System Voltage 380 Volts

Load Current 3 Amp


Length 70 Meters
Maximum Permissible Voltage Drop 2.5 %
Conductor Copper
Cable Type Cu/XLPE/SWA/PVC
No. of cores 4
Layed In Air
Amb. Temperature 35 Deg. C.
Depth of Laying NA. CM
Thermal Resistivity of soil NA. Deg. C.-CM/W

No of circuits No of cores Suitable cable size De-rated current Voltage drop Circuit voltage drop
(No of cables per phase) (Sq. mm) of selected cable (Amp) of selected cable (V/A/km) (%)

1 4 1,50 25 26,72 1,48

2 4 1,50 24 26,72 0,74

3 4 1,50 24 26,72 0,49

6 4 1,50 23 26,72 0,25

9 4 1,50 23 26,72 0,16