Communication and data formats

4-Quadrant-/Combi meter LZQJ-XC acc. to VDEW-Specifications 2.1

Edition: 02.02.2012
LZQJXC-KoDa-E-1.20
Communication and data formats

The contents of this manual are protected by copyright. It is forbidden to translate,


reprint, copy or store the contents in electronic data processing systems without the
express permission of the EMH.

All trade marks and product names mentioned in this manual are the property of the
EMH metering GmbH & Co. KG or the respective title holder.

EMH is certified in accordance with DIN EN ISO 9001:2008 and endeavour to improve
their products continually.

The contents of this manual and the technical specifications may be supplemented,
amended or deleted without prior notice.

The description for the product specification in this manual does not constitute an
integral part of the contract.

© 2012 EMH metering GmbH & Co. KG. All rights reserved.

If you have any questions or suggestions, you can contact us at:

EMH metering
GmbH & Co. KG

Neu-Galliner Weg 1
19258 Gallin
GERMANY
Tel.: +49 38851 3260
Fax: +49 38851 3261-129
E-mail: info@emh-metering.com
Web: www.emh-metering.com

Technical Support:

Tel.: +49 38851 3261-930


E-mail: support@emh-metering.com

2 EMH metering
Communication and data formats

Contents page

1 Prologue ...................................................................................................................................................... 4
2 Readout of the tables ................................................................................................................................. 5
3 Time setting commands ............................................................................................................................. 6
3.1 Date/Time ..................................................................................................................................................... 6
3.2 Date .............................................................................................................................................................. 6
3.3 Clock time ..................................................................................................................................................... 6
4 Execute reset (cumulation) ........................................................................................................................ 8
5 Read out meter identifier (identity register) ............................................................................................. 8
6 Load profiles ............................................................................................................................................... 9
6.1 Standard load profile P.01 ............................................................................................................................ 9
6.1.1 Read standard load profile ............................................................................................................................ 9
6.1.2 Output format of the standard load profile .................................................................................................. 11
6.2 User load profile P.02 ................................................................................................................................. 12
6.2.1 Read user load profile................................................................................................................................. 12
6.2.2 Output format of the user load profile ......................................................................................................... 14
7 Operation log book P.98 .......................................................................................................................... 15
7.1 Read operation log book ............................................................................................................................. 15
7.2 Output format of the operation log book ..................................................................................................... 16
8 Status information in the load profiles and in the operation log book ................................................ 17
9 Certification relevant log book P.99 ........................................................................................................ 18
9.1 Read certification relevant log book ............................................................................................................ 18
9.2 Output format of the certification relevant logbook...................................................................................... 19
9.3 Status information in the certification relevant log book .............................................................................. 19
10 User log book P.200 ................................................................................................................................. 20
10.1 Read user log book..................................................................................................................................... 20
11 Event log book P.210 (Manipulations) .................................................................................................... 21
11.1 Read event log book P.210 ........................................................................................................................ 21
12 Event log book P.211 (Voltage monitoring) ............................................................................................ 22
12.1 Read event log book P.211 ........................................................................................................................ 22
13 Test mode ................................................................................................................................................. 22
13.1 Activate the test mode ................................................................................................................................ 22
13.2 Deactivate the test mode ............................................................................................................................ 23
13.3 Testing procedure ....................................................................................................................................... 23
14 Error flags.................................................................................................................................................. 23
15 Readout examples .................................................................................................................................... 24
15.1 Table 1 ........................................................................................................................................................ 24
15.2 Table 2 ........................................................................................................................................................ 28
15.3 Table 3 (for EMH-internal test purposes) .................................................................................................... 29
15.4 Table 4 ........................................................................................................................................................ 31
15.5 Operation log book P.98 ............................................................................................................................. 32
15.6 Certification relevant log book P.99 ............................................................................................................ 33
15.7 User log book P.200 ................................................................................................................................... 33
15.8 Event log book P.210.................................................................................................................................. 34
15.9 Event log book P.211.................................................................................................................................. 34

EMH metering 3
Communication and data formats

1 Prologue
The electronic electricity meter LZQJ-XC corresponds to IEC 62056-21 standards for meter reading transfer,
tariff- and load control, data transfer for fixed and mobile connection and the new VDEW specifications
version 2.1.
Depending on the design, this meter can be e.g. a Combi-meter for measuring imported energy (WV+, BV+)
or a 4-Quadrant meter for measuring imported and exported energy (WV+, BV+, WV-, BV-). The sequence
of the load profile channels are therefore freely configurable (e.g. P+, P-, Q+, Q- or P+, Q+, P-, Q-).

Short overview of the improvements made to the LZQJ-XC meter regarding remote reading/data records:
- Increased read out transmission speed of 9.600 Baud
- OBIS code for the meter feed rate is now 1.29, instead of 1.9 as up until now
- Load profile: Output also possible as total energy value
- Asynchronous tariff switching is possible (without any effects on the load profile)
- Standard number of digits in the energy register (can be configured) adapted to VDEW-
Specifications 2.1:
Number of digits /
Meter type
accuracy
Direct connection 8.0
230 V, 5 A 5.3
58 V, 5 A 5.3
58 V, 1 A 5.3

The new meter identifier which is used is constructed according to the following structure:
/HHHB\@[\2]XXTTTTDDDDIU

With:
- HHH: Manufacturer = EMH
- B: Baud rate proposal from the meter
- \@ : VDEW-identifier „extended Mode C“
- \2: optional: Identifier for possible access to DLMS via “Mode E” acc. to IEC 62056-21
- XX: Identifier for the load profile variant (01 = RWE/Fröschl, D1= Deutsche Bahn)
- TTTT: Type description of the hardware key (here: LZQJ)
- DDDD: Data record identifier (here: L001)
- I: Current code acc. to the type code
- U: Voltage code acc. to the type code

Example: /EMH5\@01LZQJL0014E (LZQJ-XC for 5II1A and 3 x 230/400V)

Notes: If necessary, the meter identifier can be changed subsequently via a set command. Depending on
the configuration of the meter the meter identifier may differ for each interface.

4 EMH metering
Communication and data formats

2 Readout of the tables


The meter has four data tables. For each table, the sequence of the data to be represented can be
individually defined.

Table 1: <ACK>0Z0<CR><LF>
Table 2: <ACK>0Z2<CR><LF> or <ACK>0Z8<CR><LF>
Table 3: <ACK>0Z3<CR><LF> or <ACK>0Z6<CR><LF
Table 4: <ACK>0Z7<CR><LF

Note: The communication procedure takes place acc. to IEC 62056-21.

The following short commands are also possible:

/0!<CR><LF> Readout of data table 3


/1!<CR><LF> Readout of data table 1
/2!<CR><LF> Readout of data table 4

With a compulsory address recognition, the following short commands are


Possible (the leading zeros can be omitted):

/0<Adress 8 digits>!<CR><LF> Readout of data table 3


/1<Adress 8 digits >!<CR><LF> Readout of data table 1
/2<Adress 8 digits >!<CR><LF> Readout of data table 2
/3<Adress 8 digits >!<CR><LF> Readout of data table 3
/4<Adress 8 digits >!<CR><LF> Readout of data table 4

EMH metering 5
Communication and data formats

3 Time setting commands


When setting the date and the time, the subsequent listed C003 command should be used.

3.1 Date/Time
Meaning: Reading / Setting the clock time and date

Syntax: R2: C003(YYMMDDhhmmsswwnz)


W2: C003(YYMMDDhhmmss000z)

Parameter: YY: Year (00 to 99 for 2000 to 2099)


MM: Month (01 to 12)
DD: Day (01 to 31)
hh: Hour (00 to 23)
mm: Minute (00 to 59)
ss: Second (00 to 59)
ww: week number 01..53
n: weekday : 1..7, 1=Monday.
z: season identification of the date (0=normal time, 1=summer time, 2=UTC)

Alternatively the date and time can be set individually.


Note: Setting the time via a single command can lead to time shifts if this happens near a day change
(00:00:00 o’clock) or season change (02:00:00 o’clock – winter time to summer time – on the last Sunday in
March resp. 03:00:00 o’clock – summer time to winter time – on the last Sunday in October).

3.2 Date
Meaning: Reading / Setting the current date

Syntax: R5: 0.9.2(zYYMMDD)


W5: 0.9.2(zYYMMDD) or 0.9.2(YYMMDD)

Parameter: z: Season recognition (0=Normal time, 1=Summer time, 2=UTC)

3.3 Clock time


Meaning: Reading / Setting the current clock time

Syntax: R5: 0.9.1(zhhmmss)


W5: 0.9.1(zhhmmss) or 0.9.1(hhmmss)

Parameter: z: Season recognition (0=Normal time, 1=Summer time, 2=UTC)

Note: Since the W5-command in the VDEW-meter is fundamentally password protected a W5 password
must be sent (Compare with VDEW-Specifications 2.1.2 from 07.11.2003 - Table 10.8 „Register for OBIS-
formatted reading and writing“).

Note: The standard password set in then meter is 00000000.

6 EMH metering
Communication and data formats

Example 1:
Set clock time to 10:23:50:

<SOH>W5<STX>0.9.1(0102350)(00000000)<ETX><BCC>

Communication process:
sent: /?!<CR><LF>
received: /EMH5\@01LZQJL0014E <CR><LF>
sent: <ACK>051<CR><LF>
received: <SOH>P0<STX>()<ETX><BCC>
sent: <SOH>W5<STX>0.9.1(0102350)(00000000)<ETX><BCC>
received: <ACK>
sent: <SOH>B0<ETX><BCC>

Example 2:
Set date to 17.06.03:

<SOH>W5<STX>0.9.2(1030617)(00000000)<ETX><BCC>

Communication process:
sent: /?!<CR><LF>
received: /EMH5\@01LZQJC0014E <CR><LF>
sent: <ACK>051<CR><LF>
received: <SOH>P0<STX>()<ETX><BCC>
sent: <SOH>W5<STX>0.9.2(1030617)(00000000)<ETX><BCC>
received: <ACK>
sent: <SOH>B0<ETX><BCC>

Example 3:
Read the date of February 1, 2012:

<SOH>R5<STX>0.9.2()<ETX><BCC>

Communication process:
sent: /?!<CR><LF>
received: /EMH5\@01LZQJL0014E <CR><LF>
sent: <ACK>051<CR><LF>
received: <SOH>P0<STX>()<ETX><BCC>
sent: <SOH>R5<STX>0.9.2()<ETX><BCC>
received: <STX>0.9.2(0120201)<ETX><LF>
sent: <SOH>B0<ETX><BCC>

EMH metering 7
Communication and data formats

4 Execute reset (cumulation)


Syntax: E2: 0001()
Meaning: Execution of a reset (cumulation)
Example: 0001()

5 Read out meter identifier (identity register)


Syntax: R5: 0.0.#(...)
Meaning: Reading out meter identifier
Parameter: 0..32 digit Text-String
Values from #:016 ... 916
Comments: The register 0.0.0 contains the meter address.
Example: 0.0.4(EMH-1234)

8 EMH metering
Communication and data formats

6 Load profiles
6.1 Standard load profile P.01
6.1.1 Read standard load profile
Syntax: R5: P.01([[z]YYMMDDhhmm];[[z]YYMMDDhhmm])[([[Ai-]Bi:]C1[.D1])]... [([[Ai-]Bi:]Cn[.Dn])]
(Reading the user load profile without partial blocks acc. to IEC 62056-21)
or
R6 : P.01([[z]YYMMDDhhmm];[[z]YYMMDDhhmm];b)[([[Ai-]Bi:]C1[.D1])]... [([[Ai-]Bi:]Cn[.Dn])]
(Reading of the user load profile in partial blocks acc. to IEC 62056-21)
Meaning: Reading of the user load profile
Parameter: [z]YYMMDDhhmm: Information on the start-time of the readout time period (optional)
[z]YYMMDDhhmm: Information on the end-time of the readout time period (optional)
z: Format of the data information (optional)
(0=normal time / 1=summer time / 2=UTC)
If this data is missing, depending on the meter setting, season z=2 or,
depending on the season, z=0 or 1 is assumed.

