You are on page 1of 12

EE464 Power System Protection

Course Information
Course Number and Title: EE-464 Power System Protection
Credits: 3 (3-0)
Instructor(s)-in-charge: Dr Mazhar Abbas (Asst Prof)
Course type: Lecture
Required or Elective: Elective
Course pre-requisites EE-461 Power System Analysis and Design
Degree and Semester DE-41 Department of Electrical Engineering, Semester 8th
Month and Year Spring 2023

1 / 12
Contents
 Chapter 6: Protection of Transmission lines
 Reactance relay
 Mho relay

1. Course book and Related Course Material


1. Fundamentals of Power System Protection, Paithanka
Textbooks:
r & Bhide
2. Electrical Power Systems, C.L. Wadhva, Principles
Reference Books:
of Power System, V.K. Mehta

2 / 12
Chapter 6: Protection of Transmission lines

 General Torque equation for relays


 In relays, voltage, current or interaction between them produce torque
 At least two factors are required to produce a controlled torque\
 If one factor acts as a deflecting torque, the other as restraining torque

3 / 12
Chapter 6: Protection of Transmission lines

 Trip law for reactance relay

 Current provides deflection torque, so k1 is positive


 Restraining torque by product of voltage and current, so k3 is negative
 Reach of simple impedance relay is independent of angle between V & I.
 Due to independent reach K3 is zero.
 K4 is zero because there is no restoring spring

4 / 12
Chapter 6: Protection of Transmission lines

 Reactance relay implementation using Induction cap structure


 Maximum torque angle-(MTA)
MTA=90-phase angle of pressure coil
 Pressure coil: Voltage is in phase to
current (Very high external resistance)
 Pressure coil phase angle is zero
 So, MTA is 90 degree
 Restraining torque is equal to..
VIcos(θ-90°)=VIsinθ
 Deflection torque is equal to
Torque=ϕ1ϕ2sinθ=I1I2sin90

5 / 12
Chapter 6: Protection of Transmission lines

 Performance of reactance relay during normal load flow


 Impedance of double-end-fed system as seen by relay shown below
 The impedance seen by relay falls in the trip region of reactance relay
 Reactance relay can not be used as an independent relay
 The relay responds correctly in the presence of fault resistance

6 / 12
Chapter 6: Protection of Transmission lines

 Effect of ARC resistance on reach of reactance relay


 A fault at point B with resistance equal to B
 The tip of impedance (phasor AC) still remains in the trip region
 Preferable for exact location of fault in the presence of fault resistance

7 / 12
Chapter 6: Protection of Transmission lines

 Directional property exhibited by reactance relay


The trip characteristics lie both in first and third quadrant
 However, the relays responds for unlimited distance in reverse direction
 The relay must be used in conjunction with directional or distance relay

8 / 12
Chapter 6: Protection of Transmission lines

 Performance of impedance relay during power swing


 Under steady state conditions, the rotor angle is constant
 The rotor angle (angle between rotor flux and stator flux) needs to adjust
 Due to inertia of rotating systems, rotor slowly reach new angular position
 The slow and oscillatory manner of rotor angle adjustment is power swing

9 / 12
Chapter 6: Protection of Transmission lines

 Performance of impedance relay during power swing


 During power swing, the locus of tip of impedance passes through point C
 Thus, the apparent impedance enters the trip region of relay
 The power swing causes the impedance relay to trip

10 / 12
Quiz 4, OBA:Yes, Marks 10, Time:20 minutes

 The equivalent circuit of CT is shown on left side. Draw the equivalent


circuit for bus bar protection scheme on right side. Show the current
values in equivalent circuit (10)

11 / 12
Thank you
Questions/Comments??

12 / 12

You might also like