Professional Documents
Culture Documents
1706 Vitodens 100-W B1HC B1KC Installation and Service Instructions
1706 Vitodens 100-W B1HC B1KC Installation and Service Instructions
for contractors
Vitodens 100-W
Type B1HC, B1KC, 4.7 to 35.0 kW
Wall mounted gas condensing boiler
Natural gas and LPG version
Gas Council Number: 41-819-40, 41-819-41, 41-819-42, 41-819-43, 47-819-40,
47-819-41, 47-819-42
VITODENS 100-W
Danger Note
This symbol warns against the risk of injury. Details identified by the word "Note" contain additional
information.
! Please note
This symbol warns against the risk of material
losses and environmental pollution.
Target group
These instructions are exclusively intended for quali- ■ Work on gas installations may only be carried out by
fied contractors. a registered gas fitter.
■ Work on electrical equipment may only be carried
out by a qualified electrician.
■ The system must be commissioned by the system
installer or a qualified person authorised by the
installer.
Regulations to be observed
2
Safety instructions
Safety instructions (cont.)
! Please note
Spare and wearing parts that have not been tes-
ted together with the system can compromise its
function. Installing non-authorised components
and making non-approved modifications or con-
versions can compromise safety and may inva-
lidate our warranty.
For replacements, use only original spare parts
supplied or approved by Viessmann.
Danger Danger
Escaping gas can lead to explosions which may Contact with condensate can be harmful to
result in serious injury. health.
■ Do not smoke. Prevent naked flames and Never let condensate touch your skin or eyes
sparks. Never switch lights or electrical appli- and do not swallow it.
ances on or off.
■ Close the gas shut-off valve. Flue systems and combustion air
■ Open windows and doors.
■ Evacuate any people from the danger zone. Ensure that flue systems are clear and cannot be
■ Notify your gas or electricity supply utility from sealed, for instance due to accumulation of conden-
outside the building. sate or other causes. Ensure an adequate supply of
■ Have the power supply to the building shut off combustion air.
from a safe place (outside the building). Inform system users that subsequent modifications to
the building characteristics are not permissible (e.g.
If you smell flue gas cable/pipework routing, cladding or partitions).
Danger Danger
Flue gas can lead to life threatening poisoning. Leaking or blocked flue systems, or an inade-
■ Shut down the heating system. quate supply of combustion air can cause life
■ Ventilate the installation site. threatening poisoning from carbon monoxide in
■ Close doors to living spaces to prevent flue the flue gas.
gases from spreading. Ensure the flue system is in good working order.
Vents for supplying combustion air must be non-
What to do if water escapes from the appliance closable.
Danger Extractors
If water escapes from the appliance there is a
risk of electrocution. Operating appliances that extract air to the outside
Switch OFF the heating system at the external (extractor hoods, extractors, air conditioning units, etc.)
isolator (e.g. fuse box, domestic distribution can create negative pressure. If the boiler is operated
board). at the same time, this can lead to reverse flow of the
flue gas.
Danger
If water escapes from the appliance there is a Danger
risk of scalding. The simultaneous operation of the boiler and
Never touch hot heating water. appliances that extract air to the outside can
result in life threatening poisoning due to
reverse flow of the flue gas.
Fit an interlock circuit or take suitable steps to
ensure an adequate supply of combustion air.
5697 787 GB
3
Index
Index
5. Changing the gas type Changing from operation with LPG to operation with natural gas ......... 47
■ Checking the CO2 content .................................................................. 48
4
Index
Index (cont.)
5
Information
Disposal of packaging
Symbols
Step in a diagram:
1. Symbol Meaning
The numbers correspond to the order in
which the steps are carried out. Steps required during commissioning
6
Information
Intended use
The appliance is intended solely for installation and Any usage beyond this must be approved by the man-
operation in sealed unvented heating systems that ufacturer in each individual case.
comply with EN 12828, with due attention paid to the
associated installation, service and operating instruc- Incorrect usage or operation of the appliance (e.g. the
Information
tions. It is only designed for heating up heating water appliance being opened by the system user) is prohibi-
that is of potable water quality. ted and will result in an exclusion of liability. Incorrect
usage also occurs if the components in the heating
Intended use presupposes that a fixed installation in system are modified from their intended use (e.g. if the
conjunction with permissible, system-specific compo- flue gas and ventilation air paths are sealed).
nents has been carried out.
Product information
Product description
The Vitodens 100-W is available as a gas condensing These boilers are only intended for installation in
system boiler for the connection of one DHW cylinder sealed unvented heating systems. Boilers for open
and as a gas condensing combi boiler with an integral vented heating systems are also available.
plate heat exchanger for DHW heating. For the con- If the Vitodens 100-W is installed in an S plan or Y
nection of heating circuits and the DHW cylinder or the plan system, the two internal connections are not used
DHW line, see page 12 onwards. and must be capped off during installation.
In the delivered condition, the Vitodens 100-W is set
up for operation with a constant boiler water tempera- The following components are integrated into the
ture. By connecting an outside temperature sensor hydraulic system:
(accessories), the boiler can be operated in weather- ■ Circulation pump
compensated mode. ■ 3-way diverter valve
The following are integrated: one sealed unvented ■ Safety valve
hydraulic system with 2 connections for heating flow ■ Diaphragm expansion vessel
and return, and 2 connections for cylinder heating (gas ■ Plate heat exchanger for DHW heating (gas con-
condensing system boiler) or DHW heating (gas con- densing combi boiler)
densing combi boiler).
