Assessment of Feeder Voltage Regulation Using Statistical Process Control Methods
Assessment of Feeder Voltage Regulation Using Statistical Process Control Methods
1, JANUARY 2008
Abstract—Power-quality voltage and current transient wave- variations that may be an indication of a problem. Therefore,
form data have been explored rather extensively as the primary the statistical methods provide one additional indicator in pre-
input data in predictive maintenance, automatic root-cause anal- dicting possible system or equipment problems. Nonexhaustive
ysis, and evaluating system performance to indicate potential
problems. Unfortunately, very few efforts have been directed examples of problems that can be detected using process con-
toward making use of the voluminous steady-state data collected trol methods include but are not limited to abnormal load varia-
alongside waveform data. Therefore, this paper proposes to tions, arcing conditions, neutral connection problems, capacitor
use steady-state data, particularly, rms voltage data to detect bank problems, and voltage regulator problems. Capacitor bank
abnormal trend behavior that may be indicative of a problem. problems have been flagged using transient waveform data with
Specifically, this paper develops a statistical analysis algorithm
based on the well-known statistical process control methods for signal-processing methods [3]. Steady-state unbalance voltage
assessing feeder voltage regulation performance. The assessment and reactive power (var) flow data analyzed with the process
results can be used to indicate potential regulator problems as control methods can provide additional validation of capacitor
well. The efficacy of the method is demonstrated by applications problems.
to two sets of actual rms voltage data. The objective of this paper is to motivate a more widespread
Index Terms—Power quality (PQ), process control, statistics, use of steady-state data and applications of statistical process-
voltage control. control methods. Therefore, this paper presents novel statistical
analysis procedures to assess feeder voltage regulation using
steady-state rms voltage data. The outcome of the assessment
I. INTRODUCTION
can be used to indicate possible problems of the feeder voltage
OLTAGE and current waveshape or waveform data have regulation techniques and regulator or other related problems.
V been utilized extensively as part of a larger effort to im-
prove the overall power-quality (PQ) performance. Transient
The regulation assessment outcome is not intended as the sole
indicator in evaluating voltage regulation and regulator con-
waveform data have been used almost exclusively as the only cerns. It is one of many other possible indicators. As an example,
data set to determine and analyze the root causes of PQ prob- problems in voltage regulators can be indicated using unbalance
lems [1] and evaluate equipment performance and predict main- data as well as the number of daily regulator operations.
tenance requirements [2], [3] to mention just a few. This paper also demonstrates the efficacy of the proposed sta-
Unfortunately, voluminous steady-state data collected along- tistical methods by applying them to assess the performance of
side waveform data are yet to be fully exploited. Steady-state feeder voltage regulation. Steady-state data used will be the rms
data, such as rms voltage and current profiles, unbalance voltage profile.
voltage, reactive power (var) flow, and harmonic distortion The proposed control charts method builds upon and expands
data, contain a wealth of information about the equipment that proposed in [9]. Sunderman used the basic control chart to
and overall system health conditions. Instead of relying automate the detection of voltage unbalance. It worked reason-
on signal-processing techniques, statistical process control ably well; however, it produced a number of false positives. This
methods should be used to analyze steady-state data. Statistical is because the upper limit of the control chart beyond which
process control methods have been used in industrial process, voltage unbalanced is deemed to be invalid is absent. In addi-
manufacturing quality controls, and large software development tion, [9] did not statistically analyze the number of samples after
efforts to measure and monitor process variations and stability the detection of a flagged event. In this paper, the so-called beta
[5]–[8]. risk and the average run length curves are developed for that
Statistical process control methods can be applied to appro- purpose.
priate steady-state data sets to help detect abnormal data or trend Two control-chart based methods are developed for assessing
the health of a voltage regulator using its regulation profile. The
Manuscript received August 29, 2006; revised January 22, 2007. Paper no.
first method (Section III) utilizes the control chart theory for
TPWRD-00510-2006. the detection of anomalies in the regulation profile for current
N. Mago is with the Electric Reliability Council of Texas, Taylor, TX 76574 data. The second method (Section IV) uses run chart analysis
USA.
S. Santoso is with the Department of Electrical and Computer Engineering,
as the basis for a rule-based algorithm to isolate trends for indi-
The University of Texas at Austin, Austin, TX 78712 USA (e-mail: ssan- cating the possibility of a poorly performing voltage regulator.
toso@ieee.org). Section V describes the implementation and applications of the
M. McGranaghan is with EPRI, Knoxville, TN 37932 USA. proposed techniques on two actual rms voltage data. This sec-
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. tion also demonstrates the efficacy of the proposed methods.
