Indoor environment and productivity

in office environment

summary of the key contents of REHVA


Guidebook no 6

Olli Seppänen, professor


Helsinki University of Technology
Federation of European Heating and Air-
conditioning Associations

Federation of European Heating, Ventilation and Air-conditioning Associations


Federation of European Heating, Ventilation
and Air-conditioning Associations

Address:  www.rehva.eu
Rue Washington 40  info@rehva.eu
1050 Brussels  Tel: +32 2 514 11 71
 Fax: +32 2 512 90 62
Belgium

Federation of European Heating, Ventilation and Air-conditioning Associations


Use of REHVA Guidebook Power
Point Presentations
• This Power Point Presentation can be freely used for
training purposes by REHVA members.
• It is prepared by the main author to the REHVA
Guidebook.
• Please refer the original author always when making
the presentation.
• Inform REHVA secretariat each time the presentation
is used: info@rehva.eu

Federation of European Heating, Ventilation and Air-conditioning Associations


Federation of
European Heating
and
Air-conditioning
Associations
(REHVA)‫‏‬
=
Professional
organization with
28 member
countries
representing more
than 100 000 HVAC
experts in Europe

Federation of European Heating, Ventilation and Air-conditioning Associations


Procedure to include indoor environment in
calculations is needed

• for engineering analysis to compare


alternative technical systems
• to convince the employers to invest on
better indoor environment
• to motivate building owners to invest on
better indoor environment and
• to justify higher rents of high quality
leased buildings

Federation of European Heating, Ventilation and Air-conditioning Associations


Economic calculations in design and
operations stage should include

• investment cost
– euros per occupant/employee
• operation cost
– including energy
• productivity and health
benefits/decrements

Federation of European Heating, Ventilation and Air-conditioning Associations


From improved building
performance to benefits
Building design and
operation

Indoor Human Value of


air Benefits the
responses benefits
quality

Federation of European Heating, Ventilation and Air-conditioning Associations


Economic benefits as a driving force
for better IEQ
Owner
occupied
building

Investment
Economic
benefits
Better IEQ

Better productivity
Improved
performance
Less sick leave
Less complaints

Federation of European Heating, Ventilation and Air-conditioning Associations


Simplified definition of
productivity

Output
Output
Productivity
Productivity==
Input
Input

Federation of European Heating, Ventilation and Air-conditioning Associations


Productivity, building
investment and cost

Productivity
Productivity==

Work
Workperformance
performance
Investment
Investmentand
andoperational
operationalcost
cost

Federation of European Heating, Ventilation and Air-conditioning Associations


Factors affecting productivity
(Clements-Croome 2000)‫‏‬

Relationships Leadership
SOCIAL
between ORGANISATION Organisational
people ENVIRONMENT structure

PRODUCTIVITY

Work, career
Home/work
relationship PERSONAL ENVIRONMENT
Commitment CHARACTERISTICS Indoor
to work Environment

Federation of European Heating, Ventilation and Air-conditioning Associations


IAQ-factors with quantitative
effect on productivity
• Ventilation and sick leave
• Ventilation and work performance
• Temperature and performance
• Perceived indoor air quality and task
performance
• SBS-symptoms and performance

Federation of European Heating, Ventilation and Air-conditioning Associations


Ventilation rates affect
• Concentration of pollutants from indoor sources
and outdoor sources
• Pollutants from air handling system itself
• Humidity etc.

• Perceived air quality


• Sick building syndrome symptoms
• Dryness etc.

