You are on page 1of 68

TECHNICAL SUBMITTAL

T.M.F- SIKA EGYPT


PROJECT:
ZED TOWERS (MEP ROOMS) – SHEIKH ZAYED CITY.
VERSION:
FEBRUARY 10, 2021 / VERSION 1 / SIKA EGYPT / TMF
TABLE OF CONTENTS
1. Company Profile

2. Products' Data Sheets

3. Method Statement for Application & Systems Built-up

4. Test Reports

5. Projects References
COMPANY
PROF
ILE
PRODUCT DATA SHEET
Sikafloor®-161
EPOXY PRIMER , LEVELLING SEALER , INTERMEDIATE LAYER AND MORTAR SCREED

DESCRIPTION SUSTAINABILITY
Sikafloor®-161 is a high grade , high build multipur- ▪ Sikafloor®-161 conforms to the requirements of LEED
pose epoxy resin which can be used as surface sealer EQ Credit 4.2: Low-Emitting Materials: Paints & Coat-
or scratch coat with and without the addition of the ings SCAQMD Method 304-91 VOC Content < 100 g/l
suitable quartz sand or filler .
APPROVALS / CERTIFICATES
USES
▪ CE Marking and Declaration of Performance to
Sikafloor®-161 may only be used by experienced pro- EN 1504-2 - Surface protection product for concrete -
fessionals. Coating
▪ CE Marking and Declaration of Performance to
▪ Priming concrete substrates, cement screeds and EN 13813 - Resin screed material for internal use in
epoxy mortars buildings
▪ For low to medium absorbent substrates ▪ Coating Compatibility DIN EN 13578, Sikafloor®-161 /
▪ Epoxy primer under different bases of flooring sys- -264, Polymer Institut, Test report No. P 6239
tems such as resin epoxy base , fully polyurethane
systems and polyurethane screeds
▪ Intermediate layer underneath multi products such
Floor 92EG , Floor 92SL , Floor 264 , Floor 263SL ,
Floor 359EG , Purcem , Gard rang
▪ May be mixed with sand to the desired consistency
to repair patches or form covings
▪ Binder for levelling layers and mortar screeds
▪ Used as well as for the filling of fissures and joints

CHARACTERISTICS / ADVANTAGES
▪ Good penetration
▪ Good bond strength
▪ Economical and easily applied
▪ Short waiting times
▪ Multi-purpose use

Product Data Sheet


Sikafloor®-161
December 2019, Version 05.01
020811020010000049

1/5
PRODUCT INFORMATION
Composition Epoxy
Packaging
Appearance / Colour Part A brownish-transparent, liquid
Part B transparent, liquid

Shelf life 12 months from date of production


Storage conditions The product must be stored in original, unopened and undamaged sealed
packaging in dry conditions at temperatures between +5 °C and +30 °C. Al-
ways refer to packaging.
Solid content by weight ~100 %
Solid content by volume ~100 %
Volatile organic compound (VOC) con- < 100 g/l
tent

TECHNICAL INFORMATION
Shore D Hardness ~76 (7 days / +23 °C) (DIN 53 505)

Abrasion Resistance Mortar Screed when mixed with Sikadur 506 (C): 48mg loss
( CS 17 / 1000 Cycle / 1000 g )
Compressive Strength Resin: ~ 60 N/mm2 (28 days / +23 C) ( EN 196-1)
Resin: ~ 50 N/mm2 (14 days / +23 C) ( ASTM C579 - Method B )
Mortar Screed when mixed with Sikadur 506 (C):~ 70 N/mm2 (14 days /
+23 C) ( ASTM C579 - Method B )
Tensile Strength in Flexure Resin : > 26 N/mm² (ASTM D790)
Mortar Screed when mixed with Sikadur 506 (C):
>37N/mm² (ASTM D790)
Tensile Strength Resin: ~ 60 N/mm2 (28 days / +23 C) ( ASTM D638 )
Tensile Adhesion Strength > 1.7 N/mm² (failure in concrete) Resin (ASTM D4541 - Pull off)
> 1.6 N/mm² (failure in concrete) Mortar Screed (ISO 4624 - Pull off)

Resistance to Impact Excellent


Chemical Resistance Resistant to wide rang of general chemicals and acids .
For severe conditions , please refer to Sika`s Representative
Temperature Resistance Exposure* Dry heat
Permanent +50 °C
Short-term max. 7 days +80 °C
Short-term max. 12 hours +100 °C
Short-term moist/wet heat* up to +80 °C where exposure is only occasion-
al (steam cleaning etc.).
*No simultaneous chemical and mechanical exposure and only in combination with Sikafloor® systems as a
broadcast system with approx. 3–4 mm thickness.

Product Data Sheet


Sikafloor®-161
December 2019, Version 05.01
020811020010000049

2/5
SYSTEMS
Systems Primer
Low porosity concrete 1 layer of Sikafloor®-161
Primer
Medium porosity concrete 2 layers of Sikafloor®-161
Surface Sealer
Medium / High porosity concrete 1 Scratch coat of Sikafloor®-161
mixed by fine filler ( K4 )
Epoxy screed / repair mortar
(4 – 12 mm layer thickness)
Primer 1 layer of Sikafloor®-161
Screed 1 × Sikafloor®-161 mixedby suitable
sand mixture ( Sikadur 506 )
Note: The largest grain size must be a maximum 1/3 of the finished layer
thickness. Dependent on the grain shape, application temperatures, ag-
gregates and the most suitable mix must be selected and confirmed by
pre-trials.

APPLICATION INFORMATION
Consumption Coating System Product Consumption
Priming (Low Porosity 1 x Sikafloor®-161 1 layer × 0.15 - 0.2
Surface) kg/m²
Priming (Medium 2 x Sikafloor®-161 2 layers × 0.15
Porosity Surface) kg/m²/layer
Surface Sealer (High 1 pbw Sikafloor®-161 : 1 1 layers × 0.3 - 0.35
Porosity Surface) pbw fine filler ( K4 ) kg/m²
Epoxy screed / Repair 1 pbw Sikafloor®-161 : 8 2.2 kg/m²/mm
Mortar (4 –12 mm layer -10 pbw quartz sand
thickness ) (Dur 506)
These figures are theoretical and do not allow for any additional material required due to surface porosity,
surface profile, variations in level or wastage etc.

Ambient Air Temperature +10 °C min. / +30 °C max.


Relative Air Humidity 80 % r.h. max.
Dew Point Beware of condensation.
The substrate and uncured applied floor material must be at least +3 °C
above dew point to reduce the risk of condensation or blooming on the
floor finish. Low temperatures and high humidity conditions increase the
probability of blooming.
Substrate Temperature +10 °C min. / +30 °C max.
Substrate Moisture Content ≤ 6 % pbw moisture content using the Sika® - Tramex meter (at the time of
application).

Note the moisture content must be ≤ 4 % pbw when using the CM meas-
urement or Oven-dry-method. Test method: Sika®-Tramex meter, CM -
measurement or Oven-dry-method. No rising moisture according to ASTM
(Polyethylene-sheet).
Pot Life Temperature Time
+10 °C ~50 minutes
+20 °C ~25 minutes
+30 °C ~15 minutes

Curing Time Before applying non-solvent based products on Sikafloor®-161 allow:

Product Data Sheet


Sikafloor®-161
December 2019, Version 05.01
020811020010000049

3/5
Substrate temperature Minimum Maximum
+10 °C 24 hours 4 days
+20 °C 12 hours 2 days
+30 °C 8 hours 24 hours
Before applying solvent based products on Sikafloor®-161 allow:
Substrate temperature Minimum Maximum
+10 °C 36 hours 6 days
+20 °C 24 hours 4 days
+30 °C 16 hours 2 days
Times are approximate and will be affected by changing ambient condi-
tions particularly temperature and relative humidity.

