NYA (Cu/PVC)

60227 IEC 05
300/500 V
0.5 ~ 1 mm 2

SNI 04-6629.3 - 2006


Permanent installation in conduit or exposed wiring in dry location.

Nominal Cable Weight CONDUCTOR INSULATION Current Carrying Short Circuit


Cross Section Capacity Current at
Overal Nominal DC Insulation
Area at 30ºC 1 Sec
Diameter Cross Section Resistant at Resistance at
Area 20 C
o
70 C
o In Pipe In Air

mm 2
(mm) kg/km mm 2
Max. (Ω/km) Min. (MΩ.km) Max. A Max. A Max. (kA)

0.5 2.1 9 0.5 36 0.015 2.5 - 0.07


0.75 2.2 12 0.75 24.5 0.012 7 15 0.10
1.0 2.4 16 1 18.1 0.011 11 19 0.13
NYA (Cu/PVC)
60227 IEC 01
450/750 V
1.5 ~ 10 mm2
SNI 04-6629.3 - 2006
Permanent installation in conduit or exposed wiring in dry location.

CONSTRUCTION ELECTRICAL DATA


NominalDATA Cable CONDUCTOR INSULATION Current Carrying Short Circuit
Cross Section Weight Capacity Current at
Overal Nominal DC Insulation
Area at 30 C
o
1 Sec
Diameter Cross Section Resistant at Resistance at
Area 20 C
o
70 C
o In Pipe In Air

mm 2
(mm) kg/km mm 2
Max. (Ω/km) Min. (MΩ.km) Max. A Max. A Max. (kA)

1.5 2.9 20.27 1.5 12.1 0.011 15 24 0.17


2.5 3.4 32.05 2.5 7.41 0.010 19 32 0.29
4 3.9 47.79 4 4.61 0.0085 25 42 0.46
6 4.4 67.52 6 3.08 0.0007 33 54 0.69
10 5.6 111.79 10 1.83 0.00065 45 73 1.15
16
25
35
NYAF (Cu/PVC-f)
60227 IEC 02
450/750 V
1.5 ~ 120 mm 2

SNI 04-6629.3 - 2006


Permanent installation in conduit or exposed wiring in dry location.

ELECTRICAL DATA
CONSTRUCTION DATA CONDUCTOR INSULATION Current Carrying
Capacity
Short Circuit
Current at
Nominal DC Insulation at 30ºC 1 Sec
Cross Section Resistant at Resistance at
Nominal Area 20ºC 70ºC In Pipe In Air
Overal Cable
Cross Section
Diameter Weight
Area
mm 2
(mm) kg/km mm 2
Max. (Ω/km) Min. (MΩ.km) Max. A Max. A Max. (kA)

1.5 3.0 22.48 1.5 13.3 0.010 15 24 0.17


2.5 3.65 35.15 2.5 7.98 0.009 20 32 0.29
4 4.2 52.00 4 4.95 0.007 25 42 0.46
6 4.8 72.24 6 3.3 0.006 33 54 0.69
10 6.3 120.23 10 1.91 0.0056 45 73 1.16
16 7.4 183.18 16 1.21 0.0046 61 98 1.84
25 9.3 287.32 25 0.780 0.0044 83 128 2.88
35 10.7 394.43 35 0.554 0.0038 103 158 4.03
50 12.7 560.78 50 0.386 0.0037 132 197 5.75
70 14.6 770.10 70 0.272 0.0032 165 245 8.05
95 16.7 1030.82 95 0.206 0.0032 197 290 10.93
120 18.5 1290.50 120 0.161 0.0029 235 345 13.8
NYAF (Cu/PVC-f)
60227 IEC 06
300/500 V
0.5 ~ 1 mm 2

SNI 04-6629.3 - 2006


Permanent installation in conduit or exposed wiring in dry location.

CONSTRUCTION ELECTRICAL DATA


NominalDATA CONDUCTOR INSULATION Current Carrying Short Circuit
Cross Section Capacity Current at
Overal Cable Nominal DC Insulation
Area at 30 C
o
1 Sec
Diameter Weight Cross Section Resistant at Resistance at
Area 20ºC 70 C
o In Pipe In Air

mm 2
(mm) kg/km mm 2
Max. (Ω/km) Min. (MΩ.km) Max. A Max. A Max. (kA)

0.5 2.3 9.8 0.5 39.0 0.013 2.5 - 0.06


0.75 2.45 12.5 0.75 26.0 0.011 7 15 0.09
1 2.6 15.2 1 19.5 0.010 11 19 0.12
NYM (Cu/PVC/PVC)
60227 IEC 10
300/500 V
2 x (1.5 ~ 10 mm²) / 3 x (1.5 ~ 10 mm²) / 4 x (1.5 ~ 10 mm²)
SNI 04-6629.4 - 2006
Indoor and Outdor permanent installation in conduit under plaster or exposed
installation in dry location.

