You are on page 1of 34

目 录 Contents

1.480V化水PCA段……………………………………………………………………………………………
480V chemical water PCA section………………………………………………………………………

2.480V化水PCB段……………………………………………………………………………………………
480V chemical water PCB sectionn……………………………………………………………………
3.循环水泵房MCC段…………………………………………………………………………………………
Recycling water pump MCC section……………………………………………………………………
4.综合水泵房MCC段…………………………………………………………………………………………
General water pump room MCC section…………………………………………………………………
5.1号机480V保安PC段………………………………………………………………………………………
unit 1, 480V emergency PC section …………………………………………………………………
6.2号机480V保安PC段………………………………………………………………………………………
unit 2, 480V emergency PC section …………………………………………………………………
7.3号机480V保安PC段 ………………………………………………………………………………………
unit 3, 480V emergency PC section……………………………………………………………………
8.480V输煤PCA段 ……………………………………………………………………………………………
480V coal handling PCA section…………………………………………………………………………
9.480V输煤PCB段 ……………………………………………………………………………………………
480V coal handling PCB section…………………………………………………………………………
10.480V#2转运站MCC段………………………………………………………………………………………
480V#Transfer station MCC section ……………………………………………………………………
11.480V#3转运站MCC段………………………………………………………………………………………
480V#Transfer station MCC section ……………………………………………………………………
12.480V碎煤机室MCC段………………………………………………………………………………………
480V Crusher room MCC section ………………………………………………………………………
13.480V油泵房MCC段…………………………………………………………………………………………
480V Oil pump house MCC section ………………………………………………………………………
14.480V公用PCA段……………………………………………………………………………………………
480V Public PCA section …………………………………………………………………………………
15.480V公用PCB段……………………………………………………………………………………………
480V Public PCB Section …………………………………………………………………………………
16.480V煤仓间MCC段 198.480V煤仓间MCC段 ……………………………………………………………
480V COAL BUNKER BAY MCC SWITCHGEAR ………………………………………………………………
17.480V工作PC1A段 …………………………………………………………………………………………
480V working PC1A section ………………………………………………………………………………
18.480V工作PC1B段 …………………………………………………………………………………………
480 work PC1B section……………………………………………………………………………………
19.480V工作PC2A段 …………………………………………………………………………………………
480V work PC2A section……………………………………………………………………………………
20.480V工作PC2B段 …………………………………………………………………………………………
480V work PC2B section …………………………………………………………………………………
21.480V工作PC3A段 …………………………………………………………………………………………
480V work PC3A section …………………………………………………………………………………

22.480V工作PC3B段 …………………………………………………………………………………………
480V work PC3B section …………………………………………………………………………………
23.1号机480V汽机房2MCC……………………………………………………………………………………
Unit 1 480V turbine house 2 MCC section…………………………………………………………
24.2号机480V汽机房2MCC……………………………………………………………………………………
Unit 2 480V turbine house 2 MCC section…………………………………………………………
25.3号机480V汽机房2MCC……………………………………………………………………………………
Unit 3 480V turbine house 2 MCC section…………………………………………………………
26.480VPT ……………………………………………………………………………………………………
480VPT ……………………………………………………………………………………………………
s
…………………………………………1
…………………………………………1

…………………………………………3
…………………………………………3
…………………………………………5
…………………………………………5
…………………………………………7
…………………………………………7
…………………………………………8
…………………………………………8
…………………………………………9
…………………………………………9
………………………………………10
………………………………………10
………………………………………11
………………………………………11
………………………………………12
………………………………………12
………………………………………13
………………………………………13
………………………………………14
………………………………………14
………………………………………15
………………………………………15
………………………………………16
………………………………………16
………………………………………17
………………………………………17
………………………………………18
………………………………………18
………………………………………19
………………………………………19
………………………………………20
………………………………………20
………………………………………21
………………………………………21
………………………………………22
………………………………………22
………………………………………23
………………………………………23
………………………………………24
………………………………………24

………………………………………25
………………………………………25
………………………………………26
………………………………………26
………………………………………27
………………………………………27
………………………………………28
………………………………………28
………………………………………29
………………………………………29
继电保护定值通知单
Relay Protection Settings Notice Sheet
设备名称:480V化水PCA段 定值单号:2015-MSMS-015
Equipment:480V chemical water PCA section Setting value No:2015-MSMS-015

作废定值单:
Invalid setting value sheet:

负载CT比 反向热保护 过流保护over 电流相位丢 长启动保护 堵塞保护 接地保护 欠电压


失Current
Load CT Reverse heat protection currentprotect phase Long start up Block Grounding Under
ratio ion loss protection protection protection voltage
电流量
电动机 程最大
额定功 电动机 马达保护器 Current 值(A)
序号 设备名称 率 型号 故障阈 故障阈值(内部
Item Equipment Nomina 额定电
流 Motor measuri FLCmi
ng n(A)
警告阈
电机脱 故障复
故障复 值 故障阈值 故障阈值
告警阈
接地电 %FLCmin)(外
故障阈值
l protection range 值 扣等级 位超时 位阈值 故障超 (%FLC)F 故障超 (%FLC) 故障超 (%FLC) 值 流模式 故障超 部A) 故障超 (Un)
FLC(A) alarm Fault 时 超时 时 Fault 时 Fault Ground 时 Fault
Primar Second power type
(kW) Max.Val FLC1( thresh Motor Fault reset Fault ault over Fault threshol Fault threshol Alarm ing Fault threshold 时 Fault
thresho overti thresho time
y ary A) trippin reset thresh Fault threshol
ue old g overti overti d overti d old curren overtim value overtim d
(A) value grade ld me ld me value me value t e (inside
me value value value
value (%FLC) (%FLC) mode %FLCmin)
(%FLC) (outside A)

手提卸药泵A
Hand unload dosing pump A
1 1 1 0.55 1.09 LTMR08MBD 8 0.4 1.145 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 273% 5s 70%
卸次氯酸
2 UNLOAD NaClO 1 1 3 5.925 LTMR08MBD 8 0.4 6.221 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
浓缩池排泥泵A
sludge drain PumpA in
3 concentration tank 1 1 4 6.32 LTMR27MBD 27 1.35 6.636 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 468% 5s 70%
罗茨风机A(废水处理室外)
Roots fan A (outside of
waste water treatment room)
4 1 1 37.5 59.25 LTMR100MBD 100 5 62.21 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
卸酸泵
Unload acid pump
5 1 1 3 5.925 LTMR08MBD 8 0.4 6.221 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
澄清池污泥输送泵A
sludge conveying pump A
in clarifying tank
6 1 1 4 6.32 LTMR27MBD 27 1.35 6.636 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 468% 5s 70%
罗茨风机A(废水池上方)
Roots fan A (upper of waste
7 water tank) 1 1 55 86.9 LTMR100MBD 100 5 91.25 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
废水泵A
8 waste water pump A 1 1 11 17.38 LTMR27MBD 27 1.35 18.25 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
反洗水泵AA
9 backwashing pump AA 1 1 37 58.46 LTMR100MBD 100 5 61.38 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
除碳风机A
10 decarbon fan A 1 1 2.2 4.345 LTMR08MBD 8 0.4 4.562 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%

第2-1页/共29页
废水泵C
waste waterpump C
11 1 1 11 17.38 LTMR27MBD 27 1.35 18.25 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
清水泵A
clarifying water pump A
12 1 1 18.5 29.23 LTMR100MBD 100 5 30.69 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
中间水泵A
Interim water pump A
13 1 1 7.5 11.85 LTMR27MBD 27 1.35 12.44 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%

除盐水泵A
dimineralized water pump A
14 1 1 15 23.7 LTMR100MBD 100 5 24.89 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 474% 5s 70%
再生水泵A
15 rejuvenated water pump A 1 1 4 6.32 LTMR27MBD 27 1.35 6.636 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 468% 5s 70%
罗茨风机A(水泵间)
roots fan A
(between pumps)
16 1 1 12 18.96 LTMR100MBD 100 5 19.91 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 379% 5s 70%
清净水泵A
clean water pump A
17 1 1 15 23.7 LTMR100MBD 100 5 24.89 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 474% 5s 70%

1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:480V化水PCB段 定值单号:2015-MSMS-016
Equipment: 480V chemical water PCB section Setting value No:2015-MSMS-016

第3-1页/共29页
作废定值单:
Invalid setting value sheet:
电流相位丢
负载CT比 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
Load CT Reverse heat protection currentprotect Current Long start up Block Grounding Under
phase
ratio ion loss protection protection protection voltage
电流量
电动机 程最大
额定功 电动机 马达保护器 Current 值(A)
序号 设备名称 率 型号 故障阈 故障阈值(内部
Item Equipment Nomina 额定电
流 Motor measuri FLCmi
ng n(A)
警告阈
电机脱 故障复
故障复 值 故障阈值 故障阈值
告警阈
接地电 %FLCmin)(外
故障阈值
l protection 值 位阈值 故障超 (%FLC)F 故障超 (%FLC) 故障超 (%FLC) 流模式 故障超 部A)
FLC(A) range 扣等级 位超时 时 值 故障超 (Un)
alarm Fault 超时 时 Fault 时 Fault Ground 时 Fault
Primar Second power type Max.Val FLC1( Motor Fault ault Alarm 时 Fault
y ary (kW) A)
thresh
trippin reset
reset Fault thresho over Fault threshol Fault threshol
thresh
ing Fault threshold
Fault threshol
ue old g overti thresho overti time overti d overti d old curren overtim value overtim d
(A) value ld me ld me value me value t e (inside
grade me value value (%FLC) (%FLC) value mode %FLCmin) value
(%FLC) (outside A)