If a Viessmann Vitocell is connected, a cylinder tem- If a different DHW cylinder is connected, the cylinder
perature sensor will issue the heat demand (accesso- temperature sensor (accessories) may also be used
ries). The cylinder temperature sensor is connected to on this cylinder. Alternatively, a 230 V cylinder temper-
the boiler control unit. A 230 V cylinder temperature ature controller should be connected via the cylinder
5697 787 GB
controller is not required. demand junction box (part of the boiler standard deliv-
ery).
7
Information
Product description (cont.)
Connecting accessories
5697 787 GB
8
Preparing for installation
Preparing for installation
350
250
400 156
5
68
Installation
860
700
1800 G
1925 H
A B C D E
F
58 58 34
123 123 125
Fig. 1
Note
Dimensions of connections in conjunction with the con-
nection accessories provided.
5697 787 GB
9
Preparing for installation
Preparing for installation (cont.)
plied.
Note
The supplied rawl plugs are suitable for the follow-
ing materials:
250
109
■ Concrete
146
Fig. 2
! Please note
To prevent appliance damage,
connect all pipework free of load and torque
system.
10
Preparing for installation
Preparing for installation (cont.)
Installation
5697 787 GB
11
Installation sequence
Mounting the boiler and making connections
Fig. 3
A B C D E
z z
¨
Fig. 4
12
Installation sequence
Mounting the boiler and making connections (cont.)
Gas condensing system boiler Permiss. DHW operating pressure: 10 bar (1.0 MPa)
Note
Install a pressure reducer if required.
Installation
E
Fig. 5
D
E
B
A
C
Fig. 6
F Filling device
5697 787 GB
13
Installation sequence
Mounting the boiler and making connections (cont.)
Gas connection
Note
Only use suitable and approved leak detection
agents (EN 14291) and devices for the tightness
test. Leak detection agents with unsuitable constit-
uents (e.g. nitrides, sulphides) can cause material
Installation
A damage.
Remove residues of the leak detection agent after
testing.
Fig. 7
! Please note
Excessive test pressure will damage the
boiler and the gas train.
Max. test pressure 150 mbar (15 kPa).
Where higher pressure is required for tight-
ness tests, disconnect the boiler and the gas
train from the main supply pipe (undo the fit-
ting).
! Please note
A frozen condensate pipe can result in faults
and damage to the boiler.
Always protect condensate pipes against frost.
■ Observe local building regulations.
A
Connect condensate pipe A to the public sewage sys-
tem with a constant fall and a pipe vent.
Observe local waste water regulations.
Fig. 8 Note
Fill the trap with water before commissioning.
5697 787 GB
14
Installation sequence
Mounting the boiler and making connections (cont.)
! Please note
During commissioning, flue gas may escape
from the condensate drain.
Always fill the trap with water before commis-
sioning.
Installation
Fig. 9
Note Note
Only use the "System certificate" and "Skoberne The back draught safety device available as an acces-
GmbH flue system" labels in conjunction with the sory must be installed on every boiler.
Viessmann flue system made by Skoberne.
Only carry out commissioning when the following
conditions have been met:
■ Unrestricted flow in the flue gas routes.
■ Positive pressure flue system is gas-tight.
■ Inspection port covers checked for secure and tight
seating.
■ Apertures for supplying sufficient combustion air are
open and cannot be closed.
■ All current regulations on installing and commission-
ing flue systems have been observed.
Danger
Leaking or blocked flue systems, or an inade-
quate supply of combustion air can cause life
threatening poisoning from carbon monoxide in
Fig. 10 the flue gas.
Ensure the flue system is in good working order.
Connect the balanced flue pipe. Vents for supplying combustion air must be non-
During installation and positioning of the flue system, closable.
observe Building Regulations Part L and BS 5440.
15
Installation sequence
Removing the front panel
2.
Installation
1.
2x
Fig. 11
1. Undo the screws on the underside of the boiler; do 2. Remove front panel.
not remove them completely.
2.
3.
4x 2x 1.
Fig. 12
5697 787 GB
16
Installation sequence
Opening the control unit enclosure (cont.)
! Please note
Electronic assemblies can be damaged by elec-
trostatic discharge.
Prior to commencing any work, touch earthed
objects such as heating or water pipes to dis-
charge static loads.
Electrical connections
Installation
When connecting accessories observe the sep-
arate installation instructions provided with
them.
D
96
? L
C E F
%
4 3 2 1
A B
Fig. 13
17
Installation sequence
Electrical connections (cont.)
Connection of room temperature controller with time switch and DHW cylinder with 2-way valve and 230 V cylin-
der temperature controller
Installation
% C
A H
M
1~
G E
Fig. 14
18
Installation sequence
Electrical connections (cont.)
Cable entry
Installation
Fig. 15
1. Fit the outside temperature sensor. 2. Connect the outside temperature sensor to the
connecting cable across terminals 3 and 4 at slot
Installation location: "X21" (see page 17).
■ North or north-westerly wall, 2 to 2.5 m above
ground level; in multi storey buildings, in the
upper half of the second floor
■ Not above windows, doors or vents
■ Not immediately below balconies or gutters
■ Never render over
■ Connection:
2-core lead, length up to 35 m with a cross-sec-
tion of 1.5 mm2
C
B X1/96
1 LN
A NO
NC
COM
19
Installation sequence
Electrical connections (cont.)
