Series R®
Helical-rotary Chiller
Model RTAD 85-100-115-125-145-150-
165-180
250 to 650 kW (50 Hz)
RLC-PRC015-E4
Introduction
© 2008Trane RLC-PRC015-E4
Contents
Introduction 2
Application Considerations 8
Selection Procedure 11
General Data 12
Hydraulic Data 28
Controls 33
Electrical Data 38
Dimensional Data 42
Mechanical Specifications 45
RLC-PRC015-E4 3
Features and Benefits
4 RLC-PRC015-E4
Features and Benefits
obtained by reducing the rotor tip communication capability, constant supply of glycol solution. Air-
clearances. This next generation expansion valve performance and cooled chillers selected for these
compressor is no exception. With fans. In addition, each compressor lower leaving fluid temperatures are
today's advanced manufacturing is run tested to verify capacity and also selected for efficient production
technology, clearances can be efficiency. Where applicable, each of chilled fluid at nominal comfort
controlled to even tighter unit is factory preset to the cooling conditions. The ability of Trane
tolerances. This reduces the customer's design conditions, an chillers to serve "double duty" in ice
leakage between high and low example would be leaving liquid production and comfort cooling
pressure cavities during temperature set point. The end greatly reduces the capital cost of ice
compression, allowing for more result of this test program is that storage systems.
efficient compressor operation. the chiller arrives at the job site When cooling is required, ice chilled
• Capacity Control and Load fully tested and ready for glycol is pumped from the ice storage
Matching. The combination operation. tanks directly to the cooling coils. No
patented unloading system on • Factory-Installed and -Tested expensive heat exchanger is required.
Trane helical rotary screw Controls/Options Speed The glycol loop is a sealed system,
compressor utilizes the variable Installation. All Series R chiller eliminating expensive annual
unloading valve for the majority of options, including main power chemical treatment costs. The air-
the unloading function. This allows supply disconnect, low ambient cooled chiller is also available for
the compressor to modulate control, ambient temperature comfort cooling duty at nominal
infinitely to exactly match building sensor, low ambient lockout, cooling conditions and efficiencies.
load and to maintain chilled water communication interface and ice The modular concept of glycol ice
supply temperatures within ± 0.3°C making controls are factory storage systems and the proven
of setpoint. Reciprocating and installed and tested. simplicity of Trane Tracer™ controls
screw chillers that rely on stepped allow the successful blend of
capacity control must run at a reliability and energy saving
capacity equal to or greater than
Superior Control with the performance in any ice storage
the load and typically can only UCM-CLD Adaptive application.
maintain water temperature to Control™ Microprocessor The ice storage system is operated in
around ± 1°C. Much of this excess six different modes: each optimized
capacity is lost because
Module for the utility cost of the hour.
overcooling goes toward building System Options - Ice Storage 1. Provide comfort cooling with
latent heat removal, causing the Trane air-cooled chillers are well chiller
building to be dried beyond normal suited for ice production. The unique 2. Provide comfort cooling with ice
comfort requirements. When the ability to operate at decreased 3. Provide comfort cooling with ice
load becomes very low, the ambient temperature while and chiller
compressor also uses a step producing ice lends to roughly the 4. Freeze ice storage
unloader valve which is a single same work seen by the compressor. 5. Freeze ice storage when comfort
unloading step to achieve the An air-cooled machine typically cooling is required
minimum unloading point of the switches to ice production at night. 6. Off
compressor. The result of this Two things happen under this Tracer optimization software controls
design is optimized part-load assumption. First, the leaving brine operation of the required equipment
performance far superior to single temperature from the evaporator is and accessories to easily transition
reciprocating compressors and lowered to around -5.5 to -5°C. from one mode of operation to
step-only screw compressors. Second, the ambient temperature another. For example:
has typically dropped about 8.3 to Even with ice storage systems there
11°C from the peak daytime ambient. are numerous hours when ice is
Simple Installation This effectively places a lift on the neither produced nor consumed, but
• Factory Testing Means Trouble-Free compressors that is similar to saved. In this mode the chiller is the
Start-Up. All air-cooled Series R daytime running conditions. The sole source of cooling. For example,
chillers are given a complete chiller can operate in lower ambient to cool the building after all ice is
functional test at the factory. This at night and successfully produce ice produced but before high electrical
computer-based test program to supplement the next day's cooling demand charges take effect, Tracer
completely checks the sensors, demands. sets the air-cooled chiller leaving
wiring, electrical components, The Model RTAD produces ice by fluid set point to its most efficient
microprocessor function, supplying ice storage tanks with a setting and starts the chiller, chiller
RLC-PRC015-E4 5
Features and Benefits
6 RLC-PRC015-E4
Features and Benefits
RLC-PRC015-E4 7
Application Considerations
Certain application constraints therefore, unit capacity and long as this flow is equal or above
should be considered when sizing, efficiency. the minimum flow rate requirement.
