - 20 mm THICK
AIR BARRIER
GYPSUM PLASTER DOOR FRAME BEYOND
7.267 - RIGID BOARD WALL 80
SEE DOOR SCHEDULE FOR 9.011 - 20 mm THICK
INSULATION, RSI=2.29 (R-13) MATERIAL AND TYPE
MINIMUM GYPSUM PLASTER

MARK
CONTINUE TO STL LINTEL WALL BEYOND RETURN TO DOOR
FRAME BEYOND
THRESHOLD SET IN A
E 4.033 - 100 mm CONCRETE MASONRY
UNIT BED OF SEALANT FINISH FLOORING
CONC STOOP, AND WALL BASE

485
9.009 - 25 mm THICK THREE COAT

PLOT SCALE: PLOT DATE:


2/9/2022 4:38:24
STUCCO SYSTEM SLOPE 40/1000mm AS SCHEDULED
SEE STRUCTURAL
CONT TERMINATION BAR CONCRETE
7.001 - ELASTOMERIC SHEET SLOPE

SOLICITATION NO.:

SA-480530-1$-SA547DT.dwg
. SLAB-ON-GRADE

PM
100mm SOLID CMU WATERPROOFING WITH

CONTRACT NO.:
PROTECTION BOARD SEE STRUCTURAL

ISSUE DATE:
MORTAR MESH

1:1
3.024 - BLINDING CONCRETE, 75mm RIGID INSULATION

125
STAINLESS STEEL
SEE STRUCTURAL DRAWINGS
WEEP SCREED
CONC STEM WALL
THRU-WALL FLASHING THICKNESS VARIES, 3.139 - UNDER SLAB VAPOR
W/ CELL VENTS AT 400mm OC CONC FOUNDATION BARRIER
EXTEND VENTS TO

FILE NO.:
OVERHEAD DOOR-SEE AND FOOTING, 3.024 - BLINDING CONCRETE,
FACE OF STUCCO SEE STRUCT SEE STRUCTURAL DRAWINGS
SCHEDULE FOR SIZE & 150 VARIES

SUBMITTED BY:
W. LOCKWOOD
J. BLANCHARD
GALV STEEL LINTEL TYPE CRUSHED 7.001 - ELASTOMERIC SHEET

DESIGN BY:

DRAWN BY:
AGGREGATE 75
WATERPROOFING WITH

A. HANKS
D 2mmCLOSURE PLATE TO Z-TYPE LINTEL

S. OKES
CKD BY:
BASE COURSE PROTECTION BOARD

ANSI D
SPAN GAP - ATTACH TO LINTEL BRUSH SEAL, BY MFR

SIZE:
COMPACTED CRUSHED AGGREGATE
EXTERIOR INTERIOR BASE COURSE
SUBGRADE

TRANSATLANTIC MIDDLE EAST DISTRICT


50mm RIGID INSULATION
HEAD DETAIL SILL DETAIL AT SMBU TO TOP OF FOOTING

US ARMY CORPS OF ENGINEERS


D3 D6

201 PRINCE FREDERICK DRIVE,


1 : 10 1 : 10

WINCHESTER, VA 22602
INTERIOR
INTERIOR
C 9.106 - CORNER BEAD FOR CONCRETE ATTACHED ADJUSTABLE MASONRY DOOR ANCHOR
STUCCO SYSTEM DOVE-TAIL MASONRY TIE
3.007 - REINFORCED
9.011 - 20 mm THICK GYPSUM CAST-IN-PLACE CONCRETE
INSULATED COILING 9.011 - 20 mm THICK GYPSUM WALL, SEE STRUCTURAL
PLASTER
OVERHEAD DOOR PLASTER DRAWINGS
3.007 - REINFORCED
CAST-IN-PLACE CONCRETE 9.106 - CORNER BEAD FOR STUCCO 7.016 - FLUID-APPLIED MEMBRANE
WALL, SEE STRUCTURAL SYSTEM AIR BARRIER
DRAWINGS
WEATHERSTRIPPING SEALANT BOTH SIDES

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


OF FRAME

EXT. WALL ASSEMBLY


GALV STEEL GUIDE RAILS
EXT. WALL ASSEMBLY

SEE FLOOR PLAN


BY DOOR MFR
SEE FLOOR PLAN

CORRUGATED ANCHOR AT
-ATTACH TO WALL PER MFR 170 400mm OC

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
13mm RIGID INSULATION

STANDARD DETAILS
THERMAL BREAK
6mm GALV BENT STEEL PLATE

DOOR DETAILS
DOOR AND FRAME AS SCHEDULED

SA-480530
100mm SOLID CMU -GROUT FRAME SOLID
B

80
100 7.267 - RIGID BOARD WALL
7.016 - FLUID-APPLIED MEMBRANE
GRAPHIC SCALES
300 UNO

AIR BARRIER INSULATION, RSI=2.29 (R-13)


MINIMUM
7.267 - RIGID BOARD WALL
RIGID BOARD WALL INSULATION
INSULATION, RSI=2.29 (R-13) 9.106 - CORNER BEAD FOR STUCCO INFILL AT JAMB
MINIMUM SYSTEM
RIGID BOARD WALL INSULATION 4.025 - 100 mm NOMINAL CONCRETE
INFILL AT JAMB MASONRY UNIT
150mm OUTSIDE DIAMETER BOLLARD - 9.106 - CORNER BEAD FOR 9.009 - 25 mm THICK THREE COAT
ALIGN FACE OF BOLLARD W/ FACE OF STUCCO SYSTEM STUCCO SYSTEM
ROUGH OPENING AT OVERHEAD
COILING DOOR JAMB EXTERIOR EXTERIOR
2/9/2022 4:38:24 PM

A 0 6M 12M 24M
SHEET ID
$
JAMB DETAIL JAMB DETAIL AT SMBU SCALE: 1:300
A3 1 : 10 A6 1 : 10
UNLESS OTHERWISE NOTED, LINEAR SA547
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA615, SA616, SA617, SA618, SA619 AND SA620 FOR WINDOW
TYPES.

DATE
EXTERIOR EXTERIOR
9.107 - CASING BEAD FOR STUCCO COL
SYSTEM 50 25 MIN 7.188 - SEALANT 25 MIN 50 25 MIN

8.079 - FILL FRAME WITH 8.079 - FILL FRAME WITH


9.009 - 25 mm THICK THREE COAT
MINERAL WOOL INSULATION MINERAL WOOL INSULATION
STUCCO SYSTEM

DESCRIPTION
8.121 - PAINTED GALVANIZED
F 7.016 - FLUID-APPLIED MEMBRANE 8.044 - GLAZING AS SCHEDULED,
REFER TO WINDOW SCHEDULE
BULLET RESISTANT STEEL
AIR BARRIER WINDOW FRAME
4.002 - 200 mm
8.044 - GLAZING AS SCHEDULED,
CONCRETE MASONRY

25
REFER TO WINDOW SCHEDULE
UNIT 7.016 - FLUID-APPLIED

25
COL COL EW-2 MEMBRANE AIR BARRIER

4.018 - BOND BEAM, SEE 9.009 - 25 mm THICK THREE COAT

175

175
STRUCTURAL STUCCO SYSTEM
DRAWINGS

SEE STRUCTURAL
7.248 - AIR BARRIER TRANSITION
MEMBRANE. LAP MEMBRANE
8.079 - FILL FRAME WITH
OVER STUCCO DRIP FLASHING
MINERAL WOOL
BY 50 mm MIN.

300
INSULATION

425

425
9.113 - METAL DRIP FLASHING

400
FOR STUCCO SYSTEM

MARK
150
FACE OF
E STRUCTURE

50
BELOW
7.188 - SEALANT

PLOT SCALE: PLOT DATE:


2/9/2022 4:40:16
25 MIN
100

FACE OF

100

20 UNO
WALL BELOW 8.121 - PAINTED

SOLICITATION NO.:

SA-480530-1$-SA559DT.dwg
UNO

PM
GALVANIZED BULLET
20

CONTRACT NO.:
RESISTANT STEEL

ISSUE DATE:
8.121 - PAINTED GALVANIZED WINDOW FRAME
6.025 - WINDOW STOOL. REFER
BULLET RESISTANT STEEL 100 50 175

1:1
3.007 - REINFORCED CAST-IN-PLACE TO INTERIORS SHEET SI601 7.188 - SEALANT
FACE OF WINDOW FRAME
CONCRETE WALL, SEE STRUCTURAL FINISH LEGEND
WALL
DRAWINGS 7.188 - SEALANT 8.044 - GLAZING AS SCHEDULED,
EW-2A BELOW 325
REFER TO WINDOW SCHEDULE
9.096 - 15 mm GYPSUM WALL BOARD
INTERIOR INTERIOR
6.025 - WINDOW STOOL. REFER EXTERIOR

FILE NO.:
TO INTERIORS SHEET SI601

SUBMITTED BY:
W. LOCKWOOD
FINISH LEGEND

J. BLANCHARD
DESIGN BY:

DRAWN BY:
9.096 - 15 mm GYPSUM WALL BOARD

A. HANKS
D

S. OKES
CKD BY:

ANSI D
INTERIOR

SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
JAMB DETAIL JAMB DETAIL HEAD DETAIL
D1 D4 D6

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


1:5 1:5 1:5

WINCHESTER, VA 22602
COL
EXTERIOR EXTERIOR

7.188 - SEALANT
325 8.044 - GLAZING AS SCHEDULED,
50 25 MIN 25 MIN 50 25 MIN
9.107 - CASING BEAD FOR STUCCO REFER TO WINDOW SCHEDULE
SYSTEM 8.079 - FILL FRAME WITH 8.079 - FILL FRAME WITH 100 50 175
C MINERAL WOOL INSULATION MINERAL WOOL INSULATION 8.079 - FILL FRAME WITH
9.009 - 25 mm THICK THREE COAT MINERAL WOOL INSULATION
8.044 - GLAZING AS SCHEDULED, 8.121 - PAINTED GALVANIZED
STUCCO SYSTEM 7.188 - SEALANT
REFER TO WINDOW SCHEDULE BULLET RESISTANT STEEL 8.121 - PAINTED GALVANIZED
WINDOW FRAME BULLET RESISTANT STEEL
7.016 - FLUID-APPLIED MEMBRANE 6.025 - WINDOW STOOL. REFER
AIR BARRIER 8.044 - GLAZING AS SCHEDULED, WINDOW FRAME
TO INTERIORS SHEET SI601
REFER TO WINDOW SCHEDULE FINISH LEGEND 8.134 - PREFINISHED ALUMINUM

25 MIN
SILL FLASHING PAN WITH 50 mm

EXTERIOR WALL EW2 AND EW2A WINDOW DETAILS


TURNED UP EDGES. FLASHING 2
9.095 - INTERIOR 60 mm x 27 mm

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


mm THICK MIN. COAT NON
METAL WALL LINING FRAMING
VISIBLE SURFACES OF FLASHING
175

175

FIXED WITH WALL BRACKETS TO


IN CONTACT WITH STEEL FRAME
CMU OR CONCRETE AT 600 mm
WITH BITUMINOUS PAINT.

50

THAAD STANDARD FACILITIES


OC SPACING MAX

VARIOUS LOCATIONS, KSA


325

325

STANDARD DETAILS
20 UNO
50

50

7.188 - SEALANT

SA-480530
COL COL
B 9.107 - CASING BEAD FOR
20 UNO

9.096 - 15 mm GYPSUM WALL STUCCO SYSTEM


FACE OF
100

100

BOARD
WALL BELOW 4.018 - BOND BEAM, SEE
7.176 - EXTRUDED PREFORMED
CELLULAR POLYSTYRENE
STRUCTURAL DRAWINGS GRAPHIC SCALES
7.016 - FLUID-APPLIED
4.002 - 200 mm CONCRETE BOARD WALL INSULATION RSI MEMBRANE AIR BARRIER
FACE OF 6.025 - WINDOW STOOL. REFER 6.025 - WINDOW STOOL. REFER
MASONRY UNIT 1.68 (R9.52) MIN
WALL BELOW TO INTERIORS SHEET SI601 TO INTERIORS SHEET SI601
FINISH LEGEND FINISH LEGEND EW-2 9.009 - 25 mm THICK THREE COAT
9.096 - 15 mm GYPSUM WALL STUCCO SYSTEM
BOARD EW-2
8.121 - PAINTED GALVANIZED
BULLET RESISTANT STEEL
WINDOW FRAME
INTERIOR EXTERIOR
INTERIOR 7.188 - SEALANT INTERIOR
2/9/2022 4:40:16 PM

A 0 100 200 400


SHEET ID
$
JAMB DETAIL JAMB DETAIL SILL DETAIL SCALE: 1:5
A1 1:5 A4 1:5 A6 1:5
UNLESS OTHERWISE NOTED, LINEAR SA559
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA615, SA616, SA617, SA618, SA619 AND SA620 FOR WINDOW
TYPES.

DATE
EXTERIOR
INTERIOR

DESCRIPTION
F 9.106 - CORNER BEAD 50 25 MIN
FOR STUCCO SYSTEM 7.188 - SEALANT
9.096 - 15 mm GYPSUM EW-2
WALL BOARD
9.009 - 25 mm THICK
THREE COAT STUCCO 8.079 - FILL FRAME WITH
7.188 - SEALANT
SYSTEM MINERAL WOOL INSULATION

8.128 - ROLL-UP INSECT SCREEN 7.016 - FLUID-APPLIED


8.044 - GLAZING AS SCHEDULED,
7.246 - PACK JOINT WITH MEMBRANE AIR
REFER TO WINDOW SCHEDULE
MINERAL WOOL INSULATION BARRIER

4.002 - 200 mm CONCRETE


MASONRY UNIT 4.002 - 200 mm
100

50
CONCRETE MASONRY
UNIT
COL
25

MARK
4.026 - CMU JAMBS TO
325

175
BE FULLY GROUTED
WITH VERTICAL
E

325
150

4.042 - CMU CELLS AT PARTITION REINFORCING BARS IN


ENDS TO BE FULLY GROUTED EACH CELL. REFER TO
WITH VERTICAL REINFORCING STRUCTURAL

PLOT SCALE: PLOT DATE:


2/9/2022 4:41:06
BARS. REFER TO STRUCTURAL COL
DRAWINGS

SOLICITATION NO.:
100
50

SA-480530-1$-SA560DT.dwg
PM
CONTRACT NO.:
ISSUE DATE:
8.015 - ALUMINUM WINDOW 7.016 - FLUID-APPLIED 7.246 - PACK JOINT WITH

1:1
50 MEMBRANE AIR BARRIER MINERAL WOOL 8.121 - PAINTED GALVANIZED
8.014 - ALUMINUM CURTAINWALL INSULATION BULLET RESISTANT STEEL
19 MAX 9.009 - 25 mm THICK THREE COAT WINDOW FRAME
STUCCO SYSTEM
7.188 - SEALANT
EW-2 7.188 - SEALANT
9.106 - CORNER BEAD FOR

FILE NO.:
STUCCO SYSTEM 9.096 - 15 mm GYPSUM

SUBMITTED BY:
WALL BOARD

DESIGN BY:

DRAWN BY:
S. MURPHY

A. HANKS
INTERIOR
D

A. ORTIZ
EXTERIOR

E. OKES
CKD BY:

ANSI D
SIZE:
JAMB DETAIL JAMB DETAIL

TRANSATLANTIC MIDDLE EAST DISTRICT


D2 D6

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


1:5 1:5

WINCHESTER, VA 22602
INTERIOR
EXTERIOR INTERIOR

225 EW-2
8.044 - GLAZING AS SCHEDULED,
C REFER TO WINDOW SCHEDULE
50 175 9.096 - 15 mm GYPSUM
9.107 - CASING BEAD 8.014 - ALUMINUM CURTAINWALL WALL BOARD
FOR STUCCO SYSTEM
7.246 - PACK JOINT WITH
MINERAL WOOL INSULATION 7.188 - SEALANT
4.002 - 200 mm 7.246 - PACK JOINT WITH
CONCRETE MASONRY 7.188 - SEALANT MINERAL WOOL INSULATION
UNIT
9.042 - CASING BEAD GYPSUM
9.009 - 25 mm THICK PLASTERING SYSTEM

100
THREE COAT STUCCO
9.133 - SELF-FURRING METAL

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


SYSTEM
LATH FOR PLASTER BASE

EXTERIOR WALL EW2 WINDOW DETAILS


COL
WHERE MASONRY SURFACE IS

25
7.016 - FLUID-APPLIED
MEMBRANE AIR BARRIER INTERRUPTED. EXTEND LATH 50

THAAD STANDARD FACILITIES


mm ONTO MASONRY SURFACE.

VARIOUS LOCATIONS, KSA


325

STANDARD DETAILS
50

150
9.011 - 20 mm THICK GYPSUM
PLASTER

SA-480530
4.026 - CMU JAMBS TO BE FULLY
B
19 MAX

GROUTED WITH VERTICAL


REINFORCING BARS IN EACH
CELL. REFER TO STRUCTURAL

50
EW-2 GRAPHIC SCALES
7.016 - FLUID-APPLIED
M8F0.1P2 MEMBRANE AIR BARRIER
7.188 - SEALANT 8.014 - ALUMINUM CURTAINWALL
9.009 - 25 mm THICK THREE COAT
4.026 - CMU JAMBS TO BE FULLY 4.002 - 200 mm CONCRETE STUCCO SYSTEM
GROUTED WITH VERTICAL 7.188 - SEALANT
MASONRY UNIT
REINFORCING BARS IN EACH CELL. 50 19 MAX 9.106 - CORNER BEAD FOR
REFER TO STRUCTURAL STUCCO SYSTEM
7.176 - EXTRUDED PREFORMED
CELLULAR POLYSTYRENE
BOARD WALL INSULATION RSI
2/9/2022 4:41:06 PM

1.68 (R9.52) MIN EXTERIOR


A 0 100 200 400
SHEET ID
JAMB DETAIL JAMB DETAIL SCALE: 1:5 $
A2 A6
1:5 1:5
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA560
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA615, SA616, SA617, SA618, SA619 AND SA620 FOR WINDOW
TYPES.

DATE
COL

COL
150 60

DESCRIPTION
F
7.176 - EXTRUDED
PREFORMED CELLULAR
POLYSTYRENE BOARD 7.016 - FLUID-APPLIED
WALL INSULATION RSI MEMBRANE AIR BARRIER
1.68 (R9.52) MIN EW-2
4.001 - 150 mm CONCRETE 7.016 - FLUID-APPLIED
MASONRY UNIT MEMBRANE AIR BARRIER
9.096 - 15 mm GYPSUM 9.096 - 15 mm GYPSUM
WALL BOARD 45 3.058 - GLASS-FIBER WALL BOARD 9.009 - 25 mm THICK THREE COAT
REINFORCED CONCRETE (GFRC) STUCCO SYSTEM
9.095 - INTERIOR 60 mm 4.018 - BOND BEAM, SEE 9.106 - CORNER BEAD FOR
x 27 mm METAL WALL 4.018 - BOND BEAM, SEE STRUCTURAL STUCCO SYSTEM
LINING FRAMING FIXED STRUCTURAL DRAWINGS DRAWINGS
WITH WALL BRACKETS
TO CMU OR CONCRETE

19 MAX
7.247 - AIR BARRIER TRANSITION
AT 600 mm OC SPACING MEMBRANE. LAP MEMBRANE

MARK
MAX OVER WINDOW TRIM BY 50 mm
MIN.
E 9.095 - INTERIOR 60 mm x 27 mm
METAL WALL LINING FRAMING FIXED

50
8.133 - PREFINISHED ALUMINUM
WITH WALL BRACKETS TO CMU OR

PLOT SCALE: PLOT DATE:


HEAD FLASHING WITH DRIP

2/9/2022 4:41:54
CONCRETE AT 600 mm OC SPACING

50
9.096 - 15 mm GYPSUM EDGE. FLASHING 2 mm THICK
MAX 9.108 - DRIP SCREED FOR
WALL BOARD MIN. COAT NON VISIBLE
STUCCO SYSTEM

SOLICITATION NO.:

SA-480530-1$-SA561DT.dwg
SURFACES OF FLASHING IN

PM
CONTRACT NO.:
CONTACT WITH STEEL FRAME 9.096 - 15 mm GYPSUM 7.188 - SEALANT

25 MIN
7.188 - SEALANT

ISSUE DATE:
WITH BITUMINOUS PAINT. WALL BOARD
8.014 - ALUMINUM CURTAINWALL

1:1
8.079 - FILL FRAME WITH 8.121 - PAINTED GALVANIZED 7.188 - SEALANT
50 25 150 50
MINERAL WOOL INSULATION BULLET RESISTANT STEEL
WINDOW FRAME
100 175 35
8.044 - GLAZING AS SCHEDULED, 325
REFER TO WINDOW SCHEDULE

FILE NO.:
310

SUBMITTED BY:
DESIGN BY:

DRAWN BY:
S. MURPHY
INTERIOR EXTERIOR

A. HANKS
D INTERIOR EXTERIOR

A. ORTIZ

E. OKES
CKD BY:

ANSI D
SIZE:
HEAD DETAIL HEAD DETAIL

TRANSATLANTIC MIDDLE EAST DISTRICT


D2 D6

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


1:5 1:5

WINCHESTER, VA 22602
COL
COL

150 60

C
7.176 - EXTRUDED
EW-2 PREFORMED CELLULAR
7.016 - FLUID-APPLIED POLYSTYRENE BOARD 7.016 - FLUID-APPLIED
MEMBRANE AIR BARRIER WALL INSULATION RSI MEMBRANE AIR BARRIER
9.096 - 15 mm GYPSUM 1.68 (R9.52) MIN
WALL BOARD 9.009 - 25 mm THICK THREE COAT 4.001 - 150 mm CONCRETE
STUCCO SYSTEM MASONRY UNIT
9.096 - 15 mm GYPSUM
9.106 - CORNER BEAD FOR WALL BOARD 3.058 - GLASS-FIBER
4.018 - BOND BEAM, SEE STUCCO SYSTEM 45

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


STRUCTURAL REINFORCED CONCRETE (GFRC)

EXTERIOR WALL EW2 WINDOW DETAILS


DRAWINGS 9.095 - INTERIOR 60 mm 4.018 - BOND BEAM, SEE
x 27 mm METAL WALL STRUCTURAL DRAWINGS
19 MAX

THAAD STANDARD FACILITIES


LINING FRAMING FIXED

VARIOUS LOCATIONS, KSA


WITH WALL BRACKETS 7.247 - AIR BARRIER TRANSITION

STANDARD DETAILS
TO CMU OR CONCRETE MEMBRANE. LAP MEMBRANE

19 MAX
9.095 - INTERIOR 60 mm x 27 mm AT 600 mm OC SPACING OVER WINDOW TRIM BY 50 mm
MAX MIN.

SA-480530
METAL WALL LINING FRAMING FIXED
50

B WITH WALL BRACKETS TO CMU OR


CONCRETE AT 600 mm OC SPACING 8.110 - PREFINISHED ALUMINUM
MAX 9.108 - DRIP SCREED FOR WINDOW TRIM. 1 mm THICK MIN.
STUCCO SYSTEM EXTEND INTO OPENING.

GRAPHIC SCALES

50
9.096 - 15 mm GYPSUM 7.188 - SEALANT 9.096 - 15 mm GYPSUM
WALL BOARD WALL BOARD
8.014 - ALUMINUM CURTAINWALL 7.188 - SEALANT
7.188 - SEALANT
7.188 - SEALANT 8.014 - ALUMINUM CURTAINWALL
25 150 50 8.015 - ALUMINUM WINDOW
7.246 - PACK JOINT WITH
8.128 - ROLL-UP INSECT SCREEN MINERAL WOOL
325 INSULATION

100 175 35

INTERIOR
2/9/2022 4:41:54 PM

EXTERIOR 310
INTERIOR EXTERIOR
A 0 100 200 400
SHEET ID
SCALE: 1:5 $
HEAD DETAIL HEAD DETAIL
A2 1:5 A6 1:5
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA561
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA615, SA616, SA617, SA618, SA619 AND SA620 FOR WINDOW
TYPES.

DATE
COL COL

INTERIOR EXTERIOR INTERIOR EXTERIOR


325

325
100 175 50

DESCRIPTION
100 175 50
F 8.128 - ROLL-UP INSECT SCREEN 150
7.188 - SEALANT 7.188 - SEALANT
8.015 - ALUMINUM WINDOW
6.025 - WINDOW STOOL. REFER 6.025 - WINDOW STOOL. REFER 150
TO INTERIORS SHEET SI601 8.014 - ALUMINUM CURTAINWALL 8.014 - ALUMINUM CURTAINWALL
TO INTERIORS SHEET SI601
FINISH LEGEND FINISH LEGEND
7.188 - SEALANT 7.188 - SEALANT

9.095 - INTERIOR 60 mm x 27 mm 9.095 - INTERIOR 60 mm x 27 mm


METAL WALL LINING FRAMING 8.109 - PREFINISHED ALUMINUM 8.109 - PREFINISHED ALUMINUM
SILL. 2 mm THICK MIN. METAL WALL LINING FRAMING
FIXED WITH WALL BRACKETS TO FIXED WITH WALL BRACKETS TO SILL. 2 mm THICK MIN.
INTEGRATE SILL WITH CURTAIN INTEGRATE SILL WITH CURTAIN

50
CMU OR CONCRETE AT 600 mm CMU OR CONCRETE AT 600 mm
OC SPACING MAX WALL MULLION TO DRAIN WALL MULLION TO DRAIN
MOISTURE MIGRATING WITHIN OC SPACING MAX
MOISTURE MIGRATING WITHIN
CURTAIN WALL TO EXTERIOR CURTAIN WALL TO EXTERIOR
20 UNO 20 UNO

MARK
7.188 - SEALANT 7.188 - SEALANT
E
9.096 - 15 mm GYPSUM WALL 9.107 - CASING BEAD FOR 9.096 - 15 mm GYPSUM WALL 9.107 - CASING BEAD FOR
BOARD STUCCO SYSTEM BOARD STUCCO SYSTEM

PLOT SCALE: PLOT DATE:


2/9/2022 4:42:43
7.176 - EXTRUDED PREFORMED 7.246 - PACK JOINT WITH 7.246 - PACK JOINT WITH
7.176 - EXTRUDED PREFORMED
CELLULAR POLYSTYRENE MINERAL WOOL INSULATION MINERAL WOOL INSULATION

SOLICITATION NO.:
CELLULAR POLYSTYRENE

SA-480530-1$-SA562DT.dwg
PM
BOARD WALL INSULATION RSI

CONTRACT NO.:
BOARD WALL INSULATION RSI
1.68 (R9.52) MIN 4.018 - BOND BEAM, SEE 1.68 (R9.52) MIN 4.018 - BOND BEAM, SEE

ISSUE DATE:
STRUCTURAL DRAWINGS STRUCTURAL DRAWINGS

1:1
EW-2 7.016 - FLUID-APPLIED 7.016 - FLUID-APPLIED
EW-2
MEMBRANE AIR BARRIER MEMBRANE AIR BARRIER

FILE NO.:
M. CUNNINGHAM
SUBMITTED BY:
DESIGN BY:

DRAWN BY:
S. MURPHY

A. HANKS
D

A. ORTIZ
CKD BY:

ANSI D
SIZE:
SILL DETAIL SILL DETAIL

TRANSATLANTIC MIDDLE EAST DISTRICT


D2 D6

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


1:5 1:5

WINCHESTER, VA 22602
COL COL
INTERIOR EXTERIOR
310 310

100 210 100 210

C 8.079 - FILL FRAME WITH 8.128 - ROLL-UP INSECT SCREEN 175 35


MINERAL WOOL INSULATION 175 35
8.044 - GLAZING AS SCHEDULED, 7.188 - SEALANT
REFER TO WINDOW SCHEDULE 150
7.188 - SEALANT
50
6.025 - WINDOW STOOL. 8.015 - ALUMINUM WINDOW
REFER TO INTERIORS 8.121 - PAINTED GALVANIZED 6.025 - WINDOW STOOL.
SHEET SI601 FINISH BULLET RESISTANT STEEL REFER TO INTERIORS
8.014 - ALUMINUM CURTAINWALL
LEGEND WINDOW FRAME SHEET SI601 FINISH
LEGEND
7.188 - SEALANT
9.095 - INTERIOR 60 mm 7.188 - SEALANT

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


x 27 mm METAL WALL 9.095 - INTERIOR 60 mm 8.109 - PREFINISHED ALUMINUM

EXTERIOR WALL EW2 WINDOW DETAILS


LINING FRAMING FIXED 8.134 - PREFINISHED ALUMINUM x 27 mm METAL WALL SILL. 2 mm THICK MIN.
WITH WALL BRACKETS SILL FLASHING PAN WITH 50 mm LINING FRAMING FIXED INTEGRATE SILL WITH CURTAIN

THAAD STANDARD FACILITIES


TO CMU OR CONCRETE TURNED UP EDGES. FLASHING 2 WITH WALL BRACKETS WALL MULLION TO DRAIN

VARIOUS LOCATIONS, KSA


50
AT 600 mm OC SPACING mm THICK MIN. COAT NON MOISTURE MIGRATING WITHIN
50

TO CMU OR CONCRETE
25 MIN

STANDARD DETAILS
MAX VISIBLE SURFACES OF FLASHING AT 600 mm OC SPACING CURTAIN WALL TO EXTERIOR
IN CONTACT WITH STEEL FRAME MAX
WITH BITUMINOUS PAINT.

SA-480530
20 UNO 20 UNO
B 7.188 - SEALANT 7.188 - SEALANT
60 60
9.096 - 15 mm GYPSUM 9.096 - 15 mm GYPSUM
WALL BOARD 4.018 - BOND BEAM, SEE WALL BOARD 4.018 - BOND BEAM, SEE
STRUCTURAL DRAWINGS
7.176 - EXTRUDED
STRUCTURAL DRAWINGS GRAPHIC SCALES
7.176 - EXTRUDED 3.058 - GLASS-FIBER 3.058 - GLASS-FIBER
PREFORMED CELLULAR PREFORMED CELLULAR
REINFORCED CONCRETE (GFRC) POLYSTYRENE BOARD REINFORCED CONCRETE (GFRC)
POLYSTYRENE BOARD
WALL INSULATION RSI WALL INSULATION RSI
7.016 - FLUID-APPLIED 1.68 (R9.52) MIN 7.016 - FLUID-APPLIED
1.68 (R9.52) MIN MEMBRANE AIR BARRIER MEMBRANE AIR BARRIER
7.246 - PACK JOINT WITH
MINERAL WOOL
INSULATION
INTERIOR EXTERIOR
2/9/2022 4:42:43 PM

A 0 100 200 400


SHEET ID
SCALE: 1:5 $
SILL DETAIL SILL DETAIL
A2 1:5 A6 1:5 UNLESS OTHERWISE NOTED, LINEAR SA562
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA615, SA616, SA617, SA618, SA619 AND SA620 FOR WINDOW
TYPES.

DATE
8.134 - PREFINISHED ALUMINUM SILL EXTERIOR
FLASHING PAN WITH 50 mm TURNED
UP EDGES. FLASHING 2 mm THICK
MIN. COAT NON VISIBLE SURFACES
COL OF FLASHING IN CONTACT WITH COL EXTERIOR
STEEL FRAME WITH BITUMINOUS
425 PAINT.
175
175 250 20 UNO

DESCRIPTION
8.121 - PAINTED GALVANIZED BULLET
F RESISTANT STEEL WINDOW FRAME 35 50
CL 9.106 - CORNER BEAD 50 25 MIN
INTERIOR 7.188 - SEALANT
FOR STUCCO SYSTEM
8.079 - FILL FRAME WITH MINERAL
WOOL INSULATION SLOPE
9.009 - 25 mm THICK 8.079 - FILL FRAME WITH
CL THREE COAT STUCCO MINERAL WOOL INSULATION
COL SYSTEM
FACE OF 8.044 - GLAZING AS SCHEDULED,
WALL BELOW REFER TO WINDOW SCHEDULE

175
50
25 MIN

30

25

35

50
8.044 - GLAZING AS SCHEDULED,
30

67 REFER TO WINDOW SCHEDULE


40 ±

.5° 6.025 - WINDOW STOOL. REFER

225
25
TO INTERIORS SHEET SI601

425
FINISH LEGEND 8.121 - PAINTED GALVANIZED BULLET
7.188 - SEALANT RESISTANT STEEL WINDOW FRAME

175

MARK
40

325
8.079 - FILL FRAME WITH
7.188 - SEALANT
±

250
E MINERAL WOOL INSULATION
8.044 - GLAZING AS SCHEDULED, FACE OF WALL BELOW
25

REFER TO WINDOW SCHEDULE COL

PLOT SCALE: PLOT DATE:


6.025 - WINDOW STOOL. REFER TO

2/9/2022 4:43:49
M
IN

INTERIORS SHEET SI601 FINISH

100

100
8.121 - PAINTED GALVANIZED LEGEND

SOLICITATION NO.:

SA-480530-1$-SA563DT.dwg
PM
BULLET RESISTANT STEEL

CONTRACT NO.:
WINDOW FRAME

ISSUE DATE:
20 UNO
8.121 - PAINTED GALVANIZED 8.044 - GLAZING AS SCHEDULED,
3.007 - REINFORCED CAST-IN-PLACE

1:1
REFER TO WINDOW SCHEDULE 8.121 - PAINTED GALVANIZED
BULLET RESISTANT STEEL CONCRETE WALL, SEE STRUCTURAL BULLET RESISTANT STEEL
WINDOW FRAME DRAWINGS
20 UNO 250 175 WINDOW FRAME
EW-2A
EXTERIOR INTERIOR 425 EXTERIOR 9.096 - 15 mm GYPSUM WALL BOARD 7.188 - SEALANT

FILE NO.:
9.096 - 15 mm GYPSUM
WALL BOARD

SUBMITTED BY:
W. LOCKWOOD
J. BLANCHARD
INTERIOR

DESIGN BY:

DRAWN BY:

A. HANKS
D

S. OKES
CKD BY:

ANSI D
SIZE:
JAMB DETAIL JAMB DETAIL JAMB DETAIL

TRANSATLANTIC MIDDLE EAST DISTRICT


D1 D3 D6

US ARMY CORPS OF ENGINEERS


1:5 1:5 1:5

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
INTERIOR

EXTERIOR
EW-2A
9.107 - CASING BEAD FOR STUCCO
SYSTEM
50 25 MIN 7.188 - SEALANT 9.096 - 15 mm GYPSUM
C 9.009 - 25 mm THICK THREE COAT WALL BOARD 9.096 - 15 mm GYPSUM WALL
STUCCO SYSTEM 8.079 - FILL FRAME WITH BOARD
MINERAL WOOL INSULATION 7.188 - SEALANT
7.016 - FLUID-APPLIED MEMBRANE 7.246 - PACK JOINT WITH
8.044 - GLAZING AS SCHEDULED, MINERAL WOOL INSULATION
AIR BARRIER REFER TO WINDOW SCHEDULE

100
25

COL COL

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


25

EXTERIOR WALL EW2A WINDOW DETAILS


175

325

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
150

STANDARD DETAILS
325

3.007 - REINFORCED
300

CAST-IN-PLACE CONCRETE

SA-480530
50

WALL, SEE STRUCTURAL


B DRAWINGS

50
100

7.016 - FLUID-APPLIED
MEMBRANE AIR BARRIER GRAPHIC SCALES
8.014 - ALUMINUM CURTAINWALL
9.009 - 25 mm THICK THREE COAT
8.121 - PAINTED GALVANIZED STUCCO SYSTEM
7.188 - SEALANT
BULLET RESISTANT STEEL
50 19 MAX 9.106 - CORNER BEAD FOR
WINDOW FRAME
STUCCO SYSTEM
3.007 - REINFORCED CAST-IN-PLACE EW-2A
CONCRETE WALL, SEE STRUCTURAL 7.188 - SEALANT
DRAWINGS
9.096 - 15 mm GYPSUM WALL BOARD EXTERIOR
2/9/2022 4:43:49 PM

INTERIOR
A 0 100 200 400
SHEET ID
SCALE: 1:5 $
JAMB DETAIL JAMB DETAIL
A2 1:5 A6 1:5 UNLESS OTHERWISE NOTED, LINEAR SA563
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA615, SA616, SA617, SA618, SA619 AND SA620 FOR WINDOW
TYPES.

DATE
COL

150 60
COL

DESCRIPTION
7.176 - EXTRUDED
F PREFORMED CELLULAR
POLYSTYRENE BOARD 7.016 - FLUID-APPLIED
WALL INSULATION RSI MEMBRANE AIR BARRIER
1.68 (R9.52) MIN
3.007 - REINFORCED
CAST-IN-PLACE CONCRETE EW-2A 7.016 - FLUID-APPLIED
9.096 - 15 mm GYPSUM WALL, SEE STRUCTURAL
WALL BOARD MEMBRANE AIR BARRIER
45 DRAWINGS
9.096 - 15 mm GYPSUM
3.058 - GLASS-FIBER WALL BOARD 9.009 - 25 mm THICK THREE COAT
9.095 - INTERIOR 60 mm STUCCO SYSTEM
x 27 mm METAL WALL REINFORCED CONCRETE (GFRC)
3.007 - REINFORCED
LINING FRAMING FIXED CAST-IN-PLACE 9.106 - CORNER BEAD FOR
7.247 - AIR BARRIER TRANSITION
WITH WALL BRACKETS CONCRETE WALL, SEE STUCCO SYSTEM
MEMBRANE. LAP MEMBRANE
TO CMU OR CONCRETE OVER WINDOW TRIM BY 50 mm STRUCTURAL
AT 600 mm OC SPACING MIN. DRAWINGS

19 MAX
MAX
8.133 - PREFINISHED ALUMINUM

MARK
HEAD FLASHING WITH DRIP
EDGE. FLASHING 2 mm THICK
MIN. COAT NON VISIBLE 9.095 - INTERIOR 60 mm x 27 mm
E SURFACES OF FLASHING IN METAL WALL LINING FRAMING FIXED

50
9.096 - 15 mm GYPSUM CONTACT WITH STEEL FRAME WITH WALL BRACKETS TO CMU OR
WITH BITUMINOUS PAINT. CONCRETE AT 600 mm OC SPACING

PLOT SCALE: PLOT DATE:


WALL BOARD

2/9/2022 4:44:48
MAX 9.108 - DRIP SCREED FOR
8.121 - PAINTED GALVANIZED STUCCO SYSTEM
7.188 - SEALANT

SOLICITATION NO.:

SA-480530-1$-SA564DT.dwg
BULLET RESISTANT STEEL 9.096 - 15 mm GYPSUM 7.188 - SEALANT

PM
CONTRACT NO.:
WINDOW FRAME WALL BOARD

ISSUE DATE:
8.079 - FILL FRAME WITH 8.014 - ALUMINUM CURTAINWALL
MINERAL WOOL INSULATION 8.044 - GLAZING AS SCHEDULED, 7.188 - SEALANT

1:1
REFER TO WINDOW SCHEDULE 25 150 50
100 175 35
(90 AT MOSQUE)
325
310

FILE NO.:
M. CUNNINGHAM
SUBMITTED BY:
INTERIOR EXTERIOR
INTERIOR EXTERIOR

DESIGN BY:

DRAWN BY:
S. MURPHY

A. HANKS
D

A. ORTIZ
CKD BY:

ANSI D
SIZE:
HEAD DETAIL HEAD DETAIL
D2 D6

TRANSATLANTIC MIDDLE EAST DISTRICT


1:5 1:5

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
COL COL

300 25

200 150 60

C EW-2A
7.176 - EXTRUDED
7.016 - FLUID-APPLIED
3.007 - REINFORCED PREFORMED CELLULAR
MEMBRANE AIR BARRIER
CAST-IN-PLACE POLYSTYRENE BOARD 7.016 - FLUID-APPLIED
WALL INSULATION RSI MEMBRANE AIR BARRIER
CONCRETE WALL, SEE 9.009 - 25 mm THICK THREE COAT
STRUCTURAL 1.68 (R9.52) MIN
STUCCO SYSTEM 3.007 - REINFORCED
DRAWINGS 7.248 - AIR BARRIER TRANSITION CAST-IN-PLACE CONCRETE
9.096 - 15 mm GYPSUM
9.096 - 15 mm GYPSUM MEMBRANE. LAP MEMBRANE WALL, SEE STRUCTURAL
WALL BOARD 45
WALL BOARD OVER STUCCO DRIP FLASHING DRAWINGS

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


BY 50 mm MIN. 3.058 - GLASS-FIBER

EXTERIOR WALL EW2A WINDOW DETAILS


8.079 - FILL FRAME WITH 9.095 - INTERIOR 60 mm REINFORCED CONCRETE (GFRC)
MINERAL WOOL 9.113 - METAL DRIP FLASHING x 27 mm METAL WALL
FOR STUCCO SYSTEM LINING FRAMING FIXED 7.247 - AIR BARRIER TRANSITION

THAAD STANDARD FACILITIES


INSULATION
WITH WALL BRACKETS

VARIOUS LOCATIONS, KSA


MEMBRANE. LAP MEMBRANE
TO CMU OR CONCRETE OVER WINDOW TRIM BY 50 mm

STANDARD DETAILS
9.096 - 15 mm GYPSUM AT 600 mm OC SPACING MIN.
50

WALL BOARD MAX


8.110 - PREFINISHED ALUMINUM

SA-480530
19 MAX
7.188 - SEALANT WINDOW TRIM. 1 mm THICK MIN.
B EXTEND INTO OPENING.
25 MIN

8.121 - PAINTED
GALVANIZED BULLET
GRAPHIC SCALES

50
RESISTANT STEEL 9.096 - 15 mm GYPSUM
WINDOW FRAME WALL BOARD
7.188 - SEALANT
100 50 175 7.188 - SEALANT
7.188 - SEALANT 8.014 - ALUMINUM CURTAINWALL
7.246 - PACK JOINT WITH
325 8.044 - GLAZING AS SCHEDULED, MINERAL WOOL
REFER TO WINDOW SCHEDULE INSULATION

100 175 35

310
2/9/2022 4:44:48 PM

INTERIOR EXTERIOR INTERIOR EXTERIOR


A 0 100 200 400
SHEET ID
SCALE: 1:5 $
HEAD DETAIL HEAD DETAIL
A2 1:5 A6 1:5 UNLESS OTHERWISE NOTED, LINEAR SA564
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

4. REFER TO SHEET SA615, SA616, SA617, SA618, SA619 AND SA620 FOR WINDOW
TYPES.

DATE
COL COL

325
INTERIOR EXTERIOR
300 25
325
8.044 - GLAZING AS SCHEDULED,
150 175 REFER TO WINDOW SCHEDULE
100 175 50
8.079 - FILL FRAME WITH

DESCRIPTION
MINERAL WOOL INSULATION
F 7.188 - SEALANT 8.121 - PAINTED GALVANIZED 7.188 - SEALANT
BULLET RESISTANT STEEL
6.025 - WINDOW STOOL. REFER WINDOW FRAME 6.025 - WINDOW STOOL. REFER 150
TO INTERIORS SHEET SI601 TO INTERIORS SHEET SI601 8.014 - ALUMINUM CURTAINWALL
FINISH LEGEND 8.134 - PREFINISHED ALUMINUM
FINISH LEGEND
SILL FLASHING PAN WITH 50 mm

25 MIN
TURNED UP EDGES. FLASHING 2 7.188 - SEALANT
9.095 - INTERIOR 60 mm x 27 mm mm THICK MIN. COAT NON
9.095 - INTERIOR 60 mm x 27 mm
METAL WALL LINING FRAMING VISIBLE SURFACES OF FLASHING 8.109 - PREFINISHED ALUMINUM
METAL WALL LINING FRAMING
FIXED WITH WALL BRACKETS TO IN CONTACT WITH STEEL FRAME SILL. 2 mm THICK MIN.
FIXED WITH WALL BRACKETS TO
CMU OR CONCRETE AT 600 mm WITH BITUMINOUS PAINT. INTEGRATE SILL WITH CURTAIN
CMU OR CONCRETE AT 600 mm

50
OC SPACING MAX OC SPACING MAX WALL MULLION TO DRAIN
MOISTURE MIGRATING WITHIN
CURTAIN WALL TO EXTERIOR
20 UNO 7.188 - SEALANT 20 UNO
9.107 - CASING BEAD FOR 7.188 - SEALANT

MARK
9.096 - 15 mm GYPSUM WALL STUCCO SYSTEM
BOARD
3.007 - REINFORCED 9.096 - 15 mm GYPSUM WALL 9.107 - CASING BEAD FOR
E 7.176 - EXTRUDED PREFORMED CAST-IN-PLACE CONCRETE BOARD STUCCO SYSTEM
CELLULAR POLYSTYRENE WALL, SEE STRUCTURAL 7.246 - PACK JOINT WITH
BOARD WALL INSULATION RSI DRAWINGS 7.176 - EXTRUDED PREFORMED

PLOT SCALE: PLOT DATE:


MINERAL WOOL INSULATION

2/9/2022 4:45:52
1.68 (R9.52) MIN CELLULAR POLYSTYRENE
7.016 - FLUID-APPLIED BOARD WALL INSULATION RSI 3.007 - REINFORCED
MEMBRANE AIR BARRIER 1.68 (R9.52) MIN CAST-IN-PLACE CONCRETE

SOLICITATION NO.:

SA-480530-1$-SA565DT.dwg
PM
EW-2A WALL, SEE STRUCTURAL

CONTRACT NO.:
9.009 - 25 mm THICK THREE COAT
DRAWINGS

ISSUE DATE:
STUCCO SYSTEM
EW-2A 7.016 - FLUID-APPLIED
MEMBRANE AIR BARRIER

1:1
INTERIOR EXTERIOR

FILE NO.:
SUBMITTED BY:
DESIGN BY:

DRAWN BY:
S. MURPHY
SILL DETAIL SILL DETAIL

A. HANKS
D

A. ORTIZ

E. OKES
CKD BY:

ANSI D
D2 D6

SIZE:
1:5 1:5

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
COL
INTERIOR EXTERIOR

COL 310

INTERIOR EXTERIOR
25 150 100 210
7.246 - PACK JOINT WITH 175 35
C MINERAL WOOL
INSULATION 8.128 - ROLL-UP INSECT SCREEN
150
7.188 - SEALANT
7.188 - SEALANT
8.015 - ALUMINUM WINDOW
9.110 - SCHEDULED 6.025 - WINDOW STOOL.
FLOORING, REFER TO IN 8.014 - ALUMINUM CURTAINWALL REFER TO INTERIORS 8.014 - ALUMINUM CURTAINWALL
SERIES DRAWINGS FOR SHEET SI601 FINISH
FINISH PLANS LEGEND 7.188 - SEALANT
8.109 - PREFINISHED ALUMINUM

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


50

9.095 - INTERIOR 60 mm x 27 mm

EXTERIOR WALL EW2A WINDOW DETAILS


7.188 - SEALANT SILL. 2 mm THICK MIN.
FINISH FLOOR METAL WALL LINING FRAMING
INTEGRATE SILL WITH CURTAIN
FIXED WITH WALL BRACKETS TO
19 MAX

WALL MULLION TO DRAIN

THAAD STANDARD FACILITIES


40

50
CMU OR CONCRETE AT 600 mm
MOISTURE MIGRATING WITHIN

VARIOUS LOCATIONS, KSA


OC SPACING MAX
100

CURTAIN WALL TO EXTERIOR

STANDARD DETAILS
40
60

3.127 - BROOM FINISH


9.111 - FLOORING CAST-IN-PLACE REINFORCED 20 UNO

SA-480530
SETTING BED, REFER CONCRETE STOOP, SEE
B TO IN SERIES STRUCTURAL DRAWINGS.
60
7.188 - SEALANT
DRAWINGS FOR FINISH 9.096 - 15 mm GYPSUM
PLANS 3.098 - PREMOLDED JOINT WALL BOARD 3.007 - REINFORCED
FILLER STRIP EXTENDING FULL CAST-IN-PLACE CONCRETE
3.006 - REINFORCED DEPTH OF SLAB 7.176 - EXTRUDED WALL, SEE STRUCTURAL GRAPHIC SCALES
CONCRETE SLAB, SEE PREFORMED CELLULAR DRAWINGS
3.119 - REINFORCED CONCRETE
STRUCTURAL POLYSTYRENE BOARD
FOUNDATION WALL, SEE 3.058 - GLASS-FIBER
DRAWINGS WALL INSULATION RSI
STRUCTURAL DRAWINGS REINFORCED CONCRETE (GFRC)
1.68 (R9.52) MIN
7.176 - EXTRUDED 200 7.016 - FLUID-APPLIED
3.098 - PREMOLDED JOINT
PREFORMED CELLULAR FILLER STRIP EXTENDING FULL MEMBRANE AIR BARRIER
POLYSTYRENE BOARD DEPTH OF SLAB 7.246 - PACK JOINT WITH
WALL INSULATION RSI MINERAL WOOL
1.68 (R9.52) MIN INSULATION
2/9/2022 4:45:52 PM

A 0 100 200 400


SHEET ID
SILL DETAIL SILL DETAIL SCALE: 1:5 $
A2 1:5 A6 1:5
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA565
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


9.125 - CORNER BEAD FOR PLASTER 1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
SYSTEM M8F0.1P
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND Engineers ®
BASE OF SLOPING WALL SYMBOLS.
BELOW WINDOW SILL Middle East District

20
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

9.011 - 20 mm THICK GYPSUM 4. REFER TO SHEET SA615, SA616, SA617, SA618, SA619 AND SA620 FOR WINDOW
TYPES.

DATE
PLASTER

4.002 - 200 mm
CONCRETE MASONRY
UNIT

GWB SLOPING DOWN

575
INTERIOR

DESCRIPTION
F LINE OF WINDOW SILL BELOW

9.042 - CASING BEAD GYPSUM


PLASTERING SYSTEM

7.188 - SEALANT 7.176 - EXTRUDED PREFORMED


7.009 - COMPRESSIBLE CELLULAR POLYSTYRENE
FILLER BOARD WALL INSULATION RSI
7.246 - PACK JOINT WITH MINERAL
WOOL INSULATION 1.68 (R9.52) MIN
EW-2A.1
COL
8.014 - ALUMINUM CURTAINWALL

MARK
3.007 - REINFORCED

325
CAST-IN-PLACE CONCRETE
E
150

WALL, SEE STRUCTURAL


DRAWINGS

PLOT SCALE: PLOT DATE:


2/9/2022 4:46:30
SOLICITATION NO.:

SA-480530-1$-SA566DT.dwg
PM
CONTRACT NO.:
90

ISSUE DATE:

1:1
7.016 - FLUID-APPLIED
8.109 - PREFINISHED ALUMINUM SILL. MEMBRANE AIR BARRIER
2 mm THICK MIN. INTEGRATE SILL

S. MURPHY / R. THRASHER
9.009 - 25 mm THICK THREE COAT

M. CUNNINGHAM / E.OKES
WITH CURTAIN WALL MULLION TO
DRAIN MOISTURE MIGRATING WITHIN STUCCO SYSTEM
19 MAX

FILE NO.:
CURTAIN WALL TO EXTERIOR 50
9.106 - CORNER BEAD FOR

A. ORTIZ / A. JAIN

SUBMITTED BY:
STUCCO SYSTEM
7.060 - BACKER ROD AND JOINT

DESIGN BY:

DRAWN BY:
SEALANT EXTERIOR

A. HANKS
D

CKD BY:

ANSI D
SIZE:
JAMB DETAIL (MOSQ)

TRANSATLANTIC MIDDLE EAST DISTRICT


D1 1:5

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
COL

310
COL
INTERIOR EXTERIOR 100 210
235 90 8.079 - FILL FRAME WITH
MINERAL WOOL INSULATION 175 35
8.044 - GLAZING AS SCHEDULED,
C 7.062 - CONTINUOUS SEALANT, TYP 7.188 - SEALANT REFER TO WINDOW SCHEDULE

145 150 6.025 - WINDOW STOOL.


6.001 - ROUGH CARPENTRY 8.014 - ALUMINUM CURTAINWALL REFER TO INTERIORS 8.121 - PAINTED GALVANIZED
SHEET SI601 FINISH BULLET RESISTANT STEEL
LEGEND WINDOW FRAME
7.188 - SEALANT
6.025 - WINDOW STOOL. REFER TO 7.188 - SEALANT
INTERIORS SHEET SI601 FINISH 9.095 - INTERIOR 60 mm
LEGEND 8.109 - PREFINISHED ALUMINUM x 27 mm METAL WALL
19 MA X

SILL. 2 mm THICK MIN. LINING FRAMING FIXED 8.134 - PREFINISHED ALUMINUM


INTEGRATE SILL WITH CURTAIN SILL FLASHING PAN WITH 50 mm

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


50

WITH WALL BRACKETS


WALL MULLION TO DRAIN TURNED UP EDGES. FLASHING 2

EXTERIOR WALL EW2A WINDOW DETAILS


TO CMU OR CONCRETE
MOISTURE MIGRATING WITHIN AT 600 mm OC SPACING mm THICK MIN. COAT NON
CURTAIN WALL TO EXTERIOR MAX VISIBLE SURFACES OF FLASHING

THAAD STANDARD FACILITIES


7.062 - CONTINUOUS SEALANT, TYP IN CONTACT WITH STEEL FRAME

VARIOUS LOCATIONS, KSA


7.188 - SEALANT 20 UNO WITH BITUMINOUS PAINT.

STANDARD DETAILS
9.032 - 15 mm GYPSUM WALLBOARD 9.107 - CASING BEAD FOR
OVER 60 mm MET. STUDS OR 20 mm STUCCO SYSTEM 7.188 - SEALANT
60

SA-480530
THICK GYPSUM PLASTER WHERE 9.096 - 15 mm GYPSUM
9.009 - 25 mm THICK THREE COAT
B SCHEDULED.
STUCCO SYSTEM WALL BOARD 3.007 - REINFORCED
CAST-IN-PLACE CONCRETE
7.176 - EXTRUDED PREFORMED 7.246 - PACK JOINT WITH WALL, SEE STRUCTURAL
MINERAL WOOL INSULATION 7.176 - EXTRUDED DRAWINGS
CELLULAR POLYSTYRENE BOARD
WALL INSULATION RSI 1.68 (R9.52)
MIN
3.007 - REINFORCED
PREFORMED CELLULAR
POLYSTYRENE BOARD 3.058 - GLASS-FIBER GRAPHIC SCALES
CAST-IN-PLACE CONCRETE WALL INSULATION RSI REINFORCED CONCRETE (GFRC)
WALL, SEE STRUCTURAL 1.68 (R9.52) MIN
9.095 - INTERIOR 60 mm
DRAWINGS 7.016 - FLUID-APPLIED
x 27 mm METAL WALL
LINING FRAMING FIXED 7.016 - FLUID-APPLIED MEMBRANE AIR BARRIER
WITH WALL BRACKETS MEMBRANE AIR BARRIER
TO CMU OR CONCRETE
AT 600 mm OC SPACING EW-2A.1
MAX
2/9/2022 4:46:30 PM

INTERIOR EXTERIOR
A 0 100 200 400
SHEET ID
SILL DETAIL (MOSQ) SILL DETAIL $
A1 1:5 A6 1:5
SCALE: 1:5

UNLESS OTHERWISE NOTED, LINEAR


DIMENSIONS ARE IN MILLIMETERS
SA566
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
COL US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

7.016 - FLUID-APPLIED 4. REFER TO SHEET SA615, SA616, SA617, SA618, SA619 AND SA620 FOR WINDOW
TYPES.

DATE
MEMBRANE AIR
BARRIER
7.267 - RIGID BOARD
WALL INSULATION,
RSI=2.29 (R-13) MINIMUM
4.033 - 100 mm
CONCRETE MASONRY
UNIT
9.009 - 25 mm THICK
THREE COAT STUCCO
SYSTEM
4.012 - SCREW TYPE
VENEER ANCHORS.
REFER TO

DESCRIPTION
9.011 - 20 mm THICK
F GYPSUM PLASTER SPECIFICATION
SECTION 04 20 00 FOR
SPACING
5.234 - CONC
SCREW/ANCHOR INTO 7.039 - STRIP
GROUTED CMU BLOCK TRANSITION MEMBRANE
@ 300 mm ON CENTER ONTO FLASHING TO
CAPABLE OF MAINTAIN AIR BARRIER
SUPPORTING CONTINUITY
ALLOWABLE SHEAR 4.013 - CAVITY NET /
LOAD OF 2.65kN MORTAR CONTROL
DEVICE
4.024 - MASONRY 7.276 - FLEXIBLE
LINTEL, SEE FLASHING - SEAL AND
STRUCTURAL ADHERE TO DRIP EDGE
DRAWINGS
7.042 - THRU-WALL
FLASHING WITH WEEP

MARK
VENTILATORS AT 600
mm OC, TYP
E
7.084 - STAINLESS
9.028 - CORNER BEAD, STEEL DRIP EDGE SET

PLOT SCALE: PLOT DATE:


2/9/2022 4:46:35
TYP IN BED OF SEALANT
5.219 - L203 mm x 152

SOLICITATION NO.:

SA-480530-1$-SA567DT.dwg
mm x 12.7 mm GALV

PM
CONTRACT NO.:
STEEL LINTEL ANGLE -

ISSUE DATE:
PAINTED, BEAR LINTEL
MIN OF 200 mm ON

1:1
EACH SIDE OF VENEER
7.060 - BACKER ROD
AND JOINT SEALANT
200

FILE NO.:
M. MacEACHERN
SUBMITTED BY:
W. RODRIGUEZ
C. SCORZELLI
DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
HEAD DETAIL

SIZE:
D6 1:5

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


COL

WINCHESTER, VA 22602
200
9.009 - 25 mm THICK
THREE COAT STUCCO
4.033 - 100 mm CONCRETE SYSTEM
MASONRY UNIT
3.134 - PRECAST 6.006 - 20 mm SOLID
7.267 - RIGID BOARD CONCRETE SILL BELOW SURFACE WINDOW 8.015 - ALUMINUM
WALL INSULATION, STOOL WITH EASED WINDOW
RSI=2.29 (R-13) MINIMUM 7.060 - BACKER ROD AND JOINT EDGE
SEALANT 7.060 - BACKER ROD
C 7.016 - FLUID-APPLIED
8.015 - ALUMINUM WINDOW
AND JOINT SEALANT
MEMBRANE AIR 3.083 - PRECAST CONCRETE
BARRIER WINDOW SILL
245

7.062 - CONTINUOUS

40
SEALANT, TYP
20 UNO

50
200
225

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


EXT. WALL ASSEMBLY

3.047 - CONCRETE DRIP

EXTERIOR WALL EW1 WINDOW DETAILS


4.043 - 250 mm SOLID
SEE FLOOR PLAN

GROOVE
CMU CUT IN FIELD TO 30
SUPPORT PRECAST SILL 7.274 - STAINLESS

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
STEEL FLASHING WITH
COL

DRIP EDGE. SET

STANDARD DETAILS
FLASHING IN BED OF
SEALANT

SA-480530
7.276 - FLEXIBLE FLASHING -
B SEAL AND ADHERE TO DRIP
EDGE
9.011 - 20 mm THICK 3.133 - SS DOWEL OR GRAVITY
GYPSUM PLASTER CONNECTOR GRAPHIC SCALES
9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM

4.012 - SCREW TYPE VENEER


25 ANCHORS. REFER TO
SPECIFICATION SECTION 04 20
9.011 - 20 mm THICK 6.006 - 20 mm SOLID 00 FOR SPACING
GYPSUM PLASTER SURFACE WINDOW
STOOL WITH EASED 7.267 - RIGID BOARD WALL
EDGE INSULATION, RSI=2.29 (R-13)
MINIMUM
2/9/2022 4:46:35 PM

7.016 - FLUID-APPLIED
A MEMBRANE AIR BARRIER 0 100 200 400
SHEET ID
$
WINDOW JAMB DETAIL SILL DETAIL SCALE: 1:5
A3 1:5 A6 1:5
UNLESS OTHERWISE NOTED, LINEAR SA567
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
COL US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA601 FOR EXTERIOR WALL TYPES.

7.016 - FLUID-APPLIED 4. REFER TO SHEET SA615, SA616, SA617, SA618, SA619 AND SA620 FOR WINDOW
MEMBRANE AIR TYPES.

DATE
BARRIER
7.267 - RIGID BOARD
WALL INSULATION,
RSI=2.29 (R-13) MINIMUM
4.033 - 100 mm
CONCRETE MASONRY
UNIT
3.007 - REINFORCED
CAST-IN-PLACE 9.009 - 25 mm THICK
CONCRETE WALL, SEE THREE COAT STUCCO
STRUCTURAL SYSTEM
DRAWINGS 4.012 - SCREW TYPE
VENEER ANCHORS.
REFER TO

DESCRIPTION
SPECIFICATION
F SECTION 04 20 00 FOR
SPACING
5.218 - CONCRETE 7.039 - STRIP
SCREW/ANCHOR @ 300 TRANSITION MEMBRANE
mm ON CENTER ONTO FLASHING TO
CAPABLE OF MAINTAIN AIR BARRIER
SUPPORTING AN CONTINUITY
ALLOWABLE SHEAR
LOAD OF 2.65 Kn 4.013 - CAVITY NET /
MORTAR CONTROL
DEVICE
7.276 - FLEXIBLE
FLASHING - SEAL AND
ADHERE TO DRIP EDGE
7.042 - THRU-WALL

MARK
FLASHING WITH WEEP
VENTILATORS AT 600
mm OC, TYP
E
7.084 - STAINLESS
STEEL DRIP EDGE SET

PLOT SCALE: PLOT DATE:


2/9/2022 4:46:39
IN BED OF SEALANT

5.219 - L203 mm x 152

SOLICITATION NO.:

SA-480530-1$-SA568DT.dwg
mm x 12.7 mm GALV

PM
CONTRACT NO.:
STEEL LINTEL ANGLE -

ISSUE DATE:
PAINTED, BEAR LINTEL
MIN OF 200 mm ON

1:1
EACH SIDE OF VENEER
7.060 - BACKER ROD
AND JOINT SEALANT
200

FILE NO.:
HEAD DETAIL

M. MacEACHERN
SUBMITTED BY:
W. RODRIGUEZ
C. SCORZELLI
E6

DESIGN BY:

DRAWN BY:

A. HANKS
1:5
D

CKD BY:

ANSI D
SIZE:
3.007 - REINFORCED
CAST-IN-PLACE CONCRETE

TRANSATLANTIC MIDDLE EAST DISTRICT


WALL, SEE STRUCTURAL

US ARMY CORPS OF ENGINEERS


DRAWINGS COL

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
200

8.015 - ALUMINUM
WINDOW
7.060 - BACKER ROD
AND JOINT SEALANT

C 3.083 - PRECAST
245
CONCRETE WINDOW
SILL

40
COL

50
3.007 - REINFORCED 3.047 - CONCRETE DRIP
CAST-IN-PLACE

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


GROOVE
CONCRETE WALL, SEE

EXTERIOR WALL EW1A WINDOW DETAILS


45
STRUCTURAL 7.274 - STAINLESS STEEL
8.015 - ALUMINUM WINDOW DRAWINGS FLASHING WITH DRIP EDGE. SET

THAAD STANDARD FACILITIES


FLASHING IN BED OF SEALANT

VARIOUS LOCATIONS, KSA

STANDARD DETAILS
7.276 - FLEXIBLE FLASHING -
7.060 - BACKER ROD SEAL AND ADHERE TO DRIP

SA-480530
AND JOINT SEALANT EDGE
B
3.133 - SS DOWEL OR GRAVITY
CONNECTOR
25 7.016 - FLUID-APPLIED
MEMBRANE AIR BARRIER
9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM
GRAPHIC SCALES
3.134 - PRECAST
7.267 - RIGID BOARD WALL 4.012 - SCREW TYPE VENEER
CONCRETE SILL BELOW
INSULATION, RSI=2.29 (R-13) ANCHORS. REFER TO
MINIMUM SPECIFICATION SECTION 04 20
00 FOR SPACING
4.033 - 100 mm CONCRETE
MASONRY UNIT 7.267 - RIGID BOARD WALL
INSULATION, RSI=2.29 (R-13)
MINIMUM
9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM 7.016 - FLUID-APPLIED
MEMBRANE AIR BARRIER
2/9/2022 4:46:39 PM

A JAMB DETAIL SILL DETAIL 0 100 200 400


SHEET ID
A2 1:5 A6 1:5
$
SCALE: 1:5

UNLESS OTHERWISE NOTED, LINEAR


DIMENSIONS ARE IN MILLIMETERS
SA568
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
G

DATE
SEE STRUCTURE 200
THERMALLY BROKEN TO LINTEL
ALUMINUM WINDOW
SYSTEM

DESCRIPTION
F CONT FLUID APPLIED
AIR/VAPOR BARRIER
STUCCO FINISH 10mm REVEAL WITH
SEALANT
CONT TERMINATION
CMU BACK-UP
BAR
100mm CMU
20mm END DAM 7.267 - RIGID BOARD WALL
WEEP SCREED INSULATION, RSI=2.29 (R-13)
9.011 - 20 mm THICK MINIMUM
GYPSUM PLASTER
END DAM STUCCO FINISH 9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM
3.007 - REINFORCED
CAST-IN-PLACE 100mm SOLID CMU
SL HEAD
WINDOW SILL OP CONCRETE WALL, SEE
E STRUCTURAL
SI
LL DRIP EDGE DRAWINGS THRU-WALL FLASHING

MARK
WITH CELL VENTS @
400mm O.C.
E METAL
CORNER
ALUMINUM BEAD

PLOT SCALE: PLOT DATE:


2/9/2022 4:47:28
SILL STAINLESS STEEL
WEEP SCREED

SOLICITATION NO.:

SA-480530-1$-SA569DT.dwg
PM
CONTRACT NO.:
PLASTER FINISH GALVANIZED STEEL

ISSUE DATE:
RETURN TO WINDOW LINTEL - SEE STRUCT
FRAME

1:1
PLASTIC SHIM WITH
10mm REVEAL WITH BACKER ROD AND
SEALANT SEALANT
THERMALLY BROKEN ALUMINUM
120 WINDOW AND RECEPTOR

FILE NO.:
TO WINDOW

SUBMITTED BY:
W. LOCKWOOD
J. BLANCHARD
EXT WALL ASSEMBLY
INTERIOR EXTERIOR

DESIGN BY:

DRAWN BY:
SEE FLOOR PLAN

A. HANKS
D

E. OKES
CKD BY:

ANSI D
SIZE:
WINDOW DETAIL HEAD DETAIL
D2 D6

TRANSATLANTIC MIDDLE EAST DISTRICT


1:5 1:5

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
EXTERIOR
9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM
STAINLESS STEEL EXT WALL ASSEMBLY
100mm CMU
CORNER BEAD SEE FLOOR PLAN THERMALLY BROKEN
7.267 - RIGID BOARD WALL 120 ALUM WINDOW
INSULATION, RSI=2.29 (R-13)
100mm SOLID CMU
MINIMUM
AT JAMB 10mm REVEAL WITH
C 7.016 - FLUID-APPLIED MEMBRANE CONCRETE ATTACHED SEALANT
AIR BARRIER ADJUSTABLE DOVE-TAIL SILL EXTENSION WITH
MASONRY ANCHOR DRIP- FINISH
TO MATCH WINDOW
10MM REVEAL WITH
SEALANT
45 150mm SOLID CMU
PLASTIC SHIM AT WINDOW SILL
120

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


100
EXT WALL ASSEMBLY

THERMALLY BROKEN ALUMINUM


SEE FLOOR PLAN

THAAD STANDARD FACILITIES


WINDOW AND RECEPTOR

VARIOUS LOCATIONS, KSA


METAL CASING BEAD

STANDARD DETAILS
WINDOW DETAILS
CONT FLUID APPLIED

SA-480530
AIR/VAPOR BARRIER
B
10MM REVEAL WITH 13mm SOLID SURFACE
SEALANT SILL - SET AND LEVEL
IN BED OF MASTIC
GRAPHIC SCALES
13mm SOLID SURFACE
APRON
45

10mm THERMAL BREAK


9.011 - 20 mm THICK GYPSUM
PLASTER 100mm CMU
CONCRETE WALL
30
3.007 - REINFORCED CAST-IN-PLACE REINFORCED CONCRETE WALL,
CONCRETE WALL, SEE STRUCTURAL STAINLESS STEEL SEE STRUCTURAL
DRAWINGS CORNER BEAD
INTERIOR EXTERIOR
2/9/2022 4:47:28 PM

INTERIOR
A 0 100 200 400
SHEET ID
$
JAMB DETAILS SILL DETAIL SCALE: 1:5
A2 1:5 A6 1:5
UNLESS OTHERWISE NOTED, LINEAR SA569
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO SHEET SA602, SA603 AND SA604 FOR INTERIOR WALL TYPES.

