Ultra Low Flow AQUAMIST System


for the Protection of
Data Processing Equipment Rooms/Halls
Training of Test for Flame Travel and Smoke

Table of Training provided by Tyco Fire Protec-


of Wires and Cables for Use in Air-
Handling Spaces,” or

Contents tion Products (TFPP) is mandatory prior


to bidding, designing, procurement of
• propagating cable with a maximum
Fire Propagating Index (FPI) of 24
Sections components, installation, and main- in accordance with FM Approval
Training . . . . . . . . . . . . . . . . . . . . 1 taining of TYCO Ultra Low Flow (ULF) Standard 3972, “Test Standard for
FM Approval & AQUAMIST Water Mist Systems. These Cable Fire Propagation”
Application Criteria . . . . . . . . . . . 1 systems are unique in their intent and
Occupancy and Storage
design. Anyone involved at any level
Protection Objectives . . . . . . . . . 2 The TYCO Ultra Low Flow AQUAMIST
must thoroughly understand the limita-
System Components . . . . . . . . . . 2 System for the Protection of Data Pro-
tions and capabilities of such systems.
General System cessing Equipment Rooms/Halls is

FM Approval &
Design Criteria . . . . . . . . . . . . . . . 2 only suitable for the protection of data
Detection . . . . . . . . . . . . . . . . . . 11 processing equipment and power and

Application
Operation . . . . . . . . . . . . . . . . . 11 data cables. For this reason, there are
Installation . . . . . . . . . . . . . . . . . 11 restrictions on how packaging and
waste is stored.
Care & Maintenance . . . . . . . . . 14
Limited Warranty . . . . . . . . . . . . 14
Criteria New data processing equipment with
Ordering Procedure . . . . . . . . . 14 The TYCO Type ULF AM29 and packaging awaiting installation are to
Type ULF AM30 AQUAMIST Nozzles be located in storage and staging areas
Figures are listed by FM Approvals to be used separate from data processing equip-
Conceptual View of as part of an engineered, wet or preac- ment rooms (i.e., where fire involving
Hot Aisle Containment tion water mist system. These systems the storage will not expose critical
AQUAMIST System . . . . . . . . . . . 3 may be considered for use in data equipment). Where storage and staging
Conceptual View of processing equipment rooms and areas are not available, limit in-process
Cold Aisle Containment related facilities, which include control packaged equipment in data process-
AQUAMIST System . . . . . . . . . . . 3 rooms, process control rooms, diag- ing equipment rooms to a temporary
Above-Floor Design Criteria . . . . 4 nostic equipment, and critical systems basis with regular removal of the pack-
Hot Aisle Containment System and equipment associated with data aging during the installation.
below Grated Ceiling . . . . . . . . . . 6 centers. The FM Approval applies
Hot Aisle Containment System to the service conditions described NOTICE
below Grated Ceiling – below and in the System Design Cri- The TYCO Ultra Low Flow AQUA-
Elevation View . . . . . . . . . . . . . . . 7 teria section. MIST System described herein must
Below-Floor Area-of-Coverage be installed and maintained in compli-
Design Criteria – Cables ance with this document and with the
Cable Tray Between Grates . . . . 9 All grouped cables and cable trays standards recognized by the authority
Below-Floor Area-of-Coverage (power and data) are to be installed having jurisdiction (i.e., CEN/TS 14972
Design Criteria – in accordance with FM Global Prop- “Fixed Firefighting Systems – Watermist
Cable Tray under Grates . . . . . . 10 erty Loss Prevention Data Sheet 5-31, Systems – Design and Installation” or
Below-Floor Local Application “Cable and Bus Bars.” The commu- NFPA 750 “Water Mist Fire Protection
Design Criteria – AM29 . . . . . . . 12 nication and data cables used in the Systems”). Failure to do so may impair
Below-Floor Local Application protected data processing equipment the performance of this system.
Design Criteria – AM30 . . . . . . . 13 room/hall must meet one of the follow-
ing criteria: The owner is responsible for main-
Graphs taining their fire protection system
• FM Approved Group 1-4910, or and devices in proper operating con-
Type ULF AM29
Obstruction Criteria...................... 5 • FM Approved Group 1, or dition. Contact the installing contrac-
tor or product manufacturer with any
Type ULF AM30 • plenum-rated cable Listed to questions.
Obstruction Criteria...................... 8 Underwriters Laboratory (UL)
Standard 910, or
• cable that has a maximum flame
spread distance of 1,5 m (5 ft.) or
less when tested in accordance
with NFPA 262 “Standard Method

