HD-IEC60364 Wiring current-carrying capacities and watt losses

v1.5
Installation method Method G hor. Single-core cables, spaced horizontally in free air Length cable
Temp. max wire PVC 1 2 3 4 5 6 7 8 9 10 11 12 0.7m
Core material T ambient in encl. [°C] k2: number of circuits Current
# loaded conductors 2 55 - - - - - - - - - - - - 35A
Single- or multi-core k1 = 0,61 - - - - - - - - - - - - Number cores
HD-IEC60364-5-52 ► Table B.52.10 Table B.52.14 n.a. 4
cross section current-carrying cap. current-carrying cap. Current-carrying capacities based on ambient temperature and number of circuits Pv @ 70°C
[mm2] [A] [A] [A] [A] [A] [A] [A] [A] [A] [A] [A] [A] [A] [A] Watt
1.5 25 15 - - - - - - - - - - - - 49.118
2.5 33 20 - - - - - - - - - - - - 29.471
4 46 28 - - - - - - - - - - - - 18.419
6 59 36 - - - - - - - - - - - - 12.279
10 80 49 - - - - - - - - - - - - 7.368
16 108 66 - - - - - - - - - - - - 4.605
25 146 89 - - - - - - - - - - - - 2.947
35 181 110 - - - - - - - - - - - - 2.105
50 219 134 - - - - - - - - - - - - 1.474
70 281 171 - - - - - - - - - - - - 1.053
95 341 208 - - - - - - - - - - - - 0.776
120 396 242 - - - - - - - - - - - - 0.614
150 456 278 - - - - - - - - - - - - 0.491
185 521 318 - - - - - - - - - - - - 0.398
240 615 375 - - - - - - - - - - - - 0.307
300 709 432 - - - - - - - - - - - - 0.246
400 852 520 - - - - - - - - - - - - 0.184
500 982 599 - - - - - - - - - - - - 0.147
630 1138 694 - - - - - - - - - - - - 0.117

In overeenstemming met
IEC61439-1 Tabel H1 o.b.v. HD-IEC60364
IEC60890 Annex B o.b.v. HD-IEC60364
NEN1010 v2015 Bijlage 52.B o.b.v. HD-IEC60364

Current-carrying capacities 1/8


Tables IEC60364
and NEN1010:2015
Spaced in free air Spaced in free air Spaced in free air Spaced in free air Spaced in free air Spaced in free air Spaced in free air Spaced in free air Spaced in free air
Installation method 52.B.1 G horizontaal G horizontaal G horizontaal G horizontaal G horizontaal G horizontaal G horizontaal G horizontaal G horizontaal
Table B.52.10 B.52.10 B.52.12 B.52.12 B.52.9 B.52.9 B.52.11 B.52.11 B.52.13
Temp. max wire 70 70 90 90 105 105 70 70 90
Core material Copper Copper Copper Copper Copper Copper Aluminum Aluminum Aluminum
# loaded conductors 2 3 2 3 2 3 2 3 2
Single- or multi-core Single-core cable Single-core cable Single-core cable Single-core cable Single-core cable Single-core cable Single-core cable Single-core cable Single-core cable
Cross section Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity
[mm2] [A] [A] [A] [A] [A] [A] [A] [A] [A]
1.5 24.5 24.5 30.6 30.6 37 37 18.8 18.8 23.2
2.5 33.4 33.4 41.7 41.7 49 49 25.6 25.6 31.6
4 45.6 45.6 57 57 64 64 35 35 43.2
6 59 59 73.7 73.7 89 89 45.3 45.3 55.9
10 80.2 80.2 100.1 100.1 120 120 61.5 61.5 75.9
16 108.1 108.1 134.8 134.8 157 157 82.9 82.9 102.2
25 146 146 182 182 204 204 112 112 138
35 181 181 226 226 248 248 139 139 172
50 219 219 275 275 304 304 169 169 210
70 281 281 353 353 370 370 217 217 271
95 341 341 430 430 441 441 265 265 332
120 396 396 500 500 505 505 308 308 387
150 456 456 577 577 565 565 356 356 448
185 521 521 661 661 629 629 407 407 515
240 615 615 781 781 704 704 482 482 611
300 709 709 902 902 - - 557 557 708
400 852 852 1085 1085 - - 671 671 856
500 982 982 1253 1253 - - 775 775 991
630 1138 1138 1454 1454 - - 900 900 1154
Tables IEC60364
and NEN1010:2015
Spaced in free air Spaced in free air Spaced in free air Spaced in free air Spaced in free air Spaced in free air Spaced in free air Spaced in free air Spaced in free air
Installation method 52.B.1 G horizontaal E E E E E E E E
Table B.52.13 B.52.10 B.52.10 B.52.12 B.52.12 B.52.9 B.52.9 B.52.11 B.52.11
Temp. max wire 90 70 70 90 90 105 105 70 70