YY: Year (00 to 99 for 2000 to 2099)


MM: Month (01 to 12)
DD: Day (01 to 31)
hh: Hour (00 to 23)
mm: Minute (00 to 59)

Ci[.Di] Load profile-channel number, optional)


Ai: Medium acc. to OBIS (optional)
Bi: Channel number acc. to OBIS (optional)
Ci : Measured variable acc. to OBIS
Di: Measuring type acc. to OBIS (optional)

b Block length

Note: If neither the start- or the stop time of the read out period should be given then, as an option, with the
R5 command the semicolon in the brackets is omitted. The syntax can then also be the following: R5:
P.01()[...] or R5: P.01(;)[...]
However, with an R6 command the syntax without information about the start- and stop time of the read out
period must be: R6: P.01(;;b)[...]
For the (optional) specific readout of one or several load profile channels the OBIS code of the channel(s)
must be specified. Here information on the measuring variable C is obligatory and the measuring type D
optional. As a result of this, all load profile channels from one and the same measured variable can be read
out. Of course only the available channels can be read out directly.

The maximum length of a header in the load profile is unlimited. The maximum width of a read command is
250 characters. According to IEC 62056-21 the maximum length of a row should merely be 78 characters.

Since the LZQJ-XC can also have pulse inputs then, as an optional load profile channel number, the
complete OBIS code system with all value groups (incl. „medium channels:“ e.g. 1-1:1.5) can be specified.

EMH metering 9
Communication and data formats

Examples:

R5: P.01(;)
The total load profile is read out.

R5: P.01(00401021200;10405191000)
The standard load profile entries from 2. January 2004, 12:00 (normal time) to 19.May 2004, 10:00 o’clock
(local summer time) are read out without partial blocks.

R6: P.01(;;10)
The total standard load profile in partial blocks is read out, each block contains ten rows.

R6: P.01(00401021700;00402011200;10)(1)(2)(3.5)
The load profile entries of the following load profile channels from 2. January 2004, 17:00 o’clock (normal
time) to 1. February 2004, 12:00 o’clock are read out in partial blocks, each block contains 10 rows.
- All channels to the measured variable1 (positive active energy), which are defined accordingly.
- All channels to the measured variable 2 (negative active energy), which are defined accordingly.

- The load profile channel of the measured type 5 (last average value) and the measured variable 3
(positive reactive energy).

10 EMH metering
Communication and data formats

6.1.2 Output format of the standard load profile


The output format of the standard load profiles is as follows:
1. Entries with header:
P.01([z]YYMMDDhhmmss)(SSSSSSSS)(r)(k)(K1)(E1)..[(Kk)(Ek)](x...x)...[(y...y)]

2. Entries without header:


(x...x)...[(y...y)]

The values mean:


z: Season-codes: 0 = normal time, 1 = summer time, 2 = UTC
Note: Depending on the settings in the meter, the output of this value can be controlled. It
is then accepted as z=2 or depending on the season z=0 or 1.
YYMMDDhhmmss:Time stamp of the load profile entry. In the case of a clock adjustment this is the time
before the adjustment.
SSSSSSSS: Status in the form of a 32-Bit length ASCII-HEX-number.
The high quality nibble (Bits 31..28) is on the left, the low quality nibble (Bits 3..0) is on
the right. The meaning of the bits is clear from the following table.
r: Register period in minutes
k: Number of load profile channels which should be given out after this header.
th
Kn: Identification of the n- value (OBIS code) in the entry which follows this header.
th
En: Unit of the n- value in the entry which follows this header.

x...x, y...y: Load profile entries, identifiers (OBIS code) and units according to the last header given
out.

Note: If the LZQJ-XC forms load profile channels from the registered pulses then, as the identifier Kn, the
complete OBIS code system with all value groups (incl. „Medium-channel:“ e.g. 1-2:1.5) is given out.

Examples:
Standard-data output:
P.01(040211001500)(00000000)(15)(4)(1.5)(kW)(2.5)(kW)(3.5)(kvar)(4.5)(kvar)
(5.797)(0.000)(0.000)(2.205)
(5.791)(0.000)(0.000)(2.168)
(5.795)(0.000)(0.000)(2.192)
(5.804)(0.000)(0.000)(2.226)
(6.060)(0.000)(0.000)(1.815)

Output in complete OBIS code system (optional):


P.01(040211001500)(00000000)(15)(2)(1-1:1.5)(kW)(1-2:3.5)(kvar)
(5.797)(0.212)
(5.791)(0.198)
(5.795)(0.195)
(5.804)(0.216)
(6.060)(0.272)

EMH metering 11
Communication and data formats

6.2 User load profile P.02


6.2.1 Read user load profile
Syntax: R5: P.02([[z]YYMMDDhhmm];[[z]YYMMDDhhmm])[([[Ai-]Bi:]C1[.D1])]... [([[Ai-]Bi:]Cn[.Dn])]
(Reading the user load profile without partial blocks acc. to IEC 62056-21)
or
R6 : P.02([[z]YYMMDDhhmm];[[z]YYMMDDhhmm];b)[([[Ai-]Bi:]C1[.D1])]... [([[Ai-]Bi:]Cn[.Dn])]
(Reading of the user load profile in partial blocks acc. to IEC 62056-21)
Meaning: Reading of the user load profile
Parameter: [z]YYMMDDhhmm: Information on the start- time of the readout time period (optional)
[z]YYMMDDhhmm: Information on the end- time of the readout time period (optional)
z: Format of the data information (optional)
(0=normal time / 1=summer time / 2=UTC)
If this data is missing, depending on the meter setting, season z=2 or,
depending on the season, z=0 or 1 is assumed.

YY: Year (00 to 99 for 2000 to 2099)


MM: Month (01 to 12)
DD: Day (01 to 31)
hh: Hour (00 to 23)
mm: Minute (00 to 59)

Ci[.Di] Load profile-channel number, optional)


Ai: Medium acc. to OBIS (optional)
Bi: Channel number acc. to OBIS (optional)
Ci: Measured variable acc. to OBIS
Di: Measuring type acc. to OBIS (optional)

b Block length

Note: If neither the start nor the stop time of the read out period should be given then, as an option with the
R5 command the semicolon in the brackets is left out. The syntax can then also be the following: R5:
P.02()[...] or R5: P.02(;)[...].
However, with an R6 command the syntax without information about the start and stop time of the read out
period must be: R6: P.02(;;b)[...].
For the (optional) specific readout of one or several load profile channels the OBIS code of the channel(s)
must be specified. Here information on the measuring variable C is obligatory and the measuring type D
optional. As a result of this, all load profile channels from one and the same measured variable can be read
out. Of course only the available channels can be read out directly.

The maximum length of a header in the load profile is unlimited. The maximum width of a read command is
250 characters. According to IEC 62056-21 the maximum length of a row should merely be 78 characters.

Since the LZQJ-XC can also have pulse inputs then, as an optional load profile channel number, the
complete OBIS code system with all value groups (incl. „medium channels:“ e.g. 1-1:1.5) can be specified.

12 EMH metering
Communication and data formats

Examples:

R5: P.02(;)
The total user load profile is read out.

R5: P.02(00401021200;10405191000)
The user load profile entries from 2. January 2004, 12:00 (normal time) to 19.May 2004, 10:00 o’clock (local
summer time) are read out without partial blocks.

R6: P.01(;;10)
The total user load profile in partial blocks is read out, each block contains ten rows.

R6: P.01(00401021700;00402011200;10)(1)(2)(3.5)
The load profile entries of the following load profile channels from 2. January 2004, 17:00 o’clock (normal
time) to 1. February 2004, 12:00 o’clock are read out in partial blocks, each block contains 10 rows.
- All channels to the measured variable1 (positive active energy), which are defined accordingly.
- All channels to the measured variable 2 (negative active energy), which are defined accordingly.

- The load profile channel of the measured type 5 (last average value) and the measured variable 3
(positive reactive energy).

EMH metering 13
Communication and data formats

6.2.2 Output format of the user load profile


The output format of the user load profiles is as follows:
1. Entries with header:
P.02([z]YYMMDDhhmmss)(SSSSSSSS)(r)(k)(K1)(E1)..[(Kk)(Ek)](x...x)...[(y...y)]

2. Entries without header:


(x...x)...[(y...y)]

The values mean:


z: Season-codes: 0 = normal time, 1 = summer time, 2 = UTC
Note: Depending on the settings in the meter, the output of this value can be controlled. It
is then accepted as z=2, or, depending on the season z=0 or 1.
YYMMDDhhmmss: Time stamp of the load profile entry. In the case of a clock
adjustment this is the time before the adjustment.
SSSSSSSS: Status in the form of a 32-Bit length ASCII-HEX-number.
The high quality nibble (Bits 31..28) is on the left, the low quality nibble (Bits 3..0) is on
the right. The meaning of the bits is clear from the following table.
r: Registration period in minutes
k: Number of load profile channels which should be given out after this header.
th
Kn: Identification of the n- value (OBIS code) in the entry which follows this header.
th
En: Unit of the n- value in the entry which follows this header.

x...x, y...y: Load profile entries, identifiers (OBIS code) and units according to the last header given
out.

Note: If the LZQJ-XC forms load profile channels from the registered pulses then, as the identifier Kn, the
complete OBIS code system with all value groups (incl. „Medium-channel:“ e.g. 1-2:1.5) is given out.