卸碱泵UNLOAD CAUSTIC PUMP


1 1 1 3 5.925 LTMR08MBD 8 0.4 6.221 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
澄清池污泥输送泵BSLUDGE
PUMP B FOR INCLINED PLATE
2 CLARIFIER 1 1 4 6.32 LTMR27MBD 27 1.35 6.636 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 468% 5s 70%
罗茨风机B(废水池上
方)ROOTS BLOWER B(UPON
WASTE WATER STORAGE POND)
3 1 1 55 86.9 LTMR100MBD 100 5 91.25 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
浓缩池排泥泵B SLUDGE PUMP B
4 FOR CONCENTRATION POOL 1 1 4 6.32 LTMR27MBD 27 1.35 6.636 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 468% 5s 70%
罗茨风机B(废水处理室外)
ROOTS BLOWER B(UPON WASTE
WATER STORAGE POND)
5 1 1 37.5 59.25 LTMR100MBD 100 5 62.21 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
手提卸药泵B
6 PORTABLE PUMP B 1 1 0.55 1.09 LTMR08MBD 8 0.4 1.145 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 273% 5s 70%
卸凝聚剂泵
UNLOAD COAGULANT PUMP
7 1 1 3 5.925 LTMR08MBD 8 0.4 6.221 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
中间水泵C
INTERMEDIATE WATER PUMP C
8 1 1 7.5 11.85 LTMR27MBD 27 1.35 12.44 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
罗茨风机B(水泵间)
ROOT'S BLOWER B (WATER PUMP
9 HOUSE) 1 1 12 18.96 LTMR100MBD 100 5 19.91 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 379% 5s 70%
清净水泵B
10 CLARIFIED WATER PUMP B 1 1 15 23.7 LTMR100MBD 100 5 24.89 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 474% 5s 70%
中间水泵B
INTERMEDIATE WATER PUMP B
11 1 1 7.5 11.85 LTMR27MBD 27 1.35 12.44 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%

再生水泵B
REGENERATION WATER PUMP B
12 1 1 4 6.32 LTMR27MBD 27 1.35 6.636 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 468% 5s 70%

除盐水泵B
Demineralized water pump B
13 1 1 15 23.7 LTMR100MBD 100 5 24.89 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 474% 5s 70%

第4-1页/共29页
除碳风机C
14 Decarbon fan C 1 1 2.2 4.345 LTMR08MBD 8 0.4 4.562 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
废水泵D
15 Waste water pump D 1 1 11 17.38 LTMR27MBD 27 1.35 18.25 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
清水泵B
16 Clean water pump D 1 1 18.5 29.23 LTMR100MBD 100 5 30.69 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
除碳风机B
17 Decarbon fan B 1 1 2.2 4.345 LTMR08MBD 8 0.4 4.562 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
废水泵B
18 Waste water pump B 1 1 11 17.38 LTMR27MBD 27 1.35 18.25 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
反洗水泵AB
19 Backwashing pumpAB 1 1 37 58.46 LTMR100MBD 100 5 61.38 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
反洗水泵B
Backwashing pump B
20 1 1 22 34.76 LTMR100MBD 100 5 36.5 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%

1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet
3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:循环水泵房MCC段 定值单号:2015-MSMS-017
Equipment: Recycling water pump MCC section Setting value No:2015-MSMS-017
作废定值单:
Invalid setting value sheet:

第5-1页/共29页
电流相位丢
负载CT比 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
Load CT Reverse heat protection currentprotect Current Long start up Block Grounding Under
phase
ratio ion loss protection protection protection voltage
电流量
电动机 程最大
额定功 电动机 马达保护器 Current 值(A)
序号 设备名称 率 额定电 型号 measuri FLCmi 故障阈 故障阈值(内部
Item Equipment Nomina 流 Motor ng n(A) 警告阈
电机脱 故障复 位阈值 故障超
故障复 值 故障阈值 故障阈值
告警阈
接地电 %FLCmin)(外
故障阈值
l protection 值 (%FLC)F 故障超 (%FLC) 故障超 (%FLC) 流模式 故障超 部A)
FLC(A) range alarm 扣等级 位超时 Fault 时 超时 时 Fault 时 Fault 值 Ground 时 Fault 故障超 (Un)
Primar Second power type Max.Val FLC1( Motor Fault ault Alarm 时 Fault
(kW) thresh trippin reset reset Fault over Fault threshol Fault threshol ing Fault threshold
thresho overti thresho time
y ary ue A) thresh Fault threshol
old overti d overti d curren overtim value
(A) value g overti ld
me ld me value me value old t e (inside overtim d
grade me value value value
value (%FLC) (%FLC) mode %FLCmin)
(%FLC) (outside A)

铸铁闸门启闭机A CAST IRON


GATE HOIST A
1 1 1 1.5 2.96 LTMR08MBD 8 0.4 3.108 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
卸次氯酸钠泵A UNLOAD NaClO
2 PUMP A 1 1 3 5.93 LTMR08MBD 8 0.4 6.227 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
循环水泵自润滑加压泵A SELF-
LUBRICATING PUMP OF C.W.
3 PUMP A 1 1 5 7.9 LTMR27MBD 27 1.35 8.295 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
事故水泵A ACCIDENT WATER
4 PUMP A 1 1 15 23.7 LTMR100MBD 100 5 24.89 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 474% 5s 70%
滤网冲洗水泵A WASHING PUMP
A
5 1 1 50 79 LTMR100MBD 100 5 82.95 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
铸铁闸门启闭机B CAST IRON
6 GATE HOIST B 1 1 1.5 2.96 LTMR08MBD 8 0.4 3.108 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
卸次氯酸钠泵B UNLOAD NaClO
7 PUMP B 1 1 3 5.93 LTMR08MBD 8 0.4 6.227 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
循环水泵自润滑加压泵B SELF-
LUBRICATING PUMP OF C.W.
8 PUMP B 1 1 5 7.9 LTMR27MBD 27 1.35 8.295 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
事故水泵B ACCIDENT WATER
9 PUMP B 1 1 15 23.7 LTMR100MBD 100 5 24.89 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 474% 5s 70%
滤网冲洗水泵B WASHING PUMP
10 B FOR TRAVELLING SCREEN 1 1 50 79 LTMR100MBD 100 5 82.95 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
铸铁闸门启闭机C CAST IRON
GATE HOIST C
11 1 1 1.5 2.96 LTMR08MBD 8 0.4 3.108 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
循环水泵自润滑加压泵C SELF-
LUBRICATING PUMP OF C.W.
12 PUMP C 1 1 5 7.9 LTMR27MBD 27 1.35 8.295 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%

滤网冲洗水泵C WASHING PUMP


C FOR TRAVELLING SCREEN
13 1 1 50 79 LTMR100MBD 100 5 82.95 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%

1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

第6-1页/共29页
2.定值单中没有保护均退出。
Quit if no protection in setting value sheet
3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:综合水泵房MCC段 定值单号:2015-MSMS-018
Equipment:General water pump room MCC section Setting value No:2015-MSMS-018
作废定值单:
Invalid setting value sheet:
电流相位丢
负载CT比 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
Load CT Reverse heat protection currentprotect Current Long start up Block Grounding Under
phase
ratio ion loss protection protection protection voltage
电流量
电动机 程最大
额定功 电动机 马达保护器 Current 值(A)
序号 设备名称 率 额定电 型号 measuri FLCmi
Item Equipment Nomina 流 Motor ng n(A) 第7-1页/共29页
l protection
power FLC(A) type range
Max.Val
(kW) ue
(A)
电流量
电动机 程最大
额定功 电动机 马达保护器 Current 值(A)
序号 设备名称 率 型号 故障阈 故障阈值(内部
Item Equipment Nomina 额定电
流 Motor measuri FLCmi
ng n(A) 警告阈 故障复 值 故障阈值 故障阈值 接地电 %FLCmin)(外
l protection 电机脱 故障复 故障超 (%FLC)F 告警阈 故障阈值
值 位阈值 故障超 (%FLC) 故障超 (%FLC) 流模式 故障超 部A)
FLC(A) range 扣等级 位超时 时 值 故障超 (Un)
Primar Second power type alarm Fault ault 超时 时 Fault 时 Fault Ground 时 Fault
Max.Val FLC1( Motor Fault Alarm 时 Fault
trippin reset thresho Fault thresho time
(kW) thresh reset over Fault threshol Fault threshol ing Fault threshold
y ary ue A) old overti d overti d thresh curren overtim value Fault threshol
g overti overti ld old overtim d
(A) value grade ld me me value me value t e (inside
me value value value
value (%FLC) (%FLC) mode %FLCmin)
(%FLC) (outside A)

