Hilti PROFIS Engineering 3.0.

89

www.hilti.co.uk
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 92982_Resin anchors calcs -1400 mm PCD Date: 11/12/2023
Fastening Point:

Specifier's comments: Pull-out test: 90.52 kN

1 Input data
Anchor type and size: HIT-RE 500 V4 + AM (8.8) M30
Return period (service life in years): 50
Item number: 2008139 AM 8.8 M30x1000 (insert) / 2287557
HIT-RE 500 V4 (mortar)
Hilti Filling Set or any suitable annular gap filling solution
Effective embedment depth: hef,act = 600.0 mm (hef,limit = - mm)
Material: 8.8
Approval No.: ETA 20/0541
Issued I Valid: 09/06/2023 | -
Proof: Engineering judgement SOFA BOND - based on ETAG BOND testing
Stand-off installation: without clamping (anchor); restraint level (baseplate): 1.00; eb = 40.0 mm; t = 30.0 mm

Baseplate :
R lx x ly x t = 1,500.0 mm x 1,500.0 mm x 30.0 mm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: 2
cracked concrete, C20/25, fc,cube = 25.00 N/mm ; h = 1,000.0 mm, Temp. short/long: 0/0 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid baseplate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.89

www.hilti.co.uk
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 92982_Resin anchors calcs -1400 mm PCD Date: 11/12/2023
Fastening Point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = -65.000; Vx = 18.750; Vy = 0.000; no no 43
Mx = 0.000; My = 314.750; Mz = 0.000;
Nsus = -65.000; Mx,sus = 0.000; My,sus = 314.750;

2 Combination 2 N = -65.000; Vx = 0.000; Vy = 18.750; no no 43


Mx = -314.750; My = 0.000; Mz = 0.000;
Nsus = -65.000; Mx,sus = -314.750; My,sus = 0.000;

3 Combination 3 N = -61.000; Vx = -22.500; Vy = 0.000; no no 47


Mx = 0.000; My = 338.200; Mz = 0.000;
Nsus = -61.000; Mx,sus = 0.000; My,sus = 338.200;

4 Combination 4 N = -65.000; Vx = 0.000; Vy = 18.750; no no 43


Mx = 314.750; My = 0.000; Mz = 0.000;
Nsus = -65.000; Mx,sus = 314.750; My,sus = 0.000;

2 Load case/Resulting anchor forces 4 y 3

Controlling load case: 3 Combination 3


5 2

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y 6 x 1
1 -102.729 2.250 -2.250 0.000
2 -84.274 2.250 -2.250 0.000
3 -35.960 2.250 -2.250 0.000
4 23.760 2.250 -2.250 0.000 7 10
5 72.074 2.250 -2.250 0.000
6 90.529 2.250 -2.250 0.000 8 9
7 72.074 2.250 -2.250 0.000
8 23.760 2.250 -2.250 0.000
9 -35.960 2.250 -2.250 0.000
10 -84.274 2.250 -2.250 0.000

max. concrete compressive strain: - [‰]


max. concrete compressive stress: - [N/mm ]
2

resulting tension force in (x/y)=(0.0/0.0): 0.000 [kN]


resulting compression force in (x/y)=(0.0/0.0): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid baseplate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.89

www.hilti.co.uk
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 92982_Resin anchors calcs -1400 mm PCD Date: 11/12/2023
Fastening Point:

3 Tension load (EOTA TR 029, Section 5.2.2)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel failure* -102.729 299.200 35 OK
Combined pullout-concrete cone failure** 282.197 935.505 31 OK
Concrete Breakout failure** 282.197 605.814 47 OK
Splitting failure** 282.197 716.619 40 OK

* highest loaded anchor **anchor group (anchors in tension)

3.1 Steel failure

NRk,s [kN] gM,s NRd,s [kN] NSd [kN]


448.800 1.500 299.200 -102.729

The steel proof was done for the highest absolute force per anchor - in this case compression loading. Please be aware that buckling
should be verified separately