APPLICATION INSTRUCTIONS APPLICATION


Strictly follow installation procedures as defined in
SUBSTRATE QUALITY / PRE-TREATMENT method statements, application manuals and working
Cementitious substrates (concrete / screed) must be instructions which must always be adjusted to the ac-
structurally sound and of sufficient compressive tual site conditions.
strength (minimum 25 N/mm2) with a minimum Prior to application, confirm substrate moisture con-
tensile strength of 1,5 N/mm2. tent, relative air humidity, dew point, substrate, air
Substrates must be clean, dry and free of all contamin- and product temperatures. If moisture content > 6%
ants such as dirt, oil, grease, coatings, laitance, surface parts by weight, Sikafloor® EpoCem® may be applied
treatments and loose friable material. as a Temporary Moisture Barrier (T.M.B.) system.
Cementitious substrates must be prepared mechanic- Primer
ally using suitable abrasive blast cleaning or planing / Pour mixed Sikafloor®-161 onto the prepared sub-
scarifying equipment to remove cement laitance and strate and apply by brush, roller or squeegee then
achieve an open textured gripping surface profile suit- back roller in two directions at right angles to each
able for the product thickness. other. Ensure a continuous, pore free coat covers the
High spots can be removed by grinding. substrate. If necessary, apply two priming coats.
Weak cementitious substrates must be removed and Confirm primer waiting /overcoating time has been
surface defects such as blow holes and voids must be achieved before applying subsequent products.
fully exposed. Surface Sealer ( Scratch Layer )
Repairs to the substrate, filling of cracks, Spread the mix Sikafloor®-161 with fine filler ( K4 ) us-
blowholes/voids and surface levelling must be carried ing notched trowel as a scratch coat .
out using appropriate products from the Sikafloor®, Epoxy screed / repair mortar
Sikadur® and Sikagard® range of materials. Products Apply the repair or screed mortar onto the “tacky”
must be cured before applying Sikafloor®-161. primer layer . For the screed, use levelling battens and
All dust, loose and friable material must be completely screed rails as necessary. After a short waiting time,
removed from all surfaces before application of the compact and smoothen the mortar with a trowel. For
product and associated system products, preferably by the screed, a teflon coated power float (~20 - 90 rpm)
vacuum extraction equipment. is recommended.

MIXING CLEANING OF EQUIPMENT

Prior to mixing all parts, mix separately part A (resin) Clean all tools and application equipment with Thinner
using a low speed single paddle electric stirrer (300 - C immediately after use. Hardened material can only
400 rpm). Add part B (hardener) to part A and mix it be removed mechanically.
together continuously for 2-3 minutes until a uniform
mix has been achieved. When parts A and B have been FURTHER INFORMATION
mixed , gradually add the appropriate granulometry of
dried quartz sand and if required Extender T. ▪ Sika® Method Statement: Evaluation and Preparation
Mix for a further 2 - 3 minutes until a uniform mix has of Surfaces for Flooring Systems
been achieved. To ensure thorough mixing pour ma- ▪ Sika® Method Statement: Mixing & Application of
terials into another container and mix again to achieve Flooring Systems
a smooth consistent mix. Excessive mixing must be ▪ Sika® Method Statement: Sikafloor®-Cleaning Re-
avoided to minimise air entrainment. During the final gime
mixing stage, scrape down the sides and bottom of the
mixing container with a flat or straight edge trowel at IMPORTANT CONSIDERATIONS
least once to ensure complete mixing.
▪ After application, Sikafloor®-161 must be protected
For more details or clarification , please refer to Sika`s
from damp, condensation and direct water contact
Technical Team .
(rain) for 24 hours.
▪ Construction joints and existing static surface cracks

Product Data Sheet


Sikafloor®-161
December 2019, Version 05.01
020811020010000049

4/5
in substrate require pre-treating with a stripe coat by ECOLOGY, HEALTH AND SAFETY
prefilling and levelling to seal against loss of material
through the joint or cracks before full layer applica- For information and advice on the safe handling, stor-
tion. Use Sikadur® or Sikafloor® resins. age and disposal of chemical products, users shall
▪ The incorrect assessment and treatment of cracks refer to the most recent Safety Data Sheet (SDS) con-
may lead to a reduced service life and reflective taining physical, ecological, toxicological and other
cracking on the surface. safety-related data.
▪ If temporary heating is required, do not use gas, oil,
paraffin or other fossil fuel heaters, these produce DIRECTIVE 2004/42/CE LIMITATION OF EMISSIONS OF
large quantities of both CO2 and H2O water vapour, VOC
which may adversely affect the finish. For heating
use only electric powered warm air blower systems. According to the EU-Directive 2004/42, the maximum
▪ Discard any material over the pot life recommenda- allowed content of VOC (Product category IIA / j type
tions. sb) 500 g/l (Limit 2010) for the ready to use product.
▪ Do not apply on substrates with rising moisture. The maximum content of Sikafloor®-161 is < 500 g/l
▪ Sikafloor®-161 mortar screed is not suitable for fre- VOC for the ready to use product.
quent or permanent contact with water unless
sealed. LEGAL NOTES
▪ Pre-trials must be carried out for mortar mixes to as-
sess suitable aggregate grain size distribution. The information, and, in particular, the recommenda-
▪ For external applications, apply on a falling temper- tions relating to the application and end-use of Sika
ature. If applied during rising temperatures “pin hol- products, are given in good faith based on Sika’s cur-
ing” may occur from rising air. These pinholes can be rent knowledge and experience of the products when
closed after light grinding by applying a scratch coat properly stored, handled and applied under normal
of Sikafloor®-161 mixed with ~3 % of Extender T. conditions in accordance with Sika’s recommenda-
tions. In practice, the differences in materials, sub-
BASIS OF PRODUCT DATA strates and actual site conditions are such that no war-
ranty in respect of merchantability or of fitness for a
All technical data stated in this Product Data Sheet are particular purpose, nor any liability arising out of any
based on laboratory tests. Actual measured data may legal relationship whatsoever, can be inferred either
vary due to circumstances beyond our control. from this information, or from any written recom-
mendations, or from any other advice offered. The
LOCAL RESTRICTIONS user of the product must test the product’s suitability
for the intended application and purpose. Sika re-
Please note that as a result of specific local regulations serves the right to change the properties of its
the performance of this product may vary from coun- products. The proprietary rights of third parties must
try to country. Please consult the local Product Data be observed. All orders are accepted subject to our
Sheet for the exact description of the application current terms of sale and delivery. Users must always
fields. refer to the most recent issue of the local Product
Data Sheet for the product concerned, copies of which
will be supplied on request. It may be necessary to ad-
apt the above disclaimer to specific local laws and reg-
ulations. Any changes to this disclaimer may only be
implemented with permission of Sika® Corporate Legal
in Baar.