化学供水泵A CHEMICAL WATER


1 SUPPLY PUMP A 1 1 15 23.7 LTMR100MBD 100 5 24.89 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 474% 5s 70%
服务水泵A SERVICE WATER
2 PUMP A 1 1 15 23.7 LTMR100MBD 100 5 24.89 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 474% 5s 70%
原水升压泵A RAW WATER
3 BOOSTER PUMP A 1 1 18.5 29.23 LTMR100MBD 100 5 30.69 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
化学供水泵B CHEMICAL WATER
4 SUPPLY PUMP B 1 1 15 23.7 LTMR100MBD 100 5 24.89 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 474% 5s 70%
服务水泵B SERVICE WATER
5 PUMP B 1 1 15 23.7 LTMR100MBD 100 5 24.89 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 474% 5s 70%
原水升压泵B RAW WATER
6 BOOSTER PUMP B 1 1 18.5 29.23 LTMR100MBD 100 5 30.69 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%

1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第8-1页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet
设备名称:1号机480V保安PC段 定值单号:2015-MSMS-019
Euipment: unit 1, 480V emergency PC section setting value No:2015-MSMS-019

作废定值单:
Invalid setting value sheet:

电流相位丢
负载CT比Load 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
CT ratio Reverse heat protection currentprotection
Current Long start up Block Grounding Under
phase
loss protection protection protection voltage
电流量
程最大
电动机 值(A)
电动 马达保护器 Curren
额定功 机额 故障阈值(
序号 设备名称 率 定电 型号 t 内
Item Equipment Nomina Motor
流 protection measur FLCmin
(A) 警告阈 故障复位 故障阈值 故障阈值 部%FLCmin
l ing 电机脱 故障阈值 接地电 )(外部 故障阈值
值 扣等级 故障复位 阈值 故障超 (%FLC) 故障超 (%FLC) 告警阈值 流模式 故障超 A)
power FLC(A type range alarm 超时 Fault 故障超时 (%FLC)Faul
t 超时 时 Fault 时 Alarm 时
故障超 (Un)
Primar Seconda
(kW) ) Max.Va
FLC1( thresho Motor Fault reset Fault over Fault threshol Fault Fault threshol Groundi Fault Fault 时 Fault
y ry A)
ld
trippin
reset threshol threshold time overti d
threshold
overtim value d
ng threshold Fault threshol
lue g overtime value current overtim value overtim d
(A) value grade overtime d me value e (%FLC) value mode e (inside value
value (%FLC) (%FLC)
%FLCmin)
(outside
A)

顶轴油泵
jacking oil pump
1 1 1 37 58.46 LTMR100MBD 100 5 61.4 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 15s 70%

主油箱排烟风机B
main oil tank gas
extraction fan B
2 1 1 0.9 1.78 LTMR08MBD 8 0.4 1.87 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 445% 5s 70%

交流辅助油泵
AC auxiliary oil
pump
3 1 1 30 47.4 LTMR100MBD 100 5 49.8 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 15s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第2+6页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet
设备名称:2号机480V保安PC段 定值单号:2015-MSMS-020
Euipment: Unit 2, 480V Emergency PC section Setting value No:2015-MSMS-020
作废定值单:
Invalid setting value sheet:

电流相位丢
负载CT比Load 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
CT ratio Reverse heat protection currentprotection
Current Long start up Block Grounding Under
phase
loss protection protection protection voltage
电流量
程最大
电动机 值(A)
电动 马达保护器 Curren
额定功 故障阈值(
率 机额 型号 t 内
序号 设备名称 Nomina 定电 Motor measur FLCmin 警告阈 电机脱 故障复位 故障阈值
部%FLCmin
Item Equipment 流 protection (A) 故障阈值 故障阈值 接地电 )(外部 故障阈值
l ing 值 故障复位 阈值 故障超 (%FLC) 故障超 告警阈值 故障超
FLC(A alarm 扣等级 超时 Fault 故障超时 (%FLC)Faul 超时 时 Fault 时 (%FLC) Alarm 流模式 时 A) 故障超 (Un)
Primar Seconda power ) type range FLC1( Motor t Fault Groundi Fault 时 Fault
y ry (kW) Max.Va A)
thresho
trippin
Fault reset Fault threshold
over Fault threshol Fault
threshold
threshol
ng
Fault
threshold Fault threshol
ld g reset threshol overtime time overti d overtim value d current overtim value overtim d
lue value overtime d value me value e value e
(A) grade value (%FLC) (%FLC) (%FLC) mode (inside value
%FLCmin)
(outside
A)

顶轴油泵
1 jacking oil pump 1 1 37 58.46 LTMR100MBD 100 5 61.4 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 15s 70%
主油箱排烟风机B
main oil tank gas
extraction fan B
2 1 1 0.9 1.78 LTMR08MBD 8 0.4 1.87 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 445% 5s 70%
交流辅助油泵
AC auxiliary oil
pump
3 1 1 30 47.4 LTMR100MBD 100 5 49.8 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 15s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

继电保护定值通知单
Relay Protection Settings Notice Sheet

第3+6页/共29页
设备名称:3号机480V保安PC段 定值单号:2015-MSMS-021
Equipment:Unit 3, 480 V Emergency PC section Setting value No:2015-MSMS-021
作废定值单:
Invalid setting value sheet:

电流相位丢
负载CT比Load 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
CT ratio Reverse heat protection currentprotection
Current Long start up Block Grounding Under
phase
loss protection protection protection voltage
电流量
程最大
电动机 值(A)
电动 马达保护器 Curren
额定功 故障阈值(
率 机额 型号 t 内
序号 设备名称 Nomina 定电 Motor measur FLCmin 部%FLCmin
警告阈 故障复位 故障阈值 故障阈值
Item Equipment l 流 protection ing (A) 值 电机脱 故障复位 阈值 故障超 (%FLC) 故障超 故障阈值 告警阈值 接地电 故障超 )(外部 故障阈值
FLC(A alarm
扣等级
超时 Fault 故障超时 (%FLC)Faul 超时 时 Fault 时
(%FLC)
Alarm
流模式

A) 故障超 (Un)
Primar Seconda power ) type range FLC1( Motor t Fault Groundi Fault 时 Fault
(kW) Max.Va thresho Fault reset Fault over Fault threshol Fault threshol Fault
y ry A) ld trippin reset threshol overtime threshold time overti d overtim threshold d ng overtim threshold Fault threshol
lue value g overtime d value me value e value value current e value overtim d
(A) grade (%FLC) (%FLC) mode (inside value
value (%FLC) %FLCmin)
(outside
A)

顶轴油泵
1 jacking oil pump 1 1 37 58.46 LTMR100MBD 100 5 61.4 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 15s 70%
主油箱排烟风机B
main oil tank gas
extraction fan B
2 1 1 0.9 1.78 LTMR08MBD 8 0.4 1.87 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 445% 5s 70%
交流辅助油泵
AC auxiliary oil
pump
3 1 1 30 47.4 LTMR100MBD 100 5 49.8 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 15s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第4+6页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet
设备名称:480V输煤PCA段 定值单号:2015-MSMS-022
Equipment:480V coal handling PCA section Setting value No:2015-MSMS-022
作废定值单:
Invalid setting value sheet:

负载CT比Load CT 反向热保护 过流保护over 电流相位丢 长启动保护 堵塞保护 接地保护 欠电压


ratio Reverse heat protection currentprotect 失Current Long start up Block Grounding Under
phaseloss
ion protection protection protection voltage
电流量
电动机 程最大
额定功 电动机 马达保护器 Current 值(A)
故障阈值(
序号 设备名称 率 额定电 型号 measuri FLCmin 内
Nomina Motor 故障阈值 故障阈
Item Equipment 流 ng (A) 警告阈值 电机脱 故障复 故障复位 故障 (%FLC)Fa 值 故障阈值 告警阈 接地电 部%FLCmin) 故障阈
l FLC(A) protection range alarm 扣等级
阈值
位超时 Fault
故障超
(%FLC)
故障超 (%FLC)

流模式 故障 (外部A) 故障超 值
超时 ult 超时 时 时 Fault Ground 超时 Fault 时 (Un)
Seconda power type Max.Val FLC1( threshol Motor Fault Fault Alarm
Primary ry (kW) A) d trippi reset reset Fault threshol over Fault thresho Fault threshol thresh ing Fault threshold Fault Fault
ue threshol overt d time overtim overti d curren overt value overti thresh
(A) value ng overtim d e ld me value old t ime (inside m old
grade e ime value value value mode
value (%FLC) (%FLC) %FLCmin) value
(%FLC)
(outside
A)

