You are on page 1of 76

FORM 150.

70-EG1 (699)

MILLENNIUM TM

Air Cooled Reciprocating


Liquid Chillers

26810A

IED TO ARI
T IF AS
ER
C SCR
C

Y
TAR
ER

OM

EW
RO W
NUFACTUR

PLY
AN

AT
E
CENTRIFUGAL

RC

ING WITH
H IL L I N G
MA

®
• PAC K AG ES •
F

ER
C

O
A T S
R I IFICATION SECTION 9 0
S TA 5
NDARD

50 - 200 TONS YCAZ & YCAJ


50 TO 230 TONS
(176 TO 810 KW)
60 HZ

m See page 4
for U.L. and C.U.L
Metric Conversions approved models.
TABLE OF CONTENTS
Introduction ..................................................................................................... 3
Specifications .................................................................................................... 4
Accessories and Options ................................................................................... 8
Design Parameters ............................................................................................ 10
Water Pressure Drops ....................................................................................... 12
Selection Data ................................................................................................... 16
Rating Data ..................................................................................................... 18
Optional Remote DX Cooler ............................................................................... 38
Physical Data ..................................................................................................... 42
Dimensions ..................................................................................................... 45
Electrical Data ................................................................................................... 62
Sound Power ..................................................................................................... 72
Application Data ................................................................................................ 73
Guide Specifications .......................................................................................... 74

TYPICAL NOMENCLATURE
The model number denotes the following characteristics of the unit:

YC A Z 7 4 B B 3 — 46 P A

Chiller: Design Level


YC = YORK Chiller
Type Start
P = Part Wind
Air Cooled X = Across-the-Line

Compressor Type
Z – Reciprocating Voltage Code:
17 = 200-3-60
Unit Model 28 = 230-3-60
46 = 460-3-60
58 = 575-3-60

YC A J 110 — 46 P A

Chiller: Design Level


YC = YORK Chiller
Type Start
P = Part Wind
Air Cooled

Compressor Type
J – Reciprocating Voltage Code:
17 = 200-3-60
Unit Model 28 = 230-3-60
40 = 380-3-60
46 = 460-3-60
58 = 575-3-60

2 YORK INTERNATIONAL
FORM 150.70-EG1

Introduction
YORK MillenniumTM Air Cooled Liquid Chillers
50 - 230 TONS (176 - 810 kW)

26810A

IED TO ARI
T IF AS
ER
C SCR
C

Y
TAR
ER

OM

EW
RO W
NUFACTUR

PLY
AN

AT
E
CENTRIFUGAL

RC

ING WITH
H IL L I N G
MA

®
• PAC K AG ES •
F

ER
C

O
A T S
R I IFICATION SECTION 9 0
S TA 5
NDARD

YORK Millennium Air Cooled Reciprocating Liquid Chillers provide


chilled water for all air conditioning applications using central station
air handling or terminal units. They are completely self-contained and
are designed for outdoor (roof or ground level) installation. Each unit
includes accessible hermetic compressors, a liquid cooler, air cooled
condenser, and a weather resistant microprocessor control center, all
mounted on a formed steel base. 200, 230, 380 (YCAJ models only),
460, and 575-3-60 models are U.L. and C.U.L. listed. Chillers from
50 - 200 tons are rated and certified in accordance with ARI Stan-
dard 590-92.

YORK INTERNATIONAL 3
Specifications

GENERAL Cylinder Assemblies – Suction and discharge valves


are high-quality, non-flexing, stainless steel. The pistons
The 50 - 230 Ton (176 - 810 kW) Millennium Air Cooled are aluminum alloy with two piston rings. The connect-
Reciprocating Liquid Chiller is completely assembled with ing rods are aluminum alloy with integral bearing sur-
all interconnecting refrigerant piping and internal wiring, faces on both ends. Cylinder liners are removable.
ready for field installation.
Lubrication – The lubrication is force-fed by a revers-
The unit is pressure-tested, evacuated and fully charged ible oil pump to all crankshaft and bearing surfaces
with Refrigerant-22, and includes an initial oil charge. through a fine mesh stainless steel oil strainer. A mag-
After assembly, an operational test is performed with netic plug is included in the oil stream.
water flowing through the cooler to check that each re-
frigeration circuit operates correctly. Capacity Control – Capacity control is provided by so-
lenoid actuated, capacity-control valves, which are op-
The unit structure is heavy-gauge, galvanized steel, cov- erated by the microprocessor control center.
ered with a baked-on enamel meeting ASTM B117, 500
hour, 5% salt spray requirements. Base rails are of The electrical solenoid unloading coils are energized to
formed, double-thickness painted plate steel. Units are route high pressure fluid to the compressor blocked suc-
designed in accordance with NFPA 70 (National Electri- tion unloading devices to stop the flow of gas to the cyl-
cal Code), ASHRAE/ANSI 15 Safety Code for Mechani- inders. This method efficiently and effectively matches
cal Refrigeration and ASME. 200, 230, 380 (YCAJ mod- the low load conditions as required. Gas flow is suffi-
els only), 460, and 575-3-60 models are U.L. and C.U.L cient at all times to cool motor.
listed. All units are produced at an ISO-9000 registered
facility. Chillers from 50 - 200 tons are rated and cer- Isolation – Each compressor is mounted on isolator
tified in accordance with ARI Standard 590-92. pads to reduce transmission of vibration to the rest of the
unit.

COMPRESSORS
COOLER
The chiller has accessible, hermetic, reciprocating
compressors. All rotating parts are statically and dynami- The dual-circuit cooler is the direct-expansion type, with
cally balanced. refrigerant in the tubes and chilled liquid flowing through
the baffled shell. The design working pressure of the shell
Motor – The compressor motors are refrigerant gas is 150 PSIG (10.5 Kg/cm2) , and 235 PSIG (16.5 Kg/
cooled, with integral temperature-sensing, solid-state cm2) for the tube side. The refrigerant side is constructed
overload protection in each phase. The terminal boxes and tested in accordance with the applicable sections of
are raintight. Starting is by either part-winding or across- the ASME Pressure Vessel Code, Section VIII, Division
the-line for 50 - 90 ton (176 - 317 kW) models and (1). The water side is exempt per paragraph U-1, (c) (6).
part-winding for 95 - 230 ton (334 - 810 kW) models.
The water baffles are constructed of galvanized steel to
Housing – The compressor housing is cast iron, and resist corrosion. The removable heads allow access to
contains: removable cylinder heads with internal muf- the internally enhanced, seamless, copper tubes. Vent
fling; suction and discharge service valves; crankcase and drain connections are included.
sight glass and heater; oil and suction strainers; and in-
ternal relief valving conforming to ASHRAE/ANSI Stan- The cooler is equipped with a thermostatically controlled
dard 15 safety code. heater. The heater provides freeze protection for the cooler
down to -20°F (-29°C) ambient. The cooler is covered with
Crankshaft – The crankshaft is ductile (nodular) iron, 3/4" (19.1 mm) flexible, closed-cell, foam insulation (K =
drilled for positive oil distribution, with integral counter- 0.25).
weights for balancing. The main bearings are of the in-
sert type, steel-backed Babbitt. The thrust bearing is
bronze.

4 YORK INTERNATIONAL
FORM 150.70-EG1

CONDENSER Motors – The fan motors are Totally Enclosed Air-Over,


squirrel-cage type, current protected with class “F” insu-
Coils – The condenser coils are seamless copper tubes lation. They feature ball bearings that are double-sealed
arranged in staggered rows, mechanically expanded into and permanently lubricated.
aluminum fins. Integral subcooling is included. The de-
sign working pressure of the coil is 450 PSIG (31.5 Kg/
cm2). REFRIGERANT CIRCUIT
Independent refrigerant circuits will be furnished on each
Fans – The condenser fans are cast aluminum or glass
unit. All unit piping is copper, with brazed joints. The liq-
reinforced-polypropylene, high-efficiency, airfoil-type fan
uid line includes: a shutoff valve with charging port; sight
blades directly driven by independent motors, and posi-
glass with moisture-indicator; thermal expansion valve;
tioned for vertical air discharge. The fan guards are con-
solenoid valve; and filter drier. The entire suction line,
structed of heavy-gauge, rust-resistant, PVC coated steel
and the liquid line between the expansion valve and the
(50 – 90 ton [176 - 316 kW] models have zinc dichromate
cooler, is insulated with flexible, closed-cell foam insula-
coating with lacquer overcoat). All blades are dynamically
tion.
and statically balanced for vibration-free operation.

YORK INTERNATIONAL 5
MILLENNIUM MICROPROCESSOR CONTROL CENTER

All controls are contained in a NEMA 3R/12 (and equiva- Low suction pressure cutout
lent to IP55*) cabinet with hinged outer door and includes: High discharge pressure cutout
Anti-recycle timer (compressor start cycle time)
Liquid Crystal Display with Light Emitting Diode back- Anti-coincident timer (delay compressor starts)
lighting for outdoor viewing:
UNIT ON/OFF switch
Two display lines
Twenty characters per line The microprocessor control center is capable of display-
ing the following:

Color coded 32-button non-tactile key pad with sections for: • Return and leaving liquid temperature
• Low leaving liquid temperature cutout setting
DISPLAY of typical information:
• Low ambient temperature cutout setting
Chilled liquid temperatures
Ambient temperature • Outdoor air temperature
System pressures (each circuit) • English or Metric data
Percent motor currents (each circuit)
• Suction pressure cutout setting
Operating hours and starts (each circuit)
Options listing • Oil temp sensing (YCAJ Models)
• Current limiting (YCAJ Models)
ENTRY section to: • Each system suction pressure, discharge pressure
ENTER setpoint changes (optional), oil pressure and percent full-load motor cur-
CANCEL inputs rent
ADVANCE DAY • Liquid control range (2.0 - 20°F above the setpoint)
Change AM/PM • Liquid pulldown rate sensitivity adjustment
(0.5 - 5°F [0.3 - 2.8°C]/minute in 0.1° increments)
SETPOINTS updating can be performed to:
• Liquid Temperature Reset via a YORK ISN DDC or
Chilled liquid temperature range Building Automation System (by others) via:
Remote reset temperature range – a pulse width modulated (PWM) input as standard
– a 4-20 milliamp or 0-10 VDC input with the optional
CLOCK changes for: B.A.S. interface option
Set time • Anti-recycle timer status for each compressor
Set daily schedule/holiday for start/stop
• Anti-coincident compressor start timer condition
Manual override for servicing
• Compressor run status
PRINT calls up: • No cooling load condition
Operating data for the systems • Day, date and time
History of fault shutdown data for last three faults
• Out of range message
An RS-232 port, in conjunction with this press-to- • Daily start/stop times
print button, is provided to permit the capability • Holiday status
of hard copy print-outs via a separate printer
• Automatic or manual lead/lag control
(by others).
• Lead compressor definition
PROGRAM other functions such as: • Compressor starts & operating hours (each system)
Low and high ambient cutouts • Status of hot gas valves, evaporator heater and fan
Unloading steps operation
Low liquid temperature cutout • Up to 3 fault shut down conditions

6 YORK INTERNATIONAL
FORM 150.70-EG1

• Run permissive status POWER PANEL


• Number of unloading steps
Each panel contains:
• Liquid solenoid valve status
• Load & unload timers status • Compressor power terminals
• Water pump status (optional) • Compressor motor starting contactors per l.E.C.**
• Current transformer sensing on each compressor
Provisions are included for: pumpdown at shutdown and power source
recycling pumpdown; optional remote chilled water-tem- • Control power terminal strip for 115-1-60 with fuse
perature reset and two steps of demand load limiting protection
from an external building automation system; and high
• Fan contactors & overload current protection
motor current protection and demand limiting at startup
with compressor unloading. Unit alarm contacts are stan- • 15 amp, 115 volt convenience outlet with ground fault
dard. interruption protection (YCAJ Models)

The operating program is stored in non-volatile memory The power wiring is routed through liquid-tight (YCAJ
(EPROM) to eliminate chiller failure due to AC powered models) conduit to the compressors and fans.
failure/battery discharge. Programmed setpoints are re-
tained in lithium battery-backed RTC memory for 5 years The current transformer sensing, in conjunction with the
minimum. control panel, protects the compressor motors from dam-
age due to low input current, high input, imbalanced cur-
rent single phasing, input power spikes, and compres-
sor stall. See ELECTRICAL DATA for type starting.

* Intensity of Protection European Standard


** International Electrotechnical Commission

YORK INTERNATIONAL 7
Accessories and Options
AMBIENT KIT (LOW) ers in the power wiring which must comply with the Na-
tional Electric Code and/or Local Codes. This includes
Standard units will operate to 25°F (-3.9°C). This acces- the Single Point Power connection.
sory includes all necessary components to permit chiller
operation to 0°F (-17.8°C) and includes discharge pres- Single Service Disconnect Switch
sure readout capability. (Factory mounted.) (With Fusing) (YCAJ Models)

AMBIENT KIT (HIGH) A unit mounted disconnect switch with separate internal
fusing and an external lockable handle (in compliance
Required if units are to operate when the ambient tem- with N.E.C Article 440-14), can be supplied to isolate
perature is above 115°F (46.1°C). Includes factory the power voltage for servicing. This includes the single
mounted discharge pressure transducers and sun shield point power connection.
panels (50 - 90 ton [176 - 317 kW] units are factory
mounted; 95 - 230 ton [334 - 810] units are shipped loose. Single Point Supply with
See page 7 for unit location.) Separate System Circuit Breakers (YCAJ Models)

BUILDING AUTOMATION SYSTEM INTERFACE Each system contains a lockable circuit breaker with ex-
ternal handle in compliance with N.E.C. Article 440-14
A printed circuit board is added to accept a 4-20 milliamp to isolate the system for servicing. Separate external fus-
or 0-10VDC input to reset the leaving chiller liquid tem- ing must be supplied by others in the incoming power
perature from a Building Automation System (the stan- wiring.
dard unit capabilities include remote water temperature
reset via a PWM input signal, remote start-stop and two CONTROL TRANSFORMER
steps of demand limiting.)
Converts unit power voltage to 115-1-60 (2KVA capac-
(The standard control panel can be directly connected ity). This is available for all voltages. Factory mounting
to a YORK Building Automated System via the standard includes primary and secondary wiring between the
on board RS485 communication port.) (Factory mounted.) transformer and the control panel. (Factory or field
mounted.)
CHICAGO CODE RELIEF VALVES
CONDENSER COIL PROTECTION
Unit will be provided with relief valves to meet Chicago
code requirements. (Factory mounted.) Condenser protection against corrosive environments
is available for your choosing by supplying the units with
COMPRESSOR POWER CONNECTIONS any one of the following options. (Factory mounted.)

(See Electrical Data pages 62 - 71 for specific voltage Black Fin Condenser Coils – The air-cooled con-
and options availability.) (Factory mounted.) denser coils are constructed of black epoxy coated alu-
minum fins. This can provide corrosion resistance com-
Single Point Power Supply (YCAJ Models) parable to copper fin coils in typical seashore locations.
Either these or the phenolic coated coils (below) are rec-
Includes enclosure, terminal block and interconnecting ommended for any units being installed at the seashore
wiring to the compressors. or where salt spray may hit the unit.

Separate external protection must be supplied by oth- Phenolic Coated Condenser Coils – The unit is built
ers in the incoming compressor power wiring. Do not with cured phenolic coated condenser coils. This is an-
include this if the Single Service Disconnect Switch op- other choice for seashore and other corrosive applica-
tion has been included. tions with the exception of strong alkalies, oxidizers and
wet bromine, chlorine and fluorine in concentrations
Single Service Disconnect Switch greater than 100 ppm.
(Without Fusing)
Copper Fin Condenser Coils – The unit is constructed
A unit mounted disconnect switch with an external lock-
with condenser coils which have copper fins. (This is not
able handle (in compliance with Article 440-14 of N.E.C.),
recommended for units in areas where they may be ex-
can be supplied to isolate the unit power voltage for ser-
posed to acid rain).
vicing. Separate external fusing must be supplied by oth-

8 YORK INTERNATIONAL
FORM 150.70-EG1

Any of the above suitable options should be selected REMOTE COOLER


based on the particular project design parameters and
related environmental factors. The application should be A split-system arrangement with the cooler shipped loose
further reviewed and approved by the consulting engi- for field connection to the air-cooled condensing section
neer or owner based on their knowledge of the jobsite (with holding charge only). Interconnecting rigid piping,
conditions. For additional application recommendations wiring and refrigerant are by others.
refer to Form 150.12-ES1.
SEQUENCING CONTROL
DISCHARGE PRESSURE READOUT
Sequencing Control is provided with automatic unit se-
The addition of pressure transducers allows models to quencing. Necessary items for operation and control of
sense and display discharge pressure. This is recom- up to eight units with parallel water circuits. Includes
mended for brine chilling applications. This is included software for mixed liquid temperature sensor; master unit
with both the low and high ambient kits. (Factory EPROM and secondary unit(s) EPROM(s) (interconnect-
mounted.) ing wiring by others). (Field mounted.)

FLANGES WATER PUMP CONTROL

Consists of 150 lb. (68 Kg) R.F. flanges to convert to A set of contacts is provided to energize a chilled liquid
flanged cooler connections and includes companion pump starter relay (by others). A second set of contacts
flanges. (Field mounted.) is available for activating a remote run status light or
similar device (by other). This is included with the low
FLOW SWITCH (150 PSIG) ambient kit, hot gas bypass or the optional unloading
step options.
Johnson Controls models F61MG-1C Vapor-proof SPDT,
NEMA 4X switch (150 PSIG DWP), 20 - 250°F (-28.9°C UNIT ENCLOSURE
- 121.1°C), with 1" NPT connection for upright mounting
in horizontal pipe. (This flow switch or its equivalent must Wire Panels (Full Unit) Enclosure – Consists of
be furnished with each unit.) (Field mounted.) welded, wire-mesh guards mounted on the exterior of
the unit. Prevents unauthorized access, yet provides free
FLOW SWITCH (300 PSIG) air flow. This can cut installation cost by eliminating the
need for separate, expensive fencing. (Factory or field
McDonnell & Miller model FS7-4W Vapor-proof SPDT, mounted.)
NEMA 4X switch (300 PSIG DWP), -20 - 300°F with 1-1/
4" MPT connection for upright mounting in horizontal Wire/Louvered Panels Enclosure – Consists of
pipe. (This flow switch or its equivalent must be furnished welded-wire-mesh panels on the bottom part of unit and
with each unit.) (Field mounted.) louvered panels on the top part of the unit. (YCAZ88EE8
and YCAJ models) (Factory or field mounted.)
HOT GAS BYPASS
Louvered Panels (Condenser Coil Only) Enclosure –
Permits continuous, stable operation at capacities be- Louvered panels are mounted on the sides and ends of
low the minimum step of compressor unloading to as the condenser coils for protection. (Factory or field
low as 5% capacity (depending on both the unit and mounted.) (YCAJ Models)
operating conditions) by introducing an artificial load on
the cooler. Hot gas bypass is installed on each refriger- Louvered Panels (Full Unit) Enclosure – Louvered
ant circuit. (Factory mounted.) panels surround the front, back, and sides of the unit.
These prevent unauthorized access and visually screen
OPTIONAL UNLOADING STEPS unit components. Unrestricted air flow is permitted
through generously sized louvered openings. (Factory
Units can be modified to provide additional unloading or field mounted.)
steps. See Physical Data Tables. (Factory mounted.)
VIBRATION ISOLATORS
R-134a
Level adjusting, spring type, 1", 2", or seismic deflection
Contact factory for details. for mounting under unit base rails. (Field mounted.)

YORK INTERNATIONAL 9
Design Parameters

TEMPERATURES AND FLOWS


(English)

LEAVING WATER COOLER4 AIR ON


MODEL
TEMP.°F GPM CONDENSER-°F
YCA
MIN.1 MAX. MIN. MAX. MIN.2 MAX.3
Z33BA3 40 50 75 250 0 130
Z44BA3 40 50 75 250 0 130
Z74BA3 40 50 75 250 0 130
Z77CB3 40 50 90 315 0 130
Z88DB3 40 50 130 390 0 130
Z88EE3 40 50 120 430 0 130
J110 40 50 150 640 0 130
J120 40 50 150 640 0 130
J130 40 50 150 640 0 130
J150 40 50 150 640 0 130
J160 40 50 150 640 0 130
J180 40 50 200 722 0 130
J190 40 50 200 722 0 130
J200 40 50 250 803 0 130
J220 40 50 250 803 0 130
J230 40 50 250 803 0 130

NOTES:
1. Units can be used for brine temperatures down to 20°F (-6.7°C) by resetting standard controls. For leaving brine temperatures down to
10°F (-12.2°C) contact the nearest YORK office. Contact your YORK representative for application requirements.
2. Operation below 25°F (-3.9°C) requires the Optional Low Ambient kit.
3. Operation above 115°F (46.1°C) requires Optional High Ambient kit. Contact factory.
4. The evaporator is protected against freeze-up to -20°F (-28.9°C) with an electrical heater as standard.

10 YORK INTERNATIONAL
FORM 150.70-EG1

TEMPERATURES AND FLOWS


(SI)

LEAVING WATER COOLER4 AIR ON


MODEL
TEMP.°C L/sec CONDENSER-°C
YCA
MIN.1 MAX. MIN. MAX. MIN.2 MAX.3
Z33BA3 4.4 10 4.7 15.8 -17.8 54.4
Z44BA3 4.4 10 4.7 15.8 -17.8 54.4
Z74BB3 4.4 10 4.7 15.8 -17.8 54.4
Z77CB3 4.4 10 5.7 19.9 -17.8 54.4
Z88DB3 4.4 10 8.2 24.6 -17.8 54.4
Z88EE3 4.4 10 7.6 27.1 -17.8 54.4
J110 4.4 10 9.5 40.4 -17.8 54.4
J120 4.4 10 9.5 40.4 -17.8 54.4
J130 4.4 10 9.5 40.4 -17.8 54.4
J150 4.4 10 9.5 40.4 -17.8 54.4
J160 4.4 10 9.5 40.4 -17.8 54.4
J180 4.4 10 12.6 45.5 -17.8 54.4
J190 4.4 10 12.6 45.5 -17.8 54.4
J200 4.4 10 15.8 50.7 -17.8 54.4
J220 4.4 10 15.8 50.7 -17.8 54.4
J230 4.4 10 15.8 50.7 -17.8 54.4

VOLTAGE

VOLTAGE CODE UNIT POWER MIN. MAX.