Power supply
! Please note
Connecting cables/leads will be damaged if they
touch hot components.
When routing and securing cables/leads on site,
ensure that the maximum permissible tempera-
ture for these is not exceeded.
3.
2.
1.
Fig. 17
5697 787 GB
20
Commissioning, inspection, maintenance
Steps - commissioning, inspection and maintenance
Commissioning steps
Inspection steps
Maintenance steps Page
21
Commissioning, inspection, maintenance
Filling the heating system
5697 787 GB
22
Commissioning, inspection, maintenance
Filling the heating system (cont.)
4. Close valve C.
Fig. 18
Note
The cold water supply must be open.
B D C A
Fig. 19
Note
Inadequate venting can result in damage due to steam
blasts in the heat exchanger.
5697 787 GB
23
Commissioning, inspection, maintenance
Venting the boiler by flushing (cont.)
C B
Fig. 20
In the delivered condition, the boiler is set up for oper- Enter the selected gas type and the associated limits
ation with natural gas (G 20). for flue gas emissions in the table below.
For operation with a different gas type, install a conver-
sion kit and change the gas type at the control unit. For values, see separate installation instruc-
tions.
Separate installation instructions
24
Commissioning, inspection, maintenance
Checking the static pressure and supply pressure
Note
Use a suitable tester with a resolution of at least
0.1 mbar (10 Pa) to check the supply pressure.
Fig. 21 Danger
Gas escaping from the test connector leads
to a risk of explosion.
1. Close the gas shut-off valve. Check gas tightness at test connector A.
Set value:
■Natural gas: 20 mbar (2.0 kPa)
■LPG: 37 mbar (3.7 kPa)
25
Commissioning, inspection, maintenance
Reducing the maximum heating output
26
Commissioning, inspection, maintenance
Matching the circulation pump rate to the heating system
In its delivered condition the circulation pump rate is ■ For heating mode with outside temperature sen-
set to the following values: sor:
■ For DHW heating: speed 100 % Rated heating output in 19 26 30 35
■ For heating mode without outside temperature kW
sensor:
Min. speed in % 72 72 72 72
Rated heating output in 19 26 30 35
Max. speed in % 72 80 86 100
kW
The maximum speed can be changed. See the fol-
Speed in % 72 80 86 100
lowing chapter.
The speed cannot be changed.
100
D
90 C
B
Circulation pump in %
80
E
70
A
60
Speed
50
-25 -20 -15 -10 -5 0 5 10 15 20 25
Outside temperature in °C
Fig. 22
Only when operating with an outside temperature sen- 6. Use / to select "6".
sor.
7. OK to confirm.
1. Tap MODE. The selected max. speed in % will flash in the r.h.
display area.
2. / repeatedly until CONFI flashes.
8. Use / to change the speed value.
3. OK to confirm. Max. speed and setting range are subject to appli-
"P" is displayed in the l.h. display area. The r.h. ance-specific parameters.
display area flashes.
9. OK to confirm. The selected value is adopted.
4. Use / to select "12".
5. OK to confirm.
"1" flashes in the l.h. display area.
To match the burner output to the system flue pipe 03. OK to confirm.
length, a correction factor can be set. "P" is displayed in the l.h. display area. The r.h.
display area flashes.
01. Tap MODE.
04. Use / to select "12".
5697 787 GB
27
Commissioning, inspection, maintenance
Matching the burner output to the flue system (cont.)
05. OK to confirm. 08. Refer to the following table for the correction factor
"1" flashes in the l.h. display area. required for the connected flue system.
06. Use / to select "3". 09. Use / to change the correction factor.
Correction factor 0 1 2 3 4 5 6
Flue system Rated heat- Max. pipe length (m)
ing output
(kW)
Open flue operation 7 60 mm 19 3 9 15 — — — —
26 3 12 15 — — — —
30 5 9 15 21 25 — —
35 4 9 15 22 25 — —
Room sealed operation 7 60/100 mm 19 2 5 9 15 20 — —
coaxial 26 2 6 11 16 20 — —
30 3 5 8 12 16 20 25
35 2 5 8 12 16 25 —
Open flue operation 7 80 mm 19 7 25 — — — — —
26 16 25 — — — — —
30 17 25 — — — — —
35 11 25 — — — — —
Room sealed operation 7 80/125 mm 19 2 10 18 25 — — —
coaxial 26 5 20 25 — — — —
30 7 13 22 25 — — —
35 5 13 22 25 — — —
04. Use / to select "12". 08. Refer to the following tables for the correction fac-
tor required for the flue system.
5697 787 GB
28
Commissioning, inspection, maintenance
Burner adjustment when connecting multiple… (cont.)
09. Use / to set the correction factor. One boiler per floor
a
2.5 m
3m
Fig. 23
29
Commissioning, inspection, maintenance
Burner adjustment when connecting multiple… (cont.)
30
Commissioning, inspection, maintenance
Burner adjustment when connecting multiple… (cont.)
Note
The correction factor changes the boiler modulation
range.
5697 787 GB
31
Commissioning, inspection, maintenance
Burner adjustment when connecting multiple… (cont.)
a
2.2 m
3m
0.3 m
Fig. 24
32
Commissioning, inspection, maintenance
Burner adjustment when connecting multiple… (cont.)