Page 1 of 14 MAY 2015 TFP2233


TFP2233
Page 2 of 14

Protection materials. Particular attention should


be given to using plenum rated wires/
stainless steel fittings per MSS SP-114
may be used. Additionally, stainless
Objectives cables, plenum rated raceways /
routing assemblies, non-fire-propagat-
steel pipe per DIN 17440 and stainless
steel fittings per ISO 49 may be used.
ing hot/cold aisle containment materi-
The TYCO Ultra Low Flow AQUAMIST The sealant used for making up
als, and noncombustible filters and
System is designed to protect above- threaded stainless steel pipe connec-
insulation. Plastic materials, including
floor and below-floor configurations as tions must be of a type that is rated for
those of fire-retardant composition,
well as hot aisle and cold aisle setups use with stainless steel.
can produce large quantities of smoke
when installed in accordance with the
and should not be used. If plastic mate- Plain-end Schedule 5S or 10S Type
System Design Criteria. Conceptual
rials are used, ensure they are specifi- 316 stainless steel pipe per ASTM A312
views of hot and cold aisle contain-
cation tested to FM Approval Standard with minimum Class 150 socket weld
ment systems are shown in Figures 1
4910, “Cleanroom Materials Flamma- cast stainless steel fittings per MSS
and 2, respectively. This system also
bility Test Protocol” (FM4910 plastics). SP-114 may be used.
protects concealed spaces up to 1 m
(3.3 ft.) in height within the data pro- Suspended ceilings are to be con- These combinations of stainless steel
cessing equipment rooms/halls. structed of Class I materials. pipe and Class 150 fittings are suitable
Floors, raised floors, and structural for use at a maximum service pressure
Copies of the fire test report are avail-
supporting members of raised floors of 20,7 bar (300 psi) and a maximum
able upon request from the Technical
are to be constructed of noncombus- ambient service temperature of 66oC
Services department.
(150oF).
tible materials. Whenever possible,
System cable raceways and routing assemblies
should be constructed of noncombus-
Water Supply
The water supply must be taken from
Components tible materials. When cable raceways
and routing assemblies must be con-
a source that is equivalent in quality to
a potable source with respect to par-
• TYCO Type ULF AM29 and/or structed of plastic, one of the following ticulate and dissolved solids.
Type ULF AM30 Nozzles options should be used:
FM Approved pumps and pump con-
(Refer to Technical Data Sheets • FM Approvals 4910 specifications trollers must conform to the applicable
TFP2229 and TFP2201.) tested plastics listed in the Building requirements of NFPA 20 “Standard
• T YCO AQUAMIST Mist Con- Materials section of the Approval for the Installation of Stationary Pumps
trol Center (MCC) Guide (FM4910 plastics), or for Fire Protection”. Water tanks must
(Refer to Technical Data Sheet • Plenum-rated plastic raceways conform to the applicable requirements
TFP2270.) listed to Underwriters Laboratory of NFPA 22, “Standard for Water Tanks
(UL) Standard 2024 for Private Fire Protection.”
In cases where local Approvals are
required, other FM Approved pump Maximum System Size Hangers
skids may be used. 52,000 ft.2 (4830 m2) Selection and installation of the piping
system hangers must be FM Approved
• TYCO Preaction System with DV-5 Sizes for System and in accordance with the specifica-
Deluge Valve Single Interlock, Super- Pipe (Tube) and Fittings tions of NFPA 13, “Standard for the
vised – Electric Actuation Mains and branchlines are to be Installation of Sprinkler Systems,”
(Refer to Technical Data Sheet minimum DN20 (3/4 inch) pipe or tube except that the term “nozzle” is to be
TFP1420.) size. substituted for “sprinkler.”
• FM Approved detection equipment
Valves and Pressure Gauges
• TYCO Flexible Hose Connections NOTICE Valves, valve identification, and pres-
(Refer to Technical Data Sheet Failure to use the appropriately sized sure gauges must be FM Approved and
TFP720.) nozzle drop nipples may impair system conform to the applicable requirements
performance by restricting flow to the of NFPA 15, “Standard for Water Spray
TYCO Flexible Hose Connections nozzle inlet strainer.
are only FM Approved at a maximum Fixed Systems for Fire Protection.”
service pressure of 12 bar (175 psi) When nozzles are installed inside Corrosion Resistance
and can therefore only be used in outlets of tee fittings, the tee fittings The Type ULF AM29 is only to be used
systems where the supply is no must be such that the nozzle inlet in environments for which the materi-
greater than 12 bar (175 psi). TYCO strainer does not protrude into the als of construction specified in Tech-
Flexible Hose Connections cannot inside of the pipe (tube) run. nical Data Sheet TFP2229 will provide
be used in conjunction with the When nozzles are installed in elbow acceptable corrosion resistance. Any
TYCO AQUAMIST MCC Pump Skid. fittings, the elbow fittings must be of questions should be referred to the
a type that will allow clearance for the Technical Services department. The
General System nozzle inlet strainer. pipe (tube), fittings, hangers, and
hanger components must be suitable
Design Criteria Material for System
Pipe (Tube) and Fittings
for use in the application environment.