Sika Egypt Alexandria Office Cairo Sales office Borg El-Arab Factory
1st Industrial Zone (A) 4, Mihamed Masoud st 222,El-Hegaz St, Heliopolis, 2nd industrial zone block 28
Section #10, Block 13035 Bab Sharki Cairo Borg El Arab City, Alexandria
El Obour City, Egypt Alexandria Egypt Egypt
TEL: +202 44810580 Tel: +203 4244 601/2/3 Tel:+202-26235032 /4 Tel:+203-4592654/1417
FAX: +202 44810459 Mob:+2012-23909922 Mob:+2012-23999700 Mob:+2012-23919291
egy.sika.com Fax: +203 4244 604 Fax:+202-26235637 Fax:+203-4592036

Sikafloor-161-en-EG-(12-2019)-5-1.pdf

Product Data Sheet


Sikafloor®-161
December 2019, Version 05.01
020811020010000049

5/5
PRODUCT DATA SHEET
Sikafloor®-92 EG
HIGH BUILD , SOLVENT FREE , EPOXY RESIN FLOOR COATING

DESCRIPTION zine , Kerosene , Common oils , greases and skydrol


▪ Good resistant to plenty of general and common
Sikafloor 92EG is a two components , solvent free , acids with certain concentrations according to ASTM
epoxy resing floor topping which provides hardwear- D543 such as :
1. Hydrochloride acid 50% ( Slightly color change )
ing , chemical and abrasion resistant flooring system .
2. Sulfuric acid 50% ( Slightly color change )
3. Sodium Hydroxide 50% ( No effect )
USES 4. Petro ( No effect )
5. Acetic acid upto 30% ( No effect )
Sikafloor®-92 EG may only be used by experienced
6. Engine oil ( No effect )
professionals.
7. Kerosene ( No effect )
Sikafloor 92EG has multi properties that lead it to be 8. Sky droll ( No effect )
used in different industrails and different fields such 9. Sugar solution ( No effect )
as : In addtion , it offers good chemical resistance , but as
▪ Food-processing industry in all corrosive situations , a full analysis of operating
▪ Chemical manufacturing plants and exposure conditions is required , followed by ref-
▪ Beverage Production erence to chemical resistance data to ensure product
▪ Pharmaceutical and other medical laboratory fields suitability .
▪ Power stations
▪ Water industry SUSTAINABILITY
▪ Clean rooms
▪ Car parks and workshops APPROVALS / CERTIFICATES
▪ Exhibition halls and showrooms
▪ Demonstration areas and training rooms ▪ Chemical resistance test report from National Re-
▪ Airports , aircraft hangers search Center
▪ Warehouses and storage areas ▪ Sikafloor 92 EG has been tested as per SCAQMD Rule
▪ Areas where hygienic properties and smooth finish is 304-91.
required Result: VOC Content <100 g/L
▪ Areas where highly slipping and temporary wet
where anti - slip finish is needed

CHARACTERISTICS / ADVANTAGES
▪ Easy and fast to apply.
▪ Solvent free, no fire hazard.
▪ Excellent adhesion to concrete substrate
▪ Waterproof due to its water absorbtion properties
▪ Excellent wear and abrasion resistant
▪ Easy to clean
▪ Dust Proof
▪ Slip resistance finish could be provided
▪ Durable , low maintenance costs
▪ Stable against organic solvents`s effect such as Ben-

Product Data Sheet


Sikafloor®-92 EG
November 2019, Version 02.01
020811020010000004

1/4
PRODUCT INFORMATION
Composition Epoxy resin
Packaging Ready for use pre-proportioned units at 15 kg (A+B).
Appearance / Colour Light grey
Other colours on request
Shelf life 12 months from date of production if stored properly in original unopened
packing.
Storage conditions Store in shade away from direct sunlight and in dry conditions.
Density Comp. (A) : ~ 1.53 kg/l
Comp. (B) : ~ 1.02 kg/l
Comp. (A+B) : ~ 1.42 kg/l
Solid content
Solid content by weight 100 %
Solid content by volume 100 %

TECHNICAL INFORMATION
Shore D Hardness ~ 81 (7Days / 23°C ) ( ASTM-D2240)
Abrasion Resistance (CS 10/1000 Cycles/1000 g) (7 days / 23°C) ( ASTM-D4060)
Compressive Strength ~ 84 N/mm2 (7Days ASTM C579 - Method B)
Tensile Strength in Flexure ~ 38 N/mm2 (7Days / 23°C ) ( ASTM-D790)
Tensile Strength ~ 23 N/mm2 (7Days / 23°C ) ( ASTM-D638)
Temperature Resistance Reaction to fire ( Class A )
For Flame Spread Index (FSI) and Smoke Development Index (SDI)
Service Temperature It works in a temperature rang higher than +2°C & lower than +65°C
Water Absorption < 0.1% according to ASTM D570

SYSTEMS
Systems ▪ Primer : one layer primer using one of the proposed solutions below will
be sufficient in case of non porous substrates :
1. Sikafloor 94 ( A+B ) with consumption 150 - 200 gm/m2
2. Sikafloor 161 ( A+B ) with consumption 200 - 250 gm/m2
3. Sikafloor 161 ( A+B+C ) as a scratch layer with consumption 300 gm/m2
where component C is a fine filler
4. Sikafloor 92EG diluted 10% solvent as a self priming with consumption
200 gm/m2
The primer should be left to achieve a tack-free condition before applying
the top coats . A second layer of primer may be required if the substrate is
excessively porous .
▪ Putty : to seal the concrete surface and closing the pin holes , minor
cracks on the floor substrate using Sikafloor 92EG added to fine filler with
consumption approx 100 - 150 gm/m²/ layer depending on substrate
conditions. Maybe a second putty layer be required based on the surface
need .
▪ Coating: 2 X Sikafloor® -92 EG (comp. A+B) with consumption 200 - 250
gm/m2/layer
A slip resistant finish can also be achieved by evenly spreading Sikadur Ag-
gregates on the wet applied first coat of Sikafloor 92EG where it is still
tacky .

Product Data Sheet


Sikafloor®-92 EG
November 2019, Version 02.01
020811020010000004

2/4
APPLICATION INFORMATION
Mixing Ratio Comp(A) : Comp (B) = 4 : 1
Relative Air Humidity 75%.
Substrate Moisture Content < 4%.

Pot Life (20ºC) 45 min.