What about objectively measured sick


leave and performance ?
Federation of European Heating, Ventilation and Air-conditioning Associations
Ventilation rates and sick leave

Federation of European Heating, Ventilation and Air-conditioning Associations


An example of data on ventilation and
short term sick leave
(Milton et al. 2000)‫‏‬

Monthly short term sick leave


Relative risk for short term
sick leave was 1.53 with 1.96 %
2.0
lower estimated ventilation 1.2 – 1.9 days
rate of 12 L/s compared per year
1.5
with ventilation rate of 1.16 %
24 L/s 1.0

0.5

0.0
12 L/s 24 L/s per person

Federation of European Heating, Ventilation and Air-conditioning Associations


Short term sick leave or illness inflicted by infectious
diseases vs. ventilation rate (ach)
(Adapted to Wells-Riley-model)‫‏‬
Drinka (1996), illness in nursing home
Brundage (1988), illness in barracks, all years
Particle concentration model
Brundage (1988), illness in barracks, 1983 data
Milton (2000), sick leave in offices

1.0
0.8
0.6
0.4
0.2
0
0 1 2 3 4
Ventilation Rate (1/h)‫‏‬
Federation of European Heating, Ventilation and Air-conditioning Associations
Ventilation rates and
performance

Federation of European Heating, Ventilation and Air-conditioning Associations


Meta analysis of studies on
ventilation rate and performance

- six studies in office environment


- two studies in laboratory
- one in school
- some with multiple ventilation rates

Federation of European Heating, Ventilation and Air-conditioning Associations


Example of results from a laboratory study
(Wargocki et al. 2000)

Units completed per hour


258
Characters typed per min

155
Text typing Addition
154 (R² = 0.99, P < 0.03) 255 (R² = 0.97, P < 0.06)
153 252
152 249
151 246
150 243
149 240

0 5 10 15 20 25 30 0 5 10 15 20 25 30
Ventilation rate, Ventilation rate,
L/s per person L/s per person

Increaseof
Increase of ventilation
ventilation rates
rates 3,
3, 10,
10, 30
30 L/s
L/s per
per person
personimproved
improved performance
performance
of office
of office tasks
tasks in
in simulated
simulated office
office environment
environment

Federation of European Heating, Ventilation and Air-conditioning Associations


Increase of performance (%) per in increase
in ventilation rate of 10 L/s-person
reported in each study
6 Sample size
composite weighted
weighted
95% CI of composite weighted

Sample size 90% CI of composite weighted


4

and sample size weighted


outcome
weighted unweighted
2
0

90% CI
Unweighted
-2

95% CI
-4

0 10 20 30 40 50
Ventilation Rate (L/s-person)

Federation of European Heating, Ventilation and Air-conditioning Associations


Relative performance vs. ventilation rate in L/s-
person in relation to 6.5 L/s-person
1.05
Relative Performance

Weighted by
1.04 sample size

1.03

1.02 Unweighted

1.01 Weighted by sample size


and outcome relevance

1.00
0 10 20 30 40 50 60
Ventilation Rate (L/s-person)‫‏‬
Federation of European Heating, Ventilation and Air-conditioning Associations
With balancing of air ventilation rates to
better IAQ and energy efficiency
An office building in Helsinki
70
Ventilation rate l/s, person

60

50
Minimun Good ventilation rate
40 ventilation 20 l/s, person
rate
30 10 l/s, person

20

10

0
1 26 51 76 101 126 151 176 201 226 251 276 301 326
Room number (Tuomainen ym. 2003)‫‏‬
Federation of European Heating, Ventilation and Air-conditioning Associations
Performance and perceived
air quality (PAQ)‫‏‬
• Perceived air quality has been used close
to hundred years as a criteria of air quality
and ventilation rates – also in many
standards
• PAQ is affected by pollutants, adaptation,
ventilation and other environmental
parameters (oC, RH)
• PAQ is used also as an indicator of air
quality for performance

Federation of European Heating, Ventilation and Air-conditioning Associations


Performance in text-typing vs. perceived air
quality in percentage of dissatisfied (PD%)-
IAQ can be improved either by removal sources or by incresing
ventialtion reates
Relative Performance

0.8% per 10% in PAQ


1.00
wall-to-wall carpet
(poor quality)‫‏‬
0.98
R² = 0.6012
0.96
Display
terminal Building
0.94 materials

0 20 40 60 80
Perceived air quality, % dissatisfied

Federation of European Heating, Ventilation and Air-conditioning Associations


Temperature and performance

Federation of European Heating, Ventilation and Air-conditioning Associations


Effects of Temperature

• High temperature
– causes discomfort
– increases heart attacks and mortality
• Low temperature
– causes discomfort
– decreases the dexterity of fingers
• High temperature in the winter
– increases SBS-symptoms
– deteriorated perceived indoor air
quality
– increases the complaint on dry air

What about performance?