selecting and installing Trane air- The microprocessor and capacity
cooled Series R chillers. Unit and Ambient Limitations control algorithms are designed to
system reliability is often dependent Trane air-cooled Series R chillers are take a minimum of 10% change in
upon properly and completely designed for year-round operation water flow rate per minute.
complying with these over a range of ambient
considerations. When the temperatures. The air-cooled Model Flow Rates out of Range
application varies from the RTAD chiller will operate in ambient Many process cooling jobs require
guidelines presented, it should be temperatures of 7 to 40 °C. flow rates that cannot be met with
reviewed with your local Trane sales Selecting the high ambient option the minimum and maximum
engineer. will allow the chiller to operate in published values within the Model
ambient temperatures above 40 °C RTAD evaporator. A simple piping
Unit Sizing and selecting the low ambient change can alleviate this problem.
Intentionally over-sizing a unit to option will increase the operational For example: A plastic injection
assure adequate capacity is not capability of the water chiller to molding process requires 5.1 l/s of
recommended. Erratic system ambient temperatures as low as 10°C water and returns that water at
operation and excessive -18 °C. For operation outside of 15.6°C. The selected chiller can
compressor cycling are often a these ranges, contact the local Trane operate at these temperatures, but
direct result of an over-sized chiller. sales office. has a minimum flow rate of 7.6 l/s.
In addition, an oversized unit is The following system can satisfy the
usually more expensive to purchase, Water Flow Limits process.
install, and operate. If over-sizing is The minimum water flow rates are
desired, consider using two units. given in this catalog. Evaporator
flow rates below the tabulated
Water Treatment values will result in laminar flow
Dirt, scale, products of corrosion causing freeze-up problems, scaling,
and other foreign material will stratification and poor control. The
adversely affect heat transfer maximum evaporator water flow
between the water and system rate is also given in the general data
components. Foreign matter in the section. Flow rates exceeding those
chilled water system can also listed may result in excessive tube
increase pressure drop and, erosion.
consequently, reduce water flow. The evaporator can withstand up to
Proper water treatment must be 50 percent water flow reduction as
determined locally, depending on Figure 2 - Evaporator flow rate out of range
the type of system and local water
characteristics. Neither salt nor
brackish water is recommended for
use in Trane air-cooled Series R
chillers. Use of either will lead to a
shortened life to an indeterminable
degree. The Trane Company
encourages the employment of a
reputable water treatment specialist,
familiar with local water conditions,
to assist in this determination and in
the establishment of a proper water
treatment program.
8 RLC-PRC015-E4
Application Considerations
Leaving Water Temperature Range. Leaving Water Temperature out of drops from 3.3 to 10 °C may be used
Trane air-cooled Series R chillers Range as long as minimum and maximum
have three distinct leaving water Similar to the flow rates above, water temperature and minimum
categories: standard, low many process cooling jobs require and maximum flow rates are not
temperature, and ice making. The temperature ranges that cannot be violated. Temperature drops outside
standard leaving solution met with the minimum and this range are beyond the optimum
temperature range is 4.4 to 15.6 °C. maximum published values for the range for control and may adversely
Low temperature machines produce Model RTAD evaporator. A simple affect the microcomputer's ability to
leaving liquid temperatures less piping change can alleviate this maintain an acceptable supply water
than 4.4 °C. Since liquid supply problem. For example: A laboratory temperature range. Furthermore,
temperature setpoints less than load requires 7.6 l/s of water temperature drops of less than 3.3
4 .4 °C result in suction entering the process at 29.4°C and °C may result in inadequate
temperatures at or below the returning at 35°C. The accuracy refrigerant superheat. Sufficient
freezing point of water, a glycol required is better than cooling tower superheat is always a primary
solution is required for all low can give. The selected chiller has concern in any direct expansion
temperature machines. Ice making adequate capacity, but a maximum refrigerant system and is especially
machines have a leaving liquid leaving chilled water temperature of important in a package chiller where
temperature range of -6.7 to 15.6 15°C. the evaporator is closely coupled to
°C. Ice making controls include dual the compressor. When temperature
set point controls and safeties for In the example shown, both the drops are less than 3.3 °C, an
ice making and standard cooling chiller and process flow rates are evaporator runaround loop may be
capabilities. Consult your local Trane equal. This is not necessary. For required.