1A胶带机
1A belt conveyor
1 250 5 110 173.8 LTMR08MBD 8 20 0.73 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.5 5s 70%
2A胶带机
2 2A belt conveyor 250 5 110 173.8 LTMR08MBD 8 20 0.73 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.5 5s 70%
3A胶带机
3 3A belt conveyor 200 5 90 142.2 LTMR08MBD 8 16 0.747 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.6 5s 70%
轻油供油泵电动机A
light oil supplying motor 退出Quit
4 A 200 5 90 142.2 LTMR08MBD 8 16 0.747 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.6
6A头部胶带机
5 6A head belt conveyor 200 5 75 118.5 LTMR08MBD 8 16 0.622 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.0 5s 70%
6A尾部胶带机
6A tail belt conveyor
6 200 5 75 118.5 LTMR08MBD 8 16 0.622 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.0 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet
3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第2+9页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet
设备名称:480V输煤PCB段 定值单号:2015-MSMS-023
Equipment:480V coal handling PCB section Setting value No::2015-MSMS-023
作废定值单:
Invalid setting value sheet:

负载CT比Load CT 反向热保护 过流保护over 电流相位丢失 长启动保护 堵塞保护 接地保护 欠电压


ratio Reverse heat protection currentprotect Current Long start up Block Grounding Under
phase
ion loss protection protection protection voltage
电流量
电动机 程最大
额定功 电动机 马达保护器 Current 值(A)
故障阈值(
序号 设备名称 率 额定电 型号 measuri FLCmin 内
Nomina Motor 故障复位 故障阈值 故障阈 故障阈值 接地电 部%FLCmin) 故障阈
Item Equipment l 流 ng
protection range (A) 警告阈值 电机脱 故障复 阈值 故障 (%FLC)Fa 故障超 值 故障超 (%FLC) 告警阈 流模式 故障 (外部A) 故障超 值
FLC(A) alarm 扣等级 位超时 超时 ult 超时 (%FLC) 值
Seconda power type FLC1( threshol Motor Fault Fault 时 Fault 时 Fault Alarm Ground 超时 Fault 时 (Un)
Primary ry (kW) Max.Val reset Fault threshol over Fault Fault threshol ing Fault threshold Fault Fault
ue A) d trippi reset threshol time overtim thresho overti d thresh curren overt value overti thresh
value ng overtim overt d ld old
(A) grade e d ime value e value me value value t ime (inside m old
value (%FLC) (%FLC) (%FLC) mode %FLCmin) value
(outside
A)

1B胶带机
1 1B belt conveyor 250 5 110 173.8 LTMR08MBD 8 20 0.73 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.5 5s 70%
2B胶带机
2 2B belt conveyor 250 5 110 173.8 LTMR08MBD 8 20 0.73 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.5 5s 70%
3B胶带机
3B belt conveyor
3 200 5 90 142.2 LTMR08MBD 8 16 0.747 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.6 5s 70%
轻油供油泵电动机B
light oil supplying motor 退出Quit
4 B 200 5 90 142.2 LTMR08MBD 8 16 0.747 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.6

6B头部胶带机
6B head belt conveyor
5 200 5 75 118.5 LTMR08MBD 8 16 0.622 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.0 5s 70%
6B尾部胶带机
6B tail belt conveyor
6 200 5 75 118.5 LTMR08MBD 8 16 0.622 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.0 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第3+9页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet
设备名称:480V#2转运站MCC段 定值单号:2015-MSMS-024
Equipment:480V#Transfer station MCC section Setting value No:2015-MSMS-024

作废定值单:
Invalid setting value sheet

负载CT比Load CT 反向热保护 过流保护over 电流相位丢失 长启动保护 堵塞保护 接地保护 欠电压


ratio Reverse heat protection currentprotect Current Long start up Block Grounding Under
phase
ion loss protection protection protection voltage
电流量
电动机 程最大
额定功 电动机 马达保护器 Current 值(A)
率 型号 故障阈值(
序号 设备名称 Nomina 额定电 Motor measuri FLCmin 故障阈 内
Item Equipment 流 ng (A) 故障复位 故障阈值 故障阈值 接地电 部%FLCmin) 故障阈
l protection 警告阈值 电机脱 故障复 阈值 故障 (%FLC)Fa 故障超 值 故障超 (%FLC) 告警阈 流模式 故障 (外部A) 故障超 值
power FLC(A) type range alarm 扣等级 位超时
Fault 超时 ult 超时 时
(%FLC)
时 Fault

Seconda (kW) Max.Val FLC1( threshol Motor Fault Fault Alarm Ground 超时 Fault 时 (Un)
Primary ry
ue A) d trippi reset
reset Fault threshol over Fault Fault threshol ing Fault threshold Fault Fault
threshol overt d time overtim thresho overti d thresh curren overt value overti thresh
(A) value ng overtim d e ld me value old t ime (inside m old
grade e ime value value value
value (%FLC) (%FLC) (%FLC) mode %FLCmin) value
(outside
A)

6A胶带机头尾制动器
1 6A belt conveyor head &
tail breaker 1 1 0.33*2 1.3 LTMR08MBD 8 0.4 1.365 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 325% 5s 70%

2 1B胶带机制动器
1B belt conveyor breaker
1 1 0.33 0.65 LTMR08MBD 8 0.4 0.683 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 163% 5s 70%

3 1A胶带机制动器
1A belt conveyor breaker 1 1 0.33 0.65 LTMR08MBD 8 0.4 0.683 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 163% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第4+9页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet
设备名称:480V#3转运站MCC段 定值单号:2015-MSMS-025
Equipment:480V#Transfer station MCC section Setting value No:2015-MSMS-025
作废定值单:
Invalid setting value sheet:

负载CT比Load CT 反向热保护 过流保护over 电流相位丢失 长启动保护 堵塞保护 接地保护 欠电压


ratio Reverse heat protection currentprotect Current Long start up Block Grounding Under
phase
ion loss protection protection protection voltage
电流量
电动机 程最大
额定功 电动机 马达保护器 Current 值(A)
故障阈值(
序号 设备名称 率 额定电 型号 measuri FLCmin 内
Nomina Motor 故障阈值 故障阈
Item Equipment 流 ng (A) 警告阈值 电机脱 故障复 故障复位 故障 (%FLC)Fa 值 故障阈值 告警阈 接地电 部%FLCmin) 故障阈
l FLC(A) protection range alarm 扣等级 位超时 阈值 故障超 (%FLC) 故障超 (%FLC) 值 流模式 故障 (外部A) 故障超 值
Fault 超时 ult 超时 时 时 Fault Ground 超时 Fault 时 (Un)
Seconda power type Max.Val FLC1( threshol Motor Fault Fault Fault Alarm ing
Primary ry (kW) A) d trippi reset
reset Fault threshol over thresho
Fault threshol
thresh
Fault threshold Fault Fault
ue
(A) value ng overtim threshol overt d time overtim ld overti d old curren overt value overti thresh
d ime value e me value t ime (inside m old
grade e value value (%FLC) value mode %FLCmin) value
(%FLC) (%FLC)
(outside
A)

6B胶带机头部制动器
6B belt conveyor head
1 breaker 1 1 0.33*2 1.3 LTMR08MBD 8 0.4 1.365 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 325% 5s 70%
2B胶带机制动器
2B belt conveyor breaker
2 1 1 0.33 0.65 LTMR08MBD 8 0.4 0.683 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 163% 5s 70%
2A胶带机制动器
2A belt conveyor breaker
3 1 1 0.33 0.65 LTMR08MBD 8 0.4 0.683 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 163% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第5+9页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:480V碎煤机室MCC段 定值单号:2015-MSMS-026
Euipment: 480V Crusher room MCC section Setting value No:2015-MSMS-026
作废定值单:
Invalid setting value sheet

负载CT比Load CT 反向热保护 过流保护over 电流相位丢失 长启动保护 堵塞保护 接地保护 欠电压


ratio Reverse heat protection currentprotect Current Long start up Block Grounding Under
phase
ion loss protection protection protection voltage
电流量
电动机 程最大
额定功 电动机 马达保护器 Current 值(A)
故障阈值(
序号 设备名称 率 额定电 型号 measuri FLCmin 故障阈值 故障阈

Nomina Motor 故障复位 故障阈值 接地电 部%FLCmin) 故障阈
Item Equipment 流 ng (A) 警告阈值 电机脱 故障复 故障 (%FLC)Fa 值 告警阈
l protection range alarm 扣等级 位超时 阈值 故障超 (%FLC) 故障超 (%FLC) 值 流模式 故障 (外部A) 故障超 值
FLC(A) Fault 超时 ult 超时 时 时 Fault
Seconda power type FLC1( threshol Motor Fault Fault Alarm Ground 超时 Fault 时 (Un)
Primary ry Max.Val reset Fault threshol over Fault Fault threshol ing Fault threshold Fault Fault
(kW) ue
A) d trippi reset threshol overt d time overtim thresho overti d thresh curren overt value overti thresh
value ng overtim ld old
(A) grade e d ime value e value me value value t ime (inside m old
value (%FLC) (%FLC) mode %FLCmin) value
(%FLC) (outside
A)