33
Commissioning, inspection, maintenance
Burner adjustment when connecting multiple… (cont.)
Note
The correction factor changes the boiler modulation
range.
34
Commissioning, inspection, maintenance
Adjusting the burner settings if several… (cont.)
05. OK to confirm. 08. Refer to the following tables for the correction fac-
"1" flashes in the l.h. display area. tor required for the flue system.
06. Use / to select "4". 09. Use / to set the correction factor.
Fig. 25
35
Commissioning, inspection, maintenance
Adjusting the burner settings if several… (cont.)
36
Commissioning, inspection, maintenance
Adjusting the burner settings if several… (cont.)
Note
The correction factor changes the boiler modulation
range.
37
Commissioning, inspection, maintenance
Checking the CO2 content (cont.)
2. Start the boiler and check for leaks. 5. Check the CO2 content for the lower heating output
(20 %).
Danger The CO2 content must be between 0.5 and 0.9 %
Escaping gas leads to a risk of explosion. below the value of the upper heating output.
Check all gas equipment for tightness.
6. ■ If the CO2 content is within the indicated range,
3. To check the CO2 content the burner output can be continue with point 8.
adjusted manually. ■ If the CO2 content lies outside the indicated
1. Tap MODE. range, check the balanced flue system for tight-
2. / repeatedly until "SERV" appears. ness; remedy any leaks.
3. OK to confirm. Replace gas train if required.
OFF appears on the display. Test mode is not
active. 7. Re-check the CO2 content for the upper and lower
4. Use / to adjust the burner output:
heating output.
Shown on Burner output
display 8. Terminate test mode:
OFF 0% 1. / repeatedly until "SERV" flashes.
_ 20 20 % 2. OK to confirm.
The selected value flashes.
__ 40 40 %
3. repeatedly until OFF flashes.
___ 60 60 % 4. OK to confirm.
____ 80 80 % When "SERV" disappears, test mode is termi-
_____ 100 100 % nated.
5697 787 GB
38
Commissioning, inspection, maintenance
Removing the burner
F4x E D
C B A
Fig. 27
1. Switch OFF the power supply. 5. Undo gas supply pipe fitting E.
2. Shut off the gas supply. 6. Undo 4 screws F and remove the burner.
Check burner gasket A for damage and replace if Replace the burner gauze assembly if it is damaged.
necessary.
5697 787 GB
39
Commissioning, inspection, maintenance
Checking the burner gasket and burner gauze… (cont.)
E D C A
2x
Fig. 28
! Please note
Tighten screws enough
to ensure the components do not suffer
to ensure the components do not suffer
damage and will function correctly.
40
Commissioning, inspection, maintenance
Checking and adjusting the electrode (cont.)
! Please note
Tighten screws enough
to ensure the components do not suffer
8+2
damage and will function correctly.
4+0,5
Fig. 29
! Please note
Scratches to the surfaces of the heat exchanger
that come into contact with hot gas can result in
Note
Discolouration on the heat exchanger surface is a nor-
mal sign of use. It has no bearing on the function and
corrosion damage. service life of the heat exchanger.
Never use brushes to clean the heating sur- The use of chemical cleaning agents is not required.
faces.
! Please note
Brushing can cause deposits to become lodged
in the gaps between the coils.
Never use brushes to clean the heating sur-
faces.
41
Commissioning, inspection, maintenance
Checking the condensate drain and cleaning the trap
3. Clean trap A.
Fig. 31
A4x B C
F E D
Fig. 32
1. Fit the burner and tighten 4 screws A diagonally. 2. Insert the new gasket and tighten the fitting on gas
supply pipe B.
! Please note
Tighten screws enough
to ensure the components do not suffer
3. Refit Venturi extension C to the fan.
damage and will function correctly. 4. Fit cables to fan motor D, gas train E and ignition
unit F.
5697 787 GB
42
Commissioning, inspection, maintenance
Installing the burner (cont.)
Danger
Escaping gas leads to a risk of explosion.
Check the fitting for gas tightness.
! Please note
The use of leak detection spray can result in
faulty operation.
Leak detection spray must not come into
contact with electrical contacts or block the
diaphragm opening on the gas valve.
Note Note
The expansion vessel can lose some of its charge The gas condensing combi boiler can be topped up by
pressure over time. When the boiler heats up, the opening top-up valve A.
pressure gauge will indicate a higher pressure of 2 or
3 bar (0.2 or 0.3 MPa). The safety valve may also
respond and discharge the excess pressure.
Therefore check the expansion vessel pre-charge
pressure annually.
A
Check whether the installed expansion vessel is ade-
quate for the system water volume (GB only).
Carry out this test on a cold system.
Checking all connections on the heating water and DHW sides for leaks
43
Commissioning, inspection, maintenance
Checking the firm seating of electrical connections
Danger
Escaping gas leads to a risk of explosion.
Check all gas equipment for tightness.
! Please note
The use of leak detection spray can result in
faulty operation.
Leak detection spray must not come into contact
with electrical contacts or block the diaphragm
opening on the gas valve.
1.
2.
