Professional Documents
Culture Documents
Bonetti Valves
Bonetti Valves
Not Verified
Digitally signed by
Mohit Jain
Date: 2017.02.09
15:19:32 IST
Reason: CAT I
Location: NTPCEOC
Dear Sir,
A list of the above documents (indicating the document number, latest revision
number, document title and the present category) which have been reviewed,
approved and stamped by HPE as the QSGM is attached herewith as a consolidated
document duly signed by Mr.Tukehiko Ikematsu, Chief Operating Officer(COO) and
Mr.H.Keller, Project Director from HPE Germany.
Encl : As above
BBX-0010-01-0-00_-UA17-00002 Date:
N-100140-0-0_-UA17-00001-AA 29 Nov 2016
Datasheet and GA drg. of Expansion joints along with Schedule of expansion joints
1 0360-102-PVM-Y-0330A 04 29. Feb 16 CAT II
ffor ID system & Seal air system)
GA DRAWING FOR SEAL AIR FAN WITH FOUNDATION PLAN AND LOADING
2 0360-102-PVM-B-0223 07 26. Jun 15 CAT II
DETAILS
4 0360-102-PVM-N-0234 07 27. Feb 15 PERFORMANCE CURVE FOR SEAL AIR FAN CAT IVR
5 0360-102-PVM-B-1576 05 06. Apr 16 GA of Fuel System Valves (Boiler Area) - Leader Make CATIVR
6 0360-102-PVM-H-0221 AF 16. Sep 15 Valve Schedule for water and steam system CAT IVR
7 0360-102-PVM-B-0959 AE 13. Jan 16 GA drawing & Datasheet for LRSB and Wall blower CAT II
8 0360-102-PVM-B-0963 AC 17. Aug 15 GA Drawing- Valve- Water and steam system (M/s L&T) CAT II
9 0360-102-PVM-B-0964 AD 01. Dez 15 GA Drawing -Valve -Water and steam system (M/s BHEL) CAT II
10 0360-102-PVM-B-0967 AC 16. Okt 15 GA Drawing - Valve - Water and steam system (M/s Sanmar) CAT II
11 0360-102-PVM-B-0968 AC 02. Nov 15 GA Drawing -Valve -Water and steam system (M/s Leader valves) CAT II
12 0360-102-PVM-B-0999 AC 20. Okt 15 Datasheet and GA of Boiler HP & RH Attemperator Control Valve CAT II
Datasheet and GA of Boiler Steam Sootblower and Air heater Sootblower Control
13 0360-102-PVM-B-1583 AB 01. Dez 15 CAT IVR
Valve
14 0360-102-PVM-B-0220 06 19. Mrz 15 GA DRAWING FOR FD FAN WITH FOUNDATION PLAN AND LOADING DETAILS CAT II
15 0360-102-PVM-B-0221 08 23. Feb 15 GA DRAWING FOR ID FAN WITH FOUNDATION PLAN AND LOADING DETAILS CAT II
16 0360-102-PVM-B-0222 08 19. Mrz 15 GA DRAWING FOR PA FAN WITH FOUNDATION PLAN AND LOADING DETAILS CAT II
18 0360-102-PVM-U-0306 06 17. Jun 15 AUXILIARY BOILER- FEED STORAGE TANK CAPCITY CALCULATION CAT II
23 0360-102-PVM-L-0228 05 19. Dez 14 LUBE OIL SCHEME FOR FD FAN CAT IVR
26 0360-102-PVM-Y-0308 04 11. Feb 16 AUXILIARY BOILER- DATA SHEET OF FD/ID FANS CAT II
27 0360-102-PVM-B-1000 01 14. Sep 15 Aux. Boiler- BFW Pump Data sheets and GA CAT II
GA of valves for Drain and vent system (Valves in the downstream of condensate
28 0360-102-PVM-B-1606 03 07. Mrz 16 CAT II
pumps)- STEEL STRONG
Electromatic relief valve (ERV) : GA/Write up/ Scheme/ Data sheet/
29 0360-102-PVI-Y-0836 AC 05. Aug 15 CAT II
Interconnection diagram
30 0360-102-PVM-Y-0836A AC 07. Jul 15 Boiler Safety valve : GA & Data sheet. CAT II
Hita~~~ i~:~~QH
-P6Wer ur ~~ , ____.
