You are on page 1of 6

2018 IEEE International Conference on Renewable Energy and Power Engineering

Distributed Generator in Grid-Connected Mode Using Improved Exponential


Sliding Mode Control

S. Sinan1, A. Elnady2 and M. Al-Shabi3


Electrical and Computer Engineering Department
University of Sharjah
27272 Sharjah, United Arab Emirates
E-mail: ssinan03@gmail.com1, anady@sharjah.ac.ae2, malshabi@sharjah.ac.ae3

Abstract—This paper shows the operation of the considered to operate the DGS in both modes:
distributed generation system using an innovative control Grid-connected mode and stand-alone mode. In this section
scheme. The core of this distributed generation system is the the literature review is focused on the schemes used for the
distributed generator, which is based on the 5-level diode grid-connected mode because the distributed generation
clamped inverter. This distributed generator is operated by an system in this paper is operated in a grid-connected mode.
improved version of the exponential sliding mode control. Voltage oriented control (VOC), also called voltage
vector control, has been adopted to control the distributed
This developed sliding mode control perfectly fits the power
generation systems in a grid-connected mode such that it can
electronics based distributed generator to control the output be used to inject active and reactive power based on the
injected power, and it gives the shortest reaching time with system conditions [4-6]. Voltage oriented control is an
much less chattering at its output power. The performance of indirect scheme to control the output power since it controls
the whole suggested control scheme along with the improved active and reactive power through the direct and quadrature
sliding mode controller is verified using simulation results. currents, respectively. The main controller in the control
loops is the PI controller or PR controller. The good
Keywords—Exponential sliding mode control, distributed performance of the VOC is not guaranteed at different
generation system, PD-PWM, and power control. operating conditions.
Another scheme used with the DGS is the sliding mode
I. INTRODUCTION control (SMC) [7-10]. The main structure of this scheme is
The distributed generation system (DGS) has been similar to the VOC because the power references is converted
proliferating in distribution systems because it supplies the into current references. The current error, generated between
distribution system with extra power needed for the operation the current reference and its corresponding feedback, is
of the distribution system when the distribution system is controlled by the SMC to operate the DG. Several versions of
heavily loaded. The DGS is characterized by the generation the 1st order SMC have been utilized to control the DGS.
capacity of its distributed generator (DG) that is mainly These versions are classified based on the adopted reaching
determined by the rating of the inverter circuit. The law and the definition of the sliding surface, (sliding
generation capacity of the DG ranges from few KVA to few manifold). The SMC with a differential form of the sliding
MVA [1-3]. surface is employed in [7] to the control the DGS in a
The penetration of the DGS in the distribution system is grid-connected mode. The integral form of the sliding surface
continuously increasing nowadays because it brings a lot of is presented in [7-10]. A constant-rate reaching law, which is
benefits to the distribution system when it’s tied to the expressed by the signum function, is utilized for the DGS
distribution system. The DGS achieves the following in [10]. A power-rate reaching law accompanied by a
benefits: boundary layer is used in [7-9] to improve the reaching mode
x It regulates the voltage at the point of common coupling and to reduce its chattering at the sliding mode. All versions
where it is installed. of the 1st order SMC suffer from chattering in its output
x It injects more active power to the distribution system power/current. This drawback triggers the utilization of some
under heavy loading conditions. advanced sliding mode controllers to control the DGS [11],
x It increases the overall stability of the system. [12]. A 2nd order SMC, super-twisting technique, has been
x It reduces the voltage drop and the power losses over the formulated and employed to control the distributed generator
distribution feeders since the power direction is reversed in a grid-connected mode and in stand-alone mode as
in some feeders. presented in [11]. The super-twisting technique presents a
better performance at the sliding mode in terms of the
The DGS entails a control algorithm that precisely
chattering. Its performance is compared to the 1st order SMC
controls the operation of the distributed generator in a fast
in [7]. The exponential SMC has been published before in
and accurate manner. Many control schemes have been
[13-14], and it is proved that this version offers a better
developed and employed for the DGS. These schemes are
performance than the conventional SMC. This classical