2x
Fig. 34
1. Hook the front panel into place. 2. Tighten screws on the underside of the boiler.
Only possible for gas condensing combi boiler. The 04. OK to confirm.
comfort function makes DHW available faster at the "P" appears in the l.h. display area. The r.h. dis-
selected set DHW temperature. play area flashes.
44
Commissioning, inspection, maintenance
Setting the DHW comfort function (cont.)
06. OK to confirm.
"1" flashes in the l.h. display area.
06. OK to confirm.
"1" flashes in the l.h. display area.
45
Commissioning, inspection, maintenance
Setting the signal tone for display operation (cont.)
5697 787 GB
46
Changing the gas type
Changing from operation with LPG to operation with natural gas
F A
C D E
Fig. 35
Commissioning
1. Disconnect cable from gas train A. Changing the gas type at the control unit
2. Undo union nut B and remove gas gasket. 01. Turn ON the ON/OFF switch.
4. Remove gas restrictor D for LPG and gasket E 03. / repeatedly until CONFI flashes.
from gas train A.
04. OK to confirm.
5. Insert new gasket E in gas train A. "P" appears in the l.h. display area. The r.h. dis-
If the gasket is missing, order the appropriate con- play area flashes.
version kit as an individual part. See parts list
(burner assembly). 05. Use / to select "12".
! Please note
Tighten screws enough
to ensure the components do not suffer
07. Use / to select "5".
! Please note
The use of leak detection spray can result in
faulty operation.
Leak detection spray must not come into
contact with electrical contacts or block the
diaphragm opening on the gas valve.
5697 787 GB
47
Changing the gas type
Changing from operation with LPG to operation… (cont.)
5697 787 GB
48
Troubleshooting
Function sequence and possible faults
Display Measure
Control unit issues a heat No Increase set value and
demand ensure heat is drawn off
Yes
Fan starts No After approx. 1 min, fault Check the fan, fan con-
F9 necting cables, fan power
supply and fan control
Yes
Yes
Yes
Diagnosis
Ionisation current builds No Fault F4 Check electrode adjust-
(above 2 µA) ment and gas line for air-
Symbol A locks
Yes
Burner in operation No Shuts down below the set Check the flue system for
boiler water temperature tightness (flue gas recir-
and restarts immediately culation); check the gas
flow pressure
Fault display
Fig. 36
5697 787 GB
49
Troubleshooting
Fault display (cont.)
perature sensor
59 No DHW heating Lead break, outlet temper- Check sensor (see page 56).
ature sensor
5A Burner blocked Lead break, flow sensor Check connections and lead; re-
place sensor if required.
A3 Burner blocked. Flue gas temperature sen- Fit flue gas temperature sensor
sor incorrectly positioned. correctly (see page 58).
A9 Control mode without Open- Communication error, Check connections and cable; re-
Therm device OpenTherm device place OpenTherm device if re-
quired.
b0 Burner blocked Short circuit, flue gas tem- Check sensor (see page 57).
perature sensor
b7 Emergency mode Burner control unit fault Turn the ON/OFF switch off and on
again.
b8 Burner blocked Lead break, flue gas tem- Check sensor (see page 57).
perature sensor
E3 Burner in a fault state Fault in safety chain Check the temperature limiter and
connecting leads (see page 56).
Check the control unit and replace
if required.
E5 Burner blocked Internal fault Check the ionisation electrode and
connecting cables.
Press "Reset" (see page 51).
F0 Burner blocked. Internal fault Replace control unit.
F1 Burner in a fault state Max. flue gas temperature Check heating system fill level.
exceeded Check circulation pump. Vent the
system.
Press "Reset" (see page 51).
5697 787 GB
50
Troubleshooting
Fault display (cont.)
Diagnosis
Press "Reset" (see page 51).
FC Burner blocked Electrical fan control (con- Check fan connecting cable; re-
trol unit) faulty place if necessary or replace con-
trol unit
Fd Burner blocked Burner control unit fault Check ignition electrodes and con-
necting cables. Check whether a
strong interference (EMC) field ex-
ists near the appliance.
Press "Reset" (see page 51).
Replace control unit if fault per-
sists.
FF Burner blocked Burner control unit fault Check ignition electrodes and con-
necting cables. Check whether a
strong interference (EMC) field ex-
ists near the appliance.
Press "Reset" (see page 51).
Replace control unit if fault per-
sists.
51
Troubleshooting
Repairs
! Please note
Residual water will escape when the boiler or
one of the following components is fitted or
removed:
■ Water-filled pipework
■ Circulation pumps
■ Plate heat exchanger
■ Components fitted in the heating water or
DHW circuit
Water ingress can result in damage to other
components.
2.
1.
2x
Fig. 37
1. Undo the screws on the underside of the boiler but 2. Remove front panel.
do not remove them completely.
5697 787 GB
52
Troubleshooting
Repairs (cont.)
X20
4 3 2 1
Fig. 38
20
Diagnosis
10
8
6
-20 -10 0 10 20 30
Temperature in °C
Fig. 39 Sensor type: NTC 10 kΩ
5697 787 GB
53
Troubleshooting
Repairs (cont.)
A
Diagnosis
Fig. 40
2
Danger
1 The boiler water temperature sensor is
0.8
0.6 directly immersed in the heating water (risk
0.4 of scalding).
10 30 50 70 90 110
Drain the boiler before replacing the sensor.
Temperature in °C
Fig. 41
5697 787 GB
54
Troubleshooting
Repairs (cont.)
