NMC Junior Installation Manual
NMC Junior Installation Manual
Updates
Authorizer’s
Rev Change Description Change No. Date
Name
1.0 30-Jan-2008 Idan Marko
Doc. Name: NMC Junior Installation Manual Revision: 1.0 Page 4 of 109 pages
Table of Contents
1. General Instructions 7
6. Controller Set-Up 24
6.1 Input/Output Layout 24
6.2 Output Terminals 25
6.2.1 Wiring 25
6.2.2 Output Wiring Example 26
6.3 Input Terminals 27
6.3.1 Wiring 27
6.3.2 Digital Input Examples 28
6.4 PC and Inter-Controller Communication 32
6.4.1 Card Installation 32
6.4.2 Wiring and Controller Setup 33
Doc. Name: NMC Junior Installation Manual Revision: 1.0 Page 5 of 109 pages
9. System Configuration 44
9.1 Device Delay Configuration 44
9.2 Pump Station Configuration 45
9.3 Valve Configuration 46
9.4 Valve Flow Rate 46
9.5 Water Meter 47
9.6 Dosing Channel Configuration 48
9.7 Dosing Configuration 49
9.8 EC/PH Sensor Range 50
9.9 History Resolution 51
9.10 System Nutrigation™ Check 52
9.10.1 Simulation 53
9.10.2 Water Run Time 54
9.10.3 Start/Stop Valve 55
9.11 Data Plug 57
Doc. Name: NMC Junior Installation Manual Revision: 1.0 Page 6 of 109 pages
1. General Instructions
• Installation should be performed by authorized technicians only.
3. General Dimensions
22.5 cm
8.9 in
30.5 cm
12 in 30.5 cm
12 in
12.5 cm
4.9 in
18 cm 25.5 cm
7.1 in 10 in
Type A Type B
Doc. Name: NMC Junior Installation Manual Chapter: Unpacking & Installation Revision: 1.0 Page 10 of 109 pages
Type A Type B
Doc. Name: NMC Junior Installation Manual Chapter: Unpacking & Installation Revision: 1.0 Page 11 of 109 pages
1
Cover by opening
screws x4
3 4
Grounding Flat cable
Rock slightly
Spanner
Doc. Name: NMC Junior Installation Manual Chapter: Unpacking & Installation Revision: 1.0 Page 13 of 109 pages
5
Bracket from slots
Door wing
6
Door from base
Doc. Name: NMC Junior Installation Manual Chapter: Unpacking & Installation Revision: 1.0 Page 14 of 109 pages
7 8
Box on
the wall at
intended
location
Holes x4
according to
markings on
back side
Level
9 10
Exact location Screws 4.5X4
of four holes Flat washer
x4
Holes ø6mm
according to
markings on the
wall
Screwdriver
Anchors
Screw covers x4
Doc. Name: NMC Junior Installation Manual Chapter: Unpacking & Installation Revision: 1.0 Page 15 of 109 pages
11
Door to base
12 13
Flat Grounding
cable
Doc. Name: NMC Junior Installation Manual Chapter: Unpacking & Installation Revision: 1.0 Page 16 of 109 pages
1 2
Bracket Box on the wall at
X4 intended location
3 4
Exact holes Screws 4.5X4
location Flat washer x4
Drill holes
Screwdriver
Anchor
X4
Doc. Name: NMC Junior Installation Manual Chapter: Power Supply Wiring Revision: 1.0 Page 17 of 109 pages
1 2
Gland
Main power screw
Verify grounding
connection <10Ω
3
Feeding
cable into NOTE: Ensure source
Gland cover
voltage matches sticker
(USA/MEX: 115VAC)
USA:
Green =GND
White = Common
Tri-wires feeding cable
Black = Phase
3*1.5 mm2 or
3*16 AWG
Doc. Name: NMC Junior Installation Manual Chapter: Power Supply Wiring Revision: 1.0 Page 18 of 109 pages
4
Cable into gland screw
5
Gland cover
Doc. Name: NMC Junior Installation Manual Chapter: Power Supply Wiring Revision: 1.0 Page 19 of 109 pages
6 7
8
Wire accordingly:
~- Phase
N- Neutral
G- Ground
Screws x3
Doc. Name: NMC Junior Installation Manual Chapter: Power Supply Wiring Revision: 1.0 Page 20 of 109 pages
9 10 11
Connector terminal Feeding cable to
interior box wall Main power
using a tie wrap
Doc. Name: NMC Junior Installation Manual Chapter: Power Supply Wiring Revision: 1.0 Page 21 of 109 pages
