Reverse Power (Current) Relay

The document provides information about the Rishabh Reverse Power Protector, which protects generators from motoring during engine failure or surges during synchronization. It monitors current and voltage to detect reverse power flow. Key features include adjustable setpoints for the trip level and time delay, LED trip indication, auto reset, and internal differential protection. It is intended for generator set or feeder protection applications.

Uploaded by

jaytamij
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
463 views3 pages

Reverse Power (Current) Relay

The document provides information about the Rishabh Reverse Power Protector, which protects generators from motoring during engine failure or surges during synchronization. It monitors current and voltage to detect reverse power flow. Key features include adjustable setpoints for the trip level and time delay, LED trip indication, auto reset, and internal differential protection. It is intended for generator set or feeder protection applications.

Uploaded by

jaytamij
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

RISH Lay

The Protector Trip Relay Series

Data Sheet
Reverse Power (Current)
Relay

www.rishabh.co.in Page 1 of 3 Version : 1 / 03 / 0611 / A


Model available Hysteresis : Pre-set at 1%
Output Relay
Type : DP changeover
Rating : 240V 5A non-inductive
Function / System Type D.C. : 24V 5A resistive
Operations : 0.2 million at the above
loads
Reset : Automatic

Other Specifications
0 0
Operating temperature : 0 C to +60 C
Storage temperature : -200 C to +700 C
0
Temp. co-efficient : 0.05% per C
Application Interference immunity : Electrical stress surge
The Rishabh Reverse Power Protector provides continuous withstand and non function
surveillance for a.c. generators operating in parallel or for to ANSI/IEEE C37 90a
boosting mains supplies. Enclosure style : DIN-rail with wall mounting
On site adjustment of the trip point and time delay ensures facility
accurate protection against “motoring’ in the event of engine Material : Flame retardant
failure and prevents tripping from surges during synchonising. polycarbonate /ABS
Enclosure integrity : IP 50
• Generator Set Protection -
Model 256 dimensions : 150mm(5.9")wide x 70mm(2.8")H
For detecting loss of the prime mover x 112mm (4.4") deep
( engine ) and preventing motoring. Weight : Approximately 1.0kg
• Feeder protection -
To detect reverse power under fault Principle of operation
conditions.
The generator voltage provides the power supply for the relay
energising circuit and phase reference for the phase sensitive
Features detector. Current reference to the detector is taken from
• Adjustable setpoint generator load current.
• Adjustable time delay The output from the detector is compared with a reference
which is set by the trip set point potentiometer. When the set
• LED trip indication point value is exceeded an electronic trip operator to energise
• 2 pole relay contacts the relay circuit though an adjustable time delay.
• Internal differential
(factory settable only)
Setting up Instructions
• Auto Reset

The “ % set ” potentiometer trimmer on the front label is


Specifications calibrated as a percentage of the input current rating e.g. of
Nominal voltage : 100, 110, 120, 220, 230, 5A and not of the forward kW.
240,380, 400, 415 or 440V Adjust the “ % set ” trimmer to the required tripping value,
Overload : 1.2 x rating continuously Setting accuracy can be checked by reversing the current
lead connections and, with forward power, measuring the trip
1.5 x rating for 10 seconds, point value on a suitable ammeter (reconnect leads on
acc. to BS 6253 completion). Units with built - test switch simplify this
Voltage Burden : 3 VA maximum operation.
Nominal Current : 5A or 2, 3, 4, 6, 8 & 10A Adjust the ‘Delay’ to the required time delay 10 seconds is
normally adequate.
Overload : 2 x Rated current continuously
10 x rating for 10 seconds acc. to
BS 6253 Options
Current Burden : 2VA maximum • Adjustment ranges – different adjustment ranges are possible
: 50/60Hz or 400Hz on for the set point and time delay controls.
Frequency
request • Relay operation – standard models are fail safe, but the
Setpoint relays can be customised to energise or de-energise on trip.
Adjustments : Reverse power: 2-20%
Time delay: 0-20 seconds
Repeatability : > 0.5% of full span

www.rishabh.co.in Page 2 of 3 Version : 1 / 03 / 0611 / A


Connection diagram
INPUT VOLTS
L N Single phase
L1 N 3 phase 4 wire
L1 L2 L3 3 phase 3 wire

PROTECTOR 2 5 8
10 12
8
5 15 L Cos 16
11 21 4
0 20 2 20
S %
12 14 22 24
DELAY SET
11 12 14 21 22 24 1 3
S1 - k S2 - l
Contact Set 1 Contact Set 2 X1 X2
Output Relay INPUT AMPS

256-PAS/PAT/PAQ/PAR

Note: Only one CT connection is required, from the same phase as the
voltage connection to terminal 2.

Dimensions
B
112.5
A
Model 256

50

60
70
35

2 FIXING HOLE ‘A’ 2 FIXING HOLE ‘B’


RELEASE CLIP
TO SUIT M4 TO SUIT M5

Ordering Informations
Please quote :
1. Product Type.
2. Please specify standard or non standard trip. An energised
relay is indicated by a “Lit” red LED. Setpoint can be factory
adjusted to your requirements.
3. System Voltage and/or Current where applicable.
4. System Frequency.
5. Preset Differential where required.
6. Time delay where applicable.

RISHABH INSTRUMENTS PVT.LTD.


F-31, MIDC, Satpur, Nashik-422 007,India.
Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064
E-mail : India :- marketing@rishabh.co.in
International :- exp.marketing@rishabh.co.in
www.rishabh.co.in