Examples:
Standard-data output:
P.02(040211001500)(00000000)(15)(4)(1.5)(kW)(2.5)(kW)(3.5)(kvar)(4.5)(kvar)
(5.797)(0.000)(0.000)(2.205)
(5.791)(0.000)(0.000)(2.168)
(5.795)(0.000)(0.000)(2.192)
(5.804)(0.000)(0.000)(2.226)
(6.060)(0.000)(0.000)(1.815)

Output in complete OBIS code system (optional):


P.02(040211001500)(00000000)(15)(2)(1-1:1.5)(kW)(1-2:3.5)(kvar)
(5.797)(0.212)
(5.791)(0.198)
(5.795)(0.195)
(5.804)(0.216)
(6.060)(0.272)

Output network analysis:


P.02(1070902001000)(00000000)(10)(25)(32.5)(V)(52.5)(V)(72.5)(V)(32.23)(V)(52.23)(V)(72.2
3)(V)(32.26)(V)(52.26)(V)(72.26)(V)(31.5)(A)(51.5)(A)(71.5)(A)(31.26)(A)(51.26)(A)(71.26)
(A)(140.5)(%)(141.5)(%)(142.5)(%)(143.5)(%)(144.5)(%)(145.5)(%)(146.5)()(147.5)()(148.5)(
)(14.5)(Hz)

14 EMH metering
Communication and data formats

7 Operation log book P.98


7.1 Read operation log book
Syntax: R5: P.98([[z]YYMMDDhhmm];[[z]YYMMDDhhmm])
(Reading of the operation log book without partial blocks acc. to IEC 62056-21)
or
R6 : P.98([[z]YYMMDDhhmm];[[z]YYMMDDhhmm];b)
(Reading of the operation log book in partial blocks acc. to IEC 62056-21)
Meaning: Reading of the log book

Parameter: [z]YYMMDDhhmm: Information on the start- time of the readout time period (optional)
[z]YYMMDDhhmm: Information on the end- time of the readout time period (optional)
z: Format of the data information (optional)
(0=normal time / 1=summer time / 2=UTC)
If this data is missing, depending on the meter setting, season z=2
or, depending on the season, z=0 or 1 is assumed.

YY: Year (00 to 99 for 2000 to 2099)


MM: Month (01 to 12)
DD: Day (01 to 31)
hh: Hour (00 to 23)
mm: Minute (00 to 59)

b Block length

Note: If neither the start or the stop time of the read out period should be given then, as an option with the
R5 command the semicolon in the brackets is left out. The syntax can then also be the following: R5: P.98()
or R5: P.98(;).
However, with a R6-command, the syntax without information about start and stop time of the read out
period must be as follows: R6: P.98(;;b).

Examples:
R5: P.98()
The total operation log book is read out.

R5: P.98(10407021200;00411191000)
The operation log book from 2. July 2004, 12:00 o’clock (local summer time) to 19. November 2004, 10:00
o’clock (normal time) without partial blocks is read out.

R6: P.98(;;10)
The total operation log book is read out in partial blocks, each block contains ten rows.

EMH metering 15
Communication and data formats

7.2 Output format of the operation log book


The output format of the operation log book is as follows:

P.98([z]YYMMDDhhmmss)(SSSSSSSS)()(k)[(<Kenn1>)()..[(identk>)()]][(<value1>)..[(<valuek>)]]<CR><LF>
...

P.98([z]YYMMDDhhmmss)(SSSSSSSS)()(k)[(<Kenn1>)()..[( identk>)()]][(<value1>)..[(<valuek>)]]<CR><LF>

Meaning of the values: :


z: Season-codes: 0 = normal time, 1 = summer time, 2 = UTC
Note: Depending on the setting of the meter the output of this value can be controlled. It
is then accepted as z=2 or depending on the season z=0 or 1.
YYMMDDhhmmss: Time stamp of the log book entry. In the case of a time adjustment this
time stamp gives the time before the adjustment.
SSSSSSSS: Status in form of a 32-Bit length ASCII-HEX-number.
The high quality nibble (Bits 31..28) is on the left, the low quality nibble (Bits 3..0) on the
right. The meaning of the bits is clear from the following table.
k: Number of values which will follow. If it is k=0, then the information about identn and
valuen is left out.
identn: Recognition of the value (OBIS code). In case of a time adjustment, these values
correspond to the values after the adjustment.
valuen: value

16 EMH metering
Communication and data formats

8 Status information in the load profiles and in the operation log book
Bit Event Meaning in the log book this
or leads to the output of
Condition
b16 to b31 - Reserved for future extensions (always 0) -
b15 Condition The status word was logged before execution of the last Time and date
setting of the time setting. (OBIS: 0.9.1 and
0.9.2)
b14 Event Load profile memory was completely deleted -
b13 Event Log book was completely deleted -
b12 - Reserved for future extensions (always 0) -
b11 Condition There is at least one illegal external activation -
b10 - Reserved for future extensions (always 0) -
b9 Condition There is at least one illegal operating condition -
b8 Event A variable was changed by setting -
b7 Event Voltage failure (3-phase) recognized -
b6 Event Voltage return (1-phase) recognized after 3 phase
-
voltage failure
b5 Event Meter clock was set Time and date
(OBIS: 0.9.1 and
0.9.2)
b4 Event Reset / Cumulation was carried out -
b3 Event Season change has taken place (summer time after Time and date
winter time or vice versa) (OBIS: 0.9.1 and
0.9.2)
b2 Condition Measured value interfered -
b1 Condition Running reserve of the meter clock is exhausted -
b0 (LSB) Condition There is a critical meter error (certification relevant error) Error code
(OBIS: F.F)

EMH metering 17
Communication and data formats

9 Certification relevant log book P.99


9.1 Read certification relevant log book
Syntax: R5: P.99([[z]YYMMDDhhmm];[[z]YYMMDDhhmm])
(Reading of the operation log book without partial blocks acc. to IEC 62056-21)
or
R6 : P.99([[z]YYMMDDhhmm];[[z]YYMMDDhhmm];b)
(Reading of the operation log book in partial blocks acc. to IEC 62056-21)

Meaning: Reading of the log book

Parameter: [z]YYMMDDhhmm: Information on the start- time of the readout time period (optional)
[z]YYMMDDhhmm: Information on the end- time of the readout time period (optional)
z: Format of the data information (optional)
(0=normal time / 1=summer time / 2=UTC)
If this data is missing, depending on the meter setting, season z=2
or, depending on the season, z=0 or 1 is assumed.

YY: Year (00 to 99 for 2000 to 2099)


MM: Month (01 to 12)
DD: Day (01 to 31)
hh: Hour (00 to 23)
mm: Minute (00 to 59)

b: Block length

Note: If neither the start- or the stop time of the read out period should be given then, as an option, with the
R5 command the semicolon in the brackets can be omitted. The syntax can be as follows: R5: P.99() or R5:
P.99(;).
However, with the R6-command, the syntax without information about the start- and stop time of the readout
period must be: R6: P.99(;;b).

Examples:
R5: P.99()
The total certification relevant log book is read out.

R5: P.99(10407021200;00411191000)
The log book from 2. July 2004, 12:00 o’clock (local summer time) to 19. November 2004, 10:00 o’clock
(normal time) without partial blocks is read out.

R6: P.99(;;10)
The total certification relevant log book in partial blocks is read out, each block contains 10 rows.

18 EMH metering
Communication and data formats

9.2 Output format of the certification relevant logbook


The output format of the certification relevant log book is as follows:
1. Entry without value
P.99([z]YYMMDDhhmmss)(SSSSSSSS)()(0)(< identifier>)<CR><LF>

2. Entry with values


P.99([z]YYMMDDhhmmss)(SSSSSSSS)()(1)(< identifier >)(unit)(<old value>;<new value>)<CR><LF>

The values mean:


z: Season-identification: 0 = normal time 1 = summer time, 2 = UTC
Note: Depending on the setting of the meter the output of this value can be controlled. It
is then accepted as z=2 or, depending on the season, z=0 or 1.
YYMMDDhhmmss:Time stamp of the log book entry. In case of a clock adjustment, this time stamp gives the
time before the adjustment.
SSSSSSSS: Status in form of a 32-Bit length ASCII-HEX-number.
The high quality nibble (Bits 31..28) is on the left, the low quality nibble (Bits 3..0) on the
right. The meaning of the bits is clear from the following table.
1: Number of the changed parameters
Recognition: Recognition of the changed values (OBIS code)
Old value: Value before change
New value: Value after change

Example: P.99(0031211153311)(00000008)()(1)(0.3.3)(Imp./kWh)(5000;3000)<CR><LF>
The P-pulse constants were changed from 5000 to 3000 Imp./kWh.

9.3 Status information in the certification relevant log book


Bit Event or Meaning In the log book leads to
condition the output of
b14 to b31 --- Reserved for future extensions (always 0) -
b13 Event Operation log book was completely deleted (00002000)()(0)
b12 to b5 --- Reserved for future extensions (always 0) -
b4 Event Q- pulse constants changed (00000010)()(1)
(0.3.4)(Imp./kvarh)
(<old value>;<new value>)
b3 Event P-pulse constants changed (00000008)()(1)
(0.3.3)(Imp./kWh)
(<old value>;< new value>)
b2 --- Reserved for future extensions (always 0) -
b1 --- Reserved for future extensions (always 0) -
b0 (LSB) Event LED-pulse constants changed (00000001)()(1)
(0.3.0)(Imp./kWh)
(<old value>;< new value>)

EMH metering 19
Communication and data formats

10 User log book P.200


10.1 Read user log book
The output format of the user log book is as follows:
P.200([z]YYMMDDhhmmss)(SSSSSSSS)()(0)<CR><LF>
...
P.200([z]YYMMDDhhmmss)(SSSSSSSS)()(0)<CR><LF>

The values mean:


z: Season-identification: 0 = normal time 1 = summer time, 2 = UTC
Note: Depending on the setting of the meter the output of this value can be controlled. It
is then accepted as z=2 or depending on the season z=0 or 1.
YYMMDDhhmmss:Time stamp of the log book entry
SSSSSSSS: Status in form of a 32-Bit length ASCII-HEX-number.
The high quality nibble (Bits 31..28) is on the left, the low quality nibble (Bits 3..0) on the
right. The meaning of the bits is clear from the following table.
Parameter: Bit15 Voltage unbalance
Bit14 Current unbalance
Bit13 Reserved (log book deleted)
Bit12 Current interruption phase 3
Bit11 Current interruption phase 2
Bit10 Current interruption phase 1
Bit09 Unauthorized write attempt
Bit08 Unauthorized read attempt
Bit07 Tariff information T4
Bit06 Tariff information T3
Bit05 Negative rotating field
Bit04 Manipulation of the meter cover
Bit03 Manipulation of the terminal cover
Bit02 Phase failure 3
Bit01 Phase failure 2
Bit00 Phase failure 1

20 EMH metering
Communication and data formats

11 Event log book P.210 (Manipulations)


11.1 Read event log book P.210
The output format of the event log book P.200 is as follows:
P.210([z]YYMMDDhhmmss)(SSSS)()(0)<CR><LF>
...
P.210([z]YYMMDDhhmmss)(SSSS)()(0)<CR><LF>

The values mean:


z: Season-identifier: 0 = normal time 1 = summer time, 2 = UTC
Note: Depending on the setting of the meter the output of this value can be suppressed.
Then it is understood that z=2 or depending on the season z=0 or 1.
YYMMDDhhmmss: Time stamp of the log book entry

SSSS: Event code in form of a 16-Bit length ASCII-HEX-number. The following events are
definied:
2000 Log book deleted
23AC Begin of manipulation terminal cover
33AC End of manipulation terminal cover
239B Terminal cover contact has been opened
339B Terminal cover contact has been closed

23AD Begin of manipulation housing cover


33AD End of manipulation housing cover
239A Housing cover contact has been opened
339A Housing cover contact has been closed

23A8 Begin of manipulation magnetic field


33A8 End of manipulation magnetic field
239C Magnetic field sensor has been activated
339C Magnetic field sensor in neutral position again