1 3A胶带机制动器
3A belt conveyor braker
1 1 0.33 0.65 LTMR08MBD 8 0.4 0.683 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 163% 5s 70%

2 3B胶带机制动器
3B belt conveyor braker
1 1 0.33 0.65 LTMR08MBD 8 0.4 0.683 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 163% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

继电保护定值通知单
Relay Protection Settings Notice Sheet

第6+9页/共29页
设备名称:480V油泵房MCC段 定值单号:2015-MSMS-027
Equipment:480V Oil pump house MCC section Setting value No:2015-MSMS-027
作废定值单:
Invalid setting value sheet:

负载CT比Load CT 反向热保护 过流保护over 电流相位丢失 长启动保护 堵塞保护 接地保护 欠电压


ratio Reverse heat protection currentprotect Current Long start up Block Grounding Under
phase
ion loss protection protection protection voltage

电流量
电动机 程最大
额定功 电动机 马达保护器 Current 值(A)
故障阈值(
序号 设备名称 率 额定电 型号 measuri FLCmin 故障阈

Nomina Motor 故障复位 故障阈值 故障阈值 接地电 部%FLCmin) 故障阈
Item Equipment 流 ng (A) 警告阈值 电机脱 故障复 故障 (%FLC)Fa 值 告警阈
l FLC(A) protection range alarm 扣等级 位超时 阈值 超时 ult 超时
故障超 (%FLC) 故障超 (%FLC) 值 流模式 故障 (外部A) 故障超 值
Seconda power type FLC1( threshol Motor Fault Fault 时 Fault 时 Fault Alarm Ground 超时 Fault 时 (Un)
Primary ry
(kW) Max.Val A) d trippi reset
reset Fault threshol over Fault Fault threshol ing Fault threshold Fault Fault
ue threshol overt d time overtim thresho overti d thresh curren overt value overti thresh
value ng overtim ld old
(A) grade e d ime value e value me value value t ime (inside m old
value (%FLC) (%FLC) mode %FLCmin) value
(%FLC) (outside
A)

轻油卸油泵A
light oil unloading pump A
1 1 1 11 17.4 LTMR100MBD 100 5 18.27 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 348% 5s 70%

轻油卸油泵B
light oil unloading pump B
2 1 1 11 17.4 LTMR100MBD 100 5 18.27 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 348% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第7+9页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:480V公用PCA段 定值单号:2015-MSMS-028
Equipment:480V Public PCA section Setting value No:2015-MSMS-028
作废定值单:
Invalid setting value sheet
电流相位丢
负载CT比 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
Load CT Reverse heat protection currentprotect Current Long start up Block Grounding Under
phase
ratio ion loss protection protection protection voltage

电动机 电流量程
额定功 电动机 马达保护器 最大值(A) 故障阈值(
序号 设备名称 率 型号 Current 故障阈 内
Item Equipment Nomina 额定电 Motor
流 protection measuring FLCmi
n(A) 警告阈值
故障复位 值 故障阈值
故障阈值 告警阈 接地电流
部%FLCmin)
故障阈值
l range 电机脱扣 故障复位 阈值 故障超 (%FLC)F 故障超 (%FLC) 故障超 (%FLC) 故障超 (外部A)
FLC(A) alarm 时 值 模式 故障超 (Un)
等级 超时 Fault 超时 时 Fault 时 时 Fault
Primar Secon power type Max.Value threshol Motor ault Fault Fault Alarm Groundin Fault threshold 时 Fault
y dary (kW) (A) FLC1(A) d
Fault reset Fault thresho over Fault threshol
threshold thresh g Fault threshol
value tripping reset threshol overti time overtim d overti value old current overti value overtim d
grade overtime d me ld e value me me (inside
value (%FLC) value mode value
value (%FLC) %FLCmin)
(%FLC) (outside
A)

1 冲洗水泵A
washing pump A 1 1 22 33.1 LTMR100MBD 100 5 34.755 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%

2 机组排水槽泵C
unit drain pumpC 150 5 54 85.3 LTMR08MBD 8 12 0.5971 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 2.8 5s 70%
机组排水槽卸碱泵
3 Unit drain alkali
unloading pump
1 1 3 4.5 LTMR08MBD 8 0.4 4.725 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
4 罗茨风机A
Roots fan A 1 1 19 28.6 LTMR100MBD 100 5 30.03 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
5 机组排水槽泵A
unit drain pumpA 150 5 54 85.3 LTMR08MBD 8 12 0.5971 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 2.8 5s 70%
6 废水泵A
waste waterpumpA 150 5 54 85.3 LTMR08MBD 8 12 0.5971 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 2.8 5s 70%

7 C-5A胶带输送机
C-5Abelt conveyor 150 5 75 112.8 LTMR08MBD 8 12 0.7896 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.8 5s 70%

8 C-4A胶带输送机
C-4Abelt conveyor
400 5 160 252.8 LTMR08MBD 8 32 0.6636 85% 10 120s 70% 10s 130% 0.1s 18s 120% 5s 200% 130% 外部 0.1s 3.2 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet
3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第2+15页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:480V公用PCB段 定值单号:2015-MSMS-029
Equipment:480V Public PCB Section Setting value No:2015-MSMS-029
作废定值单:
Invalid setting value sheet:
负载CT比 电流相位丢

长启动保护 堵塞保护 接地保护 欠电压
Load CT Current Long start up Block Grounding Under
ratio 反向热保护 phase protection protection protection voltage
Reverse heat protection 过流保护over loss
currentprotect
ion
电动机 电流量程
额定功 电动机 马达保护器 最大值(A) 故障阈值(
序号 设备名称 率 型号 Current 故障阈 内
Item Equipment Nomina 额定电 Motor
流 protection measuring FLCmi
n(A) 警告阈值 故障复位 值 故障阈值 故障阈值 告警阈 接地电流 部%FLCmin) 故障阈值
l range 电机脱扣 故障复位 阈值 故障超 (%FLC)F 故障超 (%FLC) 故障超 (%FLC) 故障超 (外部A)
FLC(A) alarm 时 值 模式 故障超 (Un)
等级 超时 Fault 超时 时 Fault 时 时 Fault
Primar Secon power type Max.Value threshol ault Fault Fault Alarm Groundin Fault threshold 时 Fault
(kW) (A) FLC1(A) Motor Fault reset Fault over Fault threshol
threshol overti thresho time
y dary d threshold thresh g Fault threshol
value tripping reset overtim d overti value old current overti value overtim d
grade overtime d me ld e value me me (inside
value value (%FLC) (%FLC) value mode %FLCmin) value
(%FLC) (outside
A)

1 冲洗水泵B
washing pump B 1 1 22 33.1 LTMR100MBD 100 5 34.755 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
机组排水槽泵D
2 unit drain pumpD 150 5 54 85.3 LTMR08MBD 8 12 0.5971 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 2.8 5s 70%
机组排水槽卸酸泵
unit drain acid
3 unloading pump 1 1 3 4.5 LTMR08MBD 8 0.4 4.725 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
罗茨风机B
4 roots fanB 1 1 19 28.6 LTMR100MBD 100 5 30.03 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
机组排水槽泵B
5 unit drain pumpB 150 5 54 85.3 LTMR08MBD 8 12 0.5971 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 2.8 5s 70%
废水泵B
6 wast water pumpB 150 5 54 85.3 LTMR08MBD 8 12 0.5971 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 2.8 5s 70%
C-5B胶带输送机
C-5B belt conveyor
7 150 5 75 112.8 LTMR08MBD 8 12 0.7896 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.8 5s 70%
C-4B胶带输送机
8 C-4B belt conveyor 400 5 160 252.8 LTMR08MBD 8 32 0.6636 85% 10 120s 70% 10s 130% 0.1s 18s 120% 5s 200% 130% 外部 0.1s 3.2 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet
3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第3+15页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:480V煤仓间MCC段 定值单号:2015-MSMS-030
Equipment: 480V COAL BUNKER BAY MCC SWITCHGEAR Setting value No:2015-MSMS-030
作废定值单:
Invalid setting value sheet:
电流相位丢
负载CT比 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
Load CT Reverse heat protection currentprotect Current Long start up Block Grounding Under
phase
ratio ion loss protection protection protection voltage

电动机 电流量程
额定功 电动机 马达保护器 最大值(A) 故障阈值(
序号 设备名称 率 型号 Current 故障阈 内
Item Equipment Nomina 额定电 Motor
流 protection measuring FLCmi
n(A) 警告阈值 故障复位 值 故障阈值 故障阈值 告警阈 接地电流 部%FLCmin) 故障阈值
l range 电机脱扣 故障复位 阈值 故障超 (%FLC)F 故障超 (%FLC) 故障超 故障超 (外部A)
FLC(A) alarm 等级 超时 Fault 时 超时 时 Fault 时 (%FLC) 值 模式 时 Fault 故障超 (Un)
Primar Secon power type Max.Value threshol Motor ault Fault Fault Alarm Groundin Fault threshold 时 Fault
y dary (kW) (A) FLC1(A) d
Fault reset Fault thresho over Fault threshol
threshold thresh g Fault threshol
value tripping reset threshol overti time overtim d overti value old current overti value overtim d
grade overtime d me ld e value me me (inside
value value (%FLC) (%FLC) value mode %FLCmin) value
(%FLC) (outside
A)