Curing Time ▪ Can be walked on after : 24 hours
▪ Light mechanical loading permitted after : 3 days
▪ Fully cured after : 7 days

APPLICATION INSTRUCTIONS ▪ Substrate temperature must be 3°C above measured


dew point.
Surface Preparation
▪ The long term durability of any resin floor system is BASIS OF PRODUCT DATA
determined by the adhesive bond achieved between
the flooring material and the sustrate . It is most im- All technical data stated in this Product Data Sheet are
portant therefore that substrates are correctly pre- based on laboratory tests. Actual measured data may
pared prior to application . vary due to circumstances beyond our control.
▪ These should normally have been placed for at least
28 days and have a moisture content of less than 5% LOCAL RESTRICTIONS
.
▪ Floors should be sound , clean and free from con- Please note that as a result of specific local regulations
tamination such as oil , grease , paint splashes , cur- the performance of this product may vary from coun-
ing compounds , laitance and any loose material . try to country. Please consult the local Product Data
▪ Cavities or defects on the surface must be treated Sheet for the exact description of the application
and filled using suitable material ( eg. Mortar from fields.
Sikafloor 161 )
▪ Mechanical means of preparation ( such as light grit ECOLOGY, HEALTH AND SAFETY
blasting , high pressure water jetting or grinding ) are
preferred followed by the removal of dust and other Ecology
loose debris using as industrial vacuum . In a liquid state comp. (A+B) can contaminate water.
Do not dispose of into water or soil but according to
MIXING
local regulations
▪ Stir component (A) thoroughly with an electric stirrer Transport
prior to batching. ▪ Comp. (A): Non-hazardous.
▪ Add component (B) in the correct mix ratio and mix ▪ Comp. (B): Non-hazardous.
for 2-3 minutes at a low speed until a homogeneous Safety precautions
mix is achieved. This product can cause skin irritation to persons with sensit-
ive skin. Always rub barrier cream into hands and exposed
APPLICATION skin before starting work. Wear protective clothing (gloves
and goggles). If Sikafloor®- 92 EG is accidentally splashed into
Brush/Roller In order to achieve an even and uniform the eyes, nose, mouth or throat, flush immediately with
coverage of the surface at least the first application plenty of clean, warm water and seek medical attention
should be carried out by brush. Application by roller, without delay.
especially for the second application, is possible,
whereby the roller should be presses firmly to the sur- Toxicity
face ▪ Comp. (A): Class 4, under the relevant health and
safety codes.
CLEANING OF EQUIPMENT ▪ Comp. (B): Class 4.

Clean all tools and equipment immediately after use LEGAL NOTES
with Colma-Cleaner. Once hardened, the material can
only be removed mechanically. The information, and, in particular, the recommenda-
Wash soiled hands and skin thoroughly with hot soapy tions relating to the application and end-use of Sika
water. products, are given in good faith based on Sika’s cur-
rent knowledge and experience of the products when
IMPORTANT CONSIDERATIONS properly stored, handled and applied under normal
conditions in accordance with Sika’s recommenda-
▪ Cementitious substrate must be at least 3 weeks old. tions. In practice, the differences in materials, sub-
▪ Maximum moisture content of substrate < 4%. strates and actual site conditions are such that no war-
▪ Maximum relative humidity 75%. ranty in respect of merchantability or of fitness for a

Product Data Sheet


Sikafloor®-92 EG
November 2019, Version 02.01
020811020010000004

3/4
particular purpose, nor any liability arising out of any
legal relationship whatsoever, can be inferred either
from this information, or from any written recom-
mendations, or from any other advice offered. The
user of the product must test the product’s suitability
for the intended application and purpose. Sika re-
serves the right to change the properties of its
products. The proprietary rights of third parties must
be observed. All orders are accepted subject to our
current terms of sale and delivery. Users must always
refer to the most recent issue of the local Product
Data Sheet for the product concerned, copies of which
will be supplied on request. It may be necessary to ad-
apt the above disclaimer to specific local laws and reg-
ulations. Any changes to this disclaimer may only be
implemented with permission of Sika® Corporate Legal
in Baar.

Sika Egypt Alexandria Office Cairo Sales office Borg El-Arab Factory
1st Industrial Zone (A) 4, Mihamed Masoud st 222,El-Hegaz St, Heliopolis, 2nd industrial zone block 28
Section #10, Block 13035 Bab Sharki Cairo Borg El Arab City, Alexandria
El Obour City, Egypt Alexandria Egypt Egypt
TEL: +202 44810580 Tel: +203 4244 601/2/3 Tel:+202-26235032 /4 Tel:+203-4592654/1417
FAX: +202 44810459 Mob:+2012-23909922 Mob:+2012-23999700 Mob:+2012-23919291
egy.sika.com Fax: +203 4244 604 Fax:+202-26235637 Fax:+203-4592036

Sikafloor-92EG-en-EG-(11-2019)-2-1.pdf

Product Data Sheet


Sikafloor®-92 EG
November 2019, Version 02.01
020811020010000004

4/4
Safety Data Sheet
July 2018
TRADE NAME : SIKAFLOOR -161 Part (A)
Page 1/4
1.1 Chemical
Low viscosity Epoxy Resin, Solvent free.
Characterization :
1.2 Form: Liquid Color: Light Gray Odor: Characteristic.

2. Physical Data and Safety Data


Density 20º C ~1.60 kg./l
Flash Point N.A
Hazardous decomposition products Combustion will generate: oxides of carbon.
Epoxy monomers, acrid smoke and irritating
Fumes.
Hazardous Reactions Exothermic reaction.
Boiling point ~ 98 º C

3. Safety Precautions
Avoid contact with skin and eyes.

4. Protective measures storage and handling


4.1 Technical protective measures
Storage temperature min/max : +5 : +30 ºC
Keep only in the original container.
Keep container tightly closed.
Keep away from heat and frost.
Avoid dust formation during mixing application.
Keep away from extremes of cold.

4.2 Personal Protective Equipment


Respiratory protection: Protection mask.
Eye Protection : Tightly fitting protective goggles
Hand Protection: Gloves. E.g. rubber , minimum thickness 1.4 mm
Others : N.A

4.3 Industrial Hygiene


Don’t use solvent to clean the skin. Don’t smoke in working area. Remove contaminated
clothing without delay.

4.4 Protection Against Fire and Explosion


N.A.

4.5 Disposal
Arrange for disposal via a licensed waste contractor.
Dispose of containers with care.
Empty packing should be removed by a licensed waste contractor.
Dispose as special waste: mixture of water and hydrocarbons.

N.A = not applicable blank = no data available


TRADE NAME : SIKAFLOOR -161 Part (A)
Page 2/4
5. First Aid:
In case of contact with eyes. Rinse immediately under running water for 15 minutes with
eyelids open. Seek medical advice.
Take off immediately all contaminated clothing. Wash contaminated skin with plenty of soap
and water.
If swallowed, drink copious amounts of water without delay and seek medical advice. Do not
induce vomiting.

6. Transport
Non-hazardous.

7. Toxicology
Non-toxic under relevant health and safety codes.

8. Ecology
Don't release into water supplies or the ground. In cured state the product is not known to cause
an adverse environmental effect. Because of the high pH value the product can be injurious to
aquatic life.

9. Stability and reactivity


Chemical stability
This material is thermally stable when stored and used as directed.

Conditions to avoid:
Evaluated temperatures.

Incompatible Materials:
No information available.

Hazardous decomposition products:


Oxides of carbon, smoke and other toxic fumes.

Hazardous reactions:
No information available.

10. Disposal considerations


Refer to State/Territory Land Waste Management Authority.
TRADE NAME : SIKAFLOOR -161 Part (A) Page 3/4

11. Regulatory information


Poisons Schedule (Aust):
Not applicable.

12. Handling and storage


Handling :
Avoid skin and eye contact.

Storage:
Store in a cool, dry, well-ventilated place and out of direct sunlight. Store away from
incompatible materials described in section 9.
Keep containers closed when not in use – check regularly for leaks.

13. Exposure controls/personal protection


National occupational exposure limits:
No value assigned for this specific material

Biological limit values:


As per the " National Model Regulations for the control of Workplace Hazardous
Substances [NOHSC: 1005 (1994)]" the ingredients in this material do not have a Biological
Limit Allocated.

Engineering measures:
Provide exhaust ventilation where operating conditions may create excessive work place vapor
or mists.