X20
Fig. 42
1
0.8
0.6
0.4
Diagnosis
10 30 50 70 90 110
Temperature in °C
Fig. 43
5697 787 GB
55
Troubleshooting
Repairs (cont.)
Fig. 44
Fig. 45
5697 787 GB
56
Troubleshooting
Repairs (cont.)
2
Drain the DHW line and the plate heat exchanger
(on the DHW side).
1
0.8
0.6
0.4
10 30 50 70 90 110
Temperature in °C
Fig. 46
Diagnosis
B
Fig. 47
57
Troubleshooting
Repairs (cont.)
1
0.8
0.6
0.4
10 30 50 70 90 110
Temperature in °C
Fig. 48
During commissioning, the control unit checks whether 2. If necessary, correct the position of the flue gas
the flue gas temperature sensor is correctly positioned. temperature sensor or replace the faulty flue gas
If the flue gas temperature sensor is incorrectly posi- temperature sensor.
tioned, commissioning is aborted and fault message
A3 is shown. 3. Tap and hold R for approx. 2 s and repeat commis-
sioning.
1. Check whether the flue gas temperature sensor is The check is repeated until it is completed suc-
correctly inserted. See previous diagram. cessfully.
C 4. Remove cap B.
Fig. 49
58
Troubleshooting
Repairs (cont.)
Checking or replacing the plate heat exchanger (gas condensing combi boiler)
B B
C D
F E
Diagnosis
A
Fig. 50
1. Shut off and drain the boiler on the heating water 5. Check the connections on the heating water side
and DHW sides. for contamination; clean or replace the plate heat
exchanger if required.
2. Pivot the control unit downwards.
6. Install in reverse order using new gaskets.
3. Undo 2 screws A on plate heat exchanger B and
remove plate heat exchanger with gaskets. Note
During installation, ensure the fixing holes are
Note aligned and the gaskets are seated correctly. Fit
During and after removal, small amounts of water the plate heat exchanger the right way round.
may trickle from the plate heat exchanger.
59
Troubleshooting
Repairs (cont.)
F4
Fig. 51
5697 787 GB
60
Parts lists
Overview of assemblies
B C
Components
D
E F
Fig. 52
61
Parts lists
Casing assembly
0007
0002
0001
0002
0003
0008
0008
Components
0005
0006
0003
0006
0004
Fig. 53
5697 787 GB
62
Parts lists
Casing assembly (cont.)
Pos. Part
0001 Front panel
0002 Profiled seal
0003 Viessmann logo
0004 Strain relief, upper part
0005 Air box floor
0006 Diaphragm grommets (set)
0007 Wall mounting bracket
0008 Vitodens 100 logo
Components
5697 787 GB
63
Parts lists
Heat cell assembly
0005 0001
0002
0001
0003
0003
0004
0014
0015
0006
0013 0004
0013
0014
0012 0015
0007
0008
0011 0009
0010
0011
Components
0016
0017
Fig. 54
5697 787 GB
64
Parts lists
Heat cell assembly (cont.)
Pos. Part
0001 Gasket DN 60
0002 Boiler flue connection
0003 Boiler flue connection plug
0004 Flue gasket
0005 Flue gas temperature sensor
0006 Heat exchanger
0007 Condensate hose
0008 Splash trap
0009 Tee connector
0010 Gas connection
0011 Gasket A 17 x 24 x 2 (5 pce)
0012 Burner
0013 Thermal insulation block
0014 Heat exchanger mounting bracket (set)
0015 O-ring 20.63 x 2.62 (5 pce)
0016 Condensate hose 400
0017 Corrugated hose 19 x 800 with ferrule/bend
Components
5697 787 GB
65
Parts lists
Burner assembly
0007 0006
0006
0009
0014
0008
Components
0010 0013
0008
0014
0011
0014
0012
0014
Fig. 55
5697 787 GB
66
Parts lists
Burner assembly (cont.)
Pos. Part
0001 Burner gasket (wearing part)
0002 Thermal insulation ring
0003 Cylinder burner gauze assembly (wearing part)
0004 Burner gauze assembly gasket
0005 Burner door
0006 Gasket, ionisation electrode (5 pce)
0007 Ignition/ionisation electrode
0008 Gasket, burner door flange (wearing part)
0009 Mounting plate, thermal insulation ring (2 pce)
0010 Radial fan NRG 118
0011 Gas valve
0012 Conversion kit G31
0013 Venturi extension
0014 Gasket A 17 x 24 x 2 (5 pce)
Components
5697 787 GB
67
Parts lists
Hydraulic assembly
0002
0001
0003
0010 0005
0007
0007 0010
0023
0003
0006
0007
0012
0018
0010
0021
0007 0004
0010 0020 0003
0009
0018 0013
0011
Components
0007 0009
0014 0013
0007
0007
0019
0015 0007
0007 0015
0016 0016
0019
0007
0015 0015
0016 0016
0022
0008
0017
0008
Fig. 56
5697 787 GB
68
Parts lists
Hydraulic assembly (cont.)