C-4A胶带机制动器
C-4A belt conveyor
1 braker 1 1 0.33 5 LTMR08MBD 8 0.4 5.25 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
C-5A胶带机制动器
C-5A belt conveyor
braker
2 1 1 0.33 5 LTMR08MBD 8 0.4 5.25 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
C-4B胶带机制动器
C-4B belt conveyor
braker
3 1 1 0.33 5 LTMR08MBD 8 0.4 5.25 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
C-5B胶带机制动器
C-5B belt conveyor
4 braker 1 1 0.33 5 LTMR08MBD 8 0.4 5.25 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet
3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第4+15页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet
设备名称:480V工作PC1A段 定值单号:2015-MSMS-031
Equipment:480V working PC1A section Setting value No:2015-MSMS-031
作废定值单:
Invalid setting value sheet:

电流相位丢
负载CT比Load 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
CT ratio Reverse heat protection currentprote Current Long start up Block Grounding Under
phase
ction loss protection protection protection voltage
电流量
程最大
值(A)
电动机额 电动机 马达保护器 Curren 故障阈值(
序号 设备名称 定功率 型号 t FLCm 故障阈 内
Item Equipment Nominal 额定电
流 Motor measur in(A 警告阈 电机脱 故障复位 值 故障阈值 故障阈值 告警阈 接地电 部%FLCmin) 故障阈
power FLC(A) protection ing ) 值 故障复位 阈值 故障 (%FLC) 故障超 (%FLC) 故障超 (%FLC) 故障超 (外部A) 故障超 值
alarm 扣等级 超时 Fault 超时 值 流模式 时
Primar Seconda (kW) type range FLC1( Motor
thresho trippin Fault reset Fault Fault 超时
over

Fault
Fault
threshol
时 Fault
Fault threshol
Alarm Groundi
Fault
Fault threshold

Fault
(Un)
Fault
y ry Max.Va A)
ld reset threshol thresh time overtim d overtim d
thresho ng
overtim value overti thresho
lue g overt old ld current
value overtime d ime e value e value e (inside m ld
(A) grade value value (%FLC) (%FLC) value mode %FLCmin) value
(%FLC) (outside
A)

水环真空泵A(汽侧)
water ring vacuum 外部
1 pump A (Steam side) 150 5 63 99.54 LTMR08MBD 8 12 0.7 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% outside 0.1s 3.3 5s 70%
轴封冷却器抽汽风机A
gland seal cooler 内部
2 extraction fan A 1 1 11 17.38 LTMR27MBD 27 1.35 18.2 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% inside 0.1s 500% 5s 70%
液力耦合器辅助油泵A
hydraulic coupling 内部
3 auxiliary oil pumpA 1 1 11 17.38 LTMR27MBD 27 1.35 18.2 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% inside 0.1s 500% 5s 70%
主油箱排烟风机A
Main oil tank gas 内部
4 extraction fan A 1 1 0.9 1.78 LTMR08MBD 8 0.4 1.87 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% inside 0.1s 445% 5s 70%
汽机房主油箱控制油泵A
Main oil tank control
oil pump A in turbine 内部
5 house 1 1 30 47.4 LTMR100MBD 100 5 49.8 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% inside 0.1s 500% 5s 70%
主油箱加热器
Main oil tank heater 内部
6 1 1 3.15*6 29.86 LTMR100MBD 100 5 31.4 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% inside 0.1s 500% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.
2.定值单中没有保护均退出。
Quit if no protection in setting value sheet
3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第2+18页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:480V工作PC1B段 定值单号:2015-MSMS-032
Equipment: 480 work PC1B section Setting value No:2015-MSMS-032

作废定值单:
Invalid setting value sheet:
电流相位丢
负载CT比Load 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
CT ratio Reverse heat protection currentprote Current Long start up Block Grounding Under
phase
ction loss protection protection protection voltage
电流量
程最大
值(A)
电动机额 电动机 马达保护器 Curren 故障阈值(
定功率 额定电 型号 t FLCm 故障阈 内
序号 设备名称 Nominal Motor measur in(A 警告阈 故障复位 值 故障阈值 故障阈值 部%FLCmin) 故障阈
Item Equipment 流 值 电机脱 故障复位 阈值 故障 故障超 (%FLC) 故障超 (%FLC) 告警阈 接地电 故障超 (外部A) 故障超 值
power FLC(A) protection ing ) 扣等级 超时 (%FLC) 值 流模式
Primar Seconda (kW) type range FLC1( alarm Motor 超时 Fault Fault 超时 时 Fault 时 Fault Alarm Groundi 时 Fault 时 (Un)
thresho Fault reset Fault over
thresh time
Fault threshol Fault threshol Fault threshold Fault Fault
y ry Max.Va A) ld trippin reset threshol overt overtim d overtim d thresho ng overtim value overti thresho
lue value g overtime d old e value e value ld current e (inside m ld
grade ime value value mode
(A) value (%FLC) (%FLC) %FLCmin) value
(%FLC) (outside
A)

水环真空泵B(汽侧)
water ring vacuum
1 pump B (steam side) 150 5 63 99.54 LTMR08MBD 8 12 0.7 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.3 5s 70%
再循环泵
2 recycling pump 1 1 30 47.4 LTMR100MBD 100 5 49.8 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
汽机房主油箱控制油泵B
main oil control pump
B in turbine house
3 1 1 30 47.4 LTMR100MBD 100 5 49.8 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
轴封冷却器抽汽风机B
gland seal cooler
steam extraction fan
4 B 1 1 11 17.38 LTMR27MBD 27 1.35 18.2 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
液力耦合器辅助油泵B
hydraulic coupling
5 auxiliary pump B 1 1 11 17.38 LTMR27MBD 27 1.35 18.2 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第3+18页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:480V工作PC2A段 定值单号:2015-MSMS-033
Equipment:480V work PC2A section Setting value No:2015-MSMS-033
作废定值单:
Invalid setting value sheet:
电流相位丢
负载CT比Load 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
CT ratio Reverse heat protection currentprote Current Long start up Block Grounding Under
phase
ction loss protection protection protection voltage
电流量
程最大
值(A)
电动机额 电动机 马达保护器 Curren 故障阈值(
序号 设备名称 定功率 型号 t FLCm 故障阈 内
Item Equipment Nominal 额定电
流 Motor measur in(A 警告阈 电机脱 故障复位 值 故障阈值 故障阈值 告警阈 接地电 部%FLCmin) 故障阈
power FLC(A) protection ing ) 值 故障复位 阈值 故障 (%FLC) 故障超 (%FLC) 故障超 (%FLC) 故障超 (外部A) 故障超 值
alarm 扣等级 超时 Fault 超时 值 流模式 时
Primar Seconda (kW) type range FLC1( Motor
thresho trippin Fault reset Fault Fault 超时
over

Fault
Fault
threshol
时 Fault
Fault threshol
Alarm Groundi
Fault
Fault threshold

Fault
(Un)
Fault
y ry Max.Va A)
ld reset threshol thresh time overtim d overtim d
thresho ng
overtim value overti thresho
lue g overt old ld current
value overtime d ime e value e value e (inside m ld
(A) grade value value (%FLC) (%FLC) value mode %FLCmin) value
(%FLC) (outside
A)

水环真空泵A(汽侧)
water ring vacuum
1 pump(steam side) 150 5 63 99.54 LTMR08MBD 8 12 0.7 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.3 5s 70%
轴封冷却器抽汽风机A
gland seal cooler
steam extraction fanA
2 1 1 11 17.38 LTMR27MBD 27 1.35 18.2 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
液力耦合器辅助油泵A
hydaulic coupling
auxiliary oil pump A
3 1 1 11 17.38 LTMR27MBD 27 1.35 18.2 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
主油箱排烟风机A
main oil tank gas
4 extraction fan A 1 1 0.9 1.78 LTMR08MBD 8 0.4 1.87 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 445% 5s 70%
汽机房主油箱控制油泵A
main oil tank control
oil pump A in turbine
5 house 1 1 30 47.4 LTMR100MBD 100 5 49.8 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
主油箱加热器
6 main oil tank heater 1 1 3.15*6 29.86 LTMR100MBD 100 5 31.4 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet
3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第4+18页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:480V工作PC2B段 定值单号:2015-MSMS-034
Equipment: 480V work PC2B section Setting value No:2015-MSMS-034
作废定值单:
Invalid setting value sheet:
电流相位丢
负载CT比Load 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压Under
CT ratio Reverse heat protection currentprote Current Long start up Block Grounding voltage
phase
ction loss protection protection protection
电流量
程最大
值(A)
电动机额 电动机 马达保护器 Curren 故障阈值(
序号 设备名称 定功率 额定电 型号 t FLCm 故障阈 内
Item Equipment Nominal 流 Motor measur in(A 警告阈
电机脱
故障复位 值 故障阈值 故障阈值
告警阈 接地电 故障超 (外部A)
部%FLCmin) 故障阈
power FLC(A) protection ing ) 值 故障复位 阈值 故障 (%FLC) 故障超 (%FLC) 故障超 (%FLC) 故障超 值
alarm 扣等级 超时 Fault 超时 值 流模式 时
Primar Seconda (kW) type range FLC1( Motor
thresho trippin Fault reset Fault Fault 超时
over