Ö Phase to ground
Ö Phase to neutral
3 4
Electrical test
with Multimeter
Result:
24VAC± 10%
Doc. Name: NMC Junior Installation Manual Chapter: Electrical Installation Revision: 1.0 Page 24 of 109 pages
6. Electrical Installation
6.1 Input/Output Layout
Power Supply
Card
Display card
RS232 or RS485
Communication
Card Connector
CPU &
Keyboard
card
24 VAC as shown
1
Relevant screws
2
-Common wires on top row
-Command wires on lower row
Common
Black – Common
Colors - Command
Irrigation
Valves
NOTE: Before switching the controller on, the technician should verify
that there is no short circuit on each output. (Resistance test)
Doc. Name: NMC Junior Installation Manual Chapter: Electrical Installation Revision: 1.0 Page 27 of 109 pages
Input terminals
Common
Digital input #1 to #6
EC sensor input
PH sensor input
+12 VDC
Example A-
Digital input 1: Water meter, Fertilizer meter
Digital input 2: Float switch, Pressure switch
Example B-
Digital input 3: Water Meter with Photo-Diode Output
500Ω Resistor
Doc. Name: NMC Junior Installation Manual Chapter: Electrical Installation Revision: 1.0 Page 30 of 109 pages
Example B-
EC / pH sensors
24VAC±25%,
Transmitter 50-60Hz, 5Watt
Terminals
COM
EC
pH
Example C-
NOTE: Can wire 24VAC source in
Temp/ Humidity sensors Temp./Hum.
same way as on previous page.
Sensor
Measuring Box
Terminals
24VAC
Doc. Name: NMC Junior Installation Manual Chapter: Electrical Installation Revision: 1.0 Page 32 of 109 pages
Com
Rx
Tx
Ground (shield)
DB9
connector
MUX RS-232 Junior 1 Junior 2
Refer to table on page 35
Doc. Name: NMC Junior Installation Manual Chapter: Electrical Installation Revision: 1.0 Page 34 of 109 pages
Option B: RS-485
Ground (shield)
DB9
connector
MUX RS 458 Junior 1 Junior 2
7. Controller Set-Up
7.1 Start-up
Main power
“MENU” on touch
Controller
pad
Doc. Name: NMC Junior Installation Manual Chapter: Controller Set-Up Revision: 1.0 Page 37 of 109 pages
5 6 7
NOTE: In any given menu, you may use arrow and ENTER keys on
touch pad to make a selection or press the corresponding number
and ENTER on touch pad as a short cut.
Doc. Name: NMC Junior Installation Manual Chapter: Controller Set-Up Revision: 1.0 Page 38 of 109 pages
Define devices:
Ö “8. Install” in main menu and press ENTER Ex: Valves 1 and 2,
Ö “1. Device Layout” and press ENTER Technician writes an I/O list
Relays 3 and 4 as Output 3
and 4
1 2 3
4
5 “2. Device List” is read-only
overview list of definitions for
verification
1 2
Doc. Name: NMC Junior Installation Manual Chapter: Controller Set-Up Revision: 1.0 Page 40 of 109 pages
1 2
1 2
1 2
3
Ö “7. Config” in Main Menu
Ö “1. Device Delay Configuration”
Ö Enter delay values. See table below.
1 2
1 2
Ö “3. Valve Configuration”
Ö Allocate pump, main valve and water meter
(Note: If there is more than 1 pump, refer to
NMC-Junior Advanced Settings chapter)
Drippers /
Lateral
Irrigation
valve
Number of Dripper
laterals capacity
Doc. Name: NMC Junior Installation Manual Chapter: System Configuration Procedure Revision: 1.0 Page 47 of 109 pages
1 2
1 2 3
1 2
Doc. Name: NMC Junior Installation Manual Chapter: System Configuration Procedure Revision: 1.0 Page 51 of 109 pages
1 2
3 4
Enter desired amount of fertilizer to inject per Enter desired target EC/PH levels
dosing channel in l/m³ (USA: Gallon/1000 gallon)
Doc. Name: NMC Junior Installation Manual Chapter: System Configuration Procedure Revision: 1.0 Page 53 of 109 pages
9.10.1 Simulation
Use protective equipment, gloves and
goggles when handling fertilizers, acid
and other chemicals!