Core material Aluminum Copper Copper Copper Copper Copper Copper Aluminum Aluminum
# loaded conductors 3 2 3 2 3 2 3 2 3
Single- or multi-core Single-core cable Multi-core cable Multi-core cable Multi-core cable Multi-core cable Multi-core cable Multi-core cable Multi-core cable Multi-core cable
Cross section Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity
[mm2] [A] [A] [A] [A] [A] [A] [A] [A] [A]
1.5 23.2 22 18.5 26 23 31 26 - -
2.5 31.6 30 25 36 32 41 35 23 19.5
4 43.2 40 34 49 42 54 46 31 26
6 55.9 51 43 63 54 76 64 39 33
10 75.9 70 60 86 75 104 87 54 46
16 102.2 94 80 115 100 137 115 73 61
25 138 119 101 149 127 179 150 89 78
35 172 148 126 185 158 220 184 111 96
50 210 180 153 225 192 272 228 135 117
70 271 232 196 289 246 333 279 173 150
95 332 282 238 352 298 400 335 210 183
120 387 328 276 410 346 460 385 244 212
150 448 379 319 473 399 526 441 282 245
185 515 434 364 542 456 596 500 322 280
240 611 514 430 641 538 697 584 380 330
300 708 593 497 741 621 - - 439 381
400 856 - - - - - - - -
500 991 - - - - - - - -
630 1154 - - - - - - - -
Tables IEC60364
and NEN1010:2015
Spaced in free air Spaced in free air Touching in free air Touching in free air Touching in free air Touching in free air Touching in free air Touching in free air Touching in free air
Installation method 52.B.1 E E F F F F F F F
Table B.52.13 B.52.13 B.52.10 B.52.10 B.52.12 B.52.12 B.52.9 B.52.9 B.52.11
Temp. max wire 90 90 70 70 90 90 105 105 70
Core material Aluminum Aluminum Copper Copper Copper Copper Copper Copper Aluminum
# loaded conductors 2 3 2 3 2 3 2 3 2
Single- or multi-core Multi-core cable Multi-core cable Single-core cable Single-core cable Single-core cable Single-core cable Single-core cable Single-core cable Single-core cable
Cross section Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity
[mm2] [A] [A] [A] [A] [A] [A] [A] [A] [A]
1.5 - - 22 18.5 27.1 23 31 26 16.5
2.5 28 24 30 25 36.9 31 41 35 22.5
4 38 32 41 34 50.4 42 54 46 30.7
6 49 42 53 45 65.1 55 76 64 39.7
10 67 58 72 61 88.5 74 104 87 53.9
16 91 77 97 82 119.2 100 137 115 72.6
25 108 97 131 110 161 135 179 150 98
35 135 120 162 137 200 169 220 184 122
50 164 146 196 167 242 207 272 228 149
70 211 187 251 216 310 268 333 279 235
95 257 227 304 264 377 328 400 335 273
120 300 263 352 308 437 383 460 385 316
150 346 304 406 356 504 444 526 441 363
185 397 347 463 409 575 510 596 500 430
240 470 409 546 485 679 607 697 584 430
300 543 471 629 561 783 703 - - 497
400 - - 754 656 940 823 - - 600
500 - - 868 749 1083 946 - - 694
630 - - 1005 855 1254 1088 - - 808
Tables IEC60364
and NEN1010:2015
Touching in free air Touching in free air Touching in free air Touching in free air Touching in free air Touching in free air Touching in free air Touching in free air Touching in free air
Installation method 52.B.1 F F F E E E E E E
Table B.52.11 B.52.13 B.52.13 B.52.10 B.52.10 B.52.12 B.52.12 B.52.9 B.52.9
Temp. max wire 70 90 90 70 70 90 90 105 105
Core material Aluminum Aluminum Aluminum Copper Copper Copper Copper Copper Copper
# loaded conductors 3 2 3 2 3 2 3 2 3
Single- or multi-core Single-core cable Single-core cable Single-core cable Multi-core cable Multi-core cable Multi-core cable Multi-core cable Multi-core cable Multi-core cable
Cross section Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity
[mm2] [A] [A] [A] [A] [A] [A] [A] [A] [A]
1.5 14.6 20.3 17.3 22 18.5 26 23 31 26
2.5 19.9 27.7 23.6 30 25 36 32 41 35
4 27.2 37.9 32.3 40 34 49 42 54 46
6 35.2 49 41.7 51 43 63 54 76 64
10 47.8 66.5 56.6 70 60 86 75 104 87
16 64.4 89.6 76.3 94 80 115 100 137 115
25 87 121 103 119 101 149 127 179 150
35 109 150 129 148 126 185 158 220 184
50 133 184 159 180 153 225 192 272 228
