FIELD QUALITY ASSURANCE PLAN/ITP

Manufacturer’s Name & Address Project: Supply of HVAC System for


Main Supplier: M/s: Anemo Projects Pvt Ltd
Anemo Integrated operation Center IOC ,Jamnagr
Projects Pvt Item: Field Quality Plan for QP No.: AAPL /000 Package: HVAC
Limited Erection of Mechanical Equipment Rev. No.: 00 Contract no.:305/240641155
Date: 19-12-2023 Main Supplier: Anemo Projects Pvt Limited
Sub-Systems: RIL IOC BUILDING
Page 13 of 16
Sl. Characteristics/ Class of Type of Quantum Reference Acceptance Inspection
Activity & Operation Format of Record
No. Instruments Check Check of Check Documents Norms ( ANEMO /RIL )
1 2 3 4 5 6 7 8 9 D* 10

(a) Check for Erection Erection


location, supports, C Visual 100% Manual/ Manual/
Register/
- Witness By Anemo
Checklist
fixing arrangement Drawing Drawing
30 Ventilation Fan
Erection Erection
Protocol/ witness by Anemo
(b) Trial run B Visual 100% Manual/ Manual/
Checklist surveillance by RIL
Drawing Drawing
31 Air Conditioning

31.1 Refer Sl. No.: 1.0, 2.0, 3.0, 4.0 & 5.0 (as applicable)
100% Erection Erection
(a) Fabrication of GI Visual/Meas Register/
C Manual/ Manual/ - Witness by Anemo
ducting urement Checklist
Drawing Drawing
100% Erection Erection
Visual/Meas Register/ witness by anemo
(b) Erection of Duct C Manual/ Manual/ -
urement Checklist
Drawing Drawing
GI Ducting, 100% Erection Erection
31.2 grilles/diffusers, (c) Insulation of Visual/Meas Register/
duct
C
urement
Manual/ Manual/
Checklist
- witness by Anemo
filters Drawing Drawing
(d) Erection of 100% Erection Erection
grilles, diffuses & C
Visual/Meas
Manual/ Manual/
Register/
- witness by Anemo
urement Checklist
fitters Drawing Drawing
Erection Erection
(e) Installation of
C Visual 100% Manual/ Manual/
Register/
-
Witness by Anemo
Air Conditioner Checklist
Drawing Drawing

FORMAT NO: AAPL/000 13/16 ENGG. DIV/QA & I


FIELD QUALITY ASSURANCE PLAN /ITP
Manufacturer’s Name & Address Project: Supply of HVAC System for
Main Supplier: M/s:Anemo Projects Pvt Ltd Integrated operation Center IOC ,Jamnagr
Anemo Item: Field Quality Plan for QP No.: AAPL /000 Package: HVAC
Projects Pvt Erection of Mechanical Equipment Rev. No.: 00 Contract no.: 305/240641155
Limited Date: 19-12-2023 Main Supplier: Anemo Projects Pvt Limited
Sub-Systems: RIL IOC BUILDING
Page 14 of 16
Sl. Characteristics/ Class of Type of Quantum Reference Acceptance
Activity & Operation Format of Record Remarks
No. Instruments Check Check of Check Documents Norms
1 2 3 4 5 6 7 8 9 D* 10

WPS/PQR/WPQ C Visual 100% ASME IX ASME IX Report Revised by Anemo


Erection Erection
Welding of pipe,
C Visual 100% Manual/ Manual/
Register/
- Witness by Anemo
valve and fittings Checklist
Drawing Drawing
31.3 CHW Water pipe line
Butt weld- surface No relevant Witness by Anemo
B DP test 10% ASTM-E-165 DPT report
defect indication
Visual & Erection Erection
Routing, location,
C Measuremen 100% Manual/ Manual/
Register/
- Witness by Anemo
elevation Checklist
t Drawing Drawing
Positioning of base
Erection Erection
frame and Register/ Witness by Anemo
C Visual 100% Manual/ Manual/ -
alignment of fan & Checklist
Drawing Drawing
motor
1.5 times
system
Air handling unit and
31.4 design
fan Pressure test, Witness by Anemo
pressure or
leakage test for Protocol/ Servelliance by RIL
B Hydro test 100% 2 times No leakage
water Checklist
working
line/refrigerant line
pressure
whichever
is higher