Digital Object Identifier 10.1109/TPWRD.2007.905549 Section VI concludes this paper.
0885-8977/$25.00 © 2007 IEEE
Authorized licensed use limited to: Kasetsart University provided by UniNet. Downloaded on October 12,2023 at 08:34:13 UTC from IEEE Xplore. Restrictions apply.
MAGO et al.: ASSESSMENT OF FEEDER VOLTAGE REGULATION USING STATISTICAL PROCESS CONTROL METHODS 381
Fig. 4. Average run length curve for the X-bar chart with a sample size varying
from 1 to 10 shown for a variety of delta values.
Fig. 3. Beta risk curve for X-bar chart with sample size varying from 1 to 10
shown for a variety of delta values.
sample data falling within control limits on the very first sample
after an increase in the standard deviation of the trend versus the
limits. This chart is observed for anomalies (i.e., for instances
relative increase in the standard deviation. The ratio of the new
when the sample average lies outside the control limits). The
standard deviation of the trend to the original standard deviation
sample is marked as a flagged event in case lies outside
of the trend is called a shift. The beta risk for X-bar charts is
the control limits.
computed using (7)
If the X-bar chart for a particular data set indicates that the
voltage profile is within the control limits, then these values of
the control limits are chosen as the performance indicators and
all new sample data are added to the existing chart without any
modification to the control limits. Otherwise, a procedure sim-
ilar to the one indicated in Step 2) is adopted until stable control where is the probability of not changing a shift in the
limits are obtained. bar chart immediately after the shift occurs; is the size of the
3) Introducing a New Restriction: Though control limits are changed
shift, ; and is the standard normal cumulative
a realistic boundary between healthy and poor regulation, not original
all excursions beyond the control limits in the profile can be at- density function
tributed to poor voltage regulation. Hence, there is a need to have
more conditions to assess the performance of voltage regulating (7)
devices.
Detecting flagged events on successive samples in the Fig. 3 shows the beta risk curve for X-bar charts as the sample
X-bar chart is a plausible condition for concluding a faulty regu- size varies from 1 to 10. It can be observed from the figure
lator. Such practical behavior is reasonable since, if at any time, that the probability of not detecting a small shift in the standard
a voltage regulator develops a fault, the regulation profile, in deviation of the trend data is very high.
general, should have a trend deviating from the normal. In other The beta risk values calculated using (7) can be utilized to
words, if the voltage regulator becomes faulty, there should be compute the average number of samples required to detect a
more flagged events in the X-bar chart, indicating a variation sudden and persistent shift in the trend of the voltage data. This
in the standard deviation of the trend. This realization leads to quantity is known as the average run length (ARL) and can be
an additional condition, which should be satisfied in assessing estimated as follows:
feeder voltage regulation performance.
4) Implementing the Restriction: To implement the new re- (8)
striction, it is necessary to monitor a certain specific number
of the voltage samples immediately after the detection of Fig. 4 shows the average run length curve for sample sizes 1
a flagged event. The optimum value of is statistically de- to 10, computed using (8). It can be observed that the average
termined using the operating characteristic (OC) curves (also number of samples required for detecting a specific shift in the
known as the beta risk curves) and the average-run length curves standard deviation of the trend decreases as the sample size
(ARL). increases. On average, it takes less than five samples of size
OC curves indicate the risk of not detecting a sudden and to detect a shift of 1.1 in the standard deviation of
persistent shift in the standard deviation of the voltage trend on the trend.
the very first sample after the shift has occurred [10], [12]. These Thus, for the sake of generality and application to any sample
curves are basically a plot of the probability (beta risk) of a size, it would be reasonable to observe ten voltage samples im-
Authorized licensed use limited to: Kasetsart University provided by UniNet. Downloaded on October 12,2023 at 08:34:13 UTC from IEEE Xplore. Restrictions apply.
384 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 1, JANUARY 2008
Fig. 8. X-bar chart (top) and R-chart (bottom) for the phase A voltage data
measured at substation 1.
Fig. 9. Run chart for the average voltage received at phase A at substation 1.
TABLE I
PARTIAL RESULTS OF THE ANALYSIS OF THE X-BARCHART IN FIG. 9 TABLE II
SEGREGATION RESULTS FOR THE FIRST FIVE SEGMENTS OF THE
RUN CHART IN FIG. 10
Fig. 11. Run chart for the average voltage received at phase A measured at
substation 2.