Ö EC and pH levels.
Ö Results should be relatively close to
desired target.
Ö Deviation of ≤ 0.5 from target is 10 liters of Source Water
allowed.
50 ml of Fertilizer from
each Tank
30 ml ACID
Doc. Name: NMC Junior Installation Manual Chapter: System Configuration Procedure Revision: 1.0 Page 54 of 109 pages
1 2
1 2
4 5
MENU
1 2
Data plug
into terminal
3 4 5
Pump 1
Pump 2
Pump 3
Valve 1
Valve 2
Valve 3
Stability: Time between each pump start
Off Delay: Time delay between switching
each pump Off
4 5
1 2 3
Inject fertilizer according to nominal capacity of pump/measure from fertilizer meter for verification purposes
10.3.3 Method 3- Dosing Pump control =According Fert. meter pulses (For quantitative injection only)
Dosing pump measurement= Fert. Meter
Dosing pump type= Hydraulic
Doc. Name: NMC Junior Installation Manual Chapter: Controller Advanced Settings Revision: 1.0 Page 62 of 109 pages
10.4.1 EC/pH Control- System will inject +/- depending on EC levels, auto-adjust to meet target levels.
Set limits for controller adjustments when levels are too high/low
Ex: If dosing channel 1 is set by the grower to inject 10 liter/m3, the controller auto adjust range
is 5 to 15 liter/m3 in order to meet the EC level.
Set to pause irrigation during Set to pause irrigation during Set to pause dosing during filter
cooling/misting process, then filter flushing process, then flushing process, then resume
resume irrigation resume irrigation irrigation
Valve transition
5 second 5 second
overlap delay
5 sec. 5 sec.
delay overlap
Doc. Name: NMC Junior Installation Manual Chapter: Controller Advanced Settings Revision: 1.0 Page 65 of 109 pages
Baud rate
Hot Screen 1- Active Irrigation Hot Screen 2- Irrigation Process Status Hot Screen 3- Program Status
Hot Screen 4- Water Flow & EC/pH Status Hot Screen 5- Filter Flushing Status Hot Screen 6- Temp. & Hum. Status
Doc. Name: NMC Junior Installation Manual Appx. A- Parts List Revision: 1.0 Page 67 of 109 pages
APPENDIX A
NMC-JUNIOR Parts List
Doc. Name: NMC Junior Installation Manual Appx. A- Parts List Revision: 1.0 Page 68 of 109 pages
8 1
7 2
6 3
5 4
Doc. Name: NMC Junior Installation Manual Appx. A- Parts List Revision: 1.0 Page 69 of 109 pages
* Special request
Doc. Name: NMC Junior Installation Manual Appx. B- Troubleshooting Revision: 1.0 Page 70 of 109 pages
APPENDIX B
Troubleshooting
Doc. Name: NMC Junior Installation Manual Appx. B- Troubleshooting Revision: 1.0 Page 71 of 109 pages
Troubleshooting
1. Display Malfunction- Controller display is off
1 2
Main power source is O.K CPU led is blinking
Yes No
Continue to
Main power next page
Flat cable
connection
is OK
Doc. Name: NMC Junior Installation Manual Appx. B- Troubleshooting Revision: 1.0 Page 72 of 109 pages
Ö Phase to ground
Ö Phase to neutral
Voltage No
is OK Voltage
Continue to
next page
Cable
connection
CAUTION! SHOCK HAZARD! The electrical is OK
installation should be performed by a
qualified electrician only!
Doc. Name: NMC Junior Installation Manual Appx. B- Troubleshooting Revision: 1.0 Page 73 of 109 pages
If fuses 1 and 2
Main power are burnt
Contact CMT
Fuse from technical support
casing
with extra
fuses
provided
F2 F1
NOTE: Make sure that the
same current load is written
on the new fuse.