Schifferstra 0
H1tach1 Power Europe GmbH 47059 Oui burg Page 1 of 5
Germany
BBX-0010-01-0-00_ -UA17-00002 Date:
N-100140-0-0_ -UA17-00001-AA 29 Nov 2016
34 0360-102-PVM-H-0209 AG 18. Nov 15 VALVE SCHEDULE OF APH WATER WASH & FIRE FIGHTING CATIVR
35 0360-102-PVM-H-0207 AE 24. Apr 15 VALVE SCHEDULE OF COOLING WATER SUPPLY & RETURN CAT IVR
38 0360-102-PVM-B-0974 AA 16. JullS VALVE GA DRAWING FOR SERVICE WATER TO MILLS - M/S LEADER VALVES CAT II
40 0360-102-PVM-B-0971 AC 28. Jun 16 Valve GA Drawing for APH water wash & fire fighting system - M/s Leader valves CAT II
41 0360-102-PVM-B-0972 AB 31. Aug 15 Valve GA Drawing for cooling water supply & return system - M/s Leader valves CAT II
43 0360-102-PVM-W-0383 03 09. Jul 15 Data Sheet - Drain Oil Pump (in Boiler Area) CAT II
44 0360-102-PVM-B-0997 02 07. Jul 15 Data Sheet and GA for Drain oil Pump Suction Strainer (Boiler Area) CAT II
47 0360-102-PVM-B-0998 01 10. Jul 15 GA of fuel system valves (Boiler Area) - Flowserve make CAT II
50 0360-102-PVM-B-1594 AB 04. Feb 16 Datasheet and GA of Boiler Control Valve (Start-up system) CAT IVR
51 0360-102-PVM-B-0973 AB 05. Aug 15 Valve GA Drawing for service air system - M/s Leader valves CAT II
52 0360-102-PVM-B-0975 AB 30. Jul 15 Valve GA Drawing for Instrument air system - M/s Leader valves CAT II
56 0360-102-PVI-Y-1580 00 28. Aug 15 Datasheet and GA of BCP Purge/Fill water line Flow switch - M/s DK instruments CATIVR
58 0360-102-PVM-B-1001 00 10. Jul 15 GA OF FUEL SYSTEM VALVES (BOILER AREA) BHEL MAKE CAT II
59 0360-102-PVM-H-0205 AF 30. Jul 15 VALVE SCHEDULE OF AUX. STEAM TO SCAPH & SCAPH DRAIN CAT IVR
60 0360-102-PVM-B-0992 AC 07. Jan 16 Valve GA Drawing for Auxiliary steam to SCAPH & SCAPH Drain system - M/s BHEL CAT II
61 0360-102-PVM-H-0206 AE 02. Jun 15 VALVE SCHEDULE OF AUX. STEAM TO MILL INERTING CATIVR
62 0360-102-PVM-B-0993 AD 20. Okt 15 Valve GA Drawing for Auxiliary steam to Mill inerting system - M/s BHEL CAT II
63 0360-102-PVM-H-0222 AB 01. Sep 16 Valve Schedule & GA drawing for sampling cooler system CAT IVR
64 0360-102-PVM-B-0989 AA 10. Jul 15 Valve GA Drawing for service air system - M/s Xomox sanmar CAT II
65 0360-102-PVI -Y-0837 AD 01. Okt 15 Furnace temp. probe: GA/Write up/ Scheme/ Data sheet/ Interconnection diagram
fATF
66 0360-102-PVM-H-0878B 06 02. Jun 15 CORROSION PROTECTION SPECIFICATION FOR AUXILLARY BOILER cAfii
' I
v~ou
Hitacni ;~~
PowerEur · bH
SchifferstraB 80
Hitachi Power Europe GmbH 47059 Dui burg Page 2 of 5
Germany
BBX-0010-01-0-00_-UA17-00002 Date:
N-100140-0-0_-UA17-00001-AA 29 Nov 2016