FORMAT NO: AAPL/000 14/16 ENGG. DIV/QA & I


FIELD QUALITY ASSURANCE PLAN
Manufacturer’s Name & Address Project: Supply of HVAC System for
Main Supplier: MS Anemo Projects Pvt Ltd
Integrated operation Center IOC ,Jamnagr
Anemo Item: Field Quality Plan for QP No.: AAPL /000 Package: HVAC
Projects Pvt Erection of Mechanical Equipment Rev. No.: 00 Contract no.: 305/240641155
Limited Date: 19-12-2023 Main Supplier: Anemo Projects Pvt Limited
Sub-Systems: RIL IOC BUILDING
Page 15 of 16
Sl. Characteristics/ Class of Type of Quantum Reference Acceptance
Activity & Operation Format of Record Remarks
No. Instruments Check Check of Check Documents Norms
1 2 3 4 5 6 7 8 9 D* 10

Visual & Erection Erection


Orientation, Register/
C Measuremen 100% Manual/ Manual/ - Witness by Anemo
leveling, positioning Checklist
PAC/Split AC/Window t Drawing Drawing
31.5
AC Visual & Erection Erection
Run test of PAC Protocol/
A Measuremen 100% Manual/ Manual/ Witness by Anemo
assembly Checklist
t Drawing Drawing Servelliance by RIL
Visual & Erection Erection
Orientation, Register/
C Measuremen 100% Manual/ Manual/ - Witness by Anemo
leveling, positioning Checklist
t Drawing Drawing
fixing &
Visual & Erection Erection
Air cooled Chiller Unit Positioning Of Register/
31.6 C Measuremen 100% Manual/ Manual/ -
Units Checklist Witness by Anemo
t Drawing Drawing
Visual & Erection Erection
Fixing of spray set & Register/ Witness by Anemo
C Measuremen 100% Manual/ Manual/ -
accessories Checklist
t Drawing Drawing
Erection Erection Witness by Anemo
Completeness of Protocol/
31.7 A Visual 100% Manual/ Manual/ Servillience by RIL
system Checklist
Drawing Drawing
Notes:-

FORMAT NO: AAPL/000 15/16 ENGG. DIV/QA & I


FIELD QUALITY ASSURANCE PLAN
Manufacturer’s Name & Address Project: Supply of HVAC System for
Main Supplier: MS Anemo Projects Pvt Ltd
Integrated operation Center IOC ,Jamnagr
Item: Field Quality Plan for QP No.: AAPL /000 Package: HVAC
Anemo Erection of Mechanical Equipment Rev. No.: 00 Contract no.: 305/240641155
Projects Pvt Date: 19-12-2023 Main Supplier: Anemo Projects Pvt Limited
Limited Sub-Systems: RIL IOC BUILDING
Page 16 of 16
Sl. Characteristics/ Class of Type of Quantum Reference Acceptance
Activity & Operation Format of Record Remarks
No. Instruments Check Check of Check Documents Norms
1 2 3 4 5 6 7 8 9 D* 10

ONLY FOR SUPPLY AIR DUCT

LEGEND: *Records identified with “TICK ( )” DOC…………………………. REV.: …CAT: …


shall be essentially included by contractor in
QA Documentation.
‘A’ SHALL BE WITNESSED BY NTPC FQA,
MANUFACTURER/ ‘B’ SHALL BE WITNESSED BY NTPC
MAIN-SUPPLIER
SUB-SUPPLIER ERECTION/CONSTRUCTION DEPT. and
APPROVAL
SIGNATURE ‘C’ SHALL BE WITNESSED BY MAIN SUPPLIER. REVIEWED BY APPROVED BY
SEAL

FORMAT NO: QS-01-QAI-P-09/F2-R1 16/16 ENGG. DIV/QA & I





