4. REFER TO SHEET SA615, SA616, SA617, SA618, SA619 AND SA620 FOR WINDOW
TYPES.

DATE
INTERIOR
(VESTIBULE)

DESCRIPTION
F INTERIOR INTERIOR
(VESTIBULE)
M8F0.1P2 19 MAX M8F0.1P2

50
9.125 - CORNER BEAD FOR 9.011 - 20 mm THICK
PLASTER SYSTEM GYPSUM PLASTER
7.188 - SEALANT 7.246 - PACK JOINT WITH 4.018 - BOND BEAM, SEE
MINERAL WOOL STRUCTURAL DRAWINGS
8.014 - ALUMINUM CURTAINWALL INSULATION
8.044 - GLAZING AS SCHEDULED, 9.011 - 20 mm THICK GYPSUM
REFER TO WINDOW SCHEDULE 9.125 - CORNER BEAD PLASTER
FOR PLASTER SYSTEM

50
19 MAX

MARK
9.125 - CORNER BEAD FOR

150

240
PLASTER SYSTEM
E 7.188 - SEALANT
7.188 - SEALANT

PLOT SCALE: PLOT DATE:


2/9/2022 4:48:14
25
8.014 - ALUMINUM CURTAINWALL

SOLICITATION NO.:

SA-480530-1$-SA570DT.dwg
7.188 - SEALANT 150 25

PM
CONTRACT NO.:
8.044 - GLAZING AS SCHEDULED,

ISSUE DATE:
REFER TO WINDOW SCHEDULE
9.125 - CORNER BEAD FOR 240

1:1
PLASTER SYSTEM

INTERIOR

FILE NO.:
SUBMITTED BY:
DESIGN BY:

DRAWN BY:
S. MURPHY

A. HANKS
D

A. ORTIZ

E. OKES
CKD BY:

ANSI D
SIZE:
JAMB DETAIL HEAD DETAIL

TRANSATLANTIC MIDDLE EAST DISTRICT


D2 D6

US ARMY CORPS OF ENGINEERS


1:5 1:5

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
INTERIOR INTERIOR
C (VESTIBULE)
INTERIOR INTERIOR
(VESTIBULE)

200 240
25
25 150 8.044 - GLAZING AS SCHEDULED, 45 195
7.188 - SEALANT 8.044 - GLAZING AS SCHEDULED,
REFER TO WINDOW SCHEDULE
REFER TO WINDOW SCHEDULE
8.014 - ALUMINUM CURTAINWALL
4.002 - 200 mm 8.014 - ALUMINUM CURTAINWALL
CONCRETE MASONRY

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


7.246 - PACK JOINT WITH

INTERIOR WALL M8F0.1P2 WINDOW DETAILS


UNIT 7.246 - PACK JOINT WITH
MINERAL WOOL INSULATION
MINERAL WOOL INSULATION
7.188 - SEALANT
7.188 - SEALANT 9.011 - 20 mm THICK

THAAD STANDARD FACILITIES


7.188 - SEALANT
19 MAX

VARIOUS LOCATIONS, KSA


GYPSUM PLASTER
9.092 - FINISH FLOOR AS

19 MAX

STANDARD DETAILS
SCHEDULED 9.011 - 20 mm THICK GYPSUM
9.092 - FINISH FLOOR AS
PLASTER
50

SCHEDULED

50

SA-480530
B
30

3.094 - THICKSET MORTAR BED

M8F0.1P2 M8F0.1P2
GRAPHIC SCALES
3.006 - REINFORCED CONCRETE
SLAB, SEE STRUCTURAL
DRAWINGS
2/9/2022 4:48:14 PM

A 0 100 200 400


SHEET ID
SCALE: 1:5 $
SILL DETAIL JAMB DETAIL
A2 1:5 A6 1:5 UNLESS OTHERWISE NOTED, LINEAR SA570
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
G

DATE
INTERIOR INTERIOR

DESCRIPTION
F 3.007 - REINFORCED 3.007 - REINFORCED
CAST-IN-PLACE CONCRETE CAST-IN-PLACE CONCRETE
COL WALL, SEE STRUCTURAL COL
WALL, SEE STRUCTURAL
DRAWINGS DRAWINGS
BELOW BELOW

STRUCTURAL WALL

STRUCTURAL WALL
300

300
8.126 - LOUVER SCREEN 8.126 - LOUVER SCREEN

BELOW

BELOW

MARK
25
25
E

PLOT SCALE: PLOT DATE:


8.021 - ALUMINUM SAND LOUVER

2/9/2022 4:49:11
8.021 - ALUMINUM SAND LOUVER

SEE MANUFACTURERS

SOLICITATION NO.:

SA-480530-1$-SA595DT.dwg
PM
LITERATURE FOR LOUVER

CONTRACT NO.:
8.021 - ALUMINUM SAND LOUVER
WIDTHS THAT NEED TO BE

ISSUE DATE:
INSTALLED ON SITE IN
SECTIONS

1:1
EXTERIOR EXTERIOR

FILE NO.:
LOUVER WIDTH LOUVER WIDTH LOUVER WIDTH
SEE PLAN AND

SUBMITTED BY:
W. LOCKWOOD
SEE PLAN AND SEE PLAN AND

J. BLANCHARD

K. BERTHOLF
SCHEDULE FOR TYPE SCHEDULE FOR TYPE SCHEDULE FOR TYPE

DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
SIZE:
SAND LOUVER JAMB DETAIL SAND LOUVER JAMB DETAIL - EW-2A
D4 D6

TRANSATLANTIC MIDDLE EAST DISTRICT


1:5 1:5

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
7.060 - BACKER ROD AND JOINT COL
SEALANT INTERIOR INTERIOR
9.106 - CORNER BEAD FOR STUCCO 3.007 - REINFORCED
SYSTEM EXTERIOR 3.007 - REINFORCED CAST-IN-PLACE CONCRETE
CAST-IN-PLACE CONCRETE WALL, SEE STRUCTURAL
9.009 - 25 mm THICK THREE COAT WALL, SEE STRUCTURAL DRAWINGS
STUCCO SYSTEM LOUVER WIDTH DRAWINGS
BELOW
C SEE PLAN AND
SCHEDULE FOR TYPE
7.016 - FLUID-APPLIED MEMBRANE COL 7.060 - BACKER ROD AND JOINT COL 7.060 - BACKER ROD AND JOINT
AIR BARRIER SEALANT SEALANT
8.021 - ALUMINUM SAND LOUVER 6.015 - SHIM AS REQUIRED 6.015 - SHIM AS REQUIRED
3.007 - REINFORCED CAST-IN-PLACE
CONCRETE WALL, SEE STRUCTURAL 8.126 - LOUVER SCREEN
DRAWINGS

STRUCTURAL WALL
25

SEE STRUCTURAL

AT ARC FLASH DUCT SAND LOUVER


300

300
L51X51X6.4 CONT GALV ANGLE

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


BELOW
BOLTED TO WALL
STRUCTURAL

MIN 2 CONNECTIONS PER ANGLE


SEE

THAAD STANDARD FACILITIES


AT ARCH FLASH DUCT SAND LOUVER

VARIOUS LOCATIONS, KSA


125

LOUVER DETAILS - EW-2A


GRATING MF TO PROVIDE CONNECTION

STANDARD DETAILS
300

OF GRATING TO STEEL ANGLE


SUPPORT
25

25

SA-480530
B 8.021 - ALUMINUM SAND LOUVER
7.016 - FLUID-APPLIED MEMBRANE
8.021 - ALUMINUM SAND LOUVER
AT ARC FLASH DUCT SAND LOUVER AIR BARRIER
GALVANIZED STEEL GRATING 7.060 - BACKER ROD AND JOINT 3.114 - REINFORCED CAST-IN-PLACE

7.267 - RIGID BOARD WALL


COL
SEALANT
9.106 - CORNER BEAD FOR
CONCRETE COLUMN, SEE
STRUCTURAL DRAWINGS GRAPHIC SCALES
INSULATION, RSI=2.29 (R-13) STUCCO SYSTEM
9.009 - 25 mm THICK THREE COAT
MINIMUM 9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM
8.126 - LOUVER SCREEN STUCCO SYSTEM
9.095 - INTERIOR 60 mm x 27 mm BIRD SCREEN 9.106 - CORNER BEAD FOR STUCCO
7.016 - FLUID-APPLIED
METAL WALL LINING FRAMING SYSTEM
MEMBRANE AIR BARRIER
FIXED WITH WALL BRACKETS TO
CMU OR CONCRETE AT 600 mm 9.123 - 25 mm WIDE STUCCO
9.096 - 15 mm GYPSUM WALL BOARD
OC SPACING MAX EXTERIOR CONTROL JOINT WITH SEALANT. EXTERIOR
REFER TO SHEET SA510
INTERIOR LOUVER WIDTH SEE PLAN LOUVER WIDTH
2/9/2022 4:49:11 PM

SEE PLAN AND SEE PLAN AND


SCHEDULE FOR TYPE SCHEDULE FOR TYPE
A 0 100 200 400
SHEET ID
SCALE: 1:5 $
SAND LOUVER JAMB DETAIL - EW-2A SAND LOUVER JAMB DETAIL SAND LOUVER JAMB DETAIL - EW-2A
A1 1:5 A4 1:5 A6 1:5 UNLESS OTHERWISE NOTED, LINEAR SA596
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

COL

SEE STRUCTURAL 25 US Army Corps of


Engineers ®
125 8.021 - ALUMINUM SAND LOUVER
Middle East District
G

DATE
8.021 - ALUMINUM SAND LOUVER

INTERMEDIATE SAND CHUTE


CENTERED ON TALLER LOUVERS
PER MANUFACTURERS
RECOMENDATION

8.021 - ALUMINUM SAND LOUVER

8.126 - LOUVER SCREEN

DESCRIPTION
F
INTERIOR EXTERIOR
COL

SAND LOUVER DETAIL 300 25


F3 1:5
INTERIOR
100 125
EXTERIOR

8.126 - LOUVER SCREEN


8.021 - ALUMINUM SAND LOUVER
COL

SEE STRUCTURE 25

MARK
125 8.021 - ALUMINUM SAND LOUVER
8.142 - SAND LOUVER SAND
75 FACE OF STRUCTURE
E 50
CHUTE
7.060 - BACKER ROD AND JOINT
LOUVER REINFORCMENT / 6.015 - SHIM AS REQUIRED SEALANT

PLOT SCALE: PLOT DATE:


2/9/2022 4:50:09
REMOVABLE FRAMING 8.143 - ALUMINUM TRIM
SEE STRUCTURAL 7.060 - BACKER ROD AND JOINT CLOSURE BY SAND LOUVER
SEALANT SUPPLIER

SOLICITATION NO.:

SA-480530-1$-SA596DT.dwg
PM
CONTRACT NO.:
8.021 - ALUMINUM SAND LOUVER 3.007 - REINFORCED FASTENERS
CAST-IN-PLACE CONCRETE

ISSUE DATE:
WALL, SEE STRUCTURAL REGLET AND COUNTERFLASHING
DRAWINGS

1:1
INTERMEDIATE SAND CHUTE TERMINATION BAR
LOCATED ON TALLER LOUVERS
PER MANUFACTURERS 7.038 - EXTEND EPDM
RECOMENDATION MEMBRANE ON VERTICAL FACE
OF PARAPET UP TO 750 mm

FILE NO.:
8.021 - ALUMINUM SAND LOUVER ABOVE TOP OF ROOF SLAB TO
TERMINATION BAR, UNO

SUBMITTED BY:
W. LOCKWOOD
J. BLANCHARD
8.126 - LOUVER SCREEN

K. BERTHOLF
DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
INTERIOR EXTERIOR

SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
US ARMY CORPS OF ENGINEERS
SAND LOUVER AT INTERMEDIATE SUPPORT SAND LOUVER SILL DETAIL

201 PRINCE FREDERICK DRIVE,


D3 D6

WINCHESTER, VA 22602
1:5 1:5

COL COL

C 300 25 300 25
INTERIOR EXTERIOR INTERIOR EXTERIOR
100 125 100 125

8.126 - LOUVER SCREEN


8.126 - LOUVER SCREEN
8.021 - ALUMINUM SAND LOUVER
7.188 - SEALANT
8.021 - ALUMINUM SAND LOUVER
3.098 - PREMOLDED JOINT FILLER

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


STRIP EXTENDING FULL DEPTH OF
SLAB

THAAD STANDARD FACILITIES


3.006 - REINFORCED CONCRETE 8.142 - SAND LOUVER SAND 8.142 - SAND LOUVER SAND

VARIOUS LOCATIONS, KSA

LOUVER DETAILS - EW-2A


SLAB, SEE STRUCTURAL DRAWINGS CHUTE 50 CHUTE

STANDARD DETAILS
8.143 - ALUMINUM TRIM 8.143 - ALUMINUM TRIM
3.139 - UNDER SLAB VAPOR BARRIER CLOSURE BY SAND LOUVER CLOSURE BY SAND LOUVER
50

SA-480530
SUPPLIER SUPPLIER
B
9.107 - CASING BEAD FOR
STUCCO SYSTEM 7.060 - BACKER ROD AND JOINT
9.009 - 25 mm THICK THREE COAT
SEALANT
6.015 - SHIM AS REQUIRED
GRAPHIC SCALES
STUCCO SYSTEM
6.015 - SHIM AS REQUIRED 9.093 - ELASTOMERIC COATING
7.016 - FLUID-APPLIED
7.016 - FLUID-APPLIED MEMBRANE AIR BARRIER
MEMBRANE AIR BARRIER
3.119 - REINFORCED CONCRETE 3.007 - REINFORCED
FOUNDATION WALL, SEE CAST-IN-PLACE CONCRETE
3.024 - BLINDING CONCRETE, SEE WALL, SEE STRUCTURAL
STRUCTURAL DRAWINGS
STRUCTURAL DRAWINGS DRAWINGS
SEE STRUCTURAL
DRAWINGS
2/9/2022 4:50:09 PM

A 0 100 200 400


SHEET ID
SCALE: 1:5 $
SAND LOUVER SILL DETAIL SAND LOUVER SILL DETAIL
A3 1:5 A6 1:5 UNLESS OTHERWISE NOTED, LINEAR SA597
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
G

DATE
DESCRIPTION
F COL COL
300 25 3.007 - REINFORCED
300 25 CAST-IN-PLACE CONCRETE
WALL, SEE STRUCTURAL
7.267 - RIGID BOARD WALL 7.267 - RIGID BOARD WALL DRAWINGS
INSULATION, RSI=2.29 (R-13) INSULATION, RSI=2.29 (R-13)
7.016 - FLUID-APPLIED 7.016 - FLUID-APPLIED
MINIMUM MINIMUM
MEMBRANE AIR BARRIER MEMBRANE AIR BARRIER
9.095 - INTERIOR 60 mm x 27 mm 9.009 - 25 mm THICK THREE COAT 9.095 - INTERIOR 60 mm x 27 mm 9.009 - 25 mm THICK THREE COAT
METAL WALL LINING FRAMING STUCCO SYSTEM METAL WALL LINING FRAMING STUCCO SYSTEM
FIXED WITH WALL BRACKETS TO FIXED WITH WALL BRACKETS TO
CMU OR CONCRETE AT 600 mm 6.015 - SHIM AS REQUIRED CMU OR CONCRETE AT 600 mm 6.015 - SHIM AS REQUIRED
OC SPACING MAX OC SPACING MAX
9.107 - CASING BEAD FOR 9.107 - CASING BEAD FOR
STUCCO SYSTEM STUCCO SYSTEM
9.096 - 15 mm GYPSUM WALL
BOARD 7.060 - BACKER ROD AND JOINT 7.060 - BACKER ROD AND JOINT

MARK
SEALANT 9.096 - 15 mm GYPSUM WALL SEALANT
7.188 - SEALANT
BOARD
E ARC FLASH DUCT SAND LOUVER
GRATING MF TO PROVIDE CONNECTION 7.188 - SEALANT
OF GRATING TO STEEL ANGLE

PLOT SCALE: PLOT DATE:


2/9/2022 4:50:56
SUPPORT
8.126 - LOUVER SCREEN
8.126 - LOUVER SCREEN

SOLICITATION NO.:

SA-480530-1$-SA597DT.dwg
PM
8.126 - LOUVER SCREEN

CONTRACT NO.:
ISSUE DATE:
8.021 - ALUMINUM SAND LOUVER
8.021 - ALUMINUM SAND LOUVER
ARC FLASH DUCT SAND LOUVER

1:1
GALVANIZED STEEL GRATING 125
INTERIOR EXTERIOR
ARC FLASH DUCT SAND LOUVER 125
L51X51X6.4 CONT GALV ANGLE
BOLTED TO WALL
MIN 2 CONNECTIONS PER ANGLE

FILE NO.:
INTERIOR EXTERIOR

SUBMITTED BY:
W. LOCKWOOD
J. BLANCHARD

K. BERTHOLF
DESIGN BY:

DRAWN BY:

A. HANKS
D

CKD BY:

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
SAND LOUVER HEAD DETAIL SAND LOUVER HEAD DETAIL
D3 D6

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


1:5 1:5

WINCHESTER, VA 22602
COL
3.116 - REINFORCED
300 25 CAST-IN-PLACE CONCRETE
COL BEAM, SEE STRUCTURAL
INTERIOR EXTERIOR
300 25 DRAWINGS
C 9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM
125 8.021 - ALUMINUM SAND LOUVER
ARC FLASH DUCT SAND LOUVER 7.247 - AIR BARRIER TRANSITION
GALVANIZED STEEL GRATING MEMBRANE. LAP MEMBRANE
8.021 - ALUMINUM SAND LOUVER
OVER WINDOW TRIM BY 50 mm
7.016 - FLUID-APPLIED MIN.
8.126 - LOUVER SCREEN

100
ARC FLASH DUCT SAND LOUVER MEMBRANE AIR BARRIER
9.107 - CASING BEAD FOR
GRATING MF TO PROVIDE CONNECTION
SEE STRUCTURAL DRAWINGS STUCCO SYSTEM
OF GRATING TO STEEL ANGLE
FOR TOP OF WALL CONDITION PREFINISHED ALUMINUM HEAD
SUPPORT
BELOW BEAM

.
8.142 - SAND LOUVER SAND FLASHING WITH DRIP EDEGE.

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


ARC FLASH DUCT SAND LOUVER CHUTE FLASHING 2 mm THICK MIN. COAT
L51X51X6.4 CONT GALV ANGLE 7.188 - SEALANT
NON VISIBLE SURFACES OF
BOLTED TO WALL 8.143 - ALUMINUM TRIM

49 MIN
PACK JOINT WITH MINERAL FLASHING IN CONTACT WITH

THAAD STANDARD FACILITIES


MIN 2 CONNECTIONS PER ANGLE CLOSURE BY SAND LOUVER

20
DISSIMILAR MATERIALS WITH

VARIOUS LOCATIONS, KSA


50 WOOL AND SEAL BOTH SIDES

LOUVER DETAILS - EW-2A


SUPPLIER
BITUMINOUS PAINT.

STANDARD DETAILS
7.188 - SEALANT 7.060 - BACKER ROD AND JOINT 7.188 - SEALANT
SEALANT 8.126 - LOUVER SCREEN

SA-480530
9.096 - 15 mm GYPSUM 9.107 - CASING BEAD FOR
B WALL BOARD STUCCO SYSTEM
8.021 - ALUMINUM SAND LOUVER
9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM
9.095 - INTERIOR 60 mm x 27 mm 6.015 - SHIM AS REQUIRED
METAL WALL LINING FRAMING FIXED
WITH WALL BRACKETS TO CMU OR 7.016 - FLUID-APPLIED 125
GRAPHIC SCALES
CONCRETE AT 600 mm OC SPACING MEMBRANE AIR BARRIER
MAX 3.007 - REINFORCED
7.267 - RIGID BOARD WALL CAST-IN-PLACE CONCRETE
INSULATION, RSI=2.29 (R-13) SEE STRUCTURAL
WALL, SEE STRUCTURAL INTERIOR EXTERIOR
MINIMUM DRAWINGS DRAWINGS
2/9/2022 4:50:56 PM

A SAND LOUVER SILL DETAIL SAND LOUVER HEAD DETAIL 0 100 200 400
SHEET ID
A3 1:5 A6 1:5
SCALE: 1:5 $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA598
1 2 3 4 5 6 7 8 9 10

US Army Corps of
9.009 - 25 mm THICK THREE COAT
4.002 - 200 mm Engineers ®
STUCCO SYSTEM
CONCRETE MASONRY Middle East District
UNIT
G
9.108 - DRIP SCREED FOR
STUCCO SYSTEM

DATE
7.062 - CONTINUOUS SEALANT,
TYP

5.237 - CONT GALV


STEEL CLIP ANGLE AND
ANCHORS
8.021 - ALUMINUM SAND LOUVER

INTERIOR EXTERIOR

DESCRIPTION
F

SAND LOUVER HEAD DETAIL (JAMB SIM)


F1 1 : 10

COL

9.095 - INTERIOR 60 mm x 27 mm

MARK
METAL WALL LINING FRAMING FIXED 3.116 - REINFORCED
WITH WALL BRACKETS TO CMU OR CAST-IN-PLACE CONCRETE
CONCRETE AT 600 mm OC SPACING
E MAX
BEAM, SEE STRUCTURAL
8.021 - ALUMINUM SAND LOUVER DRAWINGS
5.237 - CONT GALV

PLOT SCALE: PLOT DATE:


7.016 - FLUID-APPLIED MEMBRANE

2/9/2022 4:51:35
STEEL CLIP ANGLE AND
ANCHORS AIR BARRIER
9.009 - 25 mm THICK THREE COAT

SOLICITATION NO.:

SA-480530-1$-SA599DT.dwg
35

PM
STUCCO SYSTEM

CONTRACT NO.:
ISSUE DATE:
9.107 - CASING BEAD FOR STUCCO
50

SYSTEM

1:1
7.188 - SEALANT 7.188 - SEALANT
4.002 - 200 mm
CONCRETE MASONRY 7.049 - 0.48 mm THICK STAINLESS 9.096 - 15 mm GYPSUM WALL BOARD 7.188 - SEALANT
UNIT STEEL SILL FLASHING WITH 50 8.020 - PREFINISHED METAL
mm TURNED UP EDGES . SET 7.176 - EXTRUDED PREFORMED LOUVER

FILE NO.:
FLASHING IN BED OF BUTYL CELLULAR POLYSTYRENE BOARD
SEALANT WALL INSULATION RSI 1.68 (R9.52)

SUBMITTED BY:
W. LOCKWOOD
J. BLANCHARD
MIN
9.009 - 25 mm THICK THREE COAT

DESIGN BY:

DRAWN BY:
STUCCO SYSTEM

A. HANKS
D

S. OKES
CKD BY:
8.126 - LOUVER SCREEN

ANSI D
SIZE:
152
INTERIOR 225 EXTERIOR

SAND LOUVER SILL DETAIL

TRANSATLANTIC MIDDLE EAST DISTRICT


D1

US ARMY CORPS OF ENGINEERS


LOUVER HEAD DETAIL (EW-2)

201 PRINCE FREDERICK DRIVE,


1 : 10
D5

WINCHESTER, VA 22602
1:5

EXTERIOR

COL
C 9.107 - CASING BEAD FOR
9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM 100 225
STUCCO SYSTEM
152
7.016 - FLUID-APPLIED MEMBRANE 7.188 - SEALANT
AIR BARRIER 8.020 - PREFINISHED METAL
LOUVER
4.002 - 200 mm CONCRETE
MASONRY UNIT 8.126 - LOUVER SCREEN

8.126 - LOUVER SCREEN

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


7.188 - SEALANT
8.020 - PREFINISHED METAL
LOUVER
152

THAAD STANDARD FACILITIES


225

VARIOUS LOCATIONS, KSA


9.096 - 15 mm GYPSUM WALL BOARD
7.043 - METAL FLASHING WITH

STANDARD DETAILS
LOUVER DETAILS
DRIP EDGE

SA-480530
9.095 - INTERIOR 60 mm x 27 mm
B METAL WALL LINING FRAMING FIXED
WITH WALL BRACKETS TO CMU OR
7.188 - SEALANT
COL
CONCRETE AT 600 mm OC SPACING 9.107 - CASING BEAD FOR
MAX STUCCO SYSTEM
100

7.176 - EXTRUDED PREFORMED


4.018 - BOND BEAM, SEE
STRUCTURAL DRAWINGS
GRAPHIC SCALES
CELLULAR POLYSTYRENE BOARD 4.002 - 200 mm CONCRETE
EW-2 7.188 - SEALANT WALL INSULATION RSI 1.68 (R9.52) MASONRY UNIT
7.176 - EXTRUDED PREFORMED MIN
CELLULAR POLYSTYRENE BOARD 9.096 - 15 mm GYPSUM WALL 7.016 - FLUID-APPLIED
WALL INSULATION RSI 1.68 (R9.52) BOARD EW-2
MEMBRANE AIR BARRIER
MIN
REFER TO MECHANICAL FOR
DUCTWORK CONNECTIONS TO 9.009 - 25 mm THICK THREE COAT
9.095 - INTERIOR 60 mm x 27 mm STUCCO SYSTEM 0 200 400 800
METAL WALL LINING FRAMING FIXED LOUVER
WITH WALL BRACKETS TO CMU OR
CONCRETE AT 600 mm OC SPACING INTERIOR SCALE: 1:10
2/9/2022 4:51:35 PM

MAX
INTERIOR EXTERIOR
A 0 100 200 400
SHEET ID
SCALE: 1:5 $
LOUVER JAMB DETAIL (EW-2) LOUVER SILL DETAIL (EW-2)
A2 1:5 A5 1:5 UNLESS OTHERWISE NOTED, LINEAR SA599
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

US Army Corps of
COL Engineers ®
Middle East District
G

EW-1

DATE
7.016 - FLUID-APPLIED
MEMBRANE AIR
BARRIER
7.267 - RIGID BOARD
WALL INSULATION,
RSI=2.29 (R-13) MINIMUM
4.033 - 100 mm
CONCRETE MASONRY
UNIT

4.012 - SCREW TYPE


VENEER ANCHORS.

DESCRIPTION
REFER TO
F SPECIFICATION
9.011 - 20 mm THICK SECTION 04 20 00 FOR
GYPSUM PLASTER SPACING
9.009 - 25 mm THICK
5.234 - CONC THREE COAT STUCCO
SCREW/ANCHOR INTO SYSTEM
GROUTED CMU BLOCK
@ 300 mm ON CENTER 7.039 - STRIP
CAPABLE OF TRANSITION MEMBRANE
SUPPORTING ONTO FLASHING TO
ALLOWABLE SHEAR MAINTAIN AIR BARRIER
LOAD OF 2.65kN CONTINUITY
4.024 - MASONRY 4.013 - CAVITY NET /
LINTEL, SEE MORTAR CONTROL
STRUCTURAL DEVICE
DRAWINGS
7.042 - THRU-WALL

MARK
FLASHING WITH WEEP
VENTILATORS AT 600
E mm OC, TYP

7.084 - STAINLESS

PLOT SCALE: PLOT DATE:


2/9/2022 4:52:13
STEEL DRIP EDGE SET
IN BED OF SEALANT

SOLICITATION NO.:
REFER TO MECHANICAL 5.219 - L203 mm x 152

SA-480530-1$-SA600DT.dwg
PM
CONTRACT NO.:
FOR DUCTWORK mm x 12.7 mm GALV

ISSUE DATE:
CONNECTIONS TO LOUVER STEEL LINTEL ANGLE -
PAINTED, BEAR LINTEL

1:1
MIN OF 200 mm ON
EACH SIDE OF VENEER
200
7.060 - BACKER ROD
AND JOINT SEALANT
8.021 - ALUMINUM SAND

FILE NO.:
LOUVER

M. MacEACHERN
SUBMITTED BY:
W. RODRIGUEZ
C. SCORZELLI
SAND LOUVER HEAD DETAIL - EW-1

DESIGN BY:

DRAWN BY:

A. HANKS
D D5

CKD BY:

ANSI D
1:5

SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
COL

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
4.033 - 100 mm
CONCRETE MASONRY EW-1 REFER TO MECHANICAL 200
UNIT FOR DUCTWORK
9.009 - 25 mm THICK
7.267 - RIGID BOARD THREE COAT STUCCO CONNECTIONS TO LOUVER
8.021 - ALUMINUM SAND
C WALL INSULATION, SYSTEM
LOUVER
RSI=2.29 (R-13) MINIMUM
7.016 - FLUID-APPLIED 7.060 - BACKER ROD
MEMBRANE AIR AND JOINT SEALANT
BARRIER 7.060 - BACKER ROD
AND JOINT SEALANT 8.132 - STAINLESS
STEEL TRIM CLOSURE
SLOPE BY SAND LOUVER
SUPPLIER

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


200

70

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA

STANDARD DETAILS
EW-1
COL

LOUVER DETAILS
9.009 - 25 mm THICK THREE COAT

SA-480530
STUCCO SYSTEM
B 4.033 - 100 mm
CONCRETE MASONRY
UNIT
7.016 - FLUID-APPLIED GRAPHIC SCALES
MEMBRANE AIR
9.011 - 20 mm THICK
BARRIER
GYPSUM PLASTER
7.267 - RIGID BOARD
WALL INSULATION,
RSI=2.29 (R-13) MINIMUM
8.021 - ALUMINUM SAND
LOUVER 4.012 - SCREW TYPE VENEER
9.011 - 20 mm THICK ANCHORS. REFER TO
GYPSUM PLASTER SPECIFICATION SECTION 04 20
REFER TO MECHANICAL 00 FOR SPACING
FOR DUCTWORK
2/9/2022 4:52:13 PM

CONNECTIONS TO LOUVER
A 0 100 200 400
SHEET ID
SAND LOUVER JAMB DETAIL - EW-1 SAND LOUVER SILL DETAIL - EW-1 SCALE: 1:5 $
A2 1:5 A5 1:5
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA600
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


25 VARIES 25 275
1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
9.009 - 25 mm THICK THREE COAT US Army Corps of
25 VARIES 25 2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND
STUCCO SYSTEM Engineers ®
SYMBOLS.
Middle East District
G 4.002 - 200 mm CONCRETE MASONRY
9.009 - 25 mm THICK THREE COAT UNIT
9.009 - 25 mm THICK THREE COAT
STUCCO SYSTEM STUCCO SYSTEM

DATE
EW-4
3.007 - REINFORCED
CAST-IN-PLACE CONCRETE EW-3
WALL, SEE STRUCTURAL
DRAWINGS 4.002 - 200 mm CONCRETE 7.016 - FLUID-APPLIED MEMBRANE
EW-4A MASONRY UNIT AIR BARRIER
INTERIOR EXTERIOR

4.002 - 200 mm CONCRETE MASONRY


INTERIOR EXTERIOR 9.009 - 25 mm THICK THREE COAT
UNIT
STUCCO SYSTEM
9.009 - 25 mm THICK THREE COAT INTERIOR EXTERIOR
STUCCO SYSTEM 9.091 - 2 mm PLASTER FINISH OVER
PLASTERBOARD

DESCRIPTION
F
* USE 200 mm CONCRETE MASONRY UNIT
UNLESS OTHERWISE NOTED ON PLAN

EXTERIOR WALL TYPE - EW-4A EXTERIOR WALL TYPE - EW-4 EXTERIOR WALL TYPE - EW-3
1 : 20 1 : 20 1 : 20

9.009 - 25 mm THICK THREE COAT 275

MARK
STUCCO SYSTEM 7.016 - FLUID-APPLIED
MEMBRANE AIR BARRIER
VARIES 7.176 - EXTRUDED PREFORMED
E CELLULAR POLYSTYRENE 9.009 - 25 mm THICK THREE COAT
BOARD WALL INSULATION RSI STUCCO SYSTEM
EW-2.1
EW-2A.1 1.68 (R9.52) MIN
4.002 - 200 mm CONCRETE

PLOT SCALE: PLOT DATE:


2/9/2022 4:52:21
7.016 - FLUID-APPLIED MASONRY UNIT
3.007 - REINFORCED MEMBRANE AIR BARRIER
7.176 - EXTRUDED PREFORMED

SOLICITATION NO.:

SA-480530-1$-SA601DT.dwg
CAST-IN-PLACE CONCRETE 3.007 - REINFORCED

PM
CELLULAR POLYSTYRENE

CONTRACT NO.:
WALL, SEE STRUCTURAL CAST-IN-PLACE CONCRETE
BOARD WALL INSULATION RSI

ISSUE DATE:
DRAWINGS WALL, SEE STRUCTURAL
INTERIOR EXTERIOR DRAWINGS 1.68 (R9.52) MIN
9.009 - 25 mm THICK THREE COAT

1:1
9.009 - 25 mm THICK THREE COAT 325
VARIES STUCCO SYSTEM
EW-6 100 @ EW-2A STUCCO SYSTEM
25
26.023 - CONDUIT WITH LIGHTNING
26.023 - CONDUIT WITH
PROTECTION CABLE. NOTCH WALL
LIGHTNING PROTECTION CABLE.
INSULATION AS REQUIRED FOR
NOTCH WALL INSULATION AS
CONDUIT INSTALLATION. SEE

FILE NO.:
REQUIRED FOR CONDUIT
ELECTRICAL DRAWINGS
INSTALLATION. SEE ELECTRICAL

SUBMITTED BY:
EXTERIOR WALL TYPE - EW-6

J. BLANCHARD
DRAWINGS 4.002 - 200 mm CONCRETE MASONRY

J. HOLLAND
DESIGN BY:

DRAWN BY:
3.007 - REINFORCED UNIT

A. HANKS
D INTERIOR EXTERIOR

S. OKES
CKD BY:
1 : 20 CAST-IN-PLACE CONCRETE 7.176 - EXTRUDED PREFORMED

ANSI D
INTERIOR EXTERIOR

SIZE:
WALL, SEE STRUCTURAL CELLULAR POLYSTYRENE
DRAWINGS BOARD WALL INSULATION RSI
7.176 - EXTRUDED PREFORMED 1.68 (R9.52) MIN

TRANSATLANTIC MIDDLE EAST DISTRICT


CELLULAR POLYSTYRENE 7.016 - FLUID-APPLIED MEMBRANE
BOARD WALL INSULATION RSI AIR BARRIER

US ARMY CORPS OF ENGINEERS


VARIES 25 EW-2A

201 PRINCE FREDERICK DRIVE,


1.68 (R9.52) MIN 9.095 - INTERIOR 60 mm x 27 mm
EW-2 METAL WALL LINING FRAMING FIXED
7.016 - FLUID-APPLIED

WINCHESTER, VA 22602
MEMBRANE AIR BARRIER WITH WALL BRACKETS TO CMU OR
9.009 - 25 mm THICK THREE COAT 9.095 - INTERIOR 60 mm x 27 mm CONCRETE AT 600 mm OC SPACING
STUCCO SYSTEM METAL WALL LINING FRAMING MAX
INTERIOR EXTERIOR FIXED WITH WALL BRACKETS TO
CMU OR CONCRETE AT 600 mm 9.096 - 15 mm GYPSUM WALL BOARD
3.007 - REINFORCED 125 @ EW-2A.2 OC SPACING MAX
CAST-IN-PLACE CONCRETE 9.096 - 15 mm GYPSUM WALL BOARD
WALL, SEE STRUCTURAL
EW-5A
DRAWINGS EXTERIOR WALL TYPE - EW-2A.1 IS SIMILAR TO EW-2A. EXTERIOR WALL TYPE - EW-2.1 IS SIMILAR TO EW-2.
OMIT MATERIALS 9.095 AND 9.096 OMIT MATERIALS 9.095 AND 9.096
C

EXTERIOR WALL TYPE - EW-5A EXTERIOR WALL TYPE - EW-2A, EW-2A.1 & EXTERIOR WALL TYPE - EW-2 & EW-2.1
1 : 20 EW-2A.2 1 : 20
1 : 20

VARIES 25

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


VARIES 225 425
9.115 - METAL LATH FOR STUCCO

THAAD STANDARD FACILITIES


SYSTEM

VARIOUS LOCATIONS, KSA


9.009 - 25 mm THICK THREE COAT

EXTERIOR WALL TYPES


9.009 - 25 mm THICK THREE COAT

STANDARD DETAILS
STUCCO SYSTEM
STUCCO SYSTEM
4.033 - 100 mm CONCRETE 9.115 - METAL LATH FOR STUCCO

SA-480530
MASONRY UNIT SYSTEM
9.009 - 25 mm THICK THREE COAT
B STUCCO SYSTEM 7.094 - 50 mm AIRSPACE 4.033 - 100 mm CONCRETE
MASONRY UNIT
EW-5 7.267 - RIGID BOARD WALL 7.094 - 50 mm AIRSPACE
INSULATION, RSI=2.29 (R-13)
MINIMUM
7.267 - RIGID BOARD WALL
INSULATION, RSI=2.29 (R-13)
GRAPHIC SCALES
4.002 - 200 mm CONCRETE 7.016 - FLUID-APPLIED
MASONRY UNIT MINIMUM
MEMBRANE AIR BARRIER
7.016 - FLUID-APPLIED
MEMBRANE AIR BARRIER
3.007 - REINFORCED
INTERIOR EXTERIOR
CAST-IN-PLACE CONCRETE 4.002 - 200 mm CONCRETE
EW-1A WALL, SEE STRUCTURAL MASONRY UNIT
EW-1
DRAWINGS
4.012 - SCREW TYPE
4.012 - SCREW TYPE VENEER ANCHORS.
INTERIOR EXTERIOR VENEER ANCHORS. INTERIOR EXTERIOR REFER TO
REFER TO SPECIFICATION
2/9/2022 4:52:21 PM

SPECIFICATION SECTION 04 20 00 FOR


SECTION 04 20 00 FOR
A * USE 200 mm CONCRETE MASONRY UNIT
SPACING
SPACING 0 400 800 1.6M
SHEET ID
UNLESS OTHERWISE NOTED ON PLAN

SCALE: 1:20 $
EXTERIOR WALL TYPE - EW-5 EXTERIOR WALL TYPE - EW-1A EXTERIOR WALL TYPE - EW-1 UNLESS OTHERWISE NOTED, LINEAR SA601
1 : 20 1 : 20 1 : 20 DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10
PARTITION TOP PARTITION TOP
ANCHOR. SEE STRL ANCHOR. SEE STRL GENERAL SHEET NOTES
EXTEND PLASTER TO 1. REFER TO SHEET SG003 FOR ABBREVIATIONS.

SEE STRL
UNDERSIDE OF UNDERSIDE OF

SEE STRL
UNDERSIDE OF 2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL
STRUCTURE STRUCTURE US Army Corps of
STRUCTURE WHERE NOTES, LEGENDS AND SYMBOLS. Engineers ®
NO CEILING EXIST PACK JOINT WITH PACK JOINT WITH 3. REFER TO LIFE SAFETY PLANS FOR REQUIRED FIRE RATED

FULL HEIGHT NON-RATED MASONRY CORE PARTITIONS


MINERAL WOOL AND MINERAL WOOL AND PARTITION LOCATION. Middle East District

150 MIN
G SEAL BOTH SIDES SEAL BOTH SIDES 4. SMOKE AND/OR FIRE RATED PARTITIONS SHALL BE
GROUT TOP COURSE GROUT TOP COURSE CONSTRUCTED PER THE REQUIREMENTS OF THE U.L. TEST
SOLID SOLID ASSEMBLY IDENTIFIED. PARTITIONS SHALL EXTEND FROM
STRUCTURAL SLAB TO STRUCTURAL SLAB. PROVIDE

DATE
MIN

MIN
150

150
BOND BEAM, SEE STRL BOND BEAM, SEE STRL CONTINUOUS FIRE STOPPING/SEALANT BOTH SIDES, TOP
CEILING AS AND BOTTOM, AND AT ALL PENETRATIONS.
SCHED - SEE 5. FIRE BARRIERS AND FIRE PARTITIONS SHALL BE
FINISH SCHEDULE DESIGNATED ABOVE THE CEILING AND ON CEILING ACCESS
CEILING AS SCHED - CEILING AS SCHED - DOORS WHICH PROVIDE ACCESS TO SUCH FIRE RATED
SEE FINISH SEE FINISH
Top SCHEDULE SCHEDULE
ASSEMBLIES BY SIGNAGE HAVING LETTERS NO SMALLER
THAN 25mm IN HEIGHT. SUCH SIGNAGE SHALL INDICATE
THE FIRE RESISTANCE OF THE ASSEMBLY AND THE TYPE
OF ASSEMBLY, AND BE PROVIDED AT HORIZONTAL
DIRECT-APPLIED FINISH

INTERVALS NO MORE THAN 2400mm.


PAINT CMU 6. FULL HEIGHT PARTITIONS SHALL PROVIDE FOR VERTICAL
WHERE EXPOSED MOVEMENT AT THE STRUCTURAL JOINT AT THE SLAB
REINF CMU, SIZE ABOVE AND ALLOW FOR A MAXIMUM STRUCTURAL
9.011 - 20 mm THICK AS SCHEDULED DEFLECTION OF 25mm. SEAL JOINTS TOP AND BOTTOM.
REINF CMU, SIZE 7. SEE STRUCTURAL DRAWINGS FOR TYPICAL TOP OF WALL

DESCRIPTION
GYPSUM PLASTER
AS SCHEDULED
F AND BOTTOM OF WALL DETAILS FOR MASONRY AND CONC.
8. PROVIDE SOLID FRT WOOD BLOCKING AT METAL STUD OR
CONTROL JOINT CONTROL JOINT FURRED PARTITIONS AS REQUIRED TO ACCOMMODATE
WHERE OCCURS WHERE OCCURS INSTALLATION OF CASEWORK, LOCKERS, GRAB BARS,
CONTROL JOINT HANDRAILS, AV EQUIPMENT, SIGNAGE AND OTHER WALL
SEE STRL FOR SEE STRL FOR MOUNTED SCHEDULED EQUIPMENT AND ACCESSORIES.
WHERE OCCURS
HORIZONTAL AND HORIZONTAL AND PROVIDE FRT PLYWOOD WHERE PLYWOOD BACKER
VERTICAL VERTICAL PANELS ARE INDICATED OR SPECIFIED.
REINFORCEMENT REINFORCEMENT 9. GYPSUM BOARD PARTITIONS SPANNING ABOVE
DOOR/WINDOW OPENINGS 1800mm WIDE OR MORE SHALL
9.011 - 20 mm THICK 9.011 - 20 mm THICK BE DIAGONALLY BRACED AT 1800mm OC.
GYPSUM PLASTER GYPSUM PLASTER 10. METAL STUD SPACING SHALL BE 400mm OC UNO.
11. PROVIDE GWB CONTROL JOINTS AND CONSTRUCT IN
ACCORDANCE WITH GYPSUM ASSOCIATION GA 216-2016
Plan AND AS INDICATED ON THE DRAWINGS. COORDINATE
GWB AND PLASTER CONTROL JOINTS WITH MASONRY
CONTROL JOINTS.

MARK
SEE STRL FOR DOWEL SEE STRL FOR DOWEL 12. WHERE GWB OCCURS IN RESTROOMS AND/OR OTHER
CONNECTION TO SLAB CONNECTION TO SLAB WET AREAS OR WHERE SCHEDULED TO RECEIVE EPOXY
E SEE CORE WIDTH
PAINT, PROVIDE MOISTURE RESISTANT GWB.
13. INTERIOR PARTITIONS ARE M8F0.1P2 UNO.
SEE CORE WIDTH
14. INTERIOR PARTITIONS ARE REINFORCED, SEE

PLOT SCALE: PLOT DATE:


STRUCTURAL FOR REINFORCEMENT.

2/9/2022 4:52:25
FLOOR AND BASE AS FLOOR AND BASE AS FLOOR AND BASE AS
SCHED - SEE FINISH 15. PROVIDE CEMENT PLASTER IN LIEU OF GYPSUM PLASTER
SCHED - SEE FINISH SCHED - SEE FINISH AT PARTITIONS SCHEDULED TO RECEIVE A TILE FINISH.
SCHEDULE

SOLICITATION NO.:
SCHEDULE SCHEDULE

SA-480530-1$-SA602DT.dwg
PM
CONTRACT NO.:
LEGEND - PARTITION TYPE

ISSUE DATE:
Base

1:1
CSI DIVISION DESIGNATOR
CORE WIDTH
DIRECT-APPLIED
L1S0.P PLASTER FINISH M#F0.1P FULL HEIGHT MASONRY, NON-
RATED, WITH PLASTER FINISH
M#F0.1P2 FULL HEIGHT MASONRY,
NON-RATED, WITH PLASTER CORE HEIGHT
ONE-SIDE ONLY BOTH SIDES

FILE NO.:
DIRECT-APPLIED RATING
L1S0.C CEMENT BOARD

SUBMITTED BY:
FURRING SIZE

J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:
FINISH CONSTRUCTION /

A. HANKS
D PARTITION TOP PARTITION TOP

S. OKES
CKD BY:
SPECIALTY

ANSI D
ANCHOR. SEE STRL ANCHOR. SEE STRL

SIZE:
M8F0.2F
UNDERSIDE OF
* SEE STRL

* SEE STRL

UNDERSIDE OF UNDERSIDE OF

* SEE STRL
UNDERSIDE OF

TRANSATLANTIC MIDDLE EAST DISTRICT


STRUCTURE CORE CSI DIVISION DESIGNATOR:
STRUCTURE STRUCTURE STRUCTURE

US ARMY CORPS OF ENGINEERS


FULL HEIGHT NON-RATED CONCRETE CORE PARTITIONS

201 PRINCE FREDERICK DRIVE,


L#F0.F PACK JOINT WITH PACK JOINT WITH CODE CSI DIVISION
CONTINUOUS MINERAL WOOL AND MINERAL WOOL AND DOVETAIL SLOT
150 MIN

G 02-EXISTING (GENERIC / UNKNOWN)

WINCHESTER, VA 22602
MIN
MIN

TO ROOF DECK SEAL BOTH SIDES SEAL BOTH SIDES & PTN TOP ROD
150

150
C 03-CONCRETE
ANCHOR M 04-MASONRY
D 05-STRUCTURAL/COLD FORM
MIN
150

*OMIT GAP AT *OMIT GAP AT W 06-WOOD


CEILING AS SHEAR WALLS SHEAR WALLS L 09-INTERIOR LIGHT GAUGE METAL FRAMING
SCHED - SEE (LGMF)
*OMIT GAP AT P 10-SPECIALTY
FINISH SHEAR WALLS CEILING AS SCHED - CEILING AS SCHED -
SCHEDULE SEE FINISH SEE FINISH
METAL STUD FURRED PARTITION

CEILING AS SCHED - CORE WIDTH / FURRING SIZE:


Top SEE FINISH
SCHEDULE SCHEDULE

C SCHEDULE CODE SIZE


0 --
1 <=25 (I.E. 20 MM DIRECT APPLIED PLASTER)
22 (METAL HAT CHANNEL)
2 60 (METAL STUD)
3 90 (METAL STUD)
REINF CONC, SIZE
15mm GYPSUM REINF CONC, SIZE 15mm GYPSUM 4 100 NOMINAL (100 ACTUAL (CMU))
AS SCHEDULED
WALL BOARD, AS SCHEDULED WALL BOARD, 6 150 NOMINAL (150 ACTUAL (CMU))
PAINTED PAINTED 8 200 NOMINAL (200 ACTUAL (CMU))
10 250 NOMINAL (250 ACTUAL (CMU))
12 300 NOMINAL (300 ACTUAL (CMU))

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


REINF CONC, SIZE
9.011 - 20 mm THICK AS SCHEDULED CORE HEIGHT:
9.011 - 20 mm THICK GYPSUM PLASTER

THAAD STANDARD FACILITIES


GYPSUM PLASTER C PARTITION TO UNDERSIDE OF CEILING

VARIOUS LOCATIONS, KSA


MET. STUDS AT
400mm O.C. 60mm MET. (CEILING IS CONTINUOUS ABOVE)

STANDARD DETAILS
F FULL HEIGHT PARTITION

PARTITION TYPES
STUDS, UNO
(PROVIDE FURRING SEE STLR FOR SEE STLR FOR P PARTIAL HEIGHT PARTITION

SA-480530
HAT CHANNELS REINFORCEMENT REINFORCEMENT (HEIGHT VARIES, SEE KEYNOTE)
B WHERE SHCEDULED) SEE FURRING SIZE CODE
S
CEILING
STOP PARTITION 150MM ABOVE ADJACENT

RATING:
Plan
0 NON-RATED
1 1-HOUR RATED
SEE STLR FOR DOWEL SEE STLR FOR DOWEL
2 2-HOUR RATED
CONNECTION TO SLAB CONNECTION TO SLAB
3 3-HOUR RATED
SEE FURRING SIZE CODE SEE CORE WIDTH
4 4-HOUR RATED
SEE CORE WIDTH SEE CORE WIDTH
TOP & BOTTOM H 1/2 HOUR RATED
TRACK, TYP S SMOKE RATED
FLOOR AND BASE AS FLOOR AND BASE AS FLOOR AND BASE AS a STC 35
SCHED - SEE FINISH SCHED - SEE FINISH SCHED - SEE FINISH b STC 40
FLOOR AND BASE AS SCHEDULE SCHEDULE SCHEDULE c STC 45
SCHED - SEE FINISH
SCHEDULE d STC 50
e STC 55
2/9/2022 4:52:25 PM

A Base FINISH CONSTRUCTION / SPECIALTY: SHEET ID


C CEMENT BOARD
FULL HEIGHT CIP CONCRETE, FULL HEIGHT CIP FULL HEIGHT CIP CONCRETE, NON- F METAL FURRING / GWB (1-SIDE) $
L#S0.F METAL FURRING C#F0.1P NON-RATED, WITH PLASTER C#F0.1P2 CONCRETE, NON-RATED, C#F0.2F RATED, WITH METAL FURRING AND F2 METAL FURRING / GWB (2-SIDES)
AND GWB
FULL HEIGHT METAL
FINISH ONE-SIDE ONLY
FULL HEIGHT CIP CONCRETE,
WITH PLASTER BOTH SIDES GWB ONE-SIDE ONLY P
P2
PLASTER FINISH (1-SIDE)
PLASTER FINISH (2-SIDES)
SA602
L#F0.F FURRING AND GWB C#F0 NON-RATED, WITHOUT PLASTER
1 2 3 4 5 6 7 8 9 10
PARTITION TOP PARTITION TOP
ANCHOR. SEE STRL ANCHOR. SEE STRL GENERAL SHEET NOTES
1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
UNDERSIDE OF UNDERSIDE OF 2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL

SEE STRL
SEE STRL

SEE STRL
UNDERSIDE OF STRUCTURE STRUCTURE NOTES, LEGENDS AND SYMBOLS. US Army Corps of
STRUCTURE 3. REFER TO LIFE SAFETY PLANS FOR REQUIRED FIRE RATED Engineers ®
FIRESTOP SYSTEM AT FIRESTOP SYSTEM AT
TOP OF WALL TOP OF WALL PARTITION LOCATION. Middle East District
G ACOUSTICAL 4. SMOKE AND/OR FIRE RATED PARTITIONS SHALL BE
CONSTRUCTED PER THE REQUIREMENTS OF THE U.L. TEST
FULL HEIGHT RATED MASONRY CORE PARTITIONS

FIRESTOPPING GROUT TOP COURSE GROUT TOP COURSE


SEALANT, TOP & ASSEMBLY IDENTIFIED. PARTITIONS SHALL EXTEND FROM
SOLID SOLID STRUCTURAL SLAB TO STRUCTURAL SLAB. PROVIDE
BOTTOM

DATE
CONTINUOUS FIRE STOPPING/SEALANT BOTH SIDES, TOP
BOND BEAM, SEE STRL BOND BEAM, SEE STRL AND BOTTOM, AND AT ALL PENETRATIONS.
5. FIRE BARRIERS AND FIRE PARTITIONS SHALL BE
DESIGNATED ABOVE THE CEILING AND ON CEILING ACCESS
CEILING AS SCHED - CEILING AS SCHED - CEILING AS SCHED - DOORS WHICH PROVIDE ACCESS TO SUCH FIRE RATED
SEE FINISH SEE FINISH SEE FINISH ASSEMBLIES BY SIGNAGE HAVING LETTERS NO SMALLER
Top SCHEDULE SCHEDULE SCHEDULE THAN 25mm IN HEIGHT. SUCH SIGNAGE SHALL INDICATE
THE FIRE RESISTANCE OF THE ASSEMBLY AND THE TYPE
OF ASSEMBLY, AND BE PROVIDED AT HORIZONTAL
D-2 OR C-3 CMU AS INTERVALS NO MORE THAN 2400mm.
D-2 OR C-3 CMU AS
REQUIRED FOR UL 6. FULL HEIGHT PARTITIONS SHALL PROVIDE FOR VERTICAL
REQUIRED FOR UL
ASSEMBLY, SIZE MOVEMENT AT THE STRUCTURAL JOINT AT THE SLAB
ASSEMBLY, SIZE
AS SCHEDULED ABOVE AND ALLOW FOR A MAXIMUM STRUCTURAL
AS SCHEDULED
D-2 OR C-3 CMU AS DEFLECTION OF 25mm. SEAL JOINTS TOP AND BOTTOM.
REQUIRED FOR UL 9.011 - 20 mm THICK 7. SEE STRUCTURAL DRAWINGS FOR TYPICAL TOP OF WALL

DESCRIPTION
ASSEMBLY, SIZE GYPSUM PLASTER AND BOTTOM OF WALL DETAILS FOR MASONRY AND CONC.
F AS SCHEDULED,
9.011 - 20 mm THICK
GYPSUM PLASTER 8. PROVIDE SOLID FRT WOOD BLOCKING AT METAL STUD OR
PAINTED CONTROL JOINT FURRED PARTITIONS AS REQUIRED TO ACCOMMODATE
WHERE OCCURS CONTROL JOINT INSTALLATION OF CASEWORK, LOCKERS, GRAB BARS,
WHERE OCCURS HANDRAILS, AV EQUIPMENT, SIGNAGE AND OTHER WALL
PAINT CMU
MOUNTED SCHEDULED EQUIPMENT AND ACCESSORIES.
WHERE EXPOSED
PROVIDE FRT PLYWOOD WHERE PLYWOOD BACKER
LOOSE MASONRY
LOOSE MASONRY LOOSE MASONRY PANELS ARE INDICATED OR SPECIFIED.
FILL AND/OR
FILL AND/OR FILL AND/OR 9. GYPSUM BOARD PARTITIONS SPANNING ABOVE
GROUT SOLID AS
GROUT SOLID AS GROUT SOLID AS DOOR/WINDOW OPENINGS 1800mm WIDE OR MORE SHALL
RECOMMENDED BY
RECOMMENDED BY RECOMMENDED BY BE DIAGONALLY BRACED AT 1800mm OC.
TESTED ASSEMBLY
TESTED ASSEMBLY TESTED ASSEMBLY 10. METAL STUD SPACING SHALL BE 400mm OC UNO.
11. PROVIDE GWB CONTROL JOINTS AND CONSTRUCT IN
SEE STRL FOR SEE STRL FOR ACCORDANCE WITH GYPSUM ASSOCIATION GA 216-2016
HORIZONTAL AND HORIZONTAL AND AND AS INDICATED ON THE DRAWINGS. COORDINATE
Plan VERTICAL
REINFORCEMENT
VERTICAL
REINFORCEMENT
GWB AND PLASTER CONTROL JOINTS WITH MASONRY
CONTROL JOINTS.
12. WHERE GWB OCCURS IN RESTROOMS AND/OR OTHER

MARK
SEE STRL FOR DOWEL SEE STRL FOR DOWEL WET AREAS OR WHERE SCHEDULED TO RECEIVE EPOXY
CONNECTION TO SLAB CONNECTION TO SLAB PAINT, PROVIDE MOISTURE RESISTANT GWB.
E SEE CORE WIDTH 13. INTERIOR PARTITIONS ARE M8F0.1P2 UNO.
SEE CORE WIDTH SEE CORE WIDTH 14. INTERIOR PARTITIONS ARE REINFORCED, SEE
STRUCTURAL FOR REINFORCEMENT.

PLOT SCALE: PLOT DATE:


2/9/2022 4:52:29
FLOOR AND BASE AS FLOOR AND BASE AS FLOOR AND BASE AS 15. PROVIDE CEMENT PLASTER IN LIEU OF GYPSUM PLASTER
SCHED - SEE FINISH SCHED - SEE FINISH SCHED - SEE FINISH AT PARTITIONS SCHEDULED TO RECEIVE A TILE FINISH.

SOLICITATION NO.:
SCHEDULE SCHEDULE SCHEDULE

SA-480530-1$-SA603DT.dwg
PM
CONTRACT NO.:
LEGEND - PARTITION TYPE

ISSUE DATE:
Base

1:1
CSI DIVISION DESIGNATOR
CORE WIDTH

M#F# FULL HEIGHT MASONRY, RATED M#F#.1P FULL HEIGHT MASONRY, RATED,
WITH PLASTER FINISH ONE-SIDE
M#F#.1P2 FULL HEIGHT MASONRY,
RATED, WITH PLASTER
CORE HEIGHT

ONLY BOTH SIDES RATING

FILE NO.:
M#F0 FULL HEIGHT MASONRY,
FURRING SIZE

SUBMITTED BY:
NON-RATED

J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:
PARTITION TOP PARTITION TOP FINISH CONSTRUCTION /

A. HANKS
D SPECIALTY

S. OKES
CKD BY:
TOP OF WALL CONSTRUCTION: ANCHOR. SEE STRL ANCHOR. SEE STRL

ANSI D
SIZE:
M8F0.2F
1-HR FIRE/SMOKE RATED PARTITION:
* SEE STRL

* SEE STRL

CONSTRUCT HEAD JOINT IN ACCORDANCE UNDERSIDE OF UNDERSIDE OF


CORE CSI DIVISION DESIGNATOR:

TRANSATLANTIC MIDDLE EAST DISTRICT


WITH UL SYSTEM NO. HW-D-0244. STRUCTURE STRUCTURE

US ARMY CORPS OF ENGINEERS


CODE CSI DIVISION

201 PRINCE FREDERICK DRIVE,


2-HR FIRE/SMOKE RATED PARTITION:
CONSTRUCT HEAD JOINT IN ACCORDANCE FIRESTOP SYSTEM AT FIRESTOP SYSTEM AT G 02-EXISTING (GENERIC / UNKNOWN)
TOP OF WALL TOP OF WALL

WINCHESTER, VA 22602
C 03-CONCRETE
FULL HEIGHT RATED CONCRETE CORE PARTITIONS

WITH UL SYSTEM NO. HW-D-0244.


M 04-MASONRY
3-HR FIRE/SMOKE RATED PARTITION: D 05-STRUCTURAL/COLD FORM
*OMIT GAP AT *OMIT GAP AT W 06-WOOD
CONSTRUCT HEAD JOINT IN ACCORDANCE
SHEAR WALLS SHEAR WALLS L 09-INTERIOR LIGHT GAUGE METAL FRAMING
WITH UL SYSTEM NO. HW-D-0041.
(LGMF)
4-HR FIRE/SMOKE RATED PARTITION: P 10-SPECIALTY
CONSTRUCT HEAD JOINT IN ACCORDANCE CEILING AS SCHED - CEILING AS SCHED -
WITH UL SYSTEM NO. HW-D-0145. CORE WIDTH / FURRING SIZE:
SEE FINISH SEE FINISH
Top SCHEDULE SCHEDULE
CODE SIZE
C 0 --
1 <=25 (I.E. 20 MM DIRECT APPLIED PLASTER)
22 (METAL HAT CHANNEL)
2 60 (METAL STUD)
WALL ASSEMBLY CONSTRUCTION: 3 90 (METAL STUD)
REINF CONC, SIZE 4 100 NOMINAL (100 ACTUAL (CMU))
REINF CONC, SIZE
1-HR FIRE/SMOKE RATED PARTITION: AS SCHEDULED 6 150 NOMINAL (150 ACTUAL (CMU))
AS SCHEDULED
CONSTRUCT IN ACCORDANCE WITH 8 200 NOMINAL (200 ACTUAL (CMU))
UL DESIGN NO. U905. 10 250 NOMINAL (250 ACTUAL (CMU))
12 300 NOMINAL (300 ACTUAL (CMU))

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


2-HR FIRE/SMOKE RATED PARTITION:
CONSTRUCT IN ACCORDAINCE WITH CORE HEIGHT:
UL SESIGN NO. U905. CONTROL JOINT CONTROL JOINT
C PARTITION TO UNDERSIDE OF CEILING

THAAD STANDARD FACILITIES


WHERE OCCURS WHERE OCCURS

VARIOUS LOCATIONS, KSA


3-HR FIRE/SMOKE RATED PARTITION: (CEILING IS CONTINUOUS ABOVE)
CONSTRUCT IN ACCORDANCE WITH F FULL HEIGHT PARTITION

STANDARD DETAILS
SEE STLR FOR SEE STLR FOR

PARTITION TYPES
UL DESIGN NO. U904 OR U914. P PARTIAL HEIGHT PARTITION
REINFORCEMENT REINFORCEMENT
(HEIGHT VARIES, SEE KEYNOTE)

SA-480530
4-HR FIRE/SMOKE RATED PARTITION: S STOP PARTITION 150MM ABOVE ADJACENT
B CONSTRUCT IN ACCORDANCE WITH
9.011 - 20 mm THICK
GYPSUM PLASTER 9.011 - 20 mm THICK CEILING
UL DESIGN NO. U907. GYPSUM PLASTER
RATING:
Plan 0 NON-RATED
1 1-HOUR RATED
LOWEST SEE STLR FOR DOWEL SEE STLR FOR DOWEL 2 2-HOUR RATED
PRIORITY HIGHEST CONNECTION TO SLAB CONNECTION TO SLAB 3 3-HOUR RATED
PRIORITY
4 4-HOUR RATED
SEE CORE WIDTH SEE CORE WIDTH H 1/2 HOUR RATED
S SMOKE RATED
WALL PRIORITY LEGEND: FLOOR AND BASE AS FLOOR AND BASE AS a STC 35
4 HR RATED WALL PRIORITY 1 HIGHEST SCHED - SEE FINISH SCHED - SEE FINISH b STC 40
3 HR RATED FIRE/SMOKE BARRIER PRIORITY 2 SCHEDULE SCHEDULE c STC 45
2 HR RATED FIRE/SMOKE BARRIER PRIORITY 3 d STC 50
2 HR RATED FIRE BARRIER PRIORITY 4
1 HR RATED SMOKE BARRIER PRIORITY 5
e STC 55
2/9/2022 4:52:29 PM

1 HR RATED FIRE BARRIER PRIORITY 6


A Base SMOKE PARTITION
NON-RATED ACOUSTICAL PARTITION
PRIORITY 7
PRIORITY 8
FINISH CONSTRUCTION / SPECIALTY:
SHEET ID
NON-RATED PARTITION PRIORITY 9 LOWEST
C CEMENT BOARD
NOTE: FULL HEIGHT CIP CONCRETE, FULL HEIGHT CIP F METAL FURRING / GWB (1-SIDE) $
1. SCHEDULE CONSTRUCTION OF PARTITIONS IN ORDER C#F#.1P RATED, WITH PLASTER FINISH C#F#.1P2 CONCRETE, RATED, WITH F2 METAL FURRING / GWB (2-SIDES)
TO MAINTAIN CONTINUITY OF RATING PRIORITY.
ONE-SIDE ONLY
FULL HEIGHT CIP CONCRETE,
PLASTER BOTH SIDES P
P2
PLASTER FINISH (1-SIDE)
PLASTER FINISH (2-SIDES) SA603
C#F# RATED, WITHOUT PLASTER
1 2 3 4 5 6 7 8 9 10
SEE STRL FOR
LATERAL BRACING
SEE STRL FOR
LATERAL BRACING
SEE STRL FOR
LATERAL BRACING GENERAL SHEET NOTES
T WITH T WITH T WITH 1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
NON-FULL HEIGHT NON-RATED MASONRY CORE PARTITIONS VERTICAL SLOT VERTICAL SLOT VERTICAL SLOT 2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL
NOTES, LEGENDS AND SYMBOLS. US Army Corps of
AND BOLT W/ AND BOLT W/ AND BOLT W/ Engineers ®
DOUBLE NUT DOUBLE NUT DOUBLE NUT 3. REFER TO LIFE SAFETY PLANS FOR REQUIRED FIRE RATED
PARTITION LOCATION. Middle East District
G SOLID TOP SOLID TOP SOLID TOP 4. SMOKE AND/OR FIRE RATED PARTITIONS SHALL BE
CONSTRUCTED PER THE REQUIREMENTS OF THE U.L. TEST

MIN

MIN

MIN
150

150

150
COURSE,TYP COURSE,TYP COURSE,TYP
ASSEMBLY IDENTIFIED. PARTITIONS SHALL EXTEND FROM
STRUCTURAL SLAB TO STRUCTURAL SLAB. PROVIDE

DATE
CONTINUOUS FIRE STOPPING/SEALANT BOTH SIDES, TOP
AND BOTTOM, AND AT ALL PENETRATIONS.
CEILING AS CEILING AS SCHED - CEILING AS SCHED -
5. FIRE BARRIERS AND FIRE PARTITIONS SHALL BE
SCHED - SEE SEE FINISH SEE FINISH
DESIGNATED ABOVE THE CEILING AND ON CEILING ACCESS
FINISH SCHEDULE SCHEDULE
DOORS WHICH PROVIDE ACCESS TO SUCH FIRE RATED
SCHEDULE
ASSEMBLIES BY SIGNAGE HAVING LETTERS NO SMALLER
Top THAN 25mm IN HEIGHT. SUCH SIGNAGE SHALL INDICATE
THE FIRE RESISTANCE OF THE ASSEMBLY AND THE TYPE
OF ASSEMBLY, AND BE PROVIDED AT HORIZONTAL
INTERVALS NO MORE THAN 2400mm.
6. FULL HEIGHT PARTITIONS SHALL PROVIDE FOR VERTICAL
PAINT CMU
MOVEMENT AT THE STRUCTURAL JOINT AT THE SLAB
WHERE EXPOSED
ABOVE AND ALLOW FOR A MAXIMUM STRUCTURAL
REINF CMU, SIZE DEFLECTION OF 25mm. SEAL JOINTS TOP AND BOTTOM.
REINF CMU, SIZE
AS SCHEDULED 7. SEE STRUCTURAL DRAWINGS FOR TYPICAL TOP OF WALL
AS SCHEDULED,

DESCRIPTION
PAINTED REINF CMU, SIZE AND BOTTOM OF WALL DETAILS FOR MASONRY AND CONC.
F AS SCHEDULED 8. PROVIDE SOLID FRT WOOD BLOCKING AT METAL STUD OR
FURRED PARTITIONS AS REQUIRED TO ACCOMMODATE
INSTALLATION OF CASEWORK, LOCKERS, GRAB BARS,
HANDRAILS, AV EQUIPMENT, SIGNAGE AND OTHER WALL
CONTROL JOINT CONTROL JOINT MOUNTED SCHEDULED EQUIPMENT AND ACCESSORIES.
WHERE OCCURS WHERE OCCURS PROVIDE FRT PLYWOOD WHERE PLYWOOD BACKER
PANELS ARE INDICATED OR SPECIFIED.
9. GYPSUM BOARD PARTITIONS SPANNING ABOVE
9.011 - 20 mm THICK DOOR/WINDOW OPENINGS 1800mm WIDE OR MORE SHALL
GYPSUM PLASTER BE DIAGONALLY BRACED AT 1800mm OC.
9.011 - 20 mm THICK
GYPSUM PLASTER 10. METAL STUD SPACING SHALL BE 400mm OC UNO.
11. PROVIDE GWB CONTROL JOINTS AND CONSTRUCT IN
ACCORDANCE WITH GYPSUM ASSOCIATION GA 216-2016
AND AS INDICATED ON THE DRAWINGS. COORDINATE
Plan GWB AND PLASTER CONTROL JOINTS WITH MASONRY
CONTROL JOINTS.
12. WHERE GWB OCCURS IN RESTROOMS AND/OR OTHER

MARK
WET AREAS OR WHERE SCHEDULED TO RECEIVE EPOXY
PAINT, PROVIDE MOISTURE RESISTANT GWB.
E SEE CORE WIDTH SEE CORE WIDTH SEE CORE WIDTH
13. INTERIOR PARTITIONS ARE M8F0.1P2 UNO.
14. INTERIOR PARTITIONS ARE REINFORCED, SEE
STRUCTURAL FOR REINFORCEMENT.