-17 200-3-60 180 220
-28 230-3-60 207 253
-40 380-3-60 342 418
-46 460-3-60 414 506
-58 575-3-60 517 633

YORK INTERNATIONAL 11
Water Pressure Drop (English)

LD01169

CODE MODEL YCA


Z33BA3, Z44BA3,
B
Z74BB3

C Z77CB3

D Z88DB3

E Z88EE8

12 YORK INTERNATIONAL
FORM 150.70-EG1

LD01170

CODE MODEL YCA


J110, J120, J130,
H
J150, J160

K J180, J190

N J200, J220, J230

YORK INTERNATIONAL 13
Water Pressure Drop (SI)

LD01308

CODE MODEL YCA


Z33BA3, Z44BA3,
B
Z74BB3

C Z77CB3

D Z88DB3

E Z88EE8

14 YORK INTERNATIONAL
FORM 150.70-EG1

LD01309

CODE MODEL YCA


J110, J120, J130,
H
J150, J160

K J180, J190

N J200, J220, J230

YORK INTERNATIONAL 15
Selection Data
GUIDE TO SELECTION % WT. FACTORS FREEZE
Capacity ratings for YORK Millennium Air Cooled Recip- ETHYLENE COMPR. POINT
TONS ∆P GPM/°F/TON
rocating Liquid Chillers, shown on pages 18 - 37. Rating GLYCOL KW (°F)
between 50 - 200 tons (176 - 704 kW) are rated and 10 .994 .997 1.03 24.1 26
certified in accordance with ARI Standard 590-92. The 20 .986 .993 1.06 24.9 16
majority of design applications for these units are cov- 30 .979 .990 1.09 25.9 5
ered. For unusual applications or uses beyond the scope 40 .970 .985 1.13 27.3 -10
of this catalog, please consult the nearest YORK office or 50 .959 .980 1.16 29.0 -32
representative.
METHOD OF SELECTION
SELECTION RULES
To select of YORK Packaged Air Cooled Liquid Chiller,
1. Ratings – Ratings may be interpolated, but not ex- the following data must be known:
trapolated. The Ratings given on pages 18 - 37 and
the Design Parameters given on pages 8 - 9 indicate 1. Design Capacity in tons refrigeration (TR).
the limits of application for these chillers.
2. Entering and Leaving Liquid Temperatures.
2. Cooler Water – Ratings are based on 2.4 gpm per
ton which is equal to a 10°F (5.6°C) chilled water range 3. Outside ambient air temperature in degrees F.
and a 0.00025 fouling factor for the cooler at sea level.
Tables on pages 18 - 37 give Capacity, Compressor 4. GPM of chilled liquid.
kW required, Cooler GPM, and Unit EER.
Determine capacity requirements from the following
3. Condenser – Ratings are given in terms of Air on formula:
Condenser in degrees Fahrenheit and Celsius. TR x 24
GPM =
RANGE (°F)
4. Performance Data Correction Factors – Rating are
based on 0.00025 cooler fouling factor, 10°F (5.6°C) EXAMPLE – Water Chilling
chilled water range and at sea level. For operation at
different design conditions, apply the appropriate cor- 1. GIVEN: Provide a capacity of 100 Tons at 42°F
rection factor from the following table. leaving water 10°F range, 0.00025FF, 100°F air on
the condenser, at sea level and 60 Hz.
CHILLED FOULING FACTOR
ALTITUDE WATER .00025 .00075 .00175 2. FIND: Unit Size
∆ T (°F) TONS KW TONS KW TONS KW Compressor kW Input
8 .995 .997 .967 .987 .920 .965 Unit EER
SEA 10 1.000 1.000 .975 .989 .927 .968
LEVEL 12 1.005 1.002 .981 .991 .933 .970
3. From the Ratings on pages 18 - 37.
14 1.010 1.004 .985 .993 .939 .973
SELECT: YCAJ120 (English Units)
8 .985 1.005 .961 .993 .912 .972
104.7 Tons
10 .989 1.007 .965 .995 .917 .975 126.6 Compressor kW
2000 FT.
12 .995 1.009 .971 .999 .925 .977 8.7 Unit EER
14 1.000 1.011 .975 1.001 .930 .981
8 .974 1.012 .949 1.001 .903 .979 4. Calculate Compressor kW at 100 Tons:
10 .979 1.014 .955 1.004 .909 .983
4000 FT. 100.0
12 .984 1.017 .961 1.006 .914 .985 kW = (126.6 kW) = 120.9 kW
14 .988 1.019 .962 1.008 .920 .988
104.7
8 .963 1.020 .939 1.009 .893 .988 5. Calculate GPM:
10 .968 1.022 .945 1.011 .898 .990
6000 FT.
12 .972 1.024 .949 1.013 .904 .993 100 Tons x 24
GPM = = 240 GPM
14 .976 1.025 .955 1.016 .910 .995 10°F Range

5. Ethylene Glycol Correction Factors – The follow- 6. From Page 11, read 6.2 ft of water cooler pressure
ing factors are to be applied to the standard RATINGS drop for GPM:
for units cooling ethylene glycol. (But are not within
7. A YCAJ120 is suitable.
the scope of the ARI 590 Certification Program.)
16 YORK INTERNATIONAL
FORM 150.70-EG1

EXAMPLE – Brine Chilling

1. GIVEN: Provide a capacity of 115 tons cooling 7. Determine average full load Compressor kW at
30% by weight Ethylene Glycol from 50°F to 40°F, 115.0 tons:
0.00075FF, 95°F air on the condenser, 60 Hz and 4000 115.0 tons x (145.6 kW) = 135.3 Compressor kW
ft. altitude. 123.8 tons

2. DETERMINE: Unit Size 8. Determine Ethylene Glycol GPM:


kW Input
Ethylene Glycol GPM GPM = Tons x Gal. °F/min/Ton factor
Cooler Pressure Drop Range

GPM = 115 x 25.9


3. See Ethylene Glycol correction factors, for 30% by 10
weight Ethylene Glycol.
GPM = 297.9
READ: .979 Tons factor
.990 Compr. kW factor 9. Determine Cooler Pressure Drop:
25.9 Gal./°F/Tons factor.
A. See Ethylene Glycol correction factors for 30%
4. See Performance Data Correction Factors for 0.00075 by weight Ethylene Glycol.
fouling factor and 4000 ft. altitude. READ: 1.09 Pressure Drop Factor

READ: .955 Tons factor B. See page 11 at 298 GPM for the YCAJ150.
1.004 kW factor.
READ: 8.4 Ft. H2O Pressure Drop
5. From RATINGS on pages 18 - 37.
C. Cooler Pressure Drop = 8.4 x 1.09 or 9.2 Ft. H2O
SELECT: YCAJ150 (English Units)
132.4 Tons 10. YCAJ150 is suitable.
146.5 Compressor kW

6. Determine YCAJ150 brine cooling capacity and Com-


pressor kW requirement:
A. Tons = 132.4 x .979 x .955 = 123.8
B. Compr. kW = 146.5 x .990 x 1.004 = 145.6

YORK INTERNATIONAL 17
Ratings - 60 Hz (50 - 90 Tons) (English)
MODEL YCAZ33BA3 (IPLV = 10.4)
AIR TEMPERATURE – CONDENSER °F
LCWT
75 80 85 90 95
°F
TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER
40.0 51.7 52.8 124.1 10.7 50.2 54.4 120.5 10.1 48.7 56.0 116.9 9.6 47.2 57.5 113.3 9.1 45.7 58.9 109.8 8.6
42.0 53.6 53.6 128.7 11.0 52.1 55.3 125.1 10.4 50.6 57.0 121.4 9.8 49.1 58.5 117.8 9.3 47.5 60.0 114.1 8.8
44.0 55.6 54.5 133.5 11.2 54.1 56.2 129.8 10.6 52.5 57.9 126.0 10.0 50.9 59.6 122.3 9.5 49.4 61.2 118.5 9.0
45.0 56.6 54.9 135.9 11.4 55.1 56.7 132.2 10.7 53.5 58.4 128.4 10.1 51.9 60.1 124.5 9.6 50.3 61.7 120.7 9.0
46.0 57.7 55.3 138.4 11.5 56.1 57.2 134.6 10.8 54.5 58.9 130.7 10.2 52.9 60.7 126.9 9.7 51.2 62.3 123.0 9.1
48.0 59.7 56.2 143.4 11.7 58.1 58.1 139.4 11.0 56.5 60.0 135.5 10.4 54.8 61.7 131.5 9.9 53.2 63.4 127.6 9.3
50.0 61.8 57.0 148.4 12.0 60.2 59.0 144.4 11.3 58.5 61.0 140.4 10.6 56.8 62.8 136.3 10.0 55.1 64.6 132.3 9.5

MODEL YCAZ44BA3 (IPLV = 9.9)


40.0 56.8 62.7 136.3 10.1 55.1 64.4 132.3 9.5 53.5 66.1 128.4 9.0 51.9 67.7 124.4 8.6 50.2 69.2 120.5 8.1
42.0 58.9 63.8 141.3 10.3 57.2 65.6 137.3 9.7 55.5 67.4 133.2 9.2 53.8 69.1 129.2 8.7 52.1 70.7 125.1 8.3
44.0 61.0 64.9 146.4 10.5 59.3 66.9 142.3 9.9 57.6 68.7 138.2 9.4 55.8 70.5 134.0 8.9 54.1 72.1 129.9 8.4
45.0 62.1 65.5 149.0 10.6 60.4 67.5 144.8 10.0 58.6 69.4 140.7 9.5 56.9 71.2 136.5 9.0 55.1 72.8 132.3 8.5
46.0 63.2 66.1 151.7 10.7 61.4 68.1 147.4 10.1 59.7 70.0 143.2 9.5 57.9 71.9 138.9 9.0 56.1 73.6 134.7 8.6
48.0 65.4 67.3 157.0 10.9 63.6 69.4 152.6 10.3 61.8 71.4 148.3 9.7 60.0 73.3 143.9 9.2 58.2 75.1 139.6 8.7
50.0 67.7 68.5 162.4 11.1 65.8 70.6 158.0 10.4 64.0 72.7 153.5 9.9 62.1 74.7 149.0 9.3 60.2 76.6 144.6 8.9

MODEL YCAZ74BB3 (IPLV = 10.5)


40.0 66.4 68.5 159.4 10.8 64.5 70.5 154.8 10.3 62.6 72.4 150.3 9.7 60.7 74.2 145.7 9.2 58.8 75.8 141.1 8.7
42.0 68.9 69.7 165.3 11.1 66.9 71.8 160.6 10.5 65.0 73.7 155.9 9.9 63.0 75.6 151.2 9.4 61.1 77.4 146.6 8.9
44.0 71.4 70.9 171.3 11.3 69.4 73.1 166.5 10.7 67.4 75.1 161.7 10.1 65.4 77.1 156.9 9.6 63.4 78.9 152.1 9.1
45.0 72.6 71.5 174.3 11.4 70.6 73.7 169.5 10.8 68.6 75.8 164.7 10.2 66.6 77.8 159.8 9.6 64.6 79.7 154.9 9.1
46.0 73.9 72.2 177.4 11.5 71.9 74.4 172.5 10.9 69.8 76.5 167.6 10.3 67.8 78.6 162.7 9.7 65.7 80.5 157.8 9.2
48.0 76.5 73.4 183.7 11.7 74.4 75.7 178.6 11.1 72.3 77.9 173.6 10.5 70.2 80.1 168.6 9.9 68.1 82.1 163.5 9.4
50.0 79.2 74.6 190.0 11.9 77.0 77.1 184.9 11.3 74.9 79.4 179.7 10.7 72.7 81.6 174.6 10.1 70.6 83.7 169.4 9.5

MODEL YCAZ77CB3 (IPLV = 10.8)


40.0 74.0 76.2 177.5 10.9 71.8 78.2 172.4 10.4 69.7 80.1 167.2 9.8 67.5 82.0 162.1 9.3 65.4 83.6 156.9 8.9
42.0 76.7 77.6 184.1 11.1 74.5 79.7 178.8 10.6 72.3 81.8 173.5 10.0 70.1 83.7 168.3 9.5 67.9 85.5 163.0 9.0
44.0 79.5 79.0 190.8 11.4 77.3 81.3 185.4 10.7 75.0 83.4 180.0 10.2 72.7 85.4 174.6 9.7 70.5 87.3 169.2 9.2
45.0 80.9 79.8 194.2 11.5 78.6 82.1 188.7 10.8 76.4 84.2 183.3 10.3 74.1 86.3 177.8 9.7 71.8 88.2 172.3 9.2
46.0 82.4 80.5 197.7 11.6 80.0 82.8 192.1 10.9 77.7 85.1 186.5 10.4 75.4 87.2 181.0 9.8 73.1 89.2 175.4 9.3
48.0 85.3 82.0 204.6 11.8 82.9 84.4 196.9 11.1 80.5 86.8 193.2 10.5 78.1 89.0 187.5 10.0 75.8 91.0 181.8 9.5
50.0 88.2 83.5 211.7 12.0 85.8 86.1 205.9 11.3 83.3 88.5 200.0 10.7 80.9 90.8 194.2 10.1 78.5 93.0 186.3 9.6

MODEL YCAZ88DB3 (IPLV = 10.2)


40.0 86.3 96.0 207.2 10.3 83.8 98.4 201.0 9.7 81.2 100.6 194.9 9.2 78.7 102.6 188.8 8.8 76.1 104.5 182.7 8.3
42.0 89.5 98.0 214.7 10.4 86.8 100.5 208.4 9.9 84.2 102.8 202.1 9.4 81.6 105.0 195.8 8.9 79.0 107.0 189.5 8.5
44.0 92.6 100.1 222.4 10.6 89.9 102.7 215.9 10.0 87.2 105.1 209.4 9.5 84.6 107.4 202.9 9.0 81.9 109.5 196.5 8.6
45.0 94.3 101.1 226.2 10.7 91.5 103.8 219.7 10.1 88.8 106.2 213.1 9.6 86.1 108.6 206.6 9.1 83.4 110.7 200.0 8.6
46.0 95.9 102.2 230.1 10.7 93.1 104.9 223.5 10.2 90.4 107.4 216.8 9.6 87.6 109.8 210.2 9.2 84.8 112.0 203.6 8.7
48.0 99.2 104.3 238.0 10.9 96.3 107.1 231.2 10.3 93.5 109.8 224.4 9.8 90.7 112.3 217.6 9.3 87.9 114.6 210.8 8.8
50.0 102.5 106.4 246.1 11.0 99.6 109.4 239.1 10.5 96.7 112.2 232.1 9.9 93.8 114.8 225.1 9.4 90.9 117.2 218.2 8.9

Certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program, which is
based on ARI Standard 550/590-98.

KW = Compressor kW
EER = Unit EER
NOTE: Units must include the high ambient option above 115°F ambient. Contact Factory.

18 YORK INTERNATIONAL
FORM 150.70-EG1

MODEL YCAZ33BA3 (IPLV = 10.4)


AIR TEMPERATURE – CONDENSER °F
LCWT 100 105 110 115
°F TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER
40.0 44.2 60.2 106.2 8.1 42.7 61.5 102.6 7.7 41.3 62.7 99.0 7.3 39.8 63.8 95.5 6.9
42.0 46.0 61.4 110.4 8.3 44.5 62.8 106.7 7.9 43.0 64.0 103.1 7.5 41.4 65.2 99.4 7.1
44.0 47.8 62.6 114.7 8.5 46.2 64.0 111.0 8.0 44.7 65.4 107.2 7.6 43.1 66.6 103.5 7.2
45.0 48.7 63.2 116.9 8.6 47.1 64.7 113.1 8.1 45.5 66.0 109.3 7.7 44.0 67.3 105.5 7.3
46.0 49.6 63.9 119.1 8.7 48.0 65.3 115.3 8.2 46.4 66.7 111.4 7.8 44.8 68.0 107.6 7.4
48.0 51.5 65.1 123.6 8.8 49.9 66.6 119.7 8.4 48.2 68.1 115.7 7.9 46.6 69.5 111.8 7.5
50.0 53.4 66.3 128.2 9.0 51.7 67.9 124.1 8.5 50.0 69.5 120.1 8.1 48.4 70.9 116.1 7.6

MODEL YCAZ44BA3 (IPLV = 9.9)


40.0 48.6 70.6 116.6 7.7 46.9 71.9 112.6 7.3 45.3 73.1 108.7 7.0 43.7 74.2 104.8 6.6
42.0 50.5 72.1 121.1 7.9 48.8 73.5 117.1 7.5 47.1 74.8 113.1 7.1 45.4 75.9 109.1 6.7
44.0 52.4 73.7 125.7 8.0 50.7 75.1 121.6 7.6 49.0 76.5 117.5 7.2 47.2 77.7 113.4 6.9
45.0 53.4 74.4 128.1 8.1 51.6 75.9 123.9 7.7 49.9 77.3 119.7 7.3 48.2 78.6 115.6 6.9
46.0 54.3 75.2 130.4 8.1 52.6 76.7 126.2 7.7 50.8 78.2 122.0 7.3 49.1 79.5 117.8 7.0
48.0 56.3 76.8 135.2 8.3 54.5 78.4 130.9 7.8 52.7 79.9 126.6 7.5 50.9 81.3 122.2 7.1
50.0 58.4 78.4 140.1 8.4 56.5 80.1 135.7 8.0 54.7 81.7 131.2 7.6 52.8 83.1 126.8 7.2

MODEL YCAZ74BB3 (IPLV = 10.5)


40.0 56.9 77.4 136.5 8.3 55.0 78.9 132.0 7.9 53.1 80.2 127.4 7.5 51.2 81.4 122.9 7.1
42.0 59.1 79.0 141.9 8.4 57.2 80.6 137.2 8.0 55.2 82.0 132.5 7.6 53.3 83.3 127.9 7.2
44.0 61.4 80.7 147.3 8.6 59.4 82.3 142.5 8.2 57.4 83.8 137.7 7.8 55.4 85.2 133.0 7.4
45.0 62.5 81.5 150.1 8.7 60.5 83.2 145.2 8.2 58.5 84.7 140.4 7.8 56.5 86.2 135.5 7.4
46.0 63.7 82.3 152.9 8.8 61.6 84.1 147.9 8.3 59.6 85.7 143.0 7.9 57.6 87.1 138.1 7.5
48.0 66.0 84.0 158.5 8.9 63.9 85.8 153.5 8.4 61.8 87.5 148.4 8.0 59.8 89.1 143.4 7.6
50.0 68.4 85.7 164.2 9.1 66.3 87.6 159.1 8.6 64.1 89.4 153.9 8.2 62.0 91.1 148.8 7.7

MODEL YCAZ77CB3 (IPLV = 10.8)


40.0 63.2 85.2 151.8 8.4 61.1 86.7 146.6 8.0 59.0 88.0 141.5 7.6 56.8 89.1 136.4 7.2
42.0 65.7 87.1 157.7 8.6 63.5 88.7 152.4 8.1 61.3 90.1 147.2 7.7 59.1 91.3 141.9 7.4
44.0 68.2 89.0 163.7 8.7 66.0 90.7 158.3 8.3 63.7 92.2 152.9 7.9 61.5 93.5 147.6 7.5
45.0 69.5 90.0 166.8 8.8 67.2 91.7 161.3 8.3 64.9 93.2 155.9 7.9 62.7 94.6 150.4 7.5
46.0 70.8 91.0 169.9 8.8 68.5 92.7 164.3 8.4 66.2 94.3 158.8 8.0 63.9 95.8 153.3 7.6
48.0 73.4 93.0 176.1 9.0 71.0 94.8 170.5 8.5 68.7 96.5 164.8 8.1 66.3 98.0 159.1 7.7
50.0 76.0 95.0 182.5 9.1 73.6 96.9 176.7 8.7 71.2 98.7 170.9 8.2 68.8 100.3 165.1 7.8

MODEL YCAZ88DB3 (IPLV = 10.2)


40.0 73.6 106.3 176.6 7.9 71.0 107.8 170.5 7.6 68.5 109.2 164.5 7.2 66.1 110.4 158.5 6.9
42.0 76.4 108.8 183.3 8.1 73.8 110.5 177.1 7.7 71.2 111.9 170.9 7.3 68.7 113.2 164.8 7.0
44.0 79.2 111.4 190.1 8.2 76.6 113.2 183.7 7.8 73.9 114.8 177.4 7.4 71.3 116.2 171.1 7.1
45.0 80.6 112.7 193.6 8.2 78.0 114.5 187.1 7.8 75.3 116.2 180.7 7.5 54.1 82.6 129.8 7.4
46.0 82.1 114.1 197.0 8.3 79.4 115.9 190.5 7.9 76.7 117.6 184.0 7.5 55.1 83.5 132.3 7.5
48.0 85.0 116.8 204.1 8.4 82.2 118.7 197.4 8.0 79.5 120.5 190.7 7.6 57.3 85.3 137.5 7.6
50.0 88.0 119.5 211.3 8.5 85.2 121.6 204.4 8.1 82.3 123.5 197.6 7.7 59.6 87.1 142.3 7.8

Certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program, which is
based on ARI Standard 550/590-98.

KW = Compressor kW
EER = Unit EER
NOTE: Units must include the high ambient option above 115°F ambient. Contact Factory.

YORK INTERNATIONAL 19
Ratings - 60 Hz (95 - 130 Tons) (English)

MODEL YCAZ88EE8 (IPLV = 10.8)


AIR TEMPERATURE – CONDENSER °F
LCWT
75 80 85 90 95
°F
TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER
40.0 98.3 87.7 236.0 11.5 95.6 90.8 229.5 10.9 92.9 93.9 222.9 10.3 90.1 96.8 216.2 9.7 87.3 99.7 209.6 9.2
42.0 102.1 88.9 245.0 11.8 99.3 92.1 238.3 11.1 96.5 95.3 231.5 10.5 93.6 98.3 224.8 9.9 90.8 101.3 217.9 9.4
44.0 105.9 90.0 254.2 12.1 103.1 93.4 247.3 11.4 100.2 96.6 240.4 10.8 97.3 99.8 233.4 10.2 94.3 102.9 226.4 9.6
45.0 107.9 90.6 258.9 12.3 105.0 94.0 251.9 11.6 102.0 97.3 244.9 10.9 99.1 100.6 237.8 10.3 96.2 103.7 230.8 9.7
46.0 109.8 91.1 263.6 12.4 106.9 94.6 256.5 11.7 103.9 98.0 249.4 11.1 101.0 101.3 242.3 10.4 98.0 104.5 235.1 9.9
48.0 113.8 92.3 273.2 12.8 110.8 95.9 265.9 12.0 107.8 99.4 258.7 11.3 104.7 102.9 251.4 10.7 101.7 106.2 244.0 10.1
50.0 117.9 93.4 282.9 13.1 114.8 97.2 275.5 12.3 111.7 100.8 268.1 11.6 108.6 104.4 260.6 10.9 105.5 107.8 253.1 10.3

MODEL YCAJ110 (IPLV = 10.9)


40.0 110.4 93.2 265.0 12.0 107.3 97.1 257.5 11.2 104.1 101.1 250.0 10.5 101.0 104.6 242.5 9.9 97.8 108.2 234.7 9.3
42.0 114.6 94.8 275.1 12.3 111.4 98.9 267.4 11.5 108.2 103.1 259.6 10.8 104.9 106.9 251.8 10.1 101.7 110.5 244.0 9.5
44.0 118.9 96.5 285.4 12.5 115.6 100.7 277.6 11.8 112.3 104.9 269.6 11.0 109.0 109.1 261.5 10.3 105.6 112.9 253.4 9.7
45.0 121.1 97.4 290.7 12.7 117.8 101.6 282.7 11.9 114.4 105.9 274.6 11.1 111.0 110.2 266.5 10.4 107.6 114.0 258.2 9.8
46.0 123.3 98.1 296.0 12.8 120.0 102.5 287.9 12.0 116.6 106.8 279.8 11.3 113.1 111.3 271.5 10.5 109.6 115.2 263.1 9.9
48.0 127.8 99.5 306.8 13.1 124.4 104.3 298.5 12.3 120.9 108.8 290.2 11.5 117.4 113.3 281.7 10.8 113.8 117.6 273.1 10.1
50.0 132.4 101.0 317.7 13.4 128.9 106.2 309.3 12.5 125.3 110.8 300.7 11.7 121.7 115.4 292.1 11.0 118.0 120.0 283.3 10.3

MODEL YCAJ120 (IPLV = 10.3)


40.0 118.1 105.8 283.4 11.5 114.8 109.8 275.5 10.8 111.5 113.7 267.7 10.2 108.2 117.2 259.7 9.6 104.8 120.7 251.6 9.1
42.0 122.6 108.0 294.1 11.7 119.2 112.1 286.0 11.0 115.8 116.2 277.9 10.4 112.3 119.9 269.6 9.8 108.9 123.5 261.4 9.3
44.0 127.1 110.2 305.0 12.0 123.7 114.5 296.8 11.3 120.1 118.7 288.4 10.6 116.6 122.6 279.9 10.0 113.1 126.4 271.4 9.4
45.0 129.4 111.3 310.6 12.1 125.9 115.6 302.2 11.4 122.3 120.0 293.6 10.7 118.8 124.0 285.1 10.1 115.2 127.8 276.5 9.5
46.0 131.8 112.4 316.3 12.2 128.2 116.8 307.7 11.5 124.6 121.2 299.0 10.8 121.0 125.4 290.4 10.2 117.3 129.3 281.6 9.6
48.0 136.5 114.6 327.5 12.4 132.9 119.2 318.9 11.7 129.2 123.7 310.0 11.0 125.4 128.1 301.1 10.3 121.7 132.3 292.1 9.8
50.0 141.3 116.9 339.2 12.6 137.6 121.7 330.2 11.9 133.8 126.2 321.2 11.2 130.0 130.9 312.0 10.5 126.2 135.4 302.8 9.9

MODEL YCAJ130 (IPLV = 10.3)


40.0 125.9 118.1 302.1 11.1 122.4 122.2 293.8 10.5 118.9 125.8 285.5 10.0 115.4 129.4 277.0 9.4 111.9 132.8 268.6 8.9
42.0 130.6 120.8 313.4 11.3 127.0 125.0 304.8 10.7 123.4 129.0 296.2 10.1 119.8 132.6 287.6 9.6 116.2 136.2 278.9 9.1
44.0 135.4 123.6 324.9 11.5 131.7 127.9 316.1 10.9 128.0 132.1 307.2 10.3 124.3 135.8 298.4 9.7 120.6 139.5 289.5 9.2
45.0 137.8 125.0 330.7 11.6 134.1 129.3 321.9 11.0 130.3 133.7 312.8 10.4 126.6 137.4 303.9 9.8 122.8 141.2 294.8 9.3
46.0 140.2 126.4 336.6 11.7 136.5 130.8 327.6 11.1 132.7 135.2 318.5 10.4 128.9 139.1 309.5 9.9 125.1 142.9 300.2 9.4
48.0 145.2 129.4 348.6 11.9 141.4 133.8 339.3 11.2 137.5 138.2 330.0 10.6 133.6 142.5 320.6 10.0 129.7 146.6 311.2 9.5
50.0 150.3 132.3 360.8 12.0 146.4 136.8 351.3 11.4 142.4 141.3 341.7 10.8 138.4 146.1 332.1 10.2 134.3 150.3 322.4 9.6

Certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program, which is
based on ARI Standard 550/590-98.

KW = Compressor kW
EER = Unit EER
NOTE: Units must include the high ambient option above 115°F ambient. Contact Factory.