CONSTRUCTION DATA ELECTRICAL DATA


Nominal Overal Cable CONDUCTOR INSULATION Current Short Circuit
Cross Section Diameter Weight Carrying Current at
Area Nominal DC Insulation Capacity at 1 Sec
Cross Section Resistant at Resistance at 30 C
o

Area 20 C
o
70 C
o In Air

mm 2
mm kg/km mm 2
Max. (Ω/km) Min. (MΩ.km) Max. A Max. (kA)

2 x 1.5 8.6 116 1.5 12.1 0.011 19 0.17


2 x 2.5 9.6 149 2.5 7.41 0.010 25 0.29
2x4 11 191 4 4.61 0.0085 34 0.46
2x6 12 250 6 3.08 0.0070 44 0.69
2 x 10 15.2 411 10 1.83 0.0070 61 1.15
3 x 1.5 8.8 135.0 1.5 12.1 0.011 19 0.17
3 x 2.5 10 182.3 2.5 7.41 0.010 25 0.29
3x4 11.6 242.3 4 4.61 0.0085 34 0.46
3x6 12.7 326.5 6 3.08 0.0070 44 0.69
3 x 10 16.5 545.5 10 1.83 0.0070 61 1.15
4 x 1.5 9.6 163.9 1.5 12.1 0.011 19 0.17
4 x 2.5 11.0 237.9 2.5 7.41 0.010 25 0.29
4x4 12.5 334.5 4 4.61 0.0085 34 0.46
4x6 14.0 405.4 6 3.08 0.0070 44 0.69
4 x 10 17.5 701.9 10 1.83 0.0070 61 1.15
NYMHY / H05VV-F (Cu/PVC/PVC-f)
60227 IEC 53
300/500 V
2 x (0.75 ~ 2.5 mm²) / 3 x (0.75 ~ 2.5 mm²) / 4 x (0.75 ~ 2.5 mm²)
SNI 04-6629.5 - 2006
Indoor and Outdor location connection or portable aplication.

CONSTRUCTION DATA ELECTRICAL DATA


Nominal CONDUCTOR INSULATION Current Short Circuit
Cross Section Carrying Current at
Overal Cable Nominal DC Insulation
Area Capacity at 1 Sec
Diameter Weight Cross Section Resistant at Resistance at 30 C
o

Area 20 C
o
70 C
o In Air

mm 2
mm kg/km mm 2
Max. (Ω/km) Min. (MΩ.km) Max. A Max. (kA)

2 x 0.75 6.7 63.06 0.75 26.0 0.011 6 0.10


2 x 1.0 6.9 67.95 1.0 19.5 0.010 10 0.13
2 x 1.5 7.4 86.30 1.5 13.3 0.010 15 0.19
2 x 2.5 9.2 136.18 2.5 7.98 0.009 20 0.132
3 x 0.75 7.0 73.20 0.75 26.0 0.011 6 0.10
3 x 1.0 7.2 82.23 1.0 19.5 0.010 10 0.13
3 x 1.5 8.2 120.70 1.5 13.3 0.010 15 0.19
3 x 2.5 9.6 166.85 2.5 7.98 0.009 20 0.32
4 x 0.75 7.7 90.94 0.75 26.0 0.011 6 0.10
4 x 1.0 7.8 100.08 1.0 19.5 0.010 10 0.13
4 x 1.5 9.0 154.70 1.5 13.3 0.010 15 0.19
4 x 2.5 10.5 225.60 2.5 7.98 0.009 20 0.132
H05VVH2-F (Cu/PVC/PVC-f)
60227 IEC 53
300/500 V
2 x (0.75 ~ 1 mm²)
SNI 04-6629.5 - 2006
Indoor and Outdor location connection or portable aplication.

