TI 267F/00/en
Electronic Insert EC 61 Z
Operating Instructions
017180-1000
Transmitter for capacitance probes

Application
The electronic insert EC 61 Z is a
transmitter for capacitance limit
detection in conjunction with the limit
switch Nivotester FTC 325 3-WIRE or
FTC 420, 421, 422.

Features and Benefits


• Applicable over a wide temperature
range
• Also applicable if conductive deposit
on probe.

Measuring System
A typical measuring system comprises:
• the Nivotester FTC 325 3-WIRE or
FTC 420, 421, 422
• the EC 61 Z electronic insert
• a probe, suitable for the medium to be
measured.

Endress + Hauser
The Power of Know How
• Connect the EC 61 and Nivotester
Electrical Connection by a 3-wire installation cable, line 1. Provide earth connection
resistance max. 25 Ω/core.
• If the cable is laid through strong
electromagnetic fields, then shielded
cable, preferably with twisted cores,
must be used. Ground the shielding
at one end only.
• Ground the probe to terminal 6 of the
electronic insert. Identification colour: orange

+15 V
– 2. Fit electronic insert
Signal 3...12 V and screw in

Nivotester
12 11 13 FTC325
10 9 8 FTC420/421/422
+ – S
Bridge 1-2 1 2 3 4 5 6
for conductive EC61Z
deposit on probe
left: (FTC420/421) or
two-point control
Connection to (FTC325 3-WIRE
Nivotester FTC… FTC422)

right:
Connection to
probe head

Technical Data Housing plastic, potted electronics


Protection type to DIN 40050 electronics IP 55, terminals IP 00
Identification orange
Weight 180 g
Permissible ambient temperature –20 °C…+100 °C
Measuring frequency approx. 500 kHz
Power supply 15 V ± 0.9 V from Nivotester FTC…
Output signal voltage 3 V…12 V, equivalent to 10…350 pF
Electromagnetic compatibility interference emission to EN 61326, electrical equipment class B
interference immunity to EN 61326

Supplementary ❏ Nivotester FTC 325 3-WIRE ❏ Nivotester FTC 420


Technical Information TI 380F/00/en Quick Installation Guide
Documentation BA 043F/00/a3
❏ Nivotester FTC 420/421/422
Technical Information TI 127F/00/en ❏ Nivotester FTC 422
Operating Instructions BA 029F/00/a2
❏ Nivotester FTC 420/421
Operating Instructions BA 021F/00/a2

Endress+Hauser
GmbH+Co. KG
Instruments
International
P.O. Box 2222
D-79574 Weil am Rhein
Germany
Tel. (0 76 21) 9 75-02
Fax (0 76 21) 9 75-3 45
http://www.endress.com
info@ii.endress.com

Endress + Hauser
The Power of Know How

05.02/PT1

TI 267F/00/en/03.04
017180-1000
SL/CV5 017180- 1000

You might also like