Fig. 10. X-bar chart (top) and R-chart (bottom) for the phase A voltage data 2) Run Chart Analysis: Analogous to the previous analysis
measured at substation 2. of voltage data acquired at substation 1, voltage data from sub-
station 2 are also analyzed using the technique based on the run
chart analysis. The threshold limits are determined assuming the
1) Control Chart Analysis: The zero mean adjusted voltage bandwidth of the installed voltage regulating equipment to be 2
data from the first few days are utilized to establish the control V. Fig. 12 shows the run chart constructed using the month-long
limits of the voltage data. The voltage data for the first three days voltage data obtained at the service entrance for substation 2. A
are analyzed assuming that the average values obtained from the glance at Fig. 11 indicated that there are huge violations of the
installed PQ meter correspond to the mean of four voltage sam- voltage bandwidth at substation 2. Nevertheless, the proposed
ples (i.e., ) to obtain the control limits for the R-chart as analysis is implemented further to verify this.
and , with the centerline located at The run chart in Fig. 11 is segmented such that there are
. The R-chart is subsequently plotted and observed eight samples per segment. The voltage samples in each seg-
for exceptions which, in this case, looked reasonable enough to ment are segregated into three categories depending on whether
be used for further studies. Using these as the nominal values the voltage sample lies within the boundary limits or beyond.
for indicating the health of the installed voltage regulator, the The trend in each of the three categories is analyzed for anoma-
standard deviation is computed to have a value of 0.8113. lies. Graphs similar to Fig. 6 can be plotted and examined in
The control limits for the X-bar chart are computed using (6) as, small clusters to identify the number of runs and continuous
and . The X-bar chart and groups lying beyond the boundary limits in each cluster. Table V
R-charts in Fig. 10 are thus constructed from the month-long shows the partial results obtained for the analysis of the trend in
voltage data obtained from substation 2. the clusters for the voltage points lying beyond the upper limit.
The X-bar chart in Fig. 10 is processed for the detection of The results in Table V verify that a substantial number of ex-
flagged events. Table IV shows partial results corresponding to cursions lies beyond the boundary limits as predicted by visual
voltage samples on the fourth day of measurement. It can be observation of Fig. 11. A large part of the segments in all of
observed both in Fig. 10 and the results in Table IV that the the clusters lies beyond the upper limit with the mean voltage
voltages at the substation trigger many of the flagged events in the range of almost twice the boundary limits. This clearly
with voltage values that are approximately four times larger than indicates a continuous deviation in the voltage profile. The per-
the control limits. This is indicative of a strong deviation in the sistent trend deviation over a one-month period is indicative of
trend of the voltage across the feeder. Such deviation in the trend possible regulator problems, changes in load patterns that re-
cannot be attributed to the variation in the load alone and can quire adjustments of regulator settings, and other issues. The
be indicative of a flawed voltage regulation at the feeder in the statistical trend analysis results can be used to help engineers
substation as well. detect possible abnormal developments in the system.
Authorized licensed use limited to: Kasetsart University provided by UniNet. Downloaded on October 12,2023 at 08:34:13 UTC from IEEE Xplore. Restrictions apply.
388 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 1, JANUARY 2008
TABLE V [5] N. Eickelmann and A. Anant, “Statistical process control: What you
RESULTS OBTAINED WHEN ANALYZING THE TREND IN don’t measure can hurt you!,” IEEE Softw., vol. 20, no. 1, pp. 49–51,
THE VOLTAGE POINTS LYING ABOVE THE UPPER LIMIT Jan./Feb. 2003.
[6] B. J. Hoopes and K. P. Triantis, “Efficiency performance, control
charts, and process improvement: Complementary measurement and
evaluation,” IEEE Trans. Eng. Manag., vol. 48, no. 2, pp. 239–253,
May 2001.
[7] P. Jalote and A. Saxena, “Optimum control limits for employing sta-
tistical process control in software process,” IEEE Trans. Softw. Eng.,
vol. 28, no. 12, pp. 1126–1134, Dec. 2002.
[8] W. Zhang and T. Yu, “Control charts and process capability,” in Proc.
IEEE Int. Conf. Manag. Innovation Technol., 2000, vol. 2, pp. 904–909.