2307 PAR-status activated


3307 PAR-status deactivated

EMH metering 21
Communication and data formats

12 Event log book P.211 (Voltage monitoring)


12.1 Read event log book P.211
The output format of the event log book P.211 is as follows:
P.211([z]YYMMDDhhmmss)(SSSS)()(n) (<K>)()(<V>)<CR><LF>
...
P.211([z]YYMMDDhhmmss)(SSSS)()(n) (<K>)()(<V>)<CR><LF>

The values mean:


z: Season-identifier: 0 = normal time 1 = summer time, 2 = UTC
Note: Depending on the setting of the meter the output of this value can be suppressed.
Then it is understood that z=2 or depending on the season z=0 or 1.
YYMMDDhhmmss: Time stamp of the log book entry

SSSS: Event code in form of a 16-Bit length ASCII-HEX-number. The following events are
definied:
2000 Log book deleted
23A6 Event in the voltage quality register C.86.1
234C Failure U L1 (3 s debounced)
334C Return U L1
234D Failure U L2 (3 s debounced)
334D Return U L2
234E Failure U L3 (3 s debounced)
334E Return U L3

n: Number of values, that follow. For n=0 output of K and V is omitted


K: Identifier of value (OBIS-code).
V: Value

13 Test mode
13.1 Activate the test mode
Command type: W5

Syntax: <SOH>W5<STX>#.58.T()<ETX><BCC>
# - Activiation of the test variable via corresponding OBIS-code
1 = P+
2 = P-
3 = Q+
4 = Q-
T – Activiation of the tariff
0 - acc. to configuration
1...8 - Activation of one tariff 1...8 (energy and maximum)
F - Activation of all maxima (energy: activation acc. to configuration)

Example: 1.58.1() Activation of the test mode for P+ Tariff1 (energy and maximum)

22 EMH metering
Communication and data formats

13.2 Deactivate the test mode


Command type: W5

Syntax: <SOH>W5<STX>#.58.T(0)<ETX><BCC>

13.3 Testing procedure


Test station to test device: <SOH>W5<STX>#.58.T()<ETX><BCC>

The testing of the measured variable # with the optional activation of tariff T is started. In the display the high resolution
momentary value of the measured variable is displayed.
The LED now emits proportional pulses for the stated measured variable (P resp. Q).

A press on the call-up button now causes a jump into the test list and the first register of the test list will be displayed.
Any further activation of the call-up button displays the next register of the test list. The LED follows the currently
displayed measured variable.
If the test list contains measured variables differing from P and Q, pulses proportional to P will be generated.

The test mode is ended by <SOH>W5<STX>#.58.T(0)<ETX><BCC> or a long press on the call-up button. This will leave
the test list and show the operation display.

14 Error flags
The meter has 32 error flags.
Meaning: Reading of error flags
Syntax: F.F()
Application: R5: F.F()  Reading of the error flags

If something different to „F.F(00000000)“ is given out with the output of the error flags then, it is due to an
internal meter error!

EMH metering 23
Communication and data formats

15 Readout examples
15.1 Table 1
/EMH5\@\201LZQJL0013F
□C.1.0(00418895) Manufacturing number
0.0.1() Identity number 1
0.0.2() Identity number 2
0.0.3() Identity number 3
0.1.0(00) Reset counter
0.1.2*00(0000000000000) 00.Pre-value Reset time
0.1.2*99(0000000000000) 99.Pre-value Reset time
...
0.1.2*87(0000000000000) 87.Pre-value Reset time
0.1.2*86(0000000000000) 86.Pre-value Reset time
0.9.1(1092641) Clock time
0.9.2(1050628) Date
1-1:1.2.0(0000.00*kW) Channel 1: Cumulative Active power Import Max.-Tariff 0
1-1:1.2.1(0000.00*kW) Channel 1: Cumulative Active power Import Max.-Tariff 1
1-1:1.2.2(0000.00*kW) Channel 1: Cumulative Active power Import Max.-Tariff 2
1-1:1.2.3(0000.00*kW) Channel 1: Cumulative Active power Import Max.-Tariff 3
1-1:1.6.0(00.00*kW)(0000000000000) Channel 1: Maximum Active power Import Max.-Tariff 0
1-1:1.6.0*00(00.00*kW)(0000000000000) Channel 1: 00.Pre-value Maximum Active power Import Max.-Tariff 0
1-1:1.6.0*99(00.00*kW)(0000000000000) Channel 1: 99.Pre-value Maximum Active power Import Max.-Tariff 0
...
1-1:1.6.0*87(00.00*kW)(0000000000000) Channel 1: 87.Pre-value Maximum Active power Import Max.-Tariff 0
1-1:1.6.0*86(00.00*kW)(0000000000000) Channel 1: 86.Pre-value Maximum Active power Import Max.-Tariff 0
1-1:1.6.1(00.00*kW)(0000000000000) Channel 1: Maximum Active power Import Max.-Tariff 1
1-1:1.6.1*00(00.00*kW)(0000000000000) Channel 1: 00.Pre-value Maximum Active power Import Max.-Tariff 1
1-1:1.6.1*99(00.00*kW)(0000000000000) Channel 1: 99.Pre-value Maximum Active power Import Max.-Tariff 1
...
1-1:1.6.1*87(00.00*kW)(0000000000000) Channel 1: 87.Pre-value Maximum Active power Import Max.-Tariff 1
1-1:1.6.1*86(00.00*kW)(0000000000000) Channel 1: 86.Pre-value Maximum Active power Import Max.-Tariff 1
1-1:1.6.2(00.00*kW)(0000000000000) Channel 1: Maximum Active power Import Max.-Tariff 2
1-1:1.6.2*00(00.00*kW)(0000000000000) Channel 1: 00.Pre-value Maximum Active power Import Max.-Tariff 2
1-1:1.6.2*99(00.00*kW)(0000000000000) Channel 1: 99.Pre-value Maximum Active power Import Max.-Tariff 2
...
1-1:1.6.2*87(00.00*kW)(0000000000000) Channel 1: 87.Pre-value Maximum Active power Import Max.-Tariff 2
1-1:1.6.2*86(00.00*kW)(0000000000000) Channel 1: 86.Pre-value Maximum Active power Import Max.-Tariff 2
1-1:1.6.3(00.00*kW)(0000000000000) Channel 1: Maximum Active power Import Max.-Tariff 3
1-1:1.6.3*00(00.00*kW)(0000000000000) Channel 1: 00.Pre-value Maximum Active power Import Max.-Tariff 3
1-1:1.6.3*99(00.00*kW)(0000000000000) Channel 1: 99.Pre-value Maximum Active power Import Max.-Tariff 3
...
1-1:1.6.3*87(00.00*kW)(0000000000000) Channel 1: 87.Pre-value Maximum Active power Import Max.-Tariff 3
1-1:1.6.3*86(00.00*kW)(0000000000000) Channel 1: 86.Pre-value Maximum Active power Import Max.-Tariff 3
1-1:1.8.0(0000000*kWh) Channel 1: Energy Active power Import Energy tariff 0
1-1:1.8.0*00(0000000*kWh) Channel 1: 00.Pre-value Energy Active power Import Energy tariff 0
1-1:1.8.0*99(0000000*kWh) Channel 1: 99.Pre-value Energy Active power Import Energy tariff 0
...
1-1:1.8.0*87(0000000*kWh) Channel 1: 87.Pre-value Energy Active power Import Energy tariff 0
1-1:1.8.0*86(0000000*kWh) Channel 1: 86.Pre-value Energy Active power Import Energy tariff 0
1-1:1.8.1(0000000*kWh) Channel 1: Energy Active power Import Energy tariff 1
1-1:1.8.1*00(0000000*kWh) Channel 1: 00.Pre-value Energy Active power Import Energy tariff 1
1-1:1.8.1*99(0000000*kWh) Channel 1: 99.Pre-value Energy Active power Import Energy tariff 1
...
1-1:1.8.1*87(0000000*kWh) Channel 1: 87.Pre-value Energy Active power Import Energy tariff 1
1-1:1.8.1*86(0000000*kWh) Channel 1: 86.Pre-value Energy Active power Import Energy tariff 1
1-1:1.8.2(0000000*kWh) Channel 1: Energy Active power Import Energy tariff 2
1-1:1.8.2*00(0000000*kWh) Channel 1: 00.Pre-value Energy Active power Import Energy tariff 2
1-1:1.8.2*99(0000000*kWh) Channel 1: 99.Pre-value Energy Active power Import Energy tariff 2
...
1-1:1.8.2*87(0000000*kWh) Channel 1: 87.Pre-value Energy Active power Import Energy tariff 2
1-1:1.8.2*86(0000000*kWh) Channel 1: 86.Pre-value Energy Active power Import Energy tariff 2
1-1:1.8.3(0000000*kWh) Channel 1: Energy Active power Import Energy tariff 3
1-1:1.8.3*00(0000000*kWh) Channel 1: 00.Pre-value Energy Active power Import Energy tariff 3
1-1:1.8.3*99(0000000*kWh) Channel 1: 99.Pre-value Energy Active power Import Energy tariff 3
...
1-1:1.8.3*87(0000000*kWh) Channel 1: 87.Pre-value Energy Active power Import Energy tariff 3
1-1:1.8.3*86(0000000*kWh) Channel 1: 86.Pre-value Energy Active power Import Energy tariff 3
1-1:2.2.0(0000.00*kW) Channel 1: Cumulative Active power Export Max.-Tariff 0
1-1:2.2.1(0000.00*kW) Channel 1: Cumulative Active power Export Max.-Tariff 1
1-1:2.2.2(0000.00*kW) Channel 1: Cumulative Active power Export Max.-Tariff 2
1-1:2.2.3(0000.00*kW) Channel 1: Cumulative Active power Export Max.-Tariff 3
1-1:2.6.0(00.00*kW)(0000000000000) Channel 1: Maximum Active power Export Max.-Tariff 0
1-1:2.6.0*00(00.00*kW)(0000000000000) Channel 1: 00.Pre-value Maximum Active power Export Max.-Tariff 0
1-1:2.6.0*99(00.00*kW)(0000000000000) Channel 1: 99.Pre-value Maximum Active power Export Max.-Tariff 0
...

