Why can't we use PT bus for control supply??
Firstly,
the voltage level required for feeder control supply may not be 110V AC (which
happens to be the voltage level of the PT output).
Secondly,
even if the voltage level was same, yet, the PT is not designed to cater to the VA
burden requirement of the various components. Generally, PTs are available as
25VA, SOVA, 100VA or at max 200VA. However, VA burden requirement for a
switchboard ranges anything upwards of SOOVA, typically upto SkVA. Very rarely
we may also get to see 7.5KVA and 10KVA at max.