978-1-5386-9365-0/18/$31.00 ©2018 IEEE 7


Authorized licensed use limited to: Walchand College of Eng. Downloaded on January 09,2023 at 12:06:50 UTC from IEEE Xplore. Restrictions apply.
exponential SMC is modified in [15] to fit the operation of where G 0 is a strictly positive offset less than 1, U is a
the power electronics circuits. Its control law is modified by
adding one constant-proportional term to the discrete term of strictly positive integer, and D is strictly positive. The
its control law. formulas in (1-3) prove to be better than the conventional
The most recent scheme to control the DGS is the direct SMC in terms of the reachability time defined and proved in
power control (DPC) [16-18]. This scheme is originated from [13], [14]. The chattering is reduced at the sliding mode
the direct torque control used to control the drive systems. because at the beginning of this reaching mode the value of
The DPC adjusts the power directly not through the currents k
as mentioned before. The conventional DPC depends a s is large; so the magnitude of the udis tends to be .
hysteresis controller and the space vector modulation (SVM), G0
which cause oscillation shown in the output power and While at the end of the reaching mode, the value of s
variable switching frequency. Several modifications have becomes small; then the magnitude of the udis tends to be
been introduced to the DPC in order to improve its
performance and minimize its drawback. A look-up-table is just k . The other term of the control law is the ueq , which is
used to minimize the switching frequency [16]. Predictive derived using the Lyapunov stability criterion. The final
control is merged with the DPC to improve the performance
of the SVM and hysteresis controllers [17], [18]. expression of the ueq is given as,
The contribution of this paper is exemplified in using an 1
ª ws B º ws Ax
«¬ wx »¼ wx > @
improved exponential sliding mode control to accurately ueq (6)
control the currents and consequently the injected power.
This improvement gives a better performance than what is The improvement in the exponential SMC in this paper is
published in [13-14]. This paper has five sections, where the different from what has been published in [13-15] in the
second section shows the formulation of the exponential following aspects:
sliding mode control. The third sections depicts the suggested
control scheme along with the proposed controller. The
1- The sliding surface in this research is defined by its
fourth section displays the simulation results. The last two
integral form as given in (7), while the sliding surface in
sections demonstrate the findings and appendix of this paper.
[13-15] is defined by its differential form, which does not
guarantee the minimum steady-state error (For instance some
II. FORMULATION OF EXPONENTIAL SLIDING MODE results in [14] shows a clear steady-state error). This integral
CONTROL SMC is defined as,

The exponential SMC has been introduced in [13-15]. s (O1  O2 ³ dt ) e (7)


The contribution of this exponential SMC is in the definition It is proved that the integral SMC gives less error than any
of its control law, which is expressed as, other form for the sliding surface [7].
u udis  ueq (1) 2- The discrete term udis of the control law in this
where the udis is the discrete input, which is responsible research is innovatively defined as,
for reaching mode used for transferring the states of the k
udis  tanh( s ) (8)
system from one sliding surface to another. The ueq is the N( s )
continuous input used to keep the states of the system on the The tanh function is selected because the signum
sliding surface (sliding mode). In [13-15], the sliding surface function does not perfectly match the operation of the power
is defined by its differential form as, electronics based systems like the system under study in this
s (O1  O2 dt ) e (2) paper since it causes sudden sharp changes in its output and
spontaneous deviation of the states from the sliding surface
The contribution in [13-14] is the definition of the
leading to possible unstable operation. While the tanh
discrete input udis given as, function is different since it does not produce these sharp
k changes.
u dis 
sign ( s ) (3) 3- The definition of the continuous input u eq is slightly
N (s)
While in [15], the contribution is exemplified as, modified from what given in (6) to fit the state-space model
of the system understudy since the state-space model is given
k as,
u dis  k1s  2 sign ( s ) (4)
N (s) x Ax  Bu  Fd (9)
where k1 , k2 and k are the positive constant, the sign is the The continuous input u eq is modified to be
traditional signum function and N ( s) is defined by, =− [ + − ] (10)
| |
( )= + (1 − ) (5)

