Features
• Addressable
• Max. 3-second response time
• The call-point comprises a built-in indicator (LED)
• Can be tested by means of a special test-key
• With the SelfVerify-functions
• Short-circuit isolator in each call-point
• Automatic addressing
• Proven technology
• Intended for connection to Autronica’s interactive
alarm system, AutroSafe
• Designed to meet the requirement of the major
maritime classification societies
Applications
BF-300 is a manual call-point for indoor use.
The call-point is designed for use with Autronica’s
interactive fire alarm system, AutroSafe, and com-
prises the SelfVerify function. This function en-
sures the highest grade of reliability and the lowest Versions
degree of manual testing because all units compris-
ing this function are automatically self-tested once • BF-300 Manual call-point with SelfVerify
every 24 hours. • BF-300M* Manual call-point with SelfVerify,
with metal mounting box and cable
Optionally there is a BF-300M version, which is de- glands
livered with a metal box fitted with two cable glands. • BF-500/EX* Manual call-point with SelfVerify.
This version is made for applications where a higher EExia-version for use in all zones
degree of weather protection is required. • BF-300M/N* Manual call-point with SelfVerify.
Eexn-version for use in zone 2 only
There are also manual call-points for use in hazard- • BF-500/N Manual call-point with SelfVerify.
ous area zone 2. The BF-300M/N has a metal Eexn-version for use in zone 2 only
mounting box with two cable glands.
* See separate data sheet
The BF-500/N has a standard plastic mounting box.
They must be connected to the BSD-310/N loop Technical Specifications
driver, but do not require an isolator/barrier unit.
Weight 108 g
The call-point must be installed according to local Material Thermo plastic
regulations, which normally means along escape Colour Red
routes, landings and exits. Voltage 10 - 27V DC
Current consumption
Principle Stand by: 0,3mA
Break glass operation, releasing alarm switch. Alarm (LED): 6mA
Reset when a new glass is mounted. Environm. requirement EN-54
Degree of protection IP 24D
“SelfVerify”, the call-point’s ability to initiate Working temperature - 30 to + 50°C
alarms is regularly checked. Storage temperature - 55 to + 70°C
Humidity (non-condensing) Max. 95% RH
Maintenance Replace broken glass
Service Replace if faulty
Approvals See separate documentation
Cable wire Maximum 2,5 mm2
Certificate for BF-500/N NEMKO 03ATEX217X
1. Pos (+) in
2. Pos (+) out
3. Neg (-) in
4. Neg (-) out
5. Internal connection
6. Internal connection
Dimensions
Fig. 1 Fig. 1
Cable knock-outs
60
Ø10mm
Fig. 2
Fig. 3