24 EMH metering
Communication and data formats
1-1:2.6.0*87(00.00*kW)(0000000000000) Channel 1: 87.Pre-value Maximum Active power Export Max.-Tariff 0
1-1:2.6.0*86(00.00*kW)(0000000000000) Channel 1: 86.Pre-value Maximum Active power Export Max.-Tariff 0
1-1:2.6.1(00.00*kW)(0000000000000) Channel 1: Maximum Active power Export Max.-Tariff 1
1-1:2.6.1*00(00.00*kW)(0000000000000) Channel 1: 00.Pre-value Maximum Active power Export Max.-Tariff 1
1-1:2.6.1*99(00.00*kW)(0000000000000) Channel 1: 99.Pre-value Maximum Active power Export Max.-Tariff 1
...
1-1:2.6.1*87(00.00*kW)(0000000000000) Channel 1: 87.Pre-value Maximum Active power Export Max.-Tariff 1
1-1:2.6.1*86(00.00*kW)(0000000000000) Channel 1: 86.Pre-value Maximum Active power Export Max.-Tariff 1
1-1:2.6.2(00.00*kW)(0000000000000) Channel 1: Maximum Active power Export Max.-Tariff 2
1-1:2.6.2*00(00.00*kW)(0000000000000) Channel 1: 00.Pre-value Maximum Active power Export Max.-Tariff 2
1-1:2.6.2*99(00.00*kW)(0000000000000) Channel 1: 99.Pre-value Maximum Active power Export Max.-Tariff 2
...
1-1:2.6.2*87(00.00*kW)(0000000000000) Channel 1: 87.Pre-value Maximum Active power Export Max.-Tariff 2
1-1:2.6.2*86(00.00*kW)(0000000000000) Channel 1: 86.Pre-value Maximum Active power Export Max.-Tariff 2
1-1:2.6.3(00.00*kW)(0000000000000) Channel 1: Maximum Active power Export Max.-Tariff 3
1-1:2.6.3*00(00.00*kW)(0000000000000) Channel 1: 00.Pre-value Maximum Active power Export Max.-Tariff 3
1-1:2.6.3*99(00.00*kW)(0000000000000) Channel 1: 99.Pre-value Maximum Active power Export Max.-Tariff 3
...
1-1:2.6.3*87(00.00*kW)(0000000000000) Channel 1: 87.Pre-value Maximum Active power Export Max.-Tariff 3
1-1:2.6.3*86(00.00*kW)(0000000000000) Channel 1: 86.Pre-value Maximum Active power Export Max.-Tariff 3
1-1:2.8.0(0000000*kWh) Channel 1: Energy Active power Export Energy tariff 0
1-1:2.8.0*00(0000000*kWh) Channel 1: 00.Pre-value Energy Active power Export Energy tariff 0
1-1:2.8.0*99(0000000*kWh) Channel 1: 99.Pre-value Energy Active power Export Energy tariff 0
...
1-1:2.8.0*87(0000000*kWh) Channel 1: 87.Pre-value Energy Active power Export Energy tariff 0
1-1:2.8.0*86(0000000*kWh) Channel 1: 86.Pre-value Energy Active power Export Energy tariff 0
1-1:2.8.1(0000000*kWh) Channel 1: Energy Active power Export Energy tariff 1
1-1:2.8.1*00(0000000*kWh) Channel 1: 00.Pre-value Energy Active power Export Energy tariff 1
1-1:2.8.1*99(0000000*kWh) Channel 1: 99.Pre-value Energy Active power Export Energy tariff 1
...
1-1:2.8.1*87(0000000*kWh) Channel 1: 87.Pre-value Energy Active power Export Energy tariff 1
1-1:2.8.1*86(0000000*kWh) Channel 1: 86.Pre-value Energy Active power Export Energy tariff 1
1-1:2.8.2(0000000*kWh) Channel 1: Energy Active power Export Energy tariff 2
1-1:2.8.2*00(0000000*kWh) Channel 1: 00.Pre-value Energy Active power Export Energy tariff 2
1-1:2.8.2*99(0000000*kWh) Channel 1: 99.Pre-value Energy Active power Export Energy tariff 2
...
1-1:2.8.2*86(0000000*kWh) Channel 1: 86.Pre-value Energy Active power Export Energy tariff 2
1-1:2.8.3(0000000*kWh) Channel 1: Energy Active power Export Energy tariff 3
1-1:2.8.3*00(0000000*kWh) Channel 1: 00.Pre-value Energy Active power Export Energy tariff 3
1-1:2.8.3*99(0000000*kWh) Channel 1: 99.Pre-value Energy Active power Export Energy tariff 3
...
1-1:2.8.3*86(0000000*kWh) Channel 1: 86.Pre-value Energy Active power Export Energy tariff 3
1-1:5.8.0(0000000*kvarh) Channel 1: Energy Reactive power Q1 Energy tariff 0
1-1:5.8.0*00(0000000*kvarh) Channel 1: 00.Pre-value Energy Reactive power Q1 Energy tariff 0
1-1:5.8.0*99(0000000*kvarh) Channel 1: 99.Pre-value Energy Reactive power Q1 Energy tariff 0
...
1-1:5.8.0*87(0000000*kvarh) Channel 1: 87.Pre-value Energy Reactive power Q1 Energy tariff 0
1-1:5.8.0*86(0000000*kvarh) Channel 1: 86.Pre-value Energy Reactive power Q1 Energy tariff 0
1-1:5.8.1(0000000*kvarh) Channel 1: Energy Reactive power Q1 Energy tariff 1
1-1:5.8.1*00(0000000*kvarh) Channel 1: 00.Pre-value Energy Reactive power Q1 Energy tariff 1
1-1:5.8.1*99(0000000*kvarh) Channel 1: 99.Pre-value Energy Reactive power Q1 Energy tariff 1
...
1-1:5.8.1*87(0000000*kvarh) Channel 1: 87.Pre-value Energy Reactive power Q1 Energy tariff 1
1-1:5.8.1*86(0000000*kvarh) Channel 1: 86.Pre-value Energy Reactive power Q1 Energy tariff 1
1-1:5.8.2(0000000*kvarh) Channel 1: Energy Reactive power Q1 Energy tariff 2
1-1:5.8.2*00(0000000*kvarh) Channel 1: 00.Pre-value Energy Reactive power Q1 Energy tariff 2
1-1:5.8.2*99(0000000*kvarh) Channel 1: 99.Pre-value Energy Reactive power Q1 Energy tariff 2
...
1-1:5.8.2*87(0000000*kvarh) Channel 1: 87.Pre-value Energy Reactive power Q1 Energy tariff 2
1-1:5.8.2*86(0000000*kvarh) Channel 1: 86.Pre-value Energy Reactive power Q1 Energy tariff 2
1-1:5.8.3(0000000*kvarh) Channel 1: Energy Reactive power Q1 Energy tariff 3
1-1:5.8.3*00(0000000*kvarh) Channel 1: 00.Pre-value Energy Reactive power Q1 Energy tariff 3
1-1:5.8.3*99(0000000*kvarh) Channel 1: 99.Pre-value Energy Reactive power Q1 Energy tariff 3
...
1-1:5.8.3*87(0000000*kvarh) Channel 1: 87.Pre-value Energy Reactive power Q1 Energy tariff 3
1-1:5.8.3*86(0000000*kvarh) Channel 1: 86.Pre-value Energy Reactive power Q1 Energy tariff 3
1-1:8.8.0(0000000*kvarh) Channel 1: Energy Reactive power Q4 Energy tariff 0
1-1:8.8.0*00(0000000*kvarh) Channel 1: 00.Pre-value Energy Reactive power Q4 Energy tariff 0
1-1:8.8.0*99(0000000*kvarh) Channel 1: 99.Pre-value Energy Reactive power Q4 Energy tariff 0
...
1-1:8.8.0*87(0000000*kvarh) Channel 1: 87.Pre-value Energy Reactive power Q4 Energy tariff 0
1-1:8.8.0*86(0000000*kvarh) Channel 1: 86.Pre-value Energy Reactive power Q4 Energy tariff 0
1-1:8.8.1(0000000*kvarh) Channel 1: Energy Reactive power Q4 Energy tariff 1
1-1:8.8.1*00(0000000*kvarh) Channel 1: 00.Pre-value Energy Reactive power Q4 Energy tariff 1
1-1:8.8.1*99(0000000*kvarh) Channel 1: 99.Pre-value Energy Reactive power Q4 Energy tariff 1
...