PLOT SCALE: PLOT DATE:


2/9/2022 4:52:33
FLOOR AND FLOOR AND BASE AS FLOOR AND BASE AS 15. PROVIDE CEMENT PLASTER IN LIEU OF GYPSUM PLASTER
BASE AS SCHED - SEE FINISH SCHED - SEE FINISH AT PARTITIONS SCHEDULED TO RECEIVE A TILE FINISH.

SOLICITATION NO.:
SCHED - SEE SCHEDULE SCHEDULE

SA-480530-1$-SA604DT.dwg
PM
CONTRACT NO.:
FINISH
SCHEDULE LEGEND - PARTITION TYPE

ISSUE DATE:
Base

1:1
CSI DIVISION DESIGNATOR
CORE WIDTH

M#S0 NON-FULL HEIGHT


MASONRY, PAINTED
M#S0.1P NON-FULL HEIGHT MASONRY,
NON-RATED, WITH PLASTER
M#S0.1P2 NON-FULL HEIGHT
MASONRY, NON-RATED,
CORE HEIGHT
FINISH ONE-SIDE ONLY WITH PLASTER BOTH SIDES RATING

FILE NO.:
FURRING SIZE

SUBMITTED BY:
J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:
FINISH CONSTRUCTION /

A. HANKS
D SPECIALTY

S. OKES
CKD BY:

ANSI D
SIZE:
M8F0.2F
CEILING AS CEILING AS SCHED - CEILING AS SCHED -
SCHED - SEE SEE FINISH SEE FINISH CORE CSI DIVISION DESIGNATOR:

TRANSATLANTIC MIDDLE EAST DISTRICT


PARTIAL HEIGHT NON-RATED MASONRY CORE PARTITIONS

FINISH SCHEDULE SCHEDULE

US ARMY CORPS OF ENGINEERS


SCHEDULE CODE CSI DIVISION

201 PRINCE FREDERICK DRIVE,


G 02-EXISTING (GENERIC / UNKNOWN)

WINCHESTER, VA 22602
C 03-CONCRETE
M 04-MASONRY
D 05-STRUCTURAL/COLD FORM
W 06-WOOD
L 09-INTERIOR LIGHT GAUGE METAL FRAMING
SOLID TOP SOLID TOP SOLID TOP (LGMF)
COURSE,TYP COURSE,TYP COURSE,TYP P 10-SPECIALTY

CORE WIDTH / FURRING SIZE:


Top CODE SIZE
C 0 --
1 <=25 (I.E. 20 MM DIRECT APPLIED PLASTER)
22 (METAL HAT CHANNEL)
PAINT CMU 2 60 (METAL STUD)
WHERE EXPOSED 3 90 (METAL STUD)
4 100 NOMINAL (100 ACTUAL (CMU))
REINF CMU,
6 150 NOMINAL (150 ACTUAL (CMU))
SIZE AS
REINF CMU, SIZE 4.036 - GROUT CMU 8 200 NOMINAL (200 ACTUAL (CMU))
SCHEDULED,
AS SCHEDULED CELLS AT GFRC 10 250 NOMINAL (250 ACTUAL (CMU))
HEIGHT AS NOTED
HEIGHT AS NOTED

HEIGHT AS NOTED

PAINTED
MOUNTING BRACKETS 12 300 NOMINAL (300 ACTUAL (CMU))

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


CORE HEIGHT:
CONTROL JOINT
C PARTITION TO UNDERSIDE OF CEILING

THAAD STANDARD FACILITIES


WHERE OCCURS CONTROL JOINT

VARIOUS LOCATIONS, KSA


WHERE OCCURS (CEILING IS CONTINUOUS ABOVE)
F FULL HEIGHT PARTITION

STANDARD DETAILS
PARTITION TYPES
9.011 - 20 mm THICK P PARTIAL HEIGHT PARTITION
GYPSUM PLASTER (HEIGHT VARIES, SEE KEYNOTE)

SA-480530
9.011 - 20 mm THICK S STOP PARTITION 150MM ABOVE ADJACENT
B GYPSUM PLASTER CEILING

RATING:
Plan 0 NON-RATED
1 1-HOUR RATED
2 2-HOUR RATED
3 3-HOUR RATED
SEE CORE WIDTH SEE CORE WIDTH SEE CORE WIDTH 4 4-HOUR RATED
H 1/2 HOUR RATED
S SMOKE RATED
FLOOR AND FLOOR AND BASE AS FLOOR AND BASE AS a STC 35
BASE AS SCHED - SEE FINISH SCHED - SEE FINISH b STC 40
SCHED - SEE SCHEDULE SCHEDULE c STC 45
FINISH d STC 50
SCHEDULE e STC 55
2/9/2022 4:52:33 PM

A Base FINISH CONSTRUCTION / SPECIALTY:


SHEET ID
C CEMENT BOARD
F METAL FURRING / GWB (1-SIDE) $
M#P0 PARTIAL HEIGHT
MASONRY, PAINTED
M#P0.1P PARTIAL HEIGHT MASONRY,
NON-RATED, WITH PLASTER
M#P0.1P2 PARTIAL HEIGHT MASONRY,
NON-RATED, WITH PLASTER
F2 METAL FURRING / GWB (2-SIDES)

FINISH ONE-SIDE ONLY BOTH SIDES


P
P2
PLASTER FINISH (1-SIDE)
PLASTER FINISH (2-SIDES) SA604
1 2 3 4 5 6 7 8 9 10

7.195 - STRUCTURAL STANDING GENERAL SHEET NOTES


7.131 - ALUMINUM STRUCTURAL SEAM ROOF HALTER CLIPS
STANDING SEAM METAL 1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
ROOFING
US Army Corps of
7.196 - GALV STEEL HAT CHANNELS 2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND Engineers ®
SYMBOLS.
Middle East District
G 7.196 - GALV STEEL HAT CHANNELS 7.131 - ALUMINUM STRUCTURAL
10 STANDING SEAM METAL
1 ROOFING

DATE
10 7.279 - MINERAL FIBER BLANKET
1 5.003 - STEEL ROOF DECK, SEE INSULATION, RSI=4.40 (R-25) MIN
STRUCTURAL DRAWINGS

7.204 - REINFORCED
POLYETHYLENE AIR AND VAPOR
BARRIER

5.003 - STEEL ROOF DECK, SEE


STRUCTURAL DRAWINGS

DESCRIPTION
F REFER TO SHEETS SA522
AND SA523 FOR ROOF
TYPE RS-3 TYPICAL
DETAILS. BUILDING
SPECIFIC DETAILS FOR
ROOF TYPE RS-3 ARE
INCLUDED IN THE
BUILDING DRAWING
PACKAGES.

TYP METAL ROOF SYSTEM RS-4 TYP METAL ROOF SYSTEM RS-3
1 : 10 1 : 10

MARK
7.189 - 50 mm PRECAST
E CONCRETE BALLAST PAVERS

PLOT SCALE: PLOT DATE:


2/9/2022 4:52:46
7.078 - GEOTEXTILE FABRIC MAT
7.207 - MINERAL FIBER BLANKET

SOLICITATION NO.:
INSULATION, RSI=3.52 (R-20) MIN

SA-480530-1$-SA608DT.dwg
PM
CONTRACT NO.:
2% SLOPE MIN 7.010 - LOOSE-LAID

ISSUE DATE:
POLYSTYRENE BOARD ROOF 10

13215
INSUL, RSI=4.40 (R-25) MIN

1:1
3 7.195 - STRUCTURAL STANDING
7.025 - LOOSE-LAID BALLASTED SEAM ROOF HALTER CLIPS
EPDM SHEET ROOFING
7.131 - ALUMINUM STRUCTURAL
STANDING SEAM METAL

FILE NO.:
ROOFING

SUBMITTED BY:
J. BLANCHARD
3.136 - SLOPING ROOF SLAB, SEE

J. HOLLAND
DESIGN BY:

DRAWN BY:

A. HANKS
D STRUCTURAL DRAWINGS

S. OKES
CKD BY:
7.016 - FLUID-APPLIED

ANSI D
SIZE:
MEMBRANE AIR BARRIER

REFER TO THE GAHO AND 3.125 - PRECAST CONCRETE


REFER TO SHEET SA525 WATO BUILDING ROOF STRUCTURE, SEE

TRANSATLANTIC MIDDLE EAST DISTRICT


FOR ROOF TYPE RS-5 PACKAGES FOR ROOF STRUCTURAL DRAWINGS
TYPICAL DETAILS.

US ARMY CORPS OF ENGINEERS


TYPE RS-2 DETAILS.

201 PRINCE FREDERICK DRIVE,


BUILDING SPECIFIC
DETAILS FOR ROOF TYPE

WINCHESTER, VA 22602
RS-5 ARE INCLUDED IN
THE BUILDING DRAWING
PACKAGES.

7.196 - GALV STEEL HAT CHANNELS


RS-5 SLOPED ROOF WITH PROTECTED
C
MEMBRANE ROOF SYSTEM METAL ROOF SYSTEM RS-2
1 : 10 1 : 10

3.016 - LIGHTWEIGHT
CONCRETE TOPPING,
MIN 50 mm THICK AND
7.189 - 50 mm PRECAST MAX 150 mm THICK,
CONCRETE BALLAST PAVERS SLOPE 2% MINIMUM
TOWARD ROOF DRAINS
7.078 - GEOTEXTILE FABRIC MAT

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


7.025A - FULLY ADHERED EPDM 7.025A - FULLY ADHERED EPDM
SHEET ROOFING SHEET ROOFING 2% SLOPE MIN
7.298 - ROOF COVER BOARD 7.298 - ROOF COVER BOARD

THAAD STANDARD FACILITIES


7.010 - LOOSE-LAID

VARIOUS LOCATIONS, KSA

ROOF TYPE DETAIL SHEET


POLYSTYRENE BOARD ROOF
13.083 - SLOPE STEEL ROOF DECK 13.064 - SPACE FRAME

STANDARD DETAILS
INSUL, RSI=4.40 (R-25) MIN 2% SLOPE MIN
AND ROOF FRAMING AT CRICKETS CORRUGATED METAL ROOF
TO MAINTAIN POSITIVE SLOPE TO DECK BY MANUFACTURER

SA-480530
ROOF DRAIN, SCUPPER, OR GUTTER. 2% SLOPE 7.025 - LOOSE-LAID BALLASTED
B 2% SLOPE 2% SLOPE MIN
13.063 - SPACE FRAME ROOF
EPDM SHEET ROOFING
PURLINS AND FRAMING

MAX
MIN

150
MIN SUPPORTS BY MANUFACTURER
REFER TO SHEETS SA518
AND SA519 FOR ROOF GRAPHIC SCALES
TYPE RS-1 TYPICAL
RS-6
RS-6

50 MIN, NTS
DETAILS. BUILDING

150 MAX, NTS


SPECIFIC DETAILS FOR
ROOF TYPE RS-1 ARE
13.063 - SPACE FRAME ROOF INCLUDED IN THE
PURLINS AND FRAMING SUPPORTS BUILDING DRAWING
13.062 - SPACE FRAME
BY MANUFACTURER PACKAGES.
GALVANIZED STEEL STRUCTURE
13.062 - SPACE FRAME TRUSS BY MANUFACTURER
GALVANIZED STEEL STRUCTURE
SPACE FRAME TOP CORD 3.115 - REINFORCED 7.297 - LOOSE-LAID
TRUSS BY MANUFACTURER
SPACE FRAME DIAGONAL MEMBERS CAST-IN-PLACE CONCRETE POLYSTYRENE BOARD RIGID
2/9/2022 4:52:46 PM

ROOF SLAB, SEE STRUCTURAL INSUL ON CONC RF DECK IN 75


DRAWINGS mm THICK LAYERS TO LIMIT
A LIGHTWEIGHT CONCRETE TO 150 0 200 400 800
SHEET ID
mm THICK

METAL ROOF WITH MEMBRANE ROOF SYSTEM TYP PROTECTED MEMBRANE ROOF SYSTEM SCALE: 1:10 $

RS-6 RS-1 UNLESS OTHERWISE NOTED, LINEAR


DIMENSIONS ARE IN MILLIMETERS
SA608
1 : 10 1 : 10
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND US Army Corps of
SYMBOLS. Engineers ®
3. REFER TO ARCHITECTURAL ENLARGED AREA PLANS FOR DOOR TAG
LOCATIONS. Middle East District
G 4. COORDINATE REQUIRED FIRE-RATED DOORS WITH FIRE-RATED PARTITIONS,
REFER TO LIFE SAFETY PLAN.
5. REFER TO WINDOW SCHEDULE FOR HOLLOW METAL BORROWED LIGHT,
ALUMINUM STOREFRONT AND CURTAIN WALL FRAME TYPES.

DATE
6. DOOR OPENINGS ARE DIMENSIONED BY MASONRY OPENING OR TO
CENTERLINE OF OPENING. DOOR OPENINGS THAT ARE NOT DIMENSIONALLY
LOCATED ARE TO BE CENTERED BETWEEN WALLS OR POSITIONED WITH THE
WIDTH WIDTH WIDTH WIDTH WIDTH WIDTH WIDTH HINGED JAMB 150 mm AWAY FROM ADJACENT PERPENDICULAR WALL OR
AS SCHED AS SCHED AS SCHED AS SCHED AS SCHED AS SCHED AS SCHED COLUMN AS SHOWN ON THE PLANS AND/OR DETERMINED BY THE DETAILS.
7. FRAME DEPTH FOR WRAP-AROUND HOLLOW METAL FRAMES SHALL BE THE
WIDTH OF THE PARTITION PLUS 30mm OR AS NOTED. SEE PARTITION TYPES
200

200

200

200
FOR WIDTH OF PARITIONS.
8. FIELD VERIFY OPENINGS PRIOR TO FABRICATION OF ALUMINUM ENTRANCE
SYSTEMS.
GLASS AS GLASS AS 9. VIEW WINDOWS IN RATED DOORS ARE TO BE 64.5 SM MAXIMUM.
SCHED SCHED 10. SEE SPECIFICATIONS FOR DOOR HARDWARE SETS. REVIEW ALL HARDWARE
165 165 165 165 SETS AND LOCK FUNCTIONS WITH OWNER PRIOR TO DEVELOPING FINAL
HARDWARE SETS.
AS SCHED

AS SCHED

AS SCHED

AS SCHED

AS SCHED

AS SCHED

AS SCHED
HEIGHT

HEIGHT

HEIGHT

HEIGHT

HEIGHT

HEIGHT

HEIGHT
11. REFER TO ELECTRICAL AND TELECOM DRAWINGS FOR POWER AND/OR CARD

DESCRIPTION
F GLASS AS 400
READ ACCESS REQUIREMENTS.
SCHED GLASS
AS
SCHED

1095

1095
GLAZING TYPES:

400
100 100
165 165

300
GL-1: 25 mm CLEAR LOW-E INSULATED TEMPERED / TEMPERED GLASS UNIT
200

200
GL-2: 25 mm TINTED LOW-E INSULATED TEMPERED / TEMPERED GLASS UNIT
FULL-GLASS FULL-GLASS NARROW VISION LITE NARROW VISION LITE FLUSH-LOUVER FLUSH FLUSH
GL-3: 30 mm TINTED LOW-E INSULATED TEMPERED LAMINATED GLASS UNIT

FGP FGS NP NS FLS FP FS GL-4: NOT USED

GL-5: 6 mm VISION GLASS, CLEAR, TEMPERED

MARK
GL-6: 6 mm FIRE-RATED GLASS, CLEAR, TEMPERED
WIDTH AS SCHED WIDTH WIDTH
E AT PAIR WHERE OCCURS AS SCHED AS SCHED GL-7: NOT USED
50
WIDTH 50 GL-8: NOT USED

PLOT SCALE: PLOT DATE:


2/9/2022 4:52:49
AS SCHED

50
GL-9: BULLET RESISTANT GLAZING. GLAZING SHALL BE GLASS, PLASTIC OR
COMPOSITE WITH NO-SPALL PROTECTED INTERIOR FACE TO COMPLY

SOLICITATION NO.:

SA-480530-1$-SA610DT.dwg
PM
WITH THE SPECIFIED TEST STANDARD IN SPECIFICATION SECTION 08 34

CONTRACT NO.:
WIDTH WIDTH 02 BULLET-RESISTANT COMPONENTS

ISSUE DATE:
8.069 - STEEL PIVOT HINGES BY
AS SCHED AS SCHED DOOR MANUFACTURER
90 90 90 90 GL-10: 25 mm INSULATED GLASS UNIT, 20 MIN FIRE RATED, CLEAR, LOW-E

1:1
GL-11: ONE WAY VISION BULLET RESISTANT TINTED GLASS/PLASTIC AIR-GAP
GLAZING. GLAZING SHALL BE WITH NO-SPALL PROTECTED INTERIOR

AS SCHED
FACE. GLAZING TO COMPLY WITH THE SPECIFIED TEST STANDARD IN

HEIGHT
90

90

SPECIFICATION SECTION 08 34 02 BULLET-RESISTANT COMPONENTS.


8.067 - PULL HANDLE, HASP,
HEIGHT AS

FILE NO.:
GALVANIZED, WELDED WITH 5
SCHED

GLASS AS GLASS AS GL-12: BULLET RESISTANT TINTED GLASS/PLASTIC AIR-GAP GLAZING. GLAZING

AS SCHED

SUBMITTED BY:
mm REINFORCEMENT PLATES,

HEIGHT

J. BLANCHARD
SCHED SCHED SHALL BE WITH NO-SPALL PROTECTED INTERIOR FACE. GLAZING TO
TYP

J. HOLLAND
DESIGN BY:

DRAWN BY:
COMPLY WITH THE SPECIFIED TEST STANDARD IN SPECIFICATION

A. HANKS
D SECTION 08 34 02 BULLET-RESISTANT COMPONENTS.

S. OKES
CKD BY:
102

102

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
AS NOTED
8.068 - STANDARD BARREL BOLT

US ARMY CORPS OF ENGINEERS


ASSEMBLY FOR PADLOCK
916

916

201 PRINCE FREDERICK DRIVE,


165

165

WINCHESTER, VA 22602
AL ENTRANCE AL ENTRANCE GALVANIZED STEEL
SOLID DOOR COILING COUNTER DOOR OVERHEAD COILING DOOR

EP ES SD CCD OCD
WIDTH
WIDTH WIDTH WIDTH
C AS SCHED
AS SCHED
AS SCHED AS SCHED
300 90 90 150 150
PROVIDE CLOSURE PLATE
BETWEEN LEAVES TO CLOSE
OFF GAP BETWEEN LEAVES.
CLOSURE PLATE TO COMPLY
WITH BULLET PROTECTION GLASS AS 130
90

REQUIREMENTS AT DOORS SCHED GLASS AS


SCHEDULED TO HAVE BULLET SCHED
RESISTANT COMPONENTS.

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


HEIGHT AS
AS SCHED

AS SCHED

GLASS AS
102
HEIGHT

HEIGHT

SCHED

SCHED
102

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
1525

STANDARD DETAILS
DOOR PANEL TYPES
600
1000

1250
916

916

SA-480530
B

DUTCH DOOR VISION TRAFFIC DOOR AL ENTRANCE HALF GLAZED GRAPHIC SCALES
D V HGS HGP
2/9/2022 4:52:49 PM

A 0 600 1.2M 2.4M


SHEET ID
SCALE: 1:30 $
DOOR PANEL TYPES
1 : 30 UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA610
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND US Army Corps of
SYMBOLS. Engineers ®
3. REFER TO ARCHITECTURAL ENLARGED AREA PLANS FOR DOOR TAG
LOCATIONS. Middle East District
G 4. COORDINATE REQUIRED FIRE-RATED DOORS WITH FIRE-RATED PARTITIONS,
REFER TO LIFE SAFETY PLAN.
5. REFER TO WINDOW SCHEDULE FOR HOLLOW METAL BORROWED LIGHT,
ALUMINUM STOREFRONT AND CURTAIN WALL FRAME TYPES.

DATE
PACKAGE WIDTH
6. DOOR OPENINGS ARE DIMENSIONED BY MASONRY OPENING OR TO
TENSION CENTERLINE OF OPENING. DOOR OPENINGS THAT ARE NOT DIMENSIONALLY
END W LOCATED ARE TO BE CENTERED BETWEEN WALLS OR POSITIONED WITH THE
AS SCHED HINGED JAMB 150 mm AWAY FROM ADJACENT PERPENDICULAR WALL OR
WIDTH DRIVE COLUMN AS SHOWN ON THE PLANS AND/OR DETERMINED BY THE DETAILS.
AS SCHED END 7. FRAME DEPTH FOR WRAP-AROUND HOLLOW METAL FRAMES SHALL BE THE

HOOD
WIDTH OF THE PARTITION PLUS 30mm OR AS NOTED. SEE PARTITION TYPES

241
FOR WIDTH OF PARITIONS.
50 WIDTH 50 50 WIDTH 50 50 WIDTH 50 50 WIDTH 50
8. FIELD VERIFY OPENINGS PRIOR TO FABRICATION OF ALUMINUM ENTRANCE
AS SCHED AS SCHED AS SCHED AS SCHED SYSTEMS.
9. VIEW WINDOWS IN RATED DOORS ARE TO BE 64.5 SM MAXIMUM.
10. SEE SPECIFICATIONS FOR DOOR HARDWARE SETS. REVIEW ALL HARDWARE
COILING SETS AND LOCK FUNCTIONS WITH OWNER PRIOR TO DEVELOPING FINAL
100

50

50
50

DOOR HARDWARE SETS.

AS SCHED
11. REFER TO ELECTRICAL AND TELECOM DRAWINGS FOR POWER AND/OR CARD

DESCRIPTION
HEIGHT
HOUSING
F READ ACCESS REQUIREMENTS.

CASED OPENING

AS SCHED
AS SCHED
AS SCHED

AS SCHED

AS SCHED

HEIGHT
HEIGHT

HEIGHT
HEIGHT

H
(SEE DETAILS)
AS SCHED
COUNTERTOP AS
SCHED

F1 F2 F3 F4 F5 F6

MARK
E

PLOT SCALE: PLOT DATE:


2/9/2022 4:52:52
SOLICITATION NO.:

SA-480530-1$-SA611DT.dwg
PM
CONTRACT NO.:
ISSUE DATE:

1:1
WIDTH 50 450 50 WIDTH 50 50 WIDTH 50 50 450 50 450 50 WIDTH 50
AS SCHED AS SCHED AS SCHED AS SCHED

FILE NO.:
50

50

SUBMITTED BY:
50

J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:
AS SCHED

A. HANKS
D
HEIGHT

S. OKES
CKD BY:

ANSI D
SIZE:
SEE SCHED FOR SANITARY STOP. STOP SEE SCHED FOR
GLASS TYPE TERMINATES 200mm GLASS TYPE

AS SCHED
AS SCHED

AS SCHED
ABOVE THE FINISH
HEIGHT

HEIGHT
HEIGHT

TRANSATLANTIC MIDDLE EAST DISTRICT


FLOOR AND IS CLOSED
WITH A 45 DEGREE
50

50

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


ANGLE TO FACILITATE
16 GA. MIN. CLEANING

WINCHESTER, VA 22602
(SEE ELEV)
AS SCHED

STAINLESS STEEL
600

600
FRAME W/ EPDM
GASKET
200

200

200

200
F7 F8 F9 F10
C

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


60 WIDTH 60 50 WIDTH 50
AS SCHED AS SCHED

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA

STANDARD DETAILS
DOOR FRAME TYPES
50
60

SA-480530
B
HEIGHT AS SCHEDULED

AS SCHED

GRAPHIC SCALES
HEIGHT

CHANNEL FRAME FOR DUAL ACTING


2/9/2022 4:52:52 PM

ALUMINUM STOREFRONT FRAME TRAFFIC DOORS


A 0 600 1.2M 2.4M
SHEET ID
F11 F12
SCALE: 1:30 $
DOOR FRAME TYPES UNLESS OTHERWISE NOTED, LINEAR SA611
1 : 30 DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10
3000
GENERAL SHEET NOTES
1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®

800
SYMBOLS.
GL-1 Middle East District
G 3. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR WINDOW TAG
LOCATIONS. REFER TO WINDOW SCHEDULES FOR WINDOW FINISH AND
REFERENCED WINDOW HEAD, JAMB AND SILL DETAILS.

DATE
580 4. COORDINATE REQUIRED FIRE-RATED GLAZING WITH FIRE-RATED PARTITIONS,
600 W3D REFER TO LIFE SAFETY PLAN.
W3D - ELEVATION 5. FIELD VERIFY DIMENSION OF ROUGH OPENINGS PRIOR TO FABRICATION.
1 : 20
6. PROVIDE SELF-ADHERING TRANSITION AIR BARRIER MEMBRANE OR RIGID
3600 TRANSITION SHEET AT ALL FLUID- APPLIED AIR BARRIER SYSTEMS AND
DISSIMILAR MATERIALS TO MAINTAIN A CONTINUOUS AIR BARRIER
THROUGHOUT THE BUILDING ENVELOPE. SEAL FASTENERS THAT PENETRATE
THE AIR BARRIER.

7. PROVIDE ROLL DOWN INSECTS SCREENS AT OPERABLE WINDOWS

600
GL-1
550
600

DESCRIPTION
F

1800

1800
GL-2 GL-6 W3C

BULLET RESISTANT
W3C - ELEVATION GLAZING TYPES:
STEEL WINDOW 1 : 20
1400

GL-11
1350

GL-9 GL-1: 25 mm CLEAR LOW-E INSULATED TEMPERED / TEMPERED GLASS UNIT


3000
GL-2: 25 mm TINTED LOW-E INSULATED TEMPERED / TEMPERED GLASS UNIT

GL-3: 30 mm TINTED LOW-E INSULATED TEMPERED LAMINATED GLASS UNIT

GL-4: NOT USED

600

600
GL-2 GL-6

600

MARK
GL-1
GL-5: 6 mm VISION GLASS, CLEAR, TEMPERED

E W9 W6
GL-6: 6 mm FIRE-RATED GLASS, CLEAR, TEMPERED

W4C W4B GL-7: NOT USED


W3B

PLOT SCALE: PLOT DATE:


2/9/2022 4:53:01
GL-8: NOT USED

W9 - ELEVATION W6 - ELEVATION W4C - ELEVATION W4B - ELEVATION W3B - ELEVATION

SOLICITATION NO.:

SA-480530-1$-SA615DT.dwg
GL-9: BULLET RESISTANT GLAZING. GLAZING SHALL BE GLASS, PLASTIC OR

PM
CONTRACT NO.:
COMPOSITE WITH NO-SPALL PROTECTED INTERIOR FACE TO COMPLY

ISSUE DATE:
1 : 20 1 : 20 1 : 20 1 : 20 1 : 20 WITH THE SPECIFIED TEST STANDARD IN SPECIFICATION SECTION 08 34
02 BULLET-RESISTANT COMPONENTS
600

1:1
900
GL-10: 25 mm INSULATED GLASS UNIT, 20 MIN FIRE RATED, CLEAR, LOW-E

GL-11: ONE WAY VISION BULLET RESISTANT TINTED GLASS/PLASTIC AIR-GAP


GLAZING. GLAZING SHALL BE WITH NO-SPALL PROTECTED INTERIOR
FACE. GLAZING TO COMPLY WITH THE SPECIFIED TEST STANDARD IN

FILE NO.:
SPECIFICATION SECTION 08 34 02 BULLET-RESISTANT COMPONENTS.

SUBMITTED BY:
1470

J. BLANCHARD
900
GL-1
GL-12: BULLET RESISTANT TINTED GLASS/PLASTIC AIR-GAP GLAZING. GLAZING

J. HOLLAND
DESIGN BY:

DRAWN BY:
W3A

900
GL-1

A. HANKS
D SHALL BE WITH NO-SPALL PROTECTED INTERIOR FACE. GLAZING TO

S. OKES
CKD BY:
2200

ANSI D
COMPLY WITH THE SPECIFIED TEST STANDARD IN SPECIFICATION

SIZE:
SECTION 08 34 02 BULLET-RESISTANT COMPONENTS.

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS
W3A - ELEVATION

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
600
1350

1 : 20
GL-1
1200

GL-9
GL-1 2400

W4A

W4A - ELEVATION

600
GL-1
C W8 W5A 1 : 20
600

W3

W8 - ELEVATION W5A - ELEVATION W3 - ELEVATION


1 : 20 1 : 20 1 : 20

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


400

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA

WINDOW TYPES, W1 - W9
400
GL-3

STANDARD DETAILS
1010
1800

GL-2

SA-480530
1000
B
W2

GRAPHIC SCALES
GL-9 W2 - ELEVATION
1350

1 : 20
1200

GL-1
600
600

GL-2
2/9/2022 4:53:01 PM

600
GL-2 W1
A W7 W5 W4
0 400 800 1.6M
SHEET ID
SCALE: 1:20 $
W7 - ELEVATION W5 - ELEVATION W4 - ELEVATION W1 - ELEVATION UNLESS OTHERWISE NOTED, LINEAR SA615
1 : 20 1 : 20 1 : 20 1 : 20
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


WIDTH
1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
AS SCHED SLIDING PANEL
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR WINDOW TAG
LOCATIONS. REFER TO WINDOW SCHEDULES FOR WINDOW FINISH AND
REFERENCED WINDOW HEAD, JAMB AND SILL DETAILS.

DATE
4. COORDINATE REQUIRED FIRE-RATED GLAZING WITH FIRE-RATED PARTITIONS,

AS SCHED
REFER TO LIFE SAFETY PLAN.

HEIGHT
GL-1 GL-1
5. FIELD VERIFY DIMENSION OF ROUGH OPENINGS PRIOR TO FABRICATION.

6. PROVIDE SELF-ADHERING TRANSITION AIR BARRIER MEMBRANE OR RIGID


TRANSITION SHEET AT ALL FLUID- APPLIED AIR BARRIER SYSTEMS AND
DISSIMILAR MATERIALS TO MAINTAIN A CONTINUOUS AIR BARRIER
THROUGHOUT THE BUILDING ENVELOPE. SEAL FASTENERS THAT PENETRATE
THE AIR BARRIER.

7. PROVIDE ROLL DOWN INSECTS SCREENS AT OPERABLE WINDOWS

AS NOTED
W16

DESCRIPTION
F

4800

1200 1200 1200 1200


W16 - ELEVATION EQL EQL
GLAZING TYPES:
1 : 20

GL-1: 25 mm CLEAR LOW-E INSULATED TEMPERED / TEMPERED GLASS UNIT

GL-2: 25 mm TINTED LOW-E INSULATED TEMPERED / TEMPERED GLASS UNIT

GL-3: 30 mm TINTED LOW-E INSULATED TEMPERED LAMINATED GLASS UNIT

2400 GL-4: NOT USED

MARK
EQ EQ EQ 1000
GL-5: 6 mm VISION GLASS, CLEAR, TEMPERED
E GL-6: 6 mm FIRE-RATED GLASS, CLEAR, TEMPERED
GL-2 GL-2 GL-2 GL-2 GL-2 GL-2 GL-2 GL-2

PLOT SCALE: PLOT DATE:


GL-7: NOT USED

2/9/2022 4:53:08
2400
GL-8: NOT USED

SOLICITATION NO.:

SA-480530-1$-SA616DT.dwg
PM
CONTRACT NO.:
GL-9: BULLET RESISTANT GLAZING. GLAZING SHALL BE GLASS, PLASTIC OR

ISSUE DATE:
COMPOSITE WITH NO-SPALL PROTECTED INTERIOR FACE TO COMPLY
WITH THE SPECIFIED TEST STANDARD IN SPECIFICATION SECTION 08 34

1:1
02 BULLET-RESISTANT COMPONENTS
1400

1400
GL-9 GL-9 GL-9 GL-9
GL-10: 25 mm INSULATED GLASS UNIT, 20 MIN FIRE RATED, CLEAR, LOW-E

GL-11: ONE WAY VISION BULLET RESISTANT TINTED GLASS/PLASTIC AIR-GAP


GLAZING. GLAZING SHALL BE WITH NO-SPALL PROTECTED INTERIOR

FILE NO.:
600
GL-2 FACE. GLAZING TO COMPLY WITH THE SPECIFIED TEST STANDARD IN
GL-2 GL-2 GL-2 SPECIFICATION SECTION 08 34 02 BULLET-RESISTANT COMPONENTS.

SUBMITTED BY:
J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:
GL-12: BULLET RESISTANT TINTED GLASS/PLASTIC AIR-GAP GLAZING. GLAZING

A. HANKS
D

S. OKES
CKD BY:
SHALL BE WITH NO-SPALL PROTECTED INTERIOR FACE. GLAZING TO

ANSI D
SIZE:
COMPLY WITH THE SPECIFIED TEST STANDARD IN SPECIFICATION
W15 SECTION 08 34 02 BULLET-RESISTANT COMPONENTS.
W13 W11

TRANSATLANTIC MIDDLE EAST DISTRICT


W15 - ELEVATION W13 - ELEVATION W11 - ELEVATION

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
1 : 20 1 : 20 1 : 20

C 3200
1050 1100 1050

300

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


GL-9 GL-9 GL-9
1400

3500

THAAD STANDARD FACILITIES


1150 1200 1150

VARIOUS LOCATIONS, KSA

WINDOW TYPES, W10 - W16


STANDARD DETAILS
SA-480530
B
150

8.141 - PAINTED GALVANIZED


STEEL FRAMED BULLET GL-2 GRAPHIC SCALES
1800

8.106 8.125 - PAINTED GALVANIZED


.

RESISTANT INFILL PANEL AT

1350
STEEL FRAMED BULLET
SIDES OF BULLET RESISTANT EQL EQL GL-9 GL-9 GL-9
RESISTANT WINDOW SYSTEM
PASS-THROUGH DRAWER. FILL
INFILL PANEL WITH MINERAL 8.106
. 8.105 - BULLET RESISTANT
WOOL INSULATION. W14 SPEAKING APERTURE

8.106 - 100 mm x 400 mm BULLET


RESISTANT PASS-THROUGH
DRAWER. MINIMUM CLEAR INSIDE
DIMENSIONS OF SUFFICIENT SIZE TO
PASS IDENTIFICATION DOCUMENTS.
2/9/2022 4:53:08 PM

W10
A W12
0 400 800 1.6M
SHEET ID
SCALE: 1:20 $

W14 - ELEVATION W12 - ELEVATION W10 - ELEVATION UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA616
1 : 20 1 : 20 1 : 20
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


3000 1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
3000
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
EQL EQL SYMBOLS.
EQL EQL Middle East District
G 3. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR WINDOW TAG
LOCATIONS. REFER TO WINDOW SCHEDULES FOR WINDOW FINISH AND
REFERENCED WINDOW HEAD, JAMB AND SILL DETAILS.

DATE
4. COORDINATE REQUIRED FIRE-RATED GLAZING WITH FIRE-RATED PARTITIONS,
REFER TO LIFE SAFETY PLAN.
GL-5 GL-5 GL-5 GL-2 GL-2 GL-2
5. FIELD VERIFY DIMENSION OF ROUGH OPENINGS PRIOR TO FABRICATION.

6. PROVIDE SELF-ADHERING TRANSITION AIR BARRIER MEMBRANE OR RIGID


TRANSITION SHEET AT ALL FLUID- APPLIED AIR BARRIER SYSTEMS AND
DISSIMILAR MATERIALS TO MAINTAIN A CONTINUOUS AIR BARRIER
THROUGHOUT THE BUILDING ENVELOPE. SEAL FASTENERS THAT PENETRATE
THE AIR BARRIER.

7. PROVIDE ROLL DOWN INSECTS SCREENS AT OPERABLE WINDOWS


DOOR WIDTH AS SCHEDULED
DOOR WIDTH AS SCHEDULED

DESCRIPTION
GL-2
F DOOR HEIGHT AS SCHEDULED

DOOR HEIGHT AS SCHEDULED


GL-2
GL-5 GL-5
3000

3000
GLAZING TYPES:
GL-1: 25 mm CLEAR LOW-E INSULATED TEMPERED / TEMPERED GLASS UNIT

GL-2: 25 mm TINTED LOW-E INSULATED TEMPERED / TEMPERED GLASS UNIT

GL-3: 30 mm TINTED LOW-E INSULATED TEMPERED LAMINATED GLASS UNIT

GL-4: NOT USED

MARK
GL-5 GL-5
600

600
GL-2 GL-2 GL-5: 6 mm VISION GLASS, CLEAR, TEMPERED
E GL-6: 6 mm FIRE-RATED GLASS, CLEAR, TEMPERED
GROUND FLOOR GROUND FLOOR

PLOT SCALE: PLOT DATE:


GL-7: NOT USED

2/9/2022 4:53:13
EL 1 100 EL 1 100
GL-8: NOT USED

SOLICITATION NO.:

SA-480530-1$-SA617DT.dwg
W20 - ELEVATION (INTERIOR WINDOW) W19 - ELEVATION

PM
CONTRACT NO.:
GL-9: BULLET RESISTANT GLAZING. GLAZING SHALL BE GLASS, PLASTIC OR

ISSUE DATE:
COMPOSITE WITH NO-SPALL PROTECTED INTERIOR FACE TO COMPLY
1 : 20 1 : 20 WITH THE SPECIFIED TEST STANDARD IN SPECIFICATION SECTION 08 34

1:1
02 BULLET-RESISTANT COMPONENTS

GL-10: 25 mm INSULATED GLASS UNIT, 20 MIN FIRE RATED, CLEAR, LOW-E

GL-11: ONE WAY VISION BULLET RESISTANT TINTED GLASS/PLASTIC AIR-GAP


GLAZING. GLAZING SHALL BE WITH NO-SPALL PROTECTED INTERIOR

FILE NO.:
FACE. GLAZING TO COMPLY WITH THE SPECIFIED TEST STANDARD IN
SPECIFICATION SECTION 08 34 02 BULLET-RESISTANT COMPONENTS.

SUBMITTED BY:
J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:
GL-12: BULLET RESISTANT TINTED GLASS/PLASTIC AIR-GAP GLAZING. GLAZING

A. HANKS
D

S. OKES
CKD BY:
SHALL BE WITH NO-SPALL PROTECTED INTERIOR FACE. GLAZING TO

ANSI D
SIZE:
COMPLY WITH THE SPECIFIED TEST STANDARD IN SPECIFICATION
SECTION 08 34 02 BULLET-RESISTANT COMPONENTS.

TRANSATLANTIC MIDDLE EAST DISTRICT


1970

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


1980

WINCHESTER, VA 22602
GL-5 GL-5 GL-5
GL-2 GL-2 GL-2
C

WINDOW HEIGHT AS SCHEDULED


WINDOW HEIGHT AS SCHEDULED

2800
DOOR WIDTH AS SCHEDULED
DOOR WIDTH AS SCHEDULED
EQ EQ

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


THAAD STANDARD FACILITIES
DOOR HEIGHT AS SCHEDULED

DOOR HEIGHT AS SCHEDULED

VARIOUS LOCATIONS, KSA

WINDOW TYPES, W17 - W20


STANDARD DETAILS
GL-5 GL-5
GL-2
GL-2

SA-480530
B
400

GL-6 GL-6

GRAPHIC SCALES
1200

800

GL-6 GL-6

GL-2
600

600

GL-5 GL-2
GL-5

W18 GROUND FLOOR GROUND FLOOR


2/9/2022 4:53:13 PM

EL 150 EL 150
A W17A W17B W17B
0 400 800 1.6M
SHEET ID
SCALE: 1:20 $
W18 - ELEVATION W17A - ELEVATION (INTERIOR) W17/W17B - ELEVATION UNLESS OTHERWISE NOTED, LINEAR SA617
1 : 20 1 : 20 DIMENSIONS ARE IN MILLIMETERS
1 : 20
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


2810 1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
EQ EQ US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
SYMBOLS.
Middle East District
G 3. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR WINDOW TAG
LOCATIONS. REFER TO WINDOW SCHEDULES FOR WINDOW FINISH AND
REFERENCED WINDOW HEAD, JAMB AND SILL DETAILS.

DATE
GL-5 GL-5 GL-5 4. COORDINATE REQUIRED FIRE-RATED GLAZING WITH FIRE-RATED PARTITIONS,
REFER TO LIFE SAFETY PLAN.

5. FIELD VERIFY DIMENSION OF ROUGH OPENINGS PRIOR TO FABRICATION.

6. PROVIDE SELF-ADHERING TRANSITION AIR BARRIER MEMBRANE OR RIGID


TRANSITION SHEET AT ALL FLUID- APPLIED AIR BARRIER SYSTEMS AND
DISSIMILAR MATERIALS TO MAINTAIN A CONTINUOUS AIR BARRIER
THROUGHOUT THE BUILDING ENVELOPE. SEAL FASTENERS THAT PENETRATE
THE AIR BARRIER.
DOOR WIDTH AS SCHEDULED
7. PROVIDE ROLL DOWN INSECTS SCREENS AT OPERABLE WINDOWS

DOOR HEIGHT AS SCHEDULED

DESCRIPTION
3000
F

GL-5 GL-5
GLAZING TYPES:
GL-1: 25 mm CLEAR LOW-E INSULATED TEMPERED / TEMPERED GLASS UNIT

GL-2: 25 mm TINTED LOW-E INSULATED TEMPERED / TEMPERED GLASS UNIT

GL-3: 30 mm TINTED LOW-E INSULATED TEMPERED LAMINATED GLASS UNIT

600
GL-5 GL-5
GL-4: NOT USED

MARK
GROUND FLOOR GL-5: 6 mm VISION GLASS, CLEAR, TEMPERED
E EL 150 GL-6: 6 mm FIRE-RATED GLASS, CLEAR, TEMPERED
W22

PLOT SCALE: PLOT DATE:


GL-7: NOT USED

2/9/2022 4:53:17
GL-8: NOT USED

SOLICITATION NO.:

SA-480530-1$-SA618DT.dwg
W22 - ELEVATION (INTERIOR WINDOW)

PM
CONTRACT NO.:
GL-9: BULLET RESISTANT GLAZING. GLAZING SHALL BE GLASS, PLASTIC OR

ISSUE DATE:
COMPOSITE WITH NO-SPALL PROTECTED INTERIOR FACE TO COMPLY
1 : 20 WITH THE SPECIFIED TEST STANDARD IN SPECIFICATION SECTION 08 34

1:1
02 BULLET-RESISTANT COMPONENTS

GL-10: 25 mm INSULATED GLASS UNIT, 20 MIN FIRE RATED, CLEAR, LOW-E

GL-11: ONE WAY VISION BULLET RESISTANT TINTED GLASS/PLASTIC AIR-GAP


GLAZING. GLAZING SHALL BE WITH NO-SPALL PROTECTED INTERIOR

FILE NO.:
FACE. GLAZING TO COMPLY WITH THE SPECIFIED TEST STANDARD IN
SPECIFICATION SECTION 08 34 02 BULLET-RESISTANT COMPONENTS.

SUBMITTED BY:
J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:
GL-12: BULLET RESISTANT TINTED GLASS/PLASTIC AIR-GAP GLAZING. GLAZING

A. HANKS
D

S. OKES
CKD BY:
SHALL BE WITH NO-SPALL PROTECTED INTERIOR FACE. GLAZING TO

ANSI D
SIZE:
COMPLY WITH THE SPECIFIED TEST STANDARD IN SPECIFICATION
SECTION 08 34 02 BULLET-RESISTANT COMPONENTS.

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


2800
4820

WINCHESTER, VA 22602
EQ EQ
600 600 600 600

GL-2 GL-2 GL-2 GL-2 GL-2 GL-2 GL-2 GL-2 GL-2


C

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


DOOR HEIGHT AS SCHEDULED

DOOR HEIGHT AS SCHEDULED


GL-2 GL-2
DOOR WIDTH AS SCHEDULED DOOR WIDTH AS SCHEDULED

THAAD STANDARD FACILITIES


3000

3000

VARIOUS LOCATIONS, KSA

WINDOW TYPES, W21 - W23


STANDARD DETAILS
SA-480530
B GL-2 GL-2 GL-2 GL-2 GL-2

GRAPHIC SCALES
600

600

GL-2 GL-2
GL-2 GL-2 GL-2 GL-2

GROUND FLOOR GROUND FLOOR


EL 150 EL 150
2/9/2022 4:53:17 PM

A 0 400 800 1.6M


SHEET ID
W23 W21
SCALE: 1:20 $
W23 - ELEVATION W21 - ELEVATION UNLESS OTHERWISE NOTED, LINEAR SA618
1 : 20 1 : 20 DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
US Army Corps of
2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGENDS AND Engineers ®
1950 SYMBOLS.
Middle East District
G 3. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR WINDOW TAG
LOCATIONS. REFER TO WINDOW SCHEDULES FOR WINDOW FINISH AND
REFERENCED WINDOW HEAD, JAMB AND SILL DETAILS.

DATE
600
1000 4. COORDINATE REQUIRED FIRE-RATED GLAZING WITH FIRE-RATED PARTITIONS,
REFER TO LIFE SAFETY PLAN.

5. FIELD VERIFY DIMENSION OF ROUGH OPENINGS PRIOR TO FABRICATION.


DOOR WIDTH AS SCHEDULED
6. PROVIDE SELF-ADHERING TRANSITION AIR BARRIER MEMBRANE OR RIGID
TRANSITION SHEET AT ALL FLUID- APPLIED AIR BARRIER SYSTEMS AND
DISSIMILAR MATERIALS TO MAINTAIN A CONTINUOUS AIR BARRIER
THROUGHOUT THE BUILDING ENVELOPE. SEAL FASTENERS THAT PENETRATE
THE AIR BARRIER.

DOOR HEIGHT AS SCHEDULED


7. PROVIDE ROLL DOWN INSECTS SCREENS AT OPERABLE WINDOWS
GL-2 GL-2

DESCRIPTION
F

1800
600

3000
GL-1

2400
GL-2

GLAZING TYPES:
1200

GL-1 GL-1: 25 mm CLEAR LOW-E INSULATED TEMPERED / TEMPERED GLASS UNIT

GL-2: 25 mm TINTED LOW-E INSULATED TEMPERED / TEMPERED GLASS UNIT

GL-3: 30 mm TINTED LOW-E INSULATED TEMPERED LAMINATED GLASS UNIT

600
GL-1 GL-4: NOT USED

MARK
GL-5: 6 mm VISION GLASS, CLEAR, TEMPERED
E W36 GL-6: 6 mm FIRE-RATED GLASS, CLEAR, TEMPERED

W28 W27

PLOT SCALE: PLOT DATE:


W30 GL-7: NOT USED

2/9/2022 4:53:22
GL-8: NOT USED

SOLICITATION NO.:

SA-480530-1$-SA620DT.dwg
W37- ELEVATION W30 - ELEVATION W28 - ELEVATION W27 - ELEVATION

PM
CONTRACT NO.:
GL-9: BULLET RESISTANT GLAZING. GLAZING SHALL BE GLASS, PLASTIC OR

ISSUE DATE:
COMPOSITE WITH NO-SPALL PROTECTED INTERIOR FACE TO COMPLY
1 : 20 1 : 20 1 : 20 1 : 20 WITH THE SPECIFIED TEST STANDARD IN SPECIFICATION SECTION 08 34

1:1
02 BULLET-RESISTANT COMPONENTS

GL-10: 25 mm INSULATED GLASS UNIT, 20 MIN FIRE RATED, CLEAR, LOW-E

GL-11: ONE WAY VISION BULLET RESISTANT TINTED GLASS/PLASTIC AIR-GAP


GLAZING. GLAZING SHALL BE WITH NO-SPALL PROTECTED INTERIOR

FILE NO.:
FACE. GLAZING TO COMPLY WITH THE SPECIFIED TEST STANDARD IN
SPECIFICATION SECTION 08 34 02 BULLET-RESISTANT COMPONENTS.

SUBMITTED BY:
J. BLANCHARD

J. HOLLAND
DESIGN BY:

DRAWN BY:
GL-12: BULLET RESISTANT TINTED GLASS/PLASTIC AIR-GAP GLAZING. GLAZING

A. HANKS
D

S. OKES
CKD BY:
2970 2970 SHALL BE WITH NO-SPALL PROTECTED INTERIOR FACE. GLAZING TO

ANSI D
SIZE:
COMPLY WITH THE SPECIFIED TEST STANDARD IN SPECIFICATION
EQ EQ EQ EQ SECTION 08 34 02 BULLET-RESISTANT COMPONENTS.

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
GL-5 GL-5 GL-2 GL-2 GL-2
GL-5

DOOR WIDTH AS SCHEDULED


DOOR WIDTH AS SCHEDULED
600
C

DOOR HEIGHT AS SCHEDULED

DOOR HEIGHT AS SCHEDULED


GL-2
GL-5
GL-5 GL-2
3600

3600

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


1800

GL-12

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA

WINDOW TYPES, W24 - W30


STANDARD DETAILS
SA-480530
B

GRAPHIC SCALES
600

600
600

GL-12 GL-5 GL-5 GL-2 GL-2


W29

W26 W25
2/9/2022 4:53:22 PM

BULLET RESISTANT
STEEL WINDOW
A 0 400 800 1.6M
SHEET ID
W29 - ELEVATION W26 - ELEVATION (INTERIOR) W25 - ELEVATION SCALE: 1:20 $
1 : 20 1 : 20 1 : 20
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA620
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
G

DATE
90mm METAL FRAMING

40mm CURVED METAIL


REFER TO RCP OR ELEVATION

15 mm GWB ON METAL FRAMING


STUDS - SEE RCP

DESCRIPTION
15mm GWB ON 40mm
F CURVED METAL
SINGLE ROLLER SHADE
CEILING ATTACHMENT
5mm SHADOW GAP STUDS HARDWARE AS
VARIES

RECOMMENDED BY
15 mm GWB ON 65 mm 90mm METAL FRAMING MANUFACTURER

REFER TO RCP
PARTITION AND WALL METAL STUDS - SEE
COVE LIGHT REFER TO

VARIES
FINISH AS SCHEDULED RCP
E SERIES FOR DETAILS
5mm METAL 'W' SHAPED FASCIA TO CLOSELY
40mm METAL FRAMING MATCH WALL COLOR
ALIGN FACE OF SHADOW GAP
GWB W/ CABINET
ROLLER SHADE

150
20mm SHADOW GAP TRANSLUCENT
BETWEEN CASEWORK
AND GWB FURR DOWN.
VARIES STAINLESS STEEL
PAINT BLACK
REFER TO RCP CHAIN AS

MARK
FULL HEIGHT PLAM RECOMMENDED BY
DOOR WITH ROUTED 15 mm GWB ON 65 mm MANUFACTURER
SIDE FOR DOOR PULL METAL STUDS - SEE
E RCP
EQ EQ

PLOT SCALE: PLOT DATE:


2/9/2022 4:53:49
SECTION DETAIL - WARDROBE SOFFIT AT GWB GYP BULKHEAD @ MOSQUE SINGLE ROLLER SHADE WINDOW
E1 E4 E6

SOLICITATION NO.:

SA-480530-1$-SA630DT.dwg
PM
CONTRACT NO.:
SCALE: 1 : 10 SCALE: 1 : 10 SCALE: 1 : 5

ISSUE DATE:

1:1
KEYED LATCH

5.004 - COLD-FORMED METAL

S. DOUGLASHANSEN

FILE NO.:
FRAMING, SIZING PER
90mm METAL FRAMING

SUBMITTED BY:
MANUFACTURER SUSPENSION WIRE
RECOMMENDATIONS

DESIGN BY:

DRAWN BY:

C. BONHAM
SUSPENDED LAY-IN

A. HANKS
D

CKD BY:
J. KILBY
TO RCP OR ELEVATION
ACOUSTICAL CEILING -

ANSI D
WIDTH OF OPENING

SIZE:
SEE RCP

VARIES REFER
5mm METAL 'W' SHAPED
SHADOW GAP

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


PARTITION AND WALL
FINISH AS SCHEDULED

WINCHESTER, VA 22602
9.001 - 15 mm GYPSUM
WALLBOARD (TYPE "X" USED IN
FIRE-RATED ASSEMBLIES UNO) ALIGNS W/
SUSPENDED LAY-IN CEILING AS
CONSEALED FRAME ACOUSTICAL CEILING - SCHEDULED - COUNTERTOP
SEE RCP REFER TO RCP
WITH CASING BEAD 20mm SHADOW GAP
VARIES BETWEEN CASEWORK
8.006 - ACCESS DOOR AND FRAME 15 mm GWB ON METAL AND GWB FURR DOWN.
WITH GWB INSERT REFER TO RCP
STUDS - SEE RCP PAINT BLACK
CABINET REFER TO
C PIVOT HINGE ELEVATION

SECTION DETAIL - ACCESS HATCH IN GYP CEILING GYP BULKHEAD CABINET SOFFIT AT ACT CEILING
C1 SCALE: 1 : 10
C4 SCALE: 1 : 10
C7 SCALE: 1 : 10

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


TO STRUCTURE ABOVE TO STRUCTURE ABOVE

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
SUSPENSION WIRE

STANDARD DETAILS
SUSPENSION WIRE 90mm METAL FRAMING

CEILING DETAILS
@ 400 O.C.

SA-480530
B 90mm METAL FRAMING
REFER TO RCP

GRAPHIC SCALES
VARIES
REFER TO RCP

15 mm GWB ON METAL
STUDS - SEE RCP
VARIES

15 mm GWB ON METAL
SUSPENDED LAY-IN STUDS - SEE RCP
ACOUSTICAL CEILING -
SEE RCP TRANSITION MOLDING
0 100 200 400
15 mm GWB ON METAL
SUSPENDED LAY-IN
ACOUSTICAL CEILING -
STUDS - SEE RCP SCALE: 1:5
2/9/2022 4:53:49 PM

SEE RCP 15 mm GWB ON METAL


STUDS - SEE RCP
A 0 200 400 800
SHEET ID
SCALE: 1:10 $
ACT TO GWB TRANSITION GWB HEIGHT TRANSITION ACT TO GWB FLAT TRANSITION
A1 SCALE: 1 : 10
A4 SCALE: 1 : 10
A7 SCALE: 1 : 10
SA630
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
G

DATE
DESCRIPTION
F

8 GAUGE HANGER AT PERIMETER


SUPPORTING MAIN RUNNERS AND
CROSS RUNNERS 200mm MAXIMUM
FROM ALL WALLS - TYPICAL

50mm WALL ANGLE TRIM -


20 TYPICAL AT PERIMETER
0m
MA m 15mm GYPSUM BOARD
X.
CONCRETE SLAB,

MARK
90mm METAL FRAMING SEE S-SERIES 1
8 GAUGE HANGERS AT 1220mm ON
CENTER EACH WAY - TYPICAL
E

MAX.
10
22mm FURRING CHANNELS
12 AT 600mm ON CENTER

PLOT SCALE: PLOT DATE:


STAINLESS CABLE 20

2/9/2022 4:54:02
mm
15 mm GWB ON METAL B
STUDS - SEE RCP 90mm METAL FRAMING °
45

SOLICITATION NO.:

SA-480530-1$-SA631DT.dwg
PM
REFER TO

CONTRACT NO.:
RCP

ISSUE DATE:
15 mm GWB ON METAL mm
20
STUDS - SEE RCP 12 40mm COLD-ROLLED CHANNELS
B

1:1
REFER TO

AT 1220mm ON CENTER MAXIMUM


RCP

LA 8 GAUGE LATERAL BRACING WIRES


ON .. TE
m m RA 50mm MAXIMUM FROM MAIN and
6 0 LB
36 CE RA CROSS RUNNER INTERSECTION
AT MUM NT CIN
G I ER G EACH DIRECTION AT APPROXIMATELY
CIN MAX

FILE NO.:
300 A MA AT 45 DEGREES - LOCATE LATERAL
L BR TER XIM 366
A N UM 0mm

SUBMITTED BY:
15 mm GWB ON METAL R E BRACING AT 1220mm FROM WALL -
TE C
ON
STUDS - SEE RCP LA 3660mm ON CENTER EACH WAY

DESIGN BY:

DRAWN BY:
SUSPENDED GYPSUM BOARD

C. BONHAM

A. HANKS
D

M. STULL
CKD BY:
J. KILBY

ANSI D
SIZE:
SECTION DETAIL - GWB BULKHEAD TO GWB GYPSUM BOARD CEILING DETAIL - TYPICAL
D1 D6

TRANSATLANTIC MIDDLE EAST DISTRICT


SCALE: 1 : 10 SCALE: 1 : 10

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
C
NOTES:

1. GRID CEILING INSTALLATION APPLIES TO


600x600mm CONFIGURATION.
2. FIXTURES 26kg OR MORE SHALL BE
LIGHT FIXTURE - INDEPENDENTLY SUPPORTED FROM THE
SEE E-SERIES STRUCTURE ABOVE.

1
MAX.
POP RIVET ALL TEES TO WALL ANGLE

10
m

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


0m TYP.
40mm 20 GAUGE METAL 20 .
X
STUD COMPRESSION MA
m 12 GAUGE HANGER AT PERIMETER SUPPORTING
0m
STRUT -LATERAL BRACING 13 .

