INTRODUCTION
ABSTRACT
Electricity is the driving force behind progress in all Nowadays, to interact with any electrical system, prior knowl-
industry and globally, the most widely-used form of edge of the standards that establish the requirements for the di-
energy currently used; however, if it is not used properly agnosis and evaluation of an electrical installation is required.
and workers do not have the necessary training, there is
potential for it to cause damage. This research studies This knowledge aims at identifying dangerous conditions, phys-
the main hazards regarding electricity: electric arc and ical deterioration, misuse and other situations that increase the
electric shock. For this reason, an electrical safety probability of risk to people and their property (Carlos & Campos,
methodology that consists in recognizing the hazards 2013). Accordingly, there are safety requirements at the national
associated with the use of electricity to take preventive
actions to avoid hazards that cause injury or death is level set forth in Supreme Decree No. 024-2016-EM, Reglamen-
applied. After performing an analysis on electric arc and to de Seguridad y Salud Ocupacional en Minería [Regulations
shock, results contributed to the prevention of accidents on Occupational Safety and Health in Mining] (Ministerio de En-
in the workplace, per the NFPA 70E and IEEE 1584-2002 ergía y Minas, July 28, 2016); and in Ministerial Resolution No.
standards.
111-2013-MEM-DM, Reglamento de Seguridad y Salud en el
Keywords: electrical safety; electric arc; electric shock. Trabajo con Electricidad [Regulations on Electrical Occupational
Safety and Health] (Merino, March 17, 2013).
1 Industrial engineer. Currently working as Occupational Health and Safety engineer at the
Compañía Minera Antapaccay. (Arequipa, Peru).
ORCID: https://orcid.org/0000-0002-1133-6875
E-mail: Frank.Neyra@glencore.com.pe
Sobrino (2013) mentions that continuous improve- considered. Finally, Trejo’s paper was also examined
ment and its application can solve anticipated (2013). It compares the NFPA 70E and IEEE 1584-
problems and help in the management of potential 2002 standards and determines the workers’ incident
hazards, taking into account that it is a cycle that energy exposure, finding some criteria for an indus-
must be constantly repeated. Likewise, Niebel and trial power electrical system in which the magnitude
Freivalds (2009) note that accidents are the result of of operating voltage and short-circuit current (electric
a sequence of events caused by multiple reasons. arc) can harm people. In addition, hazard risk cat-
On the other hand, Bird’s accident causation theory egory is established according to the incident ener-
attempts to neutralize the destructive effects of po- gy level and safety equipment (personal protective
tential or actual losses, which are the consequence equipment) is identified to prevent accidents.
of unwanted events. Therefore, the correct applica-
tion of a professional’s knowledge and techniques to METHODOLOGY
methods and work procedures can reduce the losses
caused by such events (Vásquez, March 27, 2017). This is a quantitative research project, as numer-
ical measures and reports were used. The main
Considering the above, the main objective of this techniques used were interview, observation and
article is to relate working conditions to electrical analysis of data or documentary research. See the
hazards; in addition, it seeks to enhance knowledge description below:
regarding exposure to electrical hazards in order
to prevent accidents. Pursuant to those purposes, • Interview was direct and was conducted on
specific objectives are set to identify how a factor the maintenance personnel.
contributes to the energy intensity of an electric arc
• Observation was direct and structured,
and shock, and to suggest a way to prevent or re-
because an observation (structured) guide,
duce accidents related to them. It should be not-
frequency list, checklist, anecdotal record
ed that the purpose of this article is consistent with
and field journal were used.
Bird’s theory, as the causes and effects that cause
accidents in the industry should be neutralized by • Documentary analysis considered a variety of
the managing of hazards; thus, this research en- sources as secondary data, such as previous
courages the contribution of preventive solutions to research, books, reports, reports, guides,
avoid accidents related to electricity, including the manuals, electronic documents and web
use of personal protective equipment and technolo- pages, requirements for the implementation of
gy that reduces the severity of hazards. an OHS management system (OHSMS) and
national and international legal standards.
Finally, this study considers the contributions of oth-
It is also explanatory, because a causal relationship
er research related to electrical safety, such as that
was established; that is, not only was an attempt
of López (2003), who designed a program in Micro-
made to describe or approach a problem, but also
soft Visual Basic 6.0 whose objective is to analyze
to find its causes.
electrical hazards that occur in offices and computer
centers, through the identification of hazards and the On the other hand, the unit of analysis correspond-
proposal of corrective actions. Similarly, the study by ed to a group of workers of the electrical mainte-
Clavijo, Vera and Landín (2009), which helps to pre- nance area. The measurement, subject of interest
vent fires by analyzing risks and hazards at energy of this study, was conducted on this area.
transformation stations and engine control centers,
is taken into account. In turn, Rivadeneira and Tor- In regard to the methodology used for the hazard
res’ thesis (2010) is also considered. They conduct- analysis, a study of the possibilities and conse-
ed a failure analysis and control on electrical risk quences of each electrical hazard (arc and electric
protection components and proposed focusing on shock) was conducted in such a way that working
various protection elements to ensure the quality of conditions can be optimized and risk can be main-
an electrical installation, showing its main character- tained at the lowest level that is reasonably possible.
istics, as well as the use of mandatory personal pro- For electric arc hazard, the National Fire Protection
tective equipment at work to save lives. In addition, Association (2012) and the Institute of Electrical and
the hazard analysis and management conducted by Electronics Engineers (2002) establish calculation
Serrano (2011) for the maintenance of an electrical methods for incident energy and flash protection
system using the HAZOP methodology, designed to boundaries; whereas for electric shock, Ohm’s law
identify possible failures that could lead to economic, was considered to determine the passage of current
political, social and environmental problems, is also through the body in different scenarios.
Frank Neyra
This implies improvements that prevent the occur- Analysis of electric arc hazard in electrical
rence of electric arc and electric shock. systems
Electric arc and shock analyses must be performed An electric arc is composed of two stages. The first
for different activities in which a person is exposed is arc flash, measured in cal/cm2, and the second
to electrical hazards. According to the statistical re- is arc blast, which is a phenomenon characterized
sult, correlations of 0.646 and 0.878 are obtained by emitting shockwaves and by reaching high tem-
for electric arc and shock, respectively; these are peratures (peak temperature of 25,000 °C). The en-
interpreted as having a High and High-Moderate in- ergy of the electric arc ionizes the air by releasing
plasma and vapors from conductive materials. This
fluence on accident reduction. Consequently, these
phenomenon is the result of short circuits caused by
analyses represent a major contribution to the pre-
the contact between conductors (due to the lack of
vention of hazards.
insulation), heating of the circuit, failure of contac-
In other words, when managing and applying these tors to open or close circuits, materials or tools that
fall on energized lines, power surges, equipment
analyses, the variables of consequence and proba-
damage, misuse or malfunction.
bility decrease significantly; therefore, in the event
of an accident, either by electric arc or shock, the The effects and consequences of an electric arc
person would suffer minimal or insignificant harm. can be very critical, from minor to serious injuries
On the other hand, if the control measures are prop- (burns), incrustations, hearing or retinal damage
erly applied, it is very rare or unlikely that this type of and loss of life; in addition, they cause damage to
phenomenon will occur. facilities.
Reduction of
electrical accidents
Frank Neyra
Electric arc calculation according to IEEE 1584- • An arc flash mitigation system results from
2002 the creation of an alternating low-impedance
current system, which directs arc flash to a
The Institute of Electrical and Electronics Engineers controlled alternate enclosure, therefore,
(IEEE) developed empirical equations for electric preventing workers’ exposure to hazard. That
arc calculation. The following parameters and test is, when there is a circuit with low impedance,
results were applied under certain special condi- current has a greater tendency to flow along
tions (see Table 5). that path, given that, as Ohm’s law states,
lower resistance increases current intensity.
The incident energy of electric arc hazard was cal-
Thus, the fault current is directed to an
culated for the following two scenarios:
enclosure designed to withstand the release
of incident energy and prevent causing harm
• Case 1: 480 VAC voltage, with a 30 mm-gap
to people.
between conductors, in a box enclosure and
with a duration of 0.1 seconds. As a result, • The current limiting protection device system
an incident energy value of 5.12 cal/cm2 was is a conventional system that has protective
calculated at a working distance of 609 mm relays, which send a signal to a switch
and a protection boundary of 918 mm. to open a circuit due to a current fault. In
this case, the implementation of a system
• Case 2: voltage of 4.16 kVAC, with a 104 mm-
composed of relays with light sensors to emit
gap between conductors, in a box enclosure
a faster signal to the switch is intended; in
and with a duration of 0.1 seconds. As a result,
this way, the generation of an electric arc is
an incident energy value of 1.24 cal/cm2 was
prevented. It should be mentioned that the
calculated at a working distance of 910 mm
emitted signal should last less than 6 cycles.
and a protection boundary of 1352 mm.
Furthermore, there are devices that operate
For the above cases it was interpreted that, if the in 3 to 5 cycles. The time it takes to activate
voltage and gap between conductors increases, protective devices is the decisive factor in the
these are inversely proportional to the incident pow- creation of electrically safe conditions.
er generation, and that the working distance of in-
• Electricity flows through copper wires, where
cident energy is directly proportional to the above
electrons move freely, while protons and
variables.
neutrons remain still and reach a speed of up
Electric arc hazard prevention to 1 mm/s (0.001 m/s). Current is thought to
be fast because free electrons that transfer
The only safe way to prevent electric arc from occur- current flow are found throughout the circuit
ring is to de-energize the equipment before working in large quantities and high densities,
on it, and, before doing so, make sure equipment hence the speed of the current. Due to that
is really without voltage. Although there are other phenomenon, it can be said that it approaches
methods to reduce the severity of this phenomenon, the speed of light, but it is not equal, as the
here are some examples: speed of light is constant at 299 792 458 m/s.
• In other words, a protective relay usually As mentioned before, body resistance is an impor-
emits a signal in 1 cycle (0.016 s) and tant factor in determining how much current passes
switches operate in 3 to 5 cycles. If both through the body.
devices’ cycles are added together, there
is a response in 4 cycles in the best-case Electric shock calculation
scenario, and a response in 6 cycles in the
worst. If a light sensor was used, a response To calculate electric shock hazard for the cases
in 2 cycles, the time needed to save more mentioned above, it is necessary to refer to Ohm’s
than one life, is very likely. law that states that current will be equal to voltage
divided by resistance.
• Personal protective equipment (PPE) have
protection levels of 4, 8, 25 and 40 cal/cm2 In the first case, equipment with a voltage level of
for categories 1, 2, 3 and 4 respectively. 480 VAC was used, to which the following formula
These are full body suits and must meet the was applied:
standard minimum requirements.
In the event that work is required while in the pres- I = V/R … I = 480 Volts / 1000 Ohm …= 0.48 Amp
ence of an active energy source, safety checks, or 480 mA
procedures, permits and great care will be neces-
sary to perform the task. In this case, a resistance of 1000 Ohm, the average
human resistance under common working condi-
A flash arc hazard analysis will determine the arch tions, was used as reference value. However, there
flash protection boundary, i.e. the safe working dis- are factors that cause the variation of this last val-
tance, and the PPE that people must use within the ue and, therefore, the current intensity that passes
boundary. through the body is also variable.
Analysis of electric shock hazard in electrical It could be said that most of the instantaneous
systems deaths produced by an electric shock are associ-
ated with paralysis of the respiratory system (≥25
Electric shock is the best-known electrical hazard
mA), heart failure due to ventricular fibrillation (≥ 60
on which most safety standards are based.
mA) or to immediate and complete heart arrest (≥4
The effect of electric current on the body varies Amp).
in each case. The effects of electric shock range,
known as the current that passes through the body, Electric shock hazard prevention
are shown in Table 6.
For any work or environment with exposure to an
Even when shock current does not pass through a active energy source, the best form of prevention is
vital organ, it can still lead to severe injury or death to isolate the energy source and drain all residual
from internal burns (5 amperes or more); these energy. Systems that avoid direct and indirect con-
burns can cause delayed death, because they are tacts are considered protection systems. These are
internal and third-degree burns. the categories of protection:
Frank Neyra
en oficinas y centros de cómputo. (Degree [10] Rivadeneira, L. & Torres, V. (2010). Análisis
thesis). Universidad Nacional Mayor de San de fallas y control de protecciones como
Marcos, Perú. prevención de riesgos eléctricos. (Degree
thesis). Escuela Superior Politécnica del
[6] Ministerio de Energía y Minas (July 21,
Litoral, Ecuador.
2016). Decreto Supremo n.º 024-2016-
EM. Aprueban Reglamento de Seguridad [11] Serrano, J. (2011). Análisis de gestión de
y Salud Ocupacional en Minería. Retrieved riesgos en el mantenimiento de un sistema
from http://minem.gob.pe/_legislacionM. eléctrico, caso de: una subestación de alta
php?idSector=1&idLegislacion=10221. tensión. (Master thesis). Instituto Politécnico
Nacional, Mexico.
[7] Merino, J. (March 27, 2013). Resolución
Ministerial n.º 111-2013-MEM-DM. Aprueban [12] Sobrino, J. (2013) Hábitos para la mejora
Reglamento de Seguridad y Salud en el continua. Lima, Peru: Ojo Pródigo.
Trabajo con Electricidad. Retrieved from https://
[13] Trejo, J. (2013). Comparación de la Norma
www.osinergmin.gob.pe/seccion/centro_
NFPA 70E y la IEEE 1584-2002 para el análisis
documental/PlantillaMarcoLegalBusqueda/
del arco eléctrico para el uso adecuado del
Resol-111-2013-MEM-DM.pdf.
equipo de protección personal. (Degree thesis).
[8] National Fire Protection Association (2012). Instituto Politécnico Nacional, Mexico.
NFPA 70E. Standard for electrical safety in
[14] Vásquez, R. (March 27, 2017). La teoría de
the workplace. United States: National Fire
la causalidad de Frank Bird. Prevencionar.
Protection Association.
com. Retrieved from https://prevencionar.
[9] Niebel, B. & Freivalds A. (2009). Ingeniería com/2017/03/27/la-teoria-la-causalidad-frank-
industrial. Métodos, estándares y diseño del bird/.
trabajo. México D. F., Mexico: McGraw-Hill.