EMH metering 25
Communication and data formats
1-1:8.8.1*87(0000000*kvarh) Channel 1: 87.Pre-value Energy Reactive power Q4 Energy tariff 1
1-1:8.8.1*86(0000000*kvarh) Channel 1: 86.Pre-value Energy Reactive power Q4 Energy tariff 1
1-1:8.8.2(0000000*kvarh) Channel 1: Energy Reactive power Q4 Energy tariff 2
1-1:8.8.2*00(0000000*kvarh) Channel 1: 00.Pre-value Energy Reactive power Q4 Energy tariff 2
1-1:8.8.2*99(0000000*kvarh) Channel 1: 99.Pre-value Energy Reactive power Q4 Energy tariff 2
...
1-1:8.8.2*87(0000000*kvarh) Channel 1: 87.Pre-value Energy Reactive power Q4 Energy tariff 2
1-1:8.8.2*86(0000000*kvarh) Channel 1: 86.Pre-value Energy Reactive power Q4 Energy tariff 2
1-1:8.8.3(0000000*kvarh) Channel 1: Energy Reactive power Q4 Energy tariff 3
1-1:8.8.3*00(0000000*kvarh) Channel 1: 00.Pre-value Energy Reactive power Q4 Energy tariff 3
1-1:8.8.3*99(0000000*kvarh) Channel 1: 99.Pre-value Energy Reactive power Q4 Energy tariff 3
...
1-1:8.8.3*87(0000000*kvarh) Channel 1: 87.Pre-value Energy Reactive power Q4 Energy tariff 3
1-1:8.8.3*86(0000000*kvarh) Channel 1: 86.Pre-value Energy Reactive power Q4 Energy tariff 3
1-2:1.2.0(0000.00*kW) Channel 2: Cumulative Active power Import Max.-Tariff 0
1-2:1.2.1(0000.00*kW) Channel 2: Cumulative Active power Import Max.-Tariff 1
1-2:1.2.2(0000.00*kW) Channel 2: Cumulative Active power Import Max.-Tariff 2
1-2:1.2.3(0000.00*kW) Channel 2: Cumulative Active power Import Max.-Tariff 3
1-2:1.6.0(00.00*kW)(0000000000000) Channel 2: Maximum Active power Import Max.-Tariff 0
1-2:1.6.0*00(00.00*kW)(0000000000000) Channel 2: 00.Pre-value Maximum Active power Import Max.-Tariff 0
1-2:1.6.0*99(00.00*kW)(0000000000000) Channel 2: 99.Pre-value Maximum Active power Import Max.-Tariff 0
...
1-2:1.6.0*87(00.00*kW)(0000000000000) Channel 2: 87.Pre-value Maximum Active power Import Max.-Tariff 0
1-2:1.6.0*86(00.00*kW)(0000000000000) Channel 2: 86.Pre-value Maximum Active power Import Max.-Tariff 0
1-2:1.6.1(00.00*kW)(0000000000000) Channel 2: Maximum Active power Import Max.-Tariff 1
1-2:1.6.1*00(00.00*kW)(0000000000000) Channel 2: 00.Pre-value Maximum Active power Import Max.-Tariff 1
1-2:1.6.1*99(00.00*kW)(0000000000000) Channel 2: 99.Pre-value Maximum Active power Import Max.-Tariff 1
...
1-2:1.6.1*87(00.00*kW)(0000000000000) Channel 2: 87.Pre-value Maximum Active power Import Max.-Tariff 1
1-2:1.6.1*86(00.00*kW)(0000000000000) Channel 2: 86.Pre-value Maximum Active power Import Max.-Tariff 1
1-2:1.6.2(00.00*kW)(0000000000000) Channel 2: Maximum Active power Import Max.-Tariff 2
1-2:1.6.2*00(00.00*kW)(0000000000000) Channel 2: 00.Pre-value Maximum Active power Import Max.-Tariff 2
1-2:1.6.2*99(00.00*kW)(0000000000000) Channel 2: 99.Pre-value Maximum Active power Import Max.-Tariff 2
...
1-2:1.6.2*87(00.00*kW)(0000000000000) Channel 2: 87.Pre-value Maximum Active power Import Max.-Tariff 2
1-2:1.6.2*86(00.00*kW)(0000000000000) Channel 2: 86.Pre-value Maximum Active power Import Max.-Tariff 2
1-2:1.6.3(00.00*kW)(0000000000000) Channel 2: Maximum Active power Import Max.-Tariff 3
1-2:1.6.3*00(00.00*kW)(0000000000000) Channel 2: 00.Pre-value Maximum Active power Import Max.-Tariff 3
1-2:1.6.3*99(00.00*kW)(0000000000000) Channel 2: 99.Pre-value Maximum Active power Import Max.-Tariff 3
...
1-2:1.6.3*87(00.00*kW)(0000000000000) Channel 2: 87.Pre-value Maximum Active power Import Max.-Tariff 3
1-2:1.6.3*86(00.00*kW)(0000000000000) Channel 2: 86.Pre-value Maximum Active power Import Max.-Tariff 3
1-2:1.8.0(0000000*kWh) Channel 2: Energy Active power Import Energy tariff 0
1-2:1.8.0*00(0000000*kWh) Channel 2: 00.Pre-value Energy Active power Import Energy tariff 0
1-2:1.8.0*99(0000000*kWh) Channel 2: 99.Pre-value Energy Active power Import Energy tariff 0
...
1-2:1.8.0*87(0000000*kWh) Channel 2: 87.Pre-value Energy Active power Import Energy tariff 0
1-2:1.8.0*86(0000000*kWh) Channel 2: 86.Pre-value Energy Active power Import Energy tariff 0
1-2:1.8.1(0000000*kWh) Channel 2: Energy Active power Import Energy tariff 1
1-2:1.8.1*00(0000000*kWh) Channel 2: 00.Pre-value Energy Active power Import Energy tariff 1
1-2:1.8.1*99(0000000*kWh) Channel 2: 99.Pre-value Energy Active power Import Energy tariff 1
...
1-2:1.8.1*87(0000000*kWh) Channel 2: 87.Pre-value Energy Active power Import Energy tariff 1
1-2:1.8.1*86(0000000*kWh) Channel 2: 86.Pre-value Energy Active power Import Energy tariff 1
1-2:1.8.2(0000000*kWh) Channel 2: Energy Active power Import Energy tariff 2
1-2:1.8.2*00(0000000*kWh) Channel 2: 00.Pre-value Energy Active power Import Energy tariff 2
1-2:1.8.2*99(0000000*kWh) Channel 2: 99.Pre-value Energy Active power Import Energy tariff 2
...
1-2:1.8.2*87(0000000*kWh) Channel 2: 87.Pre-value Energy Active power Import Energy tariff 2
1-2:1.8.2*86(0000000*kWh) Channel 2: 86.Pre-value Energy Active power Import Energy tariff 2
1-2:1.8.3(0000000*kWh) Channel 2: Energy Active power Import Energy tariff 3
1-2:1.8.3*00(0000000*kWh) Channel 2: 00.Pre-value Energy Active power Import Energy tariff 3
1-2:1.8.3*99(0000000*kWh) Channel 2: 99.Pre-value Energy Active power Import Energy tariff 3
...
1-2:1.8.3*87(0000000*kWh) Channel 2: 87.Pre-value Energy Active power Import Energy tariff 3
1-2:1.8.3*86(0000000*kWh) Channel 2: 86.Pre-value Energy Active power Import Energy tariff 3
1-1:9.8.0(0000000*kVAh) Channel 1: Energy Apparent power+ Energy tariff 0
1-1:9.8.0*00(0000000*kVAh) Channel 1: 00.Pre-value Energy Apparent power+ Energy tariff 0
1-1:9.8.0*99(0000000*kVAh) Channel 1: 99.Pre-value Energy Apparent power+ Energy tariff 0
...
1-1:9.8.0*87(0000000*kVAh) Channel 1: 87.Pre-value Energy Apparent power+ Energy tariff 0
1-1:9.8.0*86(0000000*kVAh) Channel 1: 86.Pre-value Energy Apparent power+ Energy tariff 0
1-1:10.8.0(0000000*kVAh) Channel 1: Energy Apparent power- Energy tariff 0
1-1:10.8.0*00(0000000*kVAh) Channel 1: 00.Pre-value Energy Apparent power- Energy tariff 0
1-1:10.8.0*99(0000000*kVAh) Channel 1: 99.Pre-value Energy Apparent power- Energy tariff 0
...

26 EMH metering
Communication and data formats
1-1:10.8.0*87(0000000*kVAh) Channel 1: 87.Pre-value Energy Apparent power- Energy tariff 0
1-1:10.8.0*86(0000000*kVAh) Channel 1: 86.Pre-value Energy Apparent power- Energy tariff 0
1-1:83.8.1(00000000*kWh) Channel 1: Active energy copper losses, import
1-1:83.8.1*00(00000000*kWh) Channel 1: 00.Pre-value Active energy copper losses, import
1-1:83.8.1*99(00000000*kWh) Channel 1: 99.Pre-value Active energy copper losses, import
...
1-1:83.8.1*87(00000000*kWh) Channel 1: 87.Pre-value Active energy copper losses, import
1-1:83.8.1*86(00000000*kWh) Channel 1: 86.Pre-value Active energy copper losses, import
1-1:83.8.2(00000000*kWh) Channel 1: Active energy copper losses, export
1-1:83.8.2*00(00000000*kWh) Channel 1: 00.Pre-value Active energy copper losses, export
1-1:83.8.2*99(00000000*kWh) Channel 1: 99.Pre-value Active energy copper losses, export
...
1-1:83.8.2*87(00000000*kWh) Channel 1: 87.Pre-value Active energy copper losses, export
1-1:83.8.2*86(00000000*kWh) Channel 1: 86.Pre-value Active energy copper losses, export
1-1:83.8.4(00000034*kWh) Channel 1: Active energy iron losses, import
1-1:83.8.4*00(00000000*kWh) Channel 1: 00.Pre-value Active energy iron losses, import
1-1:83.8.4*99(00000000*kWh) Channel 1: 99.Pre-value Active energy iron losses, import
...
1-1:83.8.4*87(00000000*kWh) Channel 1: 87.Pre-value Active energy iron losses, import
1-1:83.8.4*86(00000000*kWh) Channel 1: 86.Pre-value Active energy iron losses, import
1-1:83.8.5(00000074*kWh) Channel 1: Active energy iron losses, export
1-1:83.8.5*00(00000000*kWh) Channel 1: 00.Pre-value Active energy iron losses, export
1-1:83.8.5*99(00000000*kWh) Channel 1: 99.Pre-value Active energy iron losses, export
...
1-1:83.8.5*87(00000000*kWh) Channel 1: 87.Pre-value Active energy iron losses, export
1-1:83.8.5*86(00000000*kWh) Channel 1: 86.Pre-value Active energy iron losses, export
F.F(00000000) Error register
!
□i
BCC=105 OK

EMH metering 27
Communication and data formats

15.2 Table 2
/EMH5\@\201LZQJL0013F
□C.1.0(00418895) Manufacturing number
0.0.1() Identity number 1
0.0.2() Identity number 2
0.0.3() Identity number 3
0.9.1(1092812) Clock time
0.9.2(1050628) Date
F.F(00000000) Error register
P.01(1050622111201)(00004000)(15)(7)(1-1:1.5)(kW)(1-1:2.5)(kW)(1-1:5.5)(kvar)(1-1:6.5)(kvar)
(1-1:7.5)(kvar)(1-1:8.5)(kvar)(1-2:1.5)(kW) Status : LP deleted,
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
P.01(1050622113000)(00000080)(15)(7)(1-1:1.5)(kW)(1-1:2.5)(kW)(1-1:5.5)(kvar)(1-1:6.5)(kvar)
(1-1:7.5)(kvar)(1-1:8.5)(kvar)(1-2:1.5)(kW) Status : Power failure,
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
P.01(1050622114500)(00000040)(15)(7)(1-1:1.5)(kW)(1-1:2.5)(kW)(1-1:5.5)(kvar)(1-1:6.5)(kvar)
(1-1:7.5)(kvar)(1-1:8.5)(kvar)(1-2:1.5)(kW) Status : Return of power supply,
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
P.01(1050622120000)(00000080)(15)(7)(1-1:1.5)(kW)(1-1:2.5)(kW)(1-1:5.5)(kvar)(1-1:6.5)(kvar)
(1-1:7.5)(kvar)(1-1:8.5)(kvar)(1-2:1.5)(kW) Status : Power failure,
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
P.01(1050624134500)(00000040)(15)(7)(1-1:1.5)(kW)(1-1:2.5)(kW)(1-1:5.5)(kvar)(1-1:6.5)(kvar)
(1-1:7.5)(kvar)(1-1:8.5)(kvar)(1-2:1.5)(kW) Status : Return of power supply,
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
P.01(1050624140000)(00000000)(15)(7)(1-1:1.5)(kW)(1-1:2.5)(kW)(1-1:5.5)(kvar)(1-1:6.5)(kvar)
(1-1:7.5)(kvar)(1-1:8.5)(kvar)(1-2:1.5)(kW) Status : Value correct
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
P.01(1050624150000)(000000C0)(15)(7)(1-1:1.5)(kW)(1-1:2.5)(kW)(1-1:5.5)(kvar)(1-1:6.5)(kvar)(1-
1:7.5)(kvar)(1-1:8.5)(kvar)(1-2:1.5)(kW) Status : Power failure, Return of power supply,
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
P.01(1050624151500)(00000000)(15)(7)(1-1:1.5)(kW)(1-1:2.5)(kW)(1-1:5.5)(kvar)(1-1:6.5)(kvar)
(1-1:7.5)(kvar)(1-1:8.5)(kvar)(1-2:1.5)(kW) Status : Value correct
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
...
!