8
Authorized licensed use limited to: Walchand College of Eng. Downloaded on January 09,2023 at 12:06:50 UTC from IEEE Xplore. Restrictions apply.
The proof of the formula in (10) along with its stability injected voltage of the distributed generator in the d-q frame
analysis is given in the Appendix. After incorporating all Ed  DG required , Eq  DG required . These two voltages are used
aforementioned changes, the improved exponential SMC is
to generate a control signal whose magnitude and phase are
ready to be merged with the proposed control scheme that
defined as,
will be explained in the next section.
M control  signal ( Ed2 DG  required  Eq2 DG  required ) / Vdc
III. PROPOSED CONTROL SCHEME (12)
The proposed control scheme is illustrated in Fig. 1 along E
with the model of the distribution system. In the T control  signal tan 1( q  DG  required ) (13)
grid-connected mode, the DGS is tied to the distribution
Ed  DG  required
system. Therefore, the DGS should be operated at a This generated control signal is utilized to operate the
constant-power mode. The power is controlled through the in-phase disposition pulse width modulation (PD-PWM) [19]
injected currents. The power references are converted into to operate the inverter based distributed generation.
current references as,
ª I d  ref º 3 ª Vd  DG  Vq  DG º ª P ref º IV. SIMULATION RESULTS
« » « »« »
«¬ I q  ref »¼ 2(Vd  DG  Vq  DG ) «¬Vq  DG This section shows the results of the proposed control
2 2
Vd  DG »¼ «¬Q ref »¼
scheme of Fig. 1 for the DGS when it is connected to the
(11) distribution system.
where Vd  DG ,Vq  DG are the DGS voltages in the d-q frame.
A. Power System Under Study and Distributed Generator
I d  ref , I q  ref are the required injected currents (current The distributed system under is already depicted in Fig. 1,
references) in the d-q frame. These current references are and its parameters are listed in Table 1. The parameters of the
compared to the feedback currents I d  DG , I q  DG as shown exponential sliding mode controller are given in Table 2.
in the Fig. 1. TABLE I: DISTRIBUTION SYSTEM PARAMETERS
Description of Parameters Values

Rating of the DGS 2.5 MVA

Type of the transformer Step-up

Rating of the transformer 2.5 MVA

Turn’s ration of the transformer 5

Resistance of the tie feeder 0.9 Ω

Inductance of the tie feeder 3 mH

Rated voltage of Distribution system 6.6 kV

Loads at distribution system 50+31.4j

TABLE II: CONTROLLER PARAMETErs


Its value for active Its value for reactive
Parameter
power loop power loop
k 25 25

G0 0.003 0.003
D 0.06 0.06
U 0.5 0.5

O1 1 1

Figure 1. Proposed control scheme with distribution system understudy.


O2 225 405

The current error is processed by the proposed The topology of the distributed generator (DG) with its
exponential SMC formulated in the previous section to typical output voltage is illustrated in Fig. 2-a and Fig. 2-b,
generate the input control law, which represents the required respectively. The typical voltage of the 5-level inverter and

9
Authorized licensed use limited to: Walchand College of Eng. Downloaded on January 09,2023 at 12:06:50 UTC from IEEE Xplore. Restrictions apply.
the voltage after the transformer are illustrated in Fig. 2-b.
The adopted topology of the distributed generator is the
5-level diode clamped inverter of Fig. 2-a, which is
intentionally selected to reduce the injected harmonics
compared to the 2-level or 3-level converter circuits.

Figure 3a. Active power control using proposed exponential SMC scheme.

Figure 3b. Reactive power control using proposed exponential SMC


scheme.
Figure 3. Power control using improved exponential SMC scheme in
Figure 2a. Topology of 5-level diode clamped inverter per phase. grid-connected mode.

The output of the control law for the suggested controller


is the required injected voltages Ed  DG  required and
Eq  DG  required by the distributed generator in the d  q
frame. These voltages are used to generate a control signal
using inverse Park transformation. These voltages are
portrayed in Fig. 4 to show the outputs of the suggested
controller.

Figure 2b. Voltages of distributed generator and inverter per phase.


Figure 2. Topology of the distributed generation with its output voltage
waveforms.

B. Performance of Control Scheme


The performance of the presented control scheme along
with the developed controller is depicted in Fig. 3-a for active
power and in Fig. 3-b for reactive power for some arbitrary
power references shown in red. Figure 4. Output of control law for the proposed controller.