Fault
Fault
threshol
时 Fault
Fault threshol
Alarm Groundi
Fault
Fault threshold

Fault
(Un)
Fault
y ry Max.Va A)
ld reset threshol thresh time overtim d overtim d
thresho ng
overtim value overti thresho
lue g overt old ld current e
value overtime d ime e value e value (inside m ld
(A) grade value value mode
value (%FLC) (%FLC) %FLCmin) value
(%FLC) (outside
A)

水环真空泵B(汽侧)
water ring vacuum
1 pumpB (steam side) 150 5 63 99.54 LTMR08MBD 8 12 0.7 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.3 5s 70%
再循环泵
2 Recycling pump 1 1 30 47.4 LTMR100MBD 100 5 49.8 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
汽机房主油箱控制油泵B
main oil tank control
pumpB in turbine
3 house 1 1 30 47.4 LTMR100MBD 100 5 49.8 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
轴封冷却器抽汽风机B
gland seal cooler
4 steam extraction B 1 1 11 17.38 LTMR27MBD 27 1.35 18.2 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
液力耦合器辅助油泵B
hydraulic coupling
auxiliary pumpB
5 1 1 11 17.38 LTMR27MBD 27 1.35 18.2 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

继电保护定值通知单
Relay Protection Settings Notice Sheet

第5+18页/共29页
设备名称:480V工作PC3A段 定值单号:2015-MSMS-035
Equipment:480V work PC3A section Setting value No::2015-MSMS-035
作废定值单:
Invalid setting value sheet:
电流相位丢
负载CT比Load 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
CT ratio Reverse heat protection currentprote Current Long start up Block Grounding Under
phase
ction loss protection protection protection voltage
电流量
程最大
值(A)
电动机额 电动机 马达保护器 Curren 故障阈值(
定功率 型号 t FLCm 故障阈 内
序号 设备名称 Nominal 额定电 Motor measur in(A 警告阈 故障复位 值 故障阈值 故障阈值 部%FLCmin) 故障阈
Item Equipment 流 电机脱 故障 告警阈 接地电
power FLC(A) protection ing ) 值 扣等级 故障复位 阈值 (%FLC) 故障超 (%FLC) 故障超 (%FLC) 值 流模式 故障超 (外部A) 故障超 值
alarm 超时 Fault 超时 Fault 超时 时 Fault 时 Fault 时 Fault 时 (Un)
Primar Seconda (kW) type range FLC1( thresho Motor Fault reset Fault over Fault threshol Fault threshol Alarm Groundi Fault threshold Fault Fault
y ry Max.Va A)
ld
trippin
reset threshol overt thresh time overtim d overtim d
thresho ng
overtim value overti thresho
lue g old ld current
value grade overtime d ime e value e value value mode e (inside m ld
(A) value value (%FLC) (%FLC) %FLCmin) value
(%FLC) (outside
A)

水环真空泵A(汽侧)
water ring vacuum
1 pump(steam side) 150 5 63 99.54 LTMR08MBD 8 12 0.7 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.3 5s 70%
轴封冷却器抽汽风机A
gland seal cooler
2 steam extraction fanA 1 1 11 17.38 LTMR27MBD 27 1.35 18.2 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
液力耦合器辅助油泵A
hydaulic coupling
auxiliary oil pump A
3 1 1 11 17.38 LTMR27MBD 27 1.35 18.2 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
主油箱排烟风机A
main oil tank gas
extraction fan A
4 1 1 0.9 1.78 LTMR08MBD 8 0.4 1.87 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 445% 5s 70%
汽机房主油箱控制油泵A
main oil tank control
oil pump A in turbine
5 house 1 1 30 47.4 LTMR100MBD 100 5 49.8 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
主油箱加热器
6 main oil tank heater 1 1 3.15*6 29.86 LTMR100MBD 100 5 31.4 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet
3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:480V工作PC3B段 定值单号:2015-MSMS-036
Equipment: 480V work PC3B section Setting value No:2015-MSMS-036

第6+18页/共29页
作废定值单:
Invalid setting value sheet:
负载CT比Load 反向热保护 电流相位丢

长启动保护 堵塞保护 接地保护 欠电压
CT ratio Reverse heat protection Current Long start up Block Grounding Under
过流保护over phase protection protection protection voltage
loss
currentprote
电流量 ction
程最大
值(A)
电动机额 电动机 马达保护器 Curren 故障阈值(
序号 设备名称 定功率 额定电 型号 t FLCm 故障阈 内
Nominal Motor measur in(A 警告阈 故障复位 值 故障阈值 故障阈值 部%FLCmin) 故障阈
Item Equipment 流 电机脱 故障 告警阈 接地电
power FLC(A) protection ing ) 值 扣等级 故障复位 阈值 (%FLC) 故障超 (%FLC) 故障超 (%FLC) 值 流模式 故障超 (外部A) 故障超 值
(kW) type range alarm 超时 Fault 超时 Fault 超时 时 Fault 时 Fault 时 Fault 时 (Un)
Primar Seconda FLC1( thresho Motor Fault Alarm Groundi
y ry Max.Va A) trippin reset
reset Fault over
thresh time
Fault threshol Fault threshol
thresho ng
Fault threshold Fault Fault
ld threshol overt overtim d overtim d overtim value overti thresho
lue g old ld current
value grade overtime d ime e value e value value mode e (inside m ld
(A) value value (%FLC) (%FLC) %FLCmin) value
(%FLC) (outside
A)

水环真空泵B(汽侧)
water ring vacuum
pumpB (steam side)
1 150 5 63 99.54 LTMR08MBD 8 12 0.7 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% 外部 0.1s 3.3 5s 70%
再循环泵
Recycling pump
2 1 1 30 47.4 LTMR100MBD 100 5 49.8 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
汽机房主油箱控制油泵B
main oil tank control
pumpB in turbine
3 house 1 1 30 47.4 LTMR100MBD 100 5 49.8 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
轴封冷却器抽汽风机B
gland seal cooler
4 steam extraction B 1 1 11 17.38 LTMR27MBD 27 1.35 18.2 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
液力耦合器辅助油泵B
hydraulic coupling
5 auxiliary pump B 1 1 11 17.38 LTMR27MBD 27 1.35 18.2 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.
2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:1号机480V汽机房2MCC段 定值单号:2015-MSMS-037
Equipment: Unit 1 480V turbine house 2 MCC section Setting value No:2015-MSMS-037
作废定值单:
Invalid setting value sheet:

第7+18页/共29页
负载CT比Load 反向热保护 电流相位丢

长启动保护 堵塞保护 接地保护 欠电压
CT ratio Reverse heat protection Current Long start up Block Grounding Under
过流保护over phase
loss
protection protection protection voltage
currentprote
电流量 ction
程最大
值(A)
电动机额 电动机 马达保护器 Curren 故障阈值(
序号 设备名称 定功率 额定电 型号 t FLCm 故障阈 内
Item Equipment Nominal 流 Motor measur in(A 警告阈
电机脱
故障复位 值 故障阈值 故障阈值
告警阈 接地电
部%FLCmin) 故障阈
值 故障
power FLC(A) protection ing ) 扣等级 故障复位 阈值 超时 (%FLC) 故障超 (%FLC) 故障超 (%FLC) 值 流模式 故障超 (外部A) 故障超 值
(kW) type range alarm 超时 Fault Fault 超时 时 Fault 时 Fault 时 Fault 时 (Un)
Primar Seconda FLC1( thresho Motor Fault Alarm Groundi Fault threshold
y ry Max.Va A) trippin
reset Fault over
thresh time
Fault threshol Fault threshol
thresho ng
Fault Fault
ld reset threshol overt overtim d overtim d overtim value overti thresho
lue value
g
overtime d old e value e value
ld current
e (inside m ld
(A) grade ime value value mode
value (%FLC) (%FLC) %FLCmin) value
(%FLC) (outside
A)

发电机空间加热器
Space heater of GEN
1 1 1 5 7.9 LTMR27MBD 27 1.35 8.3 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
水环真空泵(水
侧)Water ringed
Vacuum pump(water
2 side) 1 1 5.5 8.69 LTMR27MBD 27 1.35 9.12 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
锅炉上水泵fill-up
water pump
3 1 1 22 34.76 LTMR100MBD 100 5 36.5 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%