THAAD STANDARD FACILITIES


X MAIN RUNNERS AND CROSS RUNNERS 200mm
AT 3660mm ON CENTER MA

VARIOUS LOCATIONS, KSA


MAXIMUM FROM WALL - TYP.
MAXIMUM AND WITHIN mm
20

STANDARD DETAILS
1830mm OF EACH WALL 12

CEILING DETAILS
PAINTED (PNT-2) B 50mm WIDE WALL ANGLE TRIM (HORIZONTAL
ATTACHED TO mm RU CRO
CONCRETE SLAB, 50 de
g NN S S LEG) TYPICAL AT PERIMETER IN GRIDS LARGER

SA-480530
STRUCTURAL MEMBER 45 ER
RCP FOR HEIGHT

SEE S-SERIES TE THAN 13 SQ METERS


B ABOVE E
REFER TO

CAULK JOINT E ACOUSTIC CEILING PANEL - REFER TO


TE
ER FINISH SCHEDULE
NN
12 GAUGE LATERAL BRACING
WIRES 50mm MAXIMUM FROM 60
m m. . LA
TE
RA MA
IN
RU
12 GAUGE HANGERS AT 1220mm ON CENTER
GRAPHIC SCALES
36 ON LB
at U M
MAIN AND CROSS RUNNER IN
G IM CE
NT
RA
CIN
EACH WAY - TYPICAL
INTERSECTION EACH AC M AX ER G
B R R at
L E MA
15 mm GWB ON METAL DIRECTION AT APPROX. 45 RA N T X I
36
60 WITH HEAVY DUTY GRID SYSTEM; LIGHT
TE C E M U mm
STUDS - SEE RCP DEGREES - LOCATE LATERAL LA
ON M FIXTURES AND OTHER EQUIPMENT WEIGHING
BRACING AT 1830mm B FROM LESS THAN 13kg. TO BE SUPPORTED BY GRID
WALL AND 3660mm B EACH SYSTEM AND TWO 12 GA. HANGERS ATTACHED
WAY TO THE FIXTURE OR EQUIPMENT AT OPPOSITE
15 mm GWB ON METAL CORNERS (WIRES MAY BE SLACK)
STUDS - SEE RCP
2/9/2022 4:54:02 PM

A 0 200 400 800


SHEET ID
SECTION DETAIL - GWB TO STRUCT. SLAB CEILING GRID HANGING DETAIL - TYPICAL SCALE: 1:10 $
A1 SCALE: 1 : 10
A5 SCALE: 1 : 10
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA631
1 2 3 4 5 6 7 8 9 10
FINISH LEGEND - EXTERIOR GENERAL SHEET NOTES
SPEC
FINISH SECTION 1. REFER TO SHEET SG003 FOR ABBREVIATIONS.
NUMBER US Army Corps of
CODE SPEC SECTION TITLE EXTERIOR MATERIAL COLOR FINISH 2. REFER TO SHEET SA001 FOR GENERAL ARCHITECTURAL NOTES, LEGEND AND Engineers ®
CONC-A 03 30 00 CAST-IN-PLACE CONCRETE EXPOSED COATED EXTERIOR CONCRETE EXCEPT FLOOR, SLAB, AND PAVEMENT RAL 1001 ELASTOMERIC COATING SYMBOLS.
Middle East District
CONC-A 03 30 00 CAST-IN-PLACE CONCRETE EXPOSED COATED EXTERIOR CONCRETE EXCEPT FLOOR, SLAB, AND PAVEMENT RAL 1001 ELASTOMERIC COATING
G
APC-A 03 45 00 PRECAST ARCHITECTURAL CONCRETE COPINGS AND SPLASH BLOCKS RAL 1013 -

DATE
GFRC-A 03 49 00 GLASS-FIBER-REINFORCED CONCRETE (GFRC) EXTERIOR CAST GFRC RAL 1013 -

CMU-A 04 20 00 UNIT MASONRY EXPOSED COATED EXTERIOR CONCRETE UNIT MASONRY RAL 1001 ELASTOMERIC COATING

STL-A 05 12 00 STRUCTURAL STEEL EXTERIOR STEEL, BOLTS, NUTS, AND WASHERS RAL 8025 FIELD PAINTED GALVANIZED STEEL

MET-A 05 50 13 MISCELLANEOUS METAL FABRICATIONS EXTERIOR GRATINGS NA GALVANIZED STEEL


MET-B 05 50 13 MISCELLANEOUS METAL FABRICATIONS EXTERIOR BOLLARDS RAL 1018 SAFETY YELLOW FIELD PAINTED GALVANIZED STEEL
MET-C 05 50 13 MISCELLANEOUS METAL FABRICATIONS ROOF HATCHES (SCUTTLES) RAL 9003 FACTORY APPLIED POWDER COAT ON GALVANIZED STEEL
MET-D 05 50 13 MISCELLANEOUS METAL FABRICATIONS FLEXIBLE ARCHITECTURAL METAL MESH NA UNCOATED STAINLESS STEEL
MET-E 05 50 13 MISCELLANEOUS METAL FABRICATIONS RIGID ARCHITECTURAL METAL MESH NA UNCOATED STAINLESS STEEL

DESCRIPTION
ML-A 05 51 33 METAL LADDERS EXTERIOR LADDERS RAL 8025 FACTORY APPLIED POWDER COAT ON GALVANIZED STEEL
F ML-B 05 51 33 METAL LADDERS EXTERIOR SHIP'S LADDER RAL 8025 FACTORY APPLIED POWDER COAT ON GALVANIZED STEEL

RAIL-A 05 52 00 METAL RAILINGS EXTERIOR STEEL RAILINGS AND HANDRAILS RAL 8025 FIELD PAINTED GALVANIZED STEEL
RAIL-B 05 52 00 METAL RAILINGS SAFETY CHAINS NA GALVANIZED STEEL
RAIL-C 05 52 00 METAL RAILINGS SELF CLOSING SAFETY GATE RAL 1018 SAFETY YELLOW FACTORY APPLIED POWDER COAT ON GALVANIZED STEEL

EPDM-A 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING EPDM SHEET AND EPDM MEMBRANE FLASHINGS WHITE NA
EPDM-B 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING PRE-FABRICATED CURBS NA GALVANIZED STEEL
EPDM-C 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING BALLAST PAVERS - -
EPDM-D 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING STONE BALLAST - -

FLSH-A 07 60 00 FLASHING AND SHEET METAL REGLETS AND COUNTERFLASHINGS NA UNCOATED STAINLESS STEEL
FLSH-B 07 60 00 FLASHING AND SHEET METAL SCUPPERS, CONDUCTOR HEADS, AND DOWNSPOUTS RAL 8025 FACTORY APPLIED POLYVINYLIDENE FLUORIDE

MARK
SSMR-A 07 61 15.00 20 ALUMINUM STANDING SEAM ROOFING ROOFING PANEL AND EXPOSED ACCESSORIES NCS 3922-Y26R FACTORY APPLIED POLYVINYLIDENE FLUORIDE
E
SNT-A 07 92 00 JOINT SEALANTS EXTERIOR SEALANT JOINTS AROUND EXTERIOR DOORS AND WINDOWS AND FLASHINGS COLOR TO MATCH DOORS AND WINDOWS NA
SNT-B 07 92 00 JOINT SEALANTS EXTERIOR SEALANT JOINTS AROUND EXTERIOR EXHAUST LOUVERS AND FLASHINGS COLOR TO MATCH STUCCO NA

PLOT SCALE: PLOT DATE:


SNT-C 07 92 00 JOINT SEALANTS EXTERIOR SEALANT JOINTS AROUND EXTERIOR SAND LOUVERS AND FLASHINGS COLOR TO MATCH LOUVER NA

11:23:26 AM
SNT-D 07 92 00 JOINT SEALANTS EXTERIOR SEALANT JOINTS IN PRECAST COPINGS COLOR TO MATCH PRECAST NA

2/7/2022
SOLICITATION NO.:

SA-480530-1$-SA651GN.dwg
SNT-E 07 92 00 JOINT SEALANTS EXTERIOR SEALANTS IN FIELD OF STUCCO AND AT FIXTURES AND DEVICES PENETRATING STUCCO COLOR TO MATCH STUCCO NA

CONTRACT NO.:
ISSUE DATE:
DRFR-STL 08 11 13 STEEL DOORS AND FRAMES EXTERIOR DOORS AND FRAMES RAL 8025 FIELD PAINTED GALVANIZED STEEL

1:1
OHCD-A 08 33 23 OVERHEAD COILING DOORS OVERHEAD COILING DOOR RAL 8025 FACTORY APPLIED POWDER COAT

- 08 34 02 BULLET-RESISTANT COMPONENTS GLAZING AS SPECIFIED IN 08 34 02 NA


BLRS-A 08 34 02 BULLET-RESISTANT COMPONENTS BULLET RESISTANT STEEL DOORS, DOOR FRAMES, AND WINDOWS RAL 8025 FIELD PAINTED GALVANIZED STEEL

FILE NO.:
SUBMITTED BY:
DRFR-AL 08 41 13 ALUMINUM-FRAMED ENTRANCES AND RAL 8025 FACTORY APPLIED FLUOROPOLYMER RESIN

J. BLANCHARD

J. BLANCHARD
STOREFRONTS ALUMINUM FRAMES AND ENTRANCE DOORS

DESIGN BY:

DRAWN BY:

A. HANKS
D

E. OKES
CKD BY:

ANSI D
WDO-CW 08 44 00 CURTAIN WALL AND GLAZED ASSEMBLIES CURTAIN WALL FRAMING AND METAL ACCESSORIES RAL 8025 FACTORY APPLIED FLUOROPOLYMER RESIN

SIZE:
WDO-AL 08 51 13 ALUMINUM WINDOWS ALUMINUM WINDOWS AND METAL ACCESSORIES RAL 8025 FACTORY APPLIED FLUOROPOLYMER RESIN

TRANSATLANTIC MIDDLE EAST DISTRICT


- 08 71 00 DOOR HARDWARE EXTERIOR DOOR HARDWARE AS SPECIFIED IN 08 71 00 AS SPECIFIED IN 08 71 00

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
- 08 81 00 GLAZING EXTERIOR GLAZING AS SPECIFIED IN 08 81 00 NA

LVR-A 08 91 00 METAL WALL AND DOOR LOUVERS EXTERIOR METAL WALL LOUVERS RAL 8025 FACTORY APPLIED FLUOROPOLYMER RESIN
LVR-B 08 91 00 METAL WALL AND DOOR LOUVERS EXTERIOR OUTSIDE AIR INTAKE SAND RESISTANT LOUVERS NA UNCOATED STAINLESS STEEL

STU-A 09 24 23 CEMENT STUCCO STUCCO RAL 1001 SAND FINE


STU-MET 09 24 23 CEMENT STUCCO METAL ACCESSORIES NA UNFINISHED STAINLESS STEEL

FAB-A 13 31 23 TENSILE FABRIC STRUCTURE TENSILE FABRIC CANOPY RAL 1013, NATURAL UV STABILIZED CLOTH
C FAB-B 13 31 23 TENSILE FABRIC STRUCTURE TENSILE FABRIC CANOPY STRUCTURE RAL 1001 FACTORY APPLIED POWDER COAT ON GALVANIZED STEEL OR STAINLESS STEEL

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


THAAD STANDARD FACILITIES
VARIOUS LOCATIONS, KSA

EXTERIOR FINISH LEGEND


STANDARD DETAILS
SA-480530
B
2/7/2022 11:23:26 AM

A SHEET ID
$

SA651
1 2 3 4 5 6 7 8 9 10
PARTITION AND WALL PARTITION AND WALL
PARTITION AND WALL FINISH AS SCHEDULED
FINISH AS SCHEDULED
FINISH AS SCHEDULED
600 SEALANT - MATCH
F3 600 600 SOLID SURFACE COLOR
SCHEDULED F3

100
SA705 COUNTERTOP. REFER US Army Corps of

100
SA705

20
TO ELEVATION FOR SCHEDULED Engineers ®
SCHEDULED OPTIONAL BACKSPLASH COUNTERTOP. REFER
TO ELEVATION FOR Middle East District
COUNTERTOP. REFER
G OPTIONAL BACKSPLASH

150
F3

20
TO ELEVATION FOR

20
OPTIONAL BACKSPLASH SA705 SCHEDULED SINK AND
FULL EXTENSION FAUCET. HOLD TRAP AS

DATE
DRAWER RUNNER

20
CONCEALED EUROPEAN HIGH AS POSSIBLE
ELEVATION FOR HEIGHT

EQ

ELEVATION FOR HEIGHT

ELEVATION FOR HEIGHT


HINGES

20
PLAM DOOR FRONT CONCEALED EUROPEAN
HINGES
REFER TO

PLAM ADJUSTABLE

REFER TO

REFER TO
DRAWER FRONT
SHELF WITH 5mm SHELF PLAM DOOR FRONT

EQ
PINS @ 30mm O.C. PLAM ON ALL EXPOSED

20
PLAM ON ALL EXPOSED
EDGES AND SURFACES PLAM ON ALL EXPOSED EDGES AND SURFACES
ON THE INTERIOR AND EDGES AND SURFACES ON THE INTERIOR AND
EXTERIOR ON THE INTERIOR AND EXTERIOR
EXTERIOR
CONTINUOUS PLAM

EQ
BASE SCRIBED TO CONTINUOUS PLAM CONTINUOUS PLAM
FLOOR BASE SCRIBED TO BASE SCRIBED TO
FLOOR FLOOR

DESCRIPTION
SCHEDULED FLOORING
100

F SCHEDULED FLOORING SCHEDULED FLOORING

100
100
75
75 75

BASE CABINET - 4 DRAWERS BASE CABINET - DOOR BASE CABINET - SINK AND DOOR
F1 SCALE: 1 : 10
F4 SCALE: 1 : 10
F6 SCALE: 1 : 10

MARK
F3
E SA705
PARTITION AND WALL
FINISH AS SCHEDULED

PLOT SCALE: PLOT DATE:


2/9/2022 4:54:41
600
SCHEDULED

SOLICITATION NO.:

SA-480530-1$-SA701DT.dwg
PM
COUNTERTOP. REFER

CONTRACT NO.:
100

TO ELEVATION FOR

ISSUE DATE:
OPTIONAL BACKSPLASH
600

1:1
BRUSHED ALLUMINUM
900
20

CABINET GWB FURR DOWN


IDENTIFICATION RE: WHERE SHOWN ON
SIGNAGESPECIFICATION ELEVATION
GYP. BD. FURR DOWN
PACKAGE / TRASH AND AS SCHEDULED

ALIGN
RECYCLE SIGN
ELEVATION FOR HEIGHT

S. DOUGLASHANSEN

FILE NO.:
PLAM ON ALL EXPOSED

ALIGN
EDGES AND SURFACES

SUBMITTED BY:
ON THE INTERIOR AND 20mm SHADOW GAP
REFER TO

DESIGN BY:

DRAWN BY:

C. BONHAM
TRASH CAN AS EXTERIOR BETWEEN CASEWORK

A. HANKS
D SCHEDULED

CKD BY:
J. KILBY
DRAWER FRONT AND GWB FURR DOWN.

ANSI D
20mm SHADOW GAP

SIZE:
PAINT BLACK BETWEEN CASEWORK

540
FULL EXTENSION AND GWB FURR DOWN.
DRAWER RUNNER PAINT BLACK

TRANSATLANTIC MIDDLE EAST DISTRICT


PLAM ADJUSTABLE

US ARMY CORPS OF ENGINEERS


CONTINUOUS PLAM SHELF WITH 5mm SHELF

201 PRINCE FREDERICK DRIVE,


PARTITION AND WALL
BASE SCRIBED TO PINS @ 30mm O.C.
FINISH AS SCHEDULED

WINCHESTER, VA 22602
FLOOR
PLAM DOOR FRONT
SCHEDULED FLOORING SCHEDULED OFFSET
100

CONCEALED EUROPEAN
HEAVY DUTY PIVOT HINGES
MORTISED INTO
75 CABINET SIDE PANEL VERIFY F5
SEE A3/SA705 FOR

W/ EQUIPMENT
W/ EQUIPMENT SA705
DETAIL

VERIFY
FULL HEIGHT PLAM MICROWAVE AS
DOOR WITH ROUTED SCHEDULED
OR OPEN SHELF
C BASE CABINET - TRASH AND RECYCLING SIDE FOR DOOR PULL

C1 SCALE: 1 : 10
PARTITION AND WALL
FINISH AS SCHEDULED
2300

SCHEDULED OUTLET
MOUNTED IN PLASTIC

880
CONT. WD CLEATS
LAMINATE BACK

W/ EQUIPMENT
ATTACH CAB W/ MIN #10

2300
STS @ 450mm OC W/

VERIFY
PLASTIC CAPS MIN (2) MICROWAVE AS CONT. WD CLEATS
PER CAB SCHEDULED ATTACH CAB W/ MIN #10

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


GWB FURR DOWN STS @ 450mm OC W/
WHERE SHOWN ON PLASTIC CAPS MIN (2)

CASEWORK AND MILLWORK DETAILS


VERIFY W/ ELEVATION PER CAB

THAAD STANDARD FACILITIES


EQUIPMMENT DOOR / DRAWER PULL

VARIOUS LOCATIONS, KSA


ROUTED INTO DOOR /

STANDARD DETAILS
DRAWERS
BRUSHED ALLUMINUM

SA-480530
ALIGN

PLAM ADJUSTABLE CABINET


B SHELF WITH 5mm SHELF IDENTIFICATION RE:
PINS @ 30mm O.C. SIGNAGESPECIFICATION
VERIFY W/ EQUIP.

PACKAGE / TRASH AND


CONCEALED EUROPEAN 20mm SHADOW GAP RECYCLE SIGN
HINGES BETWEEN CASEWORK
PLAM ON ALL EXPOSED
DRAWER FRONT GRAPHIC SCALES

760
EDGES AND SURFACES
AND GWB FURR DOWN.
ON THE INTERIOR AND PLAM ON ALL EXPOSED
PAINT BLACK TRASH CAN AS
EXTERIOR EDGES AND SURFACES
PARTITION AND WALL SCHEDULED ON THE INTERIOR AND
FINISH AS SCHEDULED CONTINUOUS PLAM EXTERIOR
BASE SCRIBED TO
FLOOR FULL EXTENSION
PLAM DOOR FRONT
F5 DRAWER RUNNER
SCHEDULED FLOORING CONTINUOUS PLAM
SA705
100

PLAM ON ALL EXPOSED BASE SCRIBED TO


EDGES AND SURFACES WALL CAB MOUNTING FLOOR
ON THE INTERIOR AND HT AS INDICATED IN
SCHEDULED FLOORING
2/9/2022 4:54:41 PM

EXTERIOR ELEVATION 75
VERIFY W/ EQUIPMENT
A 0 200 400 800
SHEET ID
100

75
SCALE: 1:10 $
WALL CABINET - REFRIGERATOR CABINET - FULL HEIGHT SHELVING CABINET - MICROWAVE
A1 SCALE: 1 : 10
A4 SCALE: 1 : 10
A6 SCALE: 1 : 10 SA701
1 2 3 4 5 6 7 8 9 10

PARTITION AND WALL


FINISH AS SCHEDULED

US Army Corps of
70 REFER TO PLAN Engineers ®
Middle East District
600
G
PARTITION AND WALL
330 270 FINISH AS SCHEDULED

DATE
FRT WOOD FURRING

PLAM ON ALL EXPOSED


GWB FURR DOWN EDGES AND SURFACES
600 ON THE INTERIOR AND
WHERE SHOWN ON SCHEDULED
ELEVATION UNO COUNTERTOP. REFER EXTERIOR

100
TO ELEVATION FOR
20mm SHADOW GAP
OPTIONAL BACKSPLASH
BETWEEN CASEWORK
AND GWB FURR DOWN.
FRT WOOD FURRING
PAINT BLACK COUNTER TOP

1220
CONCEALED EUROPEAN SUPPORT @ 915mm OC
HINGES MAX. PAINT TO MATCH

ELEVATION FOR HEIGHT


ADJACENT PLAM. 16 GA MATTRESS BY OTHERS
PARTITION AND WALL
900

UNPUNCHED MTL STUD


FINISH AS SCHEDULED

DESCRIPTION
@ EACH STL ANGLE
F

REFER TO
PLAM DOOR FRONT BRACKET

PLAM ADJUSTABLE
SHELF WITH 5mm SHELF
PINS @ 30mm O.C. CONTINUOUS PLAM
BASE SCRIBED TO
PLAM ON ALL EXPOSED

60
FLOOR
EDGES AND SURFACES
ON THE INTERIOR AND
SCHEDULED FLOORING SCHEDULED FLOORING
EXTERIOR

100
WALL CAB MOUNTING
HT AS INDICATED IN
ELEVATION
50
F5
SA705

MARK
E
WALL CABINET OPEN COUNTERTOP DESK BEDROOM HEADBOARD
E1 E4 E7

PLOT SCALE: PLOT DATE:


2/9/2022 4:55:10
SCALE: 1 : 10 SCALE: 1 : 10 SCALE: 1 : 10

SOLICITATION NO.:

SA-480530-1$-SA702DT.dwg
PM
CONTRACT NO.:
ISSUE DATE:

1:1
650 650

GYP. BD. FURR DOWN GYP. BD. FURR DOWN


AS SCHEDULED AS SCHEDULED

S. DOUGLASHANSEN

FILE NO.:
ALIGN
ALIGN

SUBMITTED BY:
DESIGN BY:

DRAWN BY:

C. BONHAM
20mm SHADOW GAP 20mm SHADOW GAP

A. HANKS
D

CKD BY:
J. KILBY
BETWEEN CASEWORK BETWEEN CASEWORK

ANSI D
SIZE:
AND GWB FURR DOWN. AND GWB FURR DOWN.
PAINT BLACK PAINT BLACK
540
540

PLAM ADJUSTABLE

TRANSATLANTIC MIDDLE EAST DISTRICT


SHELF WITH 5mm SHELF
PINS @ 30mm O.C.

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WATER BOTTLE

WINCHESTER, VA 22602
WATER BOTTLE STORAGE
STORAGE
FULL HEIGHT PLAM
PARTITION AND WALL DOOR WITH ROUTED
FINISH AS SCHEDULED SIDE FOR DOOR PULL
FULL HEIGHT PLAM
EQ

DOOR WITH ROUTED PARTITION AND WALL


SIDE FOR DOOR PULL FINISH AS SCHEDULED

WATER COOLER AS PARTITION AND WALL


SCHEDULED OFFSET
C SCHEDULED
HEAVY DUTY PIVOT 70
FINISH AS SCHEDULED

FULL HEIGHT PLAM MORTISED INTO


DOOR WITH ROUTED CABINET SIDE PANEL
SIDE FOR DOOR PULL SEE A3/SA705 FOR FRT WOOD FURRING
EQ

DETAIL
CONT. WD CLEATS

150
2300
2300

ATTACH CAB W/ MIN #10


CONT. WD CLEATS BEDSIDE LIGHTING
STS @ 450mm OC W/
ATTACH CAB W/ MIN #10 MOUNTED BEHIND
PLASTIC CAPS MIN (2)
STS @ 450mm OC W/ HEADBOARD. REFER TO
PER CAB
VERIFY WITH EQUIP.

PLASTIC CAPS MIN (2) ELECTRICAL DRAWINGS

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


PER CAB
1620

PROVIDE CUTOUT IN
EQ

CASEWORK AND MILLWORK DETAILS


SCHEDULED OUTLET
DOOR FOR ACCESS

705
MOUNTED IN PLASTIC
290

THAAD STANDARD FACILITIES


TO WATER COOLER LAMINATE BACK

VARIOUS LOCATIONS, KSA


430
SCHEDULED OFFSET

STANDARD DETAILS
HEAVY DUTY PIVOT PLAM ON ALL EXPOSED
MORTISED INTO EDGES AND SURFACES

SA-480530
CABINET SIDE PANEL PLAM ADJUSTABLE ON THE INTERIOR AND
B

1220
SEE A3/SA705 FOR SHELF WITH 5mm SHELF EXTERIOR
VERIFY W/
EQ

DETAIL PINS @ 30mm O.C.

100

60
EQUIPMENT
SCHEDULED OUTLET
MOUNTED IN PLASTIC
LAMINATE BACK GRAPHIC SCALES
725

20
PLAM ON ALL EXPOSED PLAM ON ALL EXPOSED
EDGES AND SURFACES EDGES AND SURFACES
ON THE INTERIOR AND ON THE INTERIOR AND

300
EXTERIOR EXTERIOR CONTINUOUS PLAM

515
EQ

BASE SCRIBED TO
CONTINUOUS PLAM CONTINUOUS PLAM FLOOR

20
BASE SCRIBED TO BASE SCRIBED TO
FLOOR FLOOR
SCHEDULED FLOORING
SCHEDULED FLOORING

100
SCHEDULED FLOORING

60
100
100
2/9/2022 4:55:10 PM

A 100 100 50
0 200 400 800
SHEET ID
SCALE: 1:10 $
CABINET - WATER COOLER CABINET - WATER COOLER STORAGE BEDSIDE TABLE AND HEADBOARD SA702
A1 SCALE: 1 : 10
A4 SCALE: 1 : 10
A7 SCALE: 1 : 10
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

PLAM AS SCHEDULED
ON 16mm MDF
US Army Corps of
SUBSTRATE PAINTED
AS SCHEDULED Engineers ®
375 Middle East District
G WOOD BLOCKING

80

DATE
PARTITION AND WALL
FINISH AS SCHEDULED

500

420
WOOD BLOCKING

80

DESCRIPTION
F

900

820
SCHEDULED FLOORING

MARK
E

FLOATING SHELVES

PLOT SCALE: PLOT DATE:


2/9/2022 4:55:30
E6 SCALE: 1 : 10

SOLICITATION NO.:

SA-480530-1$-SA703DT.dwg
PM
CONTRACT NO.:
ISSUE DATE:

1:1
635
GWB FURR DOWN
WHERE SHOWN ON
GYP. BD. FURR DOWN GYP. BD. FURR DOWN ELEVATION
20

AS SCHEDULED AS SCHEDULED

ALIGN

S. DOUGLASHANSEN

FILE NO.:
PLAM ON ALL EXPOSED
SURFACES 550

SUBMITTED BY:
20mm SHADOW GAP

DESIGN BY:

DRAWN BY:

C. BONHAM
PARTITION AND WALL

A. HANKS
D BETWEEN CASEWORK
EQ
FINISH AS SCHEDULED PLAM ADJUSTABLE

CKD BY:
J. KILBY

ANSI D
SHELF WITH 5mm SHELF AND GWB FURR DOWN.

SIZE:
PINS @ 30mm O.C. PAINT BLACK

TV AS SCHEDULED; PLAM ADJUSTABLE

TRANSATLANTIC MIDDLE EAST DISTRICT


PROVIDE BLOCKING SHELF WITH 5mm SHELF
AS NEEDED PINS @ 30mm O.C.

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


PARTITION AND WALL PARTITION AND WALL

WINCHESTER, VA 22602
FINISH AS SCHEDULED FINISH AS SCHEDULED
EQ

LINE OF BOOKSHELF
BEHIND SCHEDULED OFFSET
HEAVY DUTY PIVOT
1390

MORTISED INTO
1370

CABINET SIDE PANEL


SEE A3/SA705 FOR
DETAIL
CONT. WD CLEATS 550
ATTACH CAB W/ MIN #10
EQ

MIN. 30mm CLOTHES ROD


STS @ 450mm OC W/
C CONT. WD CLEATS PLASTIC CAPS MIN (2)
ATTACH CAB W/ MIN #10 450 PER CAB FULL HEIGHT PLAM
STS @ 450mm OC W/ DOOR WITH ROUTED
PLASTIC CAPS MIN (2) SIDE FOR DOOR PULL
PER CAB

2300
F3
SCHEDULED SCHEDULED
CONT. WD CLEATS
EQ

COUNTERTOP. REFER SA705 COUNTERTOP. REFER


ATTACH CAB W/ MIN #10
TO ELEVATION FOR TO ELEVATION FOR
640 600 STS @ 450mm OC W/
OPTIONAL BACKSPLASH OPTIONAL BACKSPLASH
PLASTIC CAPS MIN (2)

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


PER CAB
F3

CASEWORK AND MILLWORK DETAILS


SA705

1640

THAAD STANDARD FACILITIES


CONCEALED EUROPEAN

VARIOUS LOCATIONS, KSA


CONCEALED EUROPEAN
HINGES HINGES

STANDARD DETAILS
630 PLAM ADJUSTABLE PLAM ADJUSTABLE PLAM ON ALL EXPOSED
630

SA-480530
SHELF WITH 5mm SHELF SHELF WITH 5mm SHELF EDGES AND SURFACES
B PINS @ 30mm O.C. PINS @ 30mm O.C. ON THE INTERIOR AND
EXTERIOR
PLAM DOOR FRONT PLAM DOOR FRONT
810

810

GRAPHIC SCALES
910

910

PLAM ON ALL EXPOSED PLAM ON ALL EXPOSED


EDGES AND SURFACES EDGES AND SURFACES
ON THE INTERIOR AND ON THE INTERIOR AND
EXTERIOR EXTERIOR
CONTINUOUS PLAM
CONTINUOUS PLAM CONTINUOUS PLAM BASE SCRIBED TO
BASE SCRIBED TO BASE SCRIBED TO FLOOR
FLOOR FLOOR

SCHEDULED FLOORING SCHEDULED FLOORING SCHEDULED FLOORING


100
100

100
2/9/2022 4:55:30 PM

75 75 100
A 0 200 400 800
SHEET ID
SCALE: 1:10 $
CABINET - LOUNGE TELEVISION CABINET - LOUNGE BOOKSHELF CABINET - WARDROBE
A1 SCALE: 1 : 10
A4 SCALE: 1 : 10
A6 SCALE: 1 : 10
UNLESS OTHERWISE NOTED, LINEAR SA703
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
G WALL FINISH AS
SCHEDULED 90mm METAL FRAMING
PT-3

DATE
CONCEALED WALL
MOUNTED PAPER
TOWEL DISPENSER PT-3
PT-3 CONCEALED WALL

400

400
15mm METAL L-SHAPED MOUNTED PAPER
TILE CORNER TRIM @ TOWEL DISPENSER
OUTSIDE CORNER
1200

PT-4
15mm METAL L-SHAPED
PT-3 TILE CORNER TRIM @
OUTSIDE CORNER
15mm METAL L-SHAPED
TILE CORNER TRIM @ PT-3
OUTSIDE CORNER

DESCRIPTION
400

400
F PT-3
PT-4
MIRROR AS SCHEDULED PT-3
WALL MOUNTED SOAP
DISPENSER 15mm METAL L-SHAPED
FAUCET AS SPECIFIED TILE CORNER TRIM @
OUTSIDE CORNER
SS-2 CUSTOM
THERMOFORMED SOLID
STEEL ANGLE SURFACE SEAT; MARINE
PLYWOOD BACKING FAUCET AS SPECIFIED
6mm PORCELAIN BEYOND FOR SUPPORT
STONEWARE ON 20mm AS REQUIRED
POLYSTYRENE CORE
300

WASHBASIN. REFER TO 550 400 WALL MOUNTED SOAP


PLUMBING DISPENSER

50
DRAIN AND PIPING SEE

MARK
50
P-SERIES DRAWINGS LINEAR DRAIN AS 90mm METAL FRAMING

1055

1055
SPECIFIED WITH 13mm
E CONCEALED EUROPEAN
ADJUSTABLE TILE
GRATE AND ANCHOR LINEAR DRAIN AS
HINGES
SUPPORTS SPECIFIED WITH 13mm
50

600
415

PLOT SCALE: PLOT DATE:


2/9/2022 4:55:55
CONTINUOUS 19-25mm ADJUSTABLE TILE
SQUARE STEEL TUBES PT-6 GRATE AND ANCHOR
SPACED 305mm MAX. OF SUPPORTS

SOLICITATION NO.:

SA-480530-1$-SA704DT.dwg
CENTER 250 500 250 120

PM
CONTRACT NO.:
PT-8

ISSUE DATE:
SCHEDULED SOLID

175
LAMINATE, ALL

1:1
SURFACES U.N.O.

80
50
VERIFY DEPTH
300

W/ SINK

40
SCHEDULED FLOORING

S. DOUGLASHANSEN

FILE NO.:
L3S0.F L3S0.F 75

SUBMITTED BY:
295 625

DESIGN BY:

DRAWN BY:

C. BONHAM

A. HANKS
D

CKD BY:
J. KILBY

ANSI D
SIZE:
CABINET - PRIVATE RESTROOM SINK ABLUTION ABLUTION - ACCESSIBLE
D1 D3 D6

TRANSATLANTIC MIDDLE EAST DISTRICT


SCALE: 1 : 10 SCALE: 1 : 10 SCALE: 1 : 10

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
5mm GROUT AS
SCHEDULED
GWB FURR DOWN 10mm TILE AS
WHERE SHOWN ON SCHEDULED
C PARTITION AND WALL
ELEVATION

FINISH AS SCHEDULED
WATER HEATER, SEE P-
600 SERIES FOR MORE
SCHEDULED DETAILS CONSTRUCTION
COUNTERTOP. REFER ADHESIVE
TO ELEVATION FOR
OPTIONAL BACKSPLASH 20mm SHADOW GAP
BETWEEN CASEWORK MANUFACTURER
AND GWB FURR DOWN. RECOMMENDED
PAINT BLACK FASTENER

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


CONCEALED EUROPEAN

CASEWORK AND MILLWORK DETAILS


PROVIDE METAL HINGES
SUPPORTS AS NEEDED CONCRETE

THAAD STANDARD FACILITIES


CL
ELEVATION FOR HEIGHT

VARIOUS LOCATIONS, KSA


PARTITION AND WALL MASONRY UNIT
FINISH AS SCHEDULED TOILET PARTITION

STANDARD DETAILS
VERIFY
REFER TO

WITH EQUIP.

SA-480530
PLAM DOOR FRONT
B PLAM ON ALL EXPOSED
EDGES AND SURFACES
MANUFACTURER
RECOMMENDED
ON THE INTERIOR AND PLAM ON ALL EXPOSED FASTENER
EXTERIOR EDGES AND SURFACES
ON THE INTERIOR AND
EXTERIOR PHENOLIC WOOD GRAPHIC SCALES
TOILET PARTITION. SEE
SPECS.

F5 WALL CAB MOUNTING


SCHEDULED FLOORING 10mm TILE AS
HT AS INDICATED IN METAL EDGING
SCHEDULED
SA705 ELEVATION
5mm GROUT AS
SCHEDULED 0 6M 12M 24M

SCALE: 1:300
2/9/2022 4:55:55 PM

A 0 200 400 800


SHEET ID
BEDROOM DESK WALL CABINET - WATER HEATER PLAN - PHENOLIC WOOD PARTITION JOINING
A1 SCALE: 1 : 10
A3 SCALE: 1 : 10
A6 SCALE: 1 : 2 SCALE: 1:10 $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA704
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
450 5
COUNTERTOP AS Middle East District
G SCHEDULED PLAM ON ALL EXPOSED
GYP. BD. FURR DOWN SURFACES

20
AS SCHEDULED

DATE
SILENCERS

ALIGN

20
DOOR / DRAWER PULL
ROUTED INTO DOOR /
DRAWERS PLAM DOOR FRONT
20mm SHADOW GAP
300

BETWEEN CASEWORK
AND GWB FURR DOWN. SILENCERS
PAINT BLACK
WOOD BLOCKING

13 mm RADIUS ROUTED
FINGER PULL
300

PARTITION AND WALL


FINISH AS SCHEDULED

DESCRIPTION
F
DOOR/DRAWER PULL FINGER PULL J BAR FOR MIRROR

F3 SCALE: 1 : 2
F5 SCALE: 1 : 2
RAILING
300

MIRROR ADHESIVE

CONT. WD CLEATS
ATTACH CAB W/ MIN #10
2030

STS @ 450mm OC W/
PLASTIC CAPS MIN (2)
PER CAB
300

PARTITION AND WALL MIRROR, REFER TO


PARTITION AND WALL FINISH AS SCHEDULED
FINISH AS SCHEDULED ELEVATION FOR
DIMENSIONS

MARK
50mm HIGH DENSITY
PLAM ADJUSTABLE 50mm HIGH DENSITY FOAM CUSHION WITH
SHELF WITH 5mm SHELF FOAM CUSHION WITH SLIP RESISTANT
E PINS @ 30mm O.C. SLIP RESISTANT BOTTOM. REFER TO MIRROR, REFER TO
BOTTOM. REFER TO ELEVATION FOR ELEVATION FOR
300

450 10 ELEVATION FOR


450 10
UPHOLSTERY DIMENSIONS

PLOT SCALE: PLOT DATE:


2/9/2022 4:56:20
UPHOLSTERY
50

50
FINISH AS INDICATED
40 ON ELEVATION ON ALL

125 40 125 40

SOLICITATION NO.:
PLAM ON ALL EXPOSED

SA-480530-1$-SA705DT.dwg
FINISH AS INDICATED EXPOSED EDGES AND

PM
CONTRACT NO.:
EDGES AND SURFACES ON ELEVATION ON ALL SURFACES ON THE
ON THE INTERIOR AND

ISSUE DATE:
EXPOSED EDGES AND INTERIOR AND
EXTERIOR SURFACES ON THE
350

350
EXTERIOR
290

1:1
INTERIOR AND
300

CONTINUOUS PLAM EXTERIOR ADJUSTABLE SHELF


BASE SCRIBED TO WITH 5mm SHELF PINS MIRROR ADHESIVE
FLOOR @ 32mm O.C.
SCHEDULED FLOORING
SCHEDULED FLOORING
100

100

S. DOUGLASHANSEN
SCHEDULED FLOORING

FILE NO.:
100

J BAR FOR MIRROR

SUBMITTED BY:
RAILING
75 75

DESIGN BY:

DRAWN BY:

C. BONHAM
75

A. HANKS
D

CKD BY:
J. KILBY

ANSI D
450 450

SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
SHOE CABINET SHOE BENCH - ONE SHELF SHOE BENCH - TWO SHELVES MIRROR MOUNTING

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


D1 D3 D5 D7

WINCHESTER, VA 22602
SCALE: 1 : 10 SCALE: 1 : 10 SCALE: 1 : 10 SCALE: 1 : 5

PARTITION AND WALL


FINISH AS SCHEDULED

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


CMU AS SCHEDULED

CASEWORK AND MILLWORK DETAILS


SCHEDULED OFFSET
HEAVY DUTY PIVOT

THAAD STANDARD FACILITIES


MORTISED INTO

VARIOUS LOCATIONS, KSA


CABINET SIDE PANEL CMU AS SCHEDULED

STANDARD DETAILS
SEE A3/SA705 FOR WALL TILE, GROUT AND
DETAIL MORTAR AS
WALL TILE, GROUT AND SCHEDULED

SA-480530
MORTAR AS
B PLAM DOOR FRONT SCHEDULED
CAULK JOINT
10 5
GRAPHIC SCALES

5
0 6M 12M 24M

10
8mm METAL TILE
CORNER TRIM @ SCALE: 1:300
OUTSIDE CORNER
0 100 200 400

SCALE: 1:5
2/9/2022 4:56:20 PM

A 0 200 400 800


SHEET ID
PIVOT MORTISED HINGE TILE CORNER - INSIDE TILE CORNER - OUTSIDE
A3 SCALE: 1 : 10
A5 SCALE: 1 : 2
A7 SCALE: 1 : 2 SCALE: 1:10 $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SA705
1 2 3 4 5 6 7 8 9 10

GENERAL NOTES THIS SHEET:


A. REFER TO SHEET SI601 IN THE SFDN PACKAGE FOR FINISH INFORMATION.
US Army Corps of
Engineers ®
Middle East District
G
REFER TO

DATE
PLANS FOR DIM

EDGE OF DOOR EDGE OF FRAME


AND FRAME
DOOR AS OCCURS, RESILIENT FLOORING TILE
THR-1 SHOWN DASHED
EDGE OF DOOR
FLOOR TILE AND GROUT FLOOR TILE AND GROUT FRAME
AS SCHEDULED THR-1
AS SCHEDULED FLOOR TILE AND GROUT
DOOR AS OCCURS, AS SCHEDULED
UNCOUPLING MORTOR BED SHOWN DASHED MORTOR BED
MEMBRANE

DESCRIPTION
UNCOUPLING
F UNCOUPLING
MEMBRANE
RESILIENT FLOORING MEMBRANE
FINISH AS SCHEDULED
PORTLAND CEMENT
FLOOR 13mm
FINISH
FLOOR

T.O T.O
SLAB SLAB
CONCRETE SLAB SELF LEVELING
SELF LEVELING SCREED SCREED

TILE TO TILE TRANSITION WITH THR-1 RESILIENT FLOORING TO TILE TRANSITION WITH THR-1

MARK
E1 1:5 E5 1:5
E

PLOT SCALE: PLOT DATE:


9:30:49 AM
2/22/2022
SOLICITATION NO.:

SA-480530-1$-SI501DT.dwg
CONTRACT NO.:
ISSUE DATE:

1:1
CL
TILE TILE

SEALED CONCRETE TILE TRANSITION OF TWO DIFFERENT TILE FINISHES


CENTERLINE OF DOOR
TO BE CENTERED UNDER DOOR, OR ROOM

S. DOUGLASHANSEN

FILE NO.:
DOOR AS OCCURS, OPENING. NO TRANSITION PIECE REQUIRED
SHOWN DASHED BETWEEN TILE FINISHES OF SAME HEIGHT DOOR AS OCCURS,

SUBMITTED BY:
CENTERLINE
OF DOOR SHOWN DASHED
FLOOR TILE AND GROUT

DESIGN BY:

DRAWN BY:
FLOOR TILE AND GROUT

C. BONHAM

A. HANKS
D AS SCHEDULED AS SCHEDULED FLOOR TILE AND GROUT

CKD BY:
J. KILBY
METAL EDGING

ANSI D
AS SCHEDULED

SIZE:
MORTOR BED MORTOR BED
SEALED CONCRETE AS
UNCOUPLING UNCOUPLING UNCOUPLING
SCHEDULED
MEMBRANE MEMBRANE MEMBRANE
FINISH

TRANSATLANTIC MIDDLE EAST DISTRICT


PORTLAND CEMENT FLOOR
10mm

US ARMY CORPS OF ENGINEERS


FINISH

201 PRINCE FREDERICK DRIVE,


FLOOR

WINCHESTER, VA 22602
T.O T.O
SLAB SLAB
CONCRETE SLAB SELF LEVELING
SCREED

SEALED CONCRETE TO TILE TRANSITION TILE TO TILE TRANSITION


C C1 1:5 C5 1:5

CL

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


RESILIENT FLOORING SEALED CONCRETE RESILIENT FLOORING TILE

TYPICAL FLOOR TRANSITION DETAILS


THAAD STANDARD FACILITIES
RUBBER REDUCER

VARIOUS LOCATIONS, KSA


CENTERLINE OF DOOR CENTERLINE OF FLOOR TILE AND GROUT

STANDARD DETAILS
DOOR AS OCCURS, TRANSITION
SHOWN DASHED AS SCHEDULED
DOOR AS OCCURS,

SA-480530
MORTOR BED
RUBBER REDUCER SHOWN DASHED
B SEALED CONCRETE AS UNCOUPLING
RESILIENT FLOORING SCHEDULED RESILIENT FLOORING
AS SCHEDULED MEMBRANE
AS SCHEDULED
PORTLAND CEMENT
T.O. T.O 13mm FINISH GRAPHIC SCALES
SLAB SLAB FLOOR

T.O
SLAB
CONCRETE SELF- LEVELING
SLAB SCREED
2/22/2022 9:30:49 AM

RESILIENT FLOORING TO
A 0 100 200 400
SEALED CONCRETE TRANSITION RESILIENT FLOORING TO TILE TRANSITION SHEET ID
A1 1:5 A5 1:5 SCALE: 1:5 $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SI501
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
G

DATE
600

DESCRIPTION
F
150

300

ALIGN
150
ALIGN

MARK
E
SQUARE DRAIN TRANSITION
E7

PLOT SCALE: PLOT DATE:


600 1:5

9:30:57 AM
2/22/2022
SOLICITATION NO.:

SA-480530-1$-SI502DT.dwg
CONTRACT NO.:
ISSUE DATE:

1:1
GROUT AS SCHEDULED CL CL
300

WITH TILE TILE FLOOR MAT FLOOR MAT TILE


220

S. DOUGLASHANSEN

FILE NO.:
LINEAR DRAIN REFER

SUBMITTED BY:
ALIGN TO PLUMBING

DESIGN BY:

DRAWN BY:

C. BONHAM
DRAWINGS FLOOR TILE AND GROUT CENTERLINE OF FLOOR TILE AND GROUT

A. HANKS
D

CKD BY:
J. KILBY
AS SCHEDULED TRANSITION AS SCHEDULED

ANSI D
SIZE:
UNCOUPLING FLOORING MAT AS
SCHEDULED UNCOUPLING
68

MEMBRANE MEMBRANE

TRANSATLANTIC MIDDLE EAST DISTRICT


STAINLESS STEEL TRAY

US ARMY CORPS OF ENGINEERS


1° AND DRAIN

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
GROUT AS SCHEDULED
150

ALIGN WITH TILE

EQ EQ

600 SHOWER HEAD


CENTERED ABOVE

PLAN VIEW - LINEAR DRAIN TRANSITION TILE TO FLOOR MAT TO TILE TRANSITION
C2 1:5 C6 1:5

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)

TYPICAL FLOOR TRANSITION DETAILS


THAAD STANDARD FACILITIES
ENTRY FLOORING TILE SEALED CONCRETE TILE

VARIOUS LOCATIONS, KSA

STANDARD DETAILS
LINEAR DRAIN AS DOOR AS OCCURS, EDGE OF DOOR EDGE OF DOOR
TILE INSERT TO SHOWN DASHED FRAME
SPECIFIED WITH 13mm AND FRAME
MATCH ADJACENT FLOOR TILE AND GROUT

SA-480530
ADJUSTABLE TILE FLOOR TILE AND GROUT
FLOOR RECESSED METAL DOOR AS OCCURS, AS SCHEDULED
B GRATE AND ANCHOR
SUPPORTS
FRAME AS SCHEDULED SHOWN DASHED
INTRABRUSH INSERT MORTOR BED MORTOR BED
THR-1
FLOOR TILE AND GROUT UNCOUPLING UNCOUPLING
FIXING TO SUBFLOOR
AS SCHEDULED MEMBRANE SEALED CONCRETE AS
MEMBRANE
GRAPHIC SCALES
UNCOUPLING LATEX UNDER LAYER PORTLAND CEMENT SCHEDULED PORTLAND CEMENT
MEMBRANE FINISH 28mm FINISH 10mm

FLOOR FLOOR

T.O
T.O SLAB
SLAB CONCRETE SELF- LEVELING
SELF LEVELING SLAB SCREED
2/22/2022 9:30:57 AM

SCREED

A 0 100 200 400


SHEET ID
SCALE: 1:5 $
SHOWER DRAIN TRANSITION ENTRY FLOORING TO TILE TRANSITION SC-1 TO PORCELAIN TILE WITH THR-1
A1 1:5 A3 1:5 A6 1:5 UNLESS OTHERWISE NOTED, LINEAR SI502
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
G

DATE
PARTITION AND WALL
PARTITION AND WALL FINISH AS SCHEDULED
FINISH AS SCHEDULED
METAL ROUNDED TRIM
TOPPER

DESCRIPTION
F TILE BASE AS
SCHEDULED
SCHEDULED METAL SEALANT
WALL BASE CHANNEL
PROFILE
FLOOR TILE AND GROUT
AS SCHEDULED
SEALED CONCRETE AS

100
SCHEDULED UNCOUPLING

100
MEMBRANE

MARK
E

PLOT SCALE: PLOT DATE:


9:31:08 AM
MTB-1 AT SEALED CONC TILE BASE AT TILE FLOOR

2/22/2022
SOLICITATION NO.:
E4 E7

SA-480530-1$-SI503DT.dwg
CONTRACT NO.:
1:5 1:5

ISSUE DATE:

1:1
PARTITION AND WALL

FILE NO.:
FINISH AS SCHEDULED WALL TILE AND GROUT
AS SCHEDULED

SUBMITTED BY:
DESIGN BY:

DRAWN BY:

C. BONHAM
WALL PROTECTION AS

A. HANKS
M. STULL
D SCHEDULED SEALANT

CKD BY:
J. KILBY

ANSI D
SIZE:
SCHEDULED RESILIENT
INTEGRAL WALL BASE FLOOR TILE AND GROUT
WITH FILLET STRIP AS SCHEDULED

TRANSATLANTIC MIDDLE EAST DISTRICT


RESILIENT FLOORING UNCOUPLING

US ARMY CORPS OF ENGINEERS


MEMBRANE

201 PRINCE FREDERICK DRIVE,


AS SCHEDULED

WINCHESTER, VA 22602
100

INTEGRAL BASE AT RES FLOOR WALL TILE AT FLOOR TILE


C4 1:5 C6 1:5

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


THAAD STANDARD FACILITIES
VARIOUS LOCATIONS, KSA
PARTITION AND WALL PARTITION AND WALL

WALL BASE DETAILS


STANDARD DETAILS
FINISH AS SCHEDULED FINISH AS SCHEDULED

SCHEDULED METAL

SA-480530
WALL BASE CHANNEL
B SCHEDULED RUBBER
WALL BASE - COVED
PROFILE
PROFILE AT RESILIENT RECESSED METAL
FLOORING FRAME

FIXING TO SUBFLOOR GRAPHIC SCALES


RESILIENT FLOORING INTRABRUSH INSERT
AS SCHEDULED

100
LATEX UNDER LAYER
100

19
2/22/2022 9:31:08 AM

A 0 100 200 400


SHEET ID
SCALE: 1:5 $
RBR AT RESILIENT FLOORING MTB-1 AT ENTRY FLOORING
A4 1:5 A7 1:5
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SI503
1 2 3 4 5 6 7 8 9 10
INTERIOR FINISH LEGEND GENERAL SHEET NOTES
FINISH SPEC
CODE SECTION CODE DESCRIPTION MATERIAL TYPE MANUFACTURER PRODUCT STYLE/DESCRIPTION COLOR SIZE ALTERNATE COMMENTS 1. COLOR / PATTERN / STYLE LISTED IN THE FINISH LEGEND IS NOT INTENDED
TO LIMIT THE SELECTION OF EQUAL COLOR / PATTERN / STYLE OF OTHER US Army Corps of
ACT-1 09 51 00 ACOUSTICAL CEILING ACOUSTICAL CEILING TILE KNAUF ARMSTRONG OPTIMA WITH 15/90 TEGULAR EDGE, EXPOSED TEE SYSTEM WHITE 600mm x 600mm USG, CERTAINTEED 0.95 NRC; GENERAL ACT MANUFACTURERS. MANUFACTURERS LISTED ARE TO SHOW DESIGN INTENT. Engineers ®
ACT-2 09 51 00 ACOUSTICAL CEILING ACOUSTICAL CEILING TILE KNAUF ARMSTRONG OPTIMA WITH 15/90 TEGULAR EDGE, EXPOSED TEE SYSTEM WHITE 600mm x 1200mm USG, CERTAINTEED 0.95 NRC
ACT-3 09 51 00 ACOUSTICAL CEILING ACOUSTICAL CEILING TILE KNAUF ARMSTRONG OPTIMA WITH 15/90 TEGULAR EDGE, EXPOSED TEE SYSTEM WHITE 600mm x 1800mm USG, CERTAINTEED 0.95 NRC 2. IN AREAS WHERE NO BASE IS REQUIRED BETWEEN SEALED CONCRETE AND Middle East District
G ACT-4 09 51 00 ACOUSTICAL CEILING ACOUSTICAL CEILING TILE KNAUF ARMSTRONG 673 KITCHEN ZONE, 15/16 SQUARE LAY-IN, PRELUDE, SMOOTH TEXTURE WHITE 600mm x 600mm USG, CERTAINTEED DIFA KITCHEN WALLS; PROVIDE SEALANT. SEE SPECIFICATIONS FOR FURTHER
INFORMATION.
ACT-5 09 51 00 ACOUSTICAL CEILING ACOUSTICAL CEILING TILE KNAUF ARMSTRONG TECTUM DIRECT ATTACH; BEVELED/SQUARE EDGE WHITE 1220mm x 2440mm x USG, CERTAINTEED 0.85 NRC
50mm THICK
3. PAINT GYP. BOARD CEILINGS, BULKHEADS AND SOFFITS PNT-2, UNO.

DATE
CG-1 10 26 00 CORNER GUARD METAL CORNER GUARD CS GROUP CO-8 STAINLESS STEEL 89mm LEGS x 2440 INPRO, PAWLING
HIGH 4. PAINT INTERIOR HOLLOW METAL DOORS AND FRAMES PNT-7, UNO.
EMF-1 12 48 13 WALK-OFF ENTRY MAT ENTRY FLOORING GRID INTRA SYSTEMS INTRAForm; CASSETTE BRUSH, FINE BRUSH SILVER WITH BLACK REFER TO PLANS CS GROUP, MATS INC.
INSERT
FA-1 09 30 10 FINISHING ACCESSORY METAL TILE EDGE PROFILE SCHLUTER INDEC OUTSIDE CORNER 90 IN 100 AE 10mm H FRY REGLET,
FM-1 12 48 13 FLOOR MAT RECESSED FLOORING MAT MATSINC. SOFT GRID BLACK 9.5mm THICK CS GROUP, MATS INC. TO BE INSTALLED WITH J-FRAME
GLF-1 08 87 33 GLASS FILM POLYVINYL CHLORIDE (PVC) 3M CRYSTAL GLASS FINISHES, ETCHED GLASS FILMS FROSTED GLASS 4.7mil THICK DECORATIVE FILM,
ARCHITECTURAL WINDOW FILM
GWB-1 09 29 00 GYPSUM CEILING GYPSUM BOARD CEILING USG GYPSUM WALL BOARD PAINT PNT-2 CERTAINTEED, NATIONAL
GYPSUM
GWB-2 09 29 00 GYPSUM CEILING MOISTURE RESISTANT GYPSUM BOARD USG GYPSUM WALL BOARD PAINT PNT-2E CERTAINTEED, NATIONAL
CEILING GYPSUM
LK-1 10 51 13 LOCKER METAL LOCKERS HALLOWELL METAL SINGLE TIER LOCKER WITH SLOPED TOPS AND CLOSED BOTTOMS TAN 300mm x 457mm x GLOBAL INDUSTRIAL,

DESCRIPTION
1830mm SALSBURY
F MKBD-1 10 11 00 MARKERBOARD DRY ERASE BOARD QUARTET PORCELAIN MARKERBOARD, MAGNETIC #SM534 WHITE 1220mm x 915 mm GLOBAL INDUSTRIAL, ULINE
MKBD-2 10 11 00 MARKERBOARD DRY ERASE BOARD QUARTET PORCELAIN MARKERBOARD, MAGNETIC #SM538 WHITE 1220mm x 2440mm GLOBAL INDUSTRIAL, ULINE
MT-1 08 11 13 METAL STAINLESS STEEL DOOR AND FRAME -- -- #4 BRUSHED SATIN DIFA DOORS AND
FINISH STAINLESS STEEL FRAMES
MTB-1 05 50 13 METAL WALL BASE METAL BASE FRY REGLET FLUSH BASE ANODISED CLEAR 100mm HIGH PROGRESS PROFILES,
ALUMINUM INPRO
PLAM-1 06 41 16.00 10 PLASTIC LAMINATE PLASTIC LAMINATE FORMICA NATURAL GRAIN (NG) 5788 HAZEL WALNUT -- ARPA, ARBORITE FOR CABINETS AND COUNTERTOPS
PNT-1 09 90 00 PAINT LATEX BENJAMIN MOORE TYPICAL: EGGSHELL @ WALLS, FLAT @ CEILINGS, SEMI-GLOSS @ METAL OC-17 WHITE DOVE -- DULUX, JOTUN FIELD PAINT
SURFACES
PNT-1E 09 90 00 PAINT EPOXY BENJAMIN MOORE EPOXY OC-17 WHITE DOVE -- DULUX, JOTUN EPOXY FIELD PAINT
PNT-2 09 90 00 PAINT LATEX SHERWIN WILLIAMS TYPICAL: EGGSHELL @ WALLS, FLAT @ CEILINGS, SEMI-GLOSS @ METAL SW 7757 HIGH -- DULUX, JOTUN CEILING PAINT
SURFACES REFLECTIVE WHITE
PNT-2E 09 90 00 PAINT EPOXY SHERWIN WILLIAMS EPOXY SW 7757 HIGH -- DULUX, JOTUN EPOXY CEILING
REFLECTIVE WHITE
PNT-3 09 90 00 PAINT LATEX SHERWIN WILLIAMS EGGSHELL SW 0064 BLUE PEACOCK -- DULUX, JOTUN OFFICE / SOBA BEDROOM ACCENT PAINT

MARK
PNT-4 09 90 00 PAINT LATEX BENJAMIN MOORE EGGSHELL CSP-100 COSMOPOLITAN -- DULUX, JOTUN BEDROOM MAIN PAINT
PNT-5 09 90 00 PAINT LATEX BENJAMIN MOORE EGGSHELL AF-505 BLUE ECHO DULUX, JOTUN BEDROOM ACCENT PAINT
E PNT-6 09 90 00 PAINT POLYURETHANE ACRYLIC WOLF GORDON SCUFFMASTER SMOOTH PEARL, SP10218 GOH32155021 -- DULUX, JOTUN MOSQUE ACCENT PAINT
PNT-7 09 90 00 PAINT LATEX BENJAMIN MOORE SEMI-GLOSS CSP-150 WINDY CITY -- DULUX, JOTUN HOLLOW METAL DOOR AND FRAME PAINT; METAL

PLOT SCALE: PLOT DATE:


HANDRAILS

9:31:09 AM
PT-1 09 30 10 PORCELAIN TILE PORCELAIN FLOOR TILE MARAZZI MARBLEPLAY NATURALE / MATT FINISH; RECTIFIED MONOCALIBER M4M4; MARFIL 600mm x 600mm, RAK CERAMICS, SAUDI STACK BOND LAY

2/22/2022
SOLICITATION NO.:
9.5mm THICK CERAMICS GROUT: LATICRETE 17 MARBLE BEIGE

SA-480530-1$-SI601DT.dwg
CONTRACT NO.:
PT-2 09 30 10 PORCELAIN TILE PORCELAIN FLOOR TILE MARAZZI SISTEM N NATURALE / MATT FINISH; RECTIFIED MONOCALIBER M83C NEUTRO PERLA 300mm x 600mm, RAK CERAMICS, SAUDI BRICK LAY

ISSUE DATE:
10.5mm THICK CERAMICS GROUT: MAPEI 11 SAHARA BEIGE
PT-3 09 30 10 PORCELAIN TILE PORCELAIN WALL TILE MARAZZI COLORPLAY; RECTIFIED MONOCALIBER M4J6 WHITE 300mm X 900mm; 10mm RAK CERAMICS, SAUDI STACK BOND LAY

1:1
THICK CERAMICS GROUT: LATICRETE 45 RAVEN
PT-4 09 30 10 PORCELAIN TILE PORCELAIN WALL TILE MARAZZI COLORPLAY; RECTIFIED MONOCALIBER M4J8 SAGE 300mm X 900mm; 10mm RAK CERAMICS, SAUDI STACK BOND LAY
THICK CERAMICS GROUT: LATICRETE 45 RAVEN
PT-5 09 30 10 PORCELAIN TILE PORCELAIN FLOOR TILE MARAZZI SISTEM N; BOCCIARDATO FINISH; RECTIFIED MONOCALIBER M830 NEUTRO GRIGIO 300mm x 600mm; RAK CERAMICS, SAUDI BRICK LAY
CHIARO 10.5mm THICK CERAMICS GROUT: , SHOWER FLOORS

FILE NO.:
PT-6 09 30 10 PORCELAIN TILE PORCELAIN WALL TILE MARAZZI ECLETTICA; RECTIFIED M19R SAGE 400mm x 1200mm; RAK CERAMICS, SAUDI STACK BOND LAY
6.0mm THICK CERAMICS GROUT: LATICRETE 45 RAVEN; SHOWER WALLS

SUBMITTED BY:
PT-7 09 30 10 EXTERIOR FLOOR TILE PORCELAIN FLOOR TILE MARAZZI MATERIAL 20; RECTIFIED MONOCALIBER BEIGE 800mm x 800mm, 20mm RAK CERAMICS, SAUDI GROUT: MAPEI - 04 BAHAMA BEIGE

DESIGN BY:

DRAWN BY:

C. BONHAM
THICK CERAMICS

A. HANKS
M. STULL
D

CKD BY:
J. KILBY

ANSI D
PTB-1 09 30 10 PORCELAIN WALL BASE PORCELAIN BASE TILE MARAZZI MARBLEPLAY NATURALE / MATT FINISH; RECTIFIED MONOCALIBER MARFIL 100mm x 600mm, RAK CERAMICS, SAUDI GROUT: LATICRETE 17 MARBLE BEIGE

SIZE:
9.5mm THICK CERAMICS
PTB-2 09 30 10 PORCELAIN WALL BASE PORCELAIN BASE TILE MARAZZI SISTEM N NATURALE / MATT FINISH; RECTIFIED MONOCALIBER NEUTRO PERLA 100mm x 600mm, RAK CERAMICS, SAUDI GROUT: MAPEI 11 SAHARA BEIGE
10.5mm THICK CERAMICS

TRANSATLANTIC MIDDLE EAST DISTRICT


RAF-1 09 69 13 RAISED ACCESS FLOOR RAISED ACCESS FLOORING WITH ESD TATE ALL STEEL 1250 ESD BOLTED STRINGE FORBO COLOREX 600mm x 600mm KINGSPAN, HAWORTH COMMUNICATIONS BUILDING
VINYL SD150213 SAHARA

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


RBR-1 09 65 00 RUBBER WALL BASE RUBBER BASE TARKETT TIGHTLOCK RUBBER BASE WITH COVE 80 FAWN 100mm HIGH FLEXCO, NORA RUBBER

WINCHESTER, VA 22602
RF-1 09 65 00 RESILIENT FLOORING VINYL SHEET WITH INTEGAL BASE ALTRO STRONGHOLD 30 K30500 TUNDRA 3mm THICK FLEXCO, NORA RUBBER TO HAVE 100mm INTEGRAL BASE
RF-2 09 65 00 RESILIENT FLOORING RUBBER SHEET ECORE FOREST RX TOASTED OAK 9822 7mm THICK GERFLOOR, TARKETT
SC-1 09 90 00 SEALED CONCRETE CONCRETE SEALER H&C CONCRETE SEALER CLEAR GLOSS 30. -- SHERWIN WILLIAMS,
102004-16 LATICRETE
SPC-1 10 21 13 SOLID PHENOLIC CORE PHENOLIC WALL PANELS AND DOORS COMPACT WOOD COMPACT LAMINATE PANELS TO MATCH PLAM-1 -- ARPA, ARBORITE
SS-1 06 61 16 COUNTERTOP SOLID SURFACE WILSONART QUARTZ COUNTERTOP Q1012 LORRAINE 20mm THICK LG HI-MACS, SILESTONE
SS-2 06 61 16 COUNTERTOP SOLID SURFACE WILSONART THERMOFORMED SOLID SURFACE SEAT 9200CS MYSTIQUE 12mm THICK LG HI-MACS, SILESTONE MOSQUE ABLUTON STOOL
SS-3 06 61 16 COUNTERTOP SOLID SURFACE WINDOW STOOL WILSONART QUARTZ WINDOW STOOL; EASED EDGE Q4025 TELLARO 20mm THICK LG HI-MACS, HANSTONE WINDOW SILLS
SS-4 06 61 16 COUNTERTOP EPOXY COUNTERTOP DURCON DURCON CLASSIC EPOXY RESIN TOP; BEVELED EDGE GRAPHITE 25mm THICK KEWAUNEE,LABDS WGTS BUILDING
C THR-1 09 30 10 MARBLE THRESHOLD STONE - MARBLE TPIGI BULLNOSE MARBLE THRESHOLD CREME MARFIL 20mm THICK; REFER RAK CERAMICS, SAUDI
TO PLANS CERAMICS
TKBD-1 10 11 00 TACKBOARD EMBOSSED FOAM QUARTET BULLETIN BOARD BLACK 1200mm x 915mm FORBO, GLOBAL
INDUSTRIAL
UP-1 06 41 16.00 10 UPHOLSTRY UPHOLSTERED BENCH BRENTANO SOLSTICE OUTDOOR / INDOOR STAIN RESISTANT FABRIC VEGA 5815-04 1370mm WIDTH MOSQUE BUILT-IN BENCH
WP-1 10 26 00 WALL PROTECTION WALL COVERING ALTRO PURAGUARD W135 SALT WHITE 2mm THICK x 3M HIGH CS GROUP, INPRO CORP. DIFA KITCHEN
x 1M WIDE
WP-2 10 26 00 WALL PROTECTION WALL COVERING P3 TECH INFINITY P3T-60177 - EVERGREEN 1220mm W WOLF GORDON, CS GROUP DIFA ENLISTED DINING AND OFFICER DINING
WS-1 12 24 13 WINDOW SHADE MANUAL SHEER SHADE MECHO SHADE MECHO 5, SINGLE SHADE, 3% OPENNESS ECOVAIL 1566 EGGSHELL REFER TO PLANS HUNTER DOUGLAS; SWF

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


CONTRACT
WS-2 12 24 13 WINDOW SHADE MANUAL BLACKOUT SHADE MECHO SHADE MECHO 5, SINGLE SHADE, OPAQUE EQUINOX 0115 LINEN REFER TO PLANS HUNTER DOUGLAS; SWF
CONTRACT

THAAD STANDARD FACILITIES


WV-1 08 14 00 WOOD VENEER WOOD VENEER DOOGE VENEERS FLAT AND QUARTER CUT; CLEAR STAIN TO MATCH PLAM-1 -- -- WOOD VENEER FOR DOORS

VARIOUS LOCATIONS, KSA

INTERIOR FINISH LEGEND


STANDARD DETAILS
SA-480530
B
2/22/2022 9:31:09 AM

A SHEET ID
$

SI601
1 2 3 4 5 6 7 8 9 10

FURNITURE, FIXTURE, AND EQUIPMENT SCHEDULE FURNITURE, FIXTURE, AND EQUIPMENT SCHEDULE GENERAL SHEET NOTES
ITEM CODE DESCRIPTION QUANTITY ITEM CODE DESCRIPTION QUANTITY 1. REFER TO IF SERIES FOR FURNITURE PLACEMENT PLANS.
100 - SEATING 720 PORTABLE AIR COMPRESSOR 1 US Army Corps of
2. FURNITURE AND EQUIPMENT IS SHOWN FOR REFERENCE ONLY. REFER TO Engineers ®
101 TASK CHAIR 43 721 HEAVY DUTY TIRE CHANGER 1 FURNITURE, FIXTURE, AND EQUIPMENT (FF&E) PACKAGE FOR FURNITURE
102 GUEST CHAIR 33 722 PORTABLE WELD FUME EXTRACTOR 1 SPECIFICATIONS. Middle East District
G 104 GUEST CHAIR 30 800 - ACCESSORIES
106 EXECUTIVE SOFA 6 802 PERSONAL TRASH CAN 55
107 CONFERENCE CHAIR 8 803 TABLE LAMP 19

DATE
108 COLLABORATIVE CHAIR 58 804 ARCHED FLOOR LAMP 4
109 DINING CHAIR 46 805 READING LAMP 116
109.1 DINING CHAIR 33 808 LARGE TRASH CAN 8
109.2 DINING CHAIR 26 809 COAT RACK 2
111 LOUNGE CHAIR 24 810 1400mm LED TV 16
112 RECLINER 62 811 1650mm LED TV 5
113 TEACHER STOOL 1 812 2185mm LED TV 1
114 LOUNGE LOVESEAT 10 813 UNDERCOUNTER TRASH CAN 9
115 ESD WORK STOOL 15 814 208 LTR TRASH CAN 32
116 WORK STOOL 18
118 DESK CHAIR 11
118.1 DESK CHAIR 36

DESCRIPTION
120 MAJLIS ARM CHAIR 16
F 122 SEWING STOOL 2
123 LOUNGE CHAIR 8
124 LONGUE SOFA 4
126 24-HOUR CHAIR 13
200 - TABLES
201 1070 DIA TABLE 4
202 OCCASIONAL TABLE 48
203 OVAL OCCASIONAL TABLE 10
206 MEETING TABLE 2
207 CLASSROOM MOBILE TABLE 31
208 SQUARE SIDE TABLE 22
209 SQUARE DINING TABLE 30
213 WORK TABLE - 1500 x 750 14
214 WORK TABLE - 1800 x 750 9

MARK
217 WORKBENCH 12
224 SEWING TABLE 2
E 300 - CASEGOODS
301 U-SHAPED DESK W/ BACK HUTCH 2

PLOT SCALE: PLOT DATE:


302 L-SHAPED DESK 7

10:34:04 AM
304 U-SHAPED DESK W/ SIDE HUTCH 1

3/11/2022
SOLICITATION NO.:
305 L-SHAPED DESK 26

SA-480530-1$-SI602DT.dwg
CONTRACT NO.:
306 SHARED OFFICE DESK 2

ISSUE DATE:
307 L-SHAPED RECEPTION DESK 2
308 CONSOLE DESK 3

1:1
309 BEDROOM DESK 3
400 - STORAGE
401 3H LATERAL FILE 41
402 ADJUSTABLE METAL SHELVES - 900 x 450 x 2200 4

S. DOUGLASHANSEN
405 ADJUSTABLE METAL SHELVES - 1200 x 450 x 2100 36

FILE NO.:
406 5H LATERAL FILE WITH LOCK BAR 1

SUBMITTED BY:
408 PALLET RACK 6

DESIGN BY:

DRAWN BY:

C. BONHAM
409 PALLET RACK STARTER UNIT 17

A. HANKS
D

CKD BY:
J. KILBY

ANSI D
410 MOBILE TOOL STORAGE 15

SIZE:
411 MOBILE METAL CABINET WITH DRAWERS 1
412 FLAMMABLE LIQUIDS CABINET 19
413 METAL CABINET 36

TRANSATLANTIC MIDDLE EAST DISTRICT


414 5H LATERAL FILE 8

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


415 MOBILE PEDESTAL 7
416 ADJUSTABLE METAL SHELVES - 1220 x 2440 x 1830 36

WINCHESTER, VA 22602
419 SINGLE TIER TIRE RACK 5
422 MISCELLANEOUS WEAPONS 7
423 FIRE-PROOF WEAPONS CABINET 3
424 HEAVY DUTY METAL SHELVES - 1200 x 760 x 1800 17
425 GEAR LOCKER 8
426 MOBILE GEAR LOCKER (ECM SITE) 2
427 TYPE A SHELVING 10
428 TYPE A SHELVING - LONG 3
429 TYPE D SHELVING 35
C
430 TEMF STORAGE SHELVING 2
431 227 LITER FLAMMABLE STORAGE CABINET 2
432 64 LITER WALL MOUNT FLAMMABLE STORAGE CABINET 2
600 - EQUIPMENT
602 REFRIGERATOR 8
603 WATER COOLER 14
604 MICROWAVE 11

ARCHITECTURAL / INTERIORS STANDARD DETAILS


FURNITURE, FIXTURE, AND EQUIPMENT SCHEDULE
606 ELECTRIC TEA KETTLE 12

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


610 HOT PLATE 12
611 SINGLE DOOR REFRIGERATOR 4
600 - EQUIPMENT (OFOI)

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
601 LASER PRINTER / COPIER / SCANNER 4
601.1 DESKTOP PRINTER / COPIER / SCANNER 18
601.2 LABEL MAKER 2

SA-480530-1
700 - SPECIALIZED FURNITURE
B 701 LECTERN 1
702 BED SIDE TABLE 7
703 TWIN XL BED 7
704 TWIN XL BUNKBED 58
705 WARDROBE 120
706 NIGHTSTAND SHELF 58
707 GSA SAFE 2
708 ESD WORKBENCH 14
709 TABLE TENNIS 2
710 FOOSBALL TABLE 3
711 POOL TABLE 3
712 POWERED CARDIO 6
713 WELDING TABLE 1
3/11/2022 10:34:04 AM

714 PORTABLE SOLDER FUME EXTRACTOR 1


700 - SPECIALIZED FURNITURE (OFOI)
A 715 50 GALLON SOAP FOAMER 1 SHEET ID
716 WORLD CLASS TOOLS 4
717 TRAILOR CADDY 1 $
718 TRAILOR CADDY CHARGER 1
719 HYDRONICS TEST FIXTURE (HTF) 1 UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SI602
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SPECIFICATION 10 14 00.20 FOR MORE INFORMATION AND DETAILS.
US Army Corps of
2. SIGNS MUST HAVE CONCEALED BACKER INSET FROM EDGES OF SIGN TYPE Engineers ®
TO AVOID SIGN BEING APPLIED DIRECTLY TO FINISH WALL.
Middle East District
G 3. CONFRIM SIGNAGE TEXT WITH CONTRACTING OFFICER BEFORE FINAL
ORDER.