[9] W. Sunderman, “Automated detection of voltage unbalance con-
ditions,” presented at the Elect. Power Res. Inst. Power Quality
Assurance Conf., Long Island, NY, May 2004.
[10] A. J. Duncan, Quality Control And Industrial Statistics. Homewood,
IL: R. D. Irwin, Inc., 1974.
[11] Manual on Presentation of Data and Control Chart Analysis, 7th ed.
West Conshohocken, PA: ASTM Int., 2002.
VI. SUMMARY [12] D. Drain, Statistical Methods For Industrial Process Control, 1st ed.
London, U.K.: Chapman & Hall, 1997.
This paper is motivated by the lack of utilization of volu-
minous steady-state PQ data collected alongside the transient Nitika V. Mago received the B.E. and M.S.E. degrees in electrical and computer
waveform data. In this paper, we demonstrated that trend engineering from Mumbai University’s Veermata Jijabai Technological Institute
(VJTI), Mumbai, India, in 2005 and the M.S.E. degree from the University of
analysis can be accomplished using statistical process control Texas at Austin in 2007.
methods. In particular, we developed novel procedures based Currently, she is with the Electric Reliability Council of Texas, Taylor, TX.
on statistical process control methods to analyze steady-state Her research interests include the development of smart algorithms for using raw
steady-state data for predictive operation and maintenance of power equipment,
rms voltage data. We confirmed their efficacies and their uti- application of distributed computing for developing time-efficient models for
lization in assessing feeder voltage regulation. We showed that nodal power system analysis, power systems quality and harmonics, and wind
both the data and methods can be used to indicate possible energy systems.
poor regulation, regulator problems, or other related problems.
The regulation assessment outcome is not intended as the sole
indicator; rather it is one of many other possible indicators. The Surya Santoso (M’96–SM’02) received the M.S.E. and Ph.D. degrees in elec-
trend analysis methods presented before can provide engineers trical and computer engineering from the University of Texas at Austin in 1994
and 1996, respectively.
with an insight about the steadiness of the long-term data and He rejoined the University of Texas at Austin as an Assistant Professor in
to detect any abnormal behavior that might unfold. 2003. Prior to joining the University of Texas, he was a Consulting Engineer
with Electrotek Concepts, Inc., Knoxville, TN, for seven years. His research in-
terests include the development of intelligent systems for analyzing raw power-
REFERENCES quality measurement data, power system modeling and studies, and wind power.
[1] T. K. Abdel-Galil, E. El-Saadany, A. M. Youssef, and M. M. A. Salama, He coauthored Electric Power Systems Quality (McGraw-Hill, 2002).
“Disturbance classification using hidden Markov models and vector
quantization,” IEEE Trans. Power Del., vol. 20, no. 3, pp. 2129–2135,
Jul. 2005.
[2] S. R. McCormick, K. Hur, S. Santoso, A. Maitra, and A. Sundaram, Mark F. McGranaghan (M’77–SM’03) is Associate Vice President with
“Capacitor bank predictive maintenance and problem identification EPRI, Knoxville, TN. He coordinates a wide range of services offered to
using conventional power quality monitoring systems,” in Proc. IEEE electric utilities and critical industrial facilities throughout the world. These
Power Eng. Soc. General Meeting, 2004, vol. 2, pp. 1846–1850. services include research projects, seminars, monitoring services, power
[3] S. Santoso, J. D. Lamoree, and M. F. McGranaghan, “Signature anal- systems analysis projects, performance benchmarking, testing services, failure
ysis to track capacitor switching performance,” in Proc. IEEE Power analysis, and designing solutions for system performance improvement. His
Eng. Soc. Transmission Distribution Conf. Expo., 2001, vol. 21, pp. technical background is in the area of power system modeling and analysis.
259–263. He is an expert in the areas of harmonic analysis, transient analysis, reliability,
[4] S. Santoso, R. C. Dugan, J. D. Lamoree, and A. Sundaram, “Distance power quality improvement, and power systems monitoring applications. He
estimation technique for single line-to-ground faults in a radial distri- has written many papers.
bution system,” in Proc. IEEE Power Eng. Soc. Winter Meeting, 2000, Mr. McGranaghan is active in IEEE and IEC standards development, and has
vol. 4, pp. 2551–2555. taught power system workshops and seminars throughout the world.
Authorized licensed use limited to: Kasetsart University provided by UniNet. Downloaded on October 12,2023 at 08:34:13 UTC from IEEE Xplore. Restrictions apply.