3.2 Combined pullout-concrete cone failure


2 0 2 2
Ap,N [mm ] Ap,N [mm ] t Rk,ucr,25 [N/mm ] scr,Np [mm] ccr,Np [mm] cmin [mm]
2,268,488 672,000 14.00 819.8 409.9 800.0
0
yc t Rk,cr [N/mm ]
2
k y g,Np y g,Np
1.000 8.50 2.300 1.171 1.070

ec1,N [mm] y ec1,Np ec2,N [mm] y ec2,Np y s,Np y re,Np


97.2 0.808 0.0 1.000 1.000 1.000
0
NRk,p [kN] NRk,p [kN] gM,p NRd,p [kN] NSd [kN]
480.664 1,403.258 1.500 935.505 282.197

Group anchor ID
4-8

3.3 Concrete Breakout failure


2 0 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm]
6,378,441 3,240,000 900.0 1,800.0

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N


97.2 0.903 0.0 1.000 0.967 1.000
0
k1 NRk,c [kN] gM,c NRd,c [kN] NSd [kN]
7.200 529.090 1.500 605.814 282.197

Group anchor ID
4-8

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.89

www.hilti.co.uk
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 92982_Resin anchors calcs -1400 mm PCD Date: 11/12/2023
Fastening Point:

3.4 Splitting failure


0 2
Ac,N [mm ]
2
Ac,N [mm ] ccr,sp [mm] scr,sp [mm] y h,sp
6,042,944 2,783,559 960.0 1,920.0 1.306
' ' '
hef [mm] ccr,sp [mm] scr,sp [mm]
521.4 834.2 1,668.4

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N k1


97.2 0.896 0.0 1.000 0.988 1.000 7.200
0
NRk,c [kN] gM,sp NRd,sp [kN] NSd [kN]
428.576 1.500 716.619 282.197

Group anchor ID
4-8

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.89

www.hilti.co.uk
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 92982_Resin anchors calcs -1400 mm PCD Date: 11/12/2023
Fastening Point:

4 Shear load (EOTA TR 029, Section 5.2.3)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel failure (without lever arm)* N/A N/A N/A N/A
Steel failure (with lever arm)* 2.250 13.502 17 OK
Pryout failure** 22.500 1,871.592 2 OK
Concrete edge failure in direction x-** 22.500 237.725 10 OK

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel failure (with lever arm)

l [mm] aM
70.0 1.00
0 0
NSd / NRd,s 1 - NSd / NRd,s MRk,s [kNm] MRk,s = MRk,s (1 - NSd/ NRd,s) [kNm]
0.343 0.657 1.799 1.181
M M
VRk,s = aM * MRk,s / l [kN] gMs,b,V VRd,s [kN] VSd [kN]
16.878 1.250 13.502 2.250

4.2 Pryout failure (concrete cone relevant)


2 0 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k-factor
8,378,696 2,783,559 900.0 1,800.0 2.000
' ' '
hef [mm] ccr,N [mm] scr,N [mm]
556.1 834.2 1,668.4

ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N


0.0 1.000 0.0 1.000 0.988 1.000
0
NRk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
472.140 1.500 1,871.592 22.500

Group anchor ID
1-10

4.3 Concrete edge failure in direction x-

lf [mm] dnom [mm] k1 a b


240.0 30.00 1.700 0.058 0.053
' 2 0 2
c1 [mm] c1 [mm] Ac,V [mm ] Ac,V [mm ]
800.0 725.7 2,999,880 2,369,621

y s,V y h,V aV [°] y a,V ec,V [mm] y ec,V y re,V


1.000 1.043 0.00 1.000 0.0 1.000 1.000
0
VRk,c [kN] gM,c VRd,c [kN] VSd [kN]
269.978 1.500 237.725 22.500

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.89

www.hilti.co.uk
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 92982_Resin anchors calcs -1400 mm PCD Date: 11/12/2023
Fastening Point:

5 Combined tension and shear loads (EOTA TR 029, Section 5.2.4)


bN bV a Utilization bN,V [%] Status
0.466 0.167 1.500 39 OK

a a
bN + bV £ 1.0

6 Displacements (highest loaded anchor)


Short term loading:

NSk = -76.096 [kN] dN = -0.2422 [mm]


VSk = 1.667 [kN] dV = 0.0500 [mm]
dNV = 0.2473 [mm]
Long term loading:

NSk = -76.096 [kN] dN = -0.2422 [mm]


VSk = 1.667 [kN] dV = 0.0833 [mm]
dNV = 0.2562 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7 Warnings
• The anchor design methods in PROFIS Engineering require rigid baseplates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the baseplate are not considered - the
baseplate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required baseplate thickness with CBFEM to limit the stress of the baseplate based on the assumptions explained
above. The proof if the rigid baseplate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be
checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• Attention! In case of compressive anchor forces a buckling check as well as the proof of the local load transfer into and within the base
material (incl. punching) has to be done separately.
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• Your design has selected filled holes. Please ensure that there is a proper method to fill the annular gap between the fixture and HIT-RE 500
V4 + AM (8.8) M30and contact Hilti in case of any questions.
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Characteristic bond resistances depend on short- and long-term temperatures.
• The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling
the gap with mortar of sufficient compressive strength (e.g. by using the HILTI Filling set) or by other suitable means
• The compliance with current standards (e.g. EN 1993, AS 4100:1998, etc.) is the responsibility of the user
• An SLS-check is not performed for SOFA and has to be provided by the user!
• The characteristic bond resistances depend on the return period (service life in years): 50

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.89

www.hilti.co.uk
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 92982_Resin anchors calcs -1400 mm PCD Date: 11/12/2023
Fastening Point:

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.89

www.hilti.co.uk
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 92982_Resin anchors calcs -1400 mm PCD Date: 11/12/2023
Fastening Point:

8 Installation data
2 2
Baseplate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm Anchor type and size: HIT-RE 500 V4 + AM (8.8) M30
Profile: no profile Item number: 2008139 AM 8.8 M30x1000 (insert) /
2287557 HIT-RE 500 V4 (mortar)
Hole diameter in the fixture: df = 33.0 mm Maximum installation torque: 300 Nm
Plate thickness (input): 30.0 mm Hole diameter in the base material: 35.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 600.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 670.0 mm
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required

Hilti AM threaded rod with HIT-RE 500 V4 injection mortar with 600 mm embedment h_ef, M30, Steel galvanized, Hammer drilling installation
per ETA 20/0541, with annular gaps filled with Hilti Filling Set or any suitable gap solutions

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Compressed air with required • Dispenser including cassette and mixer
• Properly sized drill bit accessories to blow from the bottom of • Hilti Filling Set
the hole • Torque wrench
• Proper diameter wire brush

y
750.0 750.0
254.3 84.3

4 3

5 2
750.0
411.5

6 1
x
411.4

750.0

7 10
84.3 254.3

8 9

50.0 350.0 432.6 350.0 133.7

Coordinates Anchor [mm] 133.7 50.0

Anchor x y c-x c+x c-y c+y Anchor x y c-x c+x c-y c+y
1 700.0 0.0 2,200.0 800.0 1,499.9 1,499.9 6 -700.0 0.0 800.0 2,200.0 1,499.9 1,499.9
2 566.3 411.5 2,066.3 933.7 1,911.4 1,088.5 7 -566.3 -411.4 933.7 2,066.3 1,088.5 1,911.4
3 216.3 665.7 1,716.3 1,283.7 2,165.7 834.2 8 -216.3 -665.7 1,283.7 1,716.3 834.2 2,165.7
4 -216.3 665.7 1,283.7 1,716.3 2,165.7 834.2 9 216.3 -665.7 1,716.3 1,283.7 834.2 2,165.7
5 -566.3 411.5 933.7 2,066.3 1,911.4 1,088.5 10 566.3 -411.4 2,066.3 933.7 1,088.5 1,911.4

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2023 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.89

www.hilti.co.uk
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: 92982_Resin anchors calcs -1400 mm PCD Date: 11/12/2023
Fastening Point:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with
regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to
interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability
for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.