67 0360-102-PVM-B-0990 AD 20. Okt 1S Valve GA Drawing for Auxiliary steam to Mill inerting system - M/s Forbes Marshall CAT II
68 0360-102-PVM-B-1SS9 02 28. Aug 1S GA of Seal Air System valves - Intervalve make (Boiler Area) CATIVR
69 0360-102-PVM-Y-0330 OS 22. Nov 14 DATA SHEETS FOR EXPANSION JOINTS (HPE scope) CAT II
70 0360-102-PVM-B-0986 02 09. Jun 1S DATA SHEET AND GA OF TEMPERATURE CONTROL VALVE- FLOOR COIL HEATER CAT II
71 0360-102-PVM-B-1S61 03 08. Mrz 16 AUXILIARY BOILER- DATA SHEET AND GA OF CONTROL VALVES CAT II
72 0360-102-PVM-B-1S75 AB 30. Okt 15 DATA SHEET & GA DRAWING FOR AUX STEAM CONTROL VALVES CAT IVR
74 0360-102-PVM-B-0969 AB 10. Jul 15 GA Drawing - Valve - Water and steam system (M/s Bonetti) CAT II
75 0360-102-PVM-U-0299 03 06. Apr 16 Calculation for ID fan seal air system along with write-up CAT II
78 0360-102-PVM-L-0279 04 30. Sep 14 AUX BOILER- AIR AND FLUE GAS PATCH WITH INSTRUMENTATION CAT II
82 0360-102-PVM-B-0951 AC 26. Jun 15 Data sheet, Pump Performance curve and GA Drawing for Boiler Circulation pump CAT II
INTEGRAL ACTUATOR MOTORS DATASHEET & WIRING DIAGRAM FOR EACH
83 0360-102-PVE-Y-0644 07 27. Mai 16 CAT II
TYPE AND RATING(VENDOR 1)
DATA SHEET & CURVES, OGA AND TERMINAL BOX ARRANGEMENT FOR SAPH
84 0360-102-PVE-Y-0623 03 29. Jun 16 CAT II
MOTOR
DATA SHEET & CURVES, OGA AND TERMINAL BOX ARRANGEMENT FOR PAPH
85 0360-102-PVE-Y-0624 03 29. Jun 16 CAT II
MOTOR
Electrical Actuators with Integral Starter - Datasheet and Wiring diagram for Utility
86 0360-102-PVE-Y-1S66 05 27. Mai 16 CATIVR
Piping And Control Valves
INTEGRAL ACTUATOR MOTORS DATASHEET & WIRING DIAGRAM FOR EACH
87 0360-102-PVE-Y -0645 03 13. Okt 15 CATI
TYPE AND RATING(VENDOR 2)
88 0360-102-PVM-B-0994 AB 11. Mai 16 Valve GA Drawing for Service air system - M/s BHEL CAT II
89 0360-102-PVM-X-1635 AB 03. Aug 16 Aux. safety valve GA drawing (M/s Finger Leser supply) CAT II
90 0360-102-PVM-F-0215 AI 20. Apr 15 SCHEME OF COOLING WATER SUPPLY & RETURN CATIVR
92 0360-102-PVM-F-0217 AI 20. Okt 15 SCHEME OF APH WATER WASH & FIRE FIGHTING CATIVR
93 0360-102-PVM-F-0212 AG 20. Nov 14 SCHEME OF AUX. STEAM TO SCAPH & SCAPH DRAIN CAT II
\ X&r£ J. I CAr/IvR
--
99 0360-102-PVM-X-0236 05 05. Mai 15 TYPE TEST PROCEDURE FOR FANS .I
HroachiPower Euf~~~~
SchifferstraBe 0
H1tach1 Power Europe GmbH 47059 Duis u11g Page 3 of 5
Germany
BBX-0010-01-0-00_ -UA17-00002 Date:
N-100140-0-0_-UA17-00001-AA 29 Nov 2016
100 0360-102-PVM-X-0342 04 06. Mai 1S SHOP PERFORMANCE TEST PROCEDURE FOR FD FAN CATIVR
101 0360-102-PVM-X-034S OS OS. Mai 1S SHOP PERFORMANCE TEST PROCEDURE FOR ID FAN CATIVR
10S 0360-102-PVM-X-0236A 02 17. Aug 1S Shop Performance Test procedure for Mill Seal Air fans CAT IVR