DATE
4. NUMERICAL REPRESENTATIONS ARE COORDINATED WITH CONTRACTING
OFFICER AND CONTAIN ARABIC AND ENGLISH CHARACTERS.

SIGNS MOUNTED TO SIGNS MOUNTED TO SIGNS MOUNTED TO SIGNS MOUNTED TO SIGNS MOUNTED TO 5. SIGNAGE AND GRAPHICS TO COMPLY WITH HOST NATION STANDARDS FOR:
LATCH SIDE OF DOOR LATCH SIDE OF DOOR LATCH SIDE OF DOOR LATCH SIDE OF DOOR LATCH SIDE OF DOOR • ROOM IDENTIFICATION COMPONENTS
• LIFE SAFETY COMPONENTS
TO CENTER OF 230 TO CENTER OF 230 TO CENTER OF 230 TO CENTER OF 230 TO CENTER OF 230 • WAYFINDING COMPONENTS
RAISED CHARACTERS RAISED CHARACTERS RAISED CHARACTERS RAISED CHARACTERS RAISED CHARACTERS
1,525 AFF

1,525 AFF

1,525 AFF

1,525 AFF

1,525 AFF

1,525 AFF
1,343 AFF

1,320 AFF
1,305 AFF
1,270 AFF

1,260 AFF

1,260 AFF
1,220 AFF

1,220 AFF

1,220 AFF

1,220 AFF

1,220 AFF

1,220 AFF

DESCRIPTION
F

TO BASE OF SIGN TO BASE OF SIGN TO BASE OF SIGN TO BASE OF SIGN TO BASE OF SIGN TO BASE OF SIGN

TO BASELINE OF LOWEST TO BASELINE OF LOWEST TO BASELINE OF LOWEST TO BASELINE OF LOWEST TO BASELINE OF LOWEST TO BASELINE OF LOWEST
TACTILE CHARACTER TACTILE CHARACTER TACTILE CHARACTER TACTILE CHARACTER TACTILE CHARACTER TACTILE CHARACTER

SIGN TYPE A1 SIGN TYPE A2 SIGN TYPE B1 / B1.E SIGN TYPE B2 / B2.E SIGN TYPE B3 SIGN TYPE D1

EQL EQL TACTILE SIGN CENTERED ON


INACTIVE (LOCKED) LEAF OF
EQL EQL SIGNS MOUNTED TO SIGNS MOUNTED TO DOUBLE DOOR. IF THE DOUBLE-
LATCH SIDE OF DOOR LATCH SIDE OF DOOR DOOR CONTAINS TWO ACTIVE
LEAFS (NEITHER DOOR IS LOCKED
TO CENTER OF TO CENTER OF IN PLACE), THE SIGN TO BE
CENTER SIGN 230 230 MOUNTED ON THE WALL TO THE

MARK
ON DOOR RAISED CHARACTERS RAISED CHARACTERS
RIGHT OF THE DOUBLE-DOORS.

E
50
3,000

430

PLOT SCALE: PLOT DATE:


1,525 AFF

1,524 AFF

1,524 AFF

1,525 AFF

1,320 AFF
1,260 AFF

1,260 AFF
1,220 AFF

1,220 AFF

1,220 AFF

1,220 AFF

1,220 AFF
230

9:31:11 AM
2/22/2022
SOLICITATION NO.:

SA-480530-1$-SI603DT.dwg
CONTRACT NO.:
ISSUE DATE:

1:1
TO BASE OF SIGN
TO BASE OF SIGN TO BASE OF SIGN TO BASE OF SIGN TO BASE OF SIGN
SIGN TO BE MOUNTED TO FROM COUNTERTOP
CEILING AND POINTING IN TO BASELINE OF LOWEST TO BASELINE OF LOWEST TO BASELINE OF LOWEST TO BASELINE OF LOWEST
DIRECTION OF MECCA TACTILE CHARACTER TACTILE CHARACTER TACTILE CHARACTER TACTILE CHARACTER

SIGN TYPE D3 SIGN TYPE G1 / G1.A SIGN TYPE E1 & SIGN TYPE R1 / R1.E SIGN TYPE R2 TYPICAL MOUNTING OF SIGNS

FILE NO.:
TYPICAL MOUNTING OF SIGNS ON SINGLE DOORS PLACED ON DOUBLE DOORS

SUBMITTED BY:
DESIGN BY:

DRAWN BY:

C. BONHAM

A. HANKS
M. STULL
D

CKD BY:
J. KILBY

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


MIN.

WINCHESTER, VA 22602
50
MIN.
50
FROM TOP OF CASEWORK
DOOR TO TOP OF SIGN

C SIGNS PLACED ON CASEWORK

SIGNAGE MOUNTING HEIGHTS


1 : 50

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


THAAD STANDARD FACILITIES

SIGNAGE MOUNTING HEIGHTS


VARIOUS LOCATIONS, KSA

STANDARD DETAILS
1234 1234 1234

SA-480530
B P-1: PEACOCK BLUE TEXT: WHITE
(RAL 200 30 25) (RAL 9010) FONT 1: 15mm RAISED WHITE FONT 2: 20mm RAISED BLACK FONT 3: 15mm RAISED BLACK

S-1 S-2 S-4 S-5


GRAPHIC SCALES
1234 1234 1234

PAPER: BONE WHITE TEXT: BLACK


(RAL 9001) (RAL 9005) FONT 4: 25mm RAISED WHITE FONT 5: 30mm RAISED WHITE FONT 6: 10mm RAISED BLACK
S-6 S-7 S-8 S-9

0 100 200 400

1234 1234 1234 SCALE: 1:5


2/22/2022 9:31:11 AM

A MT-1: NATURAL SATIN


S-10 S-11 0 1M 2M 4M
FONT 7: 30mm RAISED BLACK FONT 8: 50mm RAISED BLACK FONT 9: 50mm RAISED RED SHEET ID
SCALE: 1:50 $
SIGNAGE FINISHES SIGNAGE ICONS SIGNAGE FONTS
1:5 1:5 1:5 UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SI603
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SPECIFICATION 10 14 00.20 FOR MORE INFORMATION AND DETAILS.
US Army Corps of
2. SIGNS MUST HAVE CONCEALED BACKER INSET FROM EDGES OF SIGN TYPE Engineers ®
TO AVOID SIGN BEING APPLIED DIRECTLY TO FINISH WALL. Middle East District
G 3. CONFRIM SIGNAGE TEXT WITH CONTRACTING OFFICER BEFORE FINAL
ORDER.

DATE
4. NUMERICAL REPRESENTATIONS ARE COORDINATED WITH CONTRACTING
OFFICER AND CONTAIN ARABIC AND ENGLISH CHARACTERS.

5. SIGNAGE AND GRAPHICS TO COMPLY WITH HOST NATION STANDARDS FOR:


• ROOM IDENTIFICATION COMPONENTS
• LIFE SAFETY COMPONENTS
• WAYFINDING COMPONENTS

DESCRIPTION
REFER TO REFER TO
F 215 SCHEDULE
7 3 SCHEDULE
FOR ROOM 150 FOR ROOM 7 3
NUMBER NUMBER 150 220 REFER TO
SCHEDULE
1 1 FONT 2 7 3 FOR TEXT 73
MIN.
10

MIN.
#### REFER TO
60

FONT 1

10
FONT 1 FONT 2
SCHEDULE FOR
####
‫اﻟﻜﮭﺮﺑﺎﺀ‬

60
2 2

60
GRADE II #### ROOM NUMBER

100
120
BRAILLE GRADE II
180

1
ELECTRICAL
5 5

Jill Fouche
60

2 BRAILLE

5
Accounting Department Jill Fouche 2

60
GRADE II 1
Sales Manager
3 BRAILLE
5

Jill Fouche 3 GRADE II


60

5
Accounting Department BRAILLE
5

MARK
E SIGN TYPE A1 - ROOM IDENTIFICATION OCCUPANTS SIGN TYPE A2 - ROOM IDENTIFICATION OCCUPANT SIGN TYPE B1 / B1.E - ROOM NUMBER IDENTIFICATION SIGN TYPE B2 - ROOM NAME IDENTIFICATION
1. ACRYLIC SIGN PLAQUE. FACE AND RETURNS TO MATCH (P-1). ADA COMPLIANT RAISED 1. ACRYLIC SIGN PLAQUE. FACE AND RETURNS TO MATCH (P-1). ADA COMPLIANT RAISED 1. METAL SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). ADA COMPLIANT RAISED LETTER- 1. METAL SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). ADA COMPLIANT RAISED LETTER-

PLOT SCALE: PLOT DATE:


LETTER-FORMS, WHITE, WITH CLEAR ADA COMPLIANT BRAILLE. LETTER-FORMS, WHITE, WITH CLEAR ADA COMPLIANT BRAILLE. FORMS, BLACK, WITH CLEAR ADA COMPLIANT BRAILLE. FORMS, BLACK, WITH CLEAR ADA COMPLIANT BRAILLE.
2. BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE. BACKER TO BE BLACK 2. BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE. BACKER TO BE BLACK 2. BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE. BACKER TO BE BLACK 2. BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE. BACKER TO BE BLACK

9:31:12 AM
ANODIZED ALUMINUM. ANODIZED ALUMINUM. ANODIZED ALUMINUM. ANODIZED ALUMINUM.

2/22/2022
3. METAL CHANGEABLE INSERT SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). RIGID 3. METAL CHANGEABLE INSERT SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). RIGID 3. FOR ROOMS THAT CONTAIN CONTROLS FOR AIR-CONDITIONING SYSTEMS, SPRINKLER

SOLICITATION NO.:

SA-480530-1$-SI604DT.dwg
PAPER INSERT. PRINTER COMPATIBLE DIGITAL TEMPLATE TO BE SUPPLIED TO CLIENT & (2) PAPER INSERT. PRINTER COMPATIBLE DIGITAL TEMPLATE TO BE SUPPLIED TO CLIENT & (2) B1.E - EXTERIOR ROOM NUMBER IDENTIFICATION: RISERS AND VALVES, OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL ELEMENTS,

CONTRACT NO.:
REAMS OF COMPATIBLE PAPER, BONE WHITE COLOR, FOR SUBSEQUENT UPDATES BY REAMS OF COMPATIBLE PAPER, BONE WHITE COLOR, FOR SUBSEQUENT UPDATES BY 1. EXTERIOR GRADE METAL SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). ADA SIGNAGE TO INDICATE "FIRE RISER"

ISSUE DATE:
CLIENT. INSERT TO HAVE NON GLARE CLEAR ACRYLIC FACE. CLIENT. INSERT TO HAVE NON GLARE CLEAR ACRYLIC FACE. COMPLIANT RAISED LETTER-FORMS, BLACK, WITH CLEAR ADA COMPLIANT BRAILLE.
2. EXTERIOR GRADE BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE,
MOUNTED BY CONCEALED MECHANICAL FASTENERS. BACKER TO BE BLACK ANODIZED

1:1
ALUMINUM.

REFER TO 7 3 280
215 SCHEDULE FOR 73

FILE NO.:
ROOM NUMBER
220 REFER TO

SUBMITTED BY:
SCHEDULE FONT 1
FOR TEXT 7 3
####
60

‫ﺐﺗﺎﻜﻤﻟا‬

DESIGN BY:

DRAWN BY:

C. BONHAM
2

A. HANKS
1

M. STULL
D

CKD BY:
J. KILBY

ANSI D
FONT 2 1 2 OFFICES ‫اﻟﻘﺒﻠﺔ‬
MIN.

SIZE:
1 2
‫اﻟﻜﮭﺮﺑﺎﺀ‬
5
10

2 FONT 2

230
GRADE II
100

MIN.

‫ﻏﺮﻓﺔ اﻟﻤﺆﺗﻤﺮات‬
215
10

ELECTRICAL BRAILLE QIBLA


‫هﺎﯿﻤﻟا تارود‬
145

1
Conference

TRANSATLANTIC MIDDLE EAST DISTRICT


3
MIN.

Room RESTROOMS
10

GRADE II

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


BRAILLE
5

WINCHESTER, VA 22602
SIGN TYPE B2.E - EXTERIOR ROOM NAME IDENTIFICATION SIGN TYPE B3 - ROOM IDENTIFICATION SIGN TYPE D1 - DIRECTIONAL SIGN SIGN TYPE D3 - QIBLA DIRECTIONAL SIGN
1. EXTERIOR GRADE METAL SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). ADA 1. ACRYLIC SIGN PLAQUE. FACE AND RETURNS TO MATCH (P-1). ADA COMPLIANT RAISED 1. METAL CHANGEABLE INSERT SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). RIGID PAPER 1. METAL SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). SYMBOL AND FONT TO BE RAISED
COMPLIANT RAISED LETTER-FORMS, BLACK, WITH CLEAR ADA COMPLIANT BRAILLE. LETTER-FORMS, WHITE, WITH CLEAR ADA COMPLIANT BRAILLE. INSERT. PRINTER COMPATIBLE DIGITAL TEMPLATE TO BE SUPPLIED TO CLIENT & (2) REAMS OF LETTER-FORMS, BLACK.
2. EXTERIOR GRADE BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE. 2. BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE. BACKER TO BE BLACK COMPATIBLE PAPER, BONE WHITE COLOR, FOR SUBSEQUENT UPDATES BY CLIENT. INSERT TO 2. BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE MOUNTED BY CONCEALED
BACKER TO BE BLACK ANODIZED ALUMINUM. ANODIZED ALUMINUM. HAVE NON GLARE CLEAR ACRYLIC FACE. MECHANICAL FASTENERS. BACKER TO BE BLACK ANODIZED ALUMINUM.
3. FOR ROOMS THAT CONTAIN CONTROLS FOR AIR-CONDITIONING SYSTEMS, SPRINKLER 3. METAL CHANGEABLE INSERT SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). RIGID 2. BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE, MOUNTED BY CONCEALED 3. PRIOR TO MOUNTING TO CEILING, CONFIRM DIRECTION OF MECCA.
C RISERS AND VALVES, OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL ELEMENTS, PAPER INSERT. PRINTER COMPATIBLE DIGITAL TEMPLATE TO BE SUPPLIED TO CLIENT & 2 MECHANICAL FASTENERS. BACKER TO BE BLACK ANODIZED ALUMINUM.
SIGNAGE TO INDITCATE "FIRE RISER" REAMS OF COMPATIBLE PAPER, BONE WHITE COLOR, FOR SUBSEQUENT UPDATES BY
CLIENT. INSERT TO HAVE NON-GLARE CLEAR ACRYLIC FACE.

150 73
230 280
200
73 73 4
3 4

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


Don't use sinks
5

1
100

for solid waste 1 73


1 3 REFER TO
Use trash receptacles

THAAD STANDARD FACILITIES


SCHEDULE FOR
FONT 3
150

240

VARIOUS LOCATIONS, KSA


SYMBOL(S)
REFER TO 3
1 2
PAPER INSERT

STANDARD DETAILS
2 SCHEDULE FOR
225

230 ‫ﻦﺋاﺰﺧ‬
230

320
SYMBOL(S) FONT 3

SIGNAGE TYPES
Evacuation Plan LOCKERS

SA-480530
EVAC MAP 4

B ‫ﻻ ﺗﺴﺘﺨﺪم اﻟﻤﺼﺎرف‬
INFORMATION
‫هﺎﯿﻤﻟا تارو‬ FONT 1
80
100

‫ﻟﻠﻨﻔﺎﯾﺎت اﻟﺼﻠﺒﺔ‬ 1 RESTROOM

MIN.
2 2
‫رﺟﺎل‬

10
‫اﺳﺘﺨﺪم أوﻋﯿﺔ اﻟﻘﻤﺎﻣﺔ‬
5

80
FONT 3 FONT 1
MEN GRAPHIC SCALES
MIN.

GRADE II
10

3 BRAILLE
GRADE II
BRAILLE

SIGN TYPE G1 / G1.A - INFORMATIONAL SIGNS SIGN TYPE E1 - EVACUATION MAP / OCCUPANT LOAD SIGN TYPE R1 / R1.E - RESTROOM / EXTERIOR RESTROOM SIGN TYPE R2 - LOCKER ROOM
1. METAL SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). RAISED LETTER-FORMS, BLACK. 1. METAL CHANGEABLE INSERT SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). RIGID 1. METAL SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). SYMBOL TO BE ADA COMPLIANT 1. METAL SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). SYMBOL TO BE ADA COMPLIANT
2. BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE. BACKER TO BE BLACK PAPER INSERT. PRINTER COMPATIBLE DIGITAL TEMPLATE TO BE SUPPLIED TO CLIENT & 2 RASED FORMS, BLACK. RASED FORMS, BLACK.
ANODIZED ALUMINUM. REAMS OF COMPATIBLE PAPER, BONE WHITE COLOR, FOR SUBSEQUENT UPDATES BY 2. ACRYLIC SIGN PLAQUE. FACE AND RETURNS TO MATCH (P-1). ADA COMPLIANT RAISED 2. ACRYLIC SIGN PLAQUE. FACE AND RETURNS TO MATCH (P-1). ADA COMPLIANT RAISED
3. SYMBOL TO BE ADA COMPLIANT RASED FORMS, BLACK. REFER TO BUILDING SPECIFIC CLIENT. INSERT TO HAVE NON GLARE CLEAR ACRYLIC FACE. LETTER-FORMS, WHITE, WITH CLEAR ADA COMPLIANT BRAILLE. LETTER-FORMS, WHITE, WITH CLEAR ADA COMPLIANT BRAILLE.
SIGNAGE SCHEDULE FOR SYMBOL(S). 2. BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE, MOUNTED BY 3. BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE. BACKER TO BE BLACK 3. BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE. BACKER TO BE BLACK
CONCEALED MECHANICAL FASTENERS. BACKER TO BE BLACK ANODIZED ALUMINUM. ANODIZED ALUMINUM. ANODIZED ALUMINUM.
3. WHERE OCCUPANT LOAD SIGNAGE IS USED, REFER TO LIFE SAFETY FOR MAXIMUM LOAD 4. SYMBOL TO BE ADA COMPLIANT RASED FORMS, BLACK. REFER TO BUILDING SPECIFIC 4. SYMBOL TO BE ADA COMPLIANT RASED FORMS, BLACK. REFER TO BUILDING SPECIFIC
2/22/2022 9:31:12 AM

COUNT. SIGNAGE SCHEDULE FOR SYMBOL(S). SIGNAGE SCHEDULE FOR SYMBOL(S).

A R1.E - EXTERIOR RESTROOM 0 100 200 400


1. EXTERIOR GRADE METAL SIGN PANEL. FACE AND RETURNS TO MATCH (MT-1). SYMBOL TO BE SHEET ID
ADA COMPLIANT RASED FORMS, BLACK.
2. ACRYLIC SIGN PLAQUE. FACE AND RETURNS TO MATCH (P-1). ADA COMPLIANT RAISED
LETTER-FORMS, WHITE, WITH CLEAR ADA COMPLIANT BRAILLE. SCALE: 1:5 $
3. EXTERIOR GRADE BACKER TO BE INSET ON ALL SIDES 5mm FROM MAIN PANEL EDGE,
MOUNTED BY CONCEALED MECHANICAL FASTENERS. BACKER TO BE BLACK ANODIZED
ALUMINUM.
4. SYMBOL TO BE ADA COMPLIANT RASED FORMS, BLACK. REFER TO BUILDING SPECIFIC
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SI604
SIGNAGE SCHEDULE FOR SYMBOL(S).
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
CEILING
G
A/C SUPPLY NOTE: MEASUREMENTS SHOWN ARE TO

150 mm MINIMUM
AUDIO/VISUAL OR RETURN THE CLOSEST EDGE OF THE DETECTOR.

DATE
DEVICE DIFFUSER
STROBE ONLY 100 mm MINIMUM
DEVICES AUDIO ONLY 910 mm MIN
DEVICE CEILING CEILING

100 mm MINIMUM
ACCEPTABLE ACCEPTABLE
CEILING SMOKE HERE
DETECTOR
MOUNTING
SYNCHRONIZE MORE THAN
LOCATION NEVER HERE
TWO APPLIANCES IN ANY FIELD OF VIEW

300 mm MAXIMUM
CEILING MOUNTED

DESCRIPTION
300 mm MAXIMUM
F SMOKE DETECTOR

2290 mm MINIMUM
MAXIMUM OF 2440 mm

MINIMUM OF 2030 mm
TO BOTTOM OF LENS
TO TOP OF LENS

TOP OF DETECTOR TOP OF DETECTOR


ACCEPTABLE HERE ACCEPTABLE HERE
NOTE:

COORDINATE LOCATION
OF DEVICES/APPLIANCES
WITH OTHER TRADES TO
ALIGN VERTICALLY
WHERE FEASIBLE
NOTE:

MARK
REFER TO THE PROPER MEASUREMENTS SHOWN ARE
DEVICE INSTALLATION TO THE CLOSEST EDGE OF
INSTRUCTIONS FOR THE DETECTOR.
E BACKBOX MOUNTING FINISHED WALL SIDEWALL
HEIGHT

PLOT SCALE: PLOT DATE:


9:40:23 AM
2/22/2022
SOLICITATION NO.:

SA-480530-1$-SF501DT.dwg
CONTRACT NO.:
ISSUE DATE:

1:1
6 AUDIO/VISUAL DEVICE INSTALLATION HEIGHT 5 SMOKE DETECTOR INSTALLATION HEIGHT 4 HEAT DETECTOR INSTALLATION HEIGHT
SF501 NTS SF501 NTS SF501 NTS

FILE NO.:
SUBMITTED BY:
R. BELMONT
DESIGN BY:

D. RUTHER.
DRAWN BY:
T. LAYTON

A. HANKS
D

CKD BY:

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
CEILING

US ARMY CORPS OF ENGINEERS


CEILING

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
NOTE:

COORDINATE LOCATION NOTE:


OF DEVICES/APPLIANCES
WITH OTHER TRADES TO TO EXIT DOOR (MAX)
1,520 mm COORDINATE LOCATION
ALIGN VERTICALLY
OF DEVICES/APPLIANCES
WHERE FEASIBLE
WITH OTHER TRADES TO
C ALIGN VERTICALLY
WHERE FEASIBLE

NAC PANEL TOP OF CABINET 2000 mm

CENTER OF CABINET 1520 mm

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


FINISHED
LOC WALL
MANUAL PULL

THAAD STANDARD FACILITIES


STATION

VARIOUS LOCATIONS, KSA

FIRE ALARM - DETAILS


NOTE:

STANDARD DETAILS
RECESSED OR SEMI-RECESSED

SA-480530
NO HIGHER THAN 1520 mm TO TOP OF MESSAGE
IN FINISHED SPACES AND SURFACE
B TO CENTER OF NAC
CABINET
BUTTONS ON LOC
1117 mm MAX MOUNTED IN UNFINISHED SPACES
1020 mm MIN TOP OF CABINET 2000 mm ABOVE
FINISHED FLOOR OR CENTER TO HIGHEST PORTION
OF CABINET AT 1520 mm ABOVE OF OPERABLE PART FINISHED
FINISHED FLOOR, WHICHEVER 1220 mm MAX FLOOR
IS LOWER. FINISHED
1070 mm MIN
FINISHED FLOOR
FLOOR
2/22/2022 9:40:23 AM

A 3 NAC PANEL AND LOC MOUNTING HEIGHT 2 FACU AND FAA MOUNTING HEIGHT 1 MANUAL PULL STATION INSTALLATION HEIGHT
SF501 NTS SF501 NTS SF501 NTS SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SF501
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
G

DATE
DESCRIPTION
F

MARK
DURING IOC FACILITIES CONSTRUCTION, PROGRAM
PUHO FACU AS HEAD-END PANEL.
ARRANGE FIBER JUMPERS FOR PUHO TO BE AT THE
E END OF THE DAISY-CHAINED NETWORK.
UPON SCFA CONSTRUCTION, CONNECT SCFA FACU

PLOT SCALE: PLOT DATE:


TO PUHO FACU SO THAT PROGRAMMING WORK
TAKES PLACE AT PUHO FACU, AND TRANSITION SCFA

9:40:23 AM
2/22/2022
FACU TO BE THE HEAD-END.

SOLICITATION NO.:

SA-480530-1$-SF502SH.dwg
CONTRACT NO.:
ISSUE DATE:
LCD ANNUNCIATOR TO DISPLAY FIRE ALARM LCD ANNUNCIATOR TO DISPLAY FIRE ALARM
SYSTEM CONDITIONS FOR THE SITE AFTER SYSTEM CONDITIONS FOR THE SITE DURING

1:1
FOC PHASE CONSTRUCTED IOC PHASE ONLY
FIBER PATCH CONNECTOR
IN COBU (TYPICAL FOR ALL
BUILDINGS) SCFA FACU IS PRIMARY RECEIVING
UNDERGROUND FIBER
POINT FOR ALL FIRE ALARM FAA FAA
NETWORK FROM
SIGNALS ON THE NETWORK

FILE NO.:
INDIVIDUAL BUILDING
FACU TO COBU (TYPICAL

SUBMITTED BY:
FOR ALL BUILDINGS)

R. BELMONT
DESIGN BY:

D. RUTHER.
DRAWN BY:
T. LAYTON

A. HANKS
D

CKD BY:

ANSI D
SAAS DIFA SOBA SOBA OFBA MOSQ CLFA SAGF GPWA BVMF SCFA PUHO TOFA RPRE TEMF COBU

SIZE:
FACU FACU FACU FACU FACU FACU FACU FACU FACU FACU FACU FACU FACU FACU FACU FACU

24 HR BATTERY BACKUP 48 HR BATTERY BACKUP

TRANSATLANTIC MIDDLE EAST DISTRICT


FACUS REQUIRING 48 HR BATTERY BACKUP SHALL

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


FOC FACILITIES IOC FACILITIES BE ARRANGED SUCH THAT POWER FAILURE OF ANY
FACU REQUIRING 24 HR BATTERY BACKUP DOES NOT

WINCHESTER, VA 22602
INTERRUPT TRANSMISSION OF SIGNALS TO SCFA.

C
1 FIRE ALARM SITE WIDE SCHEMATIC
SF502 NTS

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)

FIRE ALARM - SITE WIDE SCHEMATIC


THAAD STANDARD FACILITIES
VARIOUS LOCATIONS, KSA

STANDARD DETAILS
SA-480530
B
2/22/2022 9:40:23 AM

A SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SF502
1 2 3 4 5 6 7 8 9 10

BOTTOM OF SLAB
US Army Corps of
BOTTOM LINE OF SLAB Engineers ®
25.4 mm (min.)
GALVANIZED
UPRIGHT TYPE FIRE STOP SEALANT GALVANIZED Middle East District
IRON SLEEVE APPROVED SEALANT
G SPRINKLER HEAD IRON SLEEVE

25mm CLOSE NIPPLE

DATE
BRANCH LINE

25mm DROP NIPPLE


25 mm CLOSE NIPPLE
RECESSED TYPE
BRANCH LINE SPRINKLER HEAD
FIRE FIGHTING FIRE RATED FIRE FIGHTING WALL
CONCENTRIC REDUCER
PIPE WALL PIPE

FALSE CEILING LINE PIPE SLEEVE THROUGH PIPE SLEEVE


FALSE CEILING LINE

DESCRIPTION
F FIRE RATED WALL THROUGH WALL
SPRINKLER HEAD UPRIGHT SPRINKLER HEAD RECESSED TYPE
TYPE
25.4mm (min.)
UPRIGHT TYPE
SPRINKLER HEAD GALVANIZED APPROVED SEALANT GALVANIZED
IRON SLEEVE IRON SLEEVE
FIRE STOP SEALANT
FIRE RATED FLOOR
FLOOR
25 mm CLOSE NIPPLE
25mm PIPE
25mm DROP NIPPLE
BRANCH LINE

MARK
RECESSED TYPE
SPRINKLER HEAD
E FIRE FIGHTING
PIPE
FIRE FIGHTING
PIPE

PLOT SCALE: PLOT DATE:


9:40:24 AM
2/22/2022
SOLICITATION NO.:

SA-480530-1$-SF511DT.dwg
CONTRACT NO.:
FALSE CEILING LINE

ISSUE DATE:
SPRINKLER HEAD CONCEALED
SPRINKLER HEAD SIDE WALL TYPE

1:1
SPACE & BELOW CEILING PIPE SLEEVE PIPE SLEEVE
THROUGH FIRE THROUGH FLOOR
RATED FLOOR

FILE NO.:
PIPE PENETRATION DETAILS

SUBMITTED BY:
1

R. BELMONT
DESIGN BY:

D. RUTHER.
DRAWN BY:
T. LAYTON
SF511 NTS

A. HANKS
D

CKD BY:

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WET SPRINKLER PIPE

WINCHESTER, VA 22602
FACE OF FITTING X

FALSE CEILING

C DRY SPRINKLER

X = MINIMUM EXPOSED BARREL LENGTH IN


ACCORDANCE WITH NFPA 13 TABLE 8.4.9.1(B)

DRY PENDENT SPRINKLER HEAD TYPE

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


THAAD STANDARD FACILITIES

FIRE SUPPRESSION - DETAILS


VARIOUS LOCATIONS, KSA

STANDARD DETAILS
2 SPRINKLER DETAILS

SA-480530
SF511 NTS
B
2/22/2022 9:40:24 AM

A SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SF511
1 2 3 4 5 6 7 8 9 10

GENERAL PLUMBING NOTES GENERAL SUPPORT NOTES


US Army Corps of
1. ALL EQUIPMENT TO BE SELECTED FOR SITE CONDITIONS, 17. ALL THREADED PIPING (VALVES, EQUIPMENT AND FITTINGS) 1. ALL PIPE SUPPORTS TO CONFORM TO THE REQUIREMENTS OF Engineers ®
INCLUDING BUT NOT LIMITED TO LOCAL OUTSIDE AIR SHOWN ON THE DRAWING AS FITTING TO FITTING AND NOT MSS-SP-58 AND MSS-SP-69. Middle East District
G TEMPERATURE AND LOCAL SOIL CONDITION. DIMENSIONED TO BE INSTALLED USING 75 mm LONG PIPE
NIPPLES BETWEEN EACH ITEM UNLESS NOTED OTHERWISE. 2. SUPPORTS MUST BE CAPABLE OF RESISTING HORIZONTAL
AND VERTICAL FORCES INDUCED BY EARTHQUAKE IN
2. LEGENDS ARE COMPOSED OF STANDARD SYMBOLS AND ARE 18. PIPING AND SUPPORTS MUST NOT INTERFERE WITH ADDITION TO NORMAL LOADS DUE TO WEIGHT OF PIPE,

DATE
PERTINENT TO THE CONDITIONS ON THIS SET OF DRAWINGS. EQUIPMENT MAINTENANCE ACCESS OR FULL SPACE. PIPE FITTINGS, WEIGHT OF FLUID, INSULATION, AND LOADS DUE TO
ADDITIONAL LEGENDS AND/OR ANOTHER LEGEND SHEET MAY SUPPORTS MUST BE PROVIDED. THERMAL EXPANSION OR CONTRACTION. SUPPORTS ON
APPEAR IN THIS SET OF DRAWINGS TO INDICATE SPECIFIC OUTSIDE PIPING EXPOSED TO WIND TO BE CAPABLE TO
CONDITIONS. 19. ALL VALVES NOT ACCESSIBLE FROM THE FLOOR USING A 2m WITHSTAND 50 m/s WIND LOAD.
LADDER MUST BE PROVIDED WITH A CHAIN WHEEL
3. PLAN AND SECTION DRAWINGS ARE BASED ON SPECIFIC OPERATOR. 3. CONTRACTOR WILL BE RESPONSIBLE FOR THE DESIGN,
BASIS-OF-DESIGN EQUIPMENT MODELS. LAYOUT OF FABRICATION, AND INSTALLATION OF ALL PIPE SUPPORTS AND
EQUIPMENT, CONCRETE PADS, DUCT CONNECTIONS AND 20. A SUFFICIENT NUMBER OF UNIONS FOR THREADED PIPING SEISMIC BRACING.
PIPING EQUIPMENT TO BE VERIFIED AND ADJUSTED BY MUST BE INSTALLED TO ALLOW MAINTENANCE OR REMOVAL
CONTRACTOR TO MATCH ACTUAL EQUIPMENT FURNISHED. OF VALVES OR EQUIPMENT WITHOUT DISTURBANCE OF INTER- 4. CONTRACTOR WILL BE RESPONSIBLE FOR ALL
PHYSICAL CONSTRAINTS MAY PRECLUDE PURCHASE OF CONNECTING PIPE. DRAWINGS DO NOT INDICATE ALL SUPPLEMENTARY STEEL REQUIRED FOR PIPE SUPPORT
CERTAIN EQUIPMENT MODELS. PLACEMENT OF ACTUAL REQUIRED UNIONS. INSTALLATION.
EQUIPMENT FURNISHED TO NOT VIOLATE CODE RELATED
SPACE REQUIREMENTS, MANUFACTURER RECOMMENDED 21. EQUIPMENT PIPING CONNECTION SIZES AND CONFIGURATION 5. CONTROL VALVE AND MOTOR OPERATED VALVE OPERATORS
MAINTENANCE SPACE AND MANUFACTURER'S INSTALLATION SHOWN ON DRAWINGS ARE ESTIMATED AND MUST BE MUST BE BRACED FOR SEISMIC LOADS.

DESCRIPTION
INSTRUCTIONS TO PROTECT WARRANTY REQUIREMENTS. ADJUSTED FOR THE ACTUAL EQUIPMENT FURNISHED.
F UNLESS INDICATED OTHERWISE, A 300mm HIGH CONCRETE 6. ALL PIPE SUPPORTS AND SEISMIC BRACING REGARDLESS OF
HOUSEKEEPING PAD TO BE PROVIDED FOR ALL FLOOR 22. ALL EXPOSED STEEL PIPING MUST BE PAINTED. PIPE PAINTING PIPE SIZE AND WHETHER INDICATED ON DRAWINGS OR NOT,
MOUNTED MECHANICAL EQUIPMENT. AND COLOR CODE STANDARDS ARE PROVIDED IN DIVISION 22 TO MEET SPECIFIED PERFORMANCE REQUIREMENT.
AND 09 90 00 SPECIFICATION.
4. ALL ELEVATIONS SHOWN ARE ABOVE FINISHED FLOOR,
UNLESS NOTED OTHERWISE. 23. PIPING AND INSTRUMENT DIAGRAMS INDICATE LINE SIZE
CHANGE EITHER BY REDUCER SYMBOL OR BY INDICATING
5. ALL PIPING SYSTEMS AND DUCT SYSTEMS MUST HAVE BRANCH LINE SIZE.
MARKERS THAT INDICATE FLOW DIRECTION AND SERVICE. ALL
PIPING IDENTIFICATION MUST CONFORM TO MIL-STD 101. 24. ALL SOLDER TO BE LEAD-FREE FOR POTABLE AND NON-
PROVIDE DUCT MARKERS OR STENCILED SIGNS. LETTERING POTABLE WATER SYSTEMS.
FOR DUCTWORK TO BE MIN 32 mm HIGH.
25. ALL BALL VALVES 50mm AND SMALLER MUST BE FULL PORT
6. THE EXACT LOCATION AND SIZE OF EQUIPMENT PADS, BALL VALVES.
ROOF/WALL OPENINGS AND MOUNTING FRAMES MUST BE
COORDINATED IN THE FIELD WITH THE ACTUAL EQUIPMENT 26. CONTRACTOR MUST PROVIDE ALL PIPING WITH VALVED AND
FURNISHED. CAPPED HIGH POINT VENTS AND LOW POINT DRAINS TO

MARK
ALLOW VENTING, FILLING AND DRAINING ALL PIPE SECTIONS.
7. ACCESS PANEL IDENTIFICATION: ACCESS POINTS MUST BE UNLESS OTHERWISE INDICATED, SIZE TO BE 25 mm FOR PIPE
E PERMANENTLY IDENTIFIED ON EXTERIOR BY A LABEL, WITH 150 mm DIAMETER AND LARGER, 20 mm FOR PIPE 20 mm
LETTERING NOT LESS THAN 25 MM HIGH. THROUGH 100mm DIAMETER, AND LINE SIZE FOR PIPE
SMALLER THAN 20 mm DIAMETER. DRAWINGS DO NOT

PLOT SCALE: PLOT DATE:


2/7/2022 3:18:25
8. AVOID INSTALLING ANY PIPING OR EQUIPMENT ABOVE THE INDICATE ALL REQUIRED VENTS AND DRAINS.
ELECTRICAL PANELS OR EQUIPMENT OR WITHIN THE

SOLICITATION NO.:
ELECTRICAL CODES REQUIRED WORKING CLEARANCES FOR 27. CONTRACTOR MUST PROVIDE AND INSTALL ALL ITEMS SHOWN

SA-480530-1$-SP001GN.dwg
PM
CONTRACT NO.:
ELECTRICAL PANELS. WHEN PIPING MUST RUN ABOVE ON PIPING AND INSTRUMENT DIAGRAMS, WHETHER OR NOT
ELECTRICAL EQUIPMENT, APPROVAL OF THE OWNER MUST BE VISIBLE ON PIPING PLAN AND SECTION DRAWINGS. P&ID'S

ISSUE DATE:
OBTAINED TO INSTALL SHEET METAL TROUGH BETWEEN TAKE PREDEDENCE OVER PIPING PLAN AND SECTION
EQUIPMENT AND PIPING. DRAWINGS.

1:1
9. PROVIDE PERMANENT IDENTIFICATION AND AREA SERVED 28. ALL VALVE OPERATORS INCLUDING CONTROL VALVE AND
DESCRIPTION ON ALL EQUIPMENT. MOTOR OPERATED VALVE OPERATORS TO BE ORIENTED PER
MANUFACTURER'S INSTRUCTIONS AND TO AVOID
10. DO NOT LOCATE PLUMBING WORK IN ELECTRICAL OR INTERFERENCE WITH OTHER PIPING AND EQUIPMENT.

FILE NO.:
COMMUNICATION ROOMS, EXCEPT FOR RUNOUTS
SPECIFICALLY SERVING THE RESPECTIVE ROOM. 29. PIPING SYSTEMS MUST BE INSULATED. PIPING SYSTEMS

SUBMITTED BY:
GENERALLY REQUIRING INSULATION INCLUDE (BUT ARE NOT

DESIGN BY:

DRAWN BY:
11. ALL PIPING TO BE ROUTED MISSING ELECTRICAL, LIMITED TO) THE FOLLOWING DOMESTIC HOT WATER,
D

A. HANKS
N. PATEL
CKD BY:
COMMUNICATION AND STRUCTURAL COMPONENTS. DOMESTIC HOT WATER RECIRCULATING, DOMESTIC COLD

ANSI D
R. SIU
P. WU
WATER, AND CONDENSATE DRAIN.

SIZE:
12. ALL EQUIPMENT MOUNTINGS TO RESIST FORCES OF 0.5 TIMES
THE EQUIPMENT WEIGHT IN ANY HORIZONTAL DIRECTION AND 30. ALL MECHANICAL PIPING INSULATION (HVAC AND PLUMBING)
1.5 TIMES THE EQUIPMENT WEIGHT IN THE DOWNWARD IS SPECIFIED UNDER SECTION 23 07 00.

TRANSATLANTIC MIDDLE EAST DISTRICT


DIRECTION, UNLESS NOTED OTHERWISE EQUIPMENT
SUPPORT TO HAVE BRACING FOR 1.5 TIMES THE EQUIPMENT 31. PROVIDE ACCESS PANELS IN WALLS AND HARD SUSPENDED

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WEIGHT. CEILING, WHERE REQUIRED TO SERVICE CLEANOUTS,
VALVES, MIXING VALVES, TRAP PRIMERS, WATER HAMMER

WINCHESTER, VA 22602
13. PIPING BETWEEN EACH PLUMBING FIXTURE AND THE ARRESTORS AND OTHER CONCEALED PLUMBING
NEAREST BRANCH OR MAIN PIPING TO BE SIZED TO MATCH APPURTENANCES. WHERE POSSIBLE, USE SAME ACCESS
THE CORRESPONDING FIXTURE SCHEDULE CONNECTION SIZE PANEL TO SERVICE MORE THAN ONE ITEM WHEN LOCATED
AT A MINIMUM UNLESS NOTED AS A LARGER SIZE ON PLANS. DIRECTLY ADJACENT IN SAME IMMEDIATE VICINITY. REFER TO
PIPE HEADERS IN WALLS SERVING BANKS OF FIXTURES TO BE SPECIFICATIONS FOR ACCESS PANEL REQUIREMENTS.
FULL LINE SIZE FROM THE UPSTREAM END OF THE BRANCH
LINE TO THE END TERMINAL UNLESS OTHERWISE INDICATED. 32. PIPES PASSING THROUGH OR UNDER FOOTINGS OF
FOUNDATION WALLS MUST HAVE A RELIEVING ARCH OR
14. HORIZONTAL WASTEWATER DRAINAGE PIPING TO BE SLOPED SLEEVE. SUCH SLEEVE MUST BE OF PIPE SIZES LARGER THAN
AT 2% UNLESS OTHERWISE INDICATED. WHERE IT IS THE PIPE.
C IMPRACTICAL TO SLOPE AT 2 %, PIPING 100mm AND GREATER
IN SIZE MAY BE INSTALLED AT 1%. 33. TRENCHING OR BACKFILL: BACKFILL FOR PIPING MUST BE
FREE OF ROCK, BLOCK AND DEBRIS.
15. HORIZONTAL WASTE VENT PIPING TO BE GRADED TO DRIP
BACK BY GRAVITY TO THE SOIL OR WASTE PIPE WHICH IT 34. REFER TO STRUCTURAL DRAWING IN EACH BUILDING
SERVES. PACKAGE FOR BUILDING SEISMIC CATEGORY.

16. PIPING IS SHOWN FOR INFORMATION AND GENERAL ROUTING. 35. WASTE PIPE INVERTS ARE FROM FFE. LOWER PIPE INVERT
THE CONTRACTOR MUST PROVIDE FINAL ROUTING FOR ALL OUTSIDE OF BUILDING AS REQUIRED TO MAINTAIN MINIMUM
PIPING AND MUST PROVIDE SHOP DRAWINGS THAT INCLUDE: BURIAL DEPTH BELOW GRADE OF 610 MM FOR NON-TRAFFIC
EXACT DIMENSIONED ROUTING OF ALL PIPE, PIPE SIZE, LOADING AND 910 MM FOR TRAFFIC LOADING AS SHOWN IN

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


DIMENSIONED TIE-IN LOCATIONS, PIPE SUPPORT, AND FIRE CIVIL DETAILS. COORDINATE WITH STRUCTURAL ON ALL PIPE
WALL PENETRATION DETAILS. THE CONTRACTOR MUST AVOID PENETRATIONS.
INTERFERENCES WITH OTHER PIPING, EQUIPMENT, CODE

THAAD STANDARD FACILITIES

PLUMBING GENERAL NOTES


REQUIRED CLEARANCES, AND THE WORK OF OTHER 36. CONTRACTOR MUST INSTALL ALL REQUIRED FITTINGS TO

VARIOUS LOCATIONS, KSA


DISCIPLINES. FIELD ROUTED LIQUIFIED-FILLED PIPING NOT TO PROPERLY CONNECT ALL UNDERGROUND PLUMBING LINES

STANDARD DETAILS
BE ROUTED ABOVE ELECTRICAL OR ELECTRONIC EQUIPMENT. WITH CIVIL SITE LATERALS.

SA-480530
B
2/7/2022 3:18:25 PM

A SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SP001
1 2 3 4 5 6 7 8 9 10

US Army Corps of
ABBREVIATIONS PIPING Engineers ®
Middle East District
G & AND m METER W WASTE, ABOVE FLOOR
AC AIR COMPRESSOR m/s METERS PER SECOND
AD ACCESS DOOR m2 SQUARE METER

DATE
ADA AMERICANS WITH DISABILITIES ACT (STANDARDS) MAX MAXIMUM W WASTE, BELOW FLOOR
AFF ABOVE FINISHED FLOOR MBH ONE THOUSAND BRITISH THERMAL UNITS PER HOUR
AF ANTIFREEZE MECH MECHANICAL GRS GREASE WASTE, BELOW FLOOR
APPROX APPROXIMATE MFR MANUFACTURER
AVG AVERAGE MPG MEDIUM PRESSURE GAS
MIN MINIMUM, MINUTE
CD CONDENSATE DRAIN (CD)
BLDG BUILDING MISC MISCELLANEOUS
BLW BELOW mm MILLIMETER
BOP BOTTOM OF PIPE mm2 SQUARE MILLIMETER V VENT
BOT BOTTOM MD MOTOR OPERATED DAMPER
BTU BRITISH THERMAL UNIT MOCP MAXIMUM OVERCURRECT PROTECTION
BTUH BRITISH THERMAL UNITS PER HOUR MV MOTOR OPERATED VALVE CW COLD WATER (POTABLE)

DESCRIPTION
BV BALANCING VALVE MS MOP SINK (PLUMBING)
F MV MIXING VALVE HW HOT WATER (POTABLE)
MV MOTORIZED VALVE
C DEGREES CELSIUS
CA COMPRESSED AIR N NORTH HWR HOT WATER RECIRCULATION (POTABLE)
CD CONDENSATE DRAIN N/R NOT REQUIRED
CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED NA NOT APPLICABLE
CFM CUBIC FEET PER MINUTE NC NORMALLY CLOSED G NATURAL GAS
CHKV CHECK VALVE NEG NEGATIVE
CO CLEANOUT NG NATURAL GAS ICW INDUSTRIAL COLD WATER
CONT CONTINUATION NO NORMALLY OPEN
CONTR CONTRACTOR NOM NOMINAL
CA COMPRESSED AIR
NTS NOT TO SCALE
D DRAIN
DCW DOMESTIC COLD WATER ø DIAMETER

MARK
DF DRINKING FOUNTAIN OA OUTSIDE AIR
E DH DEHUMIDIFIER OCC OCCUPIED
DHC DUCT HEATING COIL OD OVERFLOW DRAIN
DHW DOMESTIC HOT WATER

PLOT SCALE: PLOT DATE:


2/7/2022 3:18:48
DHWR DOMESTIC HEATING WATER RECIRCULATION P PUMP
DISCH DISCHARGE Pa PASCAL PLUMBING
DN DOWN PC PUMPED CONDENSATE

SOLICITATION NO.:

SA-480530-1$-SP002AB.dwg
PM
CONTRACT NO.:
DWG DRAWING PCV PRESSURE REGULATING VALVE
BELL-UP DRAIN OR FUNNEL

ISSUE DATE:
PRV PRESSURE REDUCING VALVE
EA EACH PS PURGE SWITCH RECEPTOR W/ TRAP

1:1
EF EXHAUST FAN PSI POUNDS PER SQUARE INCH
EL ELEVATION FLOOR DRAIN W/ P-TRAP
ELEC ELECTRIC QTY QUANTITY WCO
EO ENGINE OIL CLEANOUT (WALL)
EQUIP EQUIPMENT RD ROOF DRAIN

FILE NO.:
ERV ENERGY RECOVERY VENTILATOR REQ'D REQUIRED FCO

SUBMITTED BY:
RM ROOM
CLEANOUT (FLOOR)
ES EMERGENCY SHOWER

DESIGN BY:

DRAWN BY:
D ET EXPANSION TANK RPBFD REDUCED PRESSURE BACK FLOW DEVICE

A. HANKS
N. PATEL
CKD BY:
EXT EXTERIOR RPBP REDUDED PRESSURE BACKFLOW PREVENTER

ANSI D
R. SIU
P. WU

SIZE:
RPM REVOLUTIONS PER MINUTE WATER HAMMER ARRESTOR
F FAHRENHEIT DEGREES RT RATE
FCO FLOOR CLEANOUT

TRANSATLANTIC MIDDLE EAST DISTRICT


FD FLOOR DRAIN s SECOND EMERGENCY EYEWASH

US ARMY CORPS OF ENGINEERS


FF FINISH FLOOR S SINK (PLUMBING)

201 PRINCE FREDERICK DRIVE,


FR FUNNEL RECEPTOR SA SUPPLY AIR

WINCHESTER, VA 22602
FS FLOOR SINK SAN SANITARY MIXING VALVE
SCFM STANDARD CUBIC FEET PER MINUTE
SD STORM DRAIN FCO
GA GAUGE, GAGE H SHOWER (PLUMBING) CLEANOUT (FLOOR)
GAL GALLON SOC SHUTOFF COCK CO
GM GAS METER SOV SHUTOFF VALVE CLEANOUT (PIPE)
GO GEAR OIL SPEC SPECIFICATION
GPF GALLONS PER FLUSH SQ SQUARE FLOOR SINK
C GPH GALLONS PER HOUR SS SERVICE SINK (PLUMBING) W/P-TRAP
GPM GALLONS PER MINUTE SSD SECONDARY STORM DRAIN
GR GREASE SYS SYSTEM
VENT THROUGH ROOF (VTR)
H HEIGHT TEMP TEMPERATURE
HB HOSE BIBB TD TRENCH DRAIN
HF HOSE FAUCET TP TRAP PRIMER BOX (IMB-1, UC-1 & WB-1)
HOR HORIZONTAL TF TRANSMISSION FLUID
HW HOT WATER TMV THERMOSTATIC MIXING VALVE

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


HWS HOT WATER SUPPLY TYP TYPICAL

PLUMBING LEGEND AND ABBREVIATIONS


HWR HOT WATER RETURN TW TEMPERED WATER
HTG HEATING

THAAD STANDARD FACILITIES


HUM HUMIDITY UNO UNLESS NOTED OTHERWISE

VARIOUS LOCATIONS, KSA


HVAC HEATING, VENTILATING AND AIR CONDITIONING UR URINAL (PLUMBING)

STANDARD DETAILS
HZ HERTZ (CYCLES/SECOND)
V VENT

SA-480530
B I CURRENT, ELECTRIC V VOLT, VOLTAGE
IBC INTERNATIONAL BUILDING CODE V/PH/HZ ELECTRICAL VOLTS/PHASE/HERTZ
ID INSIDE DIAMETER VEL VELOCITY
IE INVERT ELEVATION VERT VERTICAL
IMB ICE MAKER BOX VTR VENT THRU ROOF
IN INCH, INCHES
INCL INCLUDED W WASTE
INST INSTRUMENT, INSTRUMENTATION W WIDTH
INSUL INSULATION W/ WITH
INT INTERIOR W/O WITHOUT
INV INVERT WB WASHER BOX
IPC INTERNATIONAL PLUMBING CODE WC WATER CLOSET (PLUMBING)
IPS IRON PIPE SIZE WC WATER COLUMN
IW INDUSTRIAL WASTE WCO WALL CLEANOUT (PLUMBING)
2/7/2022 3:18:48 PM

WG WATER GAUGE
A L LAVATORY WH WATER HEATER, WALL HYDRANT SHEET ID
L LENGTH WHA WATER HAMMER ARRESTOR
L LITER WM WATER METER $
L/min LITERS PER MINUTE WT WEIGHT
L/s
LB
LITERS PER SECOND
POUND
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SP002
1 2 3 4 5 6 7 8 9 10

PIPE FITTINGS VALVES US Army Corps of


Engineers ®
Middle East District
G GATE VALVE
PIPE CAP OR ENDCAP

BLIND FLANGE GATE VALVE, SLIDE

DATE
CAP
PLUG VALVE
REDUCER

SLEEVE PLUG VALVE, 3-WAY


TP
TEST PLUG
CHECK VALVE
UNION

P-TRAP CHECK VALVE, STOP

VENT THROUGH ROOF (VTR)

DESCRIPTION
F CHECK VALVE, ANGLE STOP

ELBOW UP BALL VALVE


ELBOW DOWN
TEE UP BALL VALVE, 3-WAY

TEE DOWN
BALL VALVE, WITH VENT
WATER HAMMER ARRESTOR
BUTTERFLY VALVE
CLEANOUT
PET COCK

MARK
D QUICK DISCONNECT
ANGLE VALVE
E
A COMPRESSED AIR, BREATHING
AIR OR INSTRUMENT AIR DROP

PLOT SCALE: PLOT DATE:


BALANCING VALVE

2/7/2022 3:19:02
M METER

SOLICITATION NO.:

SA-480530-1$-SP003SY.dwg
CALIBRATED BALANCING VALVE

PM
CONTRACT NO.:
ROOF DRAIN; FLOOR DRAIN

ISSUE DATE:
GLOBE VALVE

1:1
CLOSURE, FLANGED
GLOBE VALVE, 3-WAY

CLOSURE, WELDED CAP NEEDLE VALVE

FILE NO.:
SUBMITTED BY:
CLOSURE, SCREWED CAP 3-WAY VALVE

DESIGN BY:

DRAWN BY:
D

A. HANKS
N. PATEL
CKD BY:

ANSI D
FOOT VALVE

R. SIU
P. WU

SIZE:
CONNECTION, PLUGGED

HOSE CONNECTION BALANCING VALVE

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


HOSE BIBB CALIBRATED BALANCING VALVE

WINCHESTER, VA 22602
CLAMP COUPLING ANGLE RELIEF VALVE; SAFETY RELIEF VALVE

INSULATING FLANGE OR BUSHING


TRIPLE DUTY VALVE
FLANGED CONNECTION

C ORIFICE
PRESSURE REDUCING VALVE

PRESSURE/TEMPERATURE BACKFLOW PREVENTER


PLUG (P/T PLUG)

DIAPHRAGM SEAL

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


FLEXIBLE PIPE CONNECTION

THAAD STANDARD FACILITIES


T

VARIOUS LOCATIONS, KSA


TEMPERATURE GAUGE

PLUMBING SYMBOLS
STANDARD DETAILS
SA-480530
B PIPE BREAK

PIPE LINE REDUCTION

FLOW LINE WITH


DIRECTION OF NFLOW

FLOW LINE WITH DUAL FLOW

SLOPE DIRECTION OF SLOPE


(TOWARD LOW POINT)
2/7/2022 3:19:02 PM

A SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SP003
1 2 3 4 5 6 7 8 9 10

FLOOR DRAIN OR FLOOR SINK


STRAINER US Army Corps of
INTERIOR WALL FINISHED FLOOR Engineers ®
BRONZE SCORIATED TOP
CENTER SURFACE Middle East District
BACK STOP MATERIAL SECURING SCREW SEE "S" DWGS
G FLOOR LINE FOR FLOOR SLOPING
HANGER ROD ESCUTCHEON TO
SEALANT PER FED. CONCRETE
BE PROVIDED IN

MAT SLAB

DATE
PIPE HANGER SPEC TT-C-595 FLOOR SLAB
FINISHED AREAS

600
LOW DENSITY PIPE FLANGED WITH FLASHING NEOPRENE
INSULATION COLLAR AS REQ'D GASKET
UNFINISHED AREA
(MINERAL FIBER) FINISHED THREADED
AREA PLUG SEE PLANS
CONTINUOUS INSULATION FOR SIZE DRAIN BODY POURED
THRU SLEEVE. PROVIDE IN PLACE
ALUM JACKET 50 BEYOND
FITTING TYPE AS TRAP GUARD
CAULKING OR ESCUTCHEON.
REQUIRED TO SUIT
EQ EQ 8 MIN. SPACE

MIN
100
PIPE ALL AROUND
PIPE SLEEVE

DESCRIPTION
(15-75 ONLY)
F 300
PER SPECS
18 GAUGE GALV
INSULATION SHIELD

INSULATION SHIELD DETAIL WALL PIPE SLEEVE DETAIL FLOOR CLEANOUT (FCO) DEEP SEAL "P" TRAP
NTS NTS NTS NTS

INDIRECT
WASTE PIPE
FROM MECH AIR GAP

MARK
EQUIP 4 FINGER SPIDER
SET TO PIPE GUIDE BOLTED
E MOVEMENT TO PIPE
FINISHED FLOOR

PLOT SCALE: PLOT DATE:


PIPE

3/11/2022
15:31:02
SOLICITATION NO.:

SA-480530-1$-SP501DT.dwg
CONTRACT NO.:
ISSUE DATE:
GUIDING

1:1
SLEEVE
DRAIN LINE FLOOR SINK OR FLOOR DRAIN
BOLT TO
SIDE VIEW SUPPORTING END VIEW

FILE NO.:
STRUCTURE

SUBMITTED BY:
DESIGN BY:

DRAWN BY:

A. HANKS
D

N. PATEL
CKD BY:

ANSI D
R. SIU
P. WU

SIZE:
PRESSURE REDUCING
CONDENSATE DRAIN TO FLOOR RECEPTOR DETAIL PIPE ALIGNMENT GUIDE STATION AS NEEDED
WHERE THE POTABLE
NTS NTS

TRANSATLANTIC MIDDLE EAST DISTRICT


WATER PRESSURE

US ARMY CORPS OF ENGINEERS


EXCEEDING 80 PSI

201 PRINCE FREDERICK DRIVE,


SHUTOFF VALVE
AT BUILDING PLUMBING

WINCHESTER, VA 22602
STRAINER POC WITH SITE CIVIL
CONTINUE TO
WATER METER BLDG SYSTEM
CONDENSATE REDUCING
DRAIN IN WALL START INSULATION
CONDENSATE LINE ELBOW
CENTERED OVER FUNNEL
REFER TO "M" DWG'S COUNTERTOP SEE "A" DWGS
FOR WALL
INFORMATION
C
MINIMUM 450,
BEVELED END PIPE SEE PLANS
MAXIMUM 1067
300

DISCHARGED BY AIR FOR SIZES RPZ TYPE SEE PLANS FOR


FROM TOP OF SINK OR LAVATORY BLDG MAIN SHUT OFF BACKFLOW SIZES
BREAK
STANDPIPE TO PREVENTER
INTO STANDPIPE
TRAP WEIR. PIPE FLANGE
CABINET
CONNECTION PIPE STAND (TYP)
DOOR
75 X 50

1500 MAX
762 MIN
INCREASER/REDUCER

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


IRON PIPE CLAMP 20 mm HEAVY DUTY HEX AIR GAP FITTING.
50 V SEE NUT WITH WASHER (TYP) DISCHARGE TO FLOOR
CHROME PLATED WASTE RECEPTOR.

THAAD STANDARD FACILITIES


PLANS 50 IRON STRAP

VARIOUS LOCATIONS, KSA


TAILPIECE WITH DRAIN
DRAIN CONN. IN WALL CONCRETE FLOOR

STANDARD DETAILS
PLUMBING DETAILS
50 SAN 20mm

SA-480530
HOSE CLAMP THREADED
B SEE PLANS
(TYP.) WALL ROD (TYP)
DEEP SEAL INSTALL
HEAVY DUTY BLACK
'P' TRAP ESCUTCHEON (TYP.) PRIOR TO
RUBBER HOSE
CONCRETE
"P" TRAP POUR
NOTE: COORDINATE CONDENSATE CONNECTION 100 mm (TYP) DRAIN LINE
LOCATIONS WITH MECHANICAL DRAWINGS FLOOR SINK
RECESSED TOE KICK
CONT ON OR FLOOR
FINISHED FLOOR SITE DWGS DRAIN
CONCRETE
THRUST BLOCK
3/11/2022 15:31:02

A CONDENSATE CONNECTION DETAIL CONDENSATE DRAIN TO TRAP DETAIL WATER SERVICE DETAIL SHEET ID
NTS N.T.S. NTS $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SP501
1 2 3 4 5 6 7 8 9 10

US Army Corps of
Engineers ®
Middle East District
G

DATE
STAY-OPEN BALL VALVE
NEMA 3R AMBER
DELUGE STROBE LIGHT
SHOWER HEAD
NEMA 3R HORN
EXTERIOR INTERIOR
NEMA 3R SWITCH
POWER SUPPLY
TYPICAL VERTICAL
FLOW SWITCH
FOUNDATION WALL NO-HUB COUPLING
(REF. STRUCTURAL PLANS) STAINLESS (TYPICAL)
STEEL PULL TEMPERED WATER -

DESCRIPTION
TYPICAL FOOTING ROD
F (REF. STRUCTURAL PLANS)
SEE PLANS FOR
SIZING.
CLEANOUT PLUG
REFERENCE SPECIFICATIONS
FOR TYPE

2080mm - 2438mm AFF


2-HEAD
PER SPEC. EYE/FACE WALL
WASH SPRAY ROUND STAINLESS STEEL
SAND COVER ABOVE PER SPEC. ASSEMBLY
RE: ARCH DWGS ACCESS COVER PLATE
FOR SIZE & TYPE REFERENCE SPECIFICATIONS
PLUMBING PIPING BELOW SLAB FOR TYPE

1750mm MAX
(REF. P100UG SERIES PLANS)

840mm - 1140mm AFF


STAINLESS
STEEL BOWL
SAND BASE ON SIDES
AND BELOW PER SPEC STAY-OPEN
1 FINISHED SLAB
BALL VALVE
1 WITH PUSH

MARK
FLAG HANDLE
FINISHED
NOTES: FLOOR
E FLOOR FLANGE
1. REFER TO STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION ON PIPE SUPPORT REQUIREMENTS.
2. COORDINATE EXCAVATION AND BACKFILL WITH CIVIL DESIGN.

PLOT SCALE: PLOT DATE:


3. BOTTOM OF TRENCH EXCAVATION SHALL NOT EXTEND BELOW 1/1 SLOPE LINE STARTING AT BASE OF FOOTING.

3/11/2022
15:31:03
SOLICITATION NO.:

SA-480530-1$-SP502DT.dwg
CONTRACT NO.:
ISSUE DATE:
PIPING NEAR FOOTING DETAIL EMERGENCY EYE/FACE WASH/SHOWER DETAIL TYPICAL WALL CLEANOUT

1:1
NTS NTS NTS

FILE NO.:
SUBMITTED BY:
INSTALL 150mm

DESIGN BY:

DRAWN BY:

A. HANKS
D

N. PATEL
CLEANOUT FLUSH TO

CKD BY:

ANSI D
R. SIU
P. WU

SIZE:
GRADE
FINISHED HARDSCAPE OR
150mm THICK CONCRETE PAVING
CONCRETE

TRANSATLANTIC MIDDLE EAST DISTRICT


OR FINISHED GRADE
FINISHED FLOOR COLLAR

US ARMY CORPS OF ENGINEERS


REFERENCE

201 PRINCE FREDERICK DRIVE,


TILE WHERE APPLICABLE
AROUND ARCHITECTURAL

WINCHESTER, VA 22602
FINISHED FLOOR. CONCRETE DRAIN FLOOR SINK (HALF GRATE)
TRADE TO FINISH THE TOP OF (REF. FINISHED FLOOR. CONCRETE TRADE AROUND
ARCH.) DRAIN PACK W/ PEA GRAVEL
FLOOR FLUSH WITH DRAIN. TO FINISH THE TOP OF FLOOR FLUSH 600mm MIN
WITH DRAIN. (REF. FINISHED FLOOR.
ARCH.) CONCRETE TRADE SHALL
REF. ARCH PLANS FINISH THE TOP OF AROUND
REF. ARCH PLANS DRAIN CONDENSATE PIPING.
FLOOR TO COORDINATE
DRAIN
WITH TILE INSTALLATION. (REFERENCE
DRAIN ARCH.) 50mm
C
FILTER FABRIC, ALL AROUND
1200mm
PERFORATION
25 mm CRUSHED STONE

CAST IRON DRAIN


BODY WITH PUSH-ON NOTE:

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


GASKET WALL, ADJUST SLOPE TO SUIT 150 mm DIA. P.V.C. PIPE. DRILL
REFERENCE SCHEDULES AND
INSTALLATION. 8 mm DIA. HOLES, 80 mm O.C.
CAST IRON DRAIN BODY SPECS FOR DOME OR FLAT
@90° FOR DRAINAGE.

THAAD STANDARD FACILITIES


WITH PUSH-ON GASKET BOTTOM FLOOR SINK

VARIOUS LOCATIONS, KSA


350
mm

STANDARD DETAILS
PLUMBING DETAILS
FINISHED AREAS NOTE: UNFINISHED AREAS
ADJUST SLOPE TO SUIT INSTALLATION.

SA-480530
B NOTE:

SAWCUT AND REMOVE EXISTING PAVING FOR


INSTALLATION OF DRYWELL PIT AND CONDENSATE PIPE. REPLACE PAVING
TO MATCH EXISTING.