28 EMH metering
Communication and data formats

15.3 Table 3 (for EMH-internal test purposes)


/EMH5\@\201LZQJL0013F
□C.1.0(00418895) Manufacturing number
0.0.1() Identity number 1
0.0.2() Identity number 2
0.0.3() Identity number 3
1-1:1.2.0(0000.00*kW) Channel 1: Cumulative Active power Import Max.-Tariff 0
1-1:1.2.1(0000.00*kW) Channel 1: Cumulative Active power Import Max.-Tariff 1
1-1:1.2.2(0000.00*kW) Channel 1: Cumulative Active power Import Max.-Tariff 2
1-1:1.2.3(0000.00*kW) Channel 1: Cumulative Active power Import Max.-Tariff 3
1-1:2.2.0(0000.00*kW) Channel 1: Cumulative Active power Export Max.-Tariff 0
1-1:2.2.1(0000.00*kW) Channel 1: Cumulative Active power Export Max.-Tariff 1
1-1:2.2.2(0000.00*kW) Channel 1: Cumulative Active power Export Max.-Tariff 2
1-1:2.2.3(0000.00*kW) Channel 1: Cumulative Active power Export Max.-Tariff 3
1-2:1.2.0(0000.00*kW) Channel 2: Cumulative Active power Import Max.-Tariff 0
1-2:1.2.1(0000.00*kW) Channel 2: Cumulative Active power Import Max.-Tariff 1
1-2:1.2.2(0000.00*kW) Channel 2: Cumulative Active power Import Max.-Tariff 2
1-2:1.2.3(0000.00*kW) Channel 2: Cumulative Active power Import Max.-Tariff 3
1-1:1.6.0(00.00*kW)(0000000000000) Channel 1: Maximum Active power Import Max.-Tariff 0
1-1:1.6.1(00.00*kW)(0000000000000) Channel 1: Maximum Active power Import Max.-Tariff 1
1-1:1.6.2(00.00*kW)(0000000000000) Channel 1: Maximum Active power Import Max.-Tariff 2
1-1:1.6.3(00.00*kW)(0000000000000) Channel 1: Maximum Active power Import Max.-Tariff 3
1-1:2.6.0(00.00*kW)(0000000000000) Channel 1: Maximum Active power Export Max.-Tariff 0
1-1:2.6.1(00.00*kW)(0000000000000) Channel 1: Maximum Active power Export Max.-Tariff 1
1-1:2.6.2(00.00*kW)(0000000000000) Channel 1: Maximum Active power Export Max.-Tariff 2
1-1:2.6.3(00.00*kW)(0000000000000) Channel 1: Maximum Active power Export Max.-Tariff 3
1-2:1.6.0(00.00*kW)(0000000000000) Channel 2: Maximum Active power Import Max.-Tariff 0
1-2:1.6.1(00.00*kW)(0000000000000) Channel 2: Maximum Active power Import Max.-Tariff 1
1-2:1.6.2(00.00*kW)(0000000000000) Channel 2: Maximum Active power Import Max.-Tariff 2
1-2:1.6.3(00.00*kW)(0000000000000) Channel 2: Maximum Active power Import Max.-Tariff 3
1-1:1.8.0(0000000*kWh) Channel 1: Energy Active power Import Energy tariff 0
1-1:1.8.1(0000000*kWh) Channel 1: Energy Active power Import Energy tariff 1
1-1:1.8.2(0000000*kWh) Channel 1: Energy Active power Import Energy tariff 2
1-1:1.8.3(0000000*kWh) Channel 1: Energy Active power Import Energy tariff 3
1-1:2.8.0(0000000*kWh) Channel 1: Energy Active power Export Energy tariff 0
1-1:2.8.1(0000000*kWh) Channel 1: Energy Active power Export Energy tariff 1
1-1:2.8.2(0000000*kWh) Channel 1: Energy Active power Export Energy tariff 2
1-1:2.8.3(0000000*kWh) Channel 1: Energy Active power Export Energy tariff 3
1-1:5.8.0(0000000*kvarh) Channel 1: Energy Reactive power Q1 Energy tariff 0
1-1:5.8.1(0000000*kvarh) Channel 1: Energy Reactive power Q1 Energy tariff 1
1-1:5.8.2(0000000*kvarh) Channel 1: Energy Reactive power Q1 Energy tariff 2
1-1:5.8.3(0000000*kvarh) Channel 1: Energy Reactive power Q1 Energy tariff 3
1-1:8.8.0(0000000*kvarh) Channel 1: Energy Reactive power Q4 Energy tariff 0
1-1:8.8.1(0000000*kvarh) Channel 1: Energy Reactive power Q4 Energy tariff 1
1-1:8.8.2(0000000*kvarh) Channel 1: Energy Reactive power Q4 Energy tariff 3
1-2:1.8.0(0000000*kWh) Channel 2: Energy Active power Import Energy tariff 0
1-2:1.8.1(0000000*kWh) Channel 2: Energy Active power Import Energy tariff 1
1-2:1.8.2(0000000*kWh) Channel 2: Energy Active power Import Energy tariff 2
1-2:1.8.3(0000000*kWh) Channel 2: Energy Active power Import Energy tariff 3
1-1:9.8.0(0000000*kVAh) Channel 1: Energy Apparent power+ Energy tariff 0
1-1:83.8.1(0000000*kWh) Channel 1: Active energy copper losses, import
1-1:83.8.2(00000000*kWh) Channel 1: Active energy copper losses, export
1-1:83.8.4(00000034*kWh) Channel 1: Active energy iron losses, import
1-1:83.8.5(00000074*kWh) Channel 1: Active energy iron losses, export
0.1.0(00) Reset counter
0.9.1(1092837) Clock time
0.9.2(1050628) Date
0.2.1*01(05061723) PAR number
0.2.1*02(11334100) PAR settings
0.2.1*50(050617C3) SET number
0.2.2(06002200) Switching clock program number
0.3.0(500.00000*Imp/kWh) LED-constants
0.3.3(250.00000*Imp/kWh) Output constants actve
0.3.4(250.00000*Imp/kvarh) Output constants reactive
C.90.0(7B313D3F) Checksum PAR
C.90.1(9D803CEF) Checksum SET
C.90.2(9C573D17) Checksum ROM
C.90.3(F96DD618) Checksum System
F.F(00000000) Error register
P.01(1050628070000)(00000000)(15)(7)(1-1:1.5)(kW)(1-1:2.5)(kW)(1-1:5.5)(kvar)(1-1:6.5)(kvar)
(1-1:7.5)(kvar)(1-1:8.5)(kvar)(1-2:1.5)(kW) Status : Value correct
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)

EMH metering 29
Communication and data formats
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)(00.00)
P.02(1050628075000)00000000)(10)(25)(32.5)(V)(52.5)(V)(72.5)(V)(32.23)(V)(52.23)(V)(72.23)(V)(32.26)
(V)(52.26)(V)(72.26)(V)(31.5)(A)(51.5)(A)(71.5)(A)(31.26)(A)(51.26)(A)(71.26)(A)(140.5)(%)(141.5)(%)
(142.5)(%)(143.5)(%)(144.5)(%)(145.5)(%)(146.5)()(147.5)()(148.5)()(14.5)(Hz) Status : Value correct
(000.70)(000.68)(223.44)(000.69)(000.67)(220.36)(000.69)(000.67)(226.52)(000.01)(000.03)(000.02)
(000.04)(000.07)(000.04)(00.00)(00.00)(01.96)(00.00)(00.00)(00.00)(0.00)(0.00)(0.66)(50.01)
(000.69)(000.67)(222.23)(000.69)(000.67)(219.29)(000.69)(000.67)(224.77)(000.02)(000.02)(000.01)
(000.05)(000.07)(000.03)(00.00)(00.00)(02.01)(00.00)(00.00)(00.00)(0.00)(0.00)(0.66)(50.01)
(000.69)(000.68)(223.23)(000.69)(000.67)(218.41)(000.69)(000.67)(225.94)(000.02)(000.03)(000.02)
(000.05)(000.07)(000.04)(00.00)(00.00)(02.05)(00.00)(00.00)(00.00)(0.00)(0.00)(0.67)(50.02)
(000.70)(000.68)(221.71)(000.69)(000.67)(217.77)(000.69)(000.68)(224.89)(000.02)(000.02)(000.02)
(000.05)(000.06)(000.04)(00.00)(00.00)(02.07)(00.00)(00.00)(00.00)(0.00)(0.00)(0.67)(49.98)
(000.69)(000.68)(225.04)(000.69)(000.67)(218.63)(000.69)(000.67)(227.95)(000.02)(000.03)(000.01)
(000.04)(000.07)(000.03)(00.00)(00.00)(02.01)(00.00)(00.00)(00.00)(0.00)(0.00)(0.64)(49.99)
(000.70)(000.67)(224.19)(000.69)(000.67)(219.87)(000.69)(000.68)(227.60)(000.02)(000.02)(000.02)
(000.05)(000.06)(000.03)(00.00)(00.00)(02.05)(00.00)(00.00)(00.00)(0.00)(0.00)(0.62)(49.99)
(000.69)(000.68)(224.12)(000.69)(000.67)(218.59)(000.69)(000.68)(226.69)(000.02)(000.03)(000.02)
(000.04)(000.09)(000.04)(00.00)(00.00)(02.10)(00.00)(00.00)(00.00)(0.00)(0.00)(0.64)(50.00)
(000.69)(000.68)(223.19)(000.69)(000.67)(216.76)(000.69)(000.68)(225.77)(000.02)(000.03)(000.01)
(000.03)(000.06)(000.04)(00.00)(00.00)(02.15)(00.00)(00.00)(00.00)(0.00)(0.00)(0.65)(50.00)
(000.70)(000.68)(224.75)(000.69)(000.67)(222.28)(000.69)(000.68)(227.68)(000.01)(000.02)(000.02)
(000.04)(000.06)(000.03)(00.00)(00.00)(02.07)(00.00)(00.00)(00.00)(0.00)(0.00)(0.62)(50.01)
(000.69)(000.68)(225.64)(000.69)(000.67)(222.64)(000.69)(000.67)(228.64)(000.02)(000.03)(000.01)
(000.05)(000.08)(000.04)(00.00)(00.00)(02.07)(00.00)(00.00)(00.00)(0.00)(0.00)(0.62)(49.99)
P.02(1050628092150)00000080)(10)(25)(32.5)(V)(52.5)(V)(72.5)(V)(32.23)(V)(52.23)(V)(72.23)(V)(32.26)
(V)(52.26)(V)(72.26)(V)(31.5)(A)(51.5)(A)(71.5)(A)(31.26)(A)(51.26)(A)(71.26)(A)(140.5)(%)(141.5)(%)
(142.5)(%)(143.5)(%)(144.5)(%)(145.5)(%)(146.5)()(147.5)()(148.5)()(14.5)(Hz)
Status : Power failure,
(000.13)(000.12)(040.96)(000.69)(000.67)(221.15)(000.69)(000.67)(225.32)(000.01)(000.00)(000.01)
(000.05)(000.05)(000.03)(00.00)(00.00)(00.37)(00.00)(00.00)(00.00)(0.00)(0.00)(0.11)(09.17)
!