To prove the advantageous performance of the suggested


control scheme, its output is compared to the exponential

10
Authorized licensed use limited to: Walchand College of Eng. Downloaded on January 09,2023 at 12:06:50 UTC from IEEE Xplore. Restrictions apply.
SMC (classical exponential SMC) given in [13-14] and C. Impact of Distributed Generation System on Distribution
formulated in (1-5) for the same parameters defined in Tables System
1 and 2. The active and reactive power tracking performance
is given in Fig. 5-a for active power and Fig. 5-b for reactive The impact of the DGS on the distribution system is
power. Also, the output of the classical exponential sliding exemplified in this section since the DGS injects active and
mode controller is given in Fig. 6. reactive power based on the requirements of the distribution
system. Fig. 7 clarifies this beneficial impact such that the
DGS supplies the loads with its power and the surplus is
injected to the upstream system; in this figure the negative
power means injected power and vice versa. In Fig. 7 for t < 5
s, the injected power of the distributed generation system
PDGS is not enough to supply the whole power required by the
load Pload , then the distribution system supplies power PDS to
the loads as well; meaning that both the distributed
generation system and distribution system supply the loads.
For 5 s < t < 10 s, the PDGS is increased such that the whole
loads are supplied from the distributed generation system and
the surplus is absorbed by the distribution system. In this
Figure 5a. Active power control using classical exponential SMC.
duration, the PDS becomes positive, which means the
upstream system absorbs active power. For t > 10 s, the PDGS
is decreased such that both the distributed generation system
and distribution system are supplying loads. In this duration,
the PDS is reversed to be negative, which means that the
distribution system is supplying active power. A similar
performance can be obtained for the reactive power.
Eventually, the DGS helps the distribution system supply
power, which fetches a better performance for the
distribution system as described in the introduction section of
this paper.

Figure 5b. Reactive power control using classical exponential SMC.


Figure 5. Power control using classical exponential SMC scheme in
grid-connected mode.

Comparing Fig. 3 to Fig. 5 and Fig. 4 to Fig. 6 reveals that


the improved version, presented in this paper, has a better
transient performance with much less overshoot. On the other
hand, the classical exponential SMC shows a slightly less
chattering at some duration especially for the reactive power
performance for time from 20 s to 30 s.

Figure 7. Performance of active power for distribution system, distributed


generation system and loads.

V. CONCLUSION
This paper introduces a tangible improvement of the
exponential SMC to enhance its reaching mode compared to
the classical exponential SMC. Several modifications have
been introduced to the classical exponential SMC in this
research. These modifications have improved the overall
Figure 6. Output of control law for the classical exponential controller in performance of the control scheme and alleviate the
[13-14]. drawbacks of classical exponential SMC such as steady-state