70 173 237 206 232 196 289 246 333 279
95 212 289 253 282 238 352 298 400 335
120 247 337 296 328 276 410 346 460 385
150 287 389 343 379 319 473 399 526 441
185 330 447 395 434 364 542 456 596 500
240 392 530 471 514 430 641 538 697 584
300 455 613 547 593 497 741 621 - -
400 552 740 663 - - - - - -
500 640 856 770 - - - - - -
630 746 996 899 - - - - - -
Tables IEC60364
and NEN1010:2015
Touching in free air Touching in free air Touching in free air Touching in free air Cable trunking Cable trunking Cable trunking Cable trunking Cable trunking
Installation method 52.B.1 E E E E B1 B1 B1 B1 B1
Table B.52.11 B.52.11 B.52.13 B.52.13 B.52.2 B.52.4 B.52.3 B.52.5 B.52.2
Temp. max wire 70 70 90 90 70 70 90 90 70
Core material Aluminum Aluminum Aluminum Aluminum Copper Copper Copper Copper Aluminum
# loaded conductors 2 3 2 3 2 3 2 3 2
Single- or multi-core Multi-core cable Multi-core cable Multi-core cable Multi-core cable Single-core cable Single-core cable Single-core cable Single-core cable Single-core cable
Cross section Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity
[mm2] [A] [A] [A] [A] [A] [A] [A] [A] [A]
1.5 - - - - 17.5 15.5 23 20 -
2.5 23 19.5 28 24 24 21 31 28 18.5
4 31 26 38 32 32 28 42 37 25
6 39 33 49 42 41 36 54 48 32
10 54 46 67 58 57 50 75 66 44
16 73 61 91 77 76 68 100 88 60
25 89 78 108 97 101 89 133 117 79
35 111 96 135 120 125 110 164 144 97
50 135 117 164 146 151 134 198 175 118
70 173 150 211 187 192 171 253 222 150
95 210 183 257 227 232 207 306 269 181
120 244 212 300 263 269 239 354 312 210
150 282 245 346 304 300 262 393 342 234
185 322 280 397 347 341 296 449 384 266
240 380 330 470 409 400 346 528 450 312
300 439 381 543 471 458 394 603 514 358
400 - - - - - - - - -
500 - - - - - - - - -
630 - - - - - - - - -
Tables IEC60364
and NEN1010:2015
Cable trunking Cable trunking Cable trunking Cable trunking Cable trunking Cable trunking Cable trunking Cable trunking Cable trunking
Installation method 52.B.1 B1 B1 B1 B2 B2 B2 B2 B2 B2
Table B.52.4 B.52.3 B.52.5 B.52.2 B.52.4 B.52.3 B.52.5 B.52.2 B.52.4
Temp. max wire 70 90 90 70 70 90 90 70 70
Core material Aluminum Aluminum Aluminum Copper Copper Copper Copper Aluminum Aluminum
# loaded conductors 3 2 3 2 3 2 3 2 3
Single- or multi-core Single-core cable Single-core cable Single-core cable Multi-core cable Multi-core cable Multi-core cable Multi-core cable Multi-core cable Multi-core cable
Cross section Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity Current capacity
[mm2] [A] [A] [A] [A] [A] [A] [A] [A] [A]
1.5 - - - 16.5 15 22 19.5 - -
2.5 16.5 25 22 23 20 30 26 17.5 15.5
4 22 33 29 30 27 40 35 24 21
6 28 43 38 38 34 51 44 30 27
10 39 59 52 52 46 69 60 41 36
16 53 79 71 69 62 91 80 54 48
25 70 105 93 90 80 119 105 71 62
35 86 130 116 111 99 146 128 86 77
50 104 157 140 133 118 175 154 104 92
70 133 200 179 168 149 221 194 131 116
95 161 242 217 201 179 265 233 157 139
120 186 281 251 232 206 305 268 181 160
150 204 307 267 258 225 334 300 201 176
185 230 351 300 294 255 384 340 230 199
240 269 412 351 344 297 459 398 269 232
300 306 471 402 394 339 532 455 308 265
400 - - - - - - - - -
500 - - - - - - - - -
630 - - - - - - - - -
Tables IEC60364
and NEN1010:2015
Cable trunking Cable trunking
Installation method 52.B.1 B2 B2
Table B.52.3 B.52.5
Temp. max wire 90 90
Core material Aluminum Aluminum
# loaded conductors 2 3
Single- or multi-core Multi-core cable Multi-core cable
Cross section Current capacity Current capacity
[mm2] [A] [A]
1.5 - -
2.5 23 21
4 31 28
6 40 35
10 54 48
16 72 64
25 94 84
35 115 103
50 138 124
70 175 156
95 210 188
120 242 216
150 261 240
185 300 272
240 358 318
300 415 364
400 - -
500 - -
630 - -