Selection and installation of pipe (tube) The Type ULF AM30 is only to be used
System Type in environments for which the materi-
Wet pipe or single interlock dry pipe and fittings must be in accordance with
the specifications of NFPA 750 “Water als of construction specified in Tech-
preaction with a maximum 30-second nical Data Sheet TFP2201 will provide
water delivery delay Mist Fire Protection Systems.”
acceptable corrosion resistance. Any
Data Processing Equipment GRINNELL G-PRESS Press-Fit Stain- questions should be referred to the
Room/Hall Construction less Steel Pipe and Fittings or threaded Technical Services department. The
Data processing equipment rooms/ Schedule 40S Type 304 or 316 stain- pipe (tube), fittings, hangers, and
halls and related facilities are to be less steel pipe per ASTM A312 with hanger components must be suitable
constructed using noncombustible minimum Class 150 threaded cast for use in the application environment.
TFP2233
Page 3 of 14

LOOSE SEAL BARRIER


FOR PRESSURE BALANCE

CRAC COLD AISLE SERVER HOT AISLE SERVER COLD AISLE


CABINET CABINET
(SIDE VIEW) (SIDE VIEW)

FIGURE 1
CONCEPTUAL VIEW OF HOT AISLE CONTAINMENT SYSTEM

LOOSE SEAL BARRIER


FOR PRESSURE BALANCE

CRAC HOT AISLE SERVER COLD AISLE SERVER HOT AISLE


CABINET CABINET
(SIDE VIEW) (SIDE VIEW)

FIGURE 2
CONCEPTUAL VIEW OF COLD AISLE CONTAINMENT SYSTEM
TFP2233
Page 4 of 14

3,7 x 3,7 m
(12 x 12 ft)
MAX.
TOP OF CABLE TRAY

CEILING
44 to 102 mm
NOZZLE 1,75 m (1.75 to 4 in)
(5.74 ft) DIFFUSER-
MIN. DISTANCE TO-CEILING
CABLE
DISTANCE
TRAY

5,0 m (16.40 ft)


SERVER SERVER MAX. HEIGHT
CABINET CABINET
*1,5 m/s (4.92 fps) (SIDE VIEW) (SIDE VIEW)
MAX. VELOCITY

RAISED
FLOOR

AIRFLOW * AIRFLOW * 1,0 m (3.28 ft)


MAX. HEIGHT

FIGURE 3
ULF AQUAMIST FOR DATA CENTERS
TYPICAL ABOVE-FLOOR DESIGN CRITERIA

Hydraulic Calculations Waterflow Alarms Above-floor


Hydraulic calculations for the water Waterflow alarm systems are to be Design Criteria
mist system are to be made as part installed, tested, and maintained in
of the design of the piping system, accordance with CEN or NFPA stan- Nozzle Type
to verify that the minimum required dards, as applicable. ULF AM29
flowing pressure is available at each Protection Area
nozzle in the design area. Flushing Connection
Systems with underground water Unlimited
• Where the water flow velocity does supply connections are to be provided Nozzle Temperature Ratings
not exceed 7,6 m/s (25 ft./sec.), with a suitable flushing connection at 57°C (135°F) and 68°C (155°F)
hydraulic calculations may be made the inlet to the automatic water control
using the Hazen-Williams formula. valve for the system. The flushing con- Nozzle Orientation
• Where the water flow velocity nection is to be of sufficient size to The TYCO Type ULF AM29 Nozzle is
exceeds 7,6 m/s (25 ft./sec.), the establish a flow rate not less than the to be installed in the pendent position.
hydraulic calculations are to be water demand rate of the system.
Nozzle Spacing and Location
made using the Darcy-Weisbach Type ULF AM29 Nozzles are to be
formula. NOTICE installed at a maximum spacing of
When designing hydraulically balanced Suitable provision is to be made for 3,7 m x 3,7 m (12 ft. x 12 ft.), with a
wet and single interlock preaction the disposal of flushing water. Flush- maximum distance of 1,8 m (6 ft.) from
water mist systems using FM Approved ing water must be directed such that walls. The minimum spacing to prevent
calculation methods, such as Tyco’s it will not cause accidental damage to non-operation of adjacent nozzles is
SprinkCALC software, the water deliv- property or danger to persons. 1,8 m (6 ft.).
ery delay to the most remote nozzle will The diffuser-to-ceiling distance must
not exceed 30 seconds. According to be 45 to 102 mm (1.75 to 4 in.).
FM Global Property Loss Prevention
Data Sheet 5-32, Table 1 (July 2012), A typical layout of the Above-Floor
water will fill the piping system upon Design is illustrated in Figure 3. These
detection activation in a single interlock design criteria also apply to cold aisle
preaction system; therefore, when the systems.
nozzles activate, water will be ready for Nozzle Pressure
discharge resulting in a water delivery 7,6 to 17,2 bar (110 to 250 psi)
delay of no more than 30 seconds.
TFP2233
Page 5 of 14