Personal protection equipment:


OVERALLS, SAFETY SHOES, SAFETY GLASSES, GLOVES.

Wear overalls, safety glasses and impervious gloves.

14. Fire-fighting measures:


Specific hazards:
Non – combustible material.

Specific protective precautions and equipment:


Fire fighters to wear self-contained breathing apparatus and suitable protective clothing if risk of
exposure to vapor or products of combustion.
TRADE NAME : SIKAFLOOR -161 Part (A)
Page 4/4
15.
Hazard identification
Hazard Category:
Risk Phrase(s) :
Safety Phrase(s):

16.
Consumption/information on ingredients
Chemical characterization:
Epoxy resin, solvent free pigment.

Hazardous ingredients:

SIKA EGYPT Alex. Sales & Factory


Cairo Sales Office 4, Mohamed Masoud St. ,Beh. Olemby Club
222 El Hegaz St. , Heliopolis P.O.Box 2579 El Sarai + Alexandria
P.O. Box : 2943 El Horria (11361) Cairo Phone : 4244601 /2/3/5
Phone : +202 – 26235032 / 4 Fax : 4244604
Fax : +202 - 26235637 Borg El Arab Factory
Tel. : 4592654 - 4591417 Fax: 4592036
Safety Data Sheet
July 2018
TRADE NAME : SIKAFLOOR -161 Part (B)
Page 1/4
1.1 Chemical
Amine Resin, hardener.
Characterization :
1.2 Form: Liquid Color: Transparent Odor: Ammonical

2. Physical Data and Safety Data


Density 20º C ~1.0 kg./l
Flash Point N.A
Hazardous decomposition products Combustion will generate: oxides of carbon.
Epoxy monomers, acrid smoke and irritating
Fumes.
Hazardous Reactions Exothermic reaction.
Boiling point ~ 98 º C

3. Safety Precautions
Avoid contact with skin and eyes.

4. Protective measures storage and handling


4.1 Technical protective measures
Storage temperature min/max : +5 : +30 ºC
Keep only in the original container.
Keep container tightly closed.
Keep away from heat and frost.
Avoid dust formation during mixing application.
Keep away from extremes of cold.

4.2 Personal Protective Equipment


Respiratory protection: Protection mask.
Eye Protection : Tightly fitting protective goggles
Hand Protection: Gloves. E.g. rubber , minimum thickness 1.4 mm
Others : N.A

4.3 Industrial Hygiene


Don’t use solvent to clean the skin. Don’t smoke in working area. Remove contaminated
clothing without delay.

4.4 Protection Against Fire and Explosion


N.A.

4.5 Disposal
Arrange for disposal via a licensed waste contractor.
Dispose of containers with care.
Empty packing should be removed by a licensed waste contractor.
Dispose as special waste: mixture of water and hydrocarbons.

N.A = not applicable blank = no data available


TRADE NAME : SIKAFLOOR -161 Part (B)
Page 2/4
5. First Aid:
In case of contact with eyes. Rinse immediately under running water for 15 minutes with
eyelids open. Seek medical advice.
Take off immediately all contaminated clothing. Wash contaminated skin with plenty of soap
and water.
If swallowed, drink copious amounts of water without delay and seek medical advice. Do not
induce vomiting.

6. Transport
Non-hazardous.

7. Toxicology
Non-toxic under relevant health and safety codes.

8. Ecology
Don't release into water supplies or the ground. In cured state the product is not known to cause
an adverse environmental effect. Because of the high pH value the product can be injurious to
aquatic life.

9. Stability and reactivity


Chemical stability
This material is thermally stable when stored and used as directed.

Conditions to avoid:
Evaluated temperatures.

Incompatible Materials:
No information available.

Hazardous decomposition products:


Oxides of carbon, smoke and other toxic fumes.

Hazardous reactions:
No information available.

10. Disposal considerations


Refer to State/Territory Land Waste Management Authority.
TRADE NAME : SIKAFLOOR -161 Part (B) Page 3/4

11. Regulatory information


Poisons Schedule (Aust):
Not applicable.

12. Handling and storage


Handling :
Avoid skin and eye contact.

Storage:
Store in a cool, dry, well-ventilated place and out of direct sunlight. Store away from
incompatible materials described in section 9.
Keep containers closed when not in use – check regularly for leaks.

13. Exposure controls/personal protection


National occupational exposure limits:
No value assigned for this specific material

Biological limit values:


As per the " National Model Regulations for the control of Workplace Hazardous
Substances [NOHSC: 1005 (1994)]" the ingredients in this material do not have a Biological
Limit Allocated.

Engineering measures:
Provide exhaust ventilation where operating conditions may create excessive work place vapor
or mists.

Personal protection equipment:


OVERALLS, SAFETY SHOES, SAFETY GLASSES, GLOVES.

Wear overalls, safety glasses and impervious gloves.

14. Fire-fighting measures:


Specific hazards:
Non – combustible material.

Specific protective precautions and equipment:


Fire fighters to wear self-contained breathing apparatus and suitable protective clothing if risk of
exposure to vapor or products of combustion.
TRADE NAME : SIKAFLOOR -161 Part (B)
Page 4/4

15. Hazard identification


Hazard Category:
Risk Phrase(s) :
Safety Phrase(s):

16. Consumption/information on ingredients


Chemical characterization:
Amine Resin, hardener.

Hazardous ingredients:

SIKA EGYPT Alex. Sales & Factory


Cairo Sales Office 4, Mohamed Masoud St. ,Beh. Olemby Club
222 El Hegaz St. , Heliopolis P.O.Box 2579 El Sarai + Alexandria
P.O. Box : 2943 El Horria (11361) Cairo Phone : 4244601 /2/3/5
Phone : +202 – 26235032 / 4 Fax : 4244604
Fax : +202 - 26235637 Borg El Arab Factory
Tel. : 4592654 - 4591417 Fax: 4592036
Safety Data Sheet
July 2018
TRADE NAME : SIKA FLOOR -92 EG PART (A)
Page 1/4
1.1 Chemical
Epoxy resin, solvent free pigment.

1.2 Characterization :
Form: Liquid Color: Light Gray Odor: Characteristic.

2. Physical Data and Safety Data


Specific gravity 20º C ~ 1.53 kg/l
Flash point N.A
Hazardous decomposition products After evaporation of water, combustion will generate:
Oxides of carbon. Acrylic monomers, acrid smoke
And irritating fumes.
Hazardous Reactions Exothermic reaction.

3. Safety Precautions
Accidental splashes to the skin must be washed off with soap and water.
Accidental splashes to the eyes or mucous membrane must be rinsed with clean warm water.

4. Protective measures storage and handling


4.1 Technical protective measures
Storage temperature min/max : +5 : +25 ºC
Keep only in the original container.
Keep container tightly closed.
Keep away from heat and frost.
Avoid dust formation during mixing application.
Keep away from extremes of cold.

4.2 Personal Protective Equipment


Respiratory protection: Protection mask.
Eye Protection : Tightly fitting protective goggles
Hand Protection: Gloves. E.g. rubber , minimum thickness 1.4 mm
Others : Experts always wear the right protective clothing

4.3 Industrial Hygiene


Wash hands before breaks and after works.

4.4 Protection Against Fire and Explosion


N.A.