11
Authorized licensed use limited to: Walchand College of Eng. Downloaded on January 09,2023 at 12:06:50 UTC from IEEE Xplore. Restrictions apply.
error and compatibility of the discrete input of the control law operation,” IEEE Transactions on Power Delivery, vol. 23, no.
with power electronics-based systems. The suggested control 2, pp. 850–859, 2008.
scheme is applied on the distributed generation system to [7] A. Elnady, “ Newly developed 1st order sliding mode of power
operate it in a grid-connected mode. The simulation results and voltage control of multilevel inverter based distributed
prove that the improved version outperforms the classical generator”, International Journal of Power and Energy
exponential SMC in terms of reaching mode and overall Systems, ACTA Press, vol. 37, no. 4, 2018.
tracking performance. [8] J. Hu, L. Shang, Y. He, and Z. Q. Zhu,” Direct active and
reactive power regulation of grid-connected DA/AC converter
using sliding mode control approach,” IEEE Trans. on Power
APPENDIX Electronics, vol. 26, no. 1, pp. 210-222, 2011.
[9] L. Shang, D. Sun, and J. Hu,” Sliding mode based direct power
This section shows the proof of the formula given in (10) control of grid connected voltage source inverters under
of Section II. The distribution system of Fig. 1 can be unbalanced network conditions,” Proc. of IET on Power
modeled by a state-space equation as, Electronics, vol. 4, no. 5, pp. 570-579, 2010.
x Ax  Bu  Fd [10] A. M. Bouzid, J. M. Guerrero, A. Cheriti, M. Bouhamida, P.
Sicard, and M. A. Benghanem,” Survey on control of electric
s 1  O2 ³ e, edq I ref dq  I DG  dq power distributed generation systems for microgrid
applications,” Journal of Renewable and Sustainable Energy
To guarantee the stability of the system in the sliding mode, the Reviews, Elsevier, vol. 44, pp. 751-766, 2015.
Lyapunov criterion should be fulfilled. Therefore, the Lyapunov [11] D. H. Phan and S. Huang, “ Super-twisting sliding mode
function is selected to express the Euclidian distance between the control design of three-phase inverter for micro-grid
state variables and the sliding surface defined as, distributed generation systems,” Journal of Control,
1 Automation and Electric Systems, vol. 27, no. 2, pp. 179–188,
V sT s 2016.
2 [12] A. Elnady, and S. Sinan,” An improved second-order sliding
For stability of the system in the sliding mode, the derivative of mode control for the distributed generation system in
the above Lyapunov function should be less than zero, which leads standalone and grid-connected modes,” International
to s 0 that can be rewritten as, Transactions on Electric Energy Systems, vol. 27, no. 11, pp.
̇= ̇+ 2 1–10, 2017.
̇= ̇ − ̇+ [13] C. Fallaha, M. Saad, H. Kanaan, ” Sliding mode control with
2
exponential reaching law applied on a 3 DOF modular robot
̇=− − − + 2 =0 arm,” Proc. of The European Control Conference, pp.
−1
=− [ + − 2 ] 4925-4931, Greece, 2007.
[14] C. Fallaha, M. Saad, H. Y. Kanaan, K. Al-Haddad, ”Sliding
mode robot control with exponential reaching law, “ IEEE
REFERENCES
Trans. on Industrial Electronics, vol. 1, no. 2, pp. 1-9, 2010.
[1] W. El-Khattam, and M. M. A. Salama, “ Distributed [15] S. M. Mozayan, M. Saad, H. Vahedi, H. Fortin-Blanchette, and
Generation Technologies, Definitions and Benefit,” Journal of M. Soltani, ”Sliding mode control of PMSG wind turbine
Electric Power System Research,” vol. 71, pp. 119-128, 2004. based on enhanced exponential reaching law,” IEEE Trans. on
[2] T.Ackermann, G. Andersson, and L. Söder, “ Distirbuted Industrial Electronics, vol. 63, no. 10, pp. 6148-6158, 2016.
generation: a definition,” Electric Power System Research, [16] D. Zhi, L. Xu, B. W. Williams, “ Improved direct power
Elsevier, vol. 57, no. 3, pp. 195-204, 2001. control of grid-connected DC/AC converters,” IEEE Trans. on
[3] G. Pepermansa, J. Driesenb, D. Haeseldonckxc, R. Belmansc, Power Electronics, vol. 24, no. 5, pp. 1280-1292, 2009.
and W. D’haeseleerc, “ Distributed generation: definition, [17] L. Shang, “Sliding-mode-based direct power control of
benefits and issues, “ Energy Policy, Elsevier, vol. 33, no. 6, grid-connected wind-turbine-driven doubly fed induction
pp. 787-798, 2005. generators under unbalanced grid voltage conditions,” IEEE
[4] R. Teodorescu and F. Blaabjerg, “ Proportional-resonant Trans. on Energy Conversion, vol. 27, no. 2, pp. 362-373,
controller, a new breed of controllers suitable for 2012.
grid-connected voltage-source converter,” Proc. of [18] X. Liu, D. Wang, and Z. Peng, “ Predictive direct power
Optimization of Electrical and Electronic Equipment, vol. 3, control for three-phase grid-connected converters with online
pp. 9–14, 2004. parameter identification,” International Transactions on
[5] W. Xuehua, R. Xinbo, B. Chenlei, P. Donghua, and X. Lin, “ Electrical Energy Systems, vol. 27, pp.1-21, 2017.
Design of PI regulator and feedback coefficient of capacitor [19] A. T. Alsakhen, A. M. Qasim, B. Qaisieh, A. Elnady, “
current for grid-connected inverter with an LCL filter in Experimental and simulation analysis for the 5-level diode
discrete-time domain, “ IEEE Energy Conversion Congress clamped inverter,” Proc. of International Conference on
and Exposition, USA, pp. 1657–1626, 2012. Electric Power and Energy Conversion Systems, pp. 1-4, 2015.
[6] F. Gao, and M. R. Iravani,” A control strategy for a distributed
generation unit in grid-connected and autonomous modes of

12
Authorized licensed use limited to: Walchand College of Eng. Downloaded on January 09,2023 at 12:06:50 UTC from IEEE Xplore. Restrictions apply.

You might also like