20 YORK INTERNATIONAL
FORM 150.70-EG1

MODEL YCAZ88EE8 (IPLV = 10.8)


AIR TEMPERATURE – CONDENSER °F
LCWT 100 105 110 115
°F TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER
40.0 84.5 102.4 202.9 8.7 81.7 105.0 196.2 8.2 79.0 107.5 189.5 7.7 76.2 109.8 182.8 7.3
42.0 87.9 104.1 211.1 8.9 85.1 106.9 204.2 8.4 82.2 109.5 197.3 7.9 79.3 111.9 190.4 7.5
44.0 91.4 105.9 219.4 9.1 88.5 108.7 212.4 8.6 85.6 111.5 205.3 8.1 82.6 114.1 198.3 7.7
45.0 93.2 106.8 223.7 9.2 90.2 109.7 216.5 8.7 87.3 112.5 209.4 8.2 84.3 115.1 202.3 7.8
46.0 95.0 107.6 228.0 9.3 92.0 110.6 220.8 8.8 89.0 113.5 213.5 8.3 86.0 116.2 206.3 7.9
48.0 98.6 109.4 236.7 9.5 95.5 112.5 229.3 9.0 92.5 115.5 221.9 8.5 89.4 118.3 214.5 8.1
50.0 102.3 111.2 245.6 9.7 99.2 114.4 238.0 9.2 96.0 117.5 230.4 8.7 92.9 120.5 222.8 8.2

MODEL YCAJ110 (IPLV = 10.9)


40.0 94.5 111.6 226.9 8.8 91.3 114.8 219.2 8.3 88.0 117.8 211.3 7.8 84.7 120.4 203.3 7.4
42.0 98.3 114.2 235.9 9.0 95.0 117.4 228.1 8.5 91.7 120.7 220.0 8.0 88.2 123.5 211.8 7.5
44.0 102.2 116.6 245.3 9.2 98.8 120.1 237.1 8.6 95.4 123.5 228.9 8.1 91.9 126.7 220.5 7.7
45.0 104.2 117.8 250.1 9.2 100.7 121.5 241.7 8.7 97.2 124.9 233.3 8.2 93.7 128.3 224.9 7.7
46.0 106.2 119.0 254.9 9.3 102.7 122.8 246.4 8.8 99.1 126.3 237.9 8.3 95.6 129.8 229.3 7.8
48.0 110.1 121.6 264.4 9.5 106.6 125.5 255.9 9.0 103.0 129.2 247.2 8.4 99.3 132.8 238.4 7.9
50.0 114.3 124.2 274.3 9.7 110.6 128.3 265.5 9.1 106.9 132.2 256.6 8.6 103.2 135.9 247.7 8.1

MODEL YCAJ120 (IPLV = 10.3)


40.0 101.5 123.9 243.5 8.6 98.1 127.1 235.5 8.1 94.7 130.0 227.2 7.7 91.2 132.7 218.8 7.3
42.0 105.4 127.0 253.0 8.8 102.0 130.2 244.8 8.3 98.5 133.4 236.3 7.8 94.9 136.3 227.8 7.4
44.0 109.5 130.0 262.8 8.9 105.9 133.5 254.2 8.4 102.4 136.9 245.7 8.0 98.7 140.0 236.9 7.5
45.0 111.6 131.6 267.8 9.0 108.0 135.2 259.1 8.5 104.3 138.6 250.4 8.0 100.7 141.9 241.6 7.6
46.0 113.7 133.2 272.8 9.1 110.0 136.8 264.0 8.6 106.3 140.4 255.1 8.1 102.6 143.7 246.2 7.6
48.0 117.9 136.3 282.9 9.2 114.2 140.2 274.0 8.7 110.3 143.9 264.8 8.2 106.6 147.5 255.7 7.8
50.0 122.3 139.5 293.4 9.3 118.4 143.7 284.1 8.8 114.5 147.5 274.8 8.3 110.5 151.3 265.3 7.9

MODEL YCAJ130 (IPLV = 10.3)


40.0 108.4 135.9 260.2 8.5 104.9 138.9 251.8 8.1 101.3 141.7 243.2 7.6 97.7 144.6 234.6 7.2
42.0 112.6 139.4 270.3 8.6 109.0 142.6 261.7 8.2 105.3 145.7 252.8 7.7 101.6 148.6 243.9 7.3
44.0 116.9 143.1 280.5 8.7 113.1 146.5 271.5 8.3 109.4 149.8 262.6 7.9 105.6 152.9 253.5 7.4
45.0 119.0 145.0 285.7 8.8 115.3 148.5 276.6 8.3 111.5 151.9 267.6 7.9 107.7 155.0 258.4 7.5
46.0 121.2 146.9 291.0 8.9 117.4 150.4 281.8 8.4 113.5 154.0 272.4 7.9 109.7 157.2 263.3 7.5
48.0 125.7 150.7 301.7 9.0 121.7 154.5 292.2 8.5 117.8 158.1 282.7 8.1 113.8 161.6 273.2 7.6
50.0 130.3 154.5 312.6 9.1 126.2 158.7 302.9 8.6 122.1 162.4 293.0 8.1 118.0 166.1 283.1 7.7

Certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program, which is
based on ARI Standard 550/590-98.

KW = Compressor kW
EER = Unit EER
NOTE: Units must include the high ambient option above 115°F ambient. Contact Factory.

YORK INTERNATIONAL 21
Ratings - 60 Hz (150 - 190 Tons) (English)

MODEL YCAJ150 (IPLV = 11.4)


AIR TEMPERATURE – CONDENSER °F
LCWT
75 80 85 90 95
°F
TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER
40.0 152.5 129.1 365.9 12.0 147.7 134.4 354.6 11.2 143.0 139.2 343.2 10.6 138.2 143.8 331.7 9.9 133.4 148.3 320.0 9.3
42.0 158.3 131.6 380.0 12.3 153.5 137.0 368.4 11.5 148.6 142.2 356.6 10.8 143.7 146.9 344.9 10.1 138.7 151.7 332.9 9.5
44.0 164.3 134.0 394.3 12.5 159.3 139.6 382.4 11.7 154.3 145.2 370.4 11.0 149.3 150.1 358.3 10.3 144.2 155.1 346.1 9.7
45.0 167.3 135.3 401.5 12.7 162.3 140.9 389.5 11.9 157.2 146.7 377.4 11.1 152.1 151.8 365.1 10.4 147.0 156.7 352.7 9.8
46.0 170.4 136.6 408.9 12.8 165.3 142.3 396.8 12.0 160.2 148.1 384.5 11.2 155.0 153.4 372.0 10.5 149.8 158.5 359.5 9.9
48.0 176.6 139.2 423.8 13.0 171.4 145.0 411.3 12.2 166.1 151.0 398.7 11.4 160.9 156.8 386.0 10.7 155.5 162.0 373.2 10.1
50.0 182.9 141.8 439.0 13.3 177.6 147.9 426.2 12.5 172.2 153.9 413.3 11.7 166.8 160.1 400.3 10.9 161.3 165.6 387.1 10.3

MODEL YCAJ160 (IPLV = 10.9)


40.0 162.9 145.7 391.0 11.6 158.1 151.0 379.4 10.9 153.3 156.1 367.9 10.3 148.4 161.1 356.1 9.7 143.5 165.9 344.3 9.1
42.0 169.0 148.6 405.6 11.8 164.1 154.1 393.8 11.1 159.1 159.6 381.8 10.4 154.1 165.0 369.9 9.8 149.1 169.9 357.8 9.3
44.0 175.2 151.5 420.6 12.0 170.2 157.5 408.4 11.3 165.1 163.3 396.2 10.6 160.0 168.7 383.9 10.0 154.8 173.9 371.5 9.4
45.0 178.4 153.0 428.1 12.1 173.3 159.2 415.9 11.4 168.1 165.1 403.5 10.7 162.9 170.6 391.0 10.1 157.6 175.9 378.3 9.5
46.0 181.6 154.5 435.8 12.3 176.4 160.8 423.4 11.5 171.2 166.9 410.8 10.8 165.9 172.5 398.2 10.2 160.6 178.0 385.4 9.6
48.0 188.0 157.8 451.2 12.5 182.8 164.4 438.7 11.7 177.4 170.4 425.7 11.0 172.0 176.3 412.7 10.3 166.6 182.0 399.8 9.7
50.0 194.6 161.1 467.1 12.7 189.2 167.5 454.0 11.9 183.7 174.1 440.9 11.2 178.2 180.2 427.6 10.5 172.6 186.2 414.2 9.9

MODEL YCAJ180 (IPLV = 10.9)


40.0 178.8 165.0 429.1 11.4 173.8 170.5 417.0 10.8 168.6 176.1 404.7 10.2 163.5 181.9 392.3 9.6 158.2 186.8 379.7 9.0
42.0 185.4 168.4 445.0 11.6 180.2 174.6 432.4 10.9 174.9 180.4 419.8 10.3 169.5 186.3 406.9 9.7 164.2 191.5 394.1 9.2
44.0 192.1 171.9 461.0 11.8 186.7 178.6 448.1 11.1 181.3 184.8 435.1 10.5 175.8 190.6 422.0 9.9 170.3 196.3 408.8 9.3
45.0 195.5 173.7 469.2 11.9 190.1 180.5 456.2 11.2 184.6 187.0 443.0 10.5 179.0 192.8 429.7 9.9 173.5 198.7 416.3 9.4
46.0 198.9 175.7 477.4 12.0 193.4 182.5 464.3 11.3 187.9 189.1 450.9 10.6 182.3 195.0 437.5 10.0 176.6 201.0 423.9 9.5
48.0 205.9 179.7 494.1 12.2 200.3 186.7 480.8 11.5 194.6 193.5 467.0 10.8 188.8 199.5 453.2 10.2 183.1 205.8 439.3 9.6
50.0 213.0 183.7 511.1 12.3 207.2 190.8 497.3 11.6 201.4 197.7 483.4 10.9 195.5 204.2 469.2 10.3 189.6 210.9 455.0 9.7

MODEL YCAJ190 (IPLV = 10.9)


40.0 189.1 177.2 453.9 11.3 183.9 183.4 441.3 10.7 178.5 189.8 428.3 10.1 172.9 196.0 414.9 9.5 167.4 201.7 401.7 8.9
42.0 196.1 180.9 470.6 11.5 190.6 187.6 457.3 10.8 185.0 194.3 444.0 10.2 179.4 200.8 430.5 9.6 173.7 206.7 416.8 9.1
44.0 203.1 184.7 487.5 11.7 197.4 191.9 473.8 11.0 191.7 198.8 460.1 10.4 186.0 205.6 446.3 9.8 180.2 211.8 432.4 9.2
45.0 206.7 186.6 496.0 11.8 200.9 194.1 482.2 11.1 195.1 201.2 468.4 10.4 189.3 208.0 454.4 9.8 183.4 214.4 440.2 9.3
46.0 210.3 188.6 504.7 11.9 204.4 196.3 490.6 11.2 198.6 203.5 476.6 10.5 192.7 210.3 462.5 9.9 186.7 217.0 448.1 9.3
48.0 217.6 192.8 522.2 12.1 211.6 200.7 507.8 11.3 205.6 208.1 493.3 10.7 199.5 215.1 478.9 10.0 193.4 222.3 464.2 9.5
50.0 225.0 197.1 540.0 12.3 218.8 205.1 525.2 11.5 212.7 212.8 510.5 10.8 206.5 220.2 495.6 10.2 200.3 227.8 480.6 9.6

Certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program, which is
based on ARI Standard 550/590-98.

KW = Compressor kW
EER = Unit EER
NOTE: Units must include the high ambient option above 115°F ambient. Contact Factory.

22 YORK INTERNATIONAL
FORM 150.70-EG1

MODEL YCAJ150 (IPLV = 11.4)


AIR TEMPERATURE – CONDENSER °F
LCWT 100 105 110 115
°F TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER
40.0 128.5 152.2 308.4 8.8 123.6 156.1 296.7 8.3 118.9 159.5 285.3 7.8 114.1 162.7 273.8 7.4
42.0 133.8 155.9 321.0 9.0 128.8 159.9 309.0 8.4 123.8 163.7 297.2 7.9 118.9 167.1 285.6 7.5
44.0 139.1 159.7 333.9 9.1 134.0 163.9 321.6 8.6 128.9 168.0 309.3 8.1 123.8 171.5 297.2 7.6
45.0 141.8 161.6 340.3 9.2 136.7 165.9 328.0 8.7 131.5 170.1 315.5 8.2 126.3 173.8 303.2 7.7
46.0 144.5 163.5 346.9 9.3 139.3 167.9 334.4 8.7 134.1 172.2 321.8 8.2 128.9 176.1 309.2 7.8
48.0 150.1 167.2 360.2 9.5 144.7 172.1 347.4 8.9 139.3 176.5 334.8 8.4 134.0 180.7 321.5 7.9
50.0 155.8 171.0 373.8 9.6 150.3 176.2 360.7 9.0 144.8 180.7 347.5 8.5 139.3 185.1 334.3 8.0

MODEL YCAJ160 (IPLV = 10.9)


40.0 138.5 170.3 332.5 8.6 133.6 174.3 320.6 8.1 128.7 178.0 308.8 7.7 123.7 181.4 297.0 7.3
42.0 144.0 174.4 345.6 8.7 138.9 178.8 333.4 8.3 133.9 182.8 321.3 7.8 128.8 186.6 309.1 7.4
44.0 149.5 178.7 358.9 8.9 144.4 183.4 346.4 8.4 139.1 187.8 333.9 7.9 133.9 191.9 321.5 7.5
45.0 152.4 180.9 365.7 9.0 147.1 185.7 353.1 8.4 141.8 190.2 340.3 8.0 136.6 194.5 327.7 7.5
46.0 155.2 183.1 372.6 9.0 149.9 188.1 359.8 8.5 144.5 192.7 346.9 8.0 139.2 197.1 334.1 7.6
48.0 161.1 187.6 386.5 9.2 155.5 192.8 373.3 8.6 150.0 197.8 360.1 8.1 144.5 202.3 346.9 7.7
50.0 167.0 192.2 400.7 9.3 161.3 197.7 387.2 8.8 155.7 202.7 373.7 8.3 150.1 207.5 360.2 7.8

MODEL YCAJ180 (IPLV = 10.9)


40.0 153.0 191.5 367.1 8.5 147.7 195.9 354.5 8.1 142.5 200.1 342.1 7.7 137.2 204.0 329.3 7.2
42.0 158.8 196.4 381.2 8.7 153.4 201.3 368.2 8.2 148.0 205.7 355.3 7.8 142.6 210.1 342.3 7.3
44.0 164.8 201.4 395.6 8.8 159.3 206.7 382.2 8.3 153.7 211.5 368.9 7.9 148.2 216.1 355.6 7.4
45.0 167.9 204.0 402.9 8.9 162.2 209.4 389.3 8.4 156.6 214.5 375.8 7.9 151.0 219.0 362.4 7.5
46.0 171.0 206.7 410.3 8.9 165.2 212.2 396.6 8.4 159.5 217.4 382.9 8.0 153.8 222.0 369.2 7.5
48.0 177.2 212.1 425.4 9.0 171.4 217.7 411.3 8.5 165.5 223.2 397.1 8.1 159.6 228.1 383.1 7.6
50.0 183.6 217.6 440.6 9.2 177.6 223.3 426.2 8.6 171.5 229.0 411.7 8.2 165.5 234.5 397.3 7.7

MODEL YCAJ190 (IPLV = 10.9)


40.0 161.8 207.0 388.3 8.4 156.1 211.8 374.8 8.0 150.6 216.7 361.5 7.5 145.1 221.1 348.1 7.1
42.0 168.0 212.4 403.1 8.6 162.2 217.7 389.3 8.1 156.5 222.8 375.6 7.6 150.8 227.6 361.8 7.2
44.0 174.3 217.8 418.3 8.7 168.4 223.6 404.1 8.2 162.5 229.0 389.9 7.7 156.6 234.1 375.8 7.3
45.0 177.5 220.5 425.9 8.7 171.5 226.6 411.5 8.2 165.5 232.2 397.2 7.8 159.5 237.4 382.9 7.3
46.0 180.7 223.4 433.6 8.8 174.6 229.6 419.1 8.3 168.6 235.3 404.5 7.8 162.5 240.6 390.0 7.4
48.0 187.2 229.1 449.4 8.9 181.0 235.6 434.5 8.4 174.8 241.6 419.5 7.9 168.6 247.3 404.6 7.5
50.0 193.9 235.0 465.4 9.0 187.5 241.6 450.1 8.5 181.1 248.2 434.8 8.0 156.5 216.1 375.6 7.8

Certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program, which is
based on ARI Standard 550/590-98.

KW = Compressor kW
EER = Unit EER
NOTE: Units must include the high ambient option above 115°F ambient. Contact Factory.

YORK INTERNATIONAL 23
Ratings - 60 Hz (200 - 230 Tons) (English)

MODEL YCAJ200 (IPLV = 10.7)*


AIR TEMPERATURE – CONDENSER °F
LCWT
75 80 85 90 95
°F
TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER
40.0 205.2 188.7 492.5 11.3 199.4 196.0 478.6 10.6 193.6 203.2 464.6 10.0 187.7 210.7 450.5 9.4 181.8 217.3 436.2 8.8
42.0 212.7 192.5 510.4 11.5 206.7 200.2 496.1 10.8 200.8 207.8 481.8 10.1 194.7 215.6 467.3 9.5 188.6 222.6 452.6 9.0
44.0 220.3 196.4 528.7 11.7 214.1 204.6 513.9 11.0 208.0 212.6 499.2 10.3 201.8 220.5 484.4 9.7 195.6 228.1 469.4 9.1
45.0 224.2 198.3 538.0 11.8 217.9 206.8 523.0 11.1 211.7 215.0 508.1 10.4 205.4 222.9 493.0 9.8 199.1 230.8 477.8 9.2
46.0 228.1 200.3 547.4 11.9 221.8 209.0 532.2 11.2 215.4 217.5 517.0 10.5 209.1 225.4 501.8 9.8 202.7 233.5 486.4 9.2
48.0 236.1 204.4 566.6 12.1 229.6 213.4 550.9 11.3 223.0 222.3 535.2 10.6 216.5 230.5 519.6 10.0 209.9 238.8 503.8 9.4
50.0 244.1 208.8 585.9 12.3 237.5 217.9 570.1 11.5 230.8 227.1 553.9 10.8 224.1 235.6 537.8 10.1 217.4 244.3 521.7 9.5

MODEL YCAJ220 (IPLV = 10.4)†


40.0 218.9 208.9 525.3 11.0 212.7 216.5 510.6 10.4 206.6 224.1 495.8 9.8 200.4 231.7 481.0 9.2 194.1 238.7 465.9 8.7
42.0 226.8 213.5 544.3 11.2 220.5 221.5 529.1 10.5 214.1 229.3 513.9 9.9 207.7 237.1 498.6 9.3 201.4 244.5 483.3 8.8
44.0 234.7 218.3 563.3 11.4 228.3 226.4 547.9 10.7 221.8 234.6 532.3 10.1 215.3 242.7 516.6 9.5 208.7 250.5 500.9 8.9
45.0 238.8 220.6 573.1 11.5 232.3 228.9 557.4 10.8 225.7 237.3 541.6 10.1 219.0 245.5 525.7 9.6 212.4 253.5 509.8 9.0
46.0 242.9 223.0 583.0 11.5 236.3 231.5 567.2 10.9 229.6 240.0 551.1 10.2 222.9 248.3 534.9 9.6 216.1 256.4 518.8 9.1
48.0 251.2 227.8 603.0 11.7 244.5 236.8 586.7 11.0 237.6 245.5 570.2 10.4 230.7 254.0 553.8 9.8 223.8 262.5 537.1 9.2
50.0 259.8 232.8 623.5 11.9 252.8 242.0 606.6 11.2 245.7 251.1 589.7 10.5 238.7 259.9 572.8 9.9 231.6 268.8 555.8 9.3

MODEL YCAJ230 (IPLV = 10.3)†


40.0 232.9 228.8 558.9 10.8 226.4 236.7 543.4 10.2 219.9 244.7 527.8 9.6 213.4 252.2 512.2 9.1 206.9 259.8 496.5 8.6
42.0 241.2 234.2 578.9 11.0 234.5 242.3 562.9 10.4 227.9 250.4 546.9 9.8 221.1 258.2 530.7 9.2 214.4 266.0 514.7 8.7
44.0 249.5 239.8 598.9 11.1 242.8 247.9 582.7 10.5 235.9 256.2 566.3 9.9 229.0 264.5 549.7 9.3 222.1 272.4 533.2 8.8
45.0 253.8 242.5 609.1 11.2 247.0 250.8 592.7 10.6 240.0 259.2 576.1 10.0 233.0 267.6 559.2 9.4 226.0 275.7 542.5 8.9
46.0 258.1 245.2 619.5 11.3 251.2 253.8 602.8 10.6 244.2 262.2 586.0 10.0 237.0 270.7 568.9 9.5 230.0 279.0 552.0 8.9
48.0 266.8 250.8 640.4 11.4 259.7 259.8 623.3 10.8 252.5 268.3 606.1 10.2 245.2 277.1 588.6 9.6 238.0 285.7 571.1 9.1
50.0 275.8 256.5 661.9 11.6 268.4 265.8 644.1 10.9 261.0 274.7 626.3 10.3 253.6 283.6 608.6 9.7 246.1 292.7 590.6 9.2

* Certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program, which is
based on ARI Standard 550/590-98.

Outside the scope of ARI Standard 550/590-98.

KW = Compressor kW
EER = Unit EER
NOTE: Units must include the high ambient option above 115°F ambient. Contact Factory.

24 YORK INTERNATIONAL
FORM 150.70-EG1

MODEL YCAJ200 (IPLV = 10.7)*


AIR TEMPERATURE – CONDENSER °F
LCWT 100 105 110 115
°F TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER TONS KW GPM EER
40.0 175.7 223.7 421.7 8.3 169.7 229.5 407.2 7.9 163.6 235.2 392.6 7.4 157.5 240.4 378.1 7.0
42.0 182.4 229.2 437.8 8.5 176.2 235.8 422.9 8.0 170.0 241.6 407.9 7.5 163.7 247.4 392.9 7.1
44.0 189.2 234.9 454.1 8.6 182.8 242.0 438.8 8.1 176.4 248.2 423.5 7.6 170.0 254.2 408.0 7.2
45.0 192.7 237.9 462.4 8.6 186.2 245.0 446.9 8.1 179.7 251.6 431.4 7.7 173.2 257.6 415.7 7.2
46.0 196.2 240.9 470.9 8.7 189.6 248.1 455.1 8.2 183.1 255.0 439.3 7.7 176.5 261.2 423.5 7.3
48.0 203.3 246.9 487.9 8.8 196.6 254.3 471.8 8.3 189.8 261.8 455.5 7.8 183.0 268.4 439.3 7.4
50.0 210.6 253.1 505.4 8.9 203.7 260.7 488.8 8.4 196.7 268.6 472.2 7.9 189.8 276.0 455.5 7.5

MODEL YCAJ220 (IPLV = 10.4)†


40.0 187.8 245.5 450.8 8.2 181.5 251.9 435.6 7.7 175.1 257.9 420.2 7.3 168.6 263.5 404.7 6.9
42.0 194.9 251.7 467.8 8.3 188.4 258.5 452.1 7.8 181.8 264.9 436.3 7.4 175.2 270.9 420.4 7.0
44.0 202.1 257.9 485.0 8.4 195.4 265.2 468.9 8.0 188.7 272.0 452.8 7.5 181.8 278.5 436.4 7.1
45.0 205.7 261.1 493.7 8.5 198.9 268.5 477.4 8.0 192.1 275.5 461.0 7.6 185.2 282.4 444.5 7.1
46.0 209.4 264.3 502.5 8.5 202.5 271.9 486.0 8.1 195.6 279.3 469.4 7.6 188.6 286.4 452.7 7.2
48.0 216.8 270.8 520.3 8.7 209.8 278.9 503.5 8.2 202.7 286.8 486.4 7.7 195.5 294.4 469.2 7.2
50.0 224.4 277.5 538.5 8.8 217.2 286.1 521.2 8.3 209.9 294.5 503.7 7.8 202.6 302.6 486.2 7.3

MODEL YCAJ230 (IPLV = 10.3)†


40.0 200.3 266.9 480.6 8.1 193.6 273.8 464.6 7.7 186.8 280.2 448.3 7.2 180.0 286.1 432.0 6.8
42.0 207.7 273.7 498.5 8.2 200.9 280.7 482.2 7.8 193.9 287.8 465.4 7.3 186.9 293.9 448.6 6.9
44.0 215.2 280.5 516.6 8.3 208.2 287.9 499.7 7.9 201.1 295.2 482.7 7.4 194.0 302.3 465.5 7.0
45.0 219.0 283.8 525.7 8.4 211.9 291.5 508.6 7.9 204.8 299.0 491.4 7.5 197.5 306.7 474.0 7.0
46.0 222.9 287.3 534.9 8.4 215.7 295.3 517.7 8.0 208.4 303.1 500.3 7.5 201.1 311.1 482.6 7.1
48.0 230.7 294.2 553.6 8.5 223.3 303.0 535.9 8.1 215.8 311.5 518.0 7.6 208.3 319.8 500.0 7.2
50.0 238.6 301.4 572.6 8.6 231.0 311.0 554.5 8.1 223.4 320.0 536.2 7.7 215.7 328.6 517.7 7.2

* Certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program, which is
based on ARI Standard 550/590-98.