106 0360-102-PVM-B-0319 04 26. Mrz 16 GA and FOUNDATION FOR AIR RECEIVER TANK CAT II
109 0360-102-PVM-U-096S OS 26. Nov 14 Air pre-heater Sizing Calculations (Heating Suface Area) CAT II
110 0360-102-PVM-F-0249 OS 08. Apr 1S SCHEME OF APH (PRIMARY & SECONDARY) WITH INSTRUMENTATION CAT II
111 0360-102-PVM-F-02SO 04 08. Aug 14 SCHEME OF APH (PRIMARY & SECONDARY) FIRE FIGHTING & WATER WASHING. CAT II
112 0360-102-PVM-L -0300 04 08. Aug 14 SCHEME OF AIR PREHEATER SUPPORT & GUIDE BEARING LUBE OIL SYSTEM CAT II
114 0360-102-PVM-Y-0330B 06 26. Jun 1S Testing procedure of metallic expansion joints CAT II
11S 0360-102-PVM-Y-0330C OS 2S. Feb 16 Type Test Procedure for Metallic Expansion Joint ( ID System) CAT II
116 0360-102-PVM-W-0318 AD 18. Aug 16 GA and Foundation Details of Boiler Condensate Tank CAT II
117 0360-102-PVM-V-0294 AC 11. Mai 16 GA and Foundation Details of Boiler Flash Tank CATIVR
118 0360-102-PVM-P-1610 06 01. Sep 16 GA and data sheet of ECW & Service water Booster Pump CAT IVR
119 0360-102-PVI -Y-0743 03 01. Okt 1S Data Sheet and GA of Flow Orifice CAT II
120 0360-102-PVI-Y-0744 04 01. Okt 1S Data Sheet and GA of Flow Nozzle CAT II
Acoustic Steam Leak Detection System: GA/Write up/ Scheme/ Data sheet/
121 0360-102-PVI-Y-0838 07 17. Aug 1S CAT II
Interconnection diagram
122 0360-102-PVI-Y-084S 06 21. Sep 1S Data Sheet of Rota Probe Type Coal Sampling System CAT II
123 0360-102-PVI-Y-08S1 09 OS. Apr 16 Data Sheet of On line Carbon in Ash Analyser CAT II
124 0360-102-PVI -B-0320 08 04. Jan 16 GA OF INSTRUMENT FOR MEASUREMENT OF YGP INDEX CAT II
12S 0360-102-PVM-B-0100A 07 18. Aug 16 Drain oil tank foundation with GA & loading data in Boiler area CAT II
126 0360-102-PVM-B-0970 06 01. Okt 1S General Arrangement of Burner Inlet Valve CAT II
127 0360-102-PVM-B-0976 07 04. Jan 16 General Arrangement of Mill Discharge Valve CAT II
128 0360-102-PVM-B-0978 03 16. Jul 1S GA and Data sheet for Seal Air Cooler CAT II
GA and Data Sheet for Condensate Flash Tank (1 cu.m) - Fuel oil system (Boiler
129 0360-102-PVM-B-099S OS 18. Aug 16 CAT II
Area)
130 ' 0360-102-PVM-F-0082 02 22. Okt 13 P & I Diagram - MPS MILL MOTOR 10 CAT II
132 0360-102-PVM-X-0338 AD 30. Okt 1S TYPE TEST PROCEEDURE FOR START UP PUMP
i7 !I [efT
/J/ L II
133 0360-102-PVM-B-1624 03 06. Jul 16 Auxliary Boiler- LDO Pump GA and Data Sheets CATIVR
134 0360-102-PVM-F-0310 03 03. Sep 14 AUXILIARY BOILER- INSTUMENT AIR P&ID CAT II
\7~Eu~·,~~)
Hitachi Power
L
..EI\.Q.FRT k£'-([{(
Schlfferstra BC#
47059 ou· burcJtfl~fCT J)J(?c(TDI(
Germany
TA KEH IW IlcEff11SLf.
