You are on page 1of 4

GENERAL 1 Tag Number -

Infrared point flammable gas detector type complete with transmitter and weatherproof co
2 Type

3 Mounting Surface mounting with 316 ss bracket

4 Enclosure material SS316 with Ex'e' stainless steel junction box

5 Certification Ex'd' for Zone 2, Gas Group II A, B, Temperature class T3

6 Protection IP 65 as per IEC 60529 as a minimum

7 Operating voltage 24VDC (range 18 to 32VDC)

8 Circuit type 3-wire system

9 Detection range 0-100%LEL

10 Accuracy ±1% LEL

11 Response time T60 less than 6 secs.

12 Rfi immunity 20 V/M - 55 Hz to 1 Ghz

13 Cable entry 1/2" NPTF (vendor to provide adapter, if required)

14 Display Local 3 digit LCD

15 Vibration tolerance As per MFR standard

16 Operating temp -2°C to 50°C

17 Tag plate Yes, Required. SS316

18 Total quantity 6 + 2(spare)

PURCHASE 19 Manufacturer *

20 Model *

21 Purchase order Number *

22 Price *

23 Serial Number Item Number *

Notes:
1. * - VENDOR to specify / furnish
2. One Calibration equipment for the Gas detectors shall be provided,consisting minimum of two calibration gas cylinders containing methane/air mixture at 50% LEL,Regulator with gauge and flexib
complete with quick connect fitting. Quick connector size shall be suitable for 1/4" NPT(F). Vendor shall provide sufficient fittings for installation to the 1/4" NPT valve.
3. 316 SS Mounting Bracket and accessories shall be supplied with each Gas detectors.
4. All necessary calibration equipment (e.g. Gas Cap, Flow Housing, Collecting cone, Test nozzle) one complete set to be supplied with each detector.
5. One hand held device shall be provided for detector calibration and setup.
6. JB if any required for connecting the cables to the GD shall be supplied by the GD vendor. The JB shall be suitable for the hazardous area.
7. Documents
a) Data Sheets
b) Certified dimensional drawing
c) Hazardous area classification
d) Ingress protection certificate
e) Installation, Operation and maintenance record
f) Catalogue sheets
8. All Gas detectors shall be DGMS approved.
DATASHEET FOR GAS DETECTOR

0 13.02.19 MG Issued For Engineering


Rev Date By Description Doc No. P18002-IOCL-BR-IN-DS-NGS-GD-2004

Page 367 of 1305


ctor type complete with transmitter and weatherproof cover for sensor.

cket

unction box

B, Temperature class T3

mum

apter, if required)

re at 50% LEL,Regulator with gauge and flexible hose three meters long
/4" NPT valve.
Sheet: 03 of 03
Code: Rev. 0

You might also like