FLOOR DRAIN DETAIL FLOOR SINK DETAIL DRYWELL DETAIL


NTS NTS NTS
3/11/2022 15:31:03

A SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SP502
1 2 3 4 5 6 7 8 9 10

US Army Corps of
REFER TO PLANS HANGER ROD PIPE CLAMPS WITH ELASTOMER Engineers ®
FOR SIZE/ LOCATION OR NYLON INSULATOR Middle East District
G
REFRIGERANT 25 CA

DATE
AIR DRYER PARTICULATE
FILTER/ REGULATOR 25 CA AIR/POL SUPPLY
COALESCING BY-PASS SEE PLANS FOR SIZE
FILTER SHUTOFF VALVE (NC) AND LOCATION
VALVE (TYP)
25 CA 25 CA
QUICK DISCONNECT MANUAL
PRESSURE COUPLING SHUTOFF (TYP)
CAR-1 P P GAUGE (TYP)
CAD-1
SEISMIC CAR-2
STRAP (TYP) UNINSULATED COPPER LINES INSULATED PIPE LINE WITH PIPE

DESCRIPTION
CLAMP. PROVIDE INSULATION
F METAL CHANNEL STRUT SHIELD ON 80mm AND LARGER.
RECEIVER
CONDENSATE LINES UNION (TYP)
25 CA S
S OIL WATER OIL LUBRICATOR
SEPARATOR DRIP LEG W/ NOTES:
PARTICULATE 1. REFER TO STRUCTURAL DRAWINGS FOR REQUIREMENTS
DRAIN VALVE ASSOCIATED WITH SECURING TO UNDERSIDE OF
FILTER/ REGULATOR AND CAP STRUCTURE

SAN
FLOOR SINK OR DRAIN
AUTO-DRAIN HOUSEKEEPING PAD
VALVE (TYP) SEE STRUCTURAL DWGS
MAINTENANCE PIT

MARK
E AIR COMPRESSOR DETAIL MAINTENANCE PIT AIR/POL SUPPLY DETAIL TRAPEZE PIPE HANGAR DETAIL
NTS NTS N.T.S.

PLOT SCALE: PLOT DATE:


SHUTOFF VALVE (TYP)

11:11:47 AM
3/15/2022
SOLICITATION NO.:

SA-480530-1$-SP503DT.dwg
CONTRACT NO.:
ISSUE DATE:
POL. SEE PLANS FOR SIZES

1:1
COMPRESSED AIR.
SEE PLANS FOR SIZES

FILE NO.:
SUBMITTED BY:
DESIGN BY:

DRAWN BY:

A. HANKS
D

N. PATEL
COMPRESSED AIR HEADER COMPRESSED AIR PIPE

CKD BY:

ANSI D
MOUNTING BRACKET

R. SIU
P. WU

SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
CONCRETE ANCHOR (TYP)

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


HOSE REEL 20mm (OR AS INDICATED ON PLANS)

WINCHESTER, VA 22602
SOV MOUNTING BRACKET
DOUBLE UNISTRUT
20mm BUSHING OR 100 mm CHANNEL
20mm COMBINATION PRESSURE
REGULATING VALVE/IN-LINE FILTER COUPLING
WITH INTEGRAL PRESSURE GAUGE
COMPRESSED AIR
PIPING 60 mm SCH 40 STEEL PIPE
FEMALE TYPE QUICK DISCONNECT
C AT 1m AFF 15mm ON 20mm DROP
AIR HOSE REEL MALE TYPE QUICK DISCONNECT
AT 1m AFF 15MM ON 20mm DROP
250 X 250 X 12 mm BASE
ROLLER SUPPORT PLATE WITH ANCHOR BOLTS
ARM KIT
AIR HOSE REEL
4572mm MAXIMUM

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


BALL STOP INSTALLED 4572mm MAXIMUM CONCRETE FLOOR
ROLLER SUPPORT ARM KIT INSTALLED HEIGHT
POL HOSE REEL TO DESIRED HEIGHT INSTALLED HEIGHT

THAAD STANDARD FACILITIES


BALL STOP INSTALLED

VARIOUS LOCATIONS, KSA


TO DESIRED HEIGHT

STANDARD DETAILS
PLUMBING DETAILS
SA-480530
B
AIR/POL HOSE REEL MOUNTING DETAIL AIR HOSE REEL CEILING MOUNT DETAIL TYPICAL AIR DROP DETAIL PIPE STANCHION DETAIL
NTS NTS NTS NTS
3/15/2022 11:11:47 AM

A SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SP503
1 2 3 4 5 6 7 8 9 10

ASME RATED
TEMPERATURE & HW
DHW THERMOSTATIC
PRESSURE RELIEF HWR THERMOMETER (TYP) US Army Corps of
CW BALANCE VALVE MIXING VALVE TMV-1 Engineers ®
VALVE CP-1
CEILING Middle East District
G BALL VALVE (TYP)
SEISMIC RESTRAINT
SYSTEM (TYP OF 2) VALVE CHECK VALVE
(TYP) 20 HWR HW

HW (120°F)
(TYP)

DATE
CW
600S200-68 BACKING CW
PLATE MIN. BETWEEN
DOUBLE STUDS ISOLATION VALVE EQ EQ

SECURE BACKING PLATE TO THERMOSTATIC CHECK


MIXING VALVE VALVE (TYP) EQ EQ
WALL WITH 9.5mm∅ x 90mm
MIN EMBED THREADED RODS AQUASTAT HW DIELECTRIC
IN HILTI `HY-150' ADHESIVE 25 CW UNION (TYP)
CIRCULATION PUMP

300
(ICBO #ER-5193) 406mm O.C.
AT MASONRY WALL OR #12 TEMPERATURE
HOSE CONNECTION AND PRESSURE HW
SMS @ 150mm O.C. TO

DESCRIPTION
W/ ISOLATION RELIEF VALVE (TYP)
F BACKING PLATE (TYP)
VALVE
FUSED DISCONNECT PIPE DISCHARGE HEAT TRAP
SWITCH & POWER. SEE FULL SIZE TO
ELECTRICAL DWGS. EXPANSION TANK FLOOR DRAIN PIPE
DWH- DISCHARGE
MOUNTED ON WALL DWH-1 DWH-2
20mm T&P RELIEF DRAIN ET- FULL SIZE TO
WITH MAPA EXPANSION
LINE FLOOR DRAIN
TANK CAGE. ET-1
ROUTE DRAIN LINE TO
NOTE: CW
APPROVED RECEPTOR.
1. INSTALL WITH A MINIMUM AMOUNT CW
100mm CONCRETE
OF EXPOSED PIPING AS NECESSARY
HOUSEKEEPING PAD
FOR DIRECT ACCESS TO VALVES
FINISHED FLOOR AND COMPONENTS. PIPING TO BE

MARK
CONCEALED WITHIN WALLS OR
ABOVE FINISHED CEILING WHERE
E POSSIBLE. 100mm CONCRETE
ROUTE PIPING TO HOUSEKEEPING PAD.
2. WATER HEATER STRAPPING TO BE AT NEAREST FLOOR REFER TO "S" DWGS

PLOT SCALE: PLOT DATE:


POINTS WITHIN THE UPPER ONE- RECEPTOR. DISCHARGE
THIRD AND LOWER ONE THIRD OF ITS

3/11/2022
15:31:04
WITH AIR GAP.

SOLICITATION NO.:

SA-480530-1$-SP504DT.dwg
VERTICAL DIMENSIONS. AT THE
DRAIN VALVE (TYP)

CONTRACT NO.:
LOWER POINT, A MINIMUM ONE-THIRD.

ISSUE DATE:

1:1
ELECTRIC WATER HEATER DETAIL TWO ELECTRIC WATER HEATER DETAIL HW TO FIXTURES THERMOSTATIC MIXING
VALVE. SET AT 110°F.
NTS NTS

FILE NO.:
SUBMITTED BY:
BALL VALVE (TYP)

DESIGN BY:

DRAWN BY:

A. HANKS
D

N. PATEL
CKD BY:

ANSI D
R. SIU
P. WU

SIZE:
CW

HW

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
TYP THERMOSTATIC MIXING VALVE DETAIL
NTS

SEE FLOOR PLAN FOR SIZE

GRATE
6096mm
C NOTES:
SUMP PUMP CONTROLLER PRESSURE 1. FOR BRANCH LINES 6096mm OR
GAUGE INLINE PDI LESS, INSTALL WATER HAMMER
DISCHARGE SHUTOFF VALVE ARRESTER BETWEEN LAST TWO
CIRCULATING
FISXTURES.
PRESSURE PUMP
BOTTOM OF SHUT OFF SNUBBER 2. FOR BRANCH LINES OVER
MAINTENANCE VALVE 6096mm, TWO WATER HAMMER
PIT FLOOR AQUASTAT P 15 mm ARRESTER UNITS SHOULD BE
ACCESS PANEL USED. THE SECOND ONE PLACED

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


CHECK SHUT OFF GAUGE COCK (TYP) AS REQUIRED AT THE MIDPOINT OF THE LINE.
VALVE VALVE (TYP)

THAAD STANDARD FACILITIES


A

VARIOUS LOCATIONS, KSA


FLOAT SWITCH (HIGH ALARM) THERMOMETER W/
25mm

STANDARD DETAILS
SEPARABLE SOCKET

PLUMBING DETAILS
FLOAT SWITCH (PUMP ON) WATER HAMMER ARRESTER SCHEDULE

SA-480530
STRAINER CHECK VALVE HOSE BIBB AT PDI * A B C D E F
B LOW POINT
FIXTURE UNITS 1-11 12-32 33-60 61-113 114-154 155-330
SEE STRUCTURAL DRAWINGS FOR
CONCRETE TRENCH DETAILS AND NOTE: PIPE SIZE (mm) 20 25 25 25 25 25
EXACT LOCATION
SUBMERSIBLE GENERIC SYMBOL USED TO SHOW VALVE LOCATION(S). * PDI = PLUMBING AND DRAINAGE INSTITUTE.
SUMP PUMP REFER TO SPECIFICATIONS FOR EXACT VALVE TYPE.
DRAIN SHOWN WITH SIDE OUTLET. DRAIN MAY
FLOAT SWITCH (PUMP OFF) ALSO BE INSTALLED WITH BOTTOM OUTLET. ENTIRE ASSEMBLY SHOWN ON DRAWING AS

MAINTENANCE PIT SUMP PUMP DETAIL TRENCH DRAIN DETAIL RECIRCULATION PUMP DETAIL WATER HAMMER ARRESTOR DETAIL
3/11/2022 15:31:04

A NTS NTS NTS NTS SHEET ID


$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SP504
1 2 3 4 5 6 7 8 9 10

DOUBLE LINE DUCTWORK SYMBOLS MECHANICAL


MECHANICAL GENERAL
GENERAL NOTES
NOTES
PA
PIPE ANCHOR
HWS HEATING-HOT WATER SUPPLY
PG RECTANGULAR DUCT (FIRST FIGURE IS FOR SIDE
PIPE GUIDE OR SLEEVES 300x150 SHOWN, SECOND FIGURE IS FOR SIDE NOT TAP-IN BRANCH, RECTANGULAR 1. SEE SH G-003 FOR ABBREVIATIONS, CHARACTER IDENTIFIERS US Army Corps of
HWR HEATING-HOT WATER RETURN IN LINES ON PIPING LEGEND ARE ALSO USED FOR
EXPANSION JOINT SHOWN) Engineers ®
VD
ABBREVIATIONS.
CHS CHILLED WATER SUPPLY Middle East District
VENTURI
G CHR CHILLED WATER RETURN GATE VALVE 300ø ROUND DUCT
2. MECHANICAL LAYOUTS ARE SCHEMATIC. PROVIDE ANY
BRANCH DUCT, CONICAL LATERAL ADDITIONAL DROPS, RISES, OR OFFSETS REQUIRED FOR A
GCS GLYCOL COOLANT SUPPLY GLOBE VALVE COMPLETE INSTALLATION,COORDINATE EXACT ROUTING OF
FITTING, ROUND OR FLAT OVAL

DATE
HOSE VALVE WITH CAP WORK WITH ALL OTHER TRADES AND OBSTRUCTIONS. WORK
GCR GLYCOL COOLANT RETURN 300x150Ɵ FLAT OVAL DUCT (FIRST FIGURE IS FOR SIDE WITH LIGHTS, CEILING GRID, AND OTHER OBSTRUCTIONS.
BUTTERFLY VALVE SHOWN, SECOND FIGURE IS FOR SIDE NOT
D CONDENSATE DRAIN SHOWN) BRANCH DUCT, CONICAL TEE FITTING,
3. UNLESS OTHERWISE INDICATED, ROUTE ALL DUCTWORK AND
CHECK VALVE ROUND OR FLAT OVAL
FLEXIBLE ROUND DUCT PIPING ABOVE CEILINGS. ROUTE ALL DUCTWORK AND PIPING
C COLD CONDENSER WATER AS HIGH AS POSSIBLE IN AREAS WITHOUT CEILINGS.
A BALANCING VALVE
MU MAKE-UP WATER BRANCH DUCT, "Y" FITTING, ROUND OR
FLEXIBLE DUCT CONNECTION FLAT OVAL 4. DUCT DIMENSIONS ARE INSIDE CLEAR DIMENSIONS. INCREASE
CALIBRATED BALANCING VALVE
HG REFRIGERANT HOT GAS SHEET METAL DIMENSIONS ON LINED DUCTWORK TO MAINTAIN
PICBV TWO WAY PRESSURE INDEPENDENT THE INSIDE CLEAR DIMENSIONS INDICATED.
DAMPERS
RS REFRIGERANT SUCTION CONTROL AND BALANCING VALVE SUPPLY DUCT SECTION
BDD: BACKDRAFT DAMPER
BDD
FSD: FIRE/SMOKE DAMPER 5. UNLESS OTHERWISE INDICATED, PROVIDE DUCT RUNOUTS TO
RL REFRIGERANT LIQUID AUTOMATIC FLOW CONTROL VALVE RETURN/EXHAUST DUCT SECTION TERMINAL UNITS SAME SIZE AS TERMINAL UNIT INLET.
FD: FIRE DAMPER
CP CONDENSATE PUMP DISCHARGE MD: MOTORIZED DAMPER
BALL VALVE SD: SMOKE DAMPER 6. SIZE FLEXIBLE DUCT RUNOUTS TO TERMINAL AIR DEVICES AS
90° ELBOW TURNED UP, RECTANGULAR

DESCRIPTION
FOS FUEL-OIL SUPPLY VD: VOLUME DAMPER FOLLOWS:
F PLUG VALVE SP: SECURE PENETRATION
FOR FUEL-OIL RETURN S 90°ELBOW TURNED DOWN, RECTANGULAR SIZE L/s
FOV FUEL-OIL VENT SOLENOID VALVE DUCT TRANSITION, ROUND OR FLAT OVAL
TO RECTANGULAR 125ø 0-30
RHS REHEAT HOT WATER SUPPLY SAFETY OR PRESSURE RELIEF, ANGLE VALVE 90° ELBOW TURNED UP, ROUND 150ø 35-50
DUCT TRANSITION, RECTANGULAR TO
RHR REHEAT HOT WATER RETURN SAFETY OR PRESSURE RELIEF, STRAIGHT ROUND OR FLAT OVAL 175ø 55-75
THRU VALVE 90° ELBOW TURNED DOWN, ROUND
P.R.S PRESSURE REDUCING STATION 200ø 80-110
PRESSURE REDUCING VALVE (PRV) DUCT TRANSITION, RECTANGULAR, ROUND, OR 225ø 115-150
FLAT OVAL 90° ELBOW TURNED UP, FLAT OVAL
AUTOMATIC CONTROL VALVE, 2 WAY
250ø 155-200
AUTOMATIC CONTROL VALVE, 3 WAY
INCLINED RISE W/RESPECT TO AIR FLOW, 300ø 205-330
R 90° ELBOW TURNED DOWN, FLAT OVAL
RECTANGULAR
BLIND FLANGE

MARK
LATERAL Y INCLINED DROP W/RESPECT TO AIR FLOW,
D CEILING DIFFUSER (4-WAY THROW UNLESS 7. INSTALL CALIBRATED BALANCING VALVES AND VENTURIS
RECTANGULAR
INDICATED OTHERWISE BY ARROWS) WITH A MINIMUM UNRESTRICTED STRAIGHT RUN OF 5 PIPE
E SYSTEM TYPES AND ABBREVIATIONS
CAP
DIAMETERS UPSTREAM AND 3 PIPE DIAMETERS
ELBOW, 90° INCLINED RISE W/RESPECT TO AIR FLOW, DOWNSTREAM.
R CEILING DIFFUSER (4-WAY THROW UNLESS
ROUND OR FLAT OVAL

PLOT SCALE: PLOT DATE:


ELBOW, 90° TURNED UP INDICATED OTHERWISE BY ARROWS) 8. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT

10:12:58 AM
ELBOW 90°, TURNED DOWN INCLINED DROP W/RESPECT TO AIR FLOW, ROUND LOCATIONS OF DIFFUSERS, LINEAR SLOT DIFFUSERS,

2/22/2022
SAD SUPPLY AIR DUCT (SAD) D OR FLAT OVAL

SOLICITATION NO.:

SA-480530-1$-SM001GN.dwg
CEILING REGISTER OR GRILLE (RETURN ) REGISTERS, AND GRILLES.
ELBOW, 45°

CONTRACT NO.:
9. ALL WORK INDICATED IS NEW UNLESS INDICATED AS

ISSUE DATE:
EAD EXHAUST AIR DUCT (EAD) TEE 90° ELBOW, RECTANGULAR WITH TURNING VANES
CEILING REGISTER OR GRILLE (SUPPLY) EXISTING.

1:1
TEE, OUTLET TURNED UP
10. RELOCATE ALL EXISTING HANGERS, CONDUITS, WIRING,
RAD RETURN AIR DUCT (RAD) TEE, OUTLET TURNED DOWN REGISTER OR GRILLE PIPING, AND DUCTWORK AS NECESSARY TO PROVIDE PIPING
45° ELBOW, RECTANGULAR
AND DUCTWORK AS INDICATED.
CONCENTRIC REDUCER
FAD FRESH AIR DUCT (FAD) CEILING DIFFUSER WITH FLEXIBLE DUCT
11. VERIFY EXACT SIZES AND LOCATIONS OF EXISTING WORK
CONNECTION (4-WAY THROW UNLESS

FILE NO.:
90° ELBOW, ROUND OR FLAT BEFORE PURCHASING OR FABRICATING NEW WORK FOR
ECCENTRIC REDUCER (STRAIGHT INVERT) INDICATED OTHERWISE BY ARROWS)
OVAL (SMOOTH OR 5 PIECE CONNECTION TO OR INSTALLATION IN EXISTING WORK.

SUBMITTED BY:
REL RELIEF AIR DUCT (REL) UNION

C. HAIRSTON

C. HAIRSTON
ELBOWS)

DESIGN BY:

DRAWN BY:
LIGHT TROFFER WITH FLEXIBLE DUCT 12. SOME SYMBOLS INDICATED ON THIS LEGEND SHEET MAY NOT

A. HANKS
D

C. CURSI
FLEXIBLE PIPE CONNECTION

CKD BY:
S-000 APPEAR ON THE DRAWINGS.

ANSI D
CONNECTION "S" INDICATES SOFFIT,
TAD TRANSFER AIR DUCT (TAD) MITERED 90° ELBOW, ROUND OR FLAT OVAL

SIZE:
NUMBER INDICATES CFM
PRESSURE GAGE WITH SHUT OFF COCK AND 13. DO NOT LOCATE MECHANICAL WORK IN ELECTRICAL OR
SIPHON OR PULSATION DAMPENER. CEILING LINEAR SLOT OR INTEGRATED CEILING COMMUNICATION ROOMS, EXCEPT FOR RUNOUTS
DCD DUST COLLECTION DUCT (DCD)
SPECIFICALLY SERVING THE RESPECTIVE ROOM.

TRANSATLANTIC MIDDLE EAST DISTRICT


45° ELBOW, ROUND OR FLAT OVAL DIFFUSER (CLSD) WITH FLEXIBLE DUCT
T CONNECTION (ARROWS INDICATE THROW
(SMOOTH OR 3 PIECE ELBOWS)

US ARMY CORPS OF ENGINEERS


SPS DIRECTIONS) 14. DUCTS CROSSING WALLS WITH A RATING OF ONE-HOUR OR

201 PRINCE FREDERICK DRIVE,


TEMPERATURE GAGE
LESS MUST HAVE GALVANIZED DUCTWORK OF AT LEAST 1.2

WINCHESTER, VA 22602
VD
STATIC PRESSURE SENSOR mm THICK.
THERMOMETER DIVIDED FLOW FITTING
PT VD
PRESSURE/TEMPERATURE TEST PORT HUMIDIFIER
DOUBLE CHECK VALVE BACKFLOW H
PREVENTER DUCT W/LINING (SPECIFIED WHEN SHOWN
TYPICAL RECTANGULAR, ROUND, OVAL) SEE
MECHANICAL GENERAL NOTE 4.

C SINGLE LINE DUCTWORK SYMBOLS MISC SYMBOLS


300x150 RECTANGULAR DUCT (FIRST FIGURE IS 90° ELBOW, ROUND OR FLAT OVAL 0000 ROOM NUMBER
FM TT TEMPERATURE TRANSMITTER
FOR SIDE SHOWN, SECOND FIGURE IS (SMOOTH OR 5-PIECE ELBOWS) ø ROUND DUCT FLOW METER
1500ø FOR SIDE NOT SHOWN)
ROUND DUCT 45° ELBOW, RECTANGULAR WATER SENSOR (LOCATED BELOW ACCESS FLOOR) DPT DIFFERENTIAL PRESSURE TRANSMITTER
HD HEAT DETECTOR P
900x450Ɵ 45° ELBOW, ROUND OR FLAT OVAL
FLAT OVAL DUCT (FIRST FIGURE IS FOR PRE-FILTER P PRESSURE SENSOR
(SMOOTH OR 3-PIECE ELBOWS)
SIDE SHOWN, SECOND FIGURE IS FOR SD SMOKE DETECTOR
SIDE NOT SHOWN) DIVIDED FLOW FITTING, RECTANGULAR F

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)

MECHANICAL LEGEND AND GENERAL NOTES


FLEXIBLE ROUND DUCT DF
DPS DIFFERENTIAL PRESSURE SENSOR MOV MOTOR OPERATED VALVE
RECTANGULAR TAP-IN BRACH OR F
FLEXIBLE DUCT CONNECTION ROUND OR FLAT OVAL CONICAL TEE VFD VARIABLE FREQUENCY DRIVE

THAAD STANDARD FACILITIES


FINAL FILTER M BDD

VARIOUS LOCATIONS, KSA


INCLINED CONICAL TAKE-OFF, ROUND OR
FLAT OVAL ATFP ANTI TERRORISM / FORCE PROTECTION SWITCH F

STANDARD DETAILS
DAMPERS M: MOTORIZED DAMPER
BDD: BACKDRAFT DAMPER BDD: BACKDRAFT DAMPER
"Y" FITTING, ROUND OR FLAT OVAL AI ANALOG INPUT C
FSD: FIRE/SMOKE DAMPER

SA-480530
FD: FIRE DAMPER COOLING COIL
B BDD
MD: MOTORIZED DAMPER 90° ELBOW TURNED UP, RECTANGULAR
AO ANALOG OUTPUT FAN
SD: SMOKE DAMPER C
VD: VOLUME DAMPER DI DIGITAL INPUT
90° ELBOW TURNED, DOWN, RECTANGULAR
R
DUCT TRANSITION DO DIGITAL OUTPUT
90° ELBOW TURNED UP, ROUND, FLAT HOT GAS REHEAT PUMP
R
INCLINED RISE W/RESPECT TO AIR OVAL SIMILAR
INTERVAL TIMER H
FLOW, RECTANGULAR 90° ELBOW TURNED DOWN, ROUND, FLAT
D OVAL SIMILAR CO CARBON MONOXIDE SENSOR EXHAUST FAN / VENTILATOR
D
INCLINED DROP W/RESPECT TO AIR
FLOW, RECTANGULAR CEILING DIFFUSER (ARROWS INDICATE E HVAC EMERGENCY SHUTDOWN PUSHBUTTON DIRECT EXPANSION COOLING COIL
R THROW DIRECTIONS) H HUMIDISTAT AIR DEVICE TYPE (SEE AIR DEVICE SCHEDULE)
X S1A
INCLINED RISE W/RESPECT TO AIR AIR DEVICE AIRFLOW (L/S)
FLOW, ROUND OR FLAT OVAL CEILING REGISTER OR GRILLE,RETURN H2 HYDROGEN SENSOR 150
D E
2/22/2022 10:12:58 AM

FLOW ARROWS INDICATE AIRFLOW


INCLINED DROP W/RESPECT TO AIR M METER ELECTRICAL HEATING COIL DIRECTION (WHEN LESS THAN 4-WAY
FLOW, ROUND OR FLAT OVAL CEILING REGISTER OR GRILLE, SUPPLY THROW)
NO NITROGEN MONOXIDE SENSOR H
A 90° ELBOW, RECTANGULAR WITH SHEET ID
STATIC PRESSURE SENSOR S WALL SWITCH TYPICAL CLEARANCE FOR
TURNING VANES SPS
MECHANICAL EQUIPMENT
END OF DUCT RUN SP STATIC PRESSURE SENSOR MECHANICAL
$
LOUVER EQUIPMENT
T THERMOSTAT
SM001
V FUEL VAPOR SENSOR
1 2 3 4 5 6 7 8 9 10

GENERAL MECHANICAL NOTES GENERAL HVAC NOTES GENERAL PIPING NOTES GENERAL INSTRUMENTATION NOTES
1. ALL EQUIPMENT MUST BE SELECTED FOR SITE CONDITIONS. 1. ALL FIRE/SMOKE DAMPERS MUST BE INSTALLED IN 1. PIPING IS SHOWN FOR INFORMATION AND GENERAL ROUTING. 1. INSTRUMENT PIPING CONNECTIONS ARE NOT DIMENSIONED ON
THE CONTRACTOR MUST PROVIDE FINAL ROUTING FOR ALL THE DRAWINGS. THE CONNECTION LOCATIONS SHOWN ARE US Army Corps of
ACCORDANCE WITH SHEET METAL AND AIR CONDITIONING
2. LEGENDS ARE COMPOSED OF STANDARD SYMBOLS AND ARE NATIONAL ASSOCIATION (SMACNA) SMOKE, AND RADIATION PIPING AND MUST PROVIDE SHOP DRAWINGS THAT INCLUDE: INTENDED TO SERVE AS A GENERAL GUIDE ONLY TO ILLUSTRATE Engineers ®
PERTINENT TO THE CONDITIONS ON THIS SET OF DRAWINGS. DAMPER INSTALLATION GUIDE FOR HVAC SYSTEMS, UL, IBC, EXACT DIMENSIONED ROUTING OF ALL PIPE, PIPE SIZE, THE DESIRED LOCATIONS OF THE CONNECTIONS. FOR Middle East District
G ADDITIONAL LEGENDS AND/OR ANOTHER LEGEND SHEET MAY
APPEAR IN THIS SET OF DRAWINGS TO INDICATE SPECIFIC
AND DAMPER MANUFACTURER'S RECOMMENDATIONS. DIMENSIONED TIE-IN LOCATIONS AT EXISTING PIPING, AND
FIRE WALL PENETRATION DETAILS. THE CONTRACTOR MUST
INSTRUMENT CONNECTIONS NOT IDENTIFIED ON PIPING DRAWING
REFER TO PIPING OR AIRFLOW AND INSTRUMENTATION
CONDITIONS. 2. ALL RECTANGULAR DUCT ELBOWS MUST HAVE TURNING AVOID INTERFERENCES WITH OTHER PIPING, EQUIPMENT, DIAGRAMS FOR RELATIVE LOCATIONS. THE CONTRACTOR MUST
VANES UNLESS NOTED OTHERWISE. ALL UNEQUAL TURNING CODE REQUIRED CLEARANCES, AND THE WORK OF OTHER AVOID NTERFERENCE WITH OTHER INSTRUMENT CONNECTIONS,

DATE
3. PLAN AND SECTION DRAWINGS ARE BASED ON SPECIFIC VANES MUST HAVE SINGLE-THICKNESS TURNING VANES WITH DISCIPLINES. FIELD ROUTED LIQUID-FILLED PIPING MUST NOT PIPING, EQUIPMENT, AND THE WORK OF OTHER DISCIPLINES.
BASIS-OF-DESIGN EQUIPMENT MODELS. LAYOUT OF TRAILING EDGE. NOT ALL TURNING VANES ARE INDICATED ON BE ROUTED ABOVE ELECTRICAL OR ELECTRONIC EQUIPMENT. WHERE PRESSURE AND TEMPERATURE CONNECTIONS ARE
EQUIPMENT, CONCRETE PADS, DUCT CONNECTIONS AND THE DRAWINGS. SHOWN ADJACENT TO EACH OTHER, A MINIMUM DISTANCE OF
PIPING EQUIPMENT MUST BE VERIFIED AND ADJUSTED BY 2. ALL THREADED PIPING (VALVES, EQUIPMENT, AND FITTINGS) 300mm MUST BE MAINTAINED BETWEEN INSTRUMENT
CONTRACTOR TO MATCH ACTUAL EQUIPMENT FURNISHED. 3. ALL DUCT MUST BE SEAL CLASS A IN ACCORDANCE WITH SHOWN ON THE DRAWING AS FITTING TO FITTING AND NOT CONNECTIONS WHERE POSSIBLE.
PHYSICAL CONSTRAINTS MAY PRECLUDE PURCHASE OF SMACNA HVAC DUCT CONSTRUCTION STANDARDS UNLESS DIMENSIONED MUST BE INSTALLED USING 75 mm LONG PIPE
CERTAIN EQUIPMENT MODELS. PLACEMENT OF ACTUAL NOTED OTHERWISE. NIPPLES BETWEEN EACH ITEM UNLESS NOTED OTHERWISE. 2. ALL PRESSURE INSTRUMENTATION MUST BE FOR 20 mm DIA
EQUIPMENT FURNISHED MUST NOT VIOLATE CODE RELATED PIPING. TEMPERATURE TAPS MUST BE SUITABLE FOR
SPACE REQUIREMENTS, MANUFACTURER RECOMMENDED 4. ALL DUCT MUST BE DESIGNED FOR 500 PASCAL POSITIVE OR 3. PIPING AND SUPPORTS MUST NOT INTERFERE WITH THERMOWELL, IN NO CASE LESS THAN 20 mm. ALL PRESSURE
MAINTENANCE SPACE, MANUFACTURER'S INSTALLATION NEGATIVE PRESSURE IN ACCORDANCE WITH SMACNA HVAC EQUIPMENT MAINTENANCE ACCESS OR PULL SPACE. PIPE INSTRUMENTATION MUST BE PROVIDED WITH A 20 mm ISOLATION
INSTRUCTIONS AND WARRANTY ISSUES. UNLESS INDICATED DUCT CONSTRUCTION STANDARDS UNLESS NOTED SUPPORTS MUST BE PROVIDED. BALL VALVE.
OTHERWISE, A 150 mm HIGH CONCRETE HOUSEKEEPING PAD OTHERWISE.
MUST BE PROVIDED FOR ALL FLOOR MOUNTED MECHANICAL 4. ALL VALVES NOT ACCESSIBLE FROM THE FLOOR USING A 2m 3. INSTRUMENTATION (FOR EXAMPLE, PI, TI, PDI) IS NOT ALL SHOWN
EQUIPMENT. 5. ALL DUCT SIZE DIMENSIONS INDICATED ON THE DRAWINGS LADDER MUST BE PROVIDED WITH A CHAIN WHEEL ON PLAN DRAWINGS. CONTRACTOR MUST PROVIDE
ARE CLEAR INSIDE DIMENSIONS. OPERATOR. INSTRUMENTATION AS INDICATED ON CONTROL DIAGRAMS AND

DESCRIPTION
4. ALL ELEVATIONS SHOWN ARE ABOVE FINISHED FLOOR, MUST LOCATE DEVICES SUCH THAT A PERSON CAN EASILY READ
F UNLESS NOTED OTHERWISE. 6. ALL HVAC PENETRATIONS EQUAL OR GREATER THAN 62000 5. A SUFFICIENT NUMBER OF UNIONS FOR THREADED PIPING GAUGE WHILE STANDING ON FLOOR.
SQUARE MILLIMETERS AND ALONG THE SECURE BOUNDARY MUST BE INSTALLED TO ALLOW MAINTENANCE OR REMOVAL
5. ALL PIPING SYSTEMS AND DUCT SYSTEMS MUST HAVE MUST HAVE MANBARS. OF VALVES OR EQUIPMENT WITHOUT UNDUE DISTURBANCE 4. THERMOSTATS AND ROOM TEMPERATURE TRANSMITTER MUST
MARKERS THAT INDICATE FLOW DIRECTION AND SERVICE. ALL OF INTER-CONNECTING PIPE. DRAWINGS DO NOT INDICATE BE MOUNTED 1.2m AFF UNLESS NOTED OTHERWISE.
PIPING IDENTIFICATION MUST CONFORM TO MIL-STD 101. 7. DUCT SMOKE DETECTORS WHERE SHOWN ON PLANS OR ALL REQUIRED UNIONS.
PROVIDE DUCT MARKERS OR STENCILED SIGNS. LETTERING DETAILS MUST BE INSTALLED PER NFPA 72E, 90A AND 5. THE INSTRUMENT AND CONTROL MUST PIGGY BACK ON FIBER
FOR DUCTWORK MUST BE MIN 32 mm HIGH. MANUFACTURER'S REQUIREMENTS. ACCESS PANEL TO THE 6. EQUIPMENT PIPING CONNECTION SIZES AND CONFIGURATION OPTIC CABLE WHEN BEING ROUTED BETWEEN BUILDINGS.
DETECTORS MUST BE PROVIDED. SHOWN ON DRAWINGS ARE ESTIMATED AND MUST BE PROVIDE COPPER CABLING TO BE ROUTED FROM THE I&C
6. THE EXACT LOCATION AND SIZE OF EQUIPMENT PADS, ADJUSTED FOR THE ACTUAL EQUIPMENT FURNISHED. EQUIPMENT TO THE COMMS ROOM AND THE MEDIA
ROOF/WALL OPENINGS AND MOUNTING FRAMES MUST BE 8. USE STAINLESS STEEL EXHAUST DUCT FOR THE FIRST 15 CONVERTER/FIBER OPTIC CONVERTER (FOC) .
COORDINATED IN THE FIELD WITH THE ACTUAL EQUIPMENT FEET OF SHOWER EXHAUST. GRILLES IN SHOWER MUST BE OF 7. ALL EXPOSED STEEL PIPING MUST BE PAINTED.
FURNISHED. STAINLESS STEEL. 6. POINT LIST PROVIDED ARE MINIMUM REQUIRED POINTS. PROVIDE
8. PIPING AND INSTRUMENT DIAGRAMS INDICATE LINE SIZE ADDITIONAL POINTS AND INSTRUMENTATION TO PROVIDE
7. ACCESS PANEL IDENTIFICATION: ACCESS POINTS MUST BE 9. DUCT AND PLENUM ACCESS PANEL/DOORS MUST BE PIANO CHANGE EITHER BY REDUCER SYMBOL OR BY INDICATING COMPLETE OPERABLE SYSTEM IN COMPLIANCE WITH THE
PERMANENTLY IDENTIFIED ON EXTERIOR BY A LABEL, WITH HINGED, GASKETED AND DOUBLE SASH LOCKED. BRANCH LINE SIZE. SEQUENCE OF OPERATIONS AND DIAGRAMS. THE BAS MUST
LETTERING NOT LESS THAN 25 mm HIGH. TREND EVERY 15 MINUTES (INITIAL SETTING) FOR EACH POINT

MARK
10. CEILING DIFFUSER, RETURN AND EXHAUST GRILLE SIZES 9. ALL SOLDER MUST BE LEAD-FREE FOR POTABLE AND NON- IDENTIFIED IN THE POINT LIST TO BE TRENDED, UNLESS NOTED
8. AVOID INSTALLING ANY PIPING OR EQUIPMENT ABOVE THE SHOWN ON PLANS AND IN EQUIPMENT SCHEDULES ARE NECK POTABLE WATER SYSTEMS. OTHERWISE. ALL SET POINTS MUST BE ADJUSTABLE AT BAS
ELECTRICAL PANELS OR EQUIPMENT. WHEN PIPING RUNS SIZE. USE LONG RADIUS ELBOW FITTING WHEN PHYSICAL LOCALLY AND REMOTELY.
E ABOVE ELECTRICAL EQUIPMENT, APPROVAL OF THE OWNER SPACE ALLOWS. SHORT RADIUS ELBOW FITTINGS MUST HAVE 10. ALL BALL VALVES 50mm AND SMALLER MUST BE FULL PORT
MUST BE OBTAINED TO INSTALL SHEET METAL TROUGH TURNING VANES. 90 DEGREE SQUARE ELBOWS WITH BALL VALVES. 7. CONTROL/POWER WIRING REQUIRED BUT NOT SHOWN FOR AND
BETWEEN EQUIPMENT AND PIPING. TURNING VANES MUST ONLY BE USED WHERE THE RADIUS NOT LIMITED TO THERMOSTATS, VARIABLE FREQUENCY DRIVE

PLOT SCALE: PLOT DATE:


ELBOW INSTALLATION IS NOT POSSIBLE DUE TO SPACE 11. ALL REFRIGERANT PIPING AND COMPONENTS MUST BE SIZED CONTROLS, EQUIPMENT MANUFACTURER CONTROL PANELS,

10:13:00 AM
2/22/2022
9. PROVIDE PERMANENT IDENTIFICATION AND AREA SERVED LIMITATION. NUMBER AND LOCATION OF TURNING VANES AND ROUTED PER MANUFACTURERS RECOMMENDATIONS. DAMPER MOTORS, VALVES, SENSING DEVICES (TEMPERATURE,

SOLICITATION NO.:

SA-480530-1$-SM002GN.dwg
DESCRIPTION ON ALL EQUIPMENT. (SPLITTERS) MUST BE PER SMACNA. PROVIDE MANUFACTURER APPROVED INSTALLATION-SPECIFIC PRESSURE, HUMIDITY, LEVEL, FLOW, VOLUME, ON-OFF, FIRE

CONTRACT NO.:
ISOMETRIC DRAWINGS FOR APPROVAL. ALARM DEVICES) AND OTHER MECHANICAL/ FIRE

ISSUE DATE:
10. DO NOT LOCATE MECHANICAL WORK IN ELECTRICAL OR 11. PROVIDE MANUAL VOLUME DAMPERS IN EACH BRANCH OF PROTECTION/PLUMBING EQUIPMENT REQUIRING CONTROL
COMMUNICATION ROOMS, EXCEPT FOR RUNOUTS RETURN AIR, EXHAUST AIR, SUPPLY AIR DUCT AND 12. CONTRACTOR MUST PROVIDE ALL PIPING WITH VALVED AND WIRING MUST BE SUPPLIED AND INSTALLED TO PROVIDE A

1:1
SPECIFICALLY SERVING THE RESPECTIVE ROOM. DOWNSTREAM OF VAV BOXES. PROVIDE ADEQUATE NUMBER CAPPED HIGH POINT VENTS AND LOW POINT DRAINS TO COMPLETE AND USABLE FACILITY. INSTALL CONTROL WIRING IN
OF DAMPERS AS REQUIRED FOR COMPLETE BALANCING ALLOW VENTING, FILLING, AND DRAINING ALL PIPE SECTIONS. METAL CONDUITS AS PER SPECIFICATIONS.
11. ALL DUCTWORK AND PIPING MUST BE ROUTED MISSING WITHOUT THE USE OF OPPOSED BLADE DAMPERS PROVIDED UNLESS OTHERWISE INDICATED, SIZE IS 25 mm FOR PIPE 150
ELECTRICAL, COMMUNICATION AND STRUCTURAL WITH THE DIFFUSERS AND/OR REGISTERS. mm DIA AND LARGER, 20 mm FOR PIPE 20 mm THROUGH 100 8. PROVIDE DUAL LANGUAGES, ENGLISH AND ARABIC, FOR ALL
COMPONENTS. mm DIA, AND LINE SIZE FOR PIPE SMALLER THAN 20 mm PROGRAMMABLE LOGIC CONTROLS, EQUIPMENT MOUNTED
12. INSTALLATION MUST ACCOMMODATE READY ACCESS TO DIAMETER. DRAWINGS DO NOT INDICATE ALL REQUIRED PROCESSORS, BMS WORKSTATIONS AND CONTROL SEQUENCES.

FILE NO.:
12. ALL EQUIPMENT MOUNTINGS MUST RESIST FORCES OF 0.5 DAMPERS, COILS AND OTHER DEVICES. ACCESS DOORS MUST VENTS AND DRAINS.
TIMES THE EQUIPMENT WEIGHT IN ANY HORIZONTAL BE INSTALLED TO PROVIDE ADEQUATE CLEARANCES FOR 9. ALL BMS POWER SUPPLIES MUST BE FED FROM CENTRAL OR

SUBMITTED BY:
C. HAIRSTON

C. HAIRSTON
DIRECTION AND 1.5 TIMES THE EQUIPMENT WEIGHT IN THE DIRECT ACCESS. 13. CONTRACTOR MUST PROVIDE AND INSTALL ALL ITEMS SHOWN DEDICATED UPS SYSTEM. ANY SINGLE POWER SOURCE OR

DESIGN BY:

DRAWN BY:
DOWNWARD DIRECTION, UNLESS NOTED OTHERWISE ON PIPING DETAILS, AND INSTRUMENT DIAGRAMS, WHETHER COMPONENT MUST BE CAPABLE OF BEING DISCONNECTED

A. HANKS
D

C. CURSI
CKD BY:
EQUIPMENT SUPPORT MUST HAVE BRACING FOR 1.5 TIMES 13. ALL VOLUME DAMPERS ABOVE GYPSUM BOARD HARD OR NOT VISIBLE ON PIPING PLAN AND SECTION DRAWINGS. WITHOUT LOSING MONITORING AND CONTROLS OF REMAINING

ANSI D
SIZE:
THE EQUIPMENT WEIGHT. CEILINGS MUST BE FURNISHED WITH REMOTE DAMPER EQUIPMENT. ALL BUILDING DDC CONTROLLERS MUST BE
OPERATOR. 14. ALL VALVE OPERATORS INCLUDING CONTROL VALVE AND PROVIDED WITH UPS AND BACK-UP BATTERY.
13. ALL ERV AND CEILING MOUNTED FAN COILS MUST BE MOTOR OPERATED VALVE OPERATORS MUST BE ORIENTED
SUSPENDED FROM THE STRUCTURE ABOVE WITH VIBRATION 14. UNLESS OTHERWISE NOTED, ROUTE ALL DUCTWORK AND PER MANUFACTURER'S INSTRUCTIONS AND TO AVOID 10. ALL INSTRUMENTATION IN CONTACT WITH GLYCOL SOLUTION

TRANSATLANTIC MIDDLE EAST DISTRICT


ISOLATORS, UNLESS INDICATED OTHERWISE. PIPING ABOVE CEILINGS. ROUTE ALL DUCTWORK AND PIPING INTERFERENCE WITH OTHER PIPING AND EQUIPMENT. MUST BE OF 304, 304L, 316 OR 316L STAINLESS STEEL MATERIAL.

US ARMY CORPS OF ENGINEERS


AS HIGH AS POSSIBLE IN AREAS WITHOUT CEILINGS.

201 PRINCE FREDERICK DRIVE,


14. DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO 15. PIPING SYSTEMS MUST BE INSULATED. PIPING SYSTEMS

WINCHESTER, VA 22602
CONVEY SCOPE OF WORK AND TO INDICATE GENERAL 15. UNLESS OTHERWISE NOTED, PROVIDE DUCT RUNOUTS TO GENERALLY REQUIRING INSULATION INCLUDE (BUT ARE NOT
ARRANGEMENT. THEY ARE NOT INTENDED TO SHOW EVERY TERMINAL UNITS SAME SIZE AS TERMINAL UNIT INLET. LIMITED TO) THE FOLLOWING CHILLED WATER, HEATING
DETAIL INCLUDING OFFSET OR FITTING OR EVERY WATER, DOMESTIC HOT WATER, DOMESTIC HOT WATER
STRUCTURAL DIFFICULTY THAT MAY BE ENCOUNTERED 16. ALL OUTSIDE AIR INTAKES, RELIEF AIR, AND EXHAUST RECIRCULATING, DOMESTIC COLD WATER, REFRIGERANT AND
DURING THE WORK. EXCEPT AS OTHERWISE INDICATED. THE DAMPERS MUST BE LOW LEAKAGE DAMPERS. THE LOW CONDENSATE."
CONTRACTOR MUST PREPARE SHOP AND COORDINATION LEAKAGE DAMPERS WILL HAVE MAXIMUM LEAKAGE RATES OF
DRAWINGS PRIOR TO ANY WORK BEING DONE AND SHOW ALL
REQUIRED MAINTENANCE ACCESS.
15 LITERS/SECOND/SQUARE METER WITH A DIFFERENTIAL
PRESSURE OF 250 PA ACROSS THE DAMPER.
16. HYDRONIC WATER RETURN LINES MUST NOT HAVE BULLHEAD
CONNECTIONS.
GENERAL SUPPORT NOTES
15. WHERE ONLY US STANDARDS ARE PROVIDED IN THE 17. ALL UNUSED LOUVER AREA MUST BE PROVIDED WITH 50 mm 17. HYDRONIC PIPING MUST HAVE MANUAL AIR VENTS AT ALL 1. ALL PIPE SUPPORTS MUST CONFORM TO THE REQUIREMENTS
SPECIFICATIONS, THE EQUIVALENT LOCAL STANDARDS ARE THICK INSULATED METAL PANEL. HIGH POINTS. VENT COCKS MUST BE EXTENDED TO BE OF MSS-SP-58 AND MSS-SP-69.
C ALSO ACCEPTABLE. ACCESSIBLE FROM FLOOR. PROVIDE DRAIN VALVES WITH
18. INSTALL CALIBRATED BALANCING VALVES AND VENTURIS REMOVABLE PLUG AT THE BOTTOM OF VERTICAL PIPE RISERS 2. SUPPORTS MUST BE CAPABLE OF RESISTING HORIZONTAL
16. HEATING VENTILATING UNIT WITH BUILT-IN PLATE TYPE HEAT WITH A MINIMUM UNRESTRICTED STRAIGHT RUN OF 5 PIPE AND AT ALL LOW POINTS TO DRAIN PIPES. AND VERTICAL FORCES INDUCED BY THERMAL FORCES IN
RECOVERY UNIT IS ACCEPTABLE IN-LIEU OF THE SEPARATE DIAMETERS UPSTREAM AND 3 PIPE DIAMETERS ADDITION TO NORMAL LOADS DUE TO WEIGHT OF PIPE,
PIECES. THE CONTRACTOR MUST PROVIDE THE EQUIPMENT DOWNSTREAM. 18. ALL MECHANICAL PIPING INSULATION (HVAC AND PLUMBING) FITTINGS, WEIGHT OF FLUID, INSULATION. SUPPORTS ON
LAYOUT TO FIT IN THE AVAILABLE SPACE. IS SPECIFIED UNDER SECTION 23 07 00. OUTSIDE PIPING EXPOSED TO WIND MUST BE CAPABLE TO
19. UNLESS NOTED OTHERWISE, PROVIDE BRANCH DUCT TO WITHSTAND 50 m/s WIND LOAD. COMPLY WITH UFC 4-010-01
17. ALL OUTDOOR EQUIPMENT, INSTRUMENTATION, VFD, MOTORS DIFFUSERS SAME SIZE AS DIFFUSER NECK. FLEXIBLE DUCT 19. ALL HORIZONTAL COMPRESSED AIR PIPING MUST BE SLOPED STANDARDS AND MOUNT ALL OVERHEAD UTILITIES AND
ETC MUST BE RATED FOR LOCAL ENVIRONMENTAL HIGH CONNECTION TO THE DIFFUSER MUST BE NO MORE THAN 1500 IN THE DIRECTION OF AIR FLOW. PROVIDE FLOAT TYPE DRAIN OTHER FIXTURES WEIGHING 14 KILOGRAMS OR MORE
AMBIENT CONDITION. PROVIDE REMOTE WIRED PANELS WHEN MILIMETERS IN LENGTH. WITH SHUT OFF VALVE AT ALL LOW POINT. (EXCLUDING DISTRIBUTED SYSTEMS SUCH AS PIPING
NETWORKS THAT COLLECTIVELY EXCEED THAT WEIGHT)

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


HIGH TEMPERATURE RATED ELECTRONICS/PANEL IS NOT
AVAILABLE. 20. ALL CONDENSATE PIPING MUST BE PROVIDED WITH MINIMUM USING EITHER RIGID OR FLEXIBLE SYSTEMS TO MINIMIZE THE
1% SLOPE. ALL 90 DEGREE DIRECTION CHANGE IN LIKELIHOOD THAT THEY WILL FALL AND INJURE BUILDING
CONDENSATE PIPING MUST BE PROVIDED WITH TEE AND OCCUPANTS. DESIGN ALL EQUIPMENT MOUNTINGS TO RESIST

MECHANICAL GENERAL NOTES


18. ALL EQUIPMENT MUST BE PROVIDED WITH SINGLE POINT OF

THAAD STANDARD FACILITIES


FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT IN ANY

VARIOUS LOCATIONS, KSA


POWER CONNECTION UNLESS NOTED OTHERWISE. REMOVABLE PLUG.
HORIZONTAL DIRECTION AND 1.5 TIMES THE EQUIPMENT

STANDARD DETAILS
19. CONTRACTOR IS RESPONSIBLE TO FIELD COORDINATE THE 21. ALL GLYCOL PIPING, INCLUDING EQUIPMENT, FITTINGS, WEIGHT IN THE DOWNWARD DIRECTION.
REQUIRED CLEARANCES IN ACCORDANCE WITH VALVES, INSTRUMENTS IN CONTACT WITH GLYCOL MUST BE

SA-480530
MANUFCATURER'S INSTALLATION REQUIREMENTS. MADE OF STAINLESS STEEL AND RATED FOR MINIMUM 1724 3. CONTRACTOR IS RESPONSIBLE FOR THE DESIGN,
B kPa UNLESS NOTED OTHERWISE. FABRICATION, AND INSTALLATION OF ALL PIPE SUPPORTS AND
SEISMIC BRACING.
20. ALL EQUIPMENT AND DEVICES MUST BE INSTALLED IN
ACCORDANCE WITH MANUFACTURER’S REQUIREMENTS
INCLUDING ALL REQUIRED MAINTENANCE SPACES AND 4. CONTRACTOR IS RESPONSIBLE FOR ALL SUPPLEMENTARY
PROPER AIR CIRCULATIONS. STEEL REQUIRED FOR PIPE SUPPORT INSTALLATION.

5. CONTROL VALVE AND MOTOR OPERATED VALVE OPERATORS


MUST BE BRACED FOR SEISMIC LOADS.

6. ALL PIPE SUPPORTS AND SEISMIC BRACING REGARDLESS OF


PIPE SIZE AND WHETHER INDICATED ON DRAWINGS OR NOT,
TO MEET SPECIFIED PERFORMANCE REQUIREMENT.

7. ENTIRE SCOPE OF SUPPORT LOCATION, DESIGN,


FABRICATION, AND INSTALLATION OF HVAC DUCTS IS
2/22/2022 10:13:00 AM

CONTRACTOR'S RESPONSIBILITY. HVAC DUCTS AND PIPE


SUPPORTS (EXCLUDING FIRE PROTECTION) MUST BE IN
ACCORDANCE WITH THE LATEST SMACNA PUBLICATION
A "SEISMIC RESTRAINT MANUAL" AND SPECIFICATIONS. THE SHEET ID
CONTRACTOR MUST DESIGN ALL EQUIPMENT MOUNTINGS TO
RESIST FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT IN ANY
HORIZONTAL DIRECTION AND 1.5 TIMES THE EQUIPMENT $
WEIGHT IN THE DOWNWARD DIRECTION, AS A MINIMUM.
SM002
1 2 3 4 5 6 7 8 9 10

100 WIDE CLOSURE


COLLAR WHERE
WALL DUCT IS EXPOSED
(ATTACH TO DUCT)
US Army Corps of
(TYP) SHEET METAL SCREWS EXTERIOR INSULATION Engineers ®
DUCT APPROX 300mm OC - TYP Middle East District
100mm WIDE
G CLOSURE COLLAR
WHERE DUCT IS
EXPOSED (TYP) DUCT 0.8mm GALVANIZED FLASHING SEALANT BY M.C.

DATE
SEALANT (TYP) SHEET METAL SCREWS
FLOOR APPROX 300mm OC - TYP

HIGH
PACKING (TYP)

100
150
SHEET METAL
SCREW (TYP)
250mm MAX FLASHING
SLEEVE OR
PACKING (TYP) PREPARED PREFAB CURB
OPENING
SEALANT (TYP)
ROOF

DESCRIPTION
NOTES:
F NOTES:
A. DETAIL IS NOT APPLICABLE WHERE FIRE DAMPER,
REGISTER, OR DIFFUSER IS PROVIDED. A. DETAIL IS NOT APPLICABLE WHERE FIRE DAMPER, REGISTER, OR
DIFFUSER IS PROVIDED.
B. EXTERNALLY INSULATED DUCT MUST BE CAULKED TO
PROVIDE A COMPLETE SEAL BETWEEN THE INSULATION B. EXTERNALLY INSULATED DUCT MUST BE CAULKED TO PROVIDE
AND CLOSURE COLLAR. A COMPLETE SEAL BETWEEN THE INSULATION AND CLOSURE
COLLAR. ACOUSTIC LINER
C. FLOOR PENETRATIONS OF RATED FLOORS NOT INDICATED WHERE REQUIRED
AS REQUIRING DAMPERS ON THE PLANS MUST BE C. WALL PENETRATIONS OF RATED WALLS NOT INDICATED AS
PROVIDED WITH FIRESTOPPING IN ACCORDANCE WITH REQUIRING DAMPERS ON THE PLANS MUST BE PROVIDED WITH
SPECIFICATION SECTION 07 84 00 FIRSTOPPING. FIRESTOPPING IN ACCORDANCE WITH SPECIFICATION SECTION NOTES:
07 84 00 FIRSTOPPING. 1. M.C. TO SEAL AROUND SCREW HEADS.
D. DUCTWORK PENETRATING FIRE RATED FLOORS MUST 2. DUCT LINER IS NOT ALLOWED IN BUILDINGS COMPLYING WITH UFC
BE 1.2mm THICK MINIMUM. D. DUCTWORK PENETRATING FIRE RATED WALLS MUST BE 1.2mm
THICK MINIMUM. CODE, INCLUDING TOFA, TEMF, RPRE, TCPL AND TSPB.
E. PIPE PENETRATION THROUGH FLOORS SIMILAR. USE

MARK
ESCUTCHEON RATHER THAN CLOSURE COLLAR. E. PIPE PENETRATION THROUGH WALLS SIMILAR. USE
ESCUTCHEON RATHER THAN CLOSURE COLLAR.
E TYPICAL DUCT PENETRATION THRU ROOF
DUCT / PIPE PENETRATION THRU FLOORS DUCT / PIPE PENETRATION THRU WALLS DETAIL
E2 E5 E7

PLOT SCALE: PLOT DATE:


NTS NTS NTS

10:13:02 AM
2/22/2022
SOLICITATION NO.:

SA-480530-1$-SM501DT.dwg
CONTRACT NO.:
ISSUE DATE:
25 MM MIN 6 MM TO 12 MM

1:1
OVERLAP CLEARANCE
HOUSING ROUND OR ALL 4 SIDES
WELDED TO FLAT OVAL OF DAMPER 40 MM x 40 MM x 2 MM
DUCT SECTION DUCT OR HEAVIER ANGLES
SECTION SNUG TO WALL OR
INSULATION FLOOR AND SLEEVE

FILE NO.:
(WHERE ALL AROUND
SLEEVE

SUBMITTED BY:
REQUIRED)

C. HAIRSTON

C. HAIRSTON
DESIGN BY:

DRAWN BY:

A. HANKS
D

C. CURSI
FIRE

CKD BY:
DUCT

ANSI D
DAMPER

SIZE:
COVER WITH S-TYPE SLIP
HANDLE AND CONNECTOR
CHAIN RETAINER

TRANSATLANTIC MIDDLE EAST DISTRICT


GASKETED AND
DUCT SLEEVE
PRESSURE SEALED

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


SPIN-IN FITTING SUPPLY CHAIN
W/ BUTTERFLY DUCT

WINCHESTER, VA 22602
DAMPER

END OF
DUCT
TYPICAL ACCESS DOOR FOR ROUND OR CAULKING ALL
AROUND PROVIDE ACCESS
CEILING NYLON DRAW DOOR OR REMOVABLE
DIFFUSER BAND (TYP)
VD
FLAT OVAL DUCT WALL OR
FLOOR
DUCT SECTION TO

R=1.5D
C5 NTS
BOLT, SCREW, RIVET,
OR TACKWELD TO
SLEEVE AT 200 MM OC
SERVICE DAMPER

AIR FLOW MAX


MAX 1500 LENGTH OF
MIN
D

AIR TIGHT GASKET


FLEXIBLE DUCT
C FULLY EXTENDED TO
TO RUN AROUND EDGE NOTES:
SUPPLY AIR DUCT DUCT OPENING OF ACCESS PANEL 1. CURTAIN DAMPER W/ BLADES OUT OF AIRSTREAM SHOWN. OTHER
IF REQUIRED, ROUND VD
"D" "D" CURTAIN STYLES AND MULTI-BLADE DAMPER INSTALLATION SIMILAR.
DUCT ADAPTER FOR
MIN RECTANGULAR 2. CONFORM TO MANUFACTURER'S INSTRUCTIONS.
DIFFUSER CEILING CEILING
DIFFUSER NOTE 4 3. INSTALLATION OF FIRE/SMOKE DAMPER IS SIMILAR.
AIRFLOW AIRFLOW
100 MM D
MIN TYPICAL FIRE DAMPER FOR VERTICAL OR

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


45°
100 MM
MIN
45°
HORIZONTAL INSTALLATION
B7

THAAD STANDARD FACILITIES


NTS

VARIOUS LOCATIONS, KSA


VOLUME DAMPER "D" "D" VOLUME PIANO HINGE
MIN

MECHANICAL - DETAILS
NOTE 4 "D" "D" DAMPER
MIN

STANDARD DETAILS
MIN NOTE 4 PROVIDE VISUAL PORTS COIL/DAMPER
CEILING
VD AT ALL LOCATIONS CAM LATCH
VD

SA-480530
EXCEPT HEATING COILS
B EXHAUST OR
CEILING CEILING DIFFUSER RETURN REGISTER 45 DEGREES
NOTES 2 & 4 ACCESS PANEL SIZE SCHEDULE
MANUAL
NOTES: VOLUME
DUCT SIZE (D) ACCESS PANEL SIZE DAMPER
1. "D" IS THROAT DIA OR SIDE DIM. OF SQUARE CONN.

2. MIN LENGTH OF STRAIGHT DUCT ABOVE CEILING DIFFUSER IS "D". 150 TO 375 200 W x 100 D RECTANGULAR
VD MAIN DUCT
3. ABOVE DETAILS ARE REPRESENTATIVE OF STANDARD DUCT CONNECTIONS, ONLY. 375 TO 525 (D-2) W x (D-2) H
THESE DETAILS ARE NOT INTENDED TO SHOW ALL POSSIBLE DUCT CONNECTIONS.
500 AND ABOVE 450 X 450
4. VOLUME DAMPERS ATTACHED TO REGISTER OR DIFFUSER ARE PURCHASED WITH RECTANGULAR 1/4 BRANCH
REGISTER OR DIFFUSER. BRANCH DUCT DUCT WIDTH
USE TWO CAM LATCHES ON PANELS LARGER THAN 300 x 300 SIZE. OR 100 MM
2/22/2022 10:13:02 AM

5. NO KINKS OR BENDS IN FLEX DUCT. MIN.


TYPICAL ACCESS DOOR FOR RECTANGULAR
A SHEET ID
TYPICAL DUCT CONNECTION DETAIL DUCT TYPICAL BRANCH DUCT DETAIL
A2 NTS A4 NTS A7 NTS $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SM501
1 2 3 4 5 6 7 8 9 10

L5x89x8, LLH (NOTE 2)


L125x89x8, LLH (NOTE 2) DOUBLE-WALL
INSULATION DUCT
(WHERE 7MM THREADED ROD 7MM THREADED ROD US Army Corps of
APPLICABLE) Engineers ®
L75x75x7, 125MM LONG L125x89x8, LLH
LENGTH TO Middle East District
DUCT (NOTE 2)
G SUIT DUCT SIZE L75x75x7 125MM
LONG (NOTE 2)
L125x89x8, LLH AND SUPPORT
LENGTH TO SUIT PIPE SPACING
LINING (NOTE 2)

DATE
(WHERE DUCT SIZE
AND SUPPORT PIPE PIPE 75MM STD WELD
APPLICABLE)
SPACING NOTES 1 AND 4
SINGLE PLY (NOTE B)
MEMBRANE SINGLE PLY MEMBRANE
PIPE 75MM STD WELD PL 10x150x150
ROOF INSULATION NOTES 1 AND 4 ROOF INSULATION

JOIST

TYP
TYP

DESCRIPTION
F
JOIST
NOTES:
1. SEE ARCHITECTURAL SHEETS FOR FLASHING DETAIL.
ACCOUSTICALLY LINED, THROUGH- PL 10x150x150
WALL SHEET METAL TRANSFER DUCT NOTES:
1. SEE ARCHITECTURAL SHEETS FOR FLASHING DETAIL. 2. LOCATE ANGLE SNUG AGAINST DUCT IF DUCT UNINSULATED.

2. LOCATE ANGLE SNUG AGAINST DUCT IF DUCT IS UNINSULATED. 3. WHERE DUCTS RUN PARALLEL TO ROOF JOISTS, LOCATE SUPPORT LEGS
DIRECTLY OVER JOISTS AND WELD TO JOISTS AS SHOWN ABOVE.
MANBARS AT PARTITION
(IF DUCT OPENING SIZE 3. WHERE DUCTS RUN PARALLEL TO ROOF JOISTS, LOCATE SUPPORT LEGS
DIRECTLY OVER JOISTS AND WELD TO JOISTS AS SHOWN. 4. SUPPORT MUST BEAR AT JOIST PANEL POINT.
EXCEEDS 61,935MM2)
4. SUPPORT MUST BEAR AT JOIST POINT.
TYPICAL ROOF-MOUNTED ROUND DUCT
ACCESS HATCH (IN
DETAIL ON JOIST TYPE STRUCTURE
BOTTOM OF DUCT)
TYPICAL ROOF-MOUNTED RECTANGULAR E8 NTS

MARK
ANGLES WELDED TO
SLEEVE (NOTE 1)
DUCT DETAIL ON JOIST TYPE STRUCTURE
E 300MM
STC 45 OR
E4 NTS
L75x75x6 ANGLE
LENGTH TO SUIT
SAND LOUVER SAND LOUVER WIDTH

PLOT SCALE: PLOT DATE:


ACOUSTICALLY RATED
PARTITION (PLAN VIEW) PROVIDE 25 MM

10:13:04 AM
FIRE DAMPER IF INDICATED ON DUCT LINER

2/22/2022
PLANS. REFER TO FIRE

SOLICITATION NO.:
INSIDE SHEET

SA-480530-1$-SM502DT.dwg
DAMPER DETAIL.

CONTRACT NO.:
METAL DUCT

ISSUE DATE:
DUCT DIM. = TRANSFER TYP. x4
GRILLE NECK DIM. + 50 MM

1:1
ALLOWANCE FOR DUCT
L75x75x6 ANGLE
LINER.
FULL WIDTH LENGTH TO SUIT SAND
NO TURNING OF AIR DEVICE LOUVER HEIGHT
VANES IN NECK DIM.
ELBOW
NOTE 3

FILE NO.:
(TYP) 100 MM MIN.
TYP.

SUBMITTED BY:
FULL LENGTH

C. HAIRSTON

C. HAIRSTON
OF AIR DEVICE

DESIGN BY:

DRAWN BY:
TRANSFER GRILLE PIPE 75MM
NECK DIM.

A. HANKS
NOTES:
D

C. CURSI
CKD BY:
(TYP)

ANSI D
SIZE:
SECURE SIDE 1. PROVIDE ANGLES AS INDICATED IN SECURE NOTES: PL 150x150x10
PENETRATION (SP) THROUGH SECURE WALL DETAIL.
1. DUCT LINER IS NOT ALLOWED IN BUILDINGS COMPLYING WITH

TRANSATLANTIC MIDDLE EAST DISTRICT


UFC CODE, INCLUDING TOFA, TEMF, RPRE, TCPL AND TSPB.

US ARMY CORPS OF ENGINEERS


NOTES 1 & 2

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
TYPICAL SECURE Z-DUCT AIR TRANSFER TYPICAL TRANSFER DUCT DETAIL NOTES:
C1 NTS C5 NTS 1. SEE ARCHITECTURAL SHEETS FOR FLASHING DETAIL.
2. ANCHOR TO CONCRETE.
3. ANGLE AND LOUVER TO BE SITE-DRILLED AND FASTENED.
MANUAL AIR VENT
CONTROL VALVE TYPICAL ROOF MOUNTED OUTSIDE AIR
FLEXIBLE PIPE
CONNECTION - TYP FOR STEEL FLOORS
CONNECT WITH C-CLAMPS
FOR CONCRETE FLOORS
CONNECT WITH ANCHOR
SAND LOUVER DETAIL ON CONCRETE TYPE
C TEMPERATURE / PRESSURE
BOLTS INSULATION L125x89x8, LLH (NOTE 2)
STRUCTURE
PORT WITH CAP - TYP
VIBRATION ISOLATOR
(TYPICAL)
(WHERE
APPLICABLE)
7MM THREADED ROD
C8 NTS
CALIBRATED BALANCING L75x75x7, 125MM LONG
L125x89x8, LLH (NOTE 2)
VALVE DUCT (NOTE 2)

L125x89x8, LLH DOUBLE-WALL DUCT


REDUCER - TYP
LINING LENGTH TO SUIT 7MM THREADED ROD
(AS REQUIRED)
(WHERE DUCT SIZE
AND SUPPORT PIPE L125x89x8, LLH
APPLICABLE)
MV

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


PT UNDERSIDE OF FLOOR SPACING LENGTH TO
(NOTE 2) SUIT DUCT SIZE L75x75x7, 125MM
CHR SINGLE PLY LONG (NOTE 2)
MEMBRANE AND SUPPORT

THAAD STANDARD FACILITIES


PIPE 75MM STD WELD PIPE SPACING

VARIOUS LOCATIONS, KSA


PT NOTE 3 (NOTE 2)

MECHANICAL - DETAILS
ROOF INSULATION NOTE 1 PIPE 75MM STD WELD

STANDARD DETAILS
CHS ATTACH HANGAR ROD TO
FAN COIL UNIT
NOTE 3 NOTE 1

SA-480530
B FAN COIL UNIT SINGLE PLY MEMBRANE
PL 10x150x150
SHUT OFF VALVE (TYP)
STRAINER SLOPED PL 10x150x150 ROOF INSULATION
D NEOPRENE PAD (TYP.)
DOWN
HOSE VALVE WITH THREADED NOTES:
CAP ON CHILLED WATER COIL
1. SEE ARCHITECTURAL SHEETS FOR FLASHING DETAIL.
CHAIN SLOPED CONDENSATE
DRAIN PAN 2. LOCATE ANGLE SNUG AGAINST DUCT IF DUCT IS UNINSULATED. NEOPRENE PAD PL 5x150x150
UNION - TYP
NOTE 2
3. ANCHOR TO CONCRETE. NOTES:
DUCT COLLAR - TYP 1. SEE ARCHITECTURAL SHEETS FOR FLASHING DETAIL.
NOTES:

1. DUCTWORK, ELECTRIC HEATING COIL, FLEX CONNECTIONS AND SUPPORTS NOT SHOWN. 2. LOCATE ANGLE SNUG AGAINST DUCT IF DUCT UNINSULATED.