sales engineer for applications or example, if the chiller had a higher
selections involving low flow rate, there would simply be Ice Storage Provides Reduced
temperature or ice making more water bypassing and mixing Electrical Demand
machines. The maximum water with warm water. An ice storage system uses a
temperature that can be circulated standard chiller to make ice at night
through an evaporator when the Supply Water Temperature Drop when utilities charge less for
unit is not operating is 42 °C . The performance data for the Trane electricity. The ice supplements or
air-cooled Series R chiller is based even replaces mechanical cooling
on a chilled water temperature drop during the day when utility rates are
of 5°C. Chilled water temperature at their highest. This reduced need
for cooling results in big utility cost
Figure 3 - If temperatures are out of range for equipment savings.
Another advantage of ice storage is
standby cooling capacity. If the
chiller is unable to operate, one or
two days of ice may still be available
to provide cooling. In that time the
chiller can be repaired before
building occupants feel any loss of
comfort.
The Trane Model RTAD chiller is
uniquely suited to low temperature
applications like ice storage because
of the ambient relief experienced at
night. This allows the Model RTAD
chiller to produce ice efficiently, with
less stress on the machine.
Simple and smart control strategies
are another advantage the Model
1. Load 6. 15.6°C - 7.6 L/s RTAD chiller offers for ice storage
2. 35°C - 7.6 L/s 7. 15.6°C - 2.2 L/s
3. 35°C - 2.2 L/s 8. 15°C - 5.4 L/s applications. Trane Tracer® building
4. Chilled water pump 9. Chilled water pump management systems can actually
5. 21°C - 7.6 L/s 10. 35°C - 5.4 L/s anticipate how much ice needs to be
RLC-PRC015-E4 9
Application Considerations
Applications Types
• Comfort cooling.
• Industrial process cooling.
• Ice/thermal storage.
• Low temperature process cooling.
10 RLC-PRC015-E4
Selection Procedure
Performance
The computer selection program
provides performance data for each
chiller selection.
Dimensional Drawings
The dimensional drawings illustrate
overall measurements of the unit.
Also shown are the service
clearances required to easily service
the RTAD chiller. All catalog
dimensional drawings are subject to
change. Current submittal drawings
should be referred to for detailed
dimensional information. Contact
the sales office for submittal
information.
RLC-PRC015-E4 11
General Data
SI Units
Table G-1 - General Data RTAD Standard
Size 85 100 115 125 145 150 165 180
Cooling capacity (5) (6) kW 275.0 335.8 392.0 447.2 516.9 552.7 602.6 647.3
Power input (7) kW 99.7 129.2 149.1 187.4 191.1 210.4 223.1 243.5
Energy Efficiency Ratio (5) (6)
(as Eurovent) kW/kW 2.76 2.60 2.63 2.39 2.71 2.63 2.70 2.66
ESEER (as Eurovent) kW/kW 3.49 3.32 3.41 3.21 3.51 3.33 3.40 3.27
IPLV (According to ARI conditions
44°F leaving water temperature,
95°C entering air temperature) kW/kW 3.94 3.72 3.86 3.67 3.94 3.75 3.77 3.68
Compressor
Quantity 2 2 2 2 2 2 2 2
Nominal Size (1) tons 40/40 50/50 60/60 70/70 85/70 85/85 100/85 100/100
Evaporator
Evaporator Model EG120 EG140 EG170 EG200 EG200 EG200 EG250 EG250