Federation of European Heating, Ventilation and Air-conditioning Associations
Meta analysis of studies on temperature
and performance in office work
(Seppänen, Fisk, Lei 2005)

• 24 studies with objectively measured


performance and temperature – 148 data
points
• All included studies were controlled for
– work environment (ventilation, humidity, work load
etc.)‫‏‬
– clothing
– personal factors

Federation of European Heating, Ventilation and Air-conditioning Associations


Change in performance in % per 1 oC
increase in temperature
20
reported in each study
composite weighted
90% CI of composite weighted
sample size weighted
unweighted
10
Delta P%/C

0
-10

15 20 25 30 35

Temperature (C)
Seppanen et al. 2005

Federation of European Heating, Ventilation and Air-conditioning Associations


Relative performance vs. temperature compared
to the maximum
95% confidence range 20-24 oC
1.00
Relative Performance

0.95
Unweighted
0.90
Weighted by sample size
0.85 and outcome relevance

0.80 Weighted by sample size

0.75
15 20 25 30 35
Temperature (°C)‫‏‬
Federation of European Heating, Ventilation and Air-conditioning Associations
APPLICATION OF THE
PROCEDURE IN ENGINEERING
ANALYSIS

Federation of European Heating, Ventilation and Air-conditioning Associations


Example 1
Feasibility of night-time
ventilative cooling

Cool night time outdoor air is


used to cool down the
building during night
Fans use energy but day-time indoor
temperature is reduced and work
performance improved
Federation of European Heating, Ventilation and Air-conditioning Associations
Effect of night time ventilative cooling
on room temperatures
30
Temperature, °C

28

26

24

22

20 Room air - no night time v.


Room surfaces- no night time v.
18
Outdoor air
Room air – with night time v.
16
Room surfaces – with night time v.
14
00:00 06:00 12:00 18:00 00:00
Aika
Kolokotroni et al. 2001
Federation of European Heating, Ventilation and Air-conditioning Associations
Data used in the analysis
Extra operation time of fans 10 h/night
• Power use 2.5 kW
per m3/s
1.00
• Cost of electricity
0.5 – 0.20 c/kWh 0.95

Relative Performance
• Value of the work 0.90 Unweighted
25 €/h Weighted by sample size
0.85
• Effect of and outcome relevance
r
o
s
lin
te
h
u
S

temperature on 0.80 Weighted by sample size


performance at
office work 0.75
15 20 25 30 35
Temperature (°C)

Federation of European Heating, Ventilation and Air-conditioning Associations


Effect on temperatures and lost work time
8-9 9-10 10-11 11-12 13-14 14-15 15-16 16-17 8-17

t out 19 21.5 24.5 26.5 26.8 27.0 27.1 27.3

Without night-time cooling


t op 27.1 27.2 27.6 27.8 27.8 27.9 27.9 27.9

lost 2.5 2.9 2.9 3.0 3.0 3.1 3.1 3.1 23.4
min

With night-time cooling


t op 23.5 23.6 24 24.5 25.9 26.1 26.1 26

lostmi .2 .3 .4 .6 1.1 1.2 1.2 1.2 6.2


n
Less lost work time, min per day 17.2

Federation of European Heating, Ventilation and Air-conditioning Associations


Cost effectiveness of night- time
ventilative cooling
(4 ach, 8 h/night, 2.5 kW/m3s-1)‫‏‬

Cost of Use of electricity Additional Increase in Benefit to


electricity during night cost of productivity, € cost ratio
(8 h)‫‏‬ electricity 23.4-6.2 =17.2
min/d, 25 €/h
c/kWh kWh/d $/d