TYPICAL ROOF MOUNTED RECTANGULAR


2/22/2022 10:13:04 AM

2. TRAP ON CONDENSATE DRAIN IS NOT REQUIRED WHEN A CONDENSATE PUMP IS PROVIDED. WHEN
PUMPED, PROVIDE CHECK VALVE ON PUMP DISCHARGE. 3. ANCHOR TO CONCRETE.
3. CALIBRATED BALANCING VALVE IS NOT REQUIRED WHERE PRESSURE INDEPENDENT CONTROL
A VALVE INDICATED ON DRAWINGS. DUCT DETAIL ON CONCRETE TYPE TYPICAL ROOF-MOUNTED ROUND DUCT SHEET ID
TYPICAL FAN COIL UNIT PIPING DETAIL STRUCTURE DETAIL ON CONCRETE TYPE STRUCTURE $
A1 NTS A5 NTS A8 NTS
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SM502
1 2 3 4 5 6 7 8 9 10
600 MM CLEARANCE 500 MM REAR
COMPRESSOR SIDE SYSTEM MAKE-UP WATER FROM
CLEARANCE
BACKFLOW PREVENTER SEE
PLUMBING DRAWINGS; FOR
GLYCOL SERVICE, USE GLYCOL
REMOVABLE CAP FROM GLYCOL MAKE-UP UNIT GPU US Army Corps of
W/ 6 MM HOLE REFRIGERANT PIPING Engineers ®
THROUGH ROOFING AND SERVICE VALVE (TYP) Middle East District
ACCU MOUNTED ON
G 50 MM
STRUCTURE EQUIPMENT FRAME - QUICK FILL BYPASS
DRAW- . ANCHOR BOLTS 15 MM Ø.
.
THRU

DATE
UNIT NOTE:
25 MM GREATER THAN INDOOR UNIT SHALL RECEIVE POWER FROM OUTDOOR .
CASING STATIC PRESSURE UNIT. PROVIDE CONDUIT AND CONDUCTOR BETWEEN
CONDENSER AND EVAPORATOR. COORDINATE FINAL HIGH CAPACITY
NOTE A NOTE C
SIZE OF EACH WITH MANUFACTURER REQUIREMENTS. 200 MM SIDE AIR VENT
500 MM FRONT
CLEARANCE CLEARANCE
NOTE B 25 MM GREATER THAN
HALF OF CASING
STATIC PRESSURE NOTE: INLET UNION (TYP)
NOTE C CLEARANCE DIMENSIONS INDICATE MINIMUM
REQUIRED CLEARANCES. FOLLOW ALL PRESSURE REDUCING VALVE
MANUFACTURER'S REQUIRED AND FURNISH AND INSTALL
RECOMMENDED CLEARANCES. REFRIGERANT PIPING TO
REMOVABLE CAP MEET MANUFACTURER'S
W/ 6 MM HOLE REQUIREMENTS AND
100 MM LEFT SIDE
RECOMMENDATIONS
CLEARANCE CENTRIFUGAL MANUAL AIR

DESCRIPTION
50 MM AIR SEPARATOR VENT
F BLOW- 300 MM TOP
THRU CLEARANCE ROUTE PIPING ABOVE CEILINGS
HOLD TIGHT TO UNDERSIDE OF CONNECT PER
UNIT HOSE DRAIN EXPANSION TANK
50 MM STRUCTURE
VALVE WITH CAP MANUFACTURERS
RECOMMENDATIONS
NOTE A 1000 MM FRONT SEE PLAN SHEETS FOR
NOTE B 25 MM GREATER THAN ROUTING OF CONDENSATE
CLEARANCE PRESSURE GAUGE
CASING STATIC FOR SERVICE PIPING SHUT-OFF BALL
PRESSURE VALVE (FOR
NOTE C PRESSURIZED BLADDER SERVICING)
100 MM RIGHT SIDE EXPANSION TANK
CLEARANCE
NOTES:
A. DRAIN MUST BE FULL SIZE OF MECHANICAL EQUIPMENT CONNECTION. MOUNT INDOOR UNIT SECURELY MAX 100 MM WALL HOSE DRAIN
TO WALL AT CORNERS PENETRATION VALVE WITH CAP
B. EXTEND TO NEAREST FLOOR DRAIN. FOR ROOFTOP UNITS,

MARK
DISCHARGE ON SPLASH BLOCK.

E C. CASING STATIC PRESSURE MUST BE DETERMINED BY MECHANICAL


EQUIPMENT MANUFACTURER. ADJUST DIMENSIONS WHERE
TYPICAL DUCTLESS SPLIT SYSTEM PIPING
REQUIRED TO CONFORM TO MANUFACTURER'S
RECOMMENDATIONS. INSTALLATION DETAL FOR ROOF-MOUNTED TYPICAL AIR SEPERATOR AND EXPANSION

PLOT SCALE: PLOT DATE:


10:13:06 AM
TYPICAL CONDENSATE DRAIN DETAIL CONDENSING UNIT TANK PIPING SCHEMATIC

2/22/2022
E3 E5 E8

SOLICITATION NO.:

SA-480530-1$-SM503DT.dwg
CONTRACT NO.:
NTS NTS NTS

ISSUE DATE:
FROM PUMP DISCHARGE BUTTERFLY VALVE FULL SIZE LINE BYPASS
(TYP)

1:1
TO PUMP SUCTION
SERVICE BALL FLOW INDICATOR CHEMICAL
VALVES SIGHT GLASS FUNNEL

FILE NO.:
PRESSURE/TEMP TEST PORT TWO WAY CONTROL 20mm
(TYP) VALVE CHILLED

SUBMITTED BY:
WATER

C. HAIRSTON

C. HAIRSTON
SHUT-OFF VALVE

DESIGN BY:

DRAWN BY:
MANUAL AIR VENT BALANCE PIPING
COMBINATION

A. HANKS
D UNION (TYP)

C. CURSI
CKD BY:
(TYP) SHUT-OFF VALVE VALVE

ANSI D
GAGE AND MANUAL

SIZE:
(TYP) AIR VENT
PT
CHR
SOLID

TRANSATLANTIC MIDDLE EAST DISTRICT


CALIBRATED INTERNAL
PT BALANCING VALVE UNIONS BAFFLE

US ARMY CORPS OF ENGINEERS


THERMOMETER

201 PRINCE FREDERICK DRIVE,


(TYPICAL) CHEMICAL PLATE
CHS
POT 20mm DRAIN LINE

WINCHESTER, VA 22602
FEEDER 19L WITH VALVE AND
UNION STRAINER WITH HOSE
COOLING COIL (TYP) BALL VALVE & CONNECTION
PLUG
DRAIN VALVE WITH
HOSE END ADAPTOR DRAIN VALVE WITH CAP

NOTES:
1. CALIBRATED BALANCING VALVE IS NOT REQUIRED WHERE PRESSURE
TYPICAL CHILLED WATER BUFFER TANK
C INDEPENDENT CONTROL VALVE INDICATED ON DRAWINGS.
CHEMICAL POT FEEDER DETAIL DETAIL
2. PROVIDE SEPARATE BALANCING VALVE FOR EACH STACKED COIL. C5 NTS C8 NTS
FIRST 3 HANGERS FOR EACH

TYPICAL CHILLED WATER COIL PIPING HANGER, TYP


PIPE AND BRANCH MUST BE
SPRING AND NEOPRENE TYPE.
SECURE REFRIGERANT PIPING SEAL AROUND ALL OPENINGS
WITH SILICONE SEALANT. COLOR
DETAIL TO SUPPORTS WITH
"UNISTRUT" PIPE CLAMP OR TO MATCH BUILDING
C3 NTS EQUAL

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


1.5mm GALVANIZED
REFER TO PLANS INSTALL HANGER AS CLOSE TO PIPE SLEEVE
FOR PIPE SIZE ELBOW AS POSSIBLE (TYP)

THAAD STANDARD FACILITIES


AI RUN INSULATION OF

VARIOUS LOCATIONS, KSA


SUCTION LINE THRU SUCTION

MECHANICAL - DETAILS
STANDARD DETAILS
SHUT OFF VALVE, MANUAL DPT CLAMP ASSEMBLY LINE
CALIBRATED BALANCE VALVE
& CHECK VALVE

SA-480530
TRUMPET VALVE W/ HYDRONIC
B PRESSURE/TEMPERATURE PORT INDICATOR PRESSURE GAUGE
(TYP)
VIBRATION ISOLATOR (TYP)
GROUT PUMP FRAME
LEVEL TO BASE SUCTION DIFFUSER W/STRAINER
40mm P-3300
INSULATION
25mm DRAIN "UNISTRUT"
OR EQUAL
SPRING ISOLATOR 25mm MIN DIA STEEL PIPE
STAND EXTERIOR WALL
FLOOR WELD BOTH SIDES
INERTIA BASE (TYPICAL)
COUPLING GUARD 150mm CONCRETE BASE NOTE:
PUMP 100mm x 100mm x 6mm ANGLE LIQUID LINE SIMILAR
ANCHORED TO STRUCTURE WITH
2/22/2022 10:13:06 AM

10mm x 80mm EXPANSION BOLTS


NOTES:

A 1. PROVIDE MIN. 25mm CLEARANCE BETWEEN INERTIA BASE AND CONCRETE BASE.
TYPICAL EXTERIOR WALL PENETRATION SHEET ID
TYPICAL BASE MOUNTED PUMP DETAIL DETAIL $
A5 NTS A8 NTS
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SM503
1 2 3 4 5 6 7 8 9 10

.
136.5
2.8mm THICK GALVANIZED
.
41
STEEL CHANNEL
US Army Corps of
Engineers ®
41.
6.4mm THICK GALVANIZED Middle East District
G FLAT PLATE FITTING AT

200 MIN
CORNERS
CONDUIT PREFABRICATED ROOF
CURB FROM FAN

DATE
PIPE FLANGE
MANUFACTURER
BIRDSCREEN 600mm HIGH COVER UNUSED PIPE OR ELECTRICAL CONDUIT THRU BOOT
CONCRETE PAVERS
PORTS
TOP OF CURB STAINLESS STEEL CLAMP
STEEL PIPE SUPPORTS MAX SET LEVEL SEE ARCH DWG FOR
SPACING BETWEEN FLASHING DETAILS
SUPPORTS MUST BE 900mm MULTIPLE PIPE PORTAL BOOT TRIM TO SIZE
PORTAL CURB CAP
RUBBER PIPE COLLAR WATERPROOFING PRE-FABRICATED
MEMBRANE (AIR BARRIER) SELF-FLASHING CURB
SEALANT 40mm THICK INSULATION
INSULATION WATERPROOFING MEMBRANE

HT - 500mm
(AIR BARRIER)
ROOF MEMBRANE (AIR

DESCRIPTION
BARRIER)
F REFER TO ARCH DETAIL FOR
FLASHING
CONCRETE ROOF SLAB
ELECT WIRING
MOTORIZED DAMPER
ROOF SLAB
EXHAUST DUCT
NOTE: ACCESS DOOR

1. INSTALL GALVANIZED STEEL EQUIPMENT PLATFORM LEVEL OVERALL SIZE TO MATCH NOTE:
BASE OF UNIT. COORDINATE DIMENSIONS AND DETAILS WITH MANUFACTURER OF ACCU.
2. MOUNT ACCU TO FRAME WITH ANCHOR BOLTS - PROVIDE MOLDED NEOPRENE 1. FAN CONTAINS VIBRATION ISOLATORS FOR SUPPORTING THE DRIVE ASSEMBLY
ISOLATION PADS AT EACH BOLT. AND FAN WHEEL.
2. WHERE CURB MOUNTED MOTORIZED DAMPER INDICATED, PROVIDE ACCESS OPENING IN SLAB - ONLY AS PROVIDE 200mm THICK INSULATION
3. TYPICAL ACCU SUPPORT DETAIL UNLESS OTHERWISE NOTED IN THE BUIDLING DESIGN LARGE AS REQUIRED TO INSIDE BASE OF CURB
PACKAGE. FROM ROOF.
PASS PIPE & INSULATION
THROUGH

TYPICAL ROOF MOUNTED EXHAUST FAN

MARK
E TYPICAL ACCU SUPPORT DETAIL DETAIL MULTIPLE PIPE PORTAL DETAIL
E1 NTS E3 NTS E6 NTS

PLOT SCALE: PLOT DATE:


10:13:07 AM
2/22/2022
SOLICITATION NO.:

SA-480530-1$-SM504DT.dwg
CONTRACT NO.:
ISSUE DATE:

1:1
15 x 75 NIPPLE
CARRIER PIPE W/PLASTIC SLEEVE
(TYPICAL)

END CAP 7 - 20 BOLT W/LOCK NUT


(TYPICAL)

FILE NO.:
PLAN DIMENSION AS REQ'D

SUBMITTED BY:
HEAT SHRINK FLOOR SLEEVE AND SEAL FOR EQUIPMENT (COORDINATE

C. HAIRSTON

C. HAIRSTON
DESIGN BY:

DRAWN BY:
W/APPROVED SHOP DRAWINGS)

A. HANKS
D

C. CURSI
CKD BY:

ANSI D
25

SIZE:
FINISHED
EXTERIOR WALL FLOOR SLAB

TRANSATLANTIC MIDDLE EAST DISTRICT


4" 50
75

US ARMY CORPS OF ENGINEERS


450 MM AFF

201 PRINCE FREDERICK DRIVE,


150X150-W1.4 X W1.4 W.W.F.

WINCHESTER, VA 22602
INTERIOR EQUIPMENT PAD

FIN FLR
25

GRADE
TYPICAL INTERIOR EQUIPMENT PAD DETAIL
HOLES FOR AHR BOLTS
C8 NTS
PLAN

C-E (SEE PLAN)


75x125 NEOPRENE
PAD-50 DUROMETER,
C 8 MIN THICK 32mm DRAIN
SLOPING DOWN
L100x100x9.5,
INSULATION
125mm LONG
AND STUCCO
CMU
5"x5" NEOPRENE PAD
25

25 JACKET
(CEMENT PADS TO L SEALANT SEALANT AND
SURFACES) 50 BACKER ROD
DUROMETER - MIN
TYP
THICKNESS 8mm

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


INSULATION
VARIES

EQPT
ISOL
BASE CARRIER
LOCATIONS

THAAD STANDARD FACILITIES


PIPE

VARIOUS LOCATIONS, KSA


NOM 300mm
25

MECHANICAL - DETAILS
L150x100x50, RESTRAINTS,

STANDARD DETAILS
125mm LONG 4 MIN
ANCHOR BOLT

SA-480530
JACKET
B

WALL SLEEVE AND SEAL


FIN FLR

FOUNDATION
40mm ELEVATION 50
NOTE: SPLASH BLOCK

TYPICAL EQPT BASE 1. PIPES PASSING THROUGH OR UNDER FOOTINGS OF FOUNDATION


RESTRAINT LOCATIONS WALLS HAVE A RELIEVING ARCH OR A SLEEVE . SUCH SLEEVE BE A
ELEVATION
PIPE SIZES LARGER THAN THE PIPE.
GRADE
2. TYPICAL PIPE PENETRATION DETAIL UNLESS OTHERWISE NOTED
NOTE: ADJUST L SIZES TO SUIT EQPT BASE PROVIDED.
2/22/2022 10:13:07 AM

IN THE BUILDING PACKAGE.

TYPICAL CONDENSATE DRAIN THROUGH


A SHEET ID
SEISMIC RESTRAINT DETAIL TYPICAL BUILDING RISER DETAIL WALL DETAIL
A1 NTS A3 NTS A6 NTS $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SM504
1 2 3 4 5 6 7 8 9 10

CONC AHR,
OR BOLT,
TYP
US Army Corps of
Engineers ®
45° MAX,
Middle East District
TYP
G BOTTOM OF CONCRETE MAX 25mm
ANGLE BRACE, CLEARANCE
OR STRUCTURAL BEAM
TYP VIBRATION

DATE
ISOLATOR
PL 3/8 DISTANCE MUST BE AS REQD NORMAL ANGLE
EQUAL TO REQUIRED APPROXIMATELY 45°
INSULATION THICKNESS
BOLT OR
SNUBBER INSTALL AT 45° CONC AHR
BOLT, (TYP)
PLATE PARALLEL TO PIPE VIBRATION
TYP
(UP STOP) WHERE REQUIRED ISOLATOR
U-BOLT PIPING FOR LONGITUDAL
SWAY BRACING CABLE CROSS
TRANSVERSE BRACE DETAIL A TYP HANGER BRACING
CONC AHR, ROD CABLE INSTALLED W/ STIFFENER
EQUIPMENT (ALL 4 SIDES)
OR BOLT, STIFFENER SLACK, NOTE D
ANGLE BOLT EQUIPMENT
TYP
TO SUPPORT
THREADED (12mm BOLT)
ROD ROD TO ANGLE

DESCRIPTION
(TYP)
45° MAX, CLAMPS 3 PER ROD
F TYP CABLE BRACING AT EACH CORNER
ANGLED 45 DEGREES HORIZONTAL EQUIPMENT
BOTTOM OF CONCRETE SWIVEL
1 TO EQPT TO PREVENT HORIZONTAL
TYP OR STRUCTURAL BEAM CONNECTIONS
1 MOVEMENT IN ANY DIRECTION
ANGLE BOTH ENDS
BRACE, DISTANCE MUST BE
CABLE NOTE: DETAIL SIMILAR FOR TRUSS ROOF CONSTRUCTION, SUPPORT FROM TRUSSES
TYP EQUAL TO REQUIRED
CLAMP THREADED ROD
PL 3/8 INSULATION THICKNESS ROD STIFFENER
ANGLE CLAMP

PL 3/8
PIPING
U-BOLT ADJUSTABLE
END
DETAIL
LONGITUDINAL BRACE DETAIL A
PIPE NO SCALE

MARK
NOTES: HANGER

E A. DETAILS SHOWN ARE FOR PIPE BRACING, DUCTWORK TYP HANGER CABLE CROSS
AND OTHER EQPT BRACING MUST BE SIMILAR. PIPING BRACING
BOLT EQUIPMENT (ALL 4 SIDES)

PLOT SCALE: PLOT DATE:


B. PL SIZES MUST BE COORDINATED WITH PIPING,
TO SUPPORT

10:13:09 AM
DUCTWORK, AND EQPT ACTUAL SIZES. NOTES: EQUIPMENT

2/22/2022
(12mm BOLT)

SOLICITATION NO.:
C. INSULATION OR OTHER COVERING MATERIALS NOT

SA-480530-1$-SM505DT.dwg
A. DETAILS SHOWN FOR PIPE BRACING. DUCTWORK AND (TYP)

CONTRACT NO.:
SHOWN FOR CLARITY. EQUIPMENT BRACING MUST BE SIMILAR.

ISSUE DATE:
D. BRACE SIZES, SPACINGS, LOCATIONS, AND ATTACHMENTS EQUIPMENT
B. INSULATION OR OTHER COVERING MATERIALS NOT SHOWN
MUST BE AS SPECIFIED. BRACES MUST BE FULLY FOR CLARITY. ANGLE OR ROD BRACING AT EACH CORNER

1:1
COORDINATED WITH STRUCTURAL FRAMING AND WITH ANGLED 45 DEGREES HORIZONTAL TO EQPT
ALL OTHER BUILDING MATERIALS AND SERVICES. C. BRACING MUST BE FULLY COORDINATED WITH STRUCTURAL TO PREVENT MOVEMENT IN ANY DIRECTION
E. TRANSVERSE AND LONGITUDINAL BRACES MAY BE FRAMING AND ALL OTHER BUILDING MATERIALS AND SERVICES.
COMBINED WHERE REQUIRED TO RESIST MOTIONS IN NOTE: DETAIL SIMILAR FOR TRUSS ROOF CONSTRUCTION, SUPPORT FROM TRUSSES
D. CABLE MUST NOT DEFLECT MORE THAN 25mm WHEN
BOTH DIRECTIONS, AT THE SAME BRACE POINT.
SUBJECTED TO MAX HAND PRESSURE AT THE MIDPOINT

FILE NO.:
F. PIPING CLAMPS MAY BE UTILIZED IN LIEU OF WELDING OF SPAN.
AT COPPER, IRON, PVC, OR OTHER PIPING MATERIALS.

SUBMITTED BY:
C. HAIRSTON

C. HAIRSTON
DESIGN BY:

DRAWN BY:

A. HANKS
D

C. CURSI
CKD BY:
TYPICAL SEISMIC BRACING FOR SUS., VIB TYPICAL SEISMIC BRACING FOR

ANSI D
SIZE:
TYPICAL SEISMIC BRACING DETAILS ISO PIPING, DUCTWORK & EQPT SUSPENDED EQUIPMENT
D1 D4 D7

TRANSATLANTIC MIDDLE EAST DISTRICT


NTS NTS NTS

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


SEE ENLARGED DETAIL

WINCHESTER, VA 22602
CONCRETE ANCHOR
BLOCK (BY OTHERS)
HIGH TEMPERATURE MASTIC
CORROSION COATING (SEE DATA SHEET)
SEE NOTE #1 ANCHOR PLATE
AIRFLOW
HEAT SHRINK TAPE TO
MIN 3MM WATER SHED RING WELDED
SEAL RING TO JACKET
(VARIES W/PIPE SIZE) CONTINUOUSLY TO STEEL
ANCHOR AND CORROSION COATED
(TYP BOTH SIDES)
C
INSULATION
FLOW METER CONTROL PANEL - CONSTRUCTED AND SEALED
TEMPERATURE / PRESSURE PORT
TO PREVENT INGRESS OF WIND BLOWN SAND
WITH CAP - TYP
20 MESH STRAINER WITH AND SUITABLE FOR AMBIENT TEMPERATURE
VALLVED AND CAPPED BLOWDOWN RANGE OF 0 C TO 55 C DB TEMP AND 80%
DIFFERENTIAL PRESSURE SENSOR RELATIVE HUMIDITY - ENCLOSURE RATING IP 65
PT
CHR INLET TEMP SENSOR
TWO WAY
CONTROL VALVE

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


PT COMPRESSOR(S) CARRIER PIPE
CHS
JACKET
BUTTERFLY TS 150mm HIGH REINFORCED

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
VALVE - TYP CONCRETE PAD ENLARGED DETAIL
EVAPORATOR

MECHANICAL - DETAILS
TS

STANDARD DETAILS
CALIBRATED BALANCING VALVE
STEEL RING
FLEX CONNECTION - TYP

SA-480530
WELDED TO
B ANCHOR PLATE

OUTLET TEMP SENSOR DRAIN VALVE

VALVED PRESSURE GAUGE ASSEMBLY


ELASTOMERIC
ISOLATORS - TYP STEEL PIPE ANCHOR SPECIFICATIONS

NOTES: 1. STEEL ANCHOR PLATE AND WELDED RINGS FURNISHED BY THERMACOR. ANCHOR PLATE MUST MEET
ASTM A36 AND ON ALL SIZES MUST BE 50mm THICK. ANCHOR PLATE MUST EXTEND 65MM BEYOND THE
1. CHILLED WATER CONNECTIONS AT EVAPORATOR MUST BE GROOVED PIPE CONNECTIONS. CASING DIAMETER ON ALL SIDES. ANCHOR PLATE MUST BE CORROSION COATED WITH A HIGH
2. DO NOT WELD CONNECTIONS AT EVAPORATOR. TEMPERATURE MASTIC MATERIAL AFTER WATERSHED RINGS HAVE BEEN SEALED TO CASING BY HEAT
3. INSTALL CHILLERS DEAD LEVEL AND ANCHOR CHILLER TO CONCRETE PAD. SHRINK TAPE.
4. RELATIVE LOCATIONS OF WATER CONNECTIONS, COMPRESSORS, AND CONTROL PANEL MAY VARY BY MANUFACTURER 2. ANCHOR ASSEMBLY MUST BE POURED IN A CONCRETE BLOCK BY THE CONTRACTOR IN THE FIELD.
GENERALLY, THE ANCHOR BLOCK EXTENDS 300MM IN ALL DIRECTIONS FROM THE ANCHOR AND RESTS
2/22/2022 10:13:09 AM

ON UNDISTURBED EARTH. THE JOB SITE CONDITIONS MUST BE THE FINAL DETERMINING FACTOR FOR
ANCHOR BLOCK SIZING.
A SHEET ID
TYPICAL AIR COOLED CHILLER PIPING
$
DETAIL TYPICAL PIPE ANCHOR DETAIL
A1 NTS A6 NTS UNLESS OTHERWISE NOTED, LINEAR SM505
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

RELIEF AIR US Army Corps of


AIR HANDLING UNIT SECTIONS Engineers ®
POSITION 3 2 1 Middle East District
MODULE
#
G 1 PLENUM RETURN FAN SECTION (2 FANS)
RETURN
2 MIXING BOX/ECONOMIZER SECTION AIR HANDLING UNIT SECTIONS
AIR

DATE
3 MIXING BOX/ECONOMIZER SECTION
POSITION
4 AIR BLENDER SECTION MODULE
#
5 FILTER SECTION MERV 8 1 RETURN PLENUM SECTION
OA RELIEF AIR 6 ACCESS SECTION 2 RETURN FAN SECTION
SA
7 HEATING COIL SECTION 3 AIR MIXING SECTION
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 8 ACCESS SECTION 4 5 6 7 8 9 10 11
4 AIR MIXING SECTION
9 HUMIDIFIER SECTION (IF REQUIRED) 5 AIR BLENDER SECTION
10 ACCESS SECTION OA 6 FILTER SECTION
SA
11 COOLING COIL SECTION 7 ACCESS SECTION
RETURN
AIR 12 ACCESS SECTION 8 HEATING COIL SECTION
13 PLENUM SUPPLY FAN SECTION (2 FANS) 9 ACCESS SECTION

DESCRIPTION
14 FINAL FILTER SECTION MERV 14 10 COOLING COIL SECTION
F 15 SUPPLY PLENUM 11 SUPPLY FAN SECTION

TYPICAL AIR HANDLING UNIT DETAIL 1 TYPICAL AIR HANDLING UNIT DETAIL 2
F1 NTS F7 NTS

MARK
E

PLOT SCALE: PLOT DATE:


7 2 4
3 1 2 2 4

10:13:11 AM
2/22/2022
RA REL

SOLICITATION NO.:
ERU SECTIONS

SA-480530-1$-SM506DT.dwg
OA EA ERU SECTIONS

CONTRACT NO.:
POS# MODULE

ISSUE DATE:
POS# MODULE
1 OUTDOOR AIR INTAKE PLENUM SECTION 3
1 OUTDOOR AIR INTAKE PLENUM SECTION

1:1
2 FILTER SECTION MERV 8
2 FILTER SECTION MERV 8
3 ENERGY RECOVERY WHEEL SECTION
5 6 1 3 CROSS FLOW ENERGY RECOVERY SECTION
4 OUTDOOR/RELIEF AIR PLENUM FAN SECTION (2 FANS) 5
6 7 8 4 EXHAUST AIR PLENUM FAN SECTION
SA OA 5 SUPPLY AIR PLENUM FAN SECTION (2 FANS)
EA SA 5 EXHAUST AIR PLENUM SECTION
6 FILTER SECTION MERV 8

FILE NO.:
6 FILTER SECTION - MERV 13
7 RETURN AIR PLENUM SECTION

SUBMITTED BY:
7 CHILLED WATER COOLING COIL SECTION

C. HAIRSTON

C. HAIRSTON
DESIGN BY:

DRAWN BY:
8 ELECTRIC HEATING COIL SECTION

A. HANKS
D

C. CURSI
CKD BY:
9 SUPPLY AIR PLENUM FAN SECTION

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
ERU DETAIL 1 (TYPICAL FOR DOAS AND ERV) ERU DETAIL 2 (TYPICAL FOR DOAS AND ERV)

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


D1 NTS D5 NTS

WINCHESTER, VA 22602
SCREENED
OUTLET

AIR FLOW
INTERIOR EXTERIOR

STEEL ANGLE
C SUPPORT (TYP.)

WALL MOUNT
COLLAR WEATHER HOOD
DUCT ABOVE THE 300mm x 450mm
CONNECTION BE HINGED DOOR FOR
GALVANIZED DUCT CLEANOUT
AND DUCT BELOW BE
LF
I T
AND
TURN
26 GAUGE FIBERGLASS
REINFORCED PLASTIC LF
I T
AND
TURN

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


MOTORIZED
DAMPER
900mm

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
APPROX.
RISER DUCT

MECHANICAL - DETAILS
AIRFLOW

STANDARD DETAILS
FINISHED FLOOR

SA-480530
B
200mm DIA, 26
GAUGE FRP DUCT

PITCH 2mm IN 12m


AIR FLOW

200mm
MIN. BIRD SCREEN
TRUNK DUCT MOTOR SIDE
PEA GRAVEL OR DRY SUMP WELL GUARD
DRY SAND 100mm SEALED BOTTOM
MINIMUM EXTERIOR WALL
2/22/2022 10:13:11 AM

A PIT VENTILATION UNDERGROUND DUCT TYPICAL WALL MOUNTED EXHAUST FAN SHEET ID
DETAIL DETAIL $
A4 NTS A7 NTS
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SM506
1 2 3 4 5 6 7 8 9 10

SEE STRUCTURAL DRAWINGS FOR


EQUIPMENT ANCHORAGE NOTES

15° US Army Corps of


SIZE TO MAINTAIN 17.8 m/s
OUTLET VELOCITY Engineers ®
Middle East District
LOCATION OF ANCHORS
G

AS REQUIRED
(VERIFY LOCATION AND EXACT WELDED STAINLESS STEEL
NUMBER WITH EQUIPMENT EXHAUST STACK
OUTLINE OF MANUFACTURER)

DATE
EQUIPMENT 25 mm GALVANIZED STEEL
STRAP SECURED TO
EXHAUST STACK
GUY WIRE (4 REQUIRED)
PLAN VIEW OPPOSED BLADE DAMPER
130mm WIDE X 230mm L X DRIP LIP
WELDED JOINT
6mm THICK MIN BENT
ANCHOR PLATE. WELD TO TRANSITION (AS
BRANCH DUCT

3000 mm MIN.
EQUIPMENT ALL AROUND. REQUIRED)
SQUARE DAMPER ROD
DRAIN 15 mm
F.C. WELDED
COUPLING
130mm MIN.

VARIES
END EXHAUST
150mm MIN. EDGE WIDTH (TYP.)

DESCRIPTION
BEARING FAN WITH
F WIRED
INTAKE
NECK MOTORIZE
EQUIPMENT 150mm CONCRETE PAD D DAMPER
SECTION
AND BASE HARD CEILING CONCEALED
(NON T-BAR) DAMPER
REGULATOR SQUARE SOCKET DRIVER
FLOOR
DIFFUSER / REGISTER
BLANK PLATE
FLUSH COVER
ROOF

SEE STRUCTURAL ANCHORAGE


6mm NEOPRENE SCHEDULE ON STRCUTURAL
DRAWINGS SECURE SECURE GUY

MARK
STACK TO WIRE TO ROOF
ROOF (TYP.) (TYP.)
E VOLUME DAMPER W/ CONCEALED NOTES:

RTU / DOAS MOUNTING DETAIL REGULATOR DETAIL

PLOT SCALE: PLOT DATE:


1. 3000 mm MINIMUM HEIGHT IS SHOWN. INCREASE THE HEIGHT AS REQUIRED TO
E1 E4 COMPLY WITH THE RECOMMENDATIONS OF THE DISPERSION ANALYSIS.

10:13:13 AM
NTS NTS

2/22/2022
SOLICITATION NO.:

SA-480530-1$-SM507DT.dwg
2. USE THIS DETAIL FOR FUME HOODS, BIOLOGICAL SAFETY CABINETS, ISOLATION

CONTRACT NO.:
ROOM EXHAUST AND ANY OTHER APPLICABLE AREA.

ISSUE DATE:

1:1
EXHAUST STACK DETAIL
D7 NTS

FILE NO.:
NOTES:

SUBMITTED BY:
C. HAIRSTON

C. HAIRSTON
DESIGN BY:

DRAWN BY:
1. ENTIRE INSTALLATION MUST BE APPROVED LOCAL AUTHORITY HAVING JURISDICTION. SUBMIT SHOP

A. HANKS
D

C. CURSI
DWG'S FOR APPROVAL.

CKD BY:

ANSI D
2. DAMPER MUST BE NORMALLY CLOSED WITHOUT POWER.

SIZE:
OUTDOOR AIR DUCT CONNECETD
TO SAND LOUVER / INERTIA
INFILTRATION UNIT, SEE DETAILS IN

TRANSATLANTIC MIDDLE EAST DISTRICT


COMMUNICATION TO FACP MECH FLOOR PLAN DWGS FOR

US ARMY CORPS OF ENGINEERS


SA EACH AHU

201 PRINCE FREDERICK DRIVE,


COMMUNICATION TO DDC OA
SYSTEM WHERE INDICATED

WINCHESTER, VA 22602
FA CONTROL RELAY MODULE &
DETECTOR
FLEXIBLE BUILT-IN OA
CONNECTION MOTORIZED
230V-1PH-60HZ D COOLING COIL
END SWITCH STATUS (TYP) DAMPER (TYP)

DAMPER BUILT-IN RA
POWER SUPPLY MOTORIZED
SMOKE DAMPER OPERATOR ACCESS ACCESS FINAL PRE DAMPER (TYP)
VFD
DOOR PANEL FILTER FILTER
C RATED-WALL CONSTRUCTION, SEE VFD WITH MIXING AIR
ARCHITECTURAL DRAWINGS ELECTRIC DAMPER MOTOR CONTROL PANEL
OPERATOR SHALL BE CONTROLLED SUPPLY SECTION
INSIDE THE UNIT
BY DUCT DETECTOR OR ENGINEERED FAN
SMOKE CONTROL SYSTEM. RA
DUCT SMOKE DAMPER
ELASTOMERIC
PAD ISOLATOR
BREAK-AWAY DUCT CONNECTION (TYP)
CHANNEL
"S" SLIP OR EQUAL FOR
PROVIDE DUCT SUPPORT

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


RECTANGULAR DUCT
AT EACH END
150mm (H) HOUSEKEEPING PAD SEE STRUCT. DWGS

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA

MECHANICAL - DETAILS
1

STANDARD DETAILS
CD DRAIN CONN (EITHER SIDE OF MOUNTING, SEE
SM507
UNIT) COORDINATE DRAIN PAN CONN

SA-480530
LOCATION WITH DRAIN LOCATIONS.
B SLEEVE
SEE PLUMBING DWGS

DUCT
DUCT SMOKE DETECTOR NOTES:
300mm x 300mm HINGED UPSTREAM OF SMOKE BARRIER.
ACCESS DOOR SAMPLE TUBES MUST BE EXTENDED 1. SEE AHU SCHEDULE AND PLANS FOR ADDITIONAL PARTICULARS OF EACH UNIT, OTHER DUCT APPURTANCES, AND PHYSICAL DIMENSIONAL CONSTRAINTS
TO FULL WIDTH OF THE DUCT.
2. THE FAN SCROLL AND ROTATION INDICATED MUST NOT BE APPLIED THROUGHOUT. THE MANUFACTURER MUST REVIEW EACH AHU INSTALLATION AND PROPOSE
MIN. 38mm x 38mm x 355mm GAUGE THE SCROLL/FAN ROTATION THAT BEST SUITS EACH INSTALLATION WHILE KEEPING FAN SYSTEM EFFECT TO AN ABSOLUTE MINIMUM. THE SCROLL/FAN ROTATION
ANGLE SECURE TO COLLAR WITH #I0 MUST BE CAREFULLY INDICATED ON THE SHOP DRAWINGS SUBMITTAL FOR THE AHU AND IT MUST BE BROUGHT TO THE REVIEWER'S ATTENTION.
S.M.S. AT 200mm ON CENTER.
CEILING ACCESS PANEL ON NON T- 3. VAIRABILE AIR VOLUME AIR HANDLING UNIT HAS BUILT-IN AFMS AT THE SUPPLY FAN INLET.
BAR CEILING
2/22/2022 10:13:13 AM

A SHEET ID
TYPICAL SMOKE DAMPER DETAIL TYPICAL AIR HANDLING UNIT DETAIL 3 $
A1 NTS A6 NTS
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SM507
1 2 3 4 5 6 7 8 9 10

STRUCTURAL US Army Corps of


SUPPORTS (TYP) Engineers ®
Middle East District
G TUBING
DRUM

DATE
REEL FRAME

MOTOR
EXHAUST
CONNECTION

FIRST 3 HANGERS FOR EACH


PIPE AND BRANCH BE SPRING & TUBING FLANGE
NEOPRENE TYPE. TYPE "H" CONNECTION. GASKET

DESCRIPTION
FOR 100mm DIA. PIPE & REQUIRED BETWEEN
F SMALLER. TYPE "H-P" FOR FLANGE AND REEL
125mm DIA. PIPE & LARGER. POCKET
CONDENSATE
DRAIN IN 6"DIA. x 93' LONG FLEXIBLE TUBING (300°F
WALL CONTINUOUS RATING)
AV AV
RIGID PIPE
HANGER

COUNTERTOP INSTALL HANGER AS BUTTERFLY OR


CLOSE TO PIPE
AI
BALL SHUT OFF VEHICLE EXHAUST HOSE REEL DETAIL
ELBOW AS POSSIBLE
(TYP)
VALVE (TYP) E7 NTS
DPT
STRAINER
NON SLAM CHECK

MARK
SINK OR LAVATORY VALVE WITH
VIBRATION COUNTER WEIGHT
E ISOLATOR (TYP) 15mm
RESILIENT GASKET BY
ATMOSPHERIC VENT
CABINET UNIT MANUFACTURER
DOOR REDUCER (TYP) PRESSURE GAGE

PLOT SCALE: PLOT DATE:


ROOFTOP CONDENSATE DRAIN,

10:13:15 AM
2/22/2022
PACKAGED UNIT 12 mm REFER MECHANICAL

SOLICITATION NO.:
SUCTION DIFFUSER

SA-480530-1$-SM508DT.dwg
PUMP FLOOR PLAN FOR
TAILPIECE WITH ANCHOR RTU TO CURB

CONTRACT NO.:
DISCHARGE
DRAIN CONN. PER MANUFACTURER'S

ISSUE DATE:
WASTE NOTE #3 RECOMMENDATION 75 mm
DRAIN FLOOR

1:1
IN WALL
HOSE CLAMP TRAP
HEIGHT VARIES
(TYP.) PER ROOF SLOPE 300mm AT HIGHEST ROOF
WALL 25mm MIN. DIA. PIPE STAND CONCRETE PAD LINE WHERE UNIT IS

FILE NO.:
HEAVY DUTY INSTALLED
ESCUTCHEON SLOPED ROOF
BLACK NOTES:

SUBMITTED BY:
(TYP.) PRE-FABRICATED ROOF,
RUBBER HOSE

C. HAIRSTON

C. HAIRSTON
REFER TO DETAIL A1 / SA518

DESIGN BY:

DRAWN BY:
1. Y TYPE STRAINER BLOWDOWN HEIGHT ACCOMMODATES 210 LITER DRUM.

A. HANKS
D

C. CURSI
"P" TRAP

CKD BY:
2. PUMP INSTALLATION IS DIAGRAMMATIC AND INTENDED TO SHOW THE MAJOR COMPONENTS

ANSI D
SIZE:
REQUIRED FOR INSTALLATION. THE INSTALLED PIPING CONFIGURATION MUST BE BASED ON RETURN DUCT
THE ACTUAL PUMP PROVIDED. THE CONTRACTOR MUST SUBMIT FOR APPROVAL A SUPPLY DUCT
RECESSED TOE COORDINATION DRAWING SHOWING PUMP, PIPING, AND ACCESSORIES AS REQUIRED BY THIS NOTE:
INSTALLATION DETAIL.

TRANSATLANTIC MIDDLE EAST DISTRICT


KICK
FINISHED FLOOR 3. ALL PUMP AND PIPING DRAINS MUST BE HARD PIPED TO NEAREST FLOOR DRAIN, TYPICAL. 1. ROOF CURB MUST BE LEVEL AT TOP, VARY IN HEIGHT TO COMPENSATE

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


FOR ROOF PITCH OR SLOPE.

WINCHESTER, VA 22602
TYPICAL HORIZONTAL SPLIT CASE PUMP TYPICAL DOWN-DISCHARGE ROOFTOP
CONDENSATE DRAIN TO TRAP DETAIL PIPING DETAIL PACKAGED UNIT DETAIL
C1 NTS C4 NTS C7 NTS

C RETURN AIR DUCT W/


LINING (FIELD FABRICATE)
FLEXIBLE
HIGH LEVEL CONNECTION
INDICATOR
FILTER

SECURE TO STRUCTURE
ABV. CEILING W/

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


ETHYLENE VIBRATION ISLATORS
RESERVOIR TANK (TYP.)
PRESSURE REDUCING

THAAD STANDARD FACILITIES


MAKE-UP SYSTEM VALVES SET AT BLDG

VARIOUS LOCATIONS, KSA


10mm HANGER FLEXIBLE

MECHANICAL - DETAILS
CONTROL PANEL HEIGHT PLUS EPSIG RODS CONNECTION

STANDARD DETAILS
HOA
20mm TO BACK DRAFT

SA-480530
GREEN RUN CONDENSER DAMPER
B LIGHT WATER SYSTEM
MANUAL VOLUME
PROVIDE SELF CONTAINED CONTROLS TO ACHIEVE THE FOLLOWING: DAMPER (TYP.)
RED LOW CHECK VALVE &
LEVEL LIGHT SHUT-OFF VALVE 1. INDICATE LOW SOLUTION LEVEL*.
CONDENSATE DRAIN,
2. INDICATE SOLUTION PUMP RUNNING. SEE NOTE 1
2 POSITION VALVE
3. START PUMP UPON A DROP IN PRESSURE. STOP PUMP
LOW LEVEL PRESSURE SWITCH, AT HIGH PRESSURE SETTING
INDICATOR HIGH / LOW REFRIGERANT PIPES
4. DISABLE PUMP ON LOW SOLUTION LEVEL CONNECTION SUPPLY AIR DUCT W/ 2m (MIN.) DUCT
PRESSURE GAUGE 5. MAINTAIN CHILLED WATER AND HOT WATER SYSTEMS LINING UPSTREAM OF THE UNIT
PUMP PRESSURE WITH PRVS. SPRING VIBRATION
ANCHOR BOLTS 110mm O X 4 EMBEDMENT, ISOLATORS (TYP) MANUAL VOLUME
TANK AND CONTROL PANEL. 150mm CONCRETE DAMPER (TYP.)
*LOW SOLUTION LEVEL ALSO SENDS ALARM TO BLDG
HOUSEKEEPING PAD DDC SYSTEM. NOTE:
2/22/2022 10:13:15 AM

FLOOR 1. SECONDARY DRAIN OF THE UNIT MUST BE PIPED TO CONSPICUOUS LOCATION.

A TYPICAL DUCTED SPLIT INDOOR UNIT SHEET ID


GLYCOL MAKE-UP TANK PIPING DETAIL DETAIL $
A2 NTS A7 NTS
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SM508
1 2 3 4 5 6 7 8 9 10

US Army Corps of
DISPERSION Engineers ®
TUBE
TYPICAL TYPICAL Middle East District
G WATER/GLYCOL
PIPING
WATER/GLYCOL
PIPING
20mm AIR VENT.
MANUAL OR INSULATED TYPE K DUCT
FROM BACKUP COPPER PIPE, SIZE AS
AUTOMATIC HUMIDIFIER FOR TOWER
WITH CAP SHOWN ON PLAN

DATE
2
E 1:1
REDUCER, IF REQUIRED
ADAPTER TO AUTOMATIC SLOP
20mm HOSE MAKE-UP VALVE 100mm
20mm BALL VALVE 20mm 20mm X 100mm
THREAD-PROVIDE MIN
BALL VALVE NIPPLE
HOSE CAP NUT STRAINER
20mm DISPERSION
ADAPTER TO 20mm HOSE 20mm TUBE DRAIN
THREAD-PROVIDE HOSE CAP SHUT-OFF OVERFLOW
NUT 20mm BALL VALVE
VALVE
TYPICAL
ELEVATION ELEVATION WELDED WATER/GLYCOL
THREADED PIPING PIPING PIPING
ELEVATION HUMIDIFIER
12mm CW AUTOMATIC
TYPICAL CHILLED WATER AND GLYCOL COLLANT MAKE-UP DRAIN VALVE
TYPICAL MANUAL AIR VENT

DESCRIPTION
PIPING DRAIN VALVE CONNECTIONS 20mm
F 9mm TUBE 150mm MIN.
NOTES:
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR PLANS
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN
LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
NOTE: 20mm TO FS FLUID COOLER WITH
BUILT-IN AQUA STAT
DRAIN FROM BOTH LEAD AND STANDBY HUMIDIFIER CONNECTS TO OPERATED COLD WATER
TEMPERING VALVE
TYPICAL HIGH POINT VENTS & LOW POINT SINGLE DRAIN COOLER.

DRAINS DETAIL HUMIDIFIER PIPING DETAIL


E3 NTS
E8 NTS
AIRFLOW

MARK
E

PLOT SCALE: PLOT DATE:


TEMPERATURE / PRESSURE PORT CONTROL PANEL - CONSTRUCTED AND SEALED WOOD NAILING

10:13:17 AM
WITH CAP - TYP TO PREVENT INGRESS OF WIND BLOWN SAND STRIP

2/22/2022
FACTORY ASSEMBLED

SOLICITATION NO.:
AND SUITABLE FOR AMBIENT TEMPERATURE

SA-480530-1$-SM509DT.dwg
PREFABRICATED HINGED HOOD WITH

CONTRACT NO.:
RANGE OF 0 C TO 55 C DB TEMP AND 80%
20 MESH STRAINER WITH ROOF CURB LATCH & BIRD SCREEN
RELATIVE HUMIDITY - ENCLOSURE RATING IP 65;

ISSUE DATE:
VALLVED AND CAPPED BLOWDOWN
PROVIDE FIELD FABRICATED INSULATED SHED
OVER PANEL TO PROTECT FROM DIRECT SEE NOTE 2 SEE NOTE 1

1:1
SUNLIGHT. CURB CAP
PT
GCR
PT FS 150mm HIGH REINFORCED ROOF

FILE NO.:
GCS CONCRETE PAD GRAVITY BACKDRAFT
DAMPER SEE NOTE 2

SUBMITTED BY:
BUTTERFLY VALVE - TYP

C. HAIRSTON

C. HAIRSTON
DESIGN BY:

DRAWN BY:
CALIBRATED BALANCING VALVE TRANSITION DUCT TO

A. HANKS
DUCT (WHEN SHOWN)
D

C. CURSI
FULL SIZE OF DAMPER

CKD BY:

ANSI D
FLEX CONNECTION - TYP SUPPLIED WITH HOOD

SIZE:
FLOW SWITCH
NOTES:

TRANSATLANTIC MIDDLE EAST DISTRICT


DETAIL NOTES:
ELASTOMERIC 1. SECURE CURB CAP TO WOOD NAILING STRIP WITH 10mm CADMIUM PLATED LAG BOLTS NOT

US ARMY CORPS OF ENGINEERS


1. RELATIVE LOCATIONS OF WATER CONNECTIONS AND CONTROL PANEL

201 PRINCE FREDERICK DRIVE,


MAY VARY BY MANUFACTURER. ISOLATORS - TYP, OVER 300mm ON CENTER.
ANCHOR TO PAD 2. SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS (CONCRETE

WINCHESTER, VA 22602
2. PROVIDE STAINLESS STEEL MATERIAL FOR ALL PIPING, VALVES,
FLEXIBLE CONNECTION, INSTRUMENTS IN CONTACT WITH FLUID. ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST ROOF).

TYPICAL CLOSED-CIRCUIT FLUID COOLER


PIPING DETAIL ROOF MOUNTED GRAVITY HOOD DETAIL
C2 NTS C8 NTS
WATERPROOF
C SEAMS AND JOINTS
SECURE AREA NON-SECURE AREA

SHEET METAL SCREWS


40mm x 40mm x 5mm PERIMETER
HINGED ACCESS DOOR
RETAINING ANGLE. SECURE ANGLES @ SHEET METAL ANGLES
WITH LOCK
75mm O.C. ANGLES MUST LAP STRUCTURAL
OPENING 25mm MINIMUM (ON ALL FOUR
SIDES OF DUCT ON EACH SIDE OF WALL)
SEE NOTE 1 SEE NOTE 2

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


R=
CONDENSATE DRAIN

1.5
150 OR 12 mm BIRD SCREEN

W
LESS
TYP. CONTINUOUS SEAL WITH

THAAD STANDARD FACILITIES


SUITABLE MASTIC OR

VARIOUS LOCATIONS, KSA


150

30°

MECHANICAL - DETAILS
FOIL BACKED TAPE

STANDARD DETAILS
W
10mm∅ HARDENED STEEL BARS FLASHING &
150MM MIN CEILING LEVEL

450 mm MIN.
150 AT 150mm O.C. EACH WAY WELD AT

SA-480530
COUNTERFLASHING
ALL INTERSECTIONS ON DUCTS
B CONDENSATE PUMP 150 OR EXCEEDING 0.06 SQUARE METERS SHEET METAL
LESS
SEE NOTE 3 SCREWS

NOTES: NOTES: BREAKAWAY SLIP JOINT (TYP.)


1. RUN REFRIGERANT LINES TO OUTDOOR UNIT. SIZE PER
CURB
MANUFACTURER'S REQUIREMENTS. 10 GAUGE MINIMUM STEEL WALL CANT STRIP
1. INSTALL SECURITY BAR ASSEMBLY TO WALL AND FLOOR SYSTEMS.
SLEEVE EXTEND 65mm EACH SIDE
THE ABOVE INFORMATION IS FOR CONCEPTS ONLY. DETAIL WILL VARY
2. REMOVE CMU CORE (AS NECESSARY) TO CREATE FROM WALL
PER LOCATION.
CLEARANCE FOR PIPING. 2. PROVIDE SECURITY BARS IN SECURED WALLS FOR DUCTS OR OTHER 5mm to 10mm CLEARANCE
OPENINGS 0.06m2 AND LARGER.
3. CONNECT PUMPED CONDENSATE TO CONDENSATE DRAIN 3. PROVIDE ACCESS DOOR (SIZED TO SUIT) ON SECURED SIDE OF WALL.
PIPING AS SHOWN ON MECHANICAL FLOOR PLANS. ACCESS DOOR IS NOT REQUIRED IF DUCT IS TERMINATED WITH END
GRILLE OR OPENING WITH MESHES NEXT TO SECURED WALLS.
2/22/2022 10:13:17 AM

A UTILITY CONNECTIONS FOR TYPICAL DUCT PENETRATION THROUGH INTAKE OR EXHAUST DUCT ROOF SHEET ID
WALL-MOUNTED ACU SECURE WALL DETAIL GOOSE NECK DETAIL $
A1 NTS A4 NTS A7 NTS
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SM509
1 2 3 4 5 6 7 8 9 10

POWER AND MECHANICAL & PLUMBING EQUIPMENT POWER FLOOR/ROOF PLANS ONE-LINE DIAGRAMS
US Army Corps of
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION Engineers ®
Middle East District
G POWER DISTRIBUTION POWER DEVICES

FINAL DISTRIBUTION BOARD (DB) AND TAG LIST OF ANNOTATION TAGS (IDENTIFICATION OF TYPE, PURPOSE, OR INTENDED USE) FEEDER TAG. REFER TO FEEDER SCHEDULE ADJACENT TO ONE-LINE DIAGRAMS
FOR SOCKET-OUTLETS AND JUNCTION BOXES. LETTER SUBSCRIPT, ADJACENT TO

DATE
XXXX-DB1-P1 XXXX-DB1-X1 FOR FULL DESCRITION AND ADDITIONAL INFORMATION SUCH AS FEEDER
SYMBOLS, INDICATE THE FOLLOWING: LENGTH AND VOLTAGE DROP.
RING MAIN UNIT (RMU)
NUMBER DENOTES SEQUENCE
SOCKET AND JUNCTION BOX TYPES TABLE
LETTER DENOTES THE PRIMARY LOAD TYPE FOR DB:
L LIGHTING
TAG TYPE DESCRIPTION NOTES
M MECHANICAL AND PLUMBING EQUIPMENT AC ABOVE COUNTER OR COUNTERTOP MH 300mm ABOVE FINISHED OR WORKING
COUNTERTOP UON. RCD PROTECTION. MEDIUM VOLTAGE CIRCUIT BREAKER
P POWER (IN SMALLER FACILITIES MAY ALSO CONTAIN OTHER LOAD TYPES)
T TELECOMMUNICATIONS C COMPUTER (DEDICATED USE)
CP CONDENSATE PUMP FOR INTERIOR SPLIT TYPICAL MH 3200mm AFF (LOCATED IN
NUMBER DENOTES FACILITY FLOOR LEVEL FOR DB, STARTING WITH "1" FOR SYSTEM UNIT PLENUM SPACE)
FUSE
GROUND LEVEL. D LAUNDRY DRYER (DEDICATED USE)
DDC MECHANICAL DDC PANEL (DEDICATED USE) MH 1200mm UON.
"DB" DENOTES DISTRIBUTION BOARD OR "SLFP" DENOTES SITE LIGHTING FEEDER

DESCRIPTION
E EXPLOSION PROOF. RCD PROTECTION.
F PILLAR MEDIUM VOLTAGE DRAWOUT CIRCUIT BREAKER A AMMETER
EWC ELECTRIC WATER COOLER (DEDICATED INDIVIDUALLY CIRCUITED.
DENOTES FACILITY ABBREVIATED NAME. REFER TO FACILITY LABELING USE)
REFERENCE TABLE ON SHEET SE002 FOR LIST OF ALL FACILITIES AND FA FIRE ALARM CONTROL UNIT/PANEL MH 1200mm UON.
ABBREVIATED NAMES. (DEDICATED USE) V VOLTMETER
G GROUND FAULT CIRCUIT INTERRUPTOR
MAIN DISTRIBUTION BOARD (MDB) AND TAG. HP HOT PLATE (DEDICATED USE) INDIVIDUALLY CIRCUITED. SHUTTERED
XXXX-MDB-1 TYPE. MH 300mm ABOVE COUNTERTOP UON.
M MEDIUM VOLTAGE DRAWOUT CIRCUIT BREAKER, MOTORIZED
NUMBER DENOTES SEQUENCE K KITCHEN CONVENIENCE (NON-DEDICATED SHUTTERED TYPE. INDIVIDUALLY
USE) CIRCUITED. MH 300mm ABOVE COUNTERTOP TRANSFER SWITCH
"MDB" DENOTES MAIN DISTRIBUTION BOARD UON. RCD PROTECTION.
DENOTES BUILDING IDENTIFIER KE KITCHEN EQUIPMENT (DEDICATED USE) INDIVIDUALLY CIRCUITED AND SHUTTERED
TYPE.
MW MICROWAVE (DEDICATED USE) INDIVIDUALLY CIRCUITED. SHUTTERED INDICATOR LAMPS
EXAMPLE OF DB ON PLAN DEFINED
TYPE. MH 300mm ABOVE COUNTERTOP UON. A B C
FINAL DISTRIBUTION BOARD THAT IS LOCATED AT THE GENERAL PURPOSE P PRINTER / COPIER (DEDICATED USE) MEDIUM VOLTAGE DISCONNECT SWITCH

MARK
GPWA-DB1-P1 WAREHOUSE FACILITY, ON THE GROUND LEVEL FEEDING PRIMARILY POWER PJ PROJECTOR (DEDICATED USE)
ELEMENTS, AND IS THE FIRST OF SUCH IN A SEQUENCE. PMU POWER MONITORING UNIT
R RCD RCD PROTECTION.
E RA COMM RACK (DEDICATED USE)
RD ROLL-UP DOOR (DEDICATED USE) MH 1200mm UON.
CIRCUITING LINEWORK SS SELECTOR SWITCH

PLOT SCALE: PLOT DATE:


RE REFRIGERATOR (DEDICATED USE) INDIVIDUALLY CIRCUITED. SHUTTERED TYPE

2/9/2022 9:35:51
IN A KITCHEN AREA. LOW VOLTAGE CIRCUIT BREAKER
CIRCUIT HOME RUN AND CIRCUIT HOMERUN TAG FOR FIXTURES AND SP SECURITY PANEL (DEDICATED USE) MH 1200mm UON.
DB1-P1-1

SOLICITATION NO.:

SA-480530-1$-SE001LG.dwg
EQUIPMENT FED FROM DB OR MDB.

AM
TC TELECOMMUNICATIONS EQUIPMENT INDIVIDUALLY CIRCUITED. TWIST LOCKING

CONTRACT NO.:
CIRCUIT NUMBER/S CABINET (DEDICATED USE) TYPE.

ISSUE DATE:
PANEL NAME (FACILITY ABBREVIATED NAME NOT SHOWN FOR BREVITY) TK TEA KETTLE (DEDICATED USE) INDIVIDUALLY CIRCUITED. SHUTTERED
TYPE. MH 300mm ABOVE COUNTERTOP UON.

1:1
CIRCUITING / CONNECTING LINES, WHEN SOLID LINE INDICATES EXPOSED TV TELEVISION MONITOR (DEDICATED USE) COORDINATE MH BEHIND CENTER OF TV LOW VOLTAGE CIRCUIT BREAKER, MOTORIZED
M
AND ADJCENT TO CATV OUTLET.
CIRCUITING / CONNECTING LINES, WHEN DASHED LINE INDICATES CONCEALED
VM VEHICLE MAINTENANCE / CHARGING MH 1200mm UON
UNDERGROUND CONDUIT OR DUCT BANK WITHIN BUILDING (DEDICATED USE)
WM LAUNDRY WASHING MACHINE (DEDICATED

FILE NO.:
NOTE: CIRCUITING / CONNECTING LINES ARE INTENDED TO BE A DIAGRAMMATIC USE)

SUBMITTED BY:
REPRESENTATION OF WIRING AND HOMERUN LOCATIONS ONLY, NOT THE ACTUAL PHYSICAL WP WEATHERPROOF IP24 RATED ENCLOSURE AND RCD

A. TRIBBETT
DESIGN BY:

DRAWN BY:
ROUTING OF WIRING. REFER TO PANEL SCHEDULES FOR WIRING AND CONDUIT INFORMATION PROTECTION. MH 1m ABOVE GROUND WHEN

S. HOLDEN

A. HANKS
D FOR BRANCH CIRCUITS. LOCATED EXTERIOR TO BUILDING.

CKD BY:
ST LOW VOLTAGE CIRCUIT BREAKER, SHUNT TRIP

L. KING

ANSI D
SIZE:
OTHER ELECTRICAL EQUIPMENT

TRANSATLANTIC MIDDLE EAST DISTRICT


ISOLATOR (DISCONNECT), MANUALLY OPERABLE, AND TAG.
2P 20 54 230V, 13A DUPLEX SOCKET-OUTLET WITH EARTH. MOUNTED TO WALL OR VERTICAL

US ARMY CORPS OF ENGINEERS


NF SURFACE AS INDICATED ON PLAN. MH 300mm UON.

201 PRINCE FREDERICK DRIVE,


NUMBER DENOTES AMPERE RATING

WINCHESTER, VA 22602
230V, 13A DUPLEX SOCKET-OUTLET WITH EARTH. FLOOR MOUNTED. IP24 AND IK08
2P 20 54 RATED PROTECTION.
NF GFCI LOW VOLTAGE CIRCUIT BREAKER, GFCI
NUMBER DENOTES IP RATING 230V, 13A DUPLEX SOCKET-OUTLET WITH EARTH. CEILING MOUNTED.
"54" FOR INDOOR EQUIPMENT
"55" FOR OUTDOOR EQUIPMENT INDUSTRIAL SOCKET-OUTLET WITH EARTH. MOUNTED TO WALL OR VERTICAL
"68" FOR SUBMERSIBLE EQUIPMENT SURFACE AS INDICATED ON PLAN. MH 300mm UON.
NUMBER DENOTES FUSE RATING OR "NF" DENOTES NON-FUSIBLE.
DENOTES NUMBER OF POLES NEMA 5-20R, 120V, 20A DUPLEX SOCKET-OUTLET WITH EARTH AND WALL MOUNTED,
MH 300mm UON. SPD SURGE PROTECTION DEVICE

C VFD VARIABLE FREQUENCY DRIVE


NEMA 5-15R DUPLEX RECEPTACLE, MH 400mm UON. 15A, 2P, 3W, 125V
EARTH

ELECTRICAL CABLE MANAGEMENT NEMA L5-20R TWIST LOCK RECEPTACLE, MH 1200mm UON. 20A, 2P, 3W, 125V
NOTE: REFER TO SHEETS SE541, SE542, AND SE543 FOR DETAILS ASSOCIATED WITH TRANSFORMER
CABLE TRAY AND CONDUIT INSTALLATIONS.
NEMA 5-20R QUAD RECEPTACLE, MH 627mm UON. 20A, 120V, 60Hz
CABLE TRAY (AND TAG) FOR ELECTRICAL WIRING / CABLING, ROUTING AND SYMBOL INDICATES DELTA CONNECTED PRIMARY AND GROUNDED WYE
LOCATION AS INDICATED ON PLANS. NEMA 5-20R QUAD RECEPTACLE, FLOOR MOUNTED. 20A, 120V, 60Hz

ELECTRICAL SYMBOLS LEGEND FOR FACILITIES


CT-01 CONNECTED SECONDARY

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


CABLE TRAY TAG. REFER TO SPECIFIC CABLE MANAGEMENT SCHEDULE IN J JUNCTION BOX. WALL MOUNTED, MH 300mm UON.
FACILITY PACKAGE FOR MORE INFORMATION REGARDING SIZE AND SYMBOL INDICATES DELTA CONNECTED PRIMARY AND DELTA SECONDARY
ELEVATION OF CABLE TRAY INDENTIFIED.

THAAD STANDARD FACILITIES


J JUNCTION BOX. CEILING MOUNTED.

VARIOUS LOCATIONS, KSA

STANDARD DETAILS
SYMBOL INDICATES DELTA CONNECTED PRIMARY AND HIGH RESISTANCE
CONDUIT (AND TAG) FOR ELECTRICAL WIRING / CABLING, ROUTING AND
C-01 NEMA L14-20R TWIST LOCK 120/240V SPECIAL PURPOSE POWER RECEPTACLE, GROUND CONNECTION ON SECONDARY

(SHEET 1 OF 2)
LOCATION AS INDICATED ON PLANS.
1200mm AFF UNO. 20A, SINGLE PHASE, 4W, WITH WEATHER PROOF ENCLOSURE.

SA-480530
CONDUIT TAG. REFER TO SPECIFIC CABLE MANAGEMENT SCHEDULE IN FACILITY MOUNTED TO WALL OR VERTICAL SURFACE AS INDICATED ON PLAN.
B PACKAGE FOR MORE INFORMATION REGARDING SIZE AND ELEVATION OF POTENTIAL TRANSFORMER
CONDUIT IDENTIFIED.
TWIST LOCK 16A, 230V, 50HZ RECEPTACLE, IPA44. SURFACE MOUNTED, UON.

TWIST LOCK 16A, 230V, 50HZ RECEPTACLE, IPA44. WALL MOUNTED.


52 MEDIUM VOLTAGE ELECTRICALLY OPERABLE DRAWOUT VACUUM
EXAMPLE OF SOCKET OUTLET ON PLAN WITH TAGS DEFINED CIRCUIT BREAKER

UPPER CASE LETTERS DESIGNATE SOCKET FOR TELEVISION MONITOR.


520 TV
230V 13A DUPLEX SOCKET STANDARD SYMBOL.

NUMBER INDICATES MOUNTING HEIGHT (mm) AFF TO CENTER OF SOCKET. CURRENT TRANSFORMER

EMERGENCY POWER OFF (EPO) PUSH BUTTON. MH 1200mm AFF UON.