4.5 Disposal
Dispose as special waste: mixture of water and hydrocarbons.

N.A = not applicable blank = no data available


TRADE NAME : SIKA FLOOR -92 EG PART (A)
Page 2/4
5. First Aid:
In case of contact with eyes. Rinse immediately under running water for 15 minutes with
eyelids open. Seek medical advice.
Take off immediately all contaminated clothing. Wash contaminated skin with plenty of soap
and water.
If swallowed, drink copious amounts of water without delay and seek medical advice. Do not
induce vomiting.

6. Transport
Non-hazardous.

7. Toxicology
Non-toxic under relevant health and safety codes.

8. Ecology
Don't release into water supplies or the ground. In cured state the product is not known to cause
an adverse environmental effect. Because of the high pH value the product can be injurious to
aquatic life.

9. Stability and reactivity


Chemical stability
This material is thermally stable when stored and used as directed.

Conditions to avoid:
Evaluated temperatures.

Incompatible Materials:
No information available.

Hazardous decomposition products:


Oxides of carbon, smoke and other toxic fumes.

Hazardous reactions:
No information available.

10. Disposal considerations


Refer to State/Territory Land Waste Management Authority.
TRADE NAME : SIKA FLOOR -92 EG PART (A) Page 3/4

11. Regulatory information


Poisons Schedule (Aust):
Not applicable.

12. Handling and storage


Handling :
Avoid skin and eye contact.

Storage:
Store in a cool, dry, well-ventilated place and out of direct sunlight. Store away from
incompatible materials described in section 9.
Keep containers closed when not in use – check regularly for leaks.

13. Exposure controls/personal protection


National occupational exposure limits:
No value assigned for this specific material

Biological limit values:


As per the " National Model Regulations for the control of Workplace Hazardous
Substances [NOHSC: 1005 (1994)]" the ingredients in this material do not have a Biological
Limit Allocated.

Engineering measures:
Provide exhaust ventilation where operating conditions may create excessive work place vapor
or mists.

Personal protection equipment:


OVERALLS, SAFETY SHOES, SAFETY GLASSES, GLOVES.

Wear overalls, safety glasses and impervious gloves.

14. Fire-fighting measures:


Specific hazards:
Non - combustible material.

Specific protective precautions and equipment:


Fire fighters to wear self-contained breathing apparatus and suitable protective clothing if risk of
exposure to vapor or products of combustion.
TRADE NAME : SIKA FLOOR -92 EG PART (A)
Page 4/4

15. Hazard identification


Hazard Category:
Risk Phrase(s) :
Safety Phrase(s):

16. Consumption/information on ingredients


Chemical characterization:
Epoxy resin, solvent free pigment.

Hazardous ingredients:

SIKA EGYPT Alex. Sales & Factory


Cairo Sales Office 4, Mohamed Masoud St. ,Beh. Olemby Club
222 El Hegaz St. , Heliopolis P.O.Box 2579 El Sarai + Alexandria
P.O. Box : 2943 El Horria (11361) Cairo Phone : 4244601 /2/3/5
Phone : +202 – 26235032 / 4 Fax : 4244604
Fax : +202 - 26235637 Borg El Arab Factory
Tel. : 4592654 - 4591417 Fax: 4592036
Safety Data Sheet
July 2018
TRADE NAME : SIKA FLOOR -92 EG PART (B)
Page 1/4
1.1 Chemical
Amine Resin, hardener.

1.2 Characterization :
Form: Liquid Color: Clear Odor: Ammonical.

2. Physical Data and Safety Data


Specific gravity 20º C ~ 1.02 kg/l
Flash point N.A
Hazardous decomposition products After evaporation of water, combustion will generate:
Oxides of carbon. Acrylic monomers, acrid smoke
And irritating fumes.
Hazardous Reactions Exothermic reaction.

3. Safety Precautions
Accidental splashes to the skin must be washed off with soap and water.
Accidental splashes to the eyes or mucous membrane must be rinsed with clean warm water.

4. Protective measures storage and handling


4.1 Technical protective measures
Storage temperature min/max : +5 : +25º C
Keep only in the original container.
Keep container tightly closed.
Keep away from heat and frost.
Avoid dust formation during mixing application.
Keep away from extremes of cold.

4.2 Personal Protective Equipment


Respiratory protection: Protection mask.
Eye Protection : Tightly fitting protective goggles
Hand Protection: Gloves. E.g. rubber , minimum thickness 1.4 mm
Others : Experts always wear the right protective clothing

4.3 Industrial Hygiene


Wash hands before breaks and after works.

4.4 Protection Against Fire and Explosion


N.A.

4.5 Disposal
Dispose as special waste: mixture of water and hydrocarbons.

N.A = not applicable blank = no data available


TRADE NAME : SIKA FLOOR -92 EG PART (B)
Page 2/4
5. First Aid:
In case of contact with eyes. Rinse immediately under running water for 15 minutes with
eyelids open. Seek medical advice.
Take off immediately all contaminated clothing. Wash contaminated skin with plenty of soap
and water.
If swallowed, drink copious amounts of water without delay and seek medical advice. Do not
induce vomiting.

6. Transport
Non-hazardous.

7. Toxicology
Non-toxic under relevant health and safety codes.

8. Ecology
Don't release into water supplies or the ground. In cured state the product is not known to cause
an adverse environmental effect. Because of the high pH value the product can be injurious to
aquatic life.

9. Stability and reactivity


Chemical stability
This material is thermally stable when stored and used as directed.

Conditions to avoid:
Evaluated temperatures.

Incompatible Materials:
No information available.

Hazardous decomposition products:


Oxides of carbon, smoke and other toxic fumes.

Hazardous reactions:
No information available.

10. Disposal considerations


Refer to State/Territory Land Waste Management Authority.
TRADE NAME : SIKA FLOOR -92 EG PART (B) Page 3/4

11. Regulatory information


Poisons Schedule (Aust):
Not applicable.

12. Handling and storage


Handling :
Avoid skin and eye contact.

Storage:
Store in a cool, dry, well-ventilated place and out of direct sunlight. Store away from
incompatible materials described in section 9.
Keep containers closed when not in use – check regularly for leaks.

13. Exposure controls/personal protection


National occupational exposure limits:
No value assigned for this specific material

Biological limit values:


As per the " National Model Regulations for the control of Workplace Hazardous
Substances [NOHSC: 1005 (1994)]" the ingredients in this material do not have a Biological
Limit Allocated.

Engineering measures:
Provide exhaust ventilation where operating conditions may create excessive work place vapor
or mists.

Personal protection equipment:


OVERALLS, SAFETY SHOES, SAFETY GLASSES, GLOVES.

Wear overalls, safety glasses and impervious gloves.

14. Fire-fighting measures:


Specific hazards:
Non – combustible material.