Pos. Part
0001 Diaphragm expansion vessel CRI 8
0002 MAG (diaphragm expansion vessel) padding profile
0003 Gasket A 10 x 15 x 1.5 (5 pce)
0004 MAG connection line (diaphragm expansion vessel) G 3/8
0005 Connection elbow HR (heating return)
0006 Profile hose HR (heating return)
0007 Spring clip DN 25 (5 pce)
0008 Clip 7 10 (5 pce)
0009 Clip 7 8 narrow (5 pce)
0010 O-ring 20.63 x 2.62 (5 pce)
0011 Air vent valve G 3/8
0012 Temperature sensor
0013 Circular seal washer 8 x 2 (5 pce)
0014 Profile hose HV (heating flow)
0015 Clip 7 18 (5 pce)
0016 O-ring 17 x 4 (5 pce)
0017 Pressure gauge
0018 Clip 7 8 (5 pce)
0019 Adaptor, hose connector
0020 Thermal circuit breaker
0021 Connection elbow HV (heating flow)
0022 Hydraulics (see hydraulic assembly, system or combi boiler)
0023 Hose 10 x 1.5 x 1500
Components
5697 787 GB
69
Parts lists
Hydraulic assembly, system boiler
0009
0007 0006 0001 - 0011 0002
0011 0007 0003 0014 0006 0013 0001
0002
0004
0009
0008
0005
0003
0006
0009 0008
0009
0009
0006
0008
0012
0010
Components
Fig. 57
5697 787 GB
70
Parts lists
Hydraulic assembly, system boiler (cont.)
Pos. Part
0001 Air vent valve
0002 O-ring 34 x 3 (5 pce)
0003 Check valve
0004 O-ring 23.7 x 3.6 (5 pce)
0005 Bypass cartridge
0006 Clip Ø 16 (5 pce)
0007 Stepper motor adaptor
0008 O-ring 19.8 x 3.6 (5 pce)
0009 O-ring 16 x 3 (5 pce)
0010 Clip Ø 18 (5 pce)
0011 Linear stepper motor
0012 Motor, circulation pump UPM3 15-75
0013 Safety valve
0014 Hydraulic assembly, system boiler
Components
5697 787 GB
71
Parts lists
Hydraulic assembly, combi boiler
0001
0002
0015
0016
0016
0005 0012
0006 0006
0009 0009 0003
0012
0002
0009
0026
0006 0025
0019
0008
0023
0011
Components
0018
0020 0011
0025 0019
0026
0006
0008
0009
0021
0009
0008
0010
Fig. 58
5697 787 GB
72
Parts lists
Hydraulic assembly, combi boiler (cont.)
Pos. Part
0001 Air vent valve for HK (heating circuit) pump
0002 O-rings 34 x 3 (5 pce)
0003 O-ring 23.7 x 3.6 (5 pce)
0004 Linear stepper motor
0005 Bypass cartridge
0006 Clip Ø 16 (5 pce)
0007 Stepper motor adaptor
0008 O-ring 19.8 x 3.6 (5 pce)
0009 O-ring 16 x 3 (5 pce)
0010 Clip Ø 18 (5 pce)
0011 Clip Ø 10 (5 pce)
0012 Check valve
0013 Temperature sensor
0014 Clip Ø 8 narrow (5 pce)
0015 Water volume controller
0016 Oval cap seal (5 pce)
0017 Gasket set PWT
0018 Flow sensor
0019 O-ring 9.6 x 2.4 (5 pce)
0020 Expansion vessel
0021 Motor, circulation pump UPM3 15-75
0022 Plate heat exchanger
0023 Safety valve
0024 Hydraulic assembly, combi boiler
0025 Clip Ø 8 (5 pce)
0026 Circular seal washer 8 x 2 (5 pce)
Components
5697 787 GB
73
Parts lists
Control unit assembly
0002
0003 0001
0010
0004
0002
0010
0003
0002
0011
0012
Components
0005
Fig. 59
5697 787 GB
74
Parts lists
Control unit assembly (cont.)
Pos. Part
0001 Cover, wiring chamber
0002 Clip hinge
0003 Profiled seal
0004 Control unit VBC113-D20
0005 Cable harness X20
0006 Ignition cable
0007 Gas valve connecting cable 35
0008 Fan connecting cable 100
0009 Cable harness, stepper motor AMP-X
0010 Fuse, 2.5A (slow), 250V (10 pce)
0011 Outside temperature sensor NTC
0012 Cable harness X21
0013 Heating circuit pump connecting cable 20
Components
5697 787 GB
75
Parts lists
Miscellaneous assembly
0001
0002
0003
0004
0005
Fig. 60
Components
5697 787 GB
76
Parts lists
Miscellaneous assembly (cont.)
Pos. Part
0001 Touch-up spray paint, white, 150 ml can
0002 Touch-up paint stick, white
0003 Special grease
0004 Installation and service instructions
0005 Operating instructions
Components
5697 787 GB
77
Control unit
Functions and operating conditions in weather-compensated mode
90
eT eP wT
80
wP
70
qT
60
Boiler water temperature in °C
qP
50
5
40
30
20
20 15 10 5 0 -5 -10 -15
Outside temperature in °C
Fig. 61
1. Tap / . 3. OK to confirm.
The set parameter flashes and will be dis-
played.
78
Connection and wiring diagram
Connection and wiring diagram
D
B
E
A
F
G/H
K
Fig. 62
79
Reports
(cont.)
Signature
Gas type G
Static pressure mbar
kPa
Supply pressure (flow pres- mbar
sure)
kPa
Carbon dioxide content CO2
■ Upper heating output % by
vol.