GENERATOR
2/9/2022 9:35:51 AM

A SHEET ID
L.A. SURGE ARRESTER
3 $

SE001
1 2 3 4 5 6 7 8 9 10

LIGHTING FLOOR PLANS (LUMINAIRES) LIGHTING FLOOR PLANS (LUMINAIRE CONTROLS) EARTHING AND LIGHTNING PROTECTION PLANS GENERAL (ALL ELECTRICAL PLANS)
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION US Army Corps of
Engineers ®

NOTE: REFER TO MASTER LUMINIARE SCHEDULE ON SHEET SE620 FOR LIST OF ALL LUMINAIRE Middle East District
G TYPES IN THE PROJECT, THE PLAN SYMBOLOGY THAT IS USED FOR EACH TYPE, AND ADDITIONAL LIST OF ANNOTATION TAGS (IDENTIFICATION OF TYPE, PURPOSE, OR INTENDED USE) FOR LUMINAIRE G BARE COPPER EARTH CONDUCTOR
26.001 SHEET KEYNOTE
INFORMATION. REFER TO SHEETS STARTING WITH SE520 FOR LIGHTING DETAILS. SWITCHED DEVICES. LETTER SUBSCRIPT, ADJACENT TO SYMBOLS, INDICATE THE FOLLOWING:
RC COPPER TAPE CONDUCTOR
26.001

DATE
LUMINAIRES (BUILDING INTERIOR OR MOUNTED TO BUILDING EXTERIOR)
LUMINAIRE SWITCH TYPES TABLE
AIR TERMINATION ROD OR AIR TERMINAL
SHEET KEYNOTE SEQUENCE NUMBER
CEILING OR PENDANT MOUNTED LUMINAIRE STANDARD SYMBOLS. SYMBOL TAG TYPE DESCRIPTION NOTES
SHAPE IS INTENDED TO BE A REPRESENTATION OF THE 2D GEOMETRIC SHAPE D DIMMER AIR TERMINATION ROD OR AIR TERMINAL WITH MAST. NUMBER INDICATES MAST "26" INDICATES ELECTRICAL DISCIPLINE
OF THE LUMINAIRE, EXCEPT IN CASES WHERE FIXTURE LENGTH AND WIDTH OR 13 000 HEIGHT (mm).
DOS DIMMER WITH OCCUPANCY SENSOR
DIAMETER (AND ASSOCIATED SYMBOLOGY) IS TOO SMALL TO SEE AT
STANDARD 1:100 SCALE. FOR THESE INSTANCES A MINIMUM OF 300mm FOR EP EXPLOSION PROOF
LENGTH, WIDTH OR DIAMETER MAY BE SHOWN FOR A SYMBOL. M MOMENTARY ON/OFF LOW VOLTAGE AIR TERMINATION ROD ON MOUNTING PIPE. NUMBER INDICATES PIPE HEIGHT REFERENCE TO DETAIL
4 000 (mm).
ON ON-ONLY NUMBER WHERE DETAIL IS
A B OS OCCUPANCY SENSOR A1 LOCATED ON SHEET
DOWN CONDUCTOR
LETTER ADJACENT TO SYMBOL INDICATES FIXTURE TYPE. P PILOT LIGHT COMBINATION
SE501
WP WEATHERPROOF
BOLTED CONNECTION OR HYDRAULIC COMPRESSION
SHEET WHERE DETAIL IS

DESCRIPTION
SYMBOL WITH ADJACENT NUMBER (mm) INDICATES NON-TYPICAL MH OF BOUNDARY LINE
F 3000 2800
LUMINAIRE FOR PENDANT AND WALL MOUNTED LUMINAIRES. REFER TO 1-WAY LUMINAIRE SWITCH, WALL MOUNTED. MH 1200mm AFF UON. EARTH CONNECTION / EARTH ROD
LOCATED IN SFDN PACKAGE
LUMINAIRE SCHEDULE ON SE620 FOR TYPICAL MH OF WALL AND PENDANT TW TW INDICATES TEST WELL
LUMINAIRE TYPES. 2-WAY LUMINAIRE SWITCH, WALL MOUNTED. MH 1200mm AFF UON.
3000 2800
AFF TO BOTTOM OF OF LUMINAIRE FOR PENDANT MOUNTED LUMINAIRES. 3-WAY LUMINAIRE SWITCH, WALL MOUNTED. MH 1200mm AFF UON. RADAR EQUIPMENT GROUND CONNECTION POINT
FACILITY LABELING REFERENCE TABLE
AFF TO VERTICAL CENTER OF LUMINAIRE FOR WALL MOUNTED LUMINAIRES. a LOWER CASE LETTER DESIGNATES CONTROL ZONE, WHERE APPLIES. EQUIPMENT GROUND CONNECTION
ABBREVIATED NOTES
FULL NAME SYMBOL ID
NAME
EXAMPLE OF LUMINAIRE CONTROL / SWITCH ON PLAN WITH TAGS DEFINED STATIC EARTHING REEL THAAD OPERATIONS FACILITY TOFA A
UPPER CASE LETTER DESIGNATES DIMMER CONTROL / SWITCH TYPE.
THAAD EQUIPMENT MAINTENANCE TEMF B
SYMBOLS WITH DIAGONAL HATCHING FILL INDICATES EMERGENCY Da TINNED COPPER TAPE RISER OR THRU-ROOF FITTING FACILITY
LUMINAIRE. LOWER CASE LETTER DESIGNATES CONTROL ZONE "a".
TACTICAL VEHICLE SUNSHADE TVSH C
2-WAY LUMINAIRE CONTROL / SWITCH STANDARD SYMBOL EARTHING BAR

MARK
PBB MET PBB INDICATES PRIMARY BONDING BUSBAR RADAR PAD AND RADAR ENCLOSURE RPRE D
MET INDICATES MAIN EARTHING TERMINAL
UNSWITCHED LUMINAIRE CONTROL DEVICES
WALL MOUNTED LUMINAIRE STANDARD SYMBOLS. TYPICAL MH AS INDICATED
E IN "REMARKS" COLUMN ON MASTER LUMINAIRE SCHEDULE (AS APPLICABLE)
LAUNCHER PAD LAPA E
OS OCCUPANCY SENSOR, UNSWITCHED. CEILING MOUNTED.
OR REFER TO PLANS FOR MH.
HB a TACTICAL SITE POWER BUILDING TSPB F

PLOT SCALE: PLOT DATE:


2/9/2022 9:35:54
EXAMPLE OF A LUMINAIRE ON PLAN WITH TAGS DEFINED LOWER CASE LETTER DESIGNATES CONROL ZONE "a" WHERE APPLIES. TACTICAL CHILLER PLANT TCPL G

SOLICITATION NO.:
"HB" INDICATES OCCUPANCY SENSOR LOCATED IN HIGH BAY AREA,

SA-480530-1$-SE002LG.dwg
NUMBER (mm) INDICATES MOUNTING HEIGHT OF LUMINAIRE AFF OR ABOVE

AM
CONTRACT NO.:
GRADE TO CENTER OF WALL MOUNTED LUMINAIRE. PENDANT MOUNTED 4400mm AFF UON. BATTERY HEADQUARTERS BAHE H

ISSUE DATE:
3000 A VS VACANCY SENSOR, CEILING MOUNTED. SOLDIER'S BARRACKS SOBA I 1
UPPER CASE LETTER DESIGNATES LUMINAIRE TYPE "A". REFER TO

1:1
a MASTER LUMINAIRE SCHEDULE ON SHEET SE620 FOR MORE INFORMATION.
OFFICER'S BARRACKS OFBA J
DH DAYLIGHT HARVESTING SENSOR, CEILING MOUNTED.
LOWER CASE LETTER DESIGNATES CONTROL ZONE "a".
MOSQUE MOSQ K
LEG SHOWN INDICATES LUMINAIRE IS WALL MOUNTED. PUSH BUTTON. WALL MOUNTED. MH 1200mm AFF UON.

FILE NO.:
DINING FACILITY DIFA L
LUMINAIRE STANDARD PLAN SYMBOL

SUBMITTED BY:
OCCUPANCY SENSOR, UNSWITCHED. WALL MOUNTED. MH 2300mm UON.
CLUB FACILITY CLFA M

A. TRIBBETT
DESIGN BY:

DRAWN BY:
S. HOLDEN
CEILING MOUNTED EXIT SIGN LUMINAIRE SYMBOL. SOLID HATCHING

A. HANKS
D EXAMPLES OF WALL MOUNTED OCCUPANCY SENSORS ON PLAN

CKD BY:
INDICATES FACE/S AND ARROW/S INDICATE PATH OF EGRESS.

L. KING

ANSI D
GRANDSTAND AND FITNESS FIELD GAFF O

SIZE:
STANDARD MOUNTED CORNER MOUNTED
SYMBOL WITH LEG INDICATES WALL MOUNTED EXIT SIGN LUMINAIRE. OPERATIONS AND MAINTENANCE FACILITY OAMF P
MH 2032mm UON.

TRANSATLANTIC MIDDLE EAST DISTRICT


BATTERY VEHICLE MAINTENANCE FACILITY BVMF Q

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


INTERIOR WALL HAZMAT STORAGE HAST R

WINCHESTER, VA 22602
GENERAL PURPOSE WAREHOUSE GPWA S
OTHER LUMINAIRE CONTROL EQUIPMENT
PARKING LOT VEHICLE SUNSHADE PLVS T
EXTERIOR LIGHTING CONTROL CABINET FOR BLACKOUT LIGHTING MANUAL
OVERRIDE CONTROL OF FACILITY EXTERIOR AND FACADE LIGHTING. REFER TO PALLET BUILD SUNSHADE PBSS U
ELCC DETAIL C1 ON SHEET SE525.
WATCH TOWER WATO V 1

SECURITY CONTROL FACILITY SCFA W


C
GUARD HOUSE GUHO X 1

GATE HOUSE GAHO Y

GUARD HOUSE WITH SITTING AREA GHSA Z

SMALL ARMS / AMMUNITION STORAGE SAAS AA

ELECTRICAL SYMBOLS LEGEND FOR FACILITIES


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
ENTRY CONTROL POINT ECPO AB

SWITCHGEAR AND GENERATOR FACILITY SAGF AC

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
SEC METERING BUILDING SMBU AD

STANDARD DETAILS

(SHEET 2 OF 2)
FUEL STATION FUST AE

SA-480530
B FUEL FARM FUFA AF

FIRE PUMP HOUSE FPHO AG

COMMUNICATIONS BUILDING COBU AH


WASTEWATER TREATMENT - GREY
WTGS AI
STORAGE
WATER TREATMENT AND PUMP FACILITY WTPF AJ

SMP VEHICLE STORAGE WAREHOUSE SVSW AK

SMP EQUIPMENT MAINTENANCE FACILITY SEMF AL


2/9/2022 9:35:54 AM

SMP PARTS WAREHOUSE SPWA AM

A NOTES: SHEET ID
1. FACILITY HAS MULTIPLE INSTANCES. REFER TO ONE-LINE DIAGRAM IN FACILITY
PACKAGE FOR MORE INFORMATION ON LABELING OF THE INSTANCES. $

SE002
1 2 3 4 5 6 7 8 9 10

GENERAL NOTES GENERAL NOTES


(FACILITIES DESIGNED UNDER SBC STANDARDS) (FACILITIES DESIGNED UNDER UFC STANDARDS) US Army Corps of
Engineers ®
Middle East District
G ALL ELECTRICAL EARTHING AND LIGHTNING PROTECTION ALL ELECTRICAL
1. SHEETS SE001 AND SE002 ARE STANDARD LEGEND SHEETS. NOT ALL SYMBOLS MAY APPEAR ON 1. PROVIDE EARTHING CONDUCTOR FOR ALL FEEDERS AND BRANCH CIRCUITS SIZED PER KSA CODE 1. REFER TO SHEET SG003 AND FOR ABBREVIATIONS. REFER TO SHEET SG005 FOR GENERAL 33. NORMALY NON–CURRENT-CARRYING CONDUCTIVE MATERIALS ENCLOSING ELECTRICAL
DRAWINGS IN ALL FACILITIES IN THE PROGRAM. REQUIREMENTS, UNLESS OTHERWISE INDICATED. SYMBOLOGY. CONDUCTORS OR EQUIPMENT, OR FORMING PART OF SUCH EQUIPMENT, INCLUDING ENCLOSURES,
CABINETS, JUNCTION BOXES, DUCTS, AND CONDUITS, MUST BE ELECTRICALLY CONNECTED TO THE

DATE
2. REFER TO SITE ELECTRICAL DRAWINGS FOR MORE INFORMATION REGARDING INCOMING 2. REFER TO SHEET SE601 FOR TYPICAL EARTHING RISER DIAGRAM. 2. REFER TO SHEETS SE001 AND SE002 FOR ELECTRICAL LEGEND AND GENERAL NOTES. GROUNDING ELECTRODE SYSTEM. THE INSTALLATION MUST MEET THE REQUIREMENTS OF NFPA 70
DUCTBANK ROUTING TO FACILITIES. INCOMING CONDUITS FROM SITE TO FACILITY MUST BE ARTICLE 250 GROUNDING AND BONDING.
TRANSPOSED AS NEEDED 3. REER TO SHEETS STARTING AT SE501 FOR TYPICAL EARTHING AND LIGHTNING PROTECTION 3. PERFORM ALL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC VERSION
DETAILS. 2020), APPLICABLE NFPA SECTIONS, UFC, AND ALL OTHER APPLICABLE CODES INCLUDING LOCAL
3. REFER TO SHEET SG003 FOR STANDARD ABBREVIATIONS. AMENDMENTS.
4. ALL METALLIC CABLE TRAY MUST BE BONDED WITH BONDING STRAP NOT SMALLER THAN
4. ALL WIRING FOR LIGHTING AND POWER CIRCUITS MUST BE 4.0mm² MINIMUM. REQUIRED BY APPLICABLE CODES AND STANDARDS. 4. THE DRAWINGS REPRESENT THE DESIGN INTENT. PROVIDE ALL ACCESSORIES AND
APPURTENANCES INCLUDING, BUT NOT LIMITED TO, SLEEVES, OPENINGS, SUPPORTS, BOXES,
5. ALL WIRING MUST BE COPPER. 5. EARTHING AND LIGHTNING PROTECTION SYSTEMS MUST BE INSTALLED PER KSA RULES AND AND PATCHING AS REQUIRED TO EXECUTE THE CONTRACT DOCUMENTS.
REGULATIONS.
6. ALL WIRES MUST BE SIZED FOR REQUIRED VOLTAGE DROP. 5. LIGHTING AND POWER DESIGN ARE NOT SHOWN FOR ALL AREAS. LIGHTING AND POWER
6. CONTRACTOR MUST VALIDATE EARTHING CALCULATIONS ARE SUITABLE TO ACTUAL SITE LAYOUTS SHOWN ARE INTENDED TO CONVEY SAMPLE BRANCH CIRCUIT DESIGN IN
7. CONTRACTOR MUST COMPLY WITH ALL CONTRACT REQUIREMENTS AND ALL APPLICABLE CODES, CONDITIONS. ACCORDANCE WITH THE MIDDLE EAST DISTRICT DESIGN INSTRUCTION MANUAL CONCEPT
LAWS, AND REGULATIONS, INCLUDING KSA CIVIL DEFENSE CODES. SUBMITTAL REQUIREMENTS.

DESCRIPTION
7. THE DESIGNS SHOWN FOR THESE SYSTEMS ARE SCHEMATIC AND ARE INTENDED TO SHOW BASIC
F 8. WHERE MULTIPLE CIRCUITS ARE COMBINED IN A SINGLE RACEWAY, THE CONTRACTOR MUST SYSTEM DESIGN INTENT. CONTRACTOR MUST VERIFY DIMENSIONS AND SITE CONDITIONS AND 6. MOUNTING HEIGHT, UNLESS OTHERWISE NOTED, IS TO CENTER LINE OF EQUIPMENT; EXCEPT
DETERMINE THE EXACT NUMBER OF CONDUCTORS, ROUTING, AND SIZE OF THE RACEWAY PER PROVIDE SYSTEMS THAT COMPLY WITH CODE REQUIREMENTS. MOUNTING HEIGHT OF LIGHTING FIXTURES IS TO BOTTOM OF FIXTURE.
ALL APPLICABLE CODES.
8. ACTUAL JOB SITE CONDITIONS MAY NECESSITATE SLIGHT ALTERATIONS IN THE EARTHING ROD 7. MOUNT OUTLET BOXES SO THAT NONE OCCUR BACK TO BACK IN WALLS. COORDINATE DEVICE
9. THE SPECIFICATION AND THE DRAWINGS ARE NOT INTENDED TO SHOW ALL DETAILS, WIRING, PIT LOCATIONS. PROVIDE SPACING PER BS EN 62305. MOUNTING HEIGHTS WITH APPROVED CASEWORK SUBMITTALS, ARCHITECTURAL ELEVATIONS
BOXES, COVERS, FITTINGS, AND SPECIAL CONSTRUCTION WHICH MAY BE NECESSARY OR AND DETAILS, AND WORK OF OTHER TRADES PRIOR TO INSTALLATION.
REQUIRED. THE CONTRACTOR MUST FURNISH, INSTALL AND CONNECT ALL REQUIRED WORK IN 9. THE SAME EARTHING ROD PIT CANNOT BE USED FOR BOTH BUILDINGS AND MAIN ELECTRICAL
ORDER TO MAKE THE INSTALLATION COMPLETE AS INDICATED BY THIS SPECIFICATION AND THE EARTHING. 8. MECHANICAL EQUIPMENT IS SHOWN IN APPROXIMATE LOCATIONS. FOR EXACT LOCATIONS OF
DRAWINGS. "PROVIDE" MEANS FURNISH AND INSTALL COMPLETE. "APPROVED" MEANS APPROVED MECHANICAL EQUIPMENT AND PIPING, SEE MECHANICAL DRAWINGS.
BY OWNER'S REPRESENTATIVE. "DIRECTED" MEANS DIRECTED BY THE OWNER'S 10. COORDINATE LOCATIONS OF EARTHING BUS BARS WITH EQUIPMENT IN ELECTRICAL ROOMS AND
REPRESENTATIVE. OTHER SPACES TO PREVENT CONFLICTS. 9. COORDINATE THE LOCATIONS AND MOUNTING HEIGHTS OF LIGHTING FIXTURES IN MECHANICAL,
ELECTRICAL AND ELEVATOR ROOMS WITH THE FINAL LOCATIONS OF PIPES, DUCTS AND OTHER
10. THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW EXACT ROUTING OF CIRCUITING WIRING 11. THE EARTHING AND LIGHTNING PROTECTION SYSTEMS MUST BE INSTALLED PER KSA RULES AND EQUIPMENT FOR BEST ARRANGEMENT. FIXTURES MUST BE EASILY ACCESSIBLE FOR
AND EXACT LOCATION OF EQUIPMENT. CONTRACTOR MUST BECOME FAMILIAR WITH JOB REGULATIONS. MAINTENANCE.
CONDITIONS AND MUST ARRANGE ALL WORK TO AVOID CONFLICTS. ALL FINAL LOCATIONS OF
NEW CONDUITS, OUTLETS, AND EQUIPMENT MUST BE SUBJECT TO APPROVAL. 12. THE COMPLETE INSTALLATIONS MUST MEET THE REQUIREMENTS OF BS EN 62305-1 THRU E, BSI 10. EMERGENCY LUMINAIRES WITH BATTERY PACKS MUST BE FED WITH NORMAL CIRCUIT AND
STANDARDS PUBLICATION. LOCAL CONTROL. BATTERY PACKS TO BE FED AHEAD OF LOCAL CONTROL.

MARK
11. PROVIDE ALL ITEMS INDICATED ON DRAWINGS AND REQUIRED BY SPECIFICATIONS, INCLUDING:
ALL SUPPORTS, HARDWARE AND ACCESSORIES, BRANCH CIRCUIT WIRING AND DEVICES. 13. THE LIGHTNING PROTECTION SYSTEM MUST BE INSTALLED IN A NEAT AND INCONSPICUOUS 11. MOUNT BOTTOM OF WALL-MOUNTED EXIT SIGNS 155mm ABOVE THE TOP OF DOOR FRAME.
E MANNER SO THAT ALL COMPONENTS WILL BLEND IN WITH THE APPEARANCE OF THE BUILDINGS.
12. ALL LISTED MATERIALS AND EQUIPMENT ARE INDICATIVE OF COMPLETE AND WHOLE UNITS 12. WHERE LIGHT SWITCHES ARE INDICATED TO BE MOUNTED BEHIND DOOR, MOUNT SUCH
(UNLESS SPECIFICALLY INDICATED TO THE CONTRARY) AND MUST BE FURNISHED AS SUCH. 14. DOWN CONDUCTORS MUST BE AS SHORT AS POSSIBLE AND ROUTED DIRECTLY TO THEIR SWITCHES A MINIMUM OF 1170mm FROM HINGED SIDE.

PLOT SCALE: PLOT DATE:


RESPECTIVE TEST/JUNCTION CLAMP.

10:50:36 AM
13. ALL CONSTRUCTION UNDER THIS CONTRACT MUST BE INSTALLED IN A NEAT AND WORKMANLIKE 13. WHERE MORE THAN ONE SWITCH OCCURS IN HOLLOW METAL FRAME, MOUNT ONE ABOVE THE

3/8/2022
MANNER BY ELECTRICIANS SKILLED AND LICENSED/REGISTERED IN THE TRADE. THE 15. ALL BENDS IN LIGHTNING PROTECTION SYSTEM CONDUCTORS MUST HAVE A RADIUS PER BS EN OTHER WITH TOP SWITCH MOUNTED AT 1200mm.

SOLICITATION NO.:

SA-480530-1$-SE003GN.dwg
CONTRACTOR MUST REMOVE AND REPLACE ALL WORK WHICH IS NOT INSTALLED AS APPROVED. 62305.

CONTRACT NO.:
14. CONDUIT ROUTING IS PROVIDED FOR DESIGN INTENT UNLESS INDICATED OTHERWISE.

ISSUE DATE:
14. UNLESS OTHERWISE NOTED, ALL MATERIALS AND EQUIPMENT MUST BE NEW, APPROVED 16. ALL METAL PARTS WITH 2m OF POTENTIALLY LIVE METAL SURFACES MUST BE EARTHED. COORDINATE ROUTE WITH FIELD CONDITIONS AND WORK OF OTHER TRADES. ROUTE CONDUIT
QUALITY, AND SPECIFICATION GRADE. WITHIN BUILDING PARALLEL AND PERPENDICULAR TO THE BUILDING LINES.

1:1
17. EARTHED METAL BODIES WITHIN THE BONDING DISTANCE DETERMINED BY BS EN 62305 MUST BE
15. ALL CUTTING REQUIRED FOR THE INSTALLATION OF ELECTRICAL CONSTRUCTION UNDER THIS BONDED TO THE SYSTEM IN ACCORDANCE WITH THOSE REQUIREMENTS. 15. LOCATE ALL RACEWAYS TO AVOID INTERFERENCE WITH DUCTS, PIPES, MECHANICAL
CONTRACT MUST BE ACCOMPLISHED IN SUCH MANNER AS NOT TO CAUSE STRUCTURAL OR EQUIPMENT, WITH REMOVAL OF CEILING TILES, OR WITH ACCESS TO EQUIPMENT WHICH
ARCHITECTURAL DAMAGE TO BUILDING OR LEAVE UNSIGHTLY SURFACES. THIS CONTRACTOR 18. UNDERGROUND METALLIC PIPING ENTERING EACH APPLICABLE BUILDING MUST BE BONDED TO REQUIRES PERIODIC ADJUSTMENT OR MAINTENANCE.
MUST BE RESPONSIBLE FOR PATCHING TO PROVIDE A NEAT AND FINISHED SURFACE EQUAL TO THE NEAREST DOWN CONDUCTOR OR EARTH ELECTRODE.
SURROUNDING UNDISTURBED SURFACES WHEREVER CUTTING, PATCHING, DAMAGE OR REMOVAL 16. COORDINATE THE LOCATION OF CONDUIT ENTRANCES FOR ALL EQUIPMENT WITH APPROVED

FILE NO.:
OF EQUIPMENT IS PERFORMED UNDER THIS CONTRACT. ALL PATCHING AND RESTORING OF 19. THE RESISTANCE OF ANY POINT IN THE LIGHTNING PROTECTION EARTH CONTINUITY SYSTEM TO SUBMITTALS PRIOR TO INSTALLING THE PATHWAYS TO SERVE THE EQUIPMENT.

SUBMITTED BY:
SURFACES MUST BE PERFORMED BY WORKMEN SKILLED IN THE TRADE INVOLVED AND MUST BE THE LIGHTNING PROTECTION EARTH ELECTRODE MUST NOT EXCEED 5 OHMS.

A. TRIBBETT
SUBJECT TO APPROVAL. 17. PROVIDE PULL BOXES TO FACILITATE CABLE PULLING AT A MINIMUM OF ONE PULL BOX EVERY

DESIGN BY:

DRAWN BY:
S. HOLDEN

A. HANKS
D 20. THE RESISTANCE OF ANY POINT IN THE EQUIPMENT EARTH CONTINUITY SYSTEM TO THE MAIN 30.5M OF STRAIGHT CONDUIT AND ONE AFTER TWO 90 DEGREE (OR EQUIVALENT) BENDS).

CKD BY:
L. KING

ANSI D
16. THE ELECTRICAL CONTRACTOR MUST REVIEW REQUIREMENTS FOR THE INSTALLATION OF EARTH ELECTRODE MUST NOT EXCEED 5 OHMS.

SIZE:
ELECTRICAL PORTIONS OF WORK INDICATED ON THE CONSTRUCTION DOCUMENTS OF OTHER 18. SEAL PENETRATIONS THROUGH FLOORS OR RATED PARTITIONS TO MAINTAIN THE INTEGRITY OF
TRADES AND INCLUDE REQUIREMENTS IN BIDDING THIS CONTRACT. 21. A MINIMUM DISTANCE OF 7m MUST BE PROVIDED BETWEEN ANY BUILDING EARTH ELECTRODE THE FIRE AND ACOUSTIC RATINGS. COORDINATE LOCATIONS OF SMOKE/FIRE PARTITIONS WITH
AND THE MAIN EARTH ELECTRODE. LIFE-SAFETY DRAWINGS.

TRANSATLANTIC MIDDLE EAST DISTRICT


17. MECHANICAL EQUIPMENT IS SHOWN IN APPROXIMATE LOCATIONS. VERIFY LOCATION AND
TERMINATION REQUIREMENTS WITH MECHANICAL DRAWINGS AND MECHANICAL CONTRACTOR 22. REFER TO TELECOM DRAWINGS FOR TELECOM EARTHING SYSTEM. 19. STOP CABLE TRAY SHORT OF RATED PARTITIONS. UTILIZE CONDUIT SLEEVES OF EQUIVALENT

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


PRIOR TO INSTALLATION OF ELECTRICAL CONNECTIONS, CONDUIT, AND CONDUCTORS. CAPACITY AND LISTED FIRESTOP ASSEMBLIES TO PENETRATE RATED PARTITIONS.
23. PERIMETER CONDUCTORS MUST BE INSTALLED AS CLOSE TO THE OUTER EDGES OF THE ROOF

WINCHESTER, VA 22602
18. FURNITURE SHOWN ON DRAWINGS IS FOR REFERENCE ONLY. REFER TO FURNITURE PLANS FOR AS PRACTICABLE. 20. PROVIDE NAMEPLATES ON THE EXTERIOR OF ALL ELECTRICAL PANELS AND ENCLOSURES AS
EXACT LOCATION AND DETAILS. FOLLOWS:
24. ADHESIVE USED WITH ADHESIVE AIR TERMINAL BASES AND CONDUCTOR FASTENERS MUST BE
19. SEAL PENETRATIONS THROUGH FLOORS OR RATED PARTITIONS TO MAINTAIN THE INTEGRITY OF COMPATIBLE WITH ROOF MATERIALS. LINE 1: DEVICE ID PANEL L1D1
THE FIRE AND ACOUSTIC RATINGS-REFER TO DETAILS ON SHEETS SE542 AND SE543. LINE 2: DEVICE RATING 100A, 208Y/120V - 3ϕ, 4W
25. AIR TERMINALS ARE TO BE LOCATED AS SHOWN ON DRAWINGS. PROVIDE SPACING PER BS EN LINE 3: POWER SOURCE FEEDS FROM PANEL MDP
20. PROVIDE CONDUIT RATED FOR HAZARDOUS AREAS WHERE INDICATED. 62305. LINE 4: INSTALLATION DATE INSTALLED: 2022

21. PROVIDE HAZARDOUS RATED EQUIPMENT WHERE INDICATED. PROVIDE EQUIPMENT ENCLOSURES 26. FINAL AIR TERMINAL HEIGHTS MUST BE SUFFICIENT TO ACHIEVE ZONE OF PROTECTION. FOR DISCONNECT SWITCHES AND MOTOR STARTERS THE TOP LINE MUST BE THE
RATED FOR APPROPRIATE USE. NAME/DESIGNATION OF THE EQUIPMENT BEING FED BY THE SWITCH/STARTER.
C 22. REFER TO MECHANICAL SCHEDULES IN MECHANICAL DRAWINGS FOR INDOOR ELECTRICAL DATA 21. PROVIDE CONDUCTORS AS REQUIRED TO ACCOMPLISH INDICATED CIRCUIT INSTALLATION AND
OF SPLIT SYSTEMS. POWER SWITCHING AS INDICATED FOR LIGHTING EVEN THOUGH CONDUCTOR QUANTITIES (HASH
MARKS) ARE NOT INDICATED ON CONDUIT SYMBOL OR HOMERUN SYMBOL.
23. REFER TO SHEET SM003 IN THE SFDN PACKAGE FOR DUCTLESS SPLIT SYSTEM PIPING 1. DEVICES AND EQUIPMENT MUST BE MOUNTED PER SPECIFICATIONS UNLESS OTHERWISE NOTED.
INSTALLATION DETAIL FOR ROOF-MOUNTED CONDENSING UNIT. 22. INDIVIDUAL BRANCH CIRCUITS FROM SIMILAR POWER SOURCE MAY BE CONSOLIDATED FOR
2. REFER TO SOCKET AND JUNCTION BOX TYPES TABLE ON SHEET SE001 FOR ADDITIONAL POWERED SYSTEMS FURNITURE UNLESS INDICATED OTHERWISE; CONDUIT FILL AND
INFORMATION REGARDING REQUIREMENTS AND MOUNTING HEIGHT FOR THESE TYPES OF CONDUCTOR DERATING MUST BE PER NEC. CONSIDER NEUTRAL CONDUCTORS TO BE
DEVICES. CURRENT CARRYING WHEN DERATING CONDUCTORS. PROVIDE 200% NEUTRAL CONDUCTORS.
LIGHTING
1. REFER TO LUMINIARE SCHEDULE FOR FACILITIES ON SHEET SE620 FOR LIST OF ALL LUMINAIRE 3. REFER TO SHEETS STARTING AT SE640 FOR STANDARD POWER TABLES AND SCHEDULES. 23. PROVIDE A 100mm THICK CONCRETE PAD UNDER ALL FLOOR-MOUNTED ELECTRICAL

ELECTRICAL GENERAL NOTES FOR FACILITIES


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
TYPES IN THE PROJECT, THE PLAN SYMBOLOGY THAT IS USED FOR EACH TYPE, AND ADDITIONAL DISTRIBUTION EQUIPMENT UNLESS OTHERWISE INDICATED.
LUMINAIRE REQUIREMENTS AND INFORMATION. 4. REFER TO SHEETS STARTING AT SE541 FOR TYPICAL POWER DETAILS.
24. PRIOR TO INSTALLATION, VERIFY REQUIRED CLEARANCES FOR THE FINISHED COLUMNS, HUNG
2. REFER TO SHEETS STARTING AT SE520 FOR TYPICAL LIGHTING DETAILS.

THAAD STANDARD FACILITIES


5. ALL CIRCUIT BREAKERS MUST BE RATED AT 50 DEGREES CELSIUS. CEILING, PARTITIONS, ETC... ARE MAINTAINED.

VARIOUS LOCATIONS, KSA


3. THE ELECTRICAL LIGHTING PLANS INDICATE THE APPROXIMATE LOCATION OF LUMINAIRES WITH 6. COORDINATE CONNECTION REQUIREMENTS OF SOCKETS BEHIND EQUIPMENT WITH MILLWORK

STANDARD DETAILS
25. COORDINATE THE LOCATION OF ALL WALL OUTLET BOXES FOR RECEPTACLES, SWITCHES,
CONTROL AND CIRCUIT ZONING. REFER TO ARCHITECTURAL DRAWINGS FOR REFLECTED CEILING AND ARCHITECTURAL PLANS PRIOR TO ROUGH-IN. ETC... WITH OTHER TRADES PRIOR TO INSTALLATION.
PLANS.

SA-480530
7. PROVIDE NAMEPLATES ON THE EXTERIOR OF ALL ELECTRICAL PANELS AND ENCLOSURES AS 26. VERIFY THE FINAL CONNECTION REQUIREMENTS FOR ALL EQUIPMENT WITH SUPPLIER AND
B 4. STAIR LUMINAIRES ARE ON EMERGENCY POWER AND MUST REMAIN ON AT ALL TIMES. LUMINAIRES FOLLOWS: PROVIDE JUNCTION BOXES, RECEPTACLES OR DISCONNECT SWITCHES AS REQUIRED. MAKE
ARE DIMMED TO 50% BY INTEGRAL OCCUPANCY SENSORS AFTER 15 MINUTES OF UNOCCUPANCY. ALL CONNECTIONS AS REQUIRED.
LINE 1: DEVICE ID PANEL L1D1
5. PROVIDE 90 MINUTES OF BATTERY POWER FOR ALL EMERGENCY FIXTURES. LINE 2: DEVICE RATING 100A, 400Y/230V - 3ϕ, 4W
27. ALL RACEWAYS RUNNING ACROSS AN EXPANSION JOINT MUST BE EQUIPPED WITH EXPANSION
LINE 3: POWER SOURCE FEEDS FROM PANEL MDP FITTINGS. FURNISH APPROVED EXPANSION FITTINGS.
6. EMERGENCY LUMINAIRES WITH BATTERY PACKS MUST BE FED WITH NORMAL CIRCUIT AND LOCAL LINE 4: INSTALLATION DATE INSTALLED: 2022
CONTROL. BATTERY PACKS TO BE FED AHEAD OF LOCAL CONTROL. 28. PROVIDE ALL EXTERIOR ELECTRICAL EQUIPMENT, RACEWAYS AND DEVICES AS
FOR DISCONNECT SWITCHES AND MOTOR STARTERS THE TOP LINE MUST BE THE WEATHERPROOF TYPE.
7. CORRIDOR LUMINAIRES ARE ON AT ALL TIMES AND ARE DIMMED TO 50% BY LOCAL OCCUPANCY NAME/DESIGNATION OF THE EQUIPMENT BEING FED BY THE SWITCH/STARTER.
SENSORS AFTER 15 MINUTES OF UNOCCUPANCY. 29. FURNISH PULL STRING IN EACH RACEWAY OVER 3050mm IN LENGTH WHERE PERMANENT WIRE
IS NOT INSTALLED. PULL STRING MUST BE RATED FOR 91Kg.
8. ALL LUMINAIRES IN A SPACE ARE TO BE ON A SINGLE ZONE UNLESS SHOWN OTHERWISE. ALL
LIGHTING CONTROLS IN THAT SPACE ARE TO CONTROL THAT ZONE. 30. RUN ALL WIRING CONCEALED UNLESS SPECIFIED OTHERWISE.
9. SHALLOW ELECTRICAL CLOSETS HAVE LUMINAIRES ABOVE THE DOOR ON THE INSIDE OF THE 31. PROVIDE MINIMUM NUMBER OF LUGS AND NECESSARY PROVISIONS TO ACCOMMODATE
CLOSET. THE LUMINAIRES ARE CONTROLLED BY PILOT LIGHT SWITCH ADJACENT TO THE DOOR
3/8/2022 10:50:36 AM

FEEDERS.
ON THE OUTSIDE OF THE ELECTRICAL CLOSET.
A 32. EXTEND 670mm EMPTY CONDUITS FROM RECESSED PANELBOARDS TO ABOVE CEILING AND
SHEET ID
CAP AND LABEL IN AN ACCESSIBLE LOCATION FOR FUTURE USE.

SE003
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES:


1. REFER TO SHEET SG003 FOR STANDARD ABBREVIATIONS.
2. REFER TO SHEET SE001 & SE002 FOR ELECTRICAL LEGEND SYMBOLOGY.
3. REFER TO SHEET SE003 FOR ELECTRICAL GENERAL NOTES. US Army Corps of
4. REFER TO SHEET SE620 FOR MASTER LUMINAIRE SCHEDULE. Engineers ®
5. REFER TO SHEETS STARTING AT SE520 FOR LUMINAIRE PLATES.
Middle East District
6. REFER TO SHEETS STARTING AT SE501 FOR TYPICAL EARTHING DETAILS.
G 7. REFER TO SHEET SE601 FOR TYPICAL EARTHING DETAILS.

DATE
15 mm (MINIMUM) DIAMETER,
3 X 25 mm (MINIMUM) 1.5 m (MINIMUM) LONG WITH
TINNED COPPER TAPE TOP SPIKE, TINNED COPPER
EARTH CONDUCTOR AIR TERMINATION ROD

PARAPET WALL
(REFER TO ARCH. DRAWINGS
FOR WALL MATERIAL/FINISH)
BRONZE OR
COPPER PVC-SHEATHED 3 x 25 mm
TAPE CLIP

DESCRIPTION
(MINIMUM) TINNED COPPER
F (CLIP TO BE FASTENED WITH TAPE
ADHESIVE
WHERE PENETRATION OF STRUCTURE BRONZE OR
IS NOT ALLOWED) COPPER
TAPE CLIP (SEE
DETAIL E1/SE501)

(TO BE FASTENED WITH


ADHESIVE SQUARE TAPE CLAMP TAPE HOLDER
WHERE PENETRATION OF
STRUCTURE IS NOT BRONZE OR COPPER
ALLOWED) AIR TERMINAL BASE

MARK
PVC-SHEATHED 3 x 25 mm
(MINIMUM) TINNED COPPER TAPE
E

PLOT SCALE: PLOT DATE:


2/9/2022 9:35:58
SOLICITATION NO.:

SA-480530-1$-SE501DT.dwg
TYPICAL TAPE CLIP TYPICAL X AND T TAPE CONNECTOR TYPICAL PARAPET AIR TERMINAL

AM
CONTRACT NO.:
E1 E3 E6

ISSUE DATE:
NO SCALE NO SCALE NO SCALE

1:1
FILE NO.:
SUBMITTED BY:
A. TRIBBETT
DESIGN BY:

DRAWN BY:
S. HOLDEN

A. HANKS
D

CKD BY:
L. KING

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
BRONZE OR COPPER TAPE CLIPS
@ 1 m CENTERS (TYPICAL)
(AT JUNCTIONS/CHANGES IN DIRECTION OF PARAPET WALL
CONDUCTORS, CLIPS TO BE WITHIN 200 mm
OF JUNCTIONS/CHANGES IN DIRECTION)
15 mm (MINIMUM) DIAMETER,
1.5 m (MINIMUM) LONG WITH
TOP SPIKE, TINNED COPPER
AIR TERMINATION ROD
SQUARE TAPE CLAMP OR
THRU-WALL FITTING
C

PVC-SHEATHED 3 x 25 mm
(MINIMUM) TINNED COPPER TAPE

EARTHING AND LIGHTNING PROTECTION DETAILS


ROOF SLAB

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


(TO BE FASTENED WITH
ADHESIVE WHERE
PENETRATION OF STRUCTURE

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
IS NOT ALLOWED)

STANDARD DETAILS
SA-480530
B BRONZE OR COPPER
AIR TERMINAL BASE
BRONZE OR COPPER
TAPE CLIP (SEE DETAIL
PVC-SHEATHED 3 x 25 mm E1 THIS SHEET)
(MINIMUM) TINNED COPPER TAPE

TYPICAL AIR TERMINAL (FLAT SURFACE) TYPICAL ROOF CONDUCTOR


A1 NO SCALE A5 NO SCALE
2/9/2022 9:35:58 AM

A SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SE501
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES:


1. REFER TO SHEET SG003 FOR STANDARD ABBREVIATIONS.
2. REFER TO SHEET SE001 & SE002 FOR ELECTRICAL LEGEND SYMBOLOGY.
3. REFER TO SHEET SE003 FOR ELECTRICAL GENERAL NOTES. US Army Corps of
4. REFER TO SHEET SE620 FOR MASTER LUMINAIRE SCHEDULE. Engineers ®
5. REFER TO SHEETS STARTING AT SE520 FOR LUMINAIRE PLATES.
Middle East District
6. REFER TO SHEETS STARTING AT SE501 FOR TYPICAL EARTHING DETAILS.
G AIR TERMINAL 7. REFER TO SHEET SE601 FOR TYPICAL EARTHING DETAILS.

DATE
AIR TERMINAL BASE (SEE
DETAIL A1/SE501)

EARTH ROD
TAPE CLIP (SEE DETAIL
CONNECTION HOUSED
E1/SE501)
INSIDE EARTH
INSPECTION PIT,
SECURELY POSITIONED
SQUARE TAPE CLAMP

DESCRIPTION
F

PVC SHEATHED 3 x 25mm (MIN)


TINNED COPPER TAPE

FRAME
ROOF
COPPER-BONDED
STEEL
EARTH ELECTRODE

MARK
E TYPICAL AIR TERMINAL BONDING TO EQUIPMENT DETAIL TYPICAL EARTH TEST WELL DETAIL
E1 NO SCALE E6 NO SCALE

PLOT SCALE: PLOT DATE:


2/9/2022 9:35:59
SOLICITATION NO.:

SA-480530-1$-SE502DT.dwg
AM
CONTRACT NO.:
ISSUE DATE:

1:1
650mm

FILE NO.:
SUBMITTED BY:
A. TRIBBETT
DESIGN BY:

DRAWN BY:
S. HOLDEN

A. HANKS
D

CKD BY:
L. KING

ANSI D
SIZE:
96mm
NOTE:
1) ALL EARTH CONDUCTORS ARE FASTENED

TRANSATLANTIC MIDDLE EAST DISTRICT


TO BUSBAR BY BOLTED CONNECTION.
2) EARTH BAR COMPRISED OF COPPER MATERIAL.

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
6.5mm

EARTH ROD TO TAPE CLAMP. 320x320x190mm CONCRETE EARTHING PIT


FINISHED CONNECTION
WRAPPED WITH DENSO TAPE.
C
TYPICAL EARTHING BAR DETAIL
ROD TO CABLE CLAMPS
C5 NO SCALE

EARTHING AND LIGHTNING PROTECTION DETAILS


PVC SHEATHED 3 x 25mm (MIN)

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


TINNED COPPER TAPE EARTH DOWN
CONDUCTOR FROM ROOF MOUNTED 70mm2 BARE COPPER
LIGHTNING PROTECTION SYSTEM CONDUCTOR FOR

THAAD STANDARD FACILITIES


EARTHING SYSTEM

VARIOUS LOCATIONS, KSA

STANDARD DETAILS
MULTIPLE EARTH RODS
ARE INTERCONNECTED

SA-480530
B WITH STRONG BRONZE
THREADED COUPLERS 19mm DIA. x 2.4m LONG SECTION, STEEL CORE
COPPER JACKETED TYPE, COMPRISING A HIGH
STRENGTH STEEL ALLOY CORE WITH MOLTEN
WELDED COPPER COVERING EARTH ELECTRODES.

PROVIDE TO DEPTH DETERMINED


BY EARTHING CALCULATION TINNED SOLID COPPER
EARTH BONDING LINK

TYPICAL TW EARTH PIT DETAIL TYPICAL CABLE TRAY BONDING DETAIL


A1 NO SCALE A5 NO SCALE
2/9/2022 9:35:59 AM

A SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SE502
1 2 3 4 5 6 7 8 9 10

LIGHTNING PROTECTION AIR TERMINAL GENERAL SHEET NOTES:


(SEE DETAIL E6/SE501)
1. REFER TO SHEET SG003 FOR STANDARD ABBREVIATIONS.
2. REFER TO SHEET SE001 & SE002 FOR ELECTRICAL LEGEND SYMBOLOGY.
3. REFER TO SHEET SE003 FOR ELECTRICAL GENERAL NOTES. US Army Corps of
4. REFER TO SHEET SE620 FOR MASTER LUMINAIRE SCHEDULE. Engineers ®
5. REFER TO SHEETS STARTING AT SE520 FOR LUMINAIRE PLATES.
Middle East District
6. REFER TO SHEETS STARTING AT SE501 FOR TYPICAL EARTHING DETAILS.
G 7. REFER TO SHEET SE601 FOR TYPICAL EARTHING DETAILS.

DATE
ROUTE PVC SHEATHED 3 x 25mm
(MIN) TINNED COPPER TAPE DOWN
CONDUCTOR FROM AIR
TERMINATION SYSTEM THROUGH
CONDUIT TO EARTH INSPECTION PIT
PULSAR

SCHEDULE 40 PVC CONDUIT WITH


INSULATION AROUND CONDUIT

SEAL PENETRATION TO
PREVENT WATER INFILTRATION

DESCRIPTION
F
ROOF PENETRATION ASSEMBLY GUYING RING

FIBER
GLASS GUY

STAY
TIGHTENER

MAST

MARK
E

PLOT SCALE: PLOT DATE:


2/9/2022 9:36:00
SOLICITATION NO.:

SA-480530-1$-SE503DT.dwg
AM
CONTRACT NO.:
BASE

ISSUE DATE:
ANCHOR,
TYP.

1:1
TYPICAL AIR TERMINAL ON TOP OF MAST

FILE NO.:
D6 NO SCALE

SUBMITTED BY:
A. TRIBBETT
DESIGN BY:

DRAWN BY:
S. HOLDEN

A. HANKS
D

CKD BY:
L. KING

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
GROUND FLOOR

EARTHING AND LIGHTNING PROTECTION DETAILS


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
THAAD STANDARD FACILITIES
VARIOUS LOCATIONS, KSA

STANDARD DETAILS
SA-480530
B

CONTINUE DOWN CONDUCTOR ROUTE


TO TEST WELL FOR CONNECTION TO
EARTHING ELECTRODE (SEE DETAIL
A1/SE502)
2/9/2022 9:36:00 AM

A COORDINATE CONDUIT SLEEVE WITH


STRUCTURAL DRAWING AND CIVIL UTILITIES. SHEET ID
$
TYPICAL DOWN CONDUCTOR ROUTING DETAIL
A1 NO SCALE UNLESS OTHERWISE NOTED, LINEAR SE503
DIMENSIONS ARE IN MILLIMETERS
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES:


1. REFER TO SHEET SG003 FOR STANDARD ABBREVIATIONS.
2. REFER TO SHEET SE001 & SE002 FOR ELECTRICAL LEGEND SYMBOLOGY.
3. REFER TO SHEET SE003 FOR ELECTRICAL GENERAL NOTES. US Army Corps of
4. REFER TO SHEET SE620 FOR MASTER LUMINAIRE SCHEDULE. Engineers ®
5. REFER TO SHEETS STARTING AT SE520 FOR LUMINAIRE PLATES.
Middle East District
6. REFER TO SHEETS STARTING AT SE501 FOR TYPICAL EARTHING DETAILS.
G 7. REFER TO SHEET SE601 FOR TYPICAL EARTHING DETAILS.

DATE
AIR TERMINAL TO BE
SUPPORTED AT POINT NO 15 mm (MINIMUM) DIAMETER,
LESS THAN ONE-HLAF THE 1.5 m (MINIMUM) LONG WITH
HEIGHT OF THE AIR TERMINAL TOP SPIKE, TINNED COPPER
15 mm (MINIMUM) DIAMETER, AIR TERMINATION ROD
1.5 m (MINIMUM) LONG WITH
TOP SPIKE, TINNED COPPER
AIR TERMINATION ROD

PARAPET WALL
(REFER TO ARCH. DRAWINGS
AIR TERMINAL TO BE FOR WALL MATERIAL/FINISH)
SUPPORTED AT POINT NO
LESS THAN ONE-HLAF THE

DESCRIPTION
HEIGHT OF THE AIR TERMINAL
F

(TO BE FASTENED WITH


ADHESIVE WHERE
PENETRATION OF STRUCTURE
IS NOT ALLOWED) TAPE HOLDER

BRONZE OR COPPER BRONZE OR COPPER


AIR TERMINAL BASE AIR TERMINAL BASE

MARK
PVC-SHEATHED 3 x 25 mm PVC-SHEATHED 3 x 25 mm
(MINIMUM) TINNED COPPER TAPE (MINIMUM) TINNED COPPER TAPE
E

PLOT SCALE: PLOT DATE:


2/9/2022 9:36:01
TYPICAL AIR TERMINAL (FLAT SURFACE) TYPICAL PARAPET AIR TERMINAL
E1 E5

SOLICITATION NO.:
NO SCALE NO SCALE

SA-480530-1$-SE510DT.dwg
AM
CONTRACT NO.:
ISSUE DATE:

1:1
FILE NO.:
SUBMITTED BY:
C. BRISKORN
DESIGN BY:

DRAWN BY:
C. PERILLA

A. HANKS
D

CKD BY:
L. KING

ANSI D
SIZE:
CAST BRONZE COVER
FRICTION FIT.

TRANSATLANTIC MIDDLE EAST DISTRICT


US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


70

WINCHESTER, VA 22602
FINISHED GRADE

C LOCKING NUT

#10 BRASS BALL CHAIN


51 457 DIA 51
73

COMPRESSION NUT

CAST BRONZE HOUSING

EARTHING AND LIGHTNING PROTECTION DETAILS


#4 1/2" LUG
REMOVABLE DOUBLE ENDED

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


THREADED STUD, 1/2" DIAM.
19

19 N.C. THREAD

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
EPOXY OR SPOT WELD THREAD COUPLING AFTER

STANDARD DETAILS
COMPLETING ALIGNMENT WITH HANGER FLOOR, INCLUDING
COVER ALIGNMENT.

SA-480530
B INSTALL PIGTAIL TO CONNECT TO
FACILITY GROUND GRID; DO NOT
GROUND RECEPTACLE PAINT YELLOW
CUT GROUND GRID WIRES.
SET IN FLOOR
4 000

INSTALL BELOW CONCRETE SLAB. EXOTHERMIC BONDING. GROUND

PAINT RED

PAINT THE WORD "GROUND"


IN 26 BLACK LETTERS AND
THE DATE TESTED IN 13
BLACK LETTERS
2/9/2022 9:36:01 AM

A SHEET ID
EQUIPMENT GROUND CONNECTION EQUIPMENT GROUND CONNECTION PLAN
A1 NO SCALE A6 NO SCALE $
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SE510
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES:


1. REFER TO SHEET SG003 FOR STANDARD ABBREVIATIONS.
2. REFER TO SHEET SE001 & SE002 FOR ELECTRICAL LEGEND SYMBOLOGY.
305x305x305mm COVERED CONCRETE HANDHOLE
3. REFER TO SHEET SE003 FOR ELECTRICAL GENERAL NOTES. US Army Corps of
4. REFER TO SHEET SE620 FOR MASTER LUMINAIRE SCHEDULE. Engineers ®
5. REFER TO SHEETS STARTING AT SE520 FOR LUMINAIRE PLATES.
USE ONLY TOP Middle East District
6. REFER TO SHEETS STARTING AT SE501 FOR TYPICAL EARTHING DETAILS.
G EXOTHERMIC WELD FOR 1 7. REFER TO SHEET SE601 FOR TYPICAL EARTHING DETAILS.
1/2" DIAMETER HORIZONTAL CONDUCTOR,
THREADED STUD THRU OR OR END OF RUN
70mm2 BARE COPPER

DATE
#2 INSULATED COPPER CONDUCTOR PERIMETER
GROUNDING CONDUCTOR, LOCKING NUT GROUND LOOP CONDUCTOR
6.1 METER LENGTH

COMPRESSION NUT
USE TOP AND SIDE EXOTHERMIC
PROVIDE RING LUG AT BOTH WELDS FOR 2 HORIZONTAL
ENDS OF GROUNDING CONDUCTORS, THRU OR END OF RUN
CONDUCTOR . RING LUG
SIZED FOR TERMINATION AT
1/2" DIAMETER STUD. 4m x 19mm DIA. GROUND ROD, STEEL CORE
ADAPTER COPPER JACKETED TYPE, COMPRISING A HIGH
3/4" THREADED ROD STRENGTH STEEL ALLOY CORE WITH MOLTEN
WELDED COPPER COVERING EARTH ELECTRODES.

DESCRIPTION
F

GROUND LOOP TO ROD CONNECTION


RADAR EQUIPMENT GROUND CONNECTION POINT EXOTHERMIC PROCESS
F1 NO SCALE F5 SCALE: NTS

MARK
E 305mm

PLOT SCALE: PLOT DATE:


2/9/2022 9:36:02
PVC-SHEATHED 3 x 25 mm (MINIMUM) NOTE:

SOLICITATION NO.:
1) ALL EARTH CONDUCTORS ARE FASTENED

SA-480530-1$-SE511DT.dwg
TINNED COPPER TAPE DOWN CONDUCTOR 96mm

AM
CONTRACT NO.:
FROM ROOF MOUNTED AIR TERMINATION TO BUSBAR BY BOLTED CONNECTION.

ISSUE DATE:
SYSTEM 2) EARTH BAR COMPRISED OF COPPER MATERIAL.

1:1
STEEL COLUMN

FILE NO.:
6.5mm

SUBMITTED BY:
C. BRISKORN
DESIGN BY:

DRAWN BY:
C. PERILLA

A. HANKS
D

CKD BY:
L. KING

ANSI D
SIZE:
TYPICAL EARTHING BAR DETAIL

TRANSATLANTIC MIDDLE EAST DISTRICT


D4

US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


NO SCALE

WINCHESTER, VA 22602
WALL MOUNTED TEST CLAMP
FOR DISCONNECTION OF EARTH
ELECTRODE FROM LIGHTNING
PROTECTION SYSTEM

EARTH ROD CONNECTION TO BE HOUSED INSIDE EARTH ROD TO TAPE CLAMP. 320x320x190mm CONCRETE EARTHING PIT
A EARTH INSPECTION PIT, SECURELY POSITIONED
C FINISHED CONNECTION
WRAPPED WITH DENSO TAPE.

ROD TO CABLE CLAMPS

EARTHING AND LIGHTNING PROTECTION DETAILS


ROYAL SAUDI AIR DEFENSE FORCES (RSADF)
EARTH CONDUCTOR TERMINATES AT EARTH ROD
TO TAPE CLAMP. FINISHED CONNECTION
TO BE WRAPPED WITH DENSO TAPE. PVC SHEATHED 3 x 25mm (MIN)
3 x 25 mm (MINIMUM) TINNED COPPER
TINNED COPPER TAPE EARTH DOWN

THAAD STANDARD FACILITIES


TAPE EARTH CONDUCTOR

VARIOUS LOCATIONS, KSA


CONDUCTOR FROM ROOF MOUNTED 70mm2 BARE COPPER
LIGHTNING PROTECTION SYSTEM CONDUCTOR FOR

STANDARD DETAILS
EARTHING SYSTEM

SA-480530
B GROUND ROD FOR TOFA, TEMF, LAPA, & PBSS - 4m x 19mm DIA.
GROUND ROD FOR TSPB, TCPL, & RPRE - 6m x 19mm DIA.
STEEL CORE COPPER JACKETED TYPE, COMPRISING A HIGH
STRENGTH STEEL ALLOY CORE WITH MOLTEN WELDED GROUND ROD FOR TOFA, TEMF, LAPA, &
COPPER COVERING EARTH ELECTRODES. PBSS - 4m x 19mm DIA.
GROUND ROD FOR TSPB, TCPL, &
RPRE - 6m x 19mm DIA.
STEEL CORE COPPER JACKETED TYPE,
COMPRISING A HIGH STRENGTH STEEL
ALLOY CORE WITH MOLTEN WELDED
COPPER COVERING EARTH
ELECTRODES.

TYPICAL DOWN CONDUCTOR TO EARTH


2/9/2022 9:36:02 AM

A ELECTRODE CONNECTION DETAIL TYPICAL TW EARTH PIT DETAIL SHEET ID


A1 NO SCALE A5 NO SCALE
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SE511
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES:


USE ONLY TOP 1. REFER TO SHEET SG003 FOR STANDARD ABBREVIATIONS.
EXOTHERMIC WELD FOR 1 2. REFER TO SHEET SE001 & SE002 FOR ELECTRICAL LEGEND SYMBOLOGY.
HORIZONTAL CONDUCTOR, 3. REFER TO SHEET SE003 FOR ELECTRICAL GENERAL NOTES. US Army Corps of
THRU OR OR END OF RUN 4. REFER TO SHEET SE620 FOR MASTER LUMINAIRE SCHEDULE. Engineers ®
70mm2 BARE COPPER
5. REFER TO SHEETS STARTING AT SE520 FOR LUMINAIRE PLATES.
CONDUCTOR PERIMETER Middle East District
6. REFER TO SHEETS STARTING AT SE501 FOR TYPICAL EARTHING DETAILS.
G GROUND LOOP CONDUCTOR
7. REFER TO SHEET SE601 FOR TYPICAL EARTHING DETAILS.
A5
SE512

DATE
USE TOP AND SIDE EXOTHERMIC
WELDS FOR 2 HORIZONTAL
CONDUCTORS, THRU OR END OF RUN

6m x 19mm DIA. GROUND ROD, STEEL CORE


COPPER JACKETED TYPE, COMPRISING A HIGH
STRENGTH STEEL ALLOY CORE WITH MOLTEN
WELDED COPPER COVERING EARTH ELECTRODES.

TOP OF AIR TERMINAL SUPPORT

GROUND LOOP TO ROD CONNECTION PIPE SHALL BE PROVIDED AT


ELEVATION INDICATED ON

DESCRIPTION
F PLANS. AIR TERMINAL EXTENDS
EXOTHERMIC PROCESS AT TSPB, TCPL, & ABOVE MAST AS NOTED.
REFER TO
RPRE STRUCTURAL
F2 SCALE: NTS
DRAWINGS FOR
SUPPORT DETAILS

PVC-SHEATHED 3 x 25 mm (MINIMUM)
A5 TINNED COPPER TAPE TO LIGHTNING
PROTECTION SYSTEM
SE512

MARK
E

PLOT SCALE: PLOT DATE:


2/9/2022 9:36:03
SOLICITATION NO.:

SA-480530-1$-SE512DT.dwg
AM
CONTRACT NO.:
AIR TERMINAL SUPPORT PIPE DETAIL

ISSUE DATE:
E5

1:1
NO SCALE

TOP OF LIGHTNING PROTECTION MAST

FILE NO.:
SHALL BE PROVIDED AT ELEVATION

SUBMITTED BY:
INDICATED ON PLANS. AIR TERMINAL

C. BRISKORN
EXTENDS ABOVE MAST AS NOTED.

DESIGN BY:

DRAWN BY:
C. PERILLA

A. HANKS
D

CKD BY:
L. KING

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
600 AIR TERMINAL

300
GROUND BOLT

C U-BOLT AIR TERMINAL


GRADE SUPPORT
100

TO GROUND RING OR GROUNDING


SYSTEM. SEE EARTHING PLANS FOR

EARTHING AND LIGHTNING PROTECTION DETAILS


LAYOUT

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


VERTICAL BASE
CONNECTOR

THAAD STANDARD FACILITIES


VARIOUS LOCATIONS, KSA
ANCHOR RODS BY POLE MANUFACTURER
(4 MINIMUM). MANUFACTURER TO

STANDARD DETAILS
305 OF 50 mm2
PROVIDE TEMPLATE FOR ANCHOR RODS.
GROUND CONDUCTOR

SA-480530
70mm2 BARE COPPER
B

EXOTHERMIC BOND

FOUNDATION, SEE DETAILS A6 AND A8 ON


SHEET SS511 IN SFDN PACKAGE.

TYPICAL LIGHTNING PROTECTION MAST-


ENLARGED DETAIL
2/9/2022 9:36:03 AM

TYPICAL LIGHTNING PROTECTION MAST A5


A A2 NO SCALE
NO SCALE
SHEET ID
$
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS ARE IN MILLIMETERS
SE512
1 2 3 4 5 6 7 8 9 10

GENERAL SHEET NOTES


1. REFER TO SHEETS SE001, SE002, AND SE003 FOR ELECTRICAL SYMBOLS
LEGEND AND ELECTRICAL GENERAL NOTES.
US Army Corps of
2. REFER TO SHEET SG003 FOR STANDARD ABBREVIATIONS AND REFER TO SHEET Engineers ®
SG004 FOR STANDARD PROJECT SYMBOLOGY.
Middle East District
G

DATE
NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY
MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY
MANUFACTURER OR PREFERENCE. MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN
MANUFACTURER OR PREFERENCE. MANUFACTURER OR PREFERENCE.

LUMINAIRE REQUIREMENTS: LUMINAIRE REQUIREMENTS: LUMINAIRE REQUIREMENTS:

DESCRIPTION
1. HOUSING - HEAVY GAUGE COLD ROLLED STEEL OR DIE CAST ALUMINUM. SIZE SHOWN 1. HOUSING - DIE-FORMED, COLD ROLLED STEEL. SIZE AS INDICATED IN LUMINAIRE 1. HOUSING - DIE-FORMED, COLD ROLLED STEEL, WITH REINFORCEMENT RIBS FOR
F AS INDICATED IN LUMINAIRE SCHEDULE. SCHEDULE. RIGIDITY; ENDCAPS SAME MATERIAL AS HOUSING, SECURED TABS, SCREWS, OR
RIVETS. SIZE AS INDICATED IN LUMINAIRE SCHEDULE.
2. OPTICS - FROSTED ACRYLIC OR POLYCARBONATE LENS WITH DIE FORMED COLD 2. OPTICS - ACRYLIC OR POLYCARBONATE LENS AS INDICATED IN LUMINAIRE SCHEDULE.
ROLLED SHEET STEEL REFLECTORS. 2. OPTICS - ACRYLIC OR POLYCARBONATE LENS AS INDICATED IN LUMINAIRE SCHEDULE.
3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND
3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND MINIMUM EFFICACY OF 100 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS INDICATED 3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND
MINIMUM EFFICACY OF 100 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS INDICATED IN LUMINAIRE SCHEDULE. MINIMUM EFFICACY OF 110 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS INDICATED
IN LUMINAIRE SCHEDULE. IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DIMMABLE DRIVER WITH OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND < 20% THD. ON/OFF 4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,
MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND CONTROL AND FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS INDICATED IN OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND < 20% THD. ON/OFF
< 20% THD. ON/OFF CONTROL AND FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS LUMINAIRE SCHEDULE. CONTROL AND FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS INDICATED IN
INDICATED IN LUMINAIRE SCHEDULE. LUMINAIRE SCHEDULE.
5. CERTIFICATION - UL LISTED FOR DRY OR DAMP LOCATION, ROHS COMPLIANT, DLC
5. CERTIFICATION - UL LISTED FOR DRY OR DAMP LOCATION, ROHS COMPLIANT. DLC QUALIFIED. COMPLIES WITH IES LM79, LM80 AND TM21 TESTING STANDARDS. 5. CERTIFICATION - UL LISTED FOR DRY OR DAMP LOCATION, ROHS COMPLIANT, DLC
QUALIFIED. COMPLIES WITH IES LM79, LM80 AND TM21 TESTING STANDARDS. QUALIFIED. COMPLIES WITH IES LM79, LM80 AND TM21 TESTING STANDARDS.
6. MOUNTING - RECESSED IN HARD OR ACOUSTICAL TILE CEILING.

MARK
6. MOUNTING - RECESSED IN HARD OR ACOUSTICAL TILE CEILING. 6. MOUNTING - SURFACE MOUNTED.
7. OPTIONS - EDGE-LIT LENS, PRISMATIC LENS. EMERGENCY BATTERY BACK-UP,
E 7. OPTIONS - EMERGENCY BATTERY BACK-UP, INTEGRAL OCCUPANCY/VACANCY
SENSOR, VARIOUS SIZE AND OUTPUT OPTIONS, SURFACE-MOUNTING KIT.
INTEGRAL OCCUPANCY/VACANCY SENSOR, VARIOUS SIZE AND OUTPUT OPTIONS, 7. OPTIONS - EMERGENCY BATTERY BACK-UP, INTEGRAL OCCUPANCY/VACANCY
SURFACE-MOUNTING KIT. SENSOR, VARIOUS SIZE AND OUTPUT OPTIONS.

PLOT SCALE: PLOT DATE:


2/9/2022 9:36:04
SOLICITATION NO.:

SA-480530-1$-SE520DT.dwg
AM
CONTRACT NO.:
ISSUE DATE:

1:1
DIRECT/INDIRECT LED LUMINAIRE FLAT LENS LED LUMINAIRE SURFACE LED WRAPAROUND
REVISED: NOVEMBER 2020 LIGHTING PLATE: NL-1 REVISED: NOVEMBER 2020 LIGHTING PLATE: NL-2 REVISED: NOVEMBER 2020 LIGHTING PLATE: NL-3

FILE NO.:
SUBMITTED BY:
A. TRIBBETT
DESIGN BY:

DRAWN BY:
S. HOLDEN

A. HANKS
D

CKD BY:
L. KING

ANSI D
SIZE:
TRANSATLANTIC MIDDLE EAST DISTRICT
US ARMY CORPS OF ENGINEERS

201 PRINCE FREDERICK DRIVE,


WINCHESTER, VA 22602
NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY
MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN NOTE: THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY
C MANUFACTURER OR PREFERENCE. MANUFACTURER OR PREFERENCE. MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN
MANUFACTURER OR PREFERENCE.

LUMINAIRE REQUIREMENTS: LUMINAIRE REQUIREMENTS: LUMINAIRE REQUIREMENTS:


1. HOUSING - HEAVY GAUGE COLD ROLLED STEEL, EXTRUDED ALUMINUM, OR DIE CAST 1. HOUSING - COLD ROLLED OR SPUN STEEL, DIE CAST ALUMINUM, OR BRASS BODY. 1. HOUSING - DIE CAST ALUMINUM FRAME AND HEAT SINK WITH ENAMELED FINISH. SIZE
ALUMINUM BODY. SIZE AS INDICATED IN LUMINAIRE SCHEDULE. SIZE AS INDICATED IN LUMINAIRE SCHEDULE. AS INDICATED IN LUMINAIRE SCHEDULE.

2. OPTICS - FROSTED ACRYLIC OR POLYCARBONATE LENS. LAMBERTIAN, NARROW, 2. OPTICS - FROSTED ACRYLIC OR POLYCARBONATE LENS AS INDICATED IN LUMINAIRE 2. OPTICS - ACRYLIC OR POLYCARBONATE REFRACTIVE LENS. EDGE-LIT, LAMBERTIAN,
WIDE, OR ASYMMETRIC LIGHT DISTRIBUTION AS INDICATED IN LUMINAIRE SCHEDULE. SCHEDULE. NARROW, WIDE, OR ASYMMETRIC LIGHT DISTRIBUTION AS INDICATED IN LUMINAIRE
SCHEDULE.

ROYAL SAUDI AIR DEFENSE FORCES (RSADF)


3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND 3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND
MINIMUM EFFICACY OF 90 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS INDICATED MINIMUM EFFICACY OF 70 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS INDICATED 3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND
IN LUMINAIRE SCHEDULE. IN LUMINAIRE SCHEDULE. MINIMUM EFFICACY OF 75 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS INDICATED

THAAD STANDARD FACILITIES


IN LUMINAIRE SCHEDULE.

VARIOUS LOCATIONS, KSA


4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF, 4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,

STANDARD DETAILS
OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND < 20% THD. ON-OFF OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND < 20% THD. ON/OFF 4. DRIVER - REPLACEABLE, HIGH-EFFICIENCY DIMMABLE DRIVER WITH MINIMUM 0.9 PF,

LIGHTING DETAILS
CONTROL AND FULLY