AutroFlame Multispectrum Flame Detector X33AF PL

Features & Benefits


• Single detector for multiple fuels. Certified for 5
different hydrocarbon fires.
• Interfaces to PowerLoop.
• Lowest cost of coverage in the industry, extended
detection range, new standard set for cone-of-
vision.
• Best combination of flame detection and false
alarm rejection.
• Reliable flame detection with modulated infrared
background present.
• SelfVerify Function for automatic testing of the
detector.
• Calibrated automatic optical check for each sensor
eliminates need for testing with external test lamp.
• Integral wiring compartment provides
explosion/flame proof or increased safety (Eexd e)
installation in hazardous areas.
• Heated optics, enable optimal performance in
adverse environments (microprocessor controlled).
• Low maintenance cost.
• Designed in compliance with the latest approval
directives FM3260:2000, CSA, ATEX, CE and
DNV. The detector has a detection range to gasoline of
over 60m, and a solid cone of vision for methane.

The detector is suitable for applications that are at


Application / Description the extremes, and where background infrared
The AutroFlame Multispectrum Flame Detector radiation is a normal condition (Offshore
X33AF PL utilizes advanced signal processing production platforms, Offshore production ships,
algorithms, supported by an embedded 32-bit Refineries, Production facilities, Loading racks,
microprocessor, to provide continuous protection in Compressor stations, Turbine enclosures).
the presence of false alarm sources and
environments with infrared radiation present.

The detector has built-in PowerLoop technology


which makes the detector capable of being powered
and communicating with AutroSafe Integrated Fire
and Gas panels (IFG) on the same pair of wire,
saving cable cost and weight. Each detector has a
built-in short-circuit isolator, hence no detectors will
be lost because of a single break or short-circuit in the
PowerLoop lines.

All alarms and faults will be signaled via PowerLoop.

The PowerLoop is a two-wire power and signaling bus


connected in ring topology and is galvanic isolated
from the rest of the system.

The detector does not require any local power supply.

116-P-X33AF/PL/CE, Rev. A, 2006-02-06 Protecting life, environment and property...


AutroFlame X33AF PL

Technical Specifications Response Distance


Shipping Weight (g) Stainless steel: 5600g Fuel Size Distance Average
F1 (m) Response
Enclosure Material 316 stainless steel Time
(sec)
Power Consumption 11,3 W maximum during operating
conditions 2
n-Heptane 1 x 1 foot (0.1m ) 210 (64)* 11.1
2
Temperature Range Operating: -40C to +75C n-Heptane 1 x 1 foot (0.1m ) 100 (30) 3.0
2
Diesel ** 1 x 1 foot (0.1m ) 150 (45)* 13.1
Storage: -55 to + 85C 2
Methanol 1 x 1 foot (0.1m ) 150 (45)* 17.6
Humidity: 0-95% Methane 30 inch plume(0.9m) 100 (30) 2.0
2
JP-5 ** 2 x 2 foot (0.4 m ) 210 (64)* 3.3
Conduit Entry Size 4 x 25mm JP-5 **
2
2 x 2 foot (0.4 m ) 100 (30) 1.6
Mounting Swivel
Certification DNV Maritime approval n-Heptane 1 x 1 foot (0.1m )
2
100 (30) 11.3
2
Environmental: Ingress Protection to IP66/ n-Heptane 1 x 1 foot (0.1m ) 50 (15,2) 1.9
2
NEMA Type 4X Diesel ** 1 x 1 foot (0.1m ) 70 (21) 3.8
2
Methanol 1 x 1 foot (0.1m ) 70 (21) 9.4
EMC Directive: CE Certified Methane 30 inch plume(0.9m) 65 (20) 2.5
FM/CSA or FMA/CSA: Methane 30 inch plume(0.9m) 55 (17) 2.1
2
Class I, Div. 1, Groups B, C & D; JP-5 ** 2 x 2 foot (0.4 m ) 100 (30) 2.3
Class II, Div. 1, Groups E, F, & G;
Class III (T3C).
Class I, Div. 2, Groups A, B, C & D; * Outdoor test condition
Class II, Div. 2, Groups F & G; ** 10 sec. Pre-burn, norm. ignition.
Class III (T3C).
CENELEC:
Standard Temperature Model Cone of Vision
EEx d IIC T6, EEx d e IIC T6 Indicated Distance in Feet for Methane Indicated Distance in Feet for Gasoline
(T amb = –40°C to +60°C).
EEx d IIC T5, EEx d e IIC T5
(T amb = –40°C to +75°C).
Extended Temperature Model
EEx d IIC T6, EEx d e IIC T6
(T amb = –55°C to +60°C).
EEx d IIC T5, EEx d e IIC T5
(T amb = –55°C to +75°C).
EEx d IIC T4, EEx d e IIC T4
(T amb = –55°C to +125°C).

Termination
The X33AF PL has fixed wiring. The terminals can
use up to 2,0m2 cables. Note that shielded cables
must be used.

Terminal no. Signal


1 PowerLoop + IN
3 PowerLoop - IN Dimensions
18 PowerLoop + OUT
15 PowerLoop - OUT

Part number Description


116-5861-011.4410 AutroFlame X33AF Stainless Steel PL

AUTRONICA FIRE AND SECURITY AS


Fire and Security, Trondheim, Norway Phone: +47 73 58 25 00, Fax: 73 58 25 01, e-mail: info@autronicafire.no
Oil and Gas, Stavanger, Norway Phone: +47 51 84 09 00, Fax: +47 51 84 09 99
Maritime division, Spikkestad, Norway Phone: +47 31 29 55 00, Fax: +47 31 29 55 01

Visit Autronica Fire and Security AS’ website : www.autronicafire.com

You might also like