BCC=9 OK

30 EMH metering
Communication and data formats

15.4 Table 4
/EMH5\@\201LZQJL0013F
□C.86.0(00007030) Installtion register
C.1.0(00418895) Manufacturing number
0.0.1() Identity number 1
0.0.2() Identity number 2
0.0.3() Identity number 3
0.9.1(1092859) Clock time
0.9.2(1050628) Date
21.25(0.00*kW) Instantaneous active power P L1
41.25(0.00*kW) Instantaneous active power P L2
61.25(0.00*kW) Instantaneous active power P L3
1.25(0.00*kW) Instantaneous active power P Sum
23.25(0.00*kvar) Instantaneous active power Q L1
43.25(0.00*kvar) Instantaneous active power Q L2
63.25(0.00*kvar) Instantaneous active power Q L3
3.25(0.00*kvar) Instantaneous active power Q Sum
29.25(0.00*kVA) Instantaneous active power S L1
49.25(0.00*kVA) Instantaneous active power S L2
69.25(0.00*kVA) Instantaneous active power S L3
9.25(0.00*kVA) Instantaneous active power S Sum
33.25(0.00*P/S) Power factor L1
53.25(0.00*P/S) Power factor L2
73.25(0.00*P/S) Power factor L3
13.25(0.00*P/S) Power factor Sum
31.25(0.01*A) Current L1
51.25(0.04*A) Current L2
71.25(0.01*A) Current L3
32.25(0.69*V) Voltage L1
52.25(0.68*V) Voltage L2
72.25(221.39*V) Voltage L3
14.25(49.99*Hz) Line frequency
C.3(00004000) In-/output status
C.4(00E00040) Internal control signal
C.5(00201030) Internal operating conditions
C.7.0(0010) Power failure all phases
C.7.1(0000) Power failure L1
C.7.2(0000) Power failure L2
C.7.3(0000) Power failure L3
P.200(1050622111201)(00002000)()(0) Status : Log book deleted,
P.200(1050622111201)(0000000B)()(0) Status : Manipulation terminal cover, Failure phase 2,
Failure phase 1,
P.200(1050625003857)(0000004B)()(0) Status : Tariff T3, Manipulation terminal cover, Failure
phase 2, Failure phase 1,
P.200(1050625084131)(0000000B)()(0) Status : Manipulation terminal cover, Failure phase 2,
Failure phase 1,
P.200(1050628044705)(0000004B)()(0) Status : Tariff T3, Manipulation terminal cover, Failure
phase 2, Failure phase 1,
P.200(1050628060000)(0000000B)()(0) Status : Manipulation terminal cover, Failure phase 2,
Failure phase 1,
P.200(1050628092223)(00000003)()(0) Status : Failure phase 2, Failure phase 1,
!
□□
BCC=27 OK

EMH metering 31
Communication and data formats

15.5 Operation log book P.98


/EMH5\@\201LZQJL0013F

0.0.0(23456321) Meter address
P.98(1041007095703)(00002000)()(0) Status : Log book deleted,
P.98(1041007095703)(00004000)()(0) Status : LP deleted,
P.98(1041007095807)(00000100)()(0) Status : Set in the meter,
P.98(1041007095914)(00000080)()(0) Status : Power failure,
P.98(1041007100749)(00000040)()(0) Status : Return of power supply,
P.98(1041007101738)(00000100)()(0) Status : Set in the meter,
P.98(1041007101848)(00000100)()(0) Status : Set in the meter,
P.98(1041007104039)(00000010)()(0) Status : Reset,
P.98(1041021105758)(00000010)()(0) Status : Reset,
P.98(1041031030000)(00008028)()(2)(0.9.1)()(0.9.2)()(0020000)(0041031) Status : Status before time
shift, Clock set, Season change,
P.98(0041101000000)(00000010)()(0) Status : Reset,
P.98(0041116180314)(00000080)()(0) Status : Power failure,
P.98(0041116191456)(00000040)()(0) Status : Return of power supply,
P.98(0041123081833)(00000100)()(0) Status : Set in the meter,
P.98(0041201000000)(00000010)()(0) Status : Reset,
P.98(0041206150845)(00000080)()(0) Status : Power failure,
P.98(0041206155136)(00000040)()(0) Status : Return of power supply,
P.98(0041221091217)(00000100)()(0) Status : Set in the meter,
P.98(0050101000000)(00000010)()(0) Status : Reset,
P.98(0050201000000)(00000010)()(0) Status : Reset,
P.98(0050218141450)(00000100)()(0) Status : Set in the meter,
P.98(0050218141535)(00000100)()(0) Status : Set in the meter,
P.98(0050218151536)(00000100)()(0) Status : Set in the meter,
P.98(0050218151726)(00000100)()(0) Status : Set in the meter,
P.98(0050218152206)(00000100)()(0) Status : Set in the meter,
P.98(0050218152923)(00000100)()(0) Status : Set in the meter,
P.98(0050218155516)(00000100)()(0) Status : Set in the meter,
P.98(0050218155545)(00000100)()(0) Status : Set in the meter,
P.98(0050221075921)(00000100)()(0) Status : Set in the meter,
P.98(0050221080057)(00000100)()(0) Status : Set in the meter,
P.98(0050221085112)(00000100)()(0) Status : Set in the meter,
P.98(0050221085254)(00000100)()(0) Status : Set in the meter,
P.98(0050301000000)(00000010)()(0) Status : Reset,
P.98(0050309110123)(00000080)()(0) Status : Power failure,
P.98(0050309113338)(00000040)()(0) Status : Return of power supply,
P.98(0050309133529)(00000080)()(0) Status : Power failure,
P.98(0050309133648)(00000040)()(0) Status : Return of power supply,
P.98(0050327020000)(00008028)()(2)(0.9.1)()(0.9.2)()(1030000)(1050327) Status : Status before time shift,
Clock set, Season change,
P.98(1050401000000)(00000010)()(0) Status : Reset,
P.98(1050501000000)(00000010)()(0) Status : Reset,
P.98(1050513082012)(00000100)()(0) Status : Set in the meter,
P.98(1050513082127)(00000080)()(0) Status : Power failure,
P.98(1050513082138)(00000040)()(0) Status : Return of power supply,
P.98(1050518140952)(00000080)()(0) Status : Power failure,
P.98(1050518141002)(00000040)()(0) Status : Return of power supply,
P.98(1050525111501)(00000080)()(0) Status : Power failure,
P.98(1050525111527)(00000040)()(0) Status : Return of power supply,
P.98(1050525113527)(00000100)()(0) Status : Set in the meter,
P.98(1050525134305)(00000100)()(0) Status : Set in the meter,
P.98(1050530084824)(00000100)()(0) Status : Set in the meter,
P.98(1050530084836)(00000100)()(0) Status : Set in the meter,
P.98(1050601000000)(00000010)()(0) Status : Reset,
P.98(1050607120947)(00000100)()(0) Status : Set in the meter,
P.98(1050609164301)(00000100)()(0) Status : Set in the meter,
P.98(1050629105230)(00000010)()(0) Status : Reset,
P.98(1050629110739)(00000010)()(0) Status : Reset,
P.98(1050629161207)(00000010)()(0) Status : Reset,
P.98(1050701000000)(00000010)()(0) Status : Reset,
□□
Log out...
BCC=14 OK

32 EMH metering
Communication and data formats

15.6 Certification relevant log book P.99


/EMH5\@\201LZQJL0013F
Meter password is being sent. . .
Password OK

□P.99(1050622111201)(00002000)()(0) Status : Log book deleted,
P.99(1050622111245)(00000008)()(1)(0.3.3)(Imp/kWh)(250.00000;500.00000)
Status : P output constants changed,
P.99(1050622111246)(00000010)()(1)(0.3.4)(Imp/kvarh)(250.00000;500.00000)
Status : Q output constants changed,
P.99(1050622111817)(00000001)()(1)(0.3.0)(Imp/kWh)(500.00000;1000.0000)
Status : LED constants changed,
P.99(1050622111905)(00000008)()(1)(0.3.3)(Imp/kWh)(500.00000;250.00000)
Status :P output constants changed,
P.99(1050622111905)(00000010)()(1)(0.3.4)(Imp/kvarh)(500.00000;250.00000)
Status : Q output constants changed,
P.99(1050622111906)(00000001)()(1)(0.3.0)(Imp/kWh)(1000.0000;500.00000)
Status : LED constants changed,
□z
Log out...
BCC=122 OK

15.7 User log book P.200


/EMH5\@\201LZQJL0013F

□P.200(1050622111201)(00002000)()(0) Status : Log book deleted,
P.200(1050622111201)(0000000B)()(0) Status : Manipulation terminal cover, Failure phase 2, Failure phase 1,
P.200(1050625003857)(0000004B)()(0) Status : Tariff T3, Manipulation terminal cover,
Failure phase 2, Failure phase 1,
P.200(1050625084131)(0000000B)()(0) Status : Manipulation terminal cover, Failure phase 2, Failure phase 1,
P.200(1050628044705)(0000004B)()(0) Status : Tariff T3, Manipulation terminal cover, Failure
phase 2, Failure phase 1,
P.200(1050628060000)(0000000B)()(0) Status : Manipulation terminal cover, Failure phase 2, Failure phase 1,
P.200(1050628092223)(00000003)()(0) Status : Failure phase 2, Failure phase 1,
P.200(1050629044315)(00000043)()(0) Status : Tariff T3, Failure phase 2, Failure phase 1,
P.200(1050629060000)(00000003)()(0) Status : Failure phase 2, Failure phase 1,
P.200(1050629115036)(00000103)()(0) Status : Unpermitted read access, Failure phase 2, Failure phase 1,
P.200(1050629115051)(00000103)()(0) Status : Unpermitted read access, Failure phase 2, Failure phase 1,
P.200(1050629115117)(00000103)()(0) Status : Unpermitted read access, Failure phase 2, Failure phase 1,
P.200(1050629115546)(00000103)()(0) Status : Unpermitted read access, Failure phase 2, Failure phase 1,
P.200(1050629115600)(00000103)()(0) Status : Unpermitted read access, Failure phase 2, Failure phase 1,
P.200(1050629115612)(00000103)()(0) Status : Unpermitted read access, Failure phase 2, Failure phase 1,
□>
Log out...
BCC=62 OK

EMH metering 33
Communication and data formats

15.8 Event log book P.210


/EMH5\@\201LZQJL0013F

P.210(1070721145342)(2000)()(0) Event log book, Log book deleted,


P.210(1070721145342)(23AC)()(0) Event log book, Start terminal cover manipulation,
P.210(1070721145342)(23AD)()(0) Event log book, Start housing cover manipulation,
P.210(1070721145343)(2307)()(0) Event log book, PAR-status activated,
P.210(1070721145345)(22B7)()(0) Event log book, Start negative active energy L1,
P.210(1070721145345)(22B8)()(0) Event log book, Start negative active energy L2,
P.210(1070721145345)(22B9)()(0) Event log book, Start negative active energy L3,
P.210(1070722145342)(3307)()(0) Event log book, PAR-status deactivated,
P.210(1070723123008)(2307)()(0) Event log book, PAR-status activated,
P.210(1070723123008)(32B7)()(0) Event log book, End negative active energy L1,
P.210(1070723123008)(32B8)()(0) Event log book, End negative active energy L2,
P.210(1070723123008)(32B9)()(0) Event log book, End negative active energy L3,
P.210(1070723123010)(22B7)()(0) Event log book, Start negative active energy L1,
P.210(1070723123010)(22B8)()(0) Event log book, Start negative active energy L2,
P.210(1070723123010)(22B9)()(0) Event log book, Start negative active energy L3,
:
Log out...
BCC=58 OK

15.9 Event log book P.211

/EMH5\@\201LZQJL0013F

P.211(1070721145342)(2000)()(0) Event log book, Log book deleted,


P.211(1070721151001)(23A6)()(1)(C.86.1)()(00001100) Event log book, Event in voltage quality register
C.86.1,
P.211(1070723142357)(234D)()(0) Event log book, Voltage failure L2,
P.211(1070723142437)(334D)()(0) Event log book, Voltage return L2,

Log out...
BCC=10 OK