H
H H

H
OR V
V V

V
ELEVATION
ELEVATION

400
15
BELOW DIFFUSER, MILLIMETERS

BELOW DIFFUSER, INCHES


MAXIMUM DISTANCE 'V'

MAXIMUM DISTANCE 'V'


300
10

200

5
100

0 0
0,5 1,0 1,5 2,0 6 12 18 24 30 36 42 48 54 60 66 72 78

DISTANCE 'H' DISTANCE 'H'


TO OBSTRUCTION, TO OBSTRUCTION,
METERS INCHES
GRAPH A
TYPE ULF AM29
OBSTRUCTION CRITERIA

Construction Obstructions The maximum height of the ceiling is


Ceilings are to be of smooth construc- The maximum allowable vertical and limited to 5 m (16.4 ft.).
tion with a maximum slope of 5o (1/12). horizontal distance that the bottom of a
Any installed cable trays must have a
The maximum height of the ceiling is continuous or non-continuous obstruc-
minimum clearance of 1,75 m (5.75 ft.)
limited to 5 m (16.4 ft.). tion can be away from the Type ULF
from the ceiling.
AM29 diffuser is provided in Graph A.
Any installed cable trays must have a Non-continuous features at the ceiling Nozzle Spacing and Location
minimum clearance of 1,75 m (5.75 ft.) such as columns and light fixtures are Type ULF AM29 Nozzles are to be
from the ceiling. not considered obstructions. installed within the hot aisle contain-
The TYCO ULF AQUAMIST System ment system at a maximum spacing
Hot Aisle of 1,22 m (4 ft.) x 1,22 m (4 ft.), with
for the Protection of Data Process-
ing Equipment Rooms/Halls is Containment System a maximum distance of 0,61 m (2 ft.)
FM Approved for the protection of sin- Protection from walls.
gle-tier cable trays only. Hot aisle containment systems are Type ULF AM29 Nozzles are to be
Design Demand designed so that physical barriers installed outside of the hot aisle con-
The water supply shall be capable of divide the hot air exhausted from the tainment system at a maximum spacing
supplying 60 minutes of water to the data processing equipment from the of 3,7 m x 3,7 m (12 ft. x 12 ft.), with a
most remote eighteen (18) nozzles in cooler supply air flowing into the equip- maximum distance of 1,8 m (6 ft.) from
the system. ment racks. A typical layout is shown walls. The minimum spacing to prevent
in Figure 1. To protect hot aisle con- non-operation of adjacent nozzles is
Ventilation tainment systems, the nozzle spacing 1,8 m (6 ft.).
The ULF AQUAMIST System designed is altered from the typical above-floor The diffuser-to-ceiling distance must
to protect data processing equip- layout to the layouts as illustrated in be 45 to 102 mm (1.75 to 4 in.).
ment rooms and related facilities can Figures 4 and 5.
be installed in data processing equip-
ment rooms/halls that have a maximum Construction
horizontal air flow of 1,2 m/s (4 ft./sec.) Ceilings above the hot aisle are typi-
and a maximum upward air velocity of cally grated. Ceilings outside of the hot
1,5 m/s (4.9 ft./sec.) through the perfo- aisle containment system are to be of
rated floor openings. For rooms/halls smooth construction with a maximum
where ventilation exceeds these limits, slope of 5o (1/12). The barriers dividing
an automatic interlock for the shutdown the hot aisle from the cooler supply air
of the ventilation system must be pro- are considered walls.
vided in the protected area.
TFP2233
Page 6 of 14

OUTSIDE
FLOOR
AREA

PLASTIC GRATED NOZZLE BELOW


WALL CEILING GRATED CEILING

0,6 m
CONTAINMENT (2 ft)
SERVER MAX.

1,8 m 0,6 m
(6 ft) CONTAINMENT
SERVER (2 ft)
MAX. MAX.

NOZZLE
1,2 m
(4 ft)
MAX.

3,7 m 3,7 m 1,8 m


(12 ft) (12 ft) (6 ft)
MAX. MAX. MAX.