■ Lower heating output % by
vol.
Oxygen content O2
■ Upper heating output % by
vol.
■ Lower heating output % by
vol.
Carbon monoxide content CO ppm
5697 787 GB
80
Specification
Specification
Appendix
Connection values
Relative to the max. load for:
- Natural gas H m3/h 1.88 2.6 2.96 3.46
- LPG P kg/h 1.39 1.90 2.19 2.56
Rated voltage V 230
Rated frequency Hz 50
Rated current A 2.0
Backup fuse (max.) A 16
Power consumption (max.) W 82 88 96 106
Permissible ambient temperature
- during operation °C 0 to +40
- during storage and transport °C -20 to +65
IP rating IP X4 to EN 60529 (only for room sealed operation)
Protection class I
Temperature limiter setting °C 100 (fixed)
Weight kg 35 36 37 37
Product ID CE-0063CQ3356
Type B1KC
Rated heating output range in heating
mode
TF/TR 50/30 °C kW 4.7 (6.5)*1 – 26 5.9 (8.8)*1 – 30 5.9 (8.8)*1 – 35
TF/TR 80/60 °C kW 4.3 (5.9)*1 – 23.8 5.4 (8.0)*1 – 27.5 5.4 (8.0)*1 – 32.1
Connection values
Relative to the max. load for:
- Natural gas H m3/h 2.87 3.31 3.86
- LPG P kg/h 2.12 2.45 2.85
Appendix
Note
The supply values are only for reference (e.g. in the gas contract application) or for a supplementary, rough esti-
mate to check the volumetric settings. Due to factory settings, the gas pressure must not be altered from these
values. Reference: 15 °C, 1013 mbar (101.3 kPa). 5697 787 GB
Appendix
5697 787 GB
83
Certificates
Declaration of conformity
We, Viessmann Werke GmbH & Co. KG, D-35107 Allendorf, declare as sole responsible body that the named
product complies with the provisions of the following directives and regulations:
Applied standards:
EN 15036-1: 2006
EN 15502-1: 2012 + A1: 2015
EN 15502-2-1: 2012
Service
Manufacturer's declaration
This product meets the requirements of the Efficiency Directive (92/42/EEC) for condensing boilers.
5697 787 GB
84
Keyword index
Keyword index
B I
Boiler water temperature sensor ............................... 54 Ignition........................................................................40
Burner gasket.............................................................39 Ignition electrode........................................................40
Burner gauze assembly............................................. 39 Ionisation electrode.................................................... 40
Burner installation...................................................... 42
Burner removal...........................................................39 L
Limits
C – Flue gas values....................................................... 24
CO2 content check.....................................................37 LPG............................................................................ 24
Combustion chamber cleaning...................................41
Commissioning...........................................................22 M
Condensate................................................................14 Max. heating output....................................................26
Condensate drain.................................................14, 42
Connection diagram................................................... 79 O
Connections........................................................... 9, 12 Outlet temperature sensor......................................... 56
Connections on the water side...................................12 Output adjustment
Control unit, closing....................................................20 – Shared connection.................................................. 28
Control unit, opening.................................................. 16 Output matching
Cylinder temperature sensor .....................................55 – Flue gas cascade.................................................... 34
– Flue pipe length.......................................................27
D Output reduction.........................................................26
Diaphragm expansion vessel..................................... 43 Outside temperature sensor.................................19, 53
Dimensions.................................................................. 9
P
E Plate heat exchanger................................................. 59
Electrical connections................................................ 17 Power supply..............................................................20
Pressure in the system...............................................43
F Product information...................................................... 7
Fault........................................................................... 49 Pump rate adjustment................................................ 27
Fault code.................................................................. 49
Fault display............................................................... 49 R
Filling function............................................................ 22 Report........................................................................ 80
Fill water.....................................................................22 Reset..........................................................................51
Flow limiter................................................................. 58
Flue gas cascade....................................................... 34 S
Flue gas temperature sensor..................................... 57 Safety chain .............................................................. 56
Flue pipe.................................................................... 15 Safety valve................................................................14
Front panel, mounting................................................ 44 Shared flue system connection.................................. 28
Front panel removal............................................. 12, 16 Static pressure........................................................... 25
Frost limit....................................................................78 Supply pressure......................................................... 25
Frost protection.......................................................... 78 System, filling....................................................... 22, 23
Function sequence.....................................................49 System pressure.................................................. 23, 43
Fuse........................................................................... 60
T
G Temperature limiter.................................................... 56
Gas connection.......................................................... 14 Trap...................................................................... 15, 42
Gas supply pressure.................................................. 25 Troubleshooting..........................................................52
Gas train ....................................................................25
Gas type, changing V
– LPG................................................................... 24, 47 Ventilation air pipe......................................................15
Gas type conversion Venting....................................................................... 23
– At control unit.......................................................... 47 Vitotrol 100
Gas type selected...................................................... 24 – Connection.............................................................. 19
H W
Heat exchanger cleaning........................................... 41 Wall mounting.............................................................10
Heating curve............................................................. 78 Wall mounting bracket................................................10
Water quality.............................................................. 22
5697 787 GB
Weather-compensated mode..................................... 78
85
86
5697 787 GB
5697 787 GB
87
Subject to technical modifications.
Applicability
Serial No.:
7570671 7570672 7570673 7570674
7570675 7570676 7570677