2. Output Malfunction- Outputs (valves, pumps etc.) are not working although controller show “ON”
Voltage No
is OK Voltage
Continue to
next page
Output wire
connections
and cable
Doc. Name: NMC Junior Installation Manual Appx. B- Troubleshooting Revision: 1.0 Page 75 of 109 pages
If fuses 5 and 7
Main power are burnt
Contact CMT
Fuse from technical support
casing
With extra
fuses
F7
provided
F5
Main power 24VAC is available
Doc. Name: NMC Junior Installation Manual Appx. C- Replacements & Add. Installations Revision: 1.0 Page 76 of 109 pages
APPENDIX C
Replacement and Additional Installations
Doc. Name: NMC Junior Installation Manual Appx. C- Replacements & Add. Installations Revision: 1.0 Page 77 of 109 pages
3 4
Old Card
Screws x2
Doc. Name: NMC Junior Installation Manual Appx. C- Replacements & Add. Installations Revision: 1.0 Page 78 of 109 pages
1 2
3 4
Old Card
Grounding Cable
and Flat Cable
Doc. Name: NMC Junior Installation Manual Appx. C- Replacements & Add. Installations Revision: 1.0 Page 79 of 109 pages
OLD NEW
Jumper
Jumper on LED
on CCFL
Refer to next page if you have a Fluorescent version. Refer to page 81 if you have a LED version.
Doc. Name: NMC Junior Installation Manual Appx. C- Replacements & Add. Installations Revision: 1.0 Page 80 of 109 pages
Jumper
set to
CCFL
No High
Voltage
Disconnect wires
APPENDIX D
Sensor Installation and Definition
Doc. Name: NMC Junior Installation Manual Appx. D- Sensor Installation & Definition Revision: 1.0 Page 83 of 109 pages
24VAC±25%,
Transmitter 50-60Hz, 5Watt
Terminals
COM
EC
pH
Cable type
NOTE: Can wire EC/pH main power source COM/EC/pH- 3x0.5mm2 (20AWG) Shielded
to 24VAC on the output terminals. 24VAC- 2x0.5mm2 (20AWG)
Doc. Name: NMC Junior Installation Manual Appx. D- Sensor Installation & Definition Revision: 1.0 Page 84 of 109 pages
1 2
3
4
5 6 7
MENU
8 9
EC sensor into Calibration
Buffer and immerse for 30
seconds
ENTER
Doc. Name: NMC Junior Installation Manual Appx. D- Sensor Installation & Definition Revision: 1.0 Page 86 of 109 pages
10 11 12
14
13
1 2 3
4 5
1 2 3
MENU
4
5
Calibration in process
ENTER If display says “Buffer Fault”, please
see Troubleshooting Appendix B
Doc. Name: NMC Junior Installation Manual Appx. D- Sensor Installation & Definition Revision: 1.0 Page 89 of 109 pages
1 2 3
ENTER
4 5
1 2 If EC and PH numbers
match on both
screens. If not:
3
Doc. Name: NMC Junior Installation Manual Appx. D- Sensor Installation & Definition Revision: 1.0 Page 91 of 109 pages
Cable type
6x0.5mm2 (20AWG)
Measuring Box
Terminals
24VAC
Doc. Name: NMC Junior Installation Manual Appx. D- Sensor Installation & Definition Revision: 1.0 Page 92 of 109 pages
Fan
Measuring Box
2 3
Sensor Type Measured Values Accuracy Input Range Maximum Cable Length Cable Type
Temperature –
-20°C to 50°C/ -4°F to 122°F 0.3°C/ 0.54°F 30kΩ (kOhm) 500 meters (1640 feet) 2x0.5mm2 (20AWG)
RTS-s
±2% (10%-90%RH)
RH – RHS-10 0 – 100% 0 – 3 VDC 300 meters (985 feet) 3x0.5mm2 (20AWG)
±3.5% (90%-100%RH)
0 to 10mS (old transmitters used
EC 0.05-0.1mS 4 – 20mA 3x0.5mm2 (20AWG)
20mS) ---
Shielded
pH 0 - 14 0.1 4 – 20mA
Doc. Name: NMC Junior Installation Manual Appx. E- Technical Specifications Revision: 1.0 Page 95 of 109 pages
APPENDIX E
Technical Specifications
Doc. Name: NMC Junior Installation Manual Appx. E- Technical Specifications Revision: 1.0 Page 96 of 109 pages