OUTSIDE
FLOOR WALL
AREA

FIGURE 4
ULF AQUAMIST FOR DATA CENTERS
TYPICAL HOT AISLE CONTAINMENT SYSTEM BELOW GRATED CEILING
TFP2233
Page 7 of 14

3,7 m 1,8 m GRATED PLASTIC


(12 ft) (6 ft) CEILING WALL CEILING
MAX. MAX.
TOP OF CABLE TRAY

44 to 102 mm
NOZZLE 1,75 m (1.75 to 4 in)
(5.74 ft) DIFFUSER-
MIN. DISTANCE TO-CEILING
CABLE
DISTANCE
TRAY

5,0 m (16.40 ft)


SERVER SERVER MAX. HEIGHT
CABINET CABINET
(SIDE VIEW) (SIDE VIEW)

FIGURE 5
ULF AQUAMIST FOR DATA CENTERS
TYPICAL HOT AISLE CONTAINMENT SYSTEM BELOW GRATED CEILING – ELEVATION VIEW

Below-floor The TYCO ULF AQUAMIST System Obstructions


Design Criteria for the Protection of Data Process- The maximum allowable vertical and
ing Equipment Rooms/Halls is horizontal distance that the bottom
TFPP offers two protection schemes FM Approved for the protection of sin- of a continuous or non-continuous
for below-floor coverage in data pro- gle-tier cable trays only. obstruction can be from the Type ULF
cessing equipment rooms/halls, an AM30 diffuser is provided in Graph B.
Area-of-Coverage Design and a Local Design Demand Non-continuous features at the ceiling
Application Design. The Area-of-Cov- The system needs only to be designed such as open web beams (minimum
erage Design uses a square nozzle for the most demanding areas. In data 70% open) are not to be considered
spacing to be employed throughout an processing equipment rooms/halls that obstructions.
entire below-floor area regardless of have both above and below floor pro-
cable tray size or location. The Local tection, both areas of protection shall The maximum allowable vertical and
Application Design uses linear nozzle be considered during design. If a data horizontal distance that the bottom of a
spacing and is designed to fit the spe- processing equipment room/hall is continuous or non-continuous obstruc-
cific cable trays in use. Either design designed only for below floor protec- tion can be away from the Type ULF
can be used alone or in conjunction tion, the water supply shall be capable AM29 diffuser is provided in Graph A.
with an above-floor design. The design of supplying 60 minutes of water to Non-continuous features at the ceiling
criteria for both designs are explained the most remote minimum number of such as columns are not to be consid-
in the sections that follow. nozzles in the system. For Area-of-Cov- ered obstructions.
erage Design, the minimum number of
Floor Height Area-of-Coverage Design
nozzles per design area is six (6). For
1,0 m (3.3 ft.) Local Application Design, the minimum Nozzle Type
number of nozzles per design area is ULF AM30
Protection Area
Unlimited four (4). Nozzle Temperature Ratings
Ventilation 57°C (135°F) and 68°C (155°F)
Nozzle Pressure
7,6 to 17,2 bar (110 to 250 psi) The ULF AQUAMIST System designed Nozzle Orientation
to protect data processing equip- The Type ULF AM30 Nozzle is to be
Construction ment rooms and related facilities installed in the upright position.
The TYCO ULF AQUAMIST System can be installed in data processing
for the Protection of Data Process- equipment rooms/halls that have a Nozzle Spacing and Location
ing Equipment Rooms/Halls is maximum upward air velocity of 1,5 m/s Type ULF AM30 Nozzles are to be
FM Approved for two below-floor con- (4.9 ft./sec.) through the perforated installed at a maximum spacing of
struction scenarios. The first type fea- floor openings. For rooms/halls where 3,7 x 3,7 m (12 x 12 ft.), with a maximum
tures cable trays installed between floor ventilation exceeds these limits, an distance of 1,8 m (6 ft.) from walls. The
grates, which is illustrated in Figure 6. automatic interlock for the shutdown minimum spacing to prevent non-oper-
The second type features cable trays of the ventilation system must be pro- ation of adjacent nozzles is 1,8 m (6
installed directly below floor grates, vided in the protected raised floor area. ft.). In scenarios where nozzle spacing
which is illustrated in Figure 7. dictates that a nozzle be installed on
the floor grate (including the edge), the
TFP2233
Page 8 of 14

ELEVATION
BELOW DIFFUSER, MILLIMETERS

300

SYSTEM PRESSURE, BAR

BELOW DIFFUSER, INCHES


MAXIMUM DISTANCE 'V'