5 1.84 0.09 7.15 79


10 1.84 0.18 7.15 40
15 1.84 0.28 7.15 26
20 1.84 0.37 7.15 19

(REHVA Guidebook no 6, 2006)‫‏‬

Federation of European Heating, Ventilation and Air-conditioning Associations


Example 2

Cost effectiveness of air conditioning,


extended operation time of
ventilation, and increased supplu air
flow rate

Federation of European Heating, Ventilation and Air-conditioning Associations


Simulated case study
• Building description
– concrete construction
– private office of 15 m2
– 2 m2 window facing south
– venetian blinds between the glazing
• Basic case
– ventilation 2 L/sm2
– no air conditioning
– operation 10 h per day
• Improved cases compared with IDA/ICE
simulation program
– central cooling 20 W/m2
– operation time 24 h per day
– supply air flow rate 4 L/sm2
Federation of European Heating, Ventilation and Air-conditioning Associations
Costs and benefits of air conditioning and
Cost of office environment
extended operation time
(additional energy, investment, productivity loss)
Annual cost, euros/person
800
700
600
500
400
300
200
100
0
Basic case: 20 W/m², 2 L/sm², 4 L/sm², 4 L/sm²,
2 L/sm², 10 h/d 24 h/d 24 h/d 24 h/d,
10 h/d 20 W/m²
Compared cases

energy investment lost productivity total


Federation of European Heating, Ventilation and Air-conditioning Associations
Example 3

Economizer System Evaluation = use


more outdoor air and less return air
when feasible

Federation of European Heating, Ventilation and Air-conditioning Associations


Economizer Systems
Modulate Outdoor Air (OA) Supply
Purpose
• reduce HVAC energy
100% OA
• maintain minimum Min. OA
vent. rate

% Outdoor Air
Method
• use outdoor air for
cooling when less
expensive than
mechanical cooling
Usage in the USA
• common in large
HVAC No economizer
• considered too
expensive for small
HVAC 25 oC
Outdoor Temperature

Federation of European Heating, Ventilation and Air-conditioning Associations


Approach – simulation of a case
building
Energy & Ventilation Rate Modeling
• 2000 m2 office building in Washington,
DC, VAV HVAC, with and w/o economizer
– Used DOE 2 energy simulation model Milton (2000), sick leave in offices
Brundage (1988), illness in barracks, all years
– Hourly ventilation rates for year

Illness or sick leave prevalence relative


Brundage (1988), illness in barracks, 1983 data

to prevalence with no ventilation


Drinka (1996), illness in nursing home
Particle concentration model
– Energy use for year 1

Economic analyses 0.8

0.6
• energy cost savings from DOE-2 model 0.4

• apply absence - vent. rate model 0.2

• value of absence based on salary & 0


0 1 2 3 4
Ventilation rate (h-1)
benefits

Federation of European Heating, Ventilation and Air-conditioning Associations


Results
Estimated Annual Benefits of Economizer
M
ini
m u
m Savi
n gsf
rom Econo
m i
zer
V
en
tR a
t
Ee
n
er
gyCo st
Sa
vi
n g
s Si
ck Lea
ve Sa
ving
s
L
/sp
erpe
rsn €
o p
erwor
k er D ay s € perw o
rke
r
per
wo
rk er
1
0 26 0.9–1.1 €1
8 0-€
- ‫‏‬2
20
2
0 31 0.4–0.5 €‫‏‬83--€97

Estimated savings from reduced illness-related


absence is 3 - 8 times energy cost savings

Federation of European Heating, Ventilation and Air-conditioning Associations


Economic benefits as driving force
Leased building

Higher market Building owner


value of
building
Investment

Higher user Better IAQ


satisfaction Higher
rent
Better
productivity
Less sick leave
Less complaints

Benefits to
employer
Federation of European Heating, Ventilation and Air-conditioning Associations
Conclusion
• Value of productivity and health improvements
should be included in the life cycle calculations
• These costs are significant, and in same oder of
magnitude or higher than the energy cost of
buildings
• Most IAQ improvements are very cost effective
when producitivity and health benefits are
included
• Qualitative data is not adequate between IAQ and
human responses – more quantitative data is
needed

Federation of European Heating, Ventilation and Air-conditioning Associations