1(2,3)号电子设备间消
防高温排烟风机High
temperature resistant
axial flow smoke
exhaust fan
pump(water side) in
electronic equipment
for unit 1
4 1 1 0.75 1.48 LTMR08MBD 8 0.4 1.55 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 370% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet

3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:2号机480V汽机房2MCC段 定值单号:2015-MSMS-038
Equipment: Unit 2 480V turbine house 2 MCC section Setting value No:2015-MSMS-038

作废定值单:
Invalid setting value sheet:

第8+18页/共29页
电流相位丢
负载CT比Load 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
CT ratio Reverse heat protection currentprote Current Long start up Block Grounding Under
phase
ction loss protection protection protection voltage
电流量
程最大
值(A)
电动机额 电动机 马达保护器 Curren 故障阈值(
序号 设备名称 定功率 型号 t FLCm 故障阈 内
Item Equipment Nominal 额定电
流 Motor measur in(A 警告阈 故障复位 值 故障阈值 故障阈值 部%FLCmin) 故障阈
电机脱 故障复位 阈值 故障 告警阈 接地电 故障超 (外部A)
power FLC(A) protection ing ) 值
扣等级 (%FLC) 故障超 (%FLC) 故障超 (%FLC)
值 流模式
故障超 值
(kW) type range alarm 超时 Fault 超时 Fault 超时 时 Fault 时 Fault 时 Fault 时 (Un)
Primar Seconda FLC1( Motor Alarm Groundi
y ry Max.Va A) thresho trippin Fault reset Fault over
thresh time
Fault threshol Fault threshol thresho ng Fault threshold Fault Fault
lue ld reset threshol overt overtim d overtim d overtim value overti thresho
value g overtime d old e value e value ld current e (inside m ld
(A) grade ime value value mode
value (%FLC) (%FLC) %FLCmin) value
(%FLC) (outside
A)

发电机空间加热器
Generator space
1 heater 1 1 5 7.9 LTMR27MBD 27 1.35 8.3 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
水环真空泵(水侧)
water ring vacuum
pump
2 (water side) 1 1 5.5 8.69 LTMR27MBD 27 1.35 9.12 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
锅炉上水泵
Boiler feedwater pump
3 1 1 22 34.76 LTMR100MBD 100 5 36.5 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
1(2,3)号电子设备间消
防高温排烟风机
Fire fighting high
temperature gas
extraction fan in No
1(2,3)electric device
house
4 1 1 0.75 1.48 LTMR08MBD 8 0.4 1.55 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 370% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet
3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:3号机480V汽机房2MCC段 定值单号:2015-MSMS-039
Equipment: Unit 3 480V turbine house 2 MCC section Setting value No:2015-MSMS-039

作废定值单:
Invalid setting value sheet:
电流相位丢
负载CT比Load 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
CT ratio Reverse heat protection currentprote Current Long start up Block Grounding Under
phase
ction loss protection protection protection voltage
电流量
程最大
值(A)
电动机额 电动机 马达保护器 Curren
序号 设备名称 定功率 额定电 型号 t FLCm
Nominal Motor measur in(A 第9+18页/共29页
Item Equipment 流
power FLC(A) protection ing )
(kW) type range
Max.Va
lue
(A)
电流量
程最大
值(A)
电动机额 电动机 马达保护器 Curren 故障阈值(
序号 设备名称 定功率 额定电 型号 t FLCm 故障阈 内
Item Equipment Nominal 流 Motor measur in(A 警告阈 电机脱 故障复位 值 故障阈值 故障阈值 告警阈 接地电 部%FLCmin) 故障阈
值 故障复位 阈值 故障 故障超 (%FLC) 故障超 (%FLC)
power FLC(A) protection ing ) 扣等级 超时 (%FLC) 值 流模式 故障超 (外部A) 故障超 值
(kW) type range alarm 超时 Fault Fault 超时 时 Fault 时 Fault 时 Fault 时 (Un)
Primar Seconda FLC1( thresho Motor Alarm Groundi Fault threshold
y ry Max.Va A) trippin
Fault reset Fault over
thresh time
Fault threshol Fault threshol
thresho ng
Fault Fault
ld reset threshol overt overtim d overtim d overtim value overti thresho
lue value
g
overtime d old e value e value
ld current
e (inside m ld
(A) grade ime value value mode
value (%FLC) (%FLC) %FLCmin) value
(%FLC) (outside
A)

发电机空间加热器
Generator space
1 heater 1 1 5 7.9 LTMR27MBD 27 1.35 8.3 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
水环真空泵(水侧)
water ring vacuum
2 pump(water side) 1 1 5.5 8.69 LTMR27MBD 27 1.35 9.12 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
锅炉上水泵
Boiler feedwater pump
3 1 1 22 34.76 LTMR100MBD 100 5 36.5 85% 10 120s 70% 10s 130% 0.1s 10s 120% 5s 200% 130% 内部 0.1s 500% 5s 70%
1(2,3)号电子设备间消
防高温排烟风机
Fire fighting high
temperature gas
extraction fan in No
1(2,3)electric device
house
4 1 1 0.75 1.48 LTMR08MBD 8 0.4 1.55 85% 10 120s 70% 10s 130% 0.1s 8s 120% 5s 200% 130% 内部 0.1s 370% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.

2.定值单中没有保护均退出。
Quit if no protection in setting value sheet
3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1

第10+18页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet

设备名称:480VPT 定值单号:2015-MSMS-040
Equipment:480VPT Setting Value No:2015-MSMS-040
作废定值单:
Invalid setting value sheet:

序号 设备名称 电压定值 时间定值


Item Equipment Voltage setting value Time setting value

9s
480VPT 50%Un
1 0.5s
说明:Un:480VPT二次额定电压。
Instruction:480VPT Secondary rated voltage

第2+27页/共29页
继电保护定值通知单
Relay Protection Settings Notice Sheet
设备名称:480V码头变电站 定值单号:2015-MSMS-042
Equipment: Setting value No:2015-MSMS-042
作废定值单:
Invalid setting value sheet:

电流相位丢
负载CT比Load 反向热保护 过流保护over 失 长启动保护 堵塞保护 接地保护 欠电压
CT ratio Reverse heat protection currentprote Current Long start up Block Grounding Under
phase
ction loss protection protection protection voltage
电流量
程最大
值(A)
电动机额 电动机 马达保护器 Curren 故障阈值(
序号 设备名称 定功率 额定电 型号 t FLCm 故障阈 内
Nominal Motor measur in(A 警告阈 电机脱 故障复位 值 故障阈值 故障阈值 告警阈 接地电 故障超 部%FLCmin) 故障阈
Item Equipment 流 值 故障
power FLC(A) protection ing )
alarm 扣等级 故障复位超时
阈值
Fault 超时 (%FLC) 故障超 (%FLC) 故障超 (%FLC) 值 流模式 时 (外部A) 故障超 值
Primar Seconda (kW) type range FLC1( thresho Motor Fault reset Fault Fault 超时
over

Fault
Fault
threshol
时 Fault
Fault threshol Alarm Groundi Fault Fault
threshold

Fault
(Un)
Fault
y ry Max.Va A) ld trippin reset threshol thresh time overtim d overtim d thresho ng
lue value g overtime d
overt old e value e value ld current overtim
e
value
(inside
overti
m
thresho
ld
(A) grade ime value value mode
value (%FLC) (%FLC) %FLCmin) value
(%FLC) (outside
A)

带式输送机制动器(备用
) 内部
1 1 1 0.21 0.4 LTMR08MBD 8 0.4 0.42 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% inside 0.1s 500% 5s 70%

C-1带式输送机制动器 内部
2 1 1 0.21 0.4 LTMR08MBD 8 0.4 0.42 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% inside 0.1s 500% 5s 70%

C-1带式输送机 内部
3 300 5 110 165 LTMR08MBD 8 24 0.58 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% inside 0.1s 500% 5s 70%

C-2带式输送机制动器 内部
4 1 1 0.21 0.4 LTMR08MBD 8 0.4 0.42 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% inside 0.1s 100% 5s 70%

C-2带式输送机
内部
5 300 5 110 165 LTMR08MBD 8 24 0.58 85% 10 120s 70% 10s 130% 0.1s 15s 120% 5s 200% 130% inside 0.1s 500% 5s 70%
1.反向热保护、电流相位丢失保护、长启动保护、堵塞保护、接地保护、过流保护、欠电压保护执行方式为跳闸。
The executing mode is tripping off for reverse heat protection,current phase loss protection, block protection, grounding protection ,over currentprotection and
under voltage protection.
2.定值单中没有保护均退出。
Quit if no protection in setting value sheet
3.FLC为电机额定电流;FLCmin=电流量程最大值*负载CT比/20;负载CT比=负载CT一次电流/(负载CT二次电流*流经次数);流经次数=1。
FLC is motor rated current; FLCmin=Max.value of current measuring range * load CT ratio/20
load CT ratio = load CT primary current /(load CT secondary current * flowing through times; Flowing through time = 1