SYSTEM PRESSURE, PSI


MAXIMUM DISTANCE 'V'
8,6 12
250 125
10
200
10,3 8
150 150
12,1 6
175
100 4
13,8 200
50 15,5 2 225
17,2 250
0 0
0,2 0,4 0,6 0,8 1,0 1,2 1,4 1,6 1,8 2,0 6 12 18 24 30 36 42 48 54 60 66 72 78
DISTANCE 'H' DISTANCE 'H'
TO OBSTRUCTION, TO OBSTRUCTION,
METERS INCHES
GRAPH B
TYPE ULF AM30
OBSTRUCTION CRITERIA

nozzle shall not be installed further than The maximum distance from the Type Concealed Space
51 mm (2 in.) inset from the edge of ULF AM29 Nozzle diffuser to the raised Design Criteria
the grate. floor is 197 mm (7.75 in.).
Nozzle Type
The maximum distance from the dif- A typical layout of the AM29 Local Type ULF AM30 Nozzle
fuser to the raised floor is 76 mm (3 in.). Application design is illustrated in
Figure 8. Nozzle Temperature Ratings
Typical layouts of the Area-of-Coverage 57°C (135°F) and 68°C (155°F)
design are illustrated in Figures 6 and 7. Type ULF AM30 Nozzles are to be
installed at a maximum linear spacing Nozzle Orientation
Design Demand The Type ULF AM30 Nozzle is to be
of 3,7 m (12 ft.), with a maximum dis-
There must be a minimum of six (6) installed in the upright position.
tance of 1,8 m (6 ft.) from walls. The
Type ULF AM30 Nozzles installed per
minimum spacing to prevent non-
design area. Nozzle Pressure
operation of adjacent nozzles is 1,8 m
7,6 to 17,2 bar (110 to 250 psi)
Local Application Design (6 ft.). The nozzles must be installed
Nozzle Type along the length of the cable tray offset Protection Area
ULF AM29 or ULF AM30 0 to 0,3 m (0 to 12 in.) from the side of Unlimited
the tray as shown in Figure 9.
Nozzle Temperature Ratings Nozzle Spacing and Location
Type ULF AM29: The maximum distance from the Type Type ULF AM30 Nozzles are to be
57°C (135°F) and 68°C (155°F) ULF AM30 Nozzle diffuser to the raised installed at a maximum spacing of
floor is 76 mm (3 in.). 3,7 x 3,7 m (12 x 12 ft.), with a maximum
Type ULF AM30: distance of 1,8 m (6 ft.) from walls. The
57°C (135°F) and 68°C (155°F) A typical layout of the AM30
Local Application design is illustrated minimum spacing to prevent non-oper-
Nozzle Orientation in Figure 9. ation of adjacent nozzles is 1,8 m (6 ft.).
The Type ULF AM29 Nozzle is to be The maximum distance from the dif-
installed in the pendent position. Design Demand
There must be a minimum of four (4) fuser to ceiling is 76 mm (3 in.).
The Type ULF AM30 Nozzle is to be Type ULF AM29 Nozzles or four (4) Design Demand
installed in the upright position. Type ULF AM30 Nozzles installed The water supply shall be capable of
Nozzle Spacing and Location along the length of the cable tray in the supplying 60 minutes of water to the
Type ULF AM29 Nozzles are to be most hydraulically remote location per most remote six (6) nozzles in the
installed at a maximum linear spacing design area. system.
of 2,4 m (8 ft.) with a maximum dis- Construction
tance of 1,8 m (6 ft.) from walls. The The concealed space is to be con-
minimum spacing to prevent non-oper- structed with noncombustible
ation of adjacent nozzles is 1,8 m (6 ft.). materials.
The Nozzles must be installed along
the length of the cable tray offset 0 to Ceilings are to be of smooth construc-
0,3 m (0 to 12 in.) from the side of the tion with a maximum slope of 5o (1/12).
tray as shown in Figure 8. The maximum height of the concealed
space is limited to 1 m (3.3 ft.).
TFP2233
Page 9 of 14

3,7 m (12 ft)


0 to 3,7 m MAX.
(0 to 12 ft)
3,7 m (12 ft)
MAX.

CABLE
TRAY NOTES:
0 to 3,7 m
UPRIGHT 1. NOZZLES CAN BE LOCATED
(0 to 12 ft)
NOZZLE 1 DIRECTLY BENEATH FLOOR
GRATES 51 mm (2 in) MAX.
FLOOR FROM EDGE
GRATE

PLAN RAISED
FLOOR

76 mm (3 in)
DIFFUSER-TO-
1,0 m (3.28 ft) 305 mm (12 in) CABLE UPRIGHT RAISED FLOOR RAISED
MAX. HEIGHT MIN. CLEARANCE TRAY NOZZLE MAX. DISTANCE FLOOR

ELEVATION
FIGURE 6
ULF AQUAMIST FOR DATA CENTERS
TYPICAL BELOW-FLOOR AREA-OF-COVERAGE DESIGN CRITERIA – CABLE TRAY BETWEEN GRATES
TFP2233
Page 10 of 14

3,7 m (12 ft)


MAX.