Nominal CONDUCTOR INSULATION Current Short Circuit


Cross Section Carrying Current at
Cable Nominal DC Insulation
Area Overal Diameter Capacity at 1 Sec
Weight Cross Section Resistant at Resistance at 30 C
o
In Air
Area 20 C
o
70 C
o

mm 2
(mm) kg/km mm 2
Max. (Ω/km) Min. (MΩ.km) Max. A Max. (kA)

0.75 4.1 x 6.6 73.20 0.75 26.0 0.011 6 0.10


1.0 4.3 x 6.85 82.23 1.0 19.5 0.010 10 0.13
H03VVH2-F (Cu/PVC/PVC-f)
60227 IEC 52
300/300 V
2 x (0.5 ~ 0.75 mm²)
SNI 04-6629.5 - 2006
Indoor and Outdor location connection or portable aplication.

Nominal CONDUCTOR INSULATION Current Short Circuit


Cross Section Carrying Current at
Overal Cable Nominal DC Insulation
Area Capacity at 1 Sec
Diameter Weight Cross Section Resistant at Resistance at 30 C
o

Area 20 C
o
70 C
o In Air

mm 2
(mm) kg/km mm 2
Max. (Ω/km) Min. (MΩ.km) Max. A Max. (kA)

0.5 3.35 x 30.1 0.5 39 0.012 2.5 0.07


5.4
0.75 3.5 x 37.16 0.75 26 0.010 6 0.10
5.75
NYMHY-1 / H03VV-F (Cu/PVC/PVC-f)
60227 IEC 52
300/300 V
2 x (0.5 ~ 0.75 mm²) / 3 x (0.5 ~ 0.75 mm²)
SNI 04-6629.5 - 2006
Indoor and Outdor location connection or portable aplication.

CONSTRUCTION ELECTRICAL DATA


NominalDATA CONDUCTOR INSULATION Current Short Circuit
Cross Section Carrying Current at
Overal Cable NomZ inal DC Insulation
Area Capacity at 1 Sec
Diameter Weight Cross Section Resistant at Resistance at 30 C
o

Area 20 C
o
70 C
o In Air

mm 2
(mm) kg/km mm 2
Max. (Ω/km) Min. (MΩ.km) Max. A Max. (kA)

2 x 0.5 5.25 39.22 0.5 39 0.012 2.5 0.07


2 x 0.75 6.0 48.22 0.75 26 0.010 6 0.10
3 x 0.5 5.6 48.22 0.5 39 0.012 2.5 0.07
3 x 0.75 6.4 59.60 0.75 26 0.010 6 0.10
NYY (Cu/PVC/PVC)
-
0.6/1 kV
1 x (1.5 ~ 35 mm2) 2 x (1.5 ~ 35 mm2) / 3 x (1.5 ~ 35 mm2) / 4 x (1.5 ~ 35 mm2)
SNI IEC 60502-1 : 2009
Indoor, outdor, underground, in concrete and in water location connection or portable
where mechanical damages are not to be expected.

CONSTRUCTION
CONDUCTOR INSULATION Current Carrying
Nominal Overal Capacity Short Circuit
Cable Nominal DC Insulation
Cross Section Diamete at 30 C
o
Current at
Weight Cross Section Resistant at Resistance at
Area r 1 Sec
Area 20 Co
70 C o In Air In Ground

mm 2 mm kg/km mm 2
Max. (Ω/km) Min. (MΩ.km) Max. A Max. A Max. (kA)

1 x 1.5
1 x 2.5
1x4
1x6
1 x 10
1 x 16
1 x 25
1 x 35
2 x 1.5 11.2 186.99 1.5 12.1 50 21 27 0.17
2 x 2.5 12.9 256.34 2.5 7.41 50 29 36 0.29
2x4 14.0 315.20 4 4.61 50 38 47 0.46
2x6 14.4 362.87 6 3.08 50 48 59 0.69
2 x 10 16.8 527.63 10 1.83 50 66 78 1.15
2 x 16
2 x 25
2 x 35
3 x 1.5 12.1 186.99 1.5 12.1 50 18 24 0.17
3 x 2.5 12.9 256.34 2.5 7.41 50 25 32 0.29
3x4 14.9 315.20 4 4.61 50 34 41 0.46
3x6 15.9 362.87 6 3.08 50 44 52 0.69
3 x 10 17.7 527.63 10 1.83 50 60 69 1.15
3 x 16
3 x 25
3 x 35
4 x 1.5 12.8 255.85 1.5 12.1 50 18 24 0.17
4 x 2.5 13.8 322.93 2.5 7.41 50 25 32 0.29
4x4 16.0 433.35 4 4.61 50 34 41 0.46
4x6 17.2 553.35 6 3.08 50 44 52 0.69
4 x 10 19.1 774.39 10 1.83 50 60 69 1.15
4 x 16
4 x 25
4 x 35