KH wationat National Metrology Centre (NMC)
Metrology Centre 2 Fusionopolis Way, #08.05, Innovis,
Singapore 138634
NMc
TEST REPORT
: 01004309 Page 4 of 2
: Hydro Dynamic Engineering Pte Ltd
48 Toh Guan Road East
#08-97, Enterprice Hub
Singapore 608586
Subject Details
Subject Water Tank - Sunlight Transmission Test
Test Sample *SUNGIL” GRP sectional water tank
Sales Order No 2 202802831611
Test Date 2021-05-25
Site Ambient Conditions
Temperature 33°C
Relative Humidity 70 % relative humidity
pach
Bay Swee Pheng Liu Yuanjie
Testing Officer Approving Officer
Optical Metrology
Date of Issue : 9 02|- 05-2]
For further enquires, please contac the Approving Offices at Tel: +85 6714 8242 or Email lu_yuanje@nme.a-star-edu.sg
apply of Services Terms and Constons"avelale st wena eu.sg/nme ana. request ort National M
(CREATING GROWTH, ENHANCING LIVES
+65 67149200
Amember of ASSTAR Research Entities (Co, Reg. No. 1997021104) www.a-star.edu.sginmeReport No. : 0L004309 Page 2 of 2
Method of Testing
‘The subject has been tested at TUV SUD PSB Pte Ld, 60 Tuas South Street 1, $(639925) open site
between 11.30 am to 13.00 pm under the ambient conditions stated above with'a horizontal illuminance
value of more than 10 kx.
‘The measurement was carried out using a working standard illuminance meter S380 (s/n: 38044), which
is traceable to national reference standards maintained at NMC.
The illuminance measurements on the water tank were performed in accordance with the method
described in the appendix J of the Singapore Standard SS 245 : 2014, The Ratio was calculated based on
the following formula:
ILLUMINANCE INSIDE THE TANK (lux) _
Ratio =
ILLUMINANCE OUTSIDE THE TANK (lee)
Results of Testing
Testing results of Water Tank ~ Sunlight Transmission Test
‘Test Sample: "SUNGIL’ GRP Water Tank 2m x 1m x 4m (HT)):
(Reston Rato 7]
| Comer (point A) 0.000029 95 |
Manhole (point B) 0.000 043 13 |
CE Roof (point C) 000002888
Tankwall(pointDy | (0.000031 63
Suaight 7 ‘oem
om
Remark: The Ratio shall not exceed 0.001 as required by Singapore Standard SS 245 : 2014
The expanded uncertainty of measurement is 25 % of the indicated value of test meter, estimated at a
level of confidence of approximately 95 % with a coverage factor k = 2.
‘The user should determine the suitability of the subject for its intended use.
bask
esting Officer