3,7 m (12 ft) 0 to 3,7 m


MAX. (0 to 12 ft)

0 to 3,7 m CABLE FLOOR


(0 to 12 ft) TRAY GRATE

NOTES:
UPRIGHT 1. NOZZLES CAN BE LOCATED
NOZZLE 1 DIRECTLY BENEATH FLOOR
GRATES 51 mm (2 in) MAX.
FROM EDGE

PLAN RAISED
FLOOR

76 mm (3 in)
DIFFUSER-TO-
1,0 m (3.28 ft) 305 mm (12 in) CABLE UPRIGHT RAISED FLOOR RAISED
MAX. HEIGHT MIN. CLEARANCE TRAY NOZZLE MAX. DISTANCE FLOOR

ELEVATION
FIGURE 7
ULF AQUAMIST FOR DATA CENTERS
TYPICAL BELOW-FLOOR AREA-OF-COVERAGE DESIGN CRITERIA – CABLE TRAY UNDER GRATES
TFP2233
Page 11 of 14

Ventilation
The ULF AQUAMIST System designed Installation Note: TYCO Flexible Hose Connections
are only FM Approved at a maximum
to protect data processing equip- service pressure of 12 bar (175 psi) and
All Listed materials are to be installed
ment rooms and related facilities can can therefore only be used in systems
in accordance with their FM Approval
be installed in concealed spaces that where the supply is no greater than
Listing. All other materials and devices
have a maximum upward air velocity of 12 bar (175 psi). TYCO Flexible Hose
are to be installed in accordance
1,5 m/s (4.9 ft./sec.) through the perfo- Connections cannot be used in con-
with the applicable manufacturer’s
rated floor openings. For rooms/halls junction with the TYCO AQUAMIST
instructions.
where ventilation exceeds these limits, MCC Pump Skid.
an automatic interlock for the shutdown
of the ventilation system must be pro- NOTICE
vided in the protected raised floor area. Pipe, tube, and nipples are to have the
burrs and fins removed after cutting.
Obstructions Apply pipe-thread sealant to male
The maximum allowable vertical and threads only. When using TEFLON tape,
horizontal distance that the bottom do not start the tape any closer than
of a continuous or non-continuous one thread from the inlet of any pipe
obstruction can be from the Type ULF connection or the AQUAMIST Nozzles
AM30 diffuser is provided in Graph B. (strainer end).
Non-continuous features at the ceiling
such as open web beams (minimum In order to remove foreign materials
70% open) are not to be considered that may have entered underground
obstructions. mains during the course of the instal-
lation, underground mains and lead-in
Detection connections to system risers are to
be thoroughly flushed, as required by
For data processing equipment NFPA 750, “Standard on Water Mist
rooms and halls, FM Approved very Fire Protection Systems,” before con-
early warning fire detection (VEWFD) nection is made to the system piping.
systems are to be installed in accor- Refer to the Flushing Connection
dance with FM Global Data Sheet 5-32, requirements under the System Design
Data Centers and Related Facilities, Criteria section.
and the manufacturer’s instructions. Prior to installation, each pipe or tube
Proper placement of the smoke detec- section is to be swabbed internally, by
tion needs to be considered due to the running a clean rag, sponge, or other
high air flow environment based upon absorbent material down through it, as
the hazard configuration. At a minimum, needed to meet the internal cleanliness
placement of smoke detection in the requirements of NFPA 750, “Standard
return air flow is recommended. on Water Mist Fire Protection Systems.”
Any attached appurtenances, includ-
Operation ing the AQUAMIST Nozzles, subject to
a system working (service) pressure of
The mechanisms by which the TYCO 12 bar (175 psi) or less are to be hydro-
Ultra Low Flow AQUAMIST System statically tested at 13,8 bar (200 psi) or,
described herein acts to control cable 3,5 bar (50 psi) in excess of the system
fires can be a combination of the fol- working pressure, whichever is greater.
lowing factors:
For system working pressures in excess
• heat extraction from the fire as of 12 bar (175 psi), the hydrostatic pres-
water is converted into vapor and sure test is to be performed at 150% of
the fuel is cooled the normal working pressure.
• reduced oxygen levels as the water The hydrostatic test pressure is to be
vapor displaces oxygen near the fire maintained without loss of pressure for
• direct impingement wetting and two (2) hours. The loss in pressure is
cooling of the combustibles to be determined by either a drop in
gauge pressure or visual leakage.
• enveloping of the protected area
to pre-wet adjacent combusti- For a single interlock preaction system
bles, cool gases and other fuels design, refer to Technical Data Sheet
in the area, as well as block the TFP1420 for system installation instruc-
transfer of radiant heat to adjacent tions and the valve setting procedure.
combustibles When using TYCO Flexible Hose Con-
nections in this system, refer to Techni-
cal Data Sheet TFP720 for installation
instructions.
TFP2233
Page 12 of 14

FLOOR
GRATE NOTES:
1. NOZZLES CAN BE LOCATED 2. THIS DESIGN APPROACH
ON EITHER SIDE OF CABLE ALSO APPLIES TO FLOOR
TRAY BUT NOT DIRECTLY GRATE-OVER-CABLE TRAY
CABLE ABOVE CONSTRUCTION
TRAY

0 to 305 mm AM29
(0 to 12 in) 1 2,4 m (8 ft) NOZZLE
MAX.