1. Technical Specifications
Small Plastic box Sealed Plastic box
(Indoor installation) (Outdoor installation)
Ambient Conditions Operating temperature range -10 to +600 Celsius (14 to 1400 -10 to +600 Celsius (14 to 1400
Fahrenheit) Fahrenheit)
Storage temperature range -10 to +700 Celsius (14 to 1580 -10 to +700 Celsius (14 to 1580
Fahrenheit) Fahrenheit)
Power Supply
LCD Display Card
Main power
line filter
Main power
terminal
Surge
Suppression
Input
Data plug
socket
Doc. Name: NMC Junior Installation Manual Appx. E- Technical Specifications Revision: 1.0 Page 100 of 109 pages
Specifications
Main Main Max Min Main fuse
voltage frequency voltage voltage
Single 50/60 250 VAC 200 VAC 0.5 Amp
phase
230 VAC,
0.5 Amp
Single 50/60 130 VAC 90 VAC 0.5 Amp
phase
110 VAC,
0.5 Amp
F1 T1
230/115
LINE F2
GND 5V DC
Mains Supply Neutral
Filter 18V 5V To CPU
25VA 12-18V DC
To I/O Circuit
F7 T2
NOTE: 24 VAC- available power for 24VAC
To Valves
peripheral equipment: 50Watt/2A F5
50VA
Doc. Name: NMC Junior Installation Manual Appx. E- Technical Specifications Revision: 1.0 Page 102 of 109 pages
Option B: 115VAC or 230VAC power supply card with external 24VAC power for output devices
Specifications
Main Main Max Min Main fuse
voltage frequency voltage voltage
Single 50/60 250 VAC 200 VAC 0.5 Amp
phase
230 VAC,
0.5 Amp
Single 50/60 130 VAC 90 VAC 0.5 Amp
phase
110 VAC,
0.5 Amp
F1 T1
230/115
LINE F2
GND 5V DC
Mains Supply Neutral
Filter 18V 5V To CPU
25VA 12-18V DC
To I/O Circuit
24VAC P2 24VAC
NOTE: System uses 24VAC External External To Valves
transformer with limit of 6.3Amp (F5).
Doc. Name: NMC Junior Installation Manual Appx. E- Technical Specifications Revision: 1.0 Page 103 of 109 pages
Specifications
Main voltage System fuse
12 – 48 VDC/VAC 2 Amp
P2 F2
5V DC
12V 5V To CPU
12V DC
12V DC To I/O Circuit
To Valves
F5
P3
Doc. Name: NMC Junior Installation Manual Appx. E- Technical Specifications Revision: 1.0 Page 104 of 109 pages
1x pH input 4 - 20 mA
APPENDIX F
Main Menu Tree
Doc. Name: NMC Junior Installation Manual Appx. F- Main Menu Tree Revision: 1.0 Page 106 of 109 pages
1. Program
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10
Irrigation Water Run Dosing External Agitator Selector Filter Flushing Cooling Misting Water
Time Condition Heating
2. Manual
3. Alarm
4. History
4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12
Irrigation Uncompleted Uncompleted Daily Irrigation Auxillary Meter Accumulation Filters Cooling Sensor Event System
Log Irrigation Programs Irrigation Accumultation Accumultation Reset Log Log Log
5. Test
6. Setup
7. Configuration
7.1 7.2 7.3 7.4 7.5 7.6 7.7 7.8 7.9 7.10
Device Delay Pump Station Valve Valve Flow Water Dosing Dosing E/pH Sensor Cooling Misting
Configuration Configuration Configuration Rate Meter Channel Configuration Range Configuration Configuration
Configuration
8. Installation
Controller Warranty
Controller:
Netafim warrants the electronic components of the NMC-Junior Controller on to be free of defects in materials or
workmanship for 2 (two) years from the date of purchase by end user. If a defect is discovered during the applicable
warranty period, Netafim will repair or replace, at its option, the product or the defective part.
Date of commissioning:
Name: Name:
Signature: Signature: