You are on page 1of 25

OMICRON PTL User manual

OMICRON PTL

User manual
V3.00

© OMICRON electronics GmbH 1/25


OMICRON PTL User manual

Contents
1 Definition ....................................................................................................................................................4
2 General .......................................................................................................................................................4
3 Quick Start Information ............................................................................................................................4
4 XRIO Converter Structure ........................................................................................................................5
4.1 General Structure .................................................................................................................................5
4.2 Relay Parameter Section .....................................................................................................................5
4.3 Additional Information ...........................................................................................................................5
4.3.1 General ...........................................................................................................................................5
4.3.2 Relay Information ...........................................................................................................................5
4.3.3 Circuit Breaker ................................................................................................................................5
4.3.4 Test Information ..............................................................................................................................5
4.4 RIOplus .................................................................................................................................................6
4.5 Template Controller ..............................................................................................................................6
4.6 RIO .......................................................................................................................................................6
4.7 Active RIO Functions ............................................................................................................................6
5 Relay Settings Import ...............................................................................................................................7
6 Protection Test Template for Test Universe...........................................................................................8
6.1 Test Object with XRIO Converter .........................................................................................................8
6.2 Hardware Configuration .......................................................................................................................8
6.3 Common Testing Procedures ...............................................................................................................8
6.3.1 Delete Inactive Test Modules .........................................................................................................8
6.3.2 Wiring Check ..................................................................................................................................8
6.3.3 Initial Test .......................................................................................................................................8
6.3.4 Trip Test with Circuit Breaker .........................................................................................................8
6.4 Feeder Protection Templates ...............................................................................................................9
6.4.1 Main and Backup Protection...........................................................................................................9
6.4.2 Switch onto Fault Protection ...........................................................................................................9
6.5 Line Protection Templates ................................................................................................................. 10
6.5.1 Main Protection with Distance Protection .................................................................................... 10
6.5.2 Main Protection with Line Differential Protection ......................................................................... 12
6.5.3 Backup Protection ....................................................................................................................... 12
6.5.4 Switch onto Fault Protection ........................................................................................................ 13
6.6 Transformer Protection Templates .................................................................................................... 14
6.6.1 Internal Fault Protection .............................................................................................................. 14
6.6.2 External Fault Protection ............................................................................................................. 14
6.7 Generator Protection Templates ....................................................................................................... 15
6.7.1 Generator Differential Protection ................................................................................................. 15
6.7.2 Fault on Connected Network ....................................................................................................... 15
6.7.3 Other Generator Protection ......................................................................................................... 15
6.8 Motor Protection Templates .............................................................................................................. 18
6.8.1 Overload Protection ..................................................................................................................... 18
6.8.2 Short Circuit Protection ................................................................................................................ 18
6.8.3 Network Fault Protection ............................................................................................................. 19
6.9 Radial Feeder Recloser Test Templates ........................................................................................... 20
6.9.1 Metering Test ............................................................................................................................... 20
6.9.2 Minimum Trip Current Tests ........................................................................................................ 20
6.9.3 High Current Trip Tests ............................................................................................................... 20
6.9.4 Overcurrent Characteristic Tests ................................................................................................. 20
6.9.5 Cold Load Pickup or Delay Curve Characteristic Tests .............................................................. 20
6.9.6 Successful Reclose Sequence Tests .......................................................................................... 20
6.9.7 Reclose Sequence to Lockout Tests ........................................................................................... 21
6.9.8 Reset Timer Tests ....................................................................................................................... 21
6.9.9 High Current Lockout Tests ......................................................................................................... 21
6.9.10 Sequence Coordination Tests ................................................................................................... 21
6.9.11 Sensitive Earth Fault Min Trip ................................................................................................... 21
6.9.12 Sensitive Earth Fault Trip Time ................................................................................................. 22
6.9.13 Sensitive Earth Fault Sequence ................................................................................................ 22

© OMICRON electronics GmbH 2/25


OMICRON PTL User manual

6.9.14 Underfrequency Pickup ............................................................................................................. 22


6.9.15 Underfrequency Trip Times ....................................................................................................... 22
7 Protection Test Template for RelaySimTest........................................................................................ 23
7.1 Hardware Configuration .................................................................................................................... 23
7.2 General Test Preparations ................................................................................................................ 23
7.2.1 Power System Data ..................................................................................................................... 23
7.2.2 Test Case Data ............................................................................................................................ 23
7.2.3 Wiring Check ............................................................................................................................... 23
7.3 Line Protection Templates ................................................................................................................. 23
7.3.1 Automatic Reclosing .................................................................................................................... 23
7.3.2 Teleprotection with Distance Protection ...................................................................................... 24
7.3.3 Weak Infeed for Teleprotection with Distance Protection ........................................................... 24

© OMICRON electronics GmbH 3/25


OMICRON PTL User manual

1 Definition
A Protection Test Template (PTT) is one part of a Protection Testing Library (PTL) -item. There are two
types of PTTs:
➢ PTT for Test Universe with an integrated XRIO Converter (OCC file format)
➢ PTT for RelaySimTest (RSTT file format)

2 General
The OMICRON PTL User Manual describes the common aspects of all Protection Test Templates and
XRIO Converters. The specific aspects are covered in a PTT specific manual, which is automatically
installed with every PTL-item.
Each PTT is user adaptable and can be extended by inserting additional tests or shortened by deleting
tests to fit the requirements of each user.

The Protection Testing Library is intended to support the advanced Test Universe and RelaySimTest user.
Advanced knowledge of the Test Universe and RelaySimTest software, the XRIO standard and the
LinkToXRIO concept are a precondition to benefit from the PTTs.

See www.omicronenergy.com for more information on the PTL.

3 Quick Start Information


Follow these steps before testing with a PTT for Test Universe:

➢ Read the PTT specific manual first.


➢ Open the OCC file (PTT for Test Universe).
➢ Enter the relay settings into the Relay Parameter Section of the XRIO Converter or import them
using one of the available import filters.
➢ Check and adapt the Additional Information parameters in the XRIO Converter.
➢ Check the Hardware Configuration and adapt it if necessary.
➢ See the connection diagram and establish all connections between the test set and the relay.
➢ Check the test points in each test module and adapt them if necessary.
➢ Follow the specific instructions contained in the Pause modules.

The Delete Inactive Test Modules button can be executed in the group User Command of the Home tab
to remove irrelevant test modules.

Follow these steps before testing with a PTT for RelaySimTest:

➢ Read the PTT specific manual first.


➢ Open the RSTT file (PTT for RelaySimTest).
➢ Enter the Power system data.
➢ Setup the Test set configurations and establish all connections between the test set(s) and the
relay(s).
➢ Check and adapt the Test cases data.
➢ Follow the instruction commands.

© OMICRON electronics GmbH 4/25


OMICRON PTL User manual

4 XRIO Converter Structure

4.1 General Structure


The XRIO Converter is already included in a Protection Test Template for Test Universe. It can be
accessed by opening the Test Object. Relay settings can be entered into the XRIO Converter either
manually or automatically, using one of the available import filters.

The XRIO Converters are divided into two root blocks, the CUSTOM block and the RIO block. The RIO
block contains the standard RIO test module interface. The CUSTOM block is re-named to match the
protection relay type modeled in the XRIO Converter. It normally has four sub-blocks:

➢ Relay Parameter Section


➢ Additional Information
➢ RIOplus
➢ Template Controller

4.2 Relay Parameter Section


The Relay Parameter Section is a collection of setting parameters of the modeled relay. Each
XRIO Converter has its own individual Relay Parameter Section to match the parameter structure of the
corresponding relay setting software as close as possible. The section might be renamed according to the
relay settings software. The Foreign ID in the XRIO Converter can be used to identify the relay
parameters.

4.3 Additional Information


The Additional Information block stores parameters and information, which are required for testing and
are not a part of the relay settings. It contains at least the following sub-blocks:

➢ General
➢ Relay Information
➢ Circuit Breaker
➢ Test Information

4.3.1 General
The General block contains detailed information for the test report, like manufacturer, device type,
substation name etc. These parameters are linked to the NamePlate block in RIOplus and from there to
the Device sub block of the RIO block. The parameters of this block have to be set by the user.

4.3.2 Relay Information


The block Relay Information contains relay specific parameters such as tolerances or angles of
directional elements. The values set in this block can be found in the relay documentation. Typically, this
block does not have to be changed.

4.3.3 Circuit Breaker


The Circuit Breaker block includes information which is required for the CB test. This section includes
parameters which have to be defined by the user.

4.3.4 Test Information


The Test Information block is used to store test parameters required for the configuration of test
modules.

© OMICRON electronics GmbH 5/25


OMICRON PTL User manual

4.4 RIOplus
The RIOplus section is divided into different sub-blocks, which include either relay information or
modeling of a certain protection function. The sub-blocks of these protection functions include all the data
required for testing the respective function.

The RIOplus block is not visible in the Standard view of the Test Object. It can be extended, but existing
parameters must not be deleted or changed.

4.5 Template Controller


The Template Controller block contains special test data, which cannot be mapped into the standardized
RIOplus or RIO sections, like the flags for the automated activation of test modules. This block can be
extended by the user with new customized blocks and parameters.

The Template Controller block is not visible in the Standard view of the Test Object. It can be
extended, but existing parameters must not be deleted or changed.

4.6 RIO
The RIO section of the XRIO Converter contains all functions required to use the specialized test
modules (like Advanced Distance or Overcurrent) provided by the OMICRON Test Universe software.

4.7 Active RIO Functions


The test modules in the PTT are mapped to the appropriate RIO function, if multiple functions of one type
are available. The mapping can be changed by opening the local Test Object in a test module and
activate the RIO function you intend to use as shown below.

Figure 1: Activating a RIO function

© OMICRON electronics GmbH 6/25


OMICRON PTL User manual

5 Relay Settings Import


Some relay manufacturers offer an export of the relay settings. Multiple relay settings import filters are
available to import these settings into the XRIO Converter of the corresponding Protection Test Template
for Test Universe. The following import filters are currently available:

➢ Filter for ABB PCM600 .xrio Settings


➢ Filter for AREVA S-R 103 .txt Settings
➢ Filter for GE Enervista .csv Settings
➢ Filter for IntelliRupter Snapshots
➢ Filter for Mitsubishi MRD/MDT
➢ Filter for NR PCS-Studio .csv Settings
➢ Filter for NSE DIGICOM .xcfg Settings
➢ Filter for Protecta/Vivavis EuroCAP .par Settings
➢ Filter for SEL 5030 .txt Settings: A filter for SEL AcSELerator Quickset relay setting exports.
➢ Filter for SEL Grid Configurator .csv Settings
➢ Filter for Siemens Digsi V3 .asc Settings
➢ Filter for SIFANG AESP Studio .csv Settings
➢ Filter for Toshiba RSM100 .csv Settings
➢ Standard Filter for XML Files: A filter for relay settings in XML format
➢ Standard Filter for XRIO Files: A filter for relay settings in XRIO format (Siemens DIGSI V4.81
and higher, Siemens DIGSI V5 8.60 and higher, …).

Application Notes on the relay settings import for selected manufacturers are available in the OMICRON
Cutomer Portal. The handling of the import filters is similar:
➢ Click the File menu in the menu bar of the Test Object and click Import relay settings....
➢ Select the matching import filter in the Import Relay Settings dialog box.

After the relay settings have been imported successfully, a message box shows the number of imported
parameters. Additionally, the imported parameters are shown as Information in the Error View of the
Test Object. When the import of a parameter fails, it gets shown as an Error or Warning.

Figure 2: Error View with information about imported parameters

© OMICRON electronics GmbH 7/25


OMICRON PTL User manual

6 Protection Test Template for Test Universe

6.1 Test Object with XRIO Converter


The test object in a Protection Test Template for Test Universe contains already the appropriate XRIO
converter, see chapter 4.

6.2 Hardware Configuration


Each Protection Test Template for Test Universe contains an individual Hardware Configuration, which
is specially adapted to the specific relay and tests. All binary inputs are normally preset to Potential Free
and can be changed to potential sensing if necessary.

The phase rotation is set fix to ABC in PTL XRIO Converters. Relay settings for the phase rotation are
not processed. If a phase rotation ACB is needed, the wiring has to be adapted:
• Connect CMC phase B to relay phase C
• Connect CMC phase C to relay phase B

6.3 Common Testing Procedures


Some functionalities and tests are standardized and appear in all PTTs – exceptions are possible.

➢ Delete inactive test modules


➢ Wiring check
➢ Initial test
➢ Trip test with circuit breaker

6.3.1 Delete Inactive Test Modules


The execution of the Delete Inactive Test Modules button deletes all inactive test modules in the OCC
document. The button is located in the Home ribbon – group User Command. Before the execution, the
settings have to be entered in the Relay Parameter Section to set the correct activation of the test
modules.

6.3.2 Wiring Check


The wiring test is used to check the Analog Output connections between the CMC test set and the relay.
The QuickCMC test module is used to inject asymmetrical voltage and current values. For transformer
protection or some feeder protection PTTs, only asymmetrical currents are injected. If the injected values
match the values measured by the relay, the test can be manually assessed as Passed.

6.3.3 Initial Test


The Initial test is used to check whether the relay reacts correctly in case of a fault on the protected
object. Additionally, the wiring of the trip signal between the test set and the relay is checked.
The Initial test simulates a fault event that is clearly different from normal load conditions. Usually, a high
fault current is injected into all three phases with the State Sequencer test module. The relay should trip
on this event, regardless of the active protection functions. The trip command and the reset of the trip
command are measured and assessed during the Initial test.

6.3.4 Trip Test with Circuit Breaker


For testing the opening time of the circuit breaker, the State Sequencer test module is used. This test is
divided into three states: pre-fault, fault and post-fault. Usually a three-phase short circuit is simulated in
the fault stage. The time between the trip command and the opening of the circuit breaker auxiliary
contacts is measured and assessed.

© OMICRON electronics GmbH 8/25


OMICRON PTL User manual

6.4 Feeder Protection Templates


Feeder protection templates mostly cover directional or non-directional overcurrent protection functions. If
a distance protection function is covered by a feeder application, see section 6.5 for details on distance
protection specific tests.

6.4.1 Main and Backup Protection

Pickup Test
The overcurrent pickup is tested using the Pick-up/Drop-off Test of the Overcurrent test module. The
smallest pickup of all active phase, residual and negative sequence overcurrent elements is tested. The
pickup and drop-off values are assessed. See the online help of the Test Universe for further information
on the Pickup/Drop-off Test tab of the Overcurrent test module.

Directional Test
The overcurrent directional characteristic is tested with the Overcurrent test module. Two Characteristic
Tests are placed inside the directional (forward or reverse) sector. Two more Characteristic Tests are
placed just outside the directional sector. It is sufficient to attest the difference between the forward and
non-directional, alternatively between the reverse and non-directional or the forward and reverse
characteristics.

Trip Time Test


The trip times are tested with Characteristic Tests of the Overcurrent test module. To minimize
influences from overcurrent stages covering different fault types (e.g. phase overcurrent in phase to
ground tests) the following three fault types are tested:
• A-B-C for testing the phase overcurrent elements
• A-N or 3I0 for testing ground or residual overcurrent elements
• I2 for testing negative sequence overcurrent elements

The trip times of directional overcurrent protection are tested with a preset angle in the corresponding
direction. There is no specific angle preset for non-directional protection.

6.4.2 Switch onto Fault Protection


There are several different versions of switch onto fault tests, due to the different algorithms used by the
relays. These tests are individually designed for each PTT. See the specific PTT manual for a detailed
description of the switch onto fault tests.

© OMICRON electronics GmbH 9/25


OMICRON PTL User manual

6.5 Line Protection Templates

6.5.1 Main Protection with Distance Protection

Directional Test
Most line protection PTTs cover distance protection functions, where the Advanced Distance test module
is used for testing the directional characteristic. It is sufficient to attest the difference between the forward
and non-directional, alternatively between the reverse and non-directional characteristics.

Set the test points for the directional test similar to the test points shown in Figure 3.

The distance direction is tested separately for fault loop A-N and fault loop A-B-C. The directional test is
not necessary for mho distance characteristics.

If a directional overcurrent function is covered by the line protection PTT, the directional test is similar to
the feeder protection directional test.

Figure 3: Directional test point placement for quadrilateral (left) and circle zone characteristic (right)

Trip Characteristic Test


For distance protection relays, the trip characteristic test is divided into two parts, a trip time test and a
distance reach test. If a directional overcurrent function is covered by the line protection template, the trip
characteristic test is similar to the feeder protection trip characteristic test.

Trip Time Test


The zone trip time is tested by a test shot placed at 90% of each active zone and 110% of the largest
zone. These shots are set on the line angle.

© OMICRON electronics GmbH 10/25


OMICRON PTL User manual

Figure 4: Distance protection trip times

Possibly there are more test shots than necessary in the trip time test modules, because the preset test
points are set relative to all possibly active distance zones in forward and reverse direction. If a distance
zone is exclusively not active or directional, the test points set relative to this distance zone collapse into
the origin of the R-X test plane. In this case, delete all unnecessary test points. The unnecessary test
points can be identified by a very small impedance value (e.g. 0.0000 µΩ or 0.000Ω) or by their zone
reference, which is set to Line length (see red markings in Figure 4).

The test shots marked with an exclamation mark, respectively colored in pink as shown in Figure 4 are out
of range. In this case, remove the link of the test current in the settings tab and set the test current
manually. Keep in mind that the test current has to be higher than the distance protection release current.

Reach Test
The distance reaches are tested by Check Tests with check lines at 0°, 90°, 180° and 270°. Each check
line is set relative to a length of 120% of all active distance zones. In some PTTs , the check lines might
be placed at the line angle instead of 90° and 270°. The check lines at 0° and 180° are not necessary for
mho distance characteristics.

© OMICRON electronics GmbH 11/25


OMICRON PTL User manual

6.5.2 Main Protection with Line Differential Protection


The tests for the line differential protection function are grouped in:
• Communication check
• Single relay tests
• End-to-end tests

The single relay tests have to be performed with active communication. Each relay has to be tested
separately. During the test it has to be ensured, that the remote end does not measure any current.
In end-to-end tests, a CMGPS 588 is required for each side to synchronize the test signals. Please see
the CMGPS 588 user manual how to setup the system. The corresponding test modules for relay 1 and
relay 2 need to be opened and then run simultaneously on both sides.

Communication Check
An Annunciation Checker test module is used to guide the tester through the process of checking the line
differential protection communications. The test steps show instructions for relay 1 and relay 2 and have
to be executed in the provided order. The test has to be assessed manually.

Pick Up Test (Single Relay Test)


The currents are ramped with the Ramping test module until the line differential protection function picks
up. The pickup value is measured and assessed.

Trip Time Test (Single Relay Test)


The trip times are tested with the State Sequencer test module. A fault on the protected line is simulated
and the trip time is assessed.

External Fault (End-to-End Test)


The State Sequencer test module is used to test the stability of the line differential protection function for
through fault conditions. A fault outside the protection area located at side 2 followed by a fault outside the
protection area located at side 1 is simulated. Both relays must not send a trip signal during the test.

Operating Characteristic (End-to-End Test)


The Diff Operating Characteristic test module is used to test the operating characteristic of the line
differential protection function. Please check and adjust the test points to fit your characteristic. Please
make sure, that equal test points are used in the corresponding test modules for both sides.

6.5.3 Backup Protection


The backup protection in line protection templates is usually a non-directional overcurrent protection. The
pickup and trip times are tested similar to the feeder protection templates. The backup protection for a
distance protection function is activated by a loss of potential, which means that zero voltage and a small
load current are injected into the relay. A preset time duration for this loss of potential state is defined. If
this time is too short to block the main protection function, increase the time manually.

Pickup Test
The smallest pickup of all active phase, residual and negative sequence overcurrent elements is tested.
The pickup and drop-off values are assessed. See the online help of the Test Universe for further
information on the Pickup/Drop-off Test tab of the Overcurrent test module.

Trip Time Test


The trip times are tested with single phase and multiphase faults. The trip times are tested with
Characteristic Tests of the Overcurrent test module.

© OMICRON electronics GmbH 12/25


OMICRON PTL User manual

6.5.4 Switch onto Fault Protection


There are several different versions of switch onto fault tests, due to the different algorithms used by the
relays. These tests are individually designed for each PTT. See the specific PTT manual for a detailed
description of the switch onto fault tests.

© OMICRON electronics GmbH 13/25


OMICRON PTL User manual

6.6 Transformer Protection Templates

6.6.1 Internal Fault Protection


Internal faults are detected by the differential protection. The tripping and the non-operating
characteristics of the differential protection are tested.

Trip Characteristic Test


The trip characteristic test is intended to check the differential protection trip in case of an internal fault.
Internal single-phase and multi-phase faults are tested with the Diff Operating Characteristic test module.
A search test is performed to verify the trip characteristic. Change the predefined test lines to fit the
characteristic set in the protection relay.

Trip Time Test


The differential trip time test is intended to check the trip of the differential protection function. The
Diff Trip Time Characteristic test module is used. A three-phase fault is preset in this test, but any required
test point can be added.

Non-Operating Characteristic Test


The non-operating Characteristic Tests are intended to check the relay behavior in case of load current
or an external fault condition. The differential protection function must not operate whereas the external
fault protection may trip depending on the current.
Multi-phase and single-phase currents through the transformer are tested with the Diff Configuration test
module. The single-phase test additionally checks the correct zero sequence current elimination. The test
has to be assessed by clicking the Passed or Failed button after a sufficient time.

6.6.2 External Fault Protection


The external fault protection is usually a combination of timed and instantaneous overcurrent protection
functions, which can be set individually for each transformer winding. Tests are prepared for the external
fault protection of each transformer winding.

Pickup Test
The pickup of the smallest active overcurrent stage is tested with a Pick-up / Drop-off Test in the
Overcurrent test module. The fault current (single-phase and multi-phase faults) is ramped until the relay
picks up.

Trip Time Test


The overcurrent trip times are tested for multi-phase and single-phase faults. The Characteristic Test of
the Overcurrent test module is used for this test.

© OMICRON electronics GmbH 14/25


OMICRON PTL User manual

6.7 Generator Protection Templates


The generator protection templates contain tests for the protection of low or high voltage generators.
Since the characteristic of the different protection functions may overlap, it may be necessary to block
some functions during a test. Therefore, follow the test instructions given in the template Pause modules.
PTTs for low voltage generators do not contain all of the tests listed below and might also work differently.

6.7.1 Generator Differential Protection

Stability Test
The blocking test is intended to check the differential protection stability in case of an external fault that
occurs on the connected power system.

Three-phase and single-phase external faults are tested with the Diff Configuration test module. The
single-phase test additionally checks the correct zero sequence current elimination in case a step-up
transformer is also inside the protected zone. The test has to be assessed by clicking the Passed or
Failed button after a sufficient time.

Characteristic Test
The characteristic test is intended to check the differential protection trip in case of an internal fault.
Single-phase and multi-phase faults are tested with the Diff Operating Characteristic test module. A
search test is performed to verify the trip characteristic. Change the predefined test lines to fit the
characteristic set in the protection relay.

Trip Time
The differential trip time test is intended to check the differential protection trip time. The
Diff Trip Time Characteristic test module is used. Single-phase and multi-phase faults are tested. One test
point is preset for each fault type, but any required test point can be added.

6.7.2 Fault on Connected Network


The generator protection template also covers tests for protection functions that usually protect the
generator from faults on the connected power system or on the connected transformer/bus. These
protection functions may also be used as a backup protection for generator faults.

Impedance Protection
The impedance protection test is divided into two parts, a trip time test and a reach test. The
Advanced Distance test module is used. Test shots are usually placed at 0° and/or 90° of each active
zone. The test points can be adapted if necessary.

Voltage-Dependent Overcurrent Protection


The pickup value and the trip time are tested. The Ramping test module is used for the pickup test. If
applicable, the VI Starting test module may be used to check the voltage-dependent pickup characteristic.
In this case, the overcurrent pickup value is checked for different voltage levels.

The Overcurrent test module is used for the trip time test. A voltage value is preset in the test module and
can be changed in the Additional Information section if necessary.

Overload Protection
The trip time is tested by simulating a three-phase overload condition. The Overcurrent test module is
used. A test shot is preset and can be changed if necessary.

6.7.3 Other Generator Protection


The following protection functions are also covered in the generator protection templates:
• Overcurrent (phase and residual)

© OMICRON electronics GmbH 15/25


OMICRON PTL User manual

• Unbalanced load (negative sequence overcurrent)


• Power (reverse and forward)
• Overexcitation (V/Hz)
• Over- and Underfrequency
• Over- and Undervoltage (phase and residual)
• Underexcitation
• Accidential Energization Protection

Overcurrent and Unbalanced Load


The overcurrent and unbalanced load (negative sequence) pickup is tested using the Pick-up/Drop-off
Test of the Overcurrent test module. The smallest pickup of all active phase, residual and negative
sequence overcurrent elements is tested. The pickup and drop-off values are measured and assessed.
The trip time is tested by simulating a suitable fault and checking the relay response. The Overcurrent test
module is used for the overcurrent and unbalanced load trip time tests. Test points are preset in this test,
but they can be adjusted if necessary.

Power
The pickup values of power protection stages are tested with the Advanced Power test module using
Power Ramps. The absolute value of the active, reactive, or apparent power is increased or decreased
depending on the power function until the relay picks up.
If available as a relay setting, directional angles of power protection functions can be tested with the
Advanced Power test module using Power Shots. The test points have to be set manually similar to
Figure 5.
The trip times of power protection stages are tested with the Advanced Power test module using Power
Shots. The test modules include pre-defined test shots. Please check and adjust the test shots if
necessary. Test shots of deactivated stages can be deleted.

Figure 5: Power test shots for directional characteristic

Overexcitation, Voltage and Frequency


The pickup of the overexcitation, voltage and frequency functions are tested with the Pulse Ramping or
Ramping test module. It is tested with a first ramp, increasing (decreasing) the related quantity (frequency
or voltage) until the pickup value is reached. If applicable, a second ramp decreases (increases) the
quantity until the pickup signal is reset. The pickup and drop-off values are measured and assessed.
The State Sequencer test module is used for the trip time tests. This test is divided into three states: pre-
fault, fault and post-fault.

© OMICRON electronics GmbH 16/25


OMICRON PTL User manual

Accidental Energization Protection


The accidental (inadvertent) energization test is intended to check the behavior of the generator protection
relay when a not-synchronized or offline generator is accidentally connected to the network. This function
is usually pre-defined in relays as a combination of timed undervoltage and instantaneous overcurrent
elements. The pickup values (voltage and current), the trip times and the blocking logic of this function are
tested. The accidental energizing tripping and blocking conditions are simulated using the
State Sequencer test module. See the template specific documentation for a detailed description of this
test.

Underexcitation
Depending on the relay parameters, either an Advanced Distance or an Advanced Power test module is
used to test the underexcitation function. See the specific PTT manual for a detailed description on the
underexcitation tests.

© OMICRON electronics GmbH 17/25


OMICRON PTL User manual

6.8 Motor Protection Templates


Motor protection templates contain tests of protection functions supervising the magnitude of current or
voltage to protect the motor.

6.8.1 Overload Protection


The overload protection comprises tests for multiple current (or voltage and current) magnitude dependent
elements, protecting the motor from overload caused by problems in the powered process.
These functions are often depending on a thermal image with additional restart inhabitation. Therefore it
may be necessary to reset the thermal image after each test shot for a correct display of the tripping
characteristic. The thermal reset unlatches the trip command and enables the next test sequences. In
some configurations the trip command will not unlatch without an additional confirmation to the relay. In
this case it is necessary to assure the unlatching manually after every test shot.

Motor Starting Protection (Acceleration Time) Trip Time Test


The Characteristic Test of the Overcurrent test module is used for trip time tests of startup supervision
functions. The pre-fault time is set to 0 s to assure activation of this function. If an additional logic is
configured for this function, corresponding conditions need to be set manually to arm the function. One
test shot relative to the minimum trip value of this function is preset in this test, but it can be adjusted if
necessary.

Thermal Overload Trip Time Test


The Overcurrent test module is used for trip time tests of the Thermal Overload function. One test relative
to the minimum trip value of this function is preset in this test, but it can be adjusted if necessary.

Load Jam Trip Time Test


Depending on the used protection function, either an Overcurrent test module or Ramping and State
Sequencer test modules are used to test the mechanical jam function. A pre-fault time is set to a time
longer than the minimum running time duration of the motor.

Loss of Load Conditions


Depending on the function used to cover the loss of load conditions, an Overcurrent test module or
Ramping and State Sequencer test modules are used for undercurrent tests. The underpower function is
tested with Advanced Power test modules.

6.8.2 Short Circuit Protection

Current Differential Protection


Stability Test
The stability test is intended to check the stability of the differential protection function in case of an
external fault that occurs on the connected power system (the protected motor supplies the fault) and
under a normal load condition (three phase, symmetrical conditions). Both cases are simulated using the
Diff Configuration test module. The test has to be assessed by clicking the Passed or Failed button after
a sufficient time.
Characteristic Test
The characteristic test is intended to check the differential protection trip in case of an internal fault. Single
phase and multiphase faults are tested with the Diff Operating Characteristic test module. A search test is
performed to verify the trip characteristic. Change the predefined test lines to fit the characteristic set in
the protection relay.

Other protection functions used to protect the motor may trip during this test, especially if higher fault
currents are injected into the relay.

© OMICRON electronics GmbH 18/25


OMICRON PTL User manual

Trip Time Test


The differential trip time test is intended to check the differential protection trip time. The
Diff Trip Time Characteristic test module is used for this test. Single phase and multiphase faults are
tested. One test point is preset for each fault type, but any required test point can be added.

Overcurrent Protection
Pickup Test
The overcurrent pickup is tested using the Overcurrent test module. The smallest pickup of all active
phase, residual, negative sequence and zero sequence overcurrent elements is tested. The pickup
current is assessed.
Trip Time Test
The trip times are tested with the Overcurrent test module.

6.8.3 Network Fault Protection

Current Unbalance Protection


Pickup Test
The current unbalance protection pickup is tested using the Overcurrent test module. This test is similar to
the test described in the Overcurrent Protection Pickup Test chapter. Depending on the type of the
unbalance element used in the relay the value of the positive sequence current is at motor nominal level
(elements comparing ratio of negative and positive sequence currents magnitude) or at zero (elements
supervising only negative sequence current magnitude).
Trip Time Test
The trip times of the current unbalance protection are tested with the Overcurrent test module. This test is
similar to test described in Overcurrent Protection Trip Time Test chapter. Additionally the load current is
at motor nominal level (elements comparing ratio of negative and positive sequence currents magnitude)
or at zero (elements supervising only negative sequence current magnitude).

Overvoltage / Undervoltage Protection


Pickup Test
The pickup is tested with the Ramping test module. It is tested with a first ramp, increasing (decreasing)
the related quantity (phase voltage magnitude or negative sequence voltage magnitude,) until the pickup
value is reached. If applicable, a second ramp decreases (increases) the quantity until the pickup signal is
reset. The pickup and drop-off values are measured and assessed.
Trip Time Test
The trip time of the function is tested by simulating a suitable fault and checking the relay response.
The State Sequencer test module is used. This test is divided into three states: pre-fault, fault and post-
fault.

© OMICRON electronics GmbH 19/25


OMICRON PTL User manual

6.9 Radial Feeder Recloser Test Templates

6.9.1 Metering Test


The purpose of the Metering Test is to check the correct analog input configuration of the recloser
controller under test. The Quick CMC test module is used to inject slightly asymmetrical voltages and
currents, which can be compared with the currents and voltages measured by the recloser controller.
If the injected values match the measured values, the test can be assessed manually as Passed.

6.9.2 Minimum Trip Current Tests


The Minimum Trip Current of phase and neutral/ground overcurrent elements is tested using the Ramping
test module. The Minimum Trip Current setting of all active phase, neutral and residual ground
overcurrent elements is tested. The test current is ramped until it exceeds the set Min. Trip Current.
The dt setting of the ramp, which specifies the time between two ramp steps, is not linked and preset to
sufficient time to test the Min. Trip Current of inverse overcurrent characteristics. This setting can be
adapted manually if longer or shorter time intervals are needed.

The Ground Minimum Trip Current Test might interfere with the Sensitive Earth Fault function, when SEF
is set with a low minimum trip current and a long trip time. To avoid this interference, the Ground Minimum
Trip Current Test uses the Pulse Ramping test module when a SEF function is activated in the recloser
controller. The test current is pulsed with the current amplitude being raised in each new current pulse.
The time of each of the current pulses is short enough to force the ground overcurrent element to trip
without tripping the SEF element.

6.9.3 High Current Trip Tests


The High Current Trip of phase and neutral/residual ground overcurrent elements is tested using the
Pulse Ramping test module. The test current is pulsed with the current amplitude being raised in each
new current pulse. The time of each of the current pulses is short enough to force the High Current Trip
overcurrent element to trip without tripping the inverse overcurrent element.

6.9.4 Overcurrent Characteristic Tests


The overcurrent characteristic of the phase and neutral/residual ground overcurrent elements is tested
with the Overcurrent test module. Test points are preset but can be adapted to fit all needs. Basically, the
test of the overcurrent characteristic is similar to the overcurrent Characteristic Tests in feeder
applications described in the Feeder Protection Templates chapter of this manual.

6.9.5 Cold Load Pickup or Delay Curve Characteristic Tests


The delay curve of recloser controllers is tested in combination with the Cold Load Pickup function. When
a Close command is sent by pressing the Close button on the recloser controller, the Cold Load Pickup
function is activated and disables fast curve tripping for a set time. The Overcurrent test module is used
for the Delay Curve Characteristic Test. To test the delayed overcurrent curve, three test points are
defined on this curve and one test point is defined to verify the modified Minimum Trip Current setting.
The Close button on the recloser controller has to be pressed before a test point is executed. A message
box instructs the user to press the close button.
Both phase and ground delay curves and Cold Load Pickup Minimum Trip Current settings are tested.

6.9.6 Successful Reclose Sequence Tests


Successful reclosing sequences are tested using the State Sequencer test module. A successful reclosing
sequence is tested for all possible combinations of shots. If four shots to lockout are set, successful
reclosing sequences are tested with one shot, two shots and three shots.
The Successful Reclose Sequence tests start with either a Defeat CLPU / Reset Recloser state, when the
recloser locked out at the end of the preceding test, or a pre fault state, when the preceding test finished
with a closed recloser. Each shot is tested with a fault state, forcing the recloser to trip, and an Interval
state, awaiting the close command. If necessary, Transition States between Fault and Interval states are
added to allow the CB simulation to react before switching to the next state if the recloser controller
evaluates trip and close operations very strictly (Cooper F6 or F5). The Successful Reclose Sequence
Tests end with a Fault Cleared state, simulating normal load conditions after the fault has been cleared.

© OMICRON electronics GmbH 20/25


OMICRON PTL User manual

The time settings for all fault states are not linked. They may have to be adapted if the preset time is not
sufficient for the active settings.
All trip times are measured; all Interval times are measured and assessed. Additionally, a Level
Assessment of the Fault Cleared state is implemented, which assesses that no trip command must be
sent during the Fault Cleared state.
Successful reclosing sequences are tested for phase and ground faults.

6.9.7 Reclose Sequence to Lockout Tests


Reclosing Sequences to Lockout are tested using the State Sequencer test module. The reclosing
sequence to lockout test is similar to the Successful Reclose Sequence Tests.
The test starts with a pre fault state simulating normal load conditions, followed by a sequence of Fault
and Interval states. The number of Fault and Interval states depends on the number of shots to lockout
set in the recloser controller. Four shots to lockout means there are three Fault states followed by an
Interval state and one last Fault State driving the recloser controller to lockout.
The Lockout State will time out after 2 times the longest set interval time. This ensures that no Close
command is sent after the last fault in the sequence. To assess that there is no follow up close after the
last fault, an End of Test state is added, which serves as a stop condition for a time measurement of the
Lockout state.
All trip times are measured; all Interval times and the time out of the Lockout state are measured and
assessed. Sequence-to-Lockout tests are performed for phase and ground faults.

6.9.8 Reset Timer Tests


The reset timer is tested with the State Sequencer test module. The test is divided into two parts: The first
part interrupts a reclosing sequence (shot counter > 1) and waits until just before the reset timer times out.
The second test interrupts a reclosing sequence and waits until the reset times out. A new reclosing
sequence is then started and continues until the recloser controller locks out.

Only the Interval times are measured and assessed in the Reset Timer tests. Additionally, Level
Assessments are active to ensure that no Trip command is sent during the Reset Time state and that no
Close command is sent during the Lockout state.

6.9.9 High Current Lockout Tests


High Current Lockout is tested with the State Sequencer test module. The tests are intended to check the
correct interruption of a reclosing sequence when the set High Current Lockout current is exceeded.
A high current fault is simulated, which drives the recloser controller into lockout immediately.
The time out of the Lockout state is measured and assessed. Additionally, a Level Assessment is active to
check that no Close command is sent during the Lockout state.
High Current Lockout is tested for phase and ground faults.

6.9.10 Sequence Coordination Tests


Sequence Coordination is tested with the State Sequencer test module. The Sequence Coordination tests
are intended to check if the recloser controller is "in step" with an assumed downstream recloser, when
the downstream device clears a fault without reaction of the local recloser controller.
The reclose sequence in this test is similar to the Reclose Sequence to Lockout test. The main difference
is that one or more Fault states of the original sequence are replaced with a Sequence Coordination state.
The Sequence Coordination State simulates the same fault conditions as a Fault state from the original
sequence, but it times out before the recloser controller is able to send a trip command. The shot counter
will increment as the Sequence Coordination state is recognized as a fault.
All possible combinations of Sequence Coordination and Fault operations are tested. The trip times in all
Fault states are measured; all Interval times are measured and assessed.
Sequence Coordination is tested for phase and ground faults.

6.9.11 Sensitive Earth Fault Min Trip


Sensitive Earth Fault Min Trip is tested with the Ramping test module. The current in one phase is ramped
until the SEF Min Trip setting is exceeded. The time between two ramp steps is greater than the SEF trip
time setting. The Min Trip Current is measured and assessed.

© OMICRON electronics GmbH 21/25


OMICRON PTL User manual

6.9.12 Sensitive Earth Fault Trip Time


Sensitive Earth Fault Trip Times are tested with the State Sequencer test module. The test contains three
states: Defeat CLPU / Reset Recloser, Fault and End of Test. In the Fault state, a current exceeding the
SEF Min Trip setting is injected in one phase. The trip time is measured and assessed.

6.9.13 Sensitive Earth Fault Sequence


The Sensitive Earth Fault Sequence Tests are similar to the ground reclosing sequence tests. See the
Successful Reclose Sequence Tests and Reclose Sequence to Lockout Tests chapters for details.

6.9.14 Underfrequency Pickup


The Underfrequency Pickup is tested with the Ramping test module. The voltage frequency in all three
phases is decreased until the frequency protection trips. The time between two ramp steps is greater than
the underfrequency trip time. The frequency pickup is measured and assessed.

6.9.15 Underfrequency Trip Times


Underfrequency Trip Times are tested with the State Sequencer test module. The test contains three
states: Pre fault, Fault and Post Fault. In the Fault state, a voltage frequency below the Underfrequency
Min. Trip setting is injected in all three phases. The trip time is measured and assessed.

© OMICRON electronics GmbH 22/25


OMICRON PTL User manual

7 Protection Test Template for RelaySimTest

7.1 Hardware Configuration


Each Protection Test Template for RelaySimTest contains individual Test set configurations, which is
specially adapted to the specific relay and tests. The type of binary inputs is preset to dry and can be set
to wet if necessary.

7.2 General Test Preparations

7.2.1 Power System Data


The data for the power system has to be entered before testing. Every PTT specific manual contains a
mapping table for the required RelaySimTest data and the relay settings.
Ideally, the power system data is taken from a network calculation software or other databases instead
the relay settings to extend the testing depth and improve the general quality of testing.

7.2.2 Test Case Data


The data for the test cases has to be entered before testing. Every PTT specific manual contains a
mapping table for the required RelaySimTest data and the relay settings.
Ideally, the test case data is taken from the general protection concept for the power grid instead the relay
settings to extend the testing depth and improve the general quality of testing.

7.2.3 Wiring Check


RelaySimTest offers a built-in Check wiring functionality for all configured test sets.

7.3 Line Protection Templates


Main protection functions which require transient signals, for example travelling wave differential, may be
tested with RelaySimTest.

7.3.1 Automatic Reclosing

Functionality
The PTTs cover tests for a 1-/3-pole automatic reclosing (AR) mode using a protection area of 100% line
length. This may be a differential protection function or an overreaching zone of a distance protection
function. The templates have to be adapted, if you are using a different application concerning mode or
additional signals, e.g. a CB ready signal or CB aux. contacts.

Important: The Iterative Closed-Loop simulation method of RelaySimTest is used for testing the AR
function. Further information can be found in the RelaySimTest help.

Test Scenarios
The AR function is tested with faults at 100% line length (resp. on both line ends for end-to-end tests).
The phase-selective trip signals and the close command signal of the relay are measured and assessed.
In the AR successful (cycle 1) test, the line fault extinguishes after a time delay of 100 ms. In the AR
successful after cycle 2 test, the line fault has to extinguish during the second interruption. Therefore, the
Delay since previous event for the Line fault 1 inactive event (see Figure 6) has to be set greater than
the dead time of the first AR cycle plus a time which covers two trip times and CB opening times (e.g.
200 ms). In the AR unsuccessful test, the fault remains until the end of the test.
For cross-checking an AR distance zone, the power system has to be extended by a following line. The
tests have to be created manually.

© OMICRON electronics GmbH 23/25


OMICRON PTL User manual

Figure 6: Line fault 1 inactive event

7.3.2 Teleprotection with Distance Protection

Functionality
The PTTs cover tests for the teleprotection with distance protection function and the following modes:
• Permissive Underreach
• Permissive Overreach
• Blocking

Test Scenarios
The teleprotection with distance protection function is tested with significant faults at the following
locations:
• Busbar 1
• Busbar 2
• Line, 0%
• Line, 50%
• Line, 100%

The trip signals and the send signal of the relay are measured and assessed according to the expected
relay behavior of the teleprotection mode. The assessment of the send signal is important to differentiate
between the three teleprotection modes.

Important: The Iterative Closed-Loop simulation method of RelaySimTest is disabled for testing the
teleprotection function. With Iterative Closed-Loop enabled, please adjust the trip time assessments for
the “Fault on Busbar” test cases according to your application (iterative tripping of relay 1 and relay 2
possible). Further information about Iterative Closed-Loop can be found in the RelaySimTest help.

7.3.3 Weak Infeed for Teleprotection with Distance Protection

Functionality
The PTTs cover tests for the different modes of the weak infeed function for teleprotection with distance
protection:
• Only echo (with Permissive Overreach)
• Only weak infeed operate (with Permissive Overreach or Underreach)
• Echo and weak infeed operate (with Permissive Overreach)

Test Scenarios
The weak infeed function in a permissive overreach scheme is tested with significant faults at the
following locations:
• Busbar 1
• Busbar 2
• Line, 0%
• Line, 100%

The weak infeed function in a permissive underreach scheme is tested with significant faults at the
following locations:
• Busbar 1
• Busbar 2
• Line, 50%

© OMICRON electronics GmbH 24/25


OMICRON PTL User manual

The trip signals and the send/echo signals of the relay are measured and assessed according to the
expected relay behavior of the weak infeed mode.

Important: The tests are simulated with no infeed at Busbar 1.

© OMICRON electronics GmbH 25/25

You might also like