Specific protective precautions and equipment:


Fire fighters to wear self-contained breathing apparatus and suitable protective clothing if risk of
exposure to vapor or products of combustion.
TRADE NAME : SIKA FLOOR -92 EG PART (B)
Page 4/4
15.
Hazard identification
Hazard Category:
Risk Phrase(s) :
Safety Phrase(s):

16.
Consumption/information on ingredients
Chemical characterization:
Amine Resin, hardener.

Hazardous ingredients:

SIKA EGYPT Alex. Sales & Factory


Cairo Sales Office 4, Mohamed Masoud St. ,Beh. Olemby Club
222 El Hegaz St. , Heliopolis P.O.Box 2579 El Sarai + Alexandria
P.O. Box : 2943 El Horria (11361) Cairo Phone : 4244601 /2/3/5
Phone : +202 – 26235032 / 4 Fax : 4244604
Fax : +202 - 26235637 Borg El Arab Factory
Tel. : 4592654 - 4591417 Fax: 4592036
METHOD STATEMENT
FLOOR COATING SYSTEM FOR GARAGES

PROJECT: ZED Towers – Sheikh Zayed City


FLOORING DEPARTEMENT

February 2021 /SIKA EGYPT / ALAA HOSSAM


TABLE OF CONTENTS
1. Scope 3
2. Substrate Preparation 3
3. Products 4
4. Built-up section 5
5. SUBSTRATE PREPARATION 5
5.1 SUBSTRATE PRE-REQUISITES 5
5.2 SURFACE PREPARATION 6
6. SUBSTRATE PRIMING 8
6.1 MIXING SIKAFLOOR®-161 8
6.2 APPLICATION OF SIKAFLOOR®-161 AS A PRIMER 9
6.3 SIKAFLOOR®-161 EPOXY MORTAR 9
7. SIKAFLOOR®-92 EG 10
7.1 MIXING 10
7.2 APPLICATION 10
8. TOOLS AND EQUIPMENT 13
9. CLEANING 14
10. ADDITIONAL RECOMMENDATION 14
11. HEALTH AND SAFETY RECOMMENDATION 15
12. LEGAL NOTE 16
1. SCOPE

This method statement describes the step by step procedure for the application of a solvent free, low VOC, epoxy resin floor
different systems

2. SUBSTRATE PREPARATION

Concrete substrates must be mechanically prepared using abrasive blast cleaning to remove cement laitance, existing
coatings and achieve a gripping profile that is clean, dry and free from laitance, dirt, grease, oil and any other form of surface
contamination. Vacuum blasting or similar techniques are ideally suited. High spots must be removed by e.g. grinding.
All dust, loose and friable material must be completely removed from all surfaces before application of the product,
preferably by vacuum.

Weak concrete must be removed and


surface defects such as blowholes and
voids must be fully exposed.

Repairs to the substrate, filling of


blowholes / voids and surface levelling
must be carried out using appropriate
products from the Sikafloor®, SikaDur® and
SikaGard® range of materials. The concrete
or screed substrate must be primed or
levelled in order to achieve an even
surface.

The selected method of preparation will


depend on the surface condition,
Preparation of the substrate:
environmental constraints and availability
Blast cleaning or other mechanical means. E.g. Blastrac, HTC or simi
of services. The method may be selected
based on trial areas, approved by the
Contract Administrator.

Professional equipment is required to


achieve a functioning floor, such as
Scarifier, Grinder, Bush-Hammer
Equipment, Vacuum Shot Blaster, Vacuum
Cleaner and equivalent.
3. PRODUCTS
The system consisting of a primer, Base coat, and a sealer coat as follows:

Sikafloor®-161
Sikafloor® -161 is two-part, solvent free epoxy resin binder for priming,
levelling mortars and screeds

Sikafloor® -92 EG
SIKAFLOOR®-92 EG is a two-part, solvent free, low VOC emission,
economic, solvent-free coloured epoxy resin
4. Built-up section
4.1 Smooth Finish Coating System for Parking Areas:

Coating System Product Consumption


Primer Sikafloor® -161 0.15 kg/m2
Base Layer Epoxy Smoothing Layer (Consumption 0.2 kg/m2
depending on the substrate condition)
Top Coats Sikafloor®-92 EG 0.2 kg/m2
Sikafloor®-92 EG 0.2 kg/m2
5 SUBSTRATE PREPARATION

5.1 SUBSTRATE PRE-REQUISITES


Concrete substrates must be of good condition with a pull off strength and compressive strength as mentioned
below.
Procedure Equipment
Pull off Compressive Strength
• The concrete substrate must be sound.
• Compressive strength minimum 25 N/mm2.
• Pull off strength > 1.5 N/mm2.

Moisture Content
• Substrate moisture content should be < 4% pbw
• If found above, Sikafloor® EpoCem® may be applied as a T.M.B. (temporary
moisture barrier) system.

Air Humidity
• Relative air humidity max. 80%.
• Beware of condensation. The substrate must be at least 3°C above dew point.

Substrate & Ambient Temperature


• Substrate temperature > 15°C. (but at least 3°C above dew point)
• Ambient temperature < 35°C.
5.2 SURFACE PREPARATION
Concrete substrates must be mechanically prepared using abrasive blast cleaning to remove cement laitance,
existing coatings and achieve a gripping profile that is clean, dry and free from laitance, dirt, grease, oil and any
other form of surface contamination. Vacuum blasting or similar techniques are ideally suited.

Procedure Equipment

Vacuum shot blasting


Concrete substrates must be prepared mechanically using abrasive blast
cleaning or scarifying equipment to remove cement laitance and achieve a
profiled open textured.

Cleaning of the surface


All dust, loose and friable material must be completely removed from all
surfaces before application of the product, preferably by brush and
vacuum.

Clean substrate
The surface must be clean, dry and free of all contaminants, e.g. dirt, oils,
grease, coatings and surface treatments, etc.

Surface defects
Substrate defects, such as cracks, blow holes and voids must be repaired
using appropriate products from the SikaTop®, Sika® MonoTop®, Sikafloor®,
Sikadur® or Sikagard® range.

 The selected method of preparation will depend on the surface condition, environmental constraints and
availability of services. The method may be selected on the basis of trial areas, approved by the Contract
Administrator.
6 SUBSTRATE PRIMING SIKAFLOOR®-161
6.1 MIXING SIKAFLOOR®-161
1 2
Prior to mixing, stir Make sure the hardener is
Component A (resin) and fully emptied into the resin
add all of Component B component
(hardener).

3 4
Mix both components Mix both components
thoroughly with a low thoroughly with a low
speed electric stirrer (300 - speed electric stirrer (300 -
400 rpm). 400 rpm).

5 6
Mix both components Mix both components
thoroughly with a low thoroughly with a low
speed electric stirrer (300 - speed electric stirrer (300 -
400 rpm). 400 rpm).
6.2 APPLICATION OF SIKAFLOOR®-161 AS A PRIMER
Make sure, that all substrate requirements are met, such as temperature, moisture content of the prepared
substrate etc. (please refer to section 5). Apply Sikafloor®-161, if the moisture content is below 4%, (test method:
Sika-Tramex, or CM-measurement or Oven-dry-method; no rising moisture according to ASTM (Polyethylene-
sheet)). If the moisture content is above 4%, apply Sikafloor® EpoCem® system as a temporary moisture barrier –
please refer to the PDS).
Apply the mixed material by roller, taking care to ensure good wetting of the substrate but avoiding puddles on the
surface. Work within the pot life of the material (15 minutes at 30°C).
Apply by brush, roller or squeegee and work well into the substrate.
Use the Consumption as given in the System Build up above
Clean all tools and application equipment with SikaThinner C immediately after use.
Hardened / cured material can only be removed mechanically.
7 SIKAFLOOR®-92 EG
7.1 MIXING
Stir separately components A and B of Sikafloor®-92 EG well with an electric mixer.
Then add the full contents of Component B into Component A and mix with a slow speed mixer (300 - 400 rpm) for
at least 2 minutes until a homogeneous mixture is achieved.
Place mixed material into a clean container and mix again shortly (1 minute). Over mixing must be avoided to
minimize air entrainment.