eoo
NTPC Limited
(A Government of India Enterprise)
PROJECT
MEJA THERMAL POWER PROJECT
(2 x 660 MW)
PACKAGE STEAM GENERATOR (SG) PACKAGE
SG CONTRACTOR
BGR ENERGY SYSTEMS LIMITED
CHENNAI – INDIA
GA Drawing - Valve - Water and steam system (Vendor-5)_Bonetti (15 Nos. per unit)
Valve Make/
HPE
Valve Design Design Connecting Qty. Model/
End Valve Body Pressure Recommended
Sl. No. P& ID Reference No. System Description Location Line TAG No. Valve TAG No. Size Type Operation Medium Pressure Temperature line size per Weight_Refer
Connection Material Rating Operating time
(NB) (Kg/cm2(g)) (◦C) (NB) Unit Vendor GA
(Sec)
drawing No.
Angle Globe
1 0360-102-PVM-F-0086 Rev. AH Superheater System Valve at SH Attemperator 1 inlet line 1 0LAE41 BR030 1 0LAE41 AA051 100 BW Electric Spray Water 309.9 524.5 A 182 Gr. F91 3000 (Spl) 100 1 30 590517-10-70
Valve
Angle Globe
2 0360-102-PVM-F-0086 Rev. AH Superheater System Valve at SH Attemperator 1 inlet line 1 0LAE42 BR030 1 0LAE42 AA051 100 BW Electric Spray Water 309.9 524.5 A 182 Gr. F91 3000 (Spl) 100 1 30 590517-10-70
Valve
Angle Globe
3 0360-102-PVM-F-0086 Rev. AH Superheater System Valve at SH Attemperator 1 inlet line 1 0LAE61 BR030 1 0LAE61 AA051 100 BW Electric Spray Water 309.9 522 A 182 Gr. F91 3000 (Spl) 100 1 30 590517-10-70
Valve
Angle Globe
4 0360-102-PVM-F-0086 Rev. AH Superheater System Valve at SH Attemperator 1 inlet line 1 0LAE62 BR030 1 0LAE62 AA051 100 BW Electric Spray Water 309.9 522 A 182 Gr. F91 3000 (Spl) 100 1 30 590517-10-70
Valve
Angle Globe
5 0360-102-PVM-F-0087 Rev. AH Reheater System Valve at RH attemperator inlet line 1 0LAF21 BR030 1 0LAF21 AA051 125 BW Electric Spray Water 70.1 518.4 A 182 Gr. F91 1500 125 1 30 590517-20-80
Valve
Angle Globe
6 0360-102-PVM-F-0087 Rev. AH Reheater System Valve at RH attemperator inlet line 1 0LAF22 BR030 1 0LAF22 AA051 125 BW Electric Spray Water 70.1 518.4 A 182 Gr. F91 1500 125 1 30 590517-20-80
Valve
Page - 2 of 2
MEJA THERMAL POWER PROJECT (2 x 660 MW)
Sl. No. Document Title BGR Document No. NTPC Document No. Rev. Category Date of Drawing Return with Reference
QSGM recommeded operating time is incorporated in the valve list. Kindly refer.
Kindly incorporate the QSGM recommended operating times. also attach the soft copy of the complete
1 Further more the over all valve list for water and steam sytem is under final
water and steam valve schedule in the next revision of the document
preparation the same shall be submitted shortly.
2 Hydrostatic test pressure for seat may knidly be reviewed w.r.t ASME B16.34 and clarified corrected refer GAD
Page - 1 of 1