Outside the scope of ARI Standard 550/590-98.

KW = Compressor kW
EER = Unit EER
NOTE: Units must include the high ambient option above 115°F ambient. Contact Factory.

YORK INTERNATIONAL 25
Ratings - 60 Hz (176 - 317kW) (SI)
MODEL YCAZ33BA3
AIR TEMPERATURE – CONDENSER °C
LCWT
25 30 35 40 45
°C
KWo KWE L/sec. COP KWo KWE L/sec. COP KWo KWE L/sec. COP KWo KWE L/sec. COP KWo KWE L/sec. COP
5.0 183.1 53.9 7.9 3.1 173.6 56.8 7.5 2.8 164.0 59.5 7.1 2.5 154.4 61.9 6.7 2.3 144.9 64.0 6.2 2.1
6.0 189.3 54.6 8.2 3.2 179.5 57.7 7.7 2.9 169.7 60.5 7.3 2.6 160.0 63.0 6.9 2.4 150.2 65.3 6.5 2.1
7.0 195.6 55.4 8.4 3.2 185.6 58.6 8.0 2.9 175.6 61.5 7.6 2.6 165.6 64.2 7.1 2.4 155.6 66.5 6.7 2.2
8.0 202.0 56.2 8.7 3.3 191.8 59.5 8.3 3.0 181.6 62.5 7.8 2.7 171.3 65.3 7.4 2.4 161.1 67.8 6.9 2.2
9.0 208.5 57.0 9.0 3.4 198.1 60.4 8.5 3.0 187.6 63.6 8.1 2.7 177.2 66.5 7.6 2.5 166.7 69.1 7.2 2.3
10.0 215.1 57.8 9.3 3.4 204.5 61.3 8.8 3.1 193.8 64.6 8.3 2.8 183.1 67.6 7.9 2.5 172.4 70.3 7.4 2.3

MODEL YCAZ44BA3
5.0 201.0 64.0 8.7 2.9 190.5 67.1 8.2 2.6 180.0 69.9 7.8 2.4 169.4 72.4 7.3 2.2 159.0 74.6 6.9 2.0
6.0 207.7 65.0 8.9 3.0 196.9 68.3 8.5 2.7 186.1 71.2 8.0 2.4 175.4 73.9 7.6 2.2 164.7 76.2 7.1 2.0
7.0 214.4 66.1 9.2 3.0 203.4 69.5 8.8 2.7 192.4 72.6 8.3 2.5 181.4 75.3 7.8 2.3 170.5 77.7 7.3 2.1
8.0 221.3 67.1 9.5 3.1 210.0 70.7 9.0 2.8 198.8 73.9 8.6 2.5 187.5 76.8 8.1 2.3 176.4 79.3 7.6 2.1
9.0 228.3 68.2 9.8 3.1 216.8 71.9 9.3 2.8 205.3 75.2 8.8 2.6 193.8 78.3 8.3 2.3 182.3 80.9 7.9 2.1
10.0 235.4 69.3 10.1 3.2 223.6 73.1 9.6 2.9 211.8 76.6 9.1 2.6 200.1 79.8 8.6 2.4 188.4 82.6 8.1 2.2

MODEL YCAZ74BB3
5.0 235.1 70.0 10.1 3.1 223.0 73.4 9.6 2.8 210.7 76.6 9.1 2.6 198.6 79.4 8.6 2.4 186.4 81.9 8.0 2.2
6.0 242.9 71.1 10.5 3.2 230.5 74.7 9.9 2.9 218.0 78.0 9.4 2.6 205.5 81.0 8.9 2.4 193.1 83.5 8.3 2.2
7.0 250.9 72.2 10.8 3.3 238.1 76.0 10.3 2.9 225.4 79.4 9.7 2.7 212.6 82.5 9.2 2.4 199.9 85.2 8.6 2.2
8.0 258.9 73.3 11.2 3.3 245.9 77.2 10.6 3.0 232.9 80.8 10.0 2.7 219.8 84.1 9.5 2.5 206.8 86.9 8.9 2.3
9.0 267.1 74.5 11.5 3.4 253.8 78.5 10.9 3.0 240.5 82.3 10.4 2.8 227.2 85.7 9.8 2.5 213.9 88.7 9.2 2.3
10.0 275.4 75.6 11.9 3.4 261.9 79.8 11.3 3.1 248.2 83.7 10.7 2.8 234.6 87.3 10.1 2.5 221.0 90.4 9.5 2.3

MODEL YCAZ77CB3
5.0 261.9 77.7 11.3 3.2 248.1 81.3 10.7 2.9 234.4 84.6 10.1 2.6 220.6 87.4 9.5 2.4 207.0 89.8 8.9 2.2
6.0 270.6 79.1 11.7 3.2 256.5 82.8 11.0 2.9 242.4 86.2 10.4 2.7 228.4 89.2 9.8 2.4 214.4 91.7 9.2 2.2
7.0 279.4 80.4 12.0 3.3 265.0 84.3 11.4 3.0 250.6 87.8 10.8 2.7 236.2 91.0 10.2 2.5 221.9 93.6 9.6 2.3
8.0 288.4 81.8 12.4 3.3 273.7 85.8 11.8 3.0 258.9 89.5 11.2 2.7 244.2 92.8 10.5 2.5 229.6 95.6 9.9 2.3
9.0 297.5 83.2 12.8 3.4 282.5 87.4 12.2 3.1 267.4 91.2 11.5 2.8 252.4 94.7 10.9 2.5 237.4 97.6 10.2 2.3
10.0 306.8 84.6 13.2 3.4 291.4 89.0 12.6 3.1 276.0 93.0 11.9 2.8 260.6 96.6 11.2 2.6 245.3 99.7 10.6 2.3

MODEL YCAZ88DB3
5.0 305.4 98.0 13.2 3.0 289.0 102.1 12.4 2.7 272.7 105.7 11.7 2.5 256.4 108.8 11.0 2.3 240.4 111.3 10.4 2.1
6.0 315.3 99.9 13.6 3.0 298.5 104.2 12.9 2.7 281.8 108.0 12.1 2.5 265.2 111.2 11.4 2.3 248.8 113.9 10.7 2.1
7.0 325.4 101.8 14.0 3.1 308.2 106.3 13.3 2.8 291.1 110.2 12.5 2.5 274.1 113.6 11.8 2.3 257.3 116.5 11.1 2.1
8.0 335.6 103.7 14.5 3.1 318.0 108.4 13.7 2.8 300.5 112.5 12.9 2.6 283.1 116.1 12.2 2.3 265.9 119.1 11.5 2.1
9.0 346.0 105.6 14.9 3.1 328.0 110.5 14.1 2.8 310.0 114.9 13.4 2.6 292.2 118.6 12.6 2.4 274.6 121.8 11.8 2.2
10.0 356.5 107.6 15.4 3.2 338.1 112.7 14.6 2.9 319.7 117.2 13.8 2.6 301.5 121.2 13.0 2.4 283.5 124.6 12.2 2.2

KWo = Unit kW Cooling Capacity Output


KWE = Compressor kW Input
COP = Coefficent of Performance

NOTE: Units must include the high ambient option above 46.1°C ambient. Contact Factory.

26 YORK INTERNATIONAL
FORM 150.70-EG1

Ratings - 60 Hz (335 - 458 kW) (SI)


MODEL YCAZ88EE8
LCWT AIR TEMPERATURE – CONDENSER °C
25 30 35 40 45
°C
KWo KWE L/sec. COP KWo KWE L/sec. COP KWo KWE L/sec. COP KWo KWE L/sec. COP KWo KWE L/sec. COP
5.0 348.4 89.5 15.2 3.34 330.8 95.2 14.4 3.01 313.1 100.4 13.6 2.72 295.2 105.4 12.8 2.46 277.3 109.9 12.1 2.22
6.0 360.3 90.6 15.7 3.42 342.3 96.4 14.9 3.08 324.2 101.9 14.1 2.78 305.9 107.0 13.3 2.51 287.6 111.8 12.5 2.27
7.0 372.4 91.7 16.2 3.50 354.1 97.7 15.4 3.15 335.5 103.4 14.6 2.84 316.8 108.7 13.8 2.57 298.1 113.6 13.0 2.32
8.0 384.8 92.8 16.7 3.58 366.0 99.0 15.9 3.22 347.0 104.9 15.1 2.90 328.0 110.4 14.3 2.62 308.8 115.5 13.4 2.37
9.0 397.3 93.8 17.3 3.66 378.2 100.2 16.5 3.29 358.8 106.3 15.6 2.96 339.3 112.1 14.8 2.67 319.8 117.4 13.9 2.42
10.0 410.1 94.9 17.8 3.74 390.6 101.5 17.0 3.36 370.8 107.8 16.1 3.02 350.9 113.8 15.3 2.73 330.9 119.3 14.4 2.47

MODEL YCAJ110
5.0 391.2 95.6 17.0 3.46 370.9 102.9 16.1 3.08 350.6 109.4 15.3 2.77 329.9 115.4 14.4 2.48 308.7 120.9 13.4 2.23
6.0 404.5 97.1 17.6 3.53 383.8 104.6 16.7 3.14 363.0 111.4 15.8 2.82 341.7 117.8 14.9 2.53 320.2 123.7 13.9 2.27
7.0 418.1 98.7 18.2 3.60 397.0 106.4 17.3 3.21 375.4 113.5 16.3 2.87 353.8 120.2 15.4 2.57 331.8 126.4 14.4 2.31
8.0 432.0 100.3 18.8 3.67 410.4 108.1 17.9 3.27 388.4 115.6 16.9 2.92 366.2 122.7 15.9 2.61 343.6 129.0 14.9 2.35
9.0 446.1 101.7 19.4 3.75 424.1 109.9 18.4 3.33 401.5 117.8 17.5 2.97 378.8 125.0 16.5 2.66 355.7 131.7 15.5 2.39
10.0 460.5 103.1 20.0 3.82 438.1 111.7 19.1 3.39 415.0 120.0 18.1 3.02 391.5 127.4 17.0 2.70 368.1 134.4 16.0 2.42

MODEL YCAJ120
5.0 418.4 108.5 18.2 3.32 397.1 115.7 17.3 2.98 375.7 122.1 16.3 2.69 354.1 127.9 15.4 2.44 332.0 133.3 14.4 2.20
6.0 432.4 110.5 18.8 3.38 410.7 118.0 17.9 3.03 388.8 124.6 16.9 2.74 366.5 130.8 15.9 2.47 344.1 136.6 15.0 2.23
7.0 446.9 112.6 19.4 3.44 424.5 120.2 18.5 3.08 402.0 127.2 17.5 2.78 379.2 133.8 16.5 2.51 356.3 139.8 15.5 2.27
8.0 461.5 114.7 20.1 3.49 438.7 122.6 19.1 3.13 415.5 129.8 18.1 2.82 392.2 136.8 17.1 2.54 368.7 143.1 16.0 2.30
9.0 476.5 116.7 20.7 3.55 453.1 124.8 19.7 3.19 429.4 132.5 18.7 2.86 405.5 139.7 17.6 2.58 381.3 146.4 16.6 2.33
10.0 491.7 118.8 21.4 3.61 467.7 127.1 20.3 3.24 443.5 135.3 19.3 2.90 418.9 142.9 18.2 2.61 394.2 149.7 17.1 2.36

MODEL YCAJ130
5.0 445.9 121.1 19.4 3.22 423.5 128.1 18.4 2.91 401.0 134.5 17.4 2.64 378.7 140.1 16.5 2.40 355.6 145.4 15.5 2.18
6.0 460.7 123.6 20.0 3.27 437.9 130.9 19.0 2.95 414.7 137.5 18.0 2.68 391.5 143.5 17.0 2.43 368.2 149.1 16.0 2.21
7.0 475.9 126.1 20.7 3.32 452.3 133.8 19.7 2.99 428.7 140.5 18.7 2.72 404.9 146.9 17.6 2.46 381.0 152.9 16.6 2.24
8.0 491.3 128.8 21.4 3.36 467.2 136.6 20.3 3.03 443.0 143.6 19.3 2.75 418.5 150.5 18.2 2.49 394.1 156.8 17.1 2.26
9.0 507.0 131.4 22.1 3.41 482.3 139.4 21.0 3.08 457.5 146.9 19.9 2.78 432.3 154.1 18.8 2.52 407.1 160.7 17.7 2.29
10.0 523.0 134.1 22.7 3.45 497.8 142.2 21.7 3.12 472.3 150.2 20.5 2.82 446.5 157.8 19.4 2.55 420.6 164.6 18.3 2.31

KWo = Unit kW Cooling Capacity Output


KWE = Compressor kW Input
COP = Coefficent of Performance

NOTE: Units must include the high ambient option above 46.1°C ambient. Contact Factory.

YORK INTERNATIONAL 27
Ratings - 60 Hz (528 - 669 kW) (SI)
MODEL YCAJ150
LCWT AIR TEMPERATURE – CONDENSER °C
25 30 35 40 45
°C
KWo KWE L/sec. COP KWo KWE L/sec. COP KWo KWE L/sec. COP KWo KWE L/sec. COP KWo KWE L/sec. COP
5.0 539.5 132.4 23.5 3.47 509.1 141.6 22.1 3.09 478.1 150.0 20.8 2.76 447.1 157.2 19.4 2.48 416.3 163.5 18.1 2.23
6.0 558.1 134.7 24.3 3.53 527.0 144.3 22.9 3.15 495.3 153.0 21.5 2.81 463.6 160.7 20.2 2.52 431.9 167.4 18.8 2.27
7.0 577.0 137.0 25.1 3.60 545.1 147.1 23.7 3.20 512.9 156.0 22.3 2.86 480.3 164.2 20.9 2.56 447.7 171.5 19.5 2.30
8.0 596.1 139.4 25.9 3.67 563.7 149.8 24.5 3.26 530.7 159.1 23.1 2.91 497.3 167.8 21.6 2.60 463.9 175.5 20.2 2.33
9.0 615.7 141.8 26.8 3.73 582.4 152.4 25.3 3.32 548.7 162.3 23.9 2.96 514.4 171.5 22.4 2.64 480.4 179.4 20.9 2.37
10.0 635.5 144.2 27.6 3.80 601.6 155.1 26.2 3.37 567.0 165.6 24.7 3.00 532.2 175.2 23.1 2.68 497.4 183.3 21.6 2.41

MODEL YCAJ160
5.0 576.5 149.4 25.1 3.34 545.6 158.9 23.7 3.00 514.2 167.9 22.4 2.69 482.5 175.7 21.0 2.43 451.0 182.6 19.6 2.19
6.0 595.9 152.0 25.9 3.40 564.1 162.1 24.5 3.04 532.0 171.4 23.1 2.73 499.6 179.7 21.7 2.46 467.3 187.2 20.3 2.22
7.0 615.5 154.8 26.8 3.46 583.2 165.5 25.4 3.09 550.2 175.1 23.9 2.77 517.0 183.8 22.5 2.50 483.8 191.8 21.0 2.25
8.0 635.6 157.6 27.6 3.51 602.4 168.7 26.2 3.14 568.7 178.7 24.7 2.82 534.7 188.0 23.3 2.53 500.6 196.4 21.8 2.28
9.0 655.9 160.6 28.5 3.57 622.1 171.9 27.1 3.19 587.7 182.4 25.6 2.86 552.7 192.3 24.0 2.57 517.8 200.9 22.5 2.31
10.0 676.7 163.9 29.4 3.62 642.0 175.3 27.9 3.23 606.7 186.2 26.4 2.90 571.2 196.5 24.8 2.60 535.4 205.6 23.3 2.34

MODEL YCAJ180
5.0 633.0 169.0 27.5 3.29 600.0 179.4 26.1 2.96 566.7 189.1 24.7 2.67 533.0 197.6 23.2 2.41 499.4 205.4 21.7 2.18
6.0 653.5 172.2 28.4 3.34 620.0 183.3 27.0 3.00 585.8 193.4 25.5 2.71 551.3 202.4 24.0 2.44 516.9 210.7 22.5 2.21
7.0 674.9 175.6 29.4 3.39 640.5 187.3 27.9 3.04 605.4 197.7 26.3 2.74 570.1 207.2 24.8 2.47 534.7 216.0 23.3 2.24
8.0 696.5 179.2 30.3 3.44 661.2 191.1 28.8 3.09 625.6 201.9 27.2 2.78 589.2 212.1 25.7 2.50 553.0 221.4 24.1 2.26
9.0 718.2 182.8 31.2 3.49 682.4 195.1 29.7 3.13 645.8 206.3 28.1 2.81 608.8 217.1 26.5 2.53 571.5 226.8 24.9 2.29
10.0 740.7 186.6 32.2 3.53 704.0 199.0 30.6 3.17 666.5 210.8 29.0 2.85 628.6 222.1 27.3 2.56 590.3 232.3 25.7 2.31

MODEL YCAJ190
5.0 669.5 181.6 29.1 3.27 634.9 193.3 27.6 2.93 599.4 204.1 26.1 2.64 563.7 213.7 24.5 2.38 527.9 222.5 23.0 2.15
6.0 691.1 185.1 30.1 3.32 655.7 197.4 28.5 2.97 617.8 208.2 26.9 2.67 583.0 218.9 25.4 2.41 546.2 228.2 23.8 2.17
7.0 713.4 188.8 31.0 3.37 677.1 201.5 29.5 3.01 640.2 213.3 27.8 2.71 602.7 224.2 26.2 2.44 565.0 234.0 24.6 2.20
8.0 736.1 192.5 32.0 3.41 698.8 205.7 30.4 3.05 661.1 218.0 28.8 2.74 622.7 229.5 27.1 2.46 584.2 239.7 25.4 2.22
9.0 759.0 196.3 33.0 3.46 720.9 210.0 31.4 3.09 682.4 222.8 29.7 2.77 643.1 234.8 28.0 2.49 603.6 245.7 26.3 2.24
10.0 782.4 200.3 34.0 3.50 743.5 214.2 32.3 3.13 704.1 227.7 30.6 2.81 663.8 240.2 28.9 2.52 623.3 251.8 27.1 2.27

KWo = Unit kW Cooling Capacity Output


KWE = Compressor kW Input
COP = Coefficent of Performance

NOTE: Units must include the high ambient option above 46.1°C ambient. Contact Factory.

28 YORK INTERNATIONAL
FORM 150.70-EG1

Ratings - 60 Hz (704 - 810 kW) (SI)


MODEL YCAJ200
LCWT AIR TEMPERATURE – CONDENSER °C
25 30 35 40 45
°C
KWo KWE L/sec. COP KWo KWE L/sec. COP KWo KWE L/sec. COP KWo KWE L/sec. COP KWo KWE L/sec. COP
5.0 726.1 193.6 31.6 3.25 688.9 207.0 30.0 2.91 650.9 219.9 28.3 2.61 612.2 231.4 26.6 2.35 573.2 241.7 24.9 2.11
6.0 749.8 197.2 32.6 3.31 711.7 211.2 31.0 2.95 672.8 224.7 29.3 2.65 633.1 236.9 27.5 2.38 593.2 247.7 25.8 2.14
7.0 773.8 200.8 33.7 3.36 734.6 215.6 32.0 3.00 695.1 229.7 30.2 2.68 654.5 242.3 28.5 2.41 613.6 253.8 26.7 2.17
8.0 798.4 204.5 34.7 3.41 758.2 220.0 33.0 3.04 717.6 234.5 31.2 2.72 676.1 247.8 29.4 2.44 634.3 260.0 27.6 2.19
9.0 823.6 208.4 35.8 3.46 782.1 224.4 34.0 3.08 740.6 239.3 32.2 2.75 698.3 253.4 30.4 2.47 655.4 266.4 28.5 2.21
10.0 849.2 212.3 36.9 3.51 806.6 228.8 35.1 3.12 764.1 244.3 33.2 2.79 720.8 259.1 31.4 2.50 677.0 273.2 29.4 2.24

MODEL YCAJ220
5.0 774.5 214.3 33.7 3.18 734.9 228.2 32.0 2.85 695.2 241.6 30.2 2.56 654.5 253.8 28.5 2.31 613.4 264.9 26.7 2.08
6.0 799.5 218.6 34.8 3.22 759.0 232.9 33.0 2.89 718.2 246.8 31.2 2.60 676.6 259.7 29.4 2.34 634.5 271.3 27.6 2.11
7.0 824.5 222.9 35.9 3.27 783.2 237.8 34.1 2.93 741.5 252.2 32.3 2.63 699.1 265.7 30.4 2.37 656.0 278.1 28.5 2.13
8.0 850.4 227.3 37.0 3.31 808.0 242.7 35.1 2.97 765.2 257.6 33.3 2.66 721.9 271.7 31.4 2.40 677.9 285.1 29.5 2.15
9.0 876.8 231.8 38.1 3.35 833.3 247.7 36.2 3.00 789.4 263.1 34.3 2.70 745.0 277.9 32.4 2.42 700.0 292.2 30.4 2.18
10.0 903.5 236.4 39.3 3.40 858.9 252.8 37.4 3.04 814.1 268.7 35.4 2.73 768.5 284.3 33.4 2.45 722.4 299.4 31.4 2.20

MODEL YCAJ230
5.0 823.9 234.6 35.8 3.12 782.3 249.1 34.0 2.81 740.6 262.9 32.2 2.53 698.0 275.8 30.4 2.29 654.6 287.5 28.5 2.06
6.0 850.3 239.6 37.0 3.16 807.6 254.3 35.1 2.84 764.6 268.5 33.3 2.57 721.2 282.1 31.4 2.31 676.9 294.5 29.4 2.09
7.0 876.5 244.8 38.1 3.19 833.2 259.6 36.2 2.88 789.2 274.3 34.3 2.60 744.8 288.5 32.4 2.34 699.6 302.0 30.4 2.11
8.0 903.6 249.8 39.3 3.23 859.3 265.0 37.4 2.92 814.1 280.3 35.4 2.63 768.7 295.2 33.4 2.37 722.4 309.6 31.4 2.13
9.0 931.3 254.9 40.5 3.27 885.8 270.6 38.5 2.95 839.4 286.4 36.5 2.66 793.0 301.9 34.5 2.39 745.6 317.3 32.4 2.15
10.0 959.2 260.2 41.7 3.31 912.5 276.4 39.7 2.98 865.2 292.6 37.6 2.68 817.5 309.0 35.6 2.41 769.1 325.1 33.5 2.17

KWo = Unit kW Cooling Capacity Output


KWE = Compressor kW Input
COP = Coefficent of Performance

NOTE: Units must include the high ambient option above 46.1°C ambient. Contact Factory.

YORK INTERNATIONAL 29
Ratings - Part Load (50 - 90 Tons) (English)

60 HZ MODELS

YCAZ33BA3 YCAZ44BA3
% ENTERING % ENTERING
TONS KW EER TONS KW EER
DISPL. AIR °F DISPL. AIR °F
100.0 95.0 49.4 61.2 9.0 100.0 95.0 54.1 72.1 8.4
75.0 87.6 40.2 44.6 9.7 75.0 87.7 44.2 52.8 9.2
50.0 79.5 30.2 28.4 10.9 50.0 79.9 33.6 33.7 10.4
50.0 76.6 26.7 27.2 10.0 50.0 76.6 29.2 32.3 9.4
25.0 67.8 15.9 12.5 10.9 25.0 68.0 17.7 14.9 10.6
IPLV: 10.4 EER IPLV: 9.9 EER

YCAZ74BB3 YCAZ77CB3
% ENTERING % ENTERING
TONS KW EER TONS KW EER
DISPL. AIR °F DISPL. AIR °F
100.0 95.0 63.4 78.9 9.1 100.0 95.0 70.5 87.3 9.2
78.3 88.2 52.5 60.1 9.7 83.3 90.9 63.1 72.0 9.8
59.4 83.4 44.9 44.8 10.8 66.7 86.6 55.7 56.8 10.8
56.6 78.1 36.6 39.8 9.8 50.0 76.6 38.0 39.3 10.3
37.7 73.0 28.5 25.5 11.2 33.3 71.8 29.6 25.2 11.8
IPLV: 10.5 EER IPLV: 10.8 EER

YCAZ88DB3
% ENTERING
TONS KW EER
DISPL. AIR °F
100.0 95.0 81.9 109.5 8.6
83.3 90.9 73.4 90.2 9.2
66.7 86.5 64.6 70.8 10.2
50.0 76.6 44.4 49.8 9.7
33.3 71.8 34.5 31.6 11.3
IPLV: 10.2 EER

Certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program, which is
based on ARI Standard 550/590-98.

30 YORK INTERNATIONAL
FORM 150.70-EG1

Ratings - Part Load (95 - 130 Tons) (English)

60 HZ MODELS

YCAZ88EE8 YCAJ110
% ENTERING % ENTERING
TONS KW EER TONS KW EER
DISPL. AIR °F DISPL. AIR °F
100.0 95.0 93.7 102.5 9.6 100.0 95.0 104.7 112.2 9.7
83.3 90.4 82.9 83.7 10.1 75.0 87.6 85.2 79.2 10.6
66.7 85.7 71.9 65.2 10.8 50.0 79.0 62.9 48.5 11.4
50.0 75.3 47.5 47.9 10.3 50.0 76.6 56.6 48.2 11.4
33.3 70.5 36.5 30.1 11.7 25.0 67.5 32.6 21.9 11.7
IPLV: 10.8 EER IPLV: 10.9 EER

YCAJ120 YCAJ130
% ENTERING % ENTERING
TONS KW EER TONS KW EER
DISPL. AIR °F DISPL. AIR °F
100.0 95.0 112.2 126.3 9.4 100.0 95.0 119.6 138.4 9.2
77.1 88.1 92.7 93.1 10.1 75.0 87.7 97.7 100.1 10.0
50.0 79.1 67.7 56.6 11.0 50.0 79.3 72.7 64.3 10.7
54.3 77.9 64.3 62.3 10.4 50.0 76.5 64.5 61.2 10.6
27.1 68.5 37.9 29.5 11.1 25.0 67.6 37.9 29.0 11.2
IPLV: 10.3 EER IPLV: 10.3 EER

Certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program, which is
based on ARI Standard 550/590-98.

YORK INTERNATIONAL 31
Ratings - Part Load (150 - 190 Tons) (English)

YCAJ150 YCAJ160
% ENTERING % ENTERING
TONS KW EER TONS KW EER
DISPL. AIR °F DISPL. AIR °F
100.0 95.0 143.0 153.6 9.7 100.0 95.0 153.5 173.0 9.4
83.3 90.7 127.6 124.5 10.4 84.8 91.0 137.9 143.7 9.9
66.7 85.8 110.0 96.1 11.1 66.7 85.9 118.3 109.3 10.9
50.0 76.8 77.9 66.5 12.0 54.5 77.9 88.1 84.7 11.0
33.3 71.3 58.4 42.3 13.0 36.4 72.4 66.9 54.8 12.1
IPLV: 11.4 EER IPLV: 10.9 EER

YCAJ180 YCAJ190
% ENTERING % ENTERING
TONS KW EER TONS KW EER
DISPL. AIR °F DISPL. AIR °F
100.0 95.0 169.0 195.8 9.3 100.0 95.0 178.7 211.7 9.1
83.3 90.7 150.7 159.3 9.9 84.5 90.9 160.3 174.5 9.7
66.7 85.8 129.8 123.4 10.6 57.8 82.6 123.1 111.0 11.0
50.0 76.6 91.4 86.0 11.2 53.5 77.7 101.5 99.4 11.0
33.3 71.3 68.8 55.0 12.4 26.7 68.7 61.1 44.6 13.0
IPLV: 10.9 EER IPLV: 10.9 EER

Certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program, which is
based on ARI Standard 550/590-98.

32 YORK INTERNATIONAL
FORM 150.70-EG1

Ratings - Part Load (200 - 230 Tons) (English)

YCAJ200 YCAJ220
% ENTERING % ENTERING
TONS KW EER TONS KW EER
DISPL. AIR °F DISPL. AIR °F
100.0 95.0 193.9 227.4 9.1 100.0 95.0 207.1 250.5 8.9
75.0 87.9 159.3 160.7 10.0 77.2 88.3 172.4 183.2 9.7
50.0 79.6 119.4 98.7 11.2 50.0 79.6 127.8 110.7 10.9
50.0 76.6 105.0 98.3 11.1 54.4 77.8 118.4 120.2 10.5
25.0 67.8 62.3 43.9 12.7 27.2 68.7 71.1 56.3 12.0
IPLV: 10.7 EER IPLV: 10.4 EER

YCAJ230
% ENTERING
TONS KW EER
DISPL. AIR °F
100.0 95.0 220.4 273.4 8.7
75.0 87.9 181.2 195.4 9.7
50.0 79.7 136.1 122.7 10.7
50.0 76.6 119.0 119.2 10.7
25.0 67.9 71.3 56.0 12.1
IPLV: 10.3 EER

YCAJ200 is certified in accordance with the ARI Water-Chilling Packages using the Vapor Compression Cycle Certification Program,
which is based on ARI Standard 550/590-98.
YCAJ220 andYCAJ230 are outside the scope of ARI Standard 550/590-98.

KW = Compressor kW
EER = Unit EER
NOTE: Units must include the high ambient option above 115°F ambient. Contact Factory.

YORK INTERNATIONAL 33
Ratings - Part Load (176 - 317 kW) (SI)

YCAZ33BA3 YCAZ44BA3
% ENTERING UNIT COMPR % ENTERING UNIT COMPR
COP COP
DISPL. AIR °C KWo KWE DISPL. AIR °C KWo KWE
100.0 35.0 173.6 61.2 2.6 100.0 35.0 190.3 72.1 2.5
75.0 30.9 141.3 44.6 2.9 75.0 31.0 155.5 52.8 2.7
50.0 26.4 106.3 28.4 3.2 50.0 26.6 118.3 33.7 3.1
50.0 24.8 93.9 27.2 2.9 50.0 24.8 102.9 32.3 2.8
25.0 19.9 55.8 12.5 3.2 25.0 20.0 62.1 14.9 3.1
IPLV: 3.1 COP IPLV: 2.9 COP

YCAZ74BB3 YCAZ77CB3
% ENTERING UNIT COMPR % ENTERING UNIT COMPR
COP COP
DISPL. AIR °C KWo KWE DISPL. AIR °C KWo KWE
100.0 35.0 222.9 78.9 2.7 100.0 35.0 247.9 87.3 2.7
78.3 31.2 184.7 60.1 2.8 83.3 32.7 222.1 72.0 2.9
59.4 28.5 158.0 44.8 3.2 66.7 30.3 195.7 56.8 3.2
56.6 25.6 128.8 39.8 2.9 50.0 24.8 133.8 39.3 3.0
37.7 22.8 100.2 25.5 3.3 33.3 22.1 104.2 25.2 3.5
IPLV: 3.1 COP IPLV: 3.2 COP

YCAZ88DB3
% ENTERING UNIT COMPR
COP
DISPL. AIR °C KWo KWE
100.0 35.0 288.0 109.5 2.5
83.3 32.7 258.0 90.2 2.7
66.7 30.3 227.2 70.8 3.0
50.0 24.8 156.0 49.8 2.9
33.3 22.1 121.3 31.6 3.3
IPLV: 3.0 COP

34 YORK INTERNATIONAL
FORM 150.70-EG1

Ratings - Part Load (335 - 458 kW) (SI)

YCAZ88EE8 YCAJ110
% ENTERING UNIT COMPR % ENTERING UNIT COMPR
COP COP
DISPL. AIR °C KWo KWE DISPL. AIR °C KWo KWE
100.0 35.0 329.5 102.5 2.8 100.0 35.0 368.3 112.2 2.8
83.3 32.5 291.7 83.7 3.0 75.0 30.9 299.7 79.0 3.1
66.7 29.8 252.7 65.2 3.2 50.0 26.1 221.1 48.5 3.4
50.0 24.1 167.1 47.9 3.0 50.0 24.8 199.2 48.2 3.3
33.3 21.4 128.2 30.1 3.4 25.0 19.7 114.8 21.9 3.4
IPLV: 3.2 COP IPLV: 3.2 COP

YCAJ120 YCAJ130
% ENTERING UNIT COMPR % ENTERING UNIT COMPR
COP COP
DISPL. AIR °C KWo KWE DISPL. AIR °C KWo KWE
100.0 35.0 394.5 126.3 2.8 100.0 35.0 420.7 138.4 2.7
77.1 31.2 326.2 93.1 3.0 75.0 30.9 343.6 100.1 2.9
50.0 26.2 238.1 56.7 3.2 50.0 26.3 255.5 64.3 3.1
54.3 25.5 226.0 62.3 3.1 50.0 24.7 226.7 61.2 3.1
27.1 20.3 133.2 29.5 3.2 25.0 19.8 133.1 29.0 3.3
IPLV: 3.0 COP IPLV: 3.0 COP

YORK INTERNATIONAL 35
Ratings - Part Load (528 - 669 kW) (SI)

YCAJ150 YCAJ160
% ENTERING UNIT COMPR % ENTERING UNIT COMPR
COP COP
DISPL. AIR °C KWo KWE DISPL. AIR °C KWo KWE
100.0 35.0 502.9 153.6 2.9 100.0 35.0 540.0 173.0 2.8
83.3 32.6 448.6 124.5 3.0 84.8 32.8 485.0 143.6 2.9
66.7 29.9 386.7 96.1 3.2 66.7 30.1 420.0 108.3 3.2
50.0 24.9 273.9 66.5 3.5 54.5 25.5 310.0 84.7 3.2
33.3 21.8 205.4 42.3 3.8 36.4 22.4 235.1 54.8 3.5
IPLV: 3.4 COP IPLV: 3.2 COP

YCAJ180 YCAJ190
% ENTERING UNIT COMPR % ENTERING UNIT COMPR
COP COP
DISPL. AIR °C KWo KWE DISPL. AIR °C KWo KWE
100.0 35.0 594.3 195.8 2.7 100.0 35.0 628.5 211.7 2.7
83.3 32.6 529.8 159.3 2.9 84.5 32.7 564.0 174.5 2.9
66.7 29.9 456.6 123.4 3.1 57.8 28.1 433.1 111.0 3.2
50.0 24.8 321.6 86.0 3.3 53.5 25.5 359.1 98.6 3.3
33.3 21.8 242.0 55.0 3.6 26.7 20.4 214.9 44.6 3.8
IPLV: 3.2 COP IPLV: 3.2 COP

36 YORK INTERNATIONAL
FORM 150.70-EG1

Ratings - Part Load (704 - 810 kW) (SI)

YCAJ200 YCAJ220
% ENTERING UNIT COMPR % ENTERING UNIT COMPR
COP COP
DISPL. AIR °C KWo KWE DISPL. AIR °C KWo KWE
100.0 35.0 682.0 227.4 2.7 100.0 35.0 728.3 250.5 2.6
75.0 31.0 560.3 160.7 2.9 77.2 31.3 606.2 183.2 2.9
50.0 26.5 419.8 98.7 3.3 50.0 26.5 449.3 110.7 3.2
50.0 24.8 369.1 98.3 3.3 54.4 25.5 416.4 120.2 3.1
25.0 19.9 219.2 43.9 3.7 27.2 20.4 250.0 56.3 3.5
IPLV: 3.2 COP IPLV: 3.0 COP

YCAJ230
% ENTERING UNIT COMPR
COP
DISPL. AIR °C KWo KWE
100.0 35.0 775.3 273.4 2.6
75.0 31.0 637.1 195.4 2.8
50.0 26.5 478.8 122.7 3.1
50.0 24.8 418.6 119.2 3.1
25.0 20.0 250.7 56.0 3.5
IPLV: 3.0 COP

YORK INTERNATIONAL 37
Optional Remote DX Cooler (English)

OPTIONAL REMOTE DX COOLER DIMENSIONS

MODELS LENGTH SHELL DIA. HEIGHT WIDTH


E F G H I J K
YCA A B C D
Z33BA3 8'–11-13/16" 1'–3/16" 1'–4-1/2" 1'–4-1/4" 1'–3-1/2" 2-1/4" 2-1/4" 3-1/4" 4-1/8" 1-3/4" 1-3/4"
Z44BA3 8'–11-13/16" 1'–3/16" 1'–4-1/2" 1'–4-1/4" 1'–3-1/2" 2-1/4" 2-1/4" 3-1/4" 4-1/8" 1-3/4" 1-3/4"
Z74BB3 8'–11-13/16" 1'–3/16" 1'–4-1/2" 1'–4-1/4" 1'–3-1/2" 2-1/4" 2-1/4" 3-1/4" 4-1/8" 1-3/4" 1-3/4"
Z77CB3 8'–11-13/16" 1'–1-3/16" 1'–6-1/2" 1'–6-1/4" 1'–3-1/2" 2-1/2" 2-1/2" 3-5/8" 4-3/4" 1-3/4" 1-3/4"
Z88DB3 8'–11-15/16" 1'–3-7/16" 1'–7-3/4" 1'–7-1/2" 1'–3-1/2" 2-7/8" 2-7/8" 3-7/8" 5-1/8" 2-1/4" 2-1/4"
Z88EE8 8'–11-15/16" 1'–3-7/16" 1'–7-3/4" 1'–7-1/2" 1'–3-1/2" 2-7/8" 2-7/8" 3-7/8" 5-1/8" 2-1/4" 2-1/4"
J110 8'–11-15/16" 1'–3-7/16" 1'–9-3/4" 1'–9-1/2" 1'–3-1/2" 3-1/4" 3-1/4" 4-3/4" 6-1/8" 2-5/8" 2-5/8"
J120 9'–0-5/16" 1'–5-11/16" 1'–9-3/4" 1'–9-1/2" 1'–3-1/2" 3-1/4" 3-1/4" 4-3/4" 6-1/8" 2-5/8" 2-5/8"
J130 8'–11-15/16" 1'–3-7/16" 1'–9-3/4" 1'–9-1/2" 1'–3-1/2" 3-1/4" 3-1/4" 4-3/4" 6-1/8" 2-5/8" 2-5/8"
J150 9'–0-5/16" 1'–5-11/16" 1'–9-3/4" 1'–9-1/2" 1'–3-1/2" 3-1/4" 3-1/4" 4-3/4" 6-1/8" 2-5/8" 2-5/8"
J160 9'–1-3/4" 1'–6-1/8" 1'–9-3/4" 1'–9-1/2" 1'–3-1/2" 3-1/4" 3-1/4" 4-3/4" 6-1/8" 2-5/8" 2-5/8"
J180 9'–0-5/16" 1'–5-11/16" 1'–11-3/4" 1'–11-1/2" 1'–4" 4-1/4" 4-1/4" 5-1/2" 6-3/4" 3-1/4" 3-1/4"
J190 9'–0-5/16" 1'–5-11/16" 1'–11-3/4" 1'–11-1/2" 1'–4" 4-1/4" 4-1/4" 5-1/2" 6-3/4" 3-1/4" 3-1/4"
J200 9'–1-3/4" 1'–6-1/8" 2'–1-3/8" 2'–0-1/2" 1'–4-1/2" 4-1/4" 4-1/4" 5-3/8" 7-1/4" 3-1/4" 3-1/4"
J220 9'–1-3/4" 1'–6-1/8" 2'–1-3/8" 2'–0-1/2" 1'–4-1/2" 4-1/4" 4-1/4" 5-3/8" 7-1/4" 3-1/4" 3-1/4"
J230 9'–1-3/4" 1'–6-1/8" 2'–1-3/8" 2'–0-1/2" 1'–4-1/2" 4-1/4" 4-1/4" 5-3/8" 7-1/4" 3-1/4" 3-1/4"

SUCTION LINE LIQUID LINE CHILLED WATER SHIPPING OPERATING


MODELS
L DIA. IN O.D.F. DIA. IN. O.D.F. P INLET/OUTLET DIA. WEIGHT WEIGHT
YCA
M N Q (LBS.) (LBS.)
Z33BA3 8-3/8" (2) 2-1/8" (2) 1-1/8" 7' 2" 4" 785 1105
Z44BA3 8-3/8" (2) 2-1/8" (2) 1-1/8" 7' 2" 4" 785 1105
Z74BB3 8-3/8" (2) 2-1/8" (2) 1-1/8" 7' 2" 4" 785 1105
Z77CB3 9-3/8" (2) 2-5/8" (2) 1-3/8" 7' 6" 922 1150
Z88DB3 10" (2) 3-1/8" (2) 1-3/8" 7' 1" 6" 1103 1436
Z88EE8 10" (2) 3-1/8" (2) 1-3/8" 7' 1" 6" 1142 1475
J110 11" (2) 3-1/8" (2) 1-3/8" 6' 11" 6" 1552 1957
J120 11" (2) 3-1/8" (2) 1-3/8" 6' 11" 8" 1552 1957
J130 11" (2) 3-1/8" (2) 1-3/8" 6' 11" 6" 1552 1957
J150 11" (2) 3-1/8" (2) 2-1/8" 6' 11" 8" 1552 1957
J160 11" (2) 3-1/8" (2) 1-3/8" 6' 11" 8" 1552 1957
J180 1' (2) 3-5/8" (2) 1-3/8" 6' 11" 8" 1970 2427
J190 1' (2) 3-5/8" (2) 1-1/8" 6' 11" 8" 1970 2427
J200 1'–0-1/2" (2) 3-5/8" (2) 2-1/8" 6' 11" 8" 2268 2768
J220 1'–0-1/2" (2) 3-5/8" (2) 2-1/8" 6' 11" 8" 2268 2768
J230 1'–0-1/2" (2) 3-5/8" (2) 2-1/8" 6' 11" 8" 2268 2768

38 YORK INTERNATIONAL
FORM 150.70-EG1

LD01166

YORK INTERNATIONAL 39
Optional Remote DX Cooler (SI)

OPTIONAL REMOTE DX COOLER DIMENSIONS (mm)


MODELS LENGTH SHELL DIA. HEIGHT WIDTH
E F G H I J K
YCA A B C D
Z33BA3 2738 310 419 413 394 57 57 83 105 44 44
Z44BA3 2738 310 419 413 394 57 57 83 105 44 44
Z74BB3 2738 310 419 413 394 57 57 83 105 44 44
Z77CB3 2738 335 470 464 394 64 64 92 121 44 44
Z88DB3 2742 335 502 495 394 73 73 98 130 57 57
Z88EE8 2742 335 502 495 394 73 73 98 130 57 57
J110 2742 335 552 546 394 83 83 121 156 67 67
J120 2751 449 552 546 394 83 83 121 156 67 67
J130 2742 392 552 546 394 83 83 121 156 67 67
J150 2751 449 552 546 394 83 83 121 156 67 67
J160 2788 460 552 546 394 83 83 121 156 67 67
J180 2751 449 603 597 406 108 108 140 171 83 83
J190 2751 449 603 597 406 108 108 140 171 83 83
J200 2788 460 645 622 419 108 108 137 184 83 83
J220 2788 460 645 622 419 108 108 137 184 83 83
J230 2788 460 645 622 419 108 108 137 184 83 83

SUCTION LINE LIQUID LINE CHILLED WATER SHIPPING OPERATING


MODELS
L DIA. mm O.D.F. DIA. mm O.D.F. P INLET/OUTLET DIA. WEIGHT WEIGHT
YCA
M N Q (Kg) (Kg)
Z33BA3 213 54 29 2184 4" 356 501
Z44BA3 213 54 29 2184 4" 356 501
Z74BB3 213 54 29 2184 4" 356 501
Z77CB3 238 67 35 2134 6" 418 522
Z88DB3 254 79 35 2159 6" 500 651
Z88EE8 254 79 35 2159 6" 518 669
J110 279 79 35 2108 6" 704 888
J120 279 79 35 2108 8" 704 888
J130 279 79 35 2108 6" 704 888
J150 279 79 54 2108 8" 704 888
J160 279 79 35 2108 8" 704 888
J180 305 92 35 2108 8" 894 1101
J190 305 92 29 2108 8" 894 1101
J200 318 92 54 2108 8" 1029 1256
J220 318 92 54 2108 8" 1029 1256
J230 318 92 54 2108 8" 1029 1256

40 YORK INTERNATIONAL
FORM 150.70-EG1

LD01316

YORK INTERNATIONAL 41
Physical Data (50 - 90 Tons [176 - 317 kW]) (English & SI)
(ENGLISH)
MODEL
60 HZ Z33BA3 Z44BA3 Z74BB3 Z77CB3 Z88DB3
YCA
NOMINAL CAPACITY (TONS) 47.7 53.5 63.1 70.5 81.9
NO. OF REFRIG. CIRCUITS 2 2 2 2 2
ACCESSIBLE (2) ZB4K-B (2) ZB4M-C (1) ZB6S-D (2) ZB6S-D (2) ZB6W-E
HERMETIC (35 HP) (45 HP) (55 HP) (55 HP) (65 HP)
COMPRESSOR MODEL (1) ZB4M-C
(COMPRESSOR HP) (45 HP)
STANDARD 5 Steps 5 Steps 5 Steps 5 Steps 5 Steps
UNIT CAPACITY CONTROL
OPTIONAL N/A N/A 6 Steps 7 Steps 7 Steps
CONDENSER – DWP 450 PSIG
2 2 2 2 2
NO. OF FANS (42"Dia. Direct Drive)
HP/kW Each 850 RPM 3/2.5 3/2.5 3/2.5 3/2.5 3/2.5
AIRFLOW TOTAL (CFM) 30,300 30,300 34,400 34,400 34,400
COOLER – DUAL CIRCUITED
DWP – 235 PSIG REF. SIDE,
11" x 8' 11" x 8' 11" x 8' 12" x 8' 14" x 8'
150 PSIG WATER SIDE
DIA. X LENGTH
WATER VOLUME (GALS.) 24 24 24 27 41
MIN. 75 75 75 90 130
GPM
MAX. 250 250 250 315 390
Alum. Fins 4800 5150 5350 5700 5750
SHIPPING
Copper Fins 5450 5800 6200 6500 6600
WEIGHT (LBS.)
Alum. Fins 5000 5350 5550 5900 6150
OPERATING
Copper Fins 5650 6000 6400 6750 7000
Sys. 1 42 50 56 56 65
REFRIG. CHARGE (LBS. R-22)
Sys. 2 42 50 50 56 65

(SI)
MODEL
60 HZ Z33BA3 Z44BA3 Z74BB3 Z77CB3 Z88DB3
YCA
NOMINAL CAPACITY (KW) 173.6 190.3 222.9 247.9 288.0
NO. OF REFRIG. CIRCUITS 2 2 2 2 2
ACCESSIBLE (2) ZB4K-B (2) ZB4M-C (1) ZB6S-D (2) ZB6S-D (2) ZB6W-E
HERMETIC (26 KW) (33 KW) (41 KW) (41 KW) (48 KW)
COMPRESSOR MODEL (1) ZB4M-C
(COMPRESSOR KW) (33 KW)
STANDARD 5 Steps 5 Steps 5 Steps 5 Steps 5 Steps
UNIT CAPACITY CONTROL
OPTIONAL N/A N/A 6 Steps 7 Steps 7 Steps
CONDENSER – DWP 3 kPa
2 2 2 2 2
NO. OF FANS (1066 mm Dia. Direct Drive)
HP/kW Each 850 RPM 3/2.5 3/2.5 3/2.5 3/2.5 3/2.5
AIRFLOW TOTAL (L/S) 14,300 14,300 16,235 16,235 16,235
COOLER – DUAL CIRCUITED
279 mm 279 mm 279 mm 305 mm 356 mm
DWP – 1.62 kPa REF. SIDE,
x x x x x
1.0 kPa WATER SIDE
2438 mm 2438 mm 2438 mm 2438 mm 2438 mm
DIA. X LENGTH
WATER VOLUME (L) 91 91 91 102 155
MIN. 4.7 4.7 4.7 5.7 8.2
L/SEC.
MAX. 15.8 15.8 15.8 19.9 24.6
Alum. Fins 2177 2336 2427 2586 2608
SHIPPING
Copper Fins 2472 2631 2812 2948 2994
WEIGHT (Kg)
Alum. Fins 2268 2427 2517 2676 2790
OPERATING
Copper Fins 2563 2722 2903 3062 3175
Sys. 1 19 23 25 25 30
REFRIG. CHARGE (Kg. R-22)
Sys. 2 19 23 23 25 30

42 YORK INTERNATIONAL
FORM 150.70-EG1

Physical Data (95 - 130 Tons [335 - 458 kW]) (English & SI)

(ENGLISH)
MODEL
60 HZ Z88EE8 J110 J120 J130
YCA
NOMINAL CAPACITY (TONS) 93.7 104.7 112.2 119.6
NO. OF REFRIG. CIRCUITS 2 2 2 2
ZB6W-E JG43-M JG44-P JG44-P
SYS. 1
COMPRESSOR MODEL (65 HP) (60 HP) (80 HP) (80 HP)
& MOTOR HORSEPOWER ZB6W-E JG43-M JG43-M JG44-P
SYS. 2
(65) (60 HP) (45 HP) (80 HP)

UNIT CAPACITY CONTROL 5 Steps 5 Steps 5 Steps 5 Steps

CONDENSER – DWP 450 PSIG


4 6 6 6
NO. OF FANS (42"Dia. Direct Drive)
HP/kW Each 1140 RPM 5/3.7 5/2.9 5/2.9 5/2.9
TOTAL AIRFLOW (CFM) 71,600 88,533 88,533 88,533
COOLER – DUAL CIRCUITED
DWP – 235 PSIG REF. SIDE,
14" x 8' 16" x 8' 16" x 8' 16" x 8'
150 PSIG WATER SIDE
DIA. X LENGTH
WATER VOLUME (GALS.) 38 48 48 48
MIN. 120 150 150 150
GPM
MAX. 430 640 640 640
Alum. Fins 8,700 11,489 11,539 11,639
SHIPPING
Copper Fins 10,250 13,197 13,297 13,447
WEIGHT (LBS.)
Alum. Fins 9,050 11,889 11,989 12,089
OPERATING
Copper Fins 10,600 13,597 13,747 13,897
Sys. 1 71 108 115 125
REFRIG. CHARGE (LBS. R-22)
Sys. 2 71 121 128 140

(SI)
MODEL
60 HZ Z88EE8 J110 J120 J130
YCA
NOMINAL CAPACITY (KW) 329.5 368.3 394.5 420.7
NO. OF REFRIG. CIRCUITS 2 2 2 2
ZB6W-E JG43-M JG44-P JG44-P
SYS. 1
COMPRESSOR MODEL (48 KW) (44 KW) (59 KW) (59 KW)
& MOTOR KW ZB6W-E JG43-M JG43-M JG44-P
SYS. 2
(48 kW) (44 kW) (33 kW) (59 kW)

UNIT CAPACITY CONTROL 5 Steps 5 Steps 5 Steps 5 Steps

CONDENSER – DWP 3 kPa


4 6 6 6
NO. OF FANS (1066 mm Dia. Direct Drive)
HP/kW Each 1140 RPM 5/3.7 5/2.9 5/2.9 5/2.9
AIRFLOW TOTAL (L/S) 33,791 41,783 41,783 41,783
COOLER – DUAL CIRCUITED
356 mm 406 mm 406 mm 406 mm
DWP – 1.62 kPa REF. SIDE,
x x x x
1.0 kPa WATER SIDE
2438 mm 2438 mm 2438 mm 2438 mm
DIA. X LENGTH
WATER VOLUME (L) 144 182 182 182
MIN. 7.6 9.5 9.5 9.5
L/SEC.
MAX. 27.1 40.4 40.4 40.4
Alum. Fins 3946 5211 5234 5079
SHIPPING
Copper Fins 4649 5986 6031 6099
WEIGHT (Kg)
Alum. Fins 4105 5393 5438 5483
OPERATING
Copper Fins 4808 6167 6236 6304
Sys. 1 32 49 52 57
REFRIG. CHARGE (Kg R-22)
Sys. 2 32 55 58 64

YORK INTERNATIONAL 43
Physical Data (150 - 230 Tons [528 - 810 kW]) (English & SI)
(ENGLISH)
MODEL
60 HZ J150 J160 J180 J190 J200 J220 J230
YCA
NOMINAL CAPACITY (TONS) 143.0 153.5 169.0 178.7 193.4 207.1 220.4
NO. OF REFRIG. CIRCUITS 2 2 2 2 2 2 2
JG63-Q JG64-S JG64-S JG83-S JG83-S JG84-V JG84-V
SYS. 1
COMPRESSOR MODEL (90 HP) (115 HP) (115 HP) (115 HP) (115 HP) (160 HP) (160 HP)
& MOTOR HORSEPOWER JG63-Q JG63-Q JG64-S JG64-S JG83-S JG83-S JG84-V
SYS. 2
(90 HP) (90 HP) (115 HP) (115 HP) (115 HP) (115 HP) (160 HP)
STANDARD 5 Steps 5 Steps 5 Steps 5 Steps 5 Steps 5 Steps 5 Steps
UNIT CAPACITY CONTROL
OPTIONAL 7 Steps 7 Steps 7 Steps 7 Steps 7 Steps 7 Steps 7 Steps
CONDENSER – DWP 450 PSIG
8 8 8 8 8 8 8
NO. OF FANS (36"Dia. Direct Drive)
HP/kW Each 1140 RPM 3/2.9 3/2.9 3/2.9 3/2.9 5/3.7 5/3.7 5/3.7
AIRFLOW TOTAL (CFM) 124,000 124,000 124,000 124,000 143,000 143,000 143,000
COOLER – DUAL CIRCUITED
DWP – 235 PSIG REF. SIDE,
16" x 8' 16" x 8' 18" x 8' 18" x 8' 20" x 8' 20" x 8' 20" x 8'
150 PSIG WATER SIDE
DIA. X LENGTH
WATER VOLUME (GALS.) 48 48 59 59 66 66 66
MIN. 150 150 200 200 250 250 250
GPM
MAX. 640 640 722 722 803 803 803
Alum. Fins 14,818 15,509 16,400 16,400 17,400 17,562 17,774
SHIPPING
Copper Fins 17,268 17,959 18,850 18,850 20,500 20,712 20,874
WEIGHT (LBS.)
Alum. Fins 15,218 15,909 16,900 16,950 17,950 18,162 18,324
OPERATING
Copper Fins 17,668 18,359 19,350 19,400 21,100 21,262 21,474
Sys. 1 129 139 141 156 156 163 163
REFRIG. CHARGE (LBS. R-22)
Sys. 2 163 163 173 173 175 175 181

(SI)
MODEL
60 HZ J150 J160 J180 J190 J200 J220 J230
YCA
NOMINAL CAPACITY (KW) 502.9 540.0 594.3 628.5 682.0 728.3 775.3
NO. OF REFRIG. CIRCUITS 2 2 2 2 2 2 2
JG63-Q JG64-S JG64-S JG83-S JG83-S JG84-V JG84-V
SYS. 1
COMPRESSOR MODEL (67 kW) (85 kW) (85 kW) (85 kW) (85 kW) (119 kW) (119 kW)
& MOTOR KW JG63-Q JG63-Q JG64-S JG83-S JG83-S JG83-S JG84-V
SYS. 2
(67 kW) (67 kW) (85 kW) (85 kW) (85 kW) (85 kW) (119 kW)
STANDARD 5 Steps 5 Steps 5 Steps 5 Steps 5 Steps 5 Steps 5 Steps
UNIT CAPACITY CONTROL
OPTIONAL 7 Steps 7 Steps 7 Steps 7 Steps 7 Steps 7 Steps 7 Steps
CONDENSER – DWP 450 PSIG
8 8 8 8 8 8 8
NO. OF FANS (914 mm Dia. Direct Drive)
HP/kW Each 1140 RPM 3/2.9 3/2.9 3/2.9 3/2.9 5/3.7 5/3.7 5/3.7
AIRFLOW TOTAL (L/S) 58,522 58,522 58,522 58,522 67,489 67,489 67,489
COOLER – DUAL CIRCUITED
406 mm 406 mm 457 mm 457 mm 508 mm 508 mm 508 mm
DWP – 1.62 kPa REF. SIDE,
x x x x x x x
1.0 kPa WATER SIDE
2438 mm 2438 mm 2438 mm 2438 mm 2438 mm 2438 mm 2438 mm
DIA. X LENGTH
WATER VOLUME (L) 182 182 223 223 250 250 250
MIN. 9.4 9.4 12.6 12.6 15.8 15.8 15.8
L/SEC.
MAX. 40.4 40.4 45.5 45.5 50.7 50.7 50.7
Alum. Fins 6721 7035 7439 7439 7893 7966 8062
SHIPPING
Copper Fins 7833 8146 8550 8550 9299 9395 9468
WEIGHT (LBS.)
Alum. Fins 6903 7216 7666 7688 8142 8238 8312
OPERATING
Copper Fins 8014 8328 8777 8800 9571 9644 9740
Sys. 1 52 56 56 63 63 66 66
REFRIG. CHARGE (Kg R-22)
Sys. 2 52 60 64 64 71 71 75

44 YORK INTERNATIONAL
FORM 150.70-EG1

Dimensions (Unit Isolator Selection) (English & SI)

LD01089

VMC CP-2-X

NOTE: Standard 1" deflection isolator drawings. Consult your nearest YORK representative for additional isolator options.

ISOLATOR LOCATIONS (50 - 90 TONS [176 - 317 kW])


MODEL A B C D
YCAZ33BA3 CP-2-25 CP-2-25 CP-2-28 CP-2-28
YCAZ44BA3 CP-2-25 CP-2-25 CP-2-31 CP-2-31
YCAZ74BB3 CP-2-26 CP-2-26 CP-2-31 CP-2-31
YCAZ77CB3 CP-2-26 CP-2-26 CP-2-31 CP-2-31
YCAZ88DB3 CP-2-26 CP-2-26 CP-2-31 CP-2-31

ISOLATOR LOCATIONS (95 - 130 TONS [335 - 458 kW])


MODEL A B C D E F
YCAZ88EE8 CP-2-32 CP-2-31 CP-2-32 CP-2-31 N/A N/A
YCAJ110 CP-2-28 CP-2-31 CP-2-32 CP-2-28 CP-2-31 CP-2-32
YCAJ120 CP-2-28 CP-2-31 CP-2-32 CP-2-28 CP-2-31 CP-2-32
YCAJ130 CP-2-28 CP-2-31 CP-2-32 CP-2-28 CP-2-31 CP-2-32

ISOLATOR LOCATIONS (150 - 230 TONS [528 - 810 kW])


MODEL A B C D E F G H
YCAJ150 CP-2-28 CP-2-31 CP-2-31 CP-2-31 CP-2-28 CP-2-31 CP-2-31 CP-2-31
YCAJ160 CP-2-31 CP-2-31 CP-2-31 CP-2-32 CP-2-31 CP-2-31 CP-2-31 CP-2-31
YCAJ180 CP-2-31 CP-2-31 CP-2-31 CP-2-32 CP-2-31 CP-2-31 CP-2-31 CP-2-32
YCAJ190 CP-2-31 CP-2-31 CP-2-31 CP-2-32 CP-2-31 CP-2-31 CP-2-31 CP-2-32
YCAJ200 CP-2-31 CP-2-31 CP-2-31 CP-2-32 CP-2-31 CP-2-31 CP-2-31 CP-2-32
YCAJ220 CP-2-31 CP-2-31 CP-2-31 CP-2-32 CP-2-31 CP-2-31 CP-2-31 CP-2-32
YCAJ230 CP-2-31 CP-2-31 CP-2-31 CP-2-32 CP-2-31 CP-2-31 CP-2-31 CP-2-32

YORK INTERNATIONAL 45
Dimensions (50 - 90 Tons) (English)

LD01177

CHILLER Y X
Z33BA3 7'–2" 1'–2-1/8"
Z44BA3 7'–2" 1'–2-1/8"
Z74BB3 7'–2" 1'–2-1/8"
Z77CB3 7'–0" 1'–3-1/8"
Z88DB3 7'–1" 1'–3-3/4"

NOTES:
1. Clearances – Recommended YORK clearances for peak performance, reliable operation, and maintenance:
Side to wall – 8'; Rear to wall – 8'; Control panel end to wall – 5'; Over the top – no obstructions allowed; Two units side by side – 12',
(walls should be no higher than the unit). The area within the clearances and under the unit(s) must be kept clean of clutter. Additional height
should be included to allow for snow accumulation for units which are expected to operate at full load during the winter. Reduced clearances
may be used due to jobsite restrictions. The unit(s) with optional controls will allow optimal operation preventing the condenser pressure from
exceeding the maximum limit. The units will continue to operate without nuisance high pressure cutout even though the airflow may be
restricted at these conditions.

2. Panel bottom to be punched in field to accommodate power wiring conduit.


3. Use of isolators (optional) will increase height of unit approximately 6".
4. Drawings not to scale and are for planning purposes only. Contact nearest YORK Sales Office for detailed drawings.

See page 45 for 50 - 90 Ton Unit Isolator Selection.

46 YORK INTERNATIONAL
FORM 150.70-EG1

LD01179 LD01178

LD01176

WATER
WEIGHT DISTRIBUTION (LBS.)
CONN.
MODEL YCA
INLET/OUTLET
A B C D
DIA. (INCHES)
Z33BA3 791 791 1707 1707 4
Z44BA3 858 858 1811 1811 4
Z74BB3 931 931 1948 1948 4
Z77CB3 935 935 2011 2011 6
Z88DB3 977 977 2079 2079 6

YORK INTERNATIONAL 47
Dimensions (176 - 317 kW) (SI)

LD01181

NOTE: SI Unit dimensions are in mm unless otherwise noted.

CHILLER X Y
Z33BA3 2184 mm 359 mm
Z44BA3 2184 mm 359 mm
Z74BB3 2184 mm 359 mm
Z77CB3 2134 mm 384 mm
Z88DB3 2159 mm 400 mm

NOTES:
1. Clearances – Recommended YORK clearances for peak performance, reliable operation, and maintenance:
Side to wall – 2440 mm; Rear to wall – 2440 mm; Control panel end to wall – 1525 mm; Over the top – no obstructions allowed; Two units
side by side – 3660 mm, (walls should be no higher than the unit). The area within the clearances and under the unit(s) must be kept clean
of clutter. Additional height should be included to allow for snow accumulation for units which are expected to operate at full load during the
winter. Reduced clearances may be used due to jobsite restrictions. The unit(s) with optional controls will allow optimal operation preventing
the condenser pressure from exceeding the maximum limit. The units will continue to operate without nuisance high pressure cutout even
though the airflow may be restricted at these conditions.

2. Panel bottom to be punched in field to accommodate power wiring conduit.


3. Use of isolators (optional) will increase height of unit approximately 152 mm.
4. Drawings not to scale and are for planning purposes only. Contact nearest YORK Sales Office for detailed drawings.

See page 45 for 176 - 317 kW Unit Isolator Selection.

48 YORK INTERNATIONAL
FORM 150.70-EG1

LD01183 LD01182

LD01180

NOTE: SI Unit dimensions are in mm unless otherwise noted.

WATER
WEIGHT DISTRIBUTION (Kg)
CONN.
MODEL YCA
INLET/OUTLET
A B C D
DIA. (INCHES)
Z33BA3 359 359 774 774 4
Z44BA3 389 389 536 536 4
Z74BB3 422 422 884 884 4
Z77CB3 424 424 912 912 6
Z88DB3 443 443 943 943 6

YORK INTERNATIONAL 49
Dimensions (95 Ton) (English)

LD01185

NOTES:
1. Clearances – Recommended YORK clearances for peak performance, reliable operation, and maintenance:
Side to wall – 8'; Rear to wall – 8'; Control panel end to wall – 5'; Over the top – no obstructions allowed; Two units side by side – 12',
(walls should be no higher than the unit). The area within the clearances and under the unit(s) must be kept clean of clutter. Additional height
should be included to allow for snow accumulation for units which are expected to operate at full load during the winter. Reduced clearances
may be used due to jobsite restrictions. The unit(s) with optional controls will allow optimal operation preventing the condenser pressure from
exceeding the maximum limit. The units will continue to operate without nuisance high pressure cutout even though the airflow may be
restricted at these conditions.

2. Panel bottom to be punched in field to accommodate power wiring conduit.


3. Use of isolators (optional) will increase height of unit approximately 6".
4. Drawings not to scale and are for planning purposes only. Contact nearest YORK Sales Office for detailed drawings.

See page 45 for 95 Ton Unit Isolator Selection.

50 YORK INTERNATIONAL
FORM 150.70-EG1

LD01187

LD01186

LD01184

WATER
WEIGHT DISTRIBUTION (LBS.)
CONN.
MODEL YCA
INLET/OUTLET
A B C D
DIA. (INCHES)
Z88EE8 2337 2059 2246 2031 6

YORK INTERNATIONAL 51
Dimensions (335 kW) (SI)

LD01189

NOTE: SI Unit dimensions are in mm unless otherwise noted.

NOTES:
1. Clearances – Recommended YORK clearances for peak performance, reliable operation, and maintenance:
Side to wall – 2440 mm; Rear to wall – 2440 mm; Control panel end to wall – 1525 mm; Over the top – no obstructions allowed; Two units
side by side – 3660 mm, (walls should be no higher than the unit). The area within the clearances and under the unit(s) must be kept clean
of clutter. Additional height should be included to allow for snow accumulation for units which are expected to operate at full load during the
winter. Reduced clearances may be used due to jobsite restrictions. The unit(s) with optional controls will allow optimal operation preventing
the condenser pressure from exceeding the maximum limit. The units will continue to operate without nuisance high pressure cutout even
though the airflow may be restricted at these conditions.

2. Panel bottom to be punched in field to accommodate power wiring conduit.


3. Use of isolators (optional) will increase height of unit approximately 152 mm.
4. Drawings not to scale and are for planning purposes only. Contact nearest YORK Sales Office for detailed drawings.

See page 45 for 335 kW Unit Isolator Selection.

52 YORK INTERNATIONAL
FORM 150.70-EG1

LD01190

LD1191

LD01188

NOTE: SI Unit dimensions are in mm unless otherwise noted.

WATER
WEIGHT DISTRIBUTION (Kg)
CONN.
MODEL YCA
INLET/OUTLET
A B C D
DIA. (INCHES)
Z88EE8 1060 934 1019 921 6

YORK INTERNATIONAL 53
Dimensions (110 - 130 Ton) (English)

LD01337

NOTES:
1. Clearances – Recommended YORK clearances for peak performance, reliable operation, and maintenance:
Side to wall – 8'; Rear to wall – 8'; Control panel end to wall – 5'; Over the top – no obstructions allowed; Two units side by side – 12',
(walls should be no higher than the unit). The area within the clearances and under the unit(s) must be kept clean of clutter. Additional height
should be included to allow for snow accumulation for units which are expected to operate at full load during the winter. Reduced clearances
may be used due to jobsite restrictions. The unit(s) with optional controls will allow optimal operation preventing the condenser pressure from
exceeding the maximum limit. The units will continue to operate without nuisance high pressure cutout even though the airflow may be
restricted at these conditions.

2. Panel bottom to be punched in field to accommodate power wiring conduit.


3. Use of isolators (optional) will increase height of unit approximately 6".
4. Drawings not to scale and are for planning purposes only. Contact nearest YORK Sales Office for detailed drawings.

See page 45 for 110 - 130 Ton Unit Isolator Selection.

54 YORK INTERNATIONAL
FORM 150.70-EG1

LD01334

LD01335

LD01336

WATER
WEIGHT DISTRIBUTION (LBS.)
CONN.
MODEL YCA
INLET/OUTLET
A B C D E F
DIA. (INCHES)
J110 1559 1936 2312 1544 1917 2290 8
J120 1559 1936 2312 1544 1917 2290 8
J130 1559 1936 2312 1544 1917 2290 8

YORK INTERNATIONAL 55
Dimensions (387 - 458 kW) (SI)

LD01333
NOTE: SI Unit dimensions are in mm unless otherwise noted.

NOTES:
1. Clearances – Recommended YORK clearances for peak performance, reliable operation, and maintenance:
Side to wall – 2440 mm; Rear to wall – 2440 mm; Control panel end to wall – 1525 mm; Over the top – no obstructions allowed; Two units
side by side – 3660 mm, (walls should be no higher than the unit). The area within the clearances and under the unit(s) must be kept clean
of clutter. Additional height should be included to allow for snow accumulation for units which are expected to operate at full load during the
winter. Reduced clearances may be used due to jobsite restrictions. The unit(s) with optional controls will allow optimal operation preventing
the condenser pressure from exceeding the maximum limit. The units will continue to operate without nuisance high pressure cutout even
though the airflow may be restricted at these conditions.

2. Panel bottom to be punched in field to accommodate power wiring conduit.


3. Use of isolators (optional) will increase height of unit approximately 152 mm.
4. Drawings not to scale and are for planning purposes only. Contact nearest YORK Sales Office for detailed drawings.

See page 45 for 387 - 458 kW Unit Isolator Selection.

56 YORK INTERNATIONAL
FORM 150.70-EG1

LD01330

LD01331

LD01332
NOTE: SI Unit dimensions are in mm unless otherwise noted.

WATER
WEIGHT DISTRIBUTION (Kg)
CONN.
MODEL YCA
INLET/OUTLET
A B C D E F
DIA. (INCHES)
J110 707 878 1049 700 870 1039 8
J120 707 878 1049 700 870 1039 8
J130 707 878 1049 700 870 1039 8

YORK INTERNATIONAL 57
Dimensions (150 - 230 Tons) (English)

LD01193

CHILLER X
J150 1'–5"
J160 1'–5"
J180 1'–6"
J190 1'–6"
J200 1'–6-1/2"
J220 1'–6-1/2"
J230 1'–6-1/2"

NOTES:
1. Clearances – Recommended YORK clearances for peak performance, reliable operation, and maintenance:
Side to wall – 8'; Rear to wall – 8'; Control panel end to wall – 5'; Over the top – no obstructions allowed; Two units side by side – 12',
(walls should be no higher than the unit). The area within the clearances and under the unit(s) must be kept clean of clutter. Additional height
should be included to allow for snow accumulation for units which are expected to operate at full load during the winter. Reduced clearances
may be used due to jobsite restrictions. The unit(s) with optional controls will allow optimal operation preventing the condenser pressure from
exceeding the maximum limit. The units will continue to operate without nuisance high pressure cutout even though the airflow may be
restricted at these conditions.

2. Panel bottom to be punched in field to accommodate power wiring conduit.


3. Use of isolators (optional) will increase height of unit approximately 6".
4. Drawings not to scale and are for planning purposes only. Contact nearest YORK Sales Office for detailed drawings.

See page 45 for 150 - 230 Ton Unit Isolator Selection.

58 YORK INTERNATIONAL
FORM 150.70-EG1

LD01195 LD01194

LD01192

WATER
WEIGHT DISTRIBUTION (LBS.)
CONN.
MODEL YCA
INLET/OUTLET
A B C D E F G H
DIA. (INCHES)
J150 1791 1813 1843 2130 1738 1872 1893 2011 8
J160 1883 1915 1951 2228 1804 1948 1976 2089 8
J180 1939 1984 2000 2265 1979 2181 2197 2252 8
J190 1939 1984 2002 2272 1979 2181 2199 2259 8
J200 2025 2078 2093 2366 2125 2361 2377 2419 8
J220 2025 2078 2093 2366 2125 2361 2377 2419 8
J230 2094 2147 2163 2441 2156 2393 2435 2461 8

YORK INTERNATIONAL 59
Dimensions (528 - 810 kW) (SI)

LD01197

NOTE: SI Unit dimensions are in mm unless otherwise noted.

CHILLER X
J150 432 mm
J160 432 mm
J180 457 mm
J190 457 mm
J200 470 mm
J220 470 mm
J230 470 mm

NOTES:
1. Clearances – Recommended YORK clearances for peak performance, reliable operation, and maintenance:
Side to wall – 2440 mm; Rear to wall – 2440 mm; Control panel end to wall – 1525 mm; Over the top – no obstructions allowed; Two units
side by side – 3660 mm, (walls should be no higher than the unit). The area within the clearances and under the unit(s) must be kept clean
of clutter. Additional height should be included to allow for snow accumulation for units which are expected to operate at full load during the
winter. Reduced clearances may be used due to jobsite restrictions. The unit(s) with optional controls will allow optimal operation preventing
the condenser pressure from exceeding the maximum limit. The units will continue to operate without nuisance high pressure cutout even
though the airflow may be restricted at these conditions.
2. Cooler liquid connection sizes (inlet & outlet) 203 mm victaulic for all models.
3. Drawings not to scale and are for planning purposes only. Contact nearest YORK Sales Office for detailed drawings.
4. Spring isolator (optional) will increase height of unit by approximately 152 mm.
5. Modules have 29 mm space between to facilitate maintenance.

See page 45 for 528 - 810 kW Unit Isolator Selection.

60 YORK INTERNATIONAL
FORM 150.70-EG1

LD01198

LD01199

LD01196

NOTE: SI Unit dimensions are in mm unless otherwise noted.

WATER
WEIGHT DISTRIBUTION (Kg)
CONN.
MODEL YCA
INLET/OUTLET
A B C D E F G H
DIA. (INCHES)
J150 812 822 836 966 788 849 859 912 8
J160 854 869 885 1011 818 884 896 948 8
J180 880 900 907 1027 898 989 997 1021 8
J190 880 900 908 1031 898 989 997 1025 8
J200 919 943 949 1073 964 1071 1078 1097 8
J220 919 943 949 1073 964 1071 1078 1097 8
J230 950 974 981 1107 978 1085 1104 1116 8

YORK INTERNATIONAL 61
Electrical Data (50 - 90 Ton [176 - 317 kW])

UNIT POWER WIRING INCOMING WIRING RANGES SYSTEM 1 COMPR.


MODEL DUAL ELEM MAX SIZE
DISCONNECT CKT BKR PW ACL YORK SUPPLIED NON-FUSED ACL/ PW/
YCA MCA1 FUSE SIZE RLA
MINIMUM4 HACR START START DISCONNECT (OPTIONAL)8 LRA LRA
MIN.2 MAX.3 TYPE5
Z33BA3 -17 274 350 350 400 350 (2)#4-250MCM N/A (1)#1-600MCM OR (2)#1-250MCM 112 582 368
Z33BA3 -28 240 300 300 400 300 (2)#4-250MCM N/A (1)#6-350MCM 97 506 320
Z33BA3 -46 123 150 150 200 150 (2)#4-250MCM (2)#4-250MCM (1)#6-350MCM 48.5 253 160
Z33BA3 -58 99 110 125 200 125 (2)#4-250MCM (2)#4-250MCM (1)#6 350MCM 38.8 202 128
Z44BA3 -17 319 350 450 400 450 (2)#4-250MCM N/A (1)#1-600MCM OR (2)#1-250MCM 132 674 414
Z44BA3 -28 278 350 350 400 350 (2)#4-250MCM N/A (1)#1-600MCM OR (2)#1-250MCM 114 586 360
Z44BA3 -46 142 175 175 200 175 (2)#4-250MCM (2)#4-250MCM (1)#6-350MCM 57 293 180
Z44BA3 -58 114 125 150 200 150 (2)#4-250MCM (2)#4-250MCM (1)#6-350MCM 45.6 234 144
Z74BB3 -17 352 400 500 400 500 (2)#4-250MCM N/A (1)#1-600MCM OR (2)#1-250MCM 159 835 683
Z74BB3 -28 308 350 400 400 400 (2)#4-250MCM N/A (1)#1-600MCM OR (2)#1-250MCM 138 726 594
Z74BB3 -46 157 175 200 200 200 (2)#4-250MCM (2)#4-250MCM (1)#6-350MCM 69 363 297
Z74BB3 -58 126 150 175 200 175 (2)#4-250MCM (2)#4-250MCM (1)#6-350MCM 55 299 245
Z77CB3 -17 379 450 500 400 500 (2)#4-250MCM N/A (1)#1-600MCM OR (2)#1-250MCM 159 835 683
Z77CB3 -28 332 400 450 400 450 (2)#4-250MCM N/A (1)#1-600MCM OR (2)#1-250MCM 138 726 94
Z77CB3 -46 169 200 225 200 225 (2)#4-250MCM (2)#4-250MCM (1)#6-350MCM 69 363 297
Z77CB3 -58 135 150 175 200 175 (2)#4-250MCM (2)#4-250MCM (1)#6-35oMCM 55 299 245
Z88DB3 -17 467 600 600 600 600 (2)#4-250MCM N/A (2)#4/0-500MCM 198 1072 858
Z88DB3 -28 409 450 500 600 500 (2)#4-250MCM N/A (2)#4/0-500MCM 172 932 746
Z88DB3 -46 208 250 250 400 250 (2)#4-250MCM (2)#4-250MCM (1)#6-350MCM 86 466 373
Z88DB3 -58 167 200 225 200 225 (2)#4-250MCM (2)#4-250MCM (1)#6-350MCM 68.8 380 304

NOTES for Electrical Data, pages 62 - 71:

1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all
other loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to the
system #1 MCA values in the YCA Tables: -17, add 10 amps; -28, add 9 amps; -40, add 5 amps; -46, add 4 amps; -58, add 3 amps.
2. Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLA’s (U.L. Standard 1995, Section 36.1).
3. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit,
per N.E.C. 440-22.
4. The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the
circuit, per N.E.C. 440-12A1.
5. Maximum HACR is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per U.L.
1995 Fig. 36.2.
6. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2) or (3)
indicated the number of termination points which are available per phase. Actual wire size and number of wires per phase must be
determined based on ampacity and job requirements using N.E.C. wire sizing information. The above recommendations are based on the
National Electric Code and using copper connectors only. Field wiring must also comply with local codes.
7. A ground lug is provided for each compr. system to accommodate field grounding conductor per N.E.C. Article 250-54. A control circuit
grounding lug is also supplied. Incoming ground wire range is #6 - #2/0 (50 - 90 Tons)(176 - 317 kW) or #6 - 350 MCM (95 - 230 Tons)(334
- 810 kW).
8. The supplied disconnect is a “Disconnecting Means” as defined in N.E.C. 100.B, and is intended for isolating the unit from the available
power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
9. All unit compressors have a part winding electrical configuration such that the indicated Locked Rotor Amps are Part Wind Locked Rotor
Amps.
a. 50 - 90 Tons (176 - 317 kW) available as part winding start or across-the-line start
b. 95 - 230 Tons (335 - 810 kW) have part winding start as standard

62 YORK INTERNATIONAL
FORM 150.70-EG1

SYSTEM 2 COMPR.
COND.
FAN
ACL/ PW/
RLA FLA
LRA LRA EACH
112 582 368 10.6 SEE NOTE 7 (TYP)
97 506 320 10.5
48.5 253 160 6.8
38.8 202 128 5.6
132 674 414 10.6
114 586 360 10.5
57 293 180 6.8
45.6 234 144 5.6 SEE NOTE 6
132 674 414 10.6
LD01171
114 586 360 10.5
57 293 180 6.8
45.6 234 144 5.6
159 835 683 10.6
138 726 594 10.5
69 363 297 6.8 SEE NOTE 7 (TYP)
55 299 245 5.6
198 1072 858 10.6
172 932 746 6.8
86 466 373 6.8
68.8 380 304 5.6

SEE NOTE 6
LD01172

CONTROL POWER SUPPLY

MAXIMUM NON-FUSED
CONTROL MINIMUM
UNIT DUAL- DISC.
POWER CIRCUIT
VOLTAGE ELEMENT SWITCH
SUPPLY AMPACITY
FUSE SIZE SIZE
Standard
Models without 115-1-60 20A 20A, 250V 30A, 240V
Transformers

LEGEND:

VOLT = Voltage
MCA = Minimum Circuit Ampacity
DISC = Disconnect
ACL = Across-the-Line
PW = Part Wind
N/A = Not Available
RLA = Running Load Amps
FLA = Full Load Amps
ACL/LRA = Across-the-Line Inrush Amps
PW/LRA = Part Wind Inrush Amps
CKT BRK = Circuit Breaker
HACR = Heating, Air Conditioning and Refrigeration

YORK INTERNATIONAL 63
Electrical Data (95 - 130 Ton [335 - 458 kW]) (Dual Power Supply)

DUAL COMPRESSOR POWER SUPPLY WIRING (STANDARD)


SYSTEM #1 WIRING SYSTEM #2 WIRING
MODEL MIN MAXSIZE COND. MAX SIZE COND.
YCA DUAL ELEM DUAL ELEM
NF CKT. BKR. INCOMING CPR CPR FAN DIS. CKT. BKR. INCOMING CPR CPR FAN
MCA1 FUSE 6 MCA1 FUSE 6
DISC HACR5 WIRE RANGE RLA LRA9 FLA MIN.4 HACR5 WIRE RANGE RLA LRA9 FLA
SW TYPE (CU ONLY) EACH TYPE (CU ONLY) EACH
MIN.2 MAX.3 MIN.2 MAX.3
Z88EE8 -17 291 350 450 400 450 (2) #4 - 250 207 858 16.0 291 350 450 400 450 (2) #4 - 250 207 858 16
Z88EE8 -28 258 350 400 400 400 (2) #4 - 250 180 746 16.4 258 350 400 400 400 (2) #4 - 250 180 746 16.4
Z88EE8 -46 129 175 200 200 200 (2) #4 - 250 90 373 8.1 129 175 200 200 200 (2) #4 - 250 90 373 8.1
Z88EE8 -58 102 125 150 100 150 (2) #4 - 250 72 304 5.9 102 150 150 100 150 (2) #4 - 250 72 304 5.9
See notes on page 62.

DUAL COMPRESSOR POWER SUPPLY WIRING (STANDARD)


SYSTEM #1 WIRING SYSTEM #2 WIRING
MODEL MIN COND. COND.
YCA DUAL ELEM DUAL ELEM
1 NF CKT. BKR. INCOMING CPR CPR FAN 1 DIS. CKT. BKR. INCOMING CPR CPR FAN
MCA FUSE WIRE RANGE6 RLA LRA9 FLA MCA FUSE WIRE RANGE6 RLA LRA9 FLA
DISC MIN.4
SW (CU ONLY) EACH (CU ONLY) EACH
MIN.2 MAX.3 MIN MAX MIN.2 MAX.3 MIN MAX
J110 -17 295 350 500 400 350 450 (2) #6 - 250 212 803 10.0 295 350 500 400 350 450 (2) #6 - 250 212 803 10.0
J110 -28 267 350 450 400 350 400 (2) #6 - 250 184 698 12.0 267 350 450 400 350 400 (2) #6 - 250 184 698 12.0
J110 -40 162 200 250 200 200 250 (2) #6 - 250 116 441 5.2 162 200 250 200 200 250 (2) #6 - 250 116 441 5.2
J110 -46 131 175 200 200 175 200 (2) #6 - 250 92 349 5.0 131 175 200 200 175 200 (2) #6 - 250 92 349 5.0
J110 -58 107 150 175 200 150 150 (2) #6 - 250 74 279 4.9 107 150 175 200 150 150 (2) #6 - 250 74 279 4.9
J120 -17 368 450 600 400 450 600 (2) #6 - 250 270 1063 10.0 295 350 500 400 350 450 (2) #6 - 250 212 803 10.0
J120 -28 330 400 500 400 400 500 (2) #6 - 250 235 924 12.0 267 350 450 400 350 400 (2) #6 - 250 184 698 12.0
J120 -40 201 250 300 200 250 300 (2) #6 - 250 148 584 5.2 162 200 250 200 200 250 (2) #6 - 250 116 441 5.2
J120 -46 162 200 250 200 200 250 (2) #6 - 250 117 462 5.0 131 175 200 200 175 200 (2) #6 - 250 92 349 5.0
J120 -58 132 175 225 200 175 200 (2) #6 - 250 94 370 4.9 107 150 175 200 150 150 (2) #6 - 250 74 279 4.9
J130 -17 368 450 600 400 450 600 (2) #6 - 250 270 1063 10.0 368 450 600 400 450 600 (2) #6 - 250 270 1063 10.0
J130 -28 330 400 500 400 400 500 (2) #6 - 250 235 924 12.0 330 400 500 400 400 500 (2) #6 - 250 235 924 12.0
J130 -40 201 250 300 200 250 300 (2) #6 - 250 148 584 5.2 201 250 300 200 250 300 (2) #6 - 250 148 584 5.2
J130 -46 162 200 250 200 200 250 (2) #6 - 250 117 462 5.0 162 200 250 200 200 250 (2) #6 - 250 117 462 5.0
J130 -58 132 175 225 200 175 200 (2) #6 - 250 94 370 4.9 133 175 225 200 175 200 (2) #6 - 250 94 370 4.9
See notes on page 62.

SEE NOTE 6

SEE NOTE 6

SEE NOTE 7 (TYP) LD01173

64 YORK INTERNATIONAL
FORM 150.70-EG1

Electrical Data (150 - 230 Ton [528 - 810 kW]) (Dual Power Supply)

DUAL COMPRESSOR POWER SUPPLY WIRING (STANDARD)


SYSTEM #1 WIRING SYSTEM #2 WIRING
MODEL MIN COND. COND.
YCA DUAL ELEM DUAL ELEM
1 NF CKT. BKR. INCOMING CPR CPR FAN 1 DIS. CKT. BKR. INCOMING CPR CPR FAN
MCA FUSE WIRE RANGE6 RLA LRA9 FLA MCA FUSE WIRE RANGE6 RLA LRA9 FLA
DISC MIN.4
SW (CU ONLY) EACH (CU ONLY) EACH
MIN.2 MAX.3 MIN MAX MIN.2 MAX.3 MIN MAX
J150 -17 417 500 700 400 500 600 (2)1/0 - 500 301 1208 10.0 417 500 700 400 500 600 (2)1/0 - 500 301 1208 10.0
J150 -28 376 450 600 400 450 500 (2)#6 - 250 262 1050 12.0 376 450 600 400 450 500 (2)#6 - 250 262 1050 12.0
J150 -40 228 300 350 400 300 350 (2)#6 - 250 165 663 5.2 228 300 350 400 300 350 (2)#6 - 250 165 663 5.2
J150 -46 184 225 300 200 225 250 (2)#6 - 250 131 525 5.0 184 225 300 200 225 250 (2)#6 - 250 131 525 5.0
J150 -58 151 200 250 200 200 225 (2)#6 - 250 105 420 4.9 151 200 250 200 200 225 (2)#6 - 250 105 420 4.9
J160 -28 458 600 700 600 600 700 (2)1/0 - 500 328 1278 12.0 376 450 600 400 450 500 (2)1/0 - 500 262 1050 12.0
J160 -40 280 350 450 400 350 450 (2)#6 - 250 207 807 5.2 228 300 350 400 300 350 (2)#6 - 250 165 663 5.2
J160 -46 225 300 350 400 300 350 (2)#6 - 250 164 639 5.0 184 225 300 200 225 250 (2)#6 - 250 131 525 5.0
J160 -58 184 225 300 200 225 250 (2)#1 - 500 131 511 4.9 151 200 250 200 200 225 (2)#1 - 500 105 420 4.9
J180 -28 458 600 700 600 600 700 (2)1/0 - 500 328 1278 12.0 458 600 700 600 600 700 (2)1/0 - 500 328 1278 12.0
J180 -40 280 350 450 400 350 450 (2)#6 - 250 207 807 5.2 280 350 450 400 350 450 (2)#6 - 250 207 807 5.2
J180 -46 225 300 350 400 300 350 (2)#6 - 250 164 639 5.0 225 300 350 400 300 350 (2)#6 - 250 164 639 5.0
J180 -58 184 225 300 200 225 250 (2)#1 - 500 131 511 4.9 184 225 300 200 225 250 (2)#1 - 500 131 511 4.9
J190 -28 518 700 800 600 700 800 (2)1/0 - 500 376 1278 12.0 458 600 700 600 600 700 (2)1/0 - 500 328 1278 12.0
J190 -40 318 400 500 400 400 500 (2)#6 - 250 237 807 5.2 280 350 450 400 350 450 (2)#6 - 250 207 807 5.2
J190 -46 255 350 400 400 350 400 (2)#6 - 250 188 639 5.0 225 300 350 400 300 350 (2)#6 - 250 164 639 5.0
J190 -58 208 250 350 200 250 300 (2)#1 - 500 150 511 4.9 184 225 300 200 225 250 (2)#1 - 500 131 511 4.9
J200 -28 536 700 800 600 700 800 (2)1/0 - 500 376 1278 16.4 536 700 800 600 700 800 (2)1/0 - 500 376 1278 16.4
J200 -40 330 400 500 400 400 500 (2)#6 - 250 237 807 8.2 330 400 500 400 400 500 (2)#6 - 250 237 807 8.2
J200 -46 268 350 450 400 350 400 (2)#6 - 250 188 639 8.1 268 350 450 400 350 400 (2)#6 - 250 188 639 8.1
J200 -58 212 250 350 400 250 300 (2)#1 - 500 150 511 5.9 212 250 350 400 250 300 (2)#1 - 500 150 511 5.9
J220 -40 393 500 600 400 500 600 (2)1/0 - 500 288 1182 8.2 330 400 500 400 400 500 (2)1/0 - 500 237 807 8.2
J220 -46 318 400 500 400 400 500 (2)1/0 - 500 228 936 8.1 268 350 450 400 350 400 (2)1/0 - 500 188 639 8.1
J220 -58 252 300 400 400 300 400 (2)1/0 - 500 182 749 5.9 212 250 350 400 250 300 (2)1/0 - 500 150 511 5.9
J230 -40 393 500 600 400 500 600 (2)1/0 - 500 288 1182 8.2 393 500 600 400 500 600 (2)1/0 - 500 288 1182 8.2
J230 -46 318 400 500 400 400 500 (2)1/0 - 500 228 936 8.1 318 400 500 400 400 500 (2)1/0 - 500 228 936 8.1
J230 -58 252 300 400 400 300 400 (2)1/0 - 500 182 749 5.9 252 300 400 400 300 400 (2)1/0 - 500 182 749 5.9
See notes on page 62.
CONTROL POWER SUPPLY

MAXIMUM NON-FUSED
CONTROL MINIMUM
UNIT DUAL- DISC.
POWER CIRCUIT
VOLTAGE ELEMENT SWITCH
SUPPLY AMPACITY
FUSE SIZE SIZE
Standard
Models without 115-1-60 20A 20A, 250V 30A, 240V
Transformers

LEGEND:

VOLT = Voltage
MCA = Minimum Circuit Ampacity
DISC = Disconnect
N/A = Not Available
CPR-RLA = Compressor Running Load Amps
CPR-RLA = Compressor Part Winding Inrush Amps
FLA = Full Load Amps
CKT BRK = Circuit Breaker

YORK INTERNATIONAL 65
Electrical Data (95 - 230 Ton [335 - 810 kW]) (Single Point Wiring)

SINGLE POINT POWER SUPPLY WIRING (OPTIONAL)


SYSTEM #1 SYSTEM #2
MIN
MODEL DUAL ELEM MAX SIZE INCOMING
NF
YCA MCA1 FUSE CKT. BKR. WIRE RANGE6 CPR CPR FAN CPR CPR FAN
DISC 5
HACR (CU ONLY) RLA LRA9 FLA RLA LRA9 FLA
SW
MIN.2 MAX.3 TYPE
Z88EE8 -17 530 600 700 600 700 (3) #6 - 350 207 858 16 207 858 16
Z88EE8 -28 471 600 600 600 600 (3) #6 - 350 180 746 16.4 180 746 16.4
Z88EE8 -46 235 300 300 400 300 (1) #6 - 350 90 373 8.1 90 373 8.1
Z88EE8 -58 186 225 250 200 250 (1) #6 - 350 72 304 5.9 72 304 5.9
See notes on page 62.

SINGLE POINT POWER SUPPLY WIRING (OPTIONAL)


SYSTEM #1 SYSTEM #2
MIN
MODEL DUAL ELEM INCOMING
NF
YCA MCA1 FUSE WIRE RANGE CPR CPR FAN CPR CPR FAN
DISC
(CU ONLY) RLA LRA9 FLA RLA LRA9 FLA
2 3
SW
MIN. MAX.
J110 -46 238 300 300 400 (2) #2 - 600 92 349 5.0 92 349 5.0
J110 -58 196 225 250 400 (2) #2 - 600 74 279 4.9 74 279 4.9
J120 -46 269 300 350 400 (2) #2 - 600 117 462 5.0 92 349 5.0
J120 -58 221 250 300 400 (2) #2 - 600 94 370 4.9 74 279 4.9
J130 -46 294 350 400 400 (2) #2 - 600 117 462 5.0 117 462 5.0
J130 -58 241 300 300 400 (2) #2 - 600 94 370 4.9 94 370 4.9
J150 -46 335 400 450 400 (2) #2 - 600 131 525 5.0 131 525 5.0
J150 -58 275 350 350 400 (2) #2 - 600 105 420 4.9 105 420 4.9
J160 -46 376 450 500 400 (2) #2 - 600 164 639 5.0 131 525 5.0
J160 -58 308 350 400 400 (2) #2 - 600 131 511 4.9 105 420 4.9
J180 -46 409 500 500 600 (2) #2 - 600 164 639 5.0 164 639 5.0
J180 -58 334 400 450 400 (2) #2 - 600 131 511 4.9 131 511 4.9
J190 -46 439 500 600 600 (2) #2 - 600 188 639 5.0 164 639 5.0
J190 -58 358 400 500 400 (2) #2 - 600 150 511 4.9 131 511 4.9
J200 -46 488 600 600 600 (2) #2 - 600 188 639 8.1 188 639 8.1
J200 -58 385 450 500 400 (2) #2 - 600 150 511 5.9 150 511 5.9
J220 -46 538 600 700 600 (2) #2 - 600 228 936 8.1 188 639 8.1
J220 -58 425 500 600 600 (2) #2 - 600 182 749 5.9 150 511 5.9
J230 -46 578 700 800 600 (2) #2 - 600 228 936 8.1 228 936 8.1
J230 -58 457 600 600 600 (2) #2 - 600 182 749 5.9 182 749 5.9
See notes on page 62.

LEGEND:

VOLT = Voltage
MCA = Minimum Circuit Ampacity
DISC = Disconnect
N/A = Not Available
CPR-RLA = Compressor Running Load Amps
CPR-RLA = Compressor Part Winding Inrush Amps
FLA = Full Load Amps
CKT BRK = Circuit Breaker
HACR = Heating, Air Conditioning and Refrigeration

66 YORK INTERNATIONAL
FORM 150.70-EG1

SEE NOTE 7 (TYP)

SEE NOTE 6

LD01175

CONTROL POWER SUPPLY

MAXIMUM NON-FUSED
CONTROL MINIMUM
UNIT DUAL- DISC.
POWER CIRCUIT
VOLTAGE ELEMENT SWITCH
SUPPLY AMPACITY
FUSE SIZE SIZE
Standard
Models without 115-1-60 20A 20A, 250V 30A, 240V
Transformers

YORK INTERNATIONAL 67
Electrical Data (95 - 230 Ton [335 - 810 kW]) (Disconnect Switches & Fuses)
POWER SUPPLY WIRING FACTORY DISCONNECT SWITCHES AND FUSES
FACTORY MOUNTED SYSTEM #1 SYSTEM #2
MIN
MODEL DUAL ELEM NF DISCONNECT SWITCH COND. COND.
YCA CKT. BKR. FACT. MTD. FACT. MTD.
MCA1 FUSE INCOMING CPR CPR FAN CPR CPR FAN
DISC 6 FUSE RLA LRA9 FLA FUSE RLA LRA9 FLA
WIRE RANGE
SW EACH MIN2 EACH
MIN.2 MAX.3 MIN MAX (CU ONLY) MIN2 MAX3 MAX3
J110 -17 537 600 700 600 600 700 (3) 3/0 - 500 350 500 212 1005 10.0 350 500 212 1005 10.0
J110 -28 487 600 600 600 600 600 (3) 3/0 - 500 350 450 184 874 12.0 350 450 184 874 12.0
J110 -40 293 350 400 400 350 400 (1) #1 - 600 or (2) #1 - 250 200 250 116 552 5.2 200 250 116 552 5.2
J110 -46 238 300 300 400 300 300 (1) #1 - 600 or (2) #1 - 250 175 200 92 437 5.0 175 200 92 437 5.0
J110 -58 196 225 250 400 225 250 (1) #1 - 600 or (2) #1 - 250 150 175 74 350 4.9 150 175 74 350 4.9
J120 -17 610 700 800 800 700 800 (3) 3/0 - 500 450 600 270 1332 10.0 350 500 212 1005 10.0
J120 -28 550 700 700 600 700 700 (3) 3/0 - 500 400 500 235 1158 12.0 350 450 184 874 12.0
J120 -40 333 400 450 400 400 450 (1) #1 - 600 or (2) #1 - 250 250 300 148 731 5.2 200 250 116 552 5.2
J120 -46 269 300 350 400 300 350 (1) #1 - 600 or (2) #1 - 250 200 250 117 579 5.0 175 200 92 437 5.0
J120 -58 221 250 300 400 250 300 (1) #1 - 600 or (2) #1 - 250 175 225 94 463 4.9 150 175 74 350 4.9
J130 -17 668 800 800 800 800 800 (3) 3/0 - 500 450 600 270 1332 10.0 450 600 270 1332 10.0
J130 -28 600 700 800 800 700 800 (3) 3/0 - 500 400 500 235 1158 12.0 400 500 235 1158 12.0
J130 -40 365 450 500 400 450 500 (1) #1 - 600 or (2) #1 - 250 250 300 148 731 5.2 250 300 148 731 5.2
J130 -46 294 350 400 400 350 400 (1) #1 - 600 or (2) #1 - 250 200 250 117 579 5.0 200 250 117 579 5.0
J130 -58 241 300 300 400 300 300 (1) #1 - 600 or (2) #1 - 250 175 225 94 463 4.9 175 225 94 463 4.9
J150 -17 758 1000 1000 800 1000 1000 (3) 3/0 - 500 600 700 301 1513 10.0 500 700 301 1513 10.0
J150 -28 686 800 800 800 800 800 (3) 3/0 - 500 500 600 262 1316 12.0 450 600 262 1316 12.0
J150 -40 413 500 500 600 500 500 (3) 3/0 - 500 300 350 165 831 5.2 300 350 165 831 5.2
J150 -46 335 400 450 400 400 450 (1) #1 - 600 or (2) #1 - 250 225 300 131 658 5.0 225 300 131 658 5.0
J150 -58 276 350 350 400 350 350 (1) #1 - 600 or (2) #1 - 250 200 250 105 526 4.9 200 250 105 526 4.9

See notes on page 62.

DISCONNECT OPTION
UNIT PANEL

L 2 G 2L1 2L2 2L3 1L1 1L2 1L3

SEE NOTE 7 (TYP)


L3
L1

L2
GRD

GRD

OPTIONAL
CONTROL FACTORY
CONTROL
POWER OPTIONAL
MOUNTED
FACTORY-
POWER
SUPPLY
SUPPLY FUSES
MOUNTED
FUSES

BY OTHERS
BY OTHERS

SEE NOTE 6
LD01174(R)

68 YORK INTERNATIONAL
FORM 150.70-EG1

POWER SUPPLY WIRING FACTORY DISCONNECT SWITCHES AND FUSES


FACTORY MOUNTED SYSTEM #1 SYSTEM #2
MIN
MODEL DUAL ELEM NF DISCONNECT SWITCH COND. COND.
YCA CKT. BKR. FACT. MTD. FACT. MTD.
MCA1 FUSE INCOMING CPR CPR FAN CPR CPR FAN
DISC 6 FUSE RLA LRA9 FLA FUSE RLA LRA9 FLA
WIRE RANGE
SW EACH MIN2 EACH
MIN.2 MAX.3 MIN MAX (CU ONLY) MIN2 MAX3 MAX3
J160 -28 768 1000 1000 800 1000 1000 (3) 3/0 - 500 600 700 328 1602 12.0 500 600 262 1316 12.0
J160 -40 466 600 600 600 600 600 (3) 3/0 - 500 350 450 207 1012 5.2 300 350 165 831 5.2
J160 -46 376 450 500 400 450 500 (1) #1 - 600 or (2) #1 - 250 300 350 164 801 5.0 225 300 131 658 5.0
J160 -58 308 350 400 400 350 400 (1) #1 - 600 or (2) #1 - 250 225 300 131 641 4.9 200 250 105 526 4.9
J180 -28 834 1000 1000 1000 1000 1000 (3) 3/0 - 500 600 700 328 1602 12.0 600 700 328 1602 12.0
J180 -40 508 600 700 600 600 700 (3) 3/0 - 500 350 450 207 1012 5.2 350 450 207 1012 5.2
J180 -46 409 500 500 600 500 500 (3) 3/0 - 500 300 350 164 801 5.0 300 350 164 801 5.0
J180 -58 334 400 450 400 400 450 (1) #1 - 600 or (2) #1 - 250 225 300 131 641 4.9 225 300 131 641 4.9
J190 -28 894 1000 1200 1000 1000 1200 NA NA NA 376 1278 12.0 NA NA 328 1602 12.0
J190 -40 545 700 700 600 700 700 (3) 3/0 - 500 400 500 237 1012 5.2 350 450 207 1012 5.2
J190 -46 439 500 600 600 500 600 (3) 3/0 - 500 350 400 188 801 5.0 300 350 164 801 5.0
J190 -58 358 400 500 400 400 500 (1) #1 - 600 or (2) #1 - 250 250 350 150 641 4.9 225 300 131 641 4.9
J200 -28 978 1200 1200 1200 1200 1200 NA NA NA 376 1278 16.4 NA NA 376 1278 16.4
J200 -40 599 700 800 800 700 800 (3) 3/0 - 500 400 500 237 1012 8.2 400 500 237 1012 8.2
J200 -46 488 600 600 600 600 600 (3) 3/0 - 500 350 450 188 801 8.1 350 450 188 801 8.1
J200 -58 385 450 500 400 450 500 (1) #1 - 600 or (2) #1 - 250 300 350 150 641 5.9 300 350 150 641 5.9
J220 -40 663 800 800 800 800 800 (3) 3/0 - 500 500 600 288 1482 8.2 400 500 237 1012 8.2
J220 -46 538 600 700 600 600 700 (3) 3/0 - 500 400 500 228 1173 8.1 350 450 188 801 8.1
J220 -58 425 500 600 600 500 600 (3) 3/0 - 500 350 400 182 938 5.9 300 350 150 641 5.9
J230 -40 714 800 1000 800 800 1000 (3) 3/0 - 500 500 600 288 1482 8.2 500 600 288 1482 8.2
J230 -46 578 700 800 600 700 800 (3) 3/0 - 500 400 500 228 1173 8.1 400 500 228 1173 8.1
J230 -58 457 600 600 600 600 600 (3) 3/0 - 500 350 400 182 938 5.9 350 400 182 938 5.9

See notes on page 62.

LEGEND:

VOLT = Voltage
MCA = Minimum Circuit Ampacity
DISC = Disconnect
N/A = Not Available
CPR-RLA = Compressor Running Load Amps
CPR-RLA = Compressor Part Winding Inrush Amps
FLA = Full Load Amps
CKT BRK = Circuit Breaker

CONTROL POWER SUPPLY

MAXIMUM NON-FUSED
CONTROL MINIMUM
UNIT DUAL- DISC.
POWER CIRCUIT
VOLTAGE ELEMENT SWITCH
SUPPLY AMPACITY
FUSE SIZE SIZE
Standard
Models without 115-1-60 20A 20A, 250V 30A, 240V
Transformers

YORK INTERNATIONAL 69
Electrical Data (95 - 230 Ton [335 - 810 kW]) (Single Point with Unit Mounted Circuit Breakers)

POWER SUPPLY WIRING SINGLE POINT WITH FACTORY UNIT MOUNTED CIRCUIT BREAKERS
SYSTEM #1 SYSTEM #2
MIN
MODEL DUAL ELEM NF INCOMING COND. COND.
YCA CKT. BKR. 6 FACT. MTD. FACT. MTD.
MCA1 FUSE WIRE RANGE CPR CPR FAN CPR CPR FAN
DISC FUSE RLA LRA9 FLA FUSE RLA LRA9 FLA
(CU ONLY)
SW EACH MIN2 EACH
MIN.2 MAX.3 MIN MAX MIN2 MAX3 MAX3
J110 -17 537 600 700 600 600 700 (3) 3/0 - 500 350 450 212 1005 10.0 350 450 212 1005 10.0
J110 -28 487 600 600 600 600 600 (1) #1 - 600 or (2) #1 - 250 350 400 184 874 12.0 350 400 184 874 12.0
J110 -40 293 350 400 400 350 400 (1) #1 - 600 or (2) #1 - 250 200 250 116 552 5.2 200 250 116 552 5.2
J110 -46 238 300 300 400 300 300 (1) #1 - 600 or (2) #1 - 250 175 200 92 437 5.0 175 200 92 437 5.0
J110 -58 196 225 250 400 225 250 (1) #1 - 600 or (2) #1 - 250 150 150 74 350 4.9 150 150 74 350 4.9
J120 -17 610 700 800 800 700 800 (3) 3/0 - 500 450 600 270 1332 10.0 350 450 212 1005 10.0
J120 -28 550 700 700 600 700 700 (3) 3/0 - 500 400 500 235 1158 12.0 350 400 184 874 12.0
J120 -40 333 400 450 400 400 450 (1) #1 - 600 or (2) #1 - 250 250 300 148 731 5.2 200 250 116 552 5.2
J120 -46 269 300 350 400 300 350 (1) #1 - 600 or (2) #1 - 250 200 250 117 579 5.0 175 200 92 437 5.0
J120 -58 221 250 300 400 250 300 (1) #1 - 600 or (2) #1 - 250 175 200 94 463 4.9 150 150 74 350 4.9
J130 -17 668 800 800 800 800 800 (3) 3/0 - 500 450 600 270 1332 10.0 450 600 270 1332 10.0
J130 -28 600 700 800 800 700 800 (3) 3/0 - 500 400 500 235 1158 12.0 400 500 235 1158 12.0
J130 -40 365 450 500 400 450 500 (1) #1 - 600 or (2) #1 - 250 250 300 148 731 5.2 250 300 148 731 5.2
J130 -46 294 350 400 400 350 400 (1) #1 - 600 or (2) #1 - 250 200 250 117 579 5.0 200 250 117 579 5.0
J130 -58 241 300 300 400 300 300 (1) #1 - 600 or (2) #1 - 250 175 200 94 463 4.9 175 200 94 463 4.9
J150 -17 758 1000 1000 800 1000 1000 (3) 3/0 - 500 600 600 301 1513 10.0 600 600 301 1513 10.0
J150 -28 686 800 800 800 800 800 (3) 3/0 - 500 500 500 262 1316 12.0 500 500 262 1316 12.0
J150 -40 413 500 500 600 500 500 (1) #1 - 600 or (2) #1 - 250 300 350 165 831 5.2 300 350 165 831 5.2
J150 -46 335 400 450 400 400 450 (1) #1 - 600 or (2) #1 - 250 225 250 131 658 5.0 225 250 131 658 5.0
J150 -58 276 350 350 400 350 350 (1) #1 - 600 or (2) #1 - 250 200 225 105 526 4.9 200 225 105 526 4.9
J160 -28 768 1000 1000 800 1000 1000 (3) 3/0 - 500 600 700 328 1602 12.0 500 500 262 1316 12.0
J160 -40 466 600 600 600 600 600 (3) 3/0 - 500 350 450 207 1012 5.2 300 350 165 831 5.2
J160 -46 376 450 500 400 450 500 (1) #1 - 600 or (2) #1 - 250 300 350 164 801 5.0 225 250 131 658 5.0
J160 -58 308 350 400 400 350 400 (1) #1 - 600 or (2) #1 - 250 225 250 131 641 4.9 200 225 105 526 4.9
J180 -28 834 1000 1000 1000 1000 1000 (3) 3/0 - 500 600 700 328 1602 12.0 600 700 328 1602 12.0
J180 -40 508 600 700 600 600 700 (3) 3/0 - 500 350 450 207 1012 5.2 350 450 207 1012 5.2
J180 -46 409 500 500 600 500 500 (1) #1 - 600 or (2) #1 - 250 300 350 164 801 5.0 300 350 164 801 5.0
J180 -58 334 400 450 400 400 450 (1) #1 - 600 or (2) #1 - 250 225 250 131 641 4.9 225 250 131 641 4.9
J190 -28 894 1000 1200 1000 1000 1200 (3) 3/0 - 500 700 800 376 1602 12.0 600 700 328 1602 12.0
J190 -40 545 700 700 600 700 700 (3) 3/0 - 500 400 500 237 1012 5.2 350 450 207 1012 5.2
J190 -46 439 500 600 600 500 600 (1) #1 - 600 or (2) #1 - 250 350 400 188 801 5.0 300 350 164 801 5.0
J190 -58 358 400 500 400 400 500 (1) #1 - 600 or (2) #1 - 250 250 300 150 641 4.9 225 250 131 641 4.9
J200 -28 978 1200 1200 1200 1200 1200 (3) 3/0 - 500 700 800 376 1602 16.4 600 800 376 1602 4.9
J200 -40 599 700 800 800 700 800 (3) 3/0 - 500 400 500 237 1012 8.2 400 500 237 1012 5.2
J200 -46 488 600 600 600 600 600 (1) #1 - 600 or (2) #1 - 250 350 400 188 801 8.1 350 400 188 801 5.0
J200 -58 385 450 500 400 450 500 (1) #1 - 600 or (2) #1 - 250 300 300 150 641 5.9 250 300 150 641 4.9
J220 -40 663 800 800 800 800 800 (3) 3/0 - 500 500 600 288 1482 8.2 400 500 237 1012 5.2
J220 -46 538 600 700 600 600 700 (3) 3/0 - 500 400 500 228 1173 8.1 350 400 188 801 5.0
J220 -58 425 500 600 600 500 600 (1) #1 - 600 or (2) #1 - 250 350 400 182 938 5.9 250 300 150 641 4.9
J230 -40 714 800 1000 800 800 1000 (3) 3/0 - 500 500 600 288 1482 8.2 500 600 288 1482 5.2
J230 -46 578 700 800 600 700 800 (3) 3/0 - 500 400 500 228 1173 8.1 400 500 228 1173 5.0
J230 -58 457 600 600 600 600 600 (1) #1 - 600 or (2) #1 - 250 350 400 182 938 5.9 300 400 182 938 4.9
See notes on page 62.

70 YORK INTERNATIONAL
FORM 150.70-EG1

SINGLE POINT WITH FACTORY MOUNTED


CIRCUIT BREAKERS

L 2 G 2L1 2L2 2L3 1L1 1L2 1L3

GRD

GRD
SEE NOTE 7 (TYP)
CONTROL
CONTROL
POWER
POWER
SUPPLY
SUPPLY

BY OTHERS
BY OTHERS

COMPRESSOR
COMPRESSOR
POWER
SUPPLY
POWER
SUPPLY
SEE NOTE 6

LD01556(R)

LEGEND:

VOLT = Voltage
MCA = Minimum Circuit Ampacity
DISC = Disconnect
N/A = Not Available
CPR-RLA = Compressor Running Load Amps
CPR-RLA = Compressor Part Winding Inrush Amps
FLA = Full Load Amps
CKT BRK = Circuit Breaker

CONTROL POWER SUPPLY

MAXIMUM NON-FUSED
CONTROL MINIMUM
UNIT DUAL- DISC.
POWER CIRCUIT
VOLTAGE ELEMENT SWITCH
SUPPLY AMPACITY
FUSE SIZE SIZE
Standard
Models without 115-1-60 20A 20A, 250V 30A, 240V
Transformers

YORK INTERNATIONAL 71
Sound Power

SOUND POWER LEVELS


(IN dB RE 10 THE MINUS 12 WATTS)
In Accordance with the Methods of ARI 370
54°/44°F Cooler Water 95°F Air on the Condenser

60 HZ
YCA
OCTAVE BAND CENTER FREQUENCY, HZ
MODEL
LWA 63 125 250 500 1000 2000 4000 8000
Z33BA3 99 99 99 102 96 93 89 87 83
Z44BA3 99 99 99 102 96 93 89 87 83
Z74BBC 98 99 94 97 95 92 89 86 86
Z77CB3 99 99 96 99 97 93 90 88 86
Z88DE3 99 99 96 99 97 93 90 88 86
Z88EE8 102 103 103 101 99 97 94 92 89
J110 104 101 101 103 101 99 96 91 87
J120 104 101 101 103 101 99 96 91 87
J130 104 96 102 102 101 99 96 93 91
J150 104 96 102 102 101 99 96 93 91
J160 106 100 103 102 103 100 97 94 91
J180 107 100 105 102 105 101 98 94 92
J190 106 101 103 102 103 100 97 94 91
J200 104 101 100 102 101 98 96 93 90
J220 106 100 101 101 103 100 98 95 92
J230 107 98 102 100 104 102 100 96 93

72 YORK INTERNATIONAL
FORM 150.70-EG1

Application Data
UNIT LOCATION consult building contractor or architect for special instal-
lation requirements. Roof installations should incorpo-
The YCA chillers are designed for outdoor installation. rate the use of spring-type isolators to minimize the trans-
When selecting a site for installation, be guided by the mission of vibration into the building structure. They
following conditions: should be supported at the spring isolator locations.

1. For the outdoor location of the unit, select a place Ground Level Locations – It is important that the units
having an adequate supply of fresh air for the con- be installed on a substantial base that will not settle,
denser. causing strain on the liquid lines and resulting in pos-
sible leaks. A one-piece concrete slab with footers ex-
2. Avoid locations beneath windows or between struc- tended below the frost line is highly recommended. Ad-
tures where normal operating sounds may be objec- ditionally, the slab should not be tied to the main building
tionable. foundation as noises will telegraph.

3. Installation sites may be either on a roof or on ground Mounting holes (11-16" [17.5 mm] dia.) are provided in
level. (See FOUNDATION.) the steel channel for bolting the unit to its foundation.
See DIMENSIONS, for location of the mounting holes.
4. The condenser fans are propeller type and are not
recommended for use with ductwork in the condenser For ground level installations, precautions should be
air stream. taken to protect the unit from tampering by or injury to
unauthorized persons. Screws on access panels will
5. When it is desirable to surround the unit(s); it is recom- prevent casual tampering; however, further safety pre-
mended that the screening be able to pass the re- cautions, such as unit enclosure options, a fenced-in
quired chiller CFM without exceeding 0.1" (2.5 Kg/m2) enclosure or locking devices on the panels, may be ad-
of water external static pressure. visable. Check local authorities for safety regulations.

6. Protection against corrosive environments is available CHILLED LIQUID PIPING


by supplying the units with either copper fin, cured
phenolic or epoxy coating on the condenser coils. The The chilled liquid piping system should be laid out so
phenolic or epoxy coils should be offered with any that the circulating pump discharges into the cooler. The
units being installed at the seashore or where salt inlet and outlet cooler liquid connections are given in
spray may hit the unit. DIMENSIONS.

In installations where winter operation is intended and Hand stop valves are recommended for use in all lines
snow accumulations are expected, additional height must to facilitate servicing. Drain connections should be pro-
be provided to insure normal condenser air flow. vided at all low points to permit complete drainage of
the cooler and system piping. Additionally, a strainer (40
Recommended clearances for all units are shown in mesh) is recommended for use on the INLET line to the
DIMENSIONS. When the available space is less, the cooler.
unit(s) must be equipped with the discharge pressure
transducer option to permit high pressure unloading in Pressure gauge connections are recommended for
the event that air recirculation were to occur. installation in the inlet and outlet water lines. Gauges
are not furnished with the unit and are to be furnished
FOUNDATION by other suppliers.

The unit should be mounted on a flat and level founda- The chilled liquid lines that are exposed to outdoor am-
tion, ground or roof, capable of supporting the entire bients should be wrapped with a supplemental heater
operating weight of the equipment. Operating weights cable and insulated or glycol added to protect against
are given in the PHYSICAL DATA tables. freeze-up during low ambient periods.

Roof Locations – Choose a spot with adequate struc- A flow switch is available as an accessory on all units.
tural strength to safely support the entire weight of the The flow switch (or its equivalent) must be installed in
unit and service personnel. Care must be taken not to the leaving water piping of the cooler and must not be
damage the roof during installation. If the roof is “bonded”, used to start and stop the unit.

YORK INTERNATIONAL 73
Guide Specifications
YORK Model YCA __________________ Millennium seating seal-cap type suction and discharge stop valves.
Air Cooled Reciprocating Liquid Chiller(s). The (Each) The compressors shall be mounted on isolators. The her-
unit shall have a cooling capacity ________ of tons with metic motor shall be high torque, part-winding start (50 -
_________. Compressor kW when cooling __________ 90 Tons [176 - 317 kW] may have part winding start or
GPM of water from ______°F (°C) to ______°F (°C), across-the line start), 1750 rpm (60 Hz), refrigerant gas-
with an air temperature over the condenser of ______°F cooled and shall be equipped with internal temperature
(°C), and a cooler fouling factor of ________. The water sensing overload protection in each phase. The raintight
pressure drop shall not exceed ___________ feet (mm) motor terminal box shall be located above the crank-
of water through the cooler. The unit overall dimensions case oil level.
shall not exceed ____ft. ____ins. (mm) in length, _____ft.
_____ins. (mm) in width and _____ft. _____ins. (mm) in The motor shall operate on _________volts, 3 phase,
height. The unit operating weight shall not exceed 60 Hz electrical power.
_____Ibs (Kg).
CAPACITY CONTROL SYSTEM
GENERAL
The capacity control system shall modulate compres-
The (Each) Millennium Air Cooled Recoiprocating Liq- sor capacity automatically with block suction by using
uid Chiller shall be completely factory assembled includ- solenoid actuated control valves with high pressure fluid.
ing all interconnecting refrigerant piping and internal wir- This unloading shall be controlled by the YORK
ing of controls, mounted on a steel base which accom- MicroComputer Control Center.
modates the air cooled condenser, compressor(s) and
cooler. Operating test shall include operation with water COOLER
flowing through the cooler. Unit structure shall be painted
with weather resistant enamel which meets the ASTM The cooler shall be a direct expansion shell and tube
B117, 500 hour, 5% salt spray requirement. The base type with refrigerant in the tubes and liquid to be chilled
rails shall be of formed, double-thickness painted plate in the shell. The design working pressure of the cooler
steel. The unit shall be shipped with a full operating shell (liquid) side shall be 150 PSIG (1.0 kPa), and 235
charge of R-22. All units shall contain separate refriger- PSIG (1.62 kPa) for the tube (refrigerant) side. Refriger-
ant circuits, each with a single compressor for standby ant heads shall be removable. The cooler shall be
operation. All units shall be designed and constructed in equipped with a heater cable, covered with 3/4" (19 mm)
accordance with the applicable sections of the follow- flexible closed cell foam insulation (K = 0.25 maximum)
ing: Air Conditioning and Refrigeration Standard ARI 590; for freeze-up protection to -20°F (-28.9°C) ambient. The
American Society of Heating, Refrigeration and Air Con- cooler shall be constructed and tested in accordance
ditioning Engineers ANSI/ASHRAE 15 Safety Code for with ASME Code requirements. Vent and drain connec-
Mechanical Refrigeration; American Society of Mechani- tions shall be included. The water connections shall be
cal Engineers ASME Pressure Vessel Code; all units pro- fully accessible and grooved to accept victaulic couplings
duced at an ISO 9000 registered facility; National Elec- if used (by others).
trical Code/National Fire Protection Association NFPA
70; Underwriters Laboratory U.L. 1995 (200,230 and CONDENSER COILS
460-3-60); chillers from 50-200 tons are rated and
certified in accordance with ARI Standard 590-92. The condenser coil shall be constructed of seamless
copper tubes, arranged in staggered rows, mechanically
HERMETIC MOTOR-COMPRESSOR expanded into aluminum fins and include an integral
subcooling section. The design working pressure of the
There shall be a maximum of one compressor per re- condenser coil shall be 450 PSIG (3.0 kPa).
frigerant circuit. The compressors shall be accessible
hermetic reciprocating type with all rotating parts stati- CONDENSER FANS AND MOTORS
cally and dynamically balanced. The compressors shall
include ring type, stainless steel, suction and discharge The condenser fans shall be propeller type, providing
valves and removable cylinder liners. Motor cover and vertical air discharge. Fan blades shall be statically and
cylinder heads (with internal muffling devices) shall be dynamically balanced, protected above by PVC coated
removable. The compressor shall have a force-fed lubri- fan blade guards (50 - 90 Ton [176 - 317 kW] models
cation system using a reversible positive displacement shall have zinc dichromate coating with lacquer over-
type oil pump. The compressor shall also include a suc- coat). Each fan shall be driven directly by a permanently
tion strainer, oil strainer, oil stream magnetic plug, crank- lubricated individual TEAO (Totally Enclosed Air Over)
case oil sight glasses, crankcase oil heater, and back- motor with class “F” insulation.

74 YORK INTERNATIONAL
FORM 150.70-EG1

REFRIGERANT CIRCUITS increments above the setpoint); liquid pulldown rate sen-
sitivity adjustment (0.5°F to 5°F per minute in one-tenth
The unit shall contain two separate refrigerant circuits increments); anti-recycle timer status; compressor run
and each shall be constructed of copper tubing with status; no cooling load condition; day; date; time; out of
brazed joints, and shall include: shut-off valve with charg- range message; daily and holiday scheduling of start/
ing connection, liquid sight glass with moisture indica- stop times; automatic or manual lead/lag status; lead
tor, thermal expansion valve, solenoid valve and compressor definition; number of compressor starts and
filter-drier. The entire suction line and liquid line between running hours; status of hot gas bypass valves (option),
the expansion valve and the cooler shall be insulated evaporator heater, fan operation, liquid line solenoid valves,
with flexible closed cell insulation. and water pump; last fault shutdowns data; number of un-
loading steps; compressor load and unload timer status.
MICROPROCESSOR CONTROL CENTER
Operating or shutdown data shall be retained after power
Each unit shall contain a Microprocessor Control Cen- failure by the on-board ten year, lithium battery.
ter. All logic and controls shall be contained within a
raintight/dusttight type NEMA 3R/12 (and equivalent to Provisions shall be included for: pumpdown at shutdown
IP55 European standard) cabinet with hinged outer door and recycling pumpdown; a hard copy print-out from a
with positive acting latches. Inside shall be contained printer (by others) via an RS-232 electrical output; op-
the "user friendly" and interactive inputs and outputs as tional two steps of demand load limiting and remote
follows: LCD display with light emitting diode back light- chilled liquid reset from an external building automation
ing for outdoor viewing of data and input buttons for DIS- system; or Remote Millennium Control with printout ca-
PLAY (temperatures, pressures, etc.), ENTRY (enter/ pability (up to 4000 feet [1219 m] remotely) via an RS-485
cancel inputs, advance day, change AM/PM), electrical output; alarm contacts; and high motor current
SETPOINTS (change), CLOCK (set time and schedule), protection and demand limiting at start-up with compres-
PRINT (calling up operating and shutdown data), PRO- sor unloading.
GRAM (change inputs for special conditions such as
brine chilling) and UNIT ON/OFF. POWER PANEL(S)

The MicroComputer Control Center shall be capable of The power panel(s) shall contain the compressor power
displaying the following: return and leaving liquid tem- terminals, compressor motor starting contractors, cur-
perature; low leaving liquid temperature cutout setting; rent transformer sensing for each compressor power
ambient temperatures (actual outdoor temperature, low source, for protection against under voltage, over volt-
and high ambient cutout); English or Metric values; suc- age, imbalanced voltage, single phasing compressor stall
tion pressure cutout setting; system 1 and 2 percent and voltage spikes, and control power supply terminal
full-load motor current and suction, discharge (optional) strip for 115-1-60. The power wiring shall be routed
and oil differential pressures; liquid pulldown control through liquid-tight conduit (110 - 230 Ton [387 - 810
range (selectable for 2 - 20°F [1.1 - 11.1°C] in one-tenth kW] Models) to the compressors and fans.

YORK INTERNATIONAL 75
Proud Sponsor
of the 2000
U.S. Olympic Team

36USC380

P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in USA
Copyright © by York International Corporation 1999 ALL RIGHTS RESERVED
Form 150.70-EG1 (699)
Supersedes: 150.70-EG1 (397)

You might also like