7.2 APPLICATION (BODY COAT)


Apply the mixed material by roller using the consumption given in the System Build up above.
Apply by brush, roller or squeegee and work well into the substrate taking care to ensure
good wetting of the substrate but avoiding puddles on the surface.
Work within the potlife of the material.
Clean all tools and application equipment with Sika Thinner immediately after use.
Hardened and / or cured material can only be removed mechanically.
Freshly applied SIKAFLOOR®-92 EG should be protected from damp, condensation and
water for at least 24 hours.

7.3 APPLICATION (2ND COAT)


Mix the product as given above.
Apply Sikafloor®-92 EG by roller or brush as a topcoat using the consumption given in the 3. System Build-up above.
Clean all tools and application equipment with Sika Thinner immediately after use. Hardened and / or cured
material can only be removed mechanically.
Freshly applied Sikafloor®-92 EG should be protected from damp, condensation and water for at least 24 hours.
Waiting time between coats should not exceed 10 hours - otherwise surface must be abraded before re-coating.
Before exposing to traffic, allow to cure completely for approximately 5 days.
8 TOOLS AND EQUIPMENT
Professional equipment is required to achieve a functioning floor, such as:-
vacuum shot blaster, grinder, scabbler etc.
Procedure Equipment

Preparation of the substrate:


Blast cleaning or other mechanical means.
e.g. Blastrac.

Mixing
Low speed electric stirrer (300 - 400 rpm).

Even application of coating:


Medium to long haired roller or brush.
e.g. Polyplan roller and brush.

Recommended Supplier of Tools:


 PPW-Polyplan-Werkzeuge GmbH, Phone: +49 40/5597260, www.polyplan.com
 TECHNO-Werkzeuge A.E; Vertriebs GmbH Dieselstr. 44; 42579 Heiligenhaus, Phone: 02056) 9846-0 /
Info@Techno-Vertrieb.de; Homepage: http://www.techno-vertrieb.de/
9 CLEANING
To ensure that your Sika flooring system stays in the best of
shape and gives you years of satisfaction the correct cleaning and
maintenance schedule should be used.
When first installed and fully cured your floor should be cleaned
with an appropriate floor cleaner using the most suitable
equipment for the area concerned.

9.1 INITIAL CLEAN


 Firstly, you should sweep the area to remove any loose debris.
 An inspection of the flooring area is mandatory to distinguish areas that require individual treatment such as oil
spillages or scuff marks from shoes or fork lift tyres.
 Application of industrial cleaning detergents to these areas, either as supplied or diluted with water, then given
some agitation and allowed to dwell for 5 to 10 minutes will help to remove these.
 The floor area should then be cleaned using a mild alkaline cleaner or the heavier duty alkaline cleaner.
 Method of and equipment for the cleaning of the area will depend upon size and manpower available.
 On site surveys should be carried out by a professional specialist floor cleaning company. Their representatives
have knowledge of resin products coupled with the correct chemicals and machinery to clean and maintain your
Sikafloor® to the highest levels at all times.

9.2 PRE-USE INSPECTION


 The floor should now be inspected to ensure that it has been cleaned to your required standard and that all soiling
has been removed.

9.3 PRECAUTIONS
 If you will now be placing equipment, storage racking, goods, furniture, filing cabinets etc. on the floor, then
every effort should be taken to minimise surface scratching and marking.
 Dragging of heavy articles across the flooring may damage the surface.
 Fork lift trucks should be driven with care to avoid marking caused by wheel spin or slide.

9.4 LOOKING AFTER YOUR FLOOR


 If the correct cleaning and maintenance schedule is used, the appearance of your floor can be easily maintained.
 For floors with a high gloss finish it is acceptable practice to lay a sacrificial layer of an acrylic polish, which will keep
the high gloss finish, give a hard wearing surface, have the ability to allow for the removal of surface scratches or
blemishes, whilst still incorporating anti-slip properties.
 Once the above action or the decision to leave the floor as supplied has been taken, then the floor will require
regular cleaning with either a neutral or mildly alkaline floor cleaner depending upon the type and level of soiling
encountered.
 If you have decided to use a sacrificial surface polish on your floor then any visible wear can be overlaid with a fresh
coat. However, if continual additions of coats are made then it may be necessary to occasionally remove the polish
and start-a-fresh.
9.5 SPILLAGES
 Spillages of any liquid should be wiped up or absorbed and removed as soon as possible. Not only is this a
responsible action as far as Health and Safety is concerned, it will also help you to keep your floor in good condition.
 Once the spillage is removed the area should be cleaned as usual with your standard floor cleaner.
 If a sacrificial coat has been previously applied the floor should be inspected to see if this remains. If not, it should
be reapplied as soon as possible.

9.6 REMEMBER
Initial clean before use.
 Take care when installing equipment etc.
 Sacrificial polish if required.
 Regular cleaning with the right product and equipment where necessary.
 Clean up spillages.
And your Sikafloor® will give you years of hard wear and still look good.
Sikafloor® - Cleaning Regime with cleaning agents from Kärcher (available on www.sika.com)

9.7 RECOMMENDED SUPPLIER OF CLEANING PRODUCTS


Alfred Kärcher GmbH & Co. KG www.kaercher.com
Wetrok AG www.wetrok.de
JohnsonDiversey www.johnsondiversey.com
Johannes Kiehl KG www.kiehl-group.com

10 ADDITIONAL RECOMMENDATION
Read the Product Data Sheet carefully, particularly the Notes on Applications / Limitations to prevent application
mistakes.

11 HEALTH AND SAFETY RECOMMENDATION


 Ensure sufficient ventilation during application.
 Wear proper safety equipment (gloves, eye goggles, safety boots and protective clothes) during application.
 For more details, refer to Individual Material Safety Data Sheet (available upon request).
12 LEGAL NOTE
The information, and, in particular, the recommendations relating to the application and end-use of Sika products,
are given in good faith based on Sika's current knowledge and experience of the products when properly stored,
handled and applied under normal conditions in accordance with Sika’s recommendations. in practice, the
differences in materials, substrates and actual site conditions are such that no warranty in respect of
merchantability or of fitness for a particular purpose, nor any liability arising out of any legal relationship
whatsoever, can be inferred either from this information, or from any written recommendations, or from any
other advice offered. The user of the product must test the products suitability for the intended application and
purpose. Sika reserves the right to change the properties of its products. The proprietary rights of third parties
must be observed. All orders are accepted subject to our current terms of sale and delivery. Users must always
refer to the most recent issue of the local Product Data Sheet for the product concerned, copies of which will be
supplied on request.
FLOORING
REFERENCES 2013-2018
Startex Factory P&G

Schneider Electric Ismailia Tunnel

Makrouna El Maleka Avenue Mall - Rehab

Low Denisty Ammonium Nitrate Factory Can Factory Regwa

Americana’s New Production Line Jokey For Plastic Cans Manufacture

7
GLOBAL BUT LOCAL PARTNERSHIP

SIKA EGYPT Contact


1st Industrial zone (A) Phone +202 44810580
Section # 10, Block 13035 Fax +202 44810459
El Obour City, Egypt egy.sika.com Buy Online:www.sikaegshop.com