PLAN RAISED
FLOOR

197 mm (7.75 in)


DIFFUSER-TO-
1,0 m (3.28 ft) 305 mm (12 in) CABLE AM29 RAISED FLOOR RAISED
MAX. HEIGHT MIN. CLEARANCE TRAY NOZZLE MAX. DISTANCE FLOOR

ELEVATION
FIGURE 8
ULF AQUAMIST FOR DATA CENTERS
TYPICAL BELOW-FLOOR LOCAL APPLICATION DESIGN CRITERIA – AM29
TFP2233
Page 13 of 14

FLOOR
GRATE NOTES:
1. NOZZLES CAN BE LOCATED 2. THIS DESIGN APPROACH
ON EITHER SIDE OF CABLE ALSO APPLIES TO FLOOR
TRAY BUT NOT DIRECTLY GRATE-OVER-CABLE TRAY
CABLE ABOVE CONSTRUCTION
TRAY

0 to 305 mm AM30
(0 to 12 in) 1 3,7 m (12 ft) NOZZLE
MAX.

PLAN RAISED
FLOOR

76 mm (3 in)
DIFFUSER-TO-
1,0 m (3.28 ft) 305 mm (12 in) CABLE AM30 RAISED FLOOR RAISED
MAX. HEIGHT MIN. CLEARANCE TRAY NOZZLE MAX. DISTANCE FLOOR

ELEVATION
FIGURE 9
ULF AQUAMIST FOR DATA CENTERS
TYPICAL BELOW-FLOOR LOCAL APPLICATION DESIGN CRITERIA – AM30
TFP2233
Page 14 of 14

Care and Underground lead-in connections to


the system riser are to be flushed at Limited
Maintenance least annually at a flow rate not less
than the water demand rate of the Warranty
TYCO Ultra Low Flow AQUAMIST system. The flushing operation is to be For warranty terms and conditions, visit
Water Mist Systems must be main- continued for a sufficient time to ensure www.tyco-fire.com.
tained and serviced in accordance with thorough cleaning.
this section. The strainers in the TYCO AQUAMIST
Pump Skid must be cleaned after every
Ordering
Before closing a fire protection system
control valve for inspection or main- system operation.
Procedure
tenance work on the fire protection Responsibility lies with the owner for
system that it controls, permission to the inspection, testing, and mainte- Ordering information is provided in
shut down the affected fire protection nance of their fire protection system separate component Technical Data
system must first be obtained from and devices in compliance with this Sheets. Refer to System Component
the proper authorities and all person- document, as well as with the require- section for data sheet descriptions and
nel who may be affected by this action ments of the NFPA 750, “Standard on numbers.
must be notified. Water Mist Fire Protection Systems,” in
After placing a fire protection system addition to the standards of the author-
in service, notify the proper authorities ity having jurisdiction. Contact the
and advise those responsible for moni- installing contractor or product manu-
toring proprietary and/or central station facturer with any questions.
alarms. For a single-interlock preaction system
Exercise care to avoid damage to design, refer to Technical Data Sheet
AQUAMIST Nozzles before, during TFP1420 for system maintenance
and after installation. Never paint, plate, procedures.
coat, or otherwise alter nozzles after
they leave the factory. Replace nozzles
damaged by dropping, striking, wrench
twisting, wrench slippage, or the like.
Water mist systems for fire protec-
tion service require regularly sched-
uled care and maintenance by trained
personnel. It is recommended that the
AQUAMIST Nozzles be periodically
inspected for loading/obstructions,
improper orientation, or other evidence
of impaired protection. The inspections
should be scheduled at least annually
but more frequently if found to be nec-
essary and corrective action taken
immediately to ensure that the AQUA-
MIST Nozzles will perform as intended
in the event of a fire.
Water mist systems for fire protection
should be inspected, tested, and main-
tained by a qualified Inspection Service
in accordance with all of the following:
• NFPA 25, “Standard for the Inspec-
tion, Testing, and Maintenance
of Water-based Fire Protection
Systems”
• FM Global Property Loss Prevention
Data Sheet 2-81
• FM Global Property Loss Prevention
Data Sheet 4-2
• local requirements and/or national
codes

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright © 2015 Tyco Fire Products, LP. All rights reserved.