You are on page 1of 2

FMP visited the site on 01.01.2024 and did the survey regarding the said requirement.

The support which FMP-E can provide is as follows:

Pole Street Light / Flood Light / Pole / Cable Support FMP (E)
Near By Area Watt FLP / NFLP Qty. Reason For Replacement
No Well Glass Required Required can provide
1 Main Gate 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
1 Main Gate 150-190W NFLP Flood Light (Pole Mounted) - 1 Not Working One flood light
2 Main Gate 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
3 Gas Header - - - cable - Cable Fault (30 m cable required) -
4 Gas Header 150-190W FLP Flood Light (Pole Mounted) - 2 Not Working One FLP flood light
5 Gas Header 150-190W FLP Flood Light (Pole Mounted) - 2 Not Working One FLP flood light
13 Gas Header 35-50W FLP Well Glass - 1 Not Working One well glass
6 Road 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
7 Road 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
8 Road 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
9 Road 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
10 Road 45-60W NFLP Street Light - 2 low Lumens (Yellow Colour) -
39 Back Side Oil Tank 5 150-190W NFLP Flood Light (Pole Mounted) - 1 Not Working One flood light
40 Oil Tank 6 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
49 Back Side Oil Tank 7 - - - cable - Cable Fault -
45 Back Side Oil Tank 7 - - - cable - Cable Fault -
Cable Fault (35 m cable required ,
47 Back Side Oil Tank 7 - - - cable - -
will cover Pt. 47, 48 & 49))
48 Back Side Oil Tank 7 - - - cable - Cable Fault -
T-2 Back Side Eff Tank 3 150-190W FLP Flood Light (Pole Mounted) - 1 Not Working -
T-1 Opp Eff Tank - - - cable - Cable Fault -
43 Back Side Eff Tank 3 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
44 Back Side Eff Tank 3 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
Low Lumens (Yellow Colour) (45 m
60 Back Side Eff Tank 3 45-60W NFLP Street Light - 1 -
cable required a Flexible cable 10m.)
28 Near Skim Tank 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
29 Near Skim Tank 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
35 Back Side Oil Pump House 120-150W NFLP Flood Light (Pole Mounted) cable - Cable Fault -

Cable Fault (25 m cable required , -


36 Back Side Oil Pump House 120-150W NFLP Flood Light (Pole Mounted) cable -
will cover Pt. 35 & 36)
33 Road New Office To HT 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
34 Road New Office To HT 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
37 Road New Office To HT 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
38 Road New Office To HT 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
11 Separator 150-190W NFLP Flood Light (Pole Mounted) - 1 Not Working One flood light
16 Dozing 150-190W NFLP Flood Light (Pole Mounted) - 1 Found Working -
- ON Office/Control Room 45-60W NFLP Street Light - 7 low Lumens (Yellow Colour) -
- Oil Tank Header 35-50W FLP Well Glass - 2 Not Working 2 No. One well glass
54 Fire Pump House 45-60W NFLP Street Light - 1 low Lumens (Yellow Colour) -
- Fire Pump House 150-190W NFLP Flood Light (Pole Mounted) - 1 Not Working One flood light
Boundary Wall Fire Pump To
55 45-60W NFLP Street Light 1 1 Pole Broken + 1 Street Light -
HT
Boundary Wall Fire Pump To
56
HT
45-60W NFLP Street Light 1 1 Only street-light is required. -

Boundary Wall Fire Pump To


57 45-60W NFLP Street Light 1 1 -
HT
Pole Broken (3 new pole + 60 m
Boundary Wall Fire Pump To
58 45-60W NFLP Street Light 1 1 cable + Syntax box 3 + 3 MCB of 6 -
HT
Amp. Required)
Boundary Wall Fire Pump To
59 45-60W NFLP Street Light 1 1 -
HT
- Dozing / ODP / EDP shed 35-50W FLP Flood Light (Ceiling mounted) - 6 Blinking / Not Working 6 No. well glass

After the support from FMP-E, following is the requirement remains, to fulfill the said requirement, to resolve the issue:

1. NFLP LED Street Lights (45-60W): 31 Nos.


2. FLP Flood Lights (120W): 03 Nos.
3. NFLP Ceiling mounted light fittings (60W) [For fire pump house): 4 Nos.
4. Lighting Poles with Double arm brackets: 04 Nos.
5. Syntax box with MCBs: 04 Nos.
6. Cable (2.5 sqmm x 3C armored copper) along with laying job in soft soil: 200 Mtrs.
7. Cable (1.5 x 2C flexible copper cable): 10 Mtrs.

Submitted for the necessary action.