Water Storage l 106 270 222 204 204 204 415 415
Minimum Flow l/s 4.1 6.0 7.3 8.8 8.8 8.8 11.6 11.6
Maximum Flow l/s 17.3 20.8 24.6 30.7 30.7 30.7 38.0 38.0
Condenser
Qty of Coils 2 2 2 2 2 2 2 2
Coil Length mm 2743 3658 3658 3658 4572 4572 5486 5486
Coil Height mm 1626 1626 1626 1626 1626 1626 1626 1626
Fin series fins/ft 192 192 192 192 192 192 192 192
Number of Rows 3/3 2/2 3/3 3/3 3/3 3/3 3/3 3/3
Condenser Fans
Quantity (1) 3/3 3/3 3/3 3/3 5/4 5/5 6/5 6/6
Diameter mm 762 762 762 762 762 762 762 762
Total Air Flow m3/s 23.52 28.09 26.71 26.73 36.99 39.24 44.89 47.08
Nominal RPM 915 915 915 915 915 915 915 915
Tip Speed m/s 37.1 37.1 37.1 37.1 37.1 37.1 37.1 37.1
Motor kW kW 2.05 2.05 2.05 2.05 2.05 2.05 2.05 2.05
Minimum Starting/Oper Ambient(2)
Standard Unit °C 0 0 0 0 0 0 0 0
Low Ambient Unit °C -18 -18 -18 -18 -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2 2 2
% Minimum. Load (3) 17 17 17 17 17 17 17 17
Operating Weight (4) kg 2760 3205 3655 3670 4260 4520 5440 5525
Shipping Weight (4) kg 2660 2940 3440 3470 4060 4320 5030 5115
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
12 RLC-PRC015-E4
General Data
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
RLC-PRC015-E4 13
General Data
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
14 RLC-PRC015-E4
General Data
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
RLC-PRC015-E4 15
General Data
Table G-5 - General Data RTAD Standard Low Noise with Night Noise Set Back option
Size 85 100 115 125 145 150 165 180
Cooling capacity (5) (6) kW 251.0 318.9 366.4 398.0 483.1 508.4 569.6 605.5
Power input (7) kW 109.4 133.3 159.4 194.5 207 231.8 238.7 264.3
Energy Efficiency Ratio (5) (6)
(as Eurovent) kW/kW 2.30 2.39 2.30 2.05 2.34 2.20 2.39 2.29
ESEER (as Eurovent) kW/kW 3.28 3.26 3.20 2.93 3.32 3.07 3.26 3.05
IPLV (According to ARI conditions
44°F leaving water temperature,
95°C entering air temperature) kW/kW 3.76 3.70 3.69 3.41 3.78 3.52 3.69 3.50
Compressor
Quantity 2 2 2 2 2 2 2 2
Nominal Size (1) tons 40/40 50/50 60/60 70/70 85/70 85/85 100/85 100/100
Evaporator
Evaporator Model EG120 EG140 EG170 EG200 EG200 EG200 EG250 EG250
Water Storage l 106 270 222 204 204 204 415 415
Minimum Flow l/s 4.1 6.0 7.3 8.8 8.8 8.8 11.6 11.6
Maximum Flow l/s 17.3 20.8 24.6 30.7 30.7 30.7 38 38
Condenser
Qty of Coils 2 2 2 2 2 2 2 2
Coil Length mm 2743 3658 3658 3658 4572 4572 5486 5486
Coil Height mm 1626 1626 1626 1626 1626 1626 1626 1626
Fin series fins/ft 192 192 192 192 192 192 192 192
Number of Rows 3/3 2/2 3/3 3/3 3/3 3/3 3/3 3/3
Condenser Fans
Quantity (1) 2/2 3/3 3/3 3/3 4/4 4/4 5/5 5/5
Diameter mm 762 762 762 762 762 762 762 762
Total Air Flow m3/s 13.97 21.28 19.94 19.96 25.78 25.79 31.55 31.57
Nominal RPM 550 550 550 550 550 550 550 550
Tip Speed m/s 28.1 28.1 28.1 28.1 28.1 28.1 28.1 28.1
Motor kW kW 1.05 1.05 1.05 1.05 1.05 1.05 1.05 1.05
Minimum Starting/Oper Ambient(2)
Standard Unit °C 0 0 0 0 0 0 0 0
Low Ambient Unit °C -18 -18 -18 -18 -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2 2 2
% Minimum Load (3) 17 17 17 17 17 17 17 17
Operating Weight (4) kg 2670 3205 3655 3670 4360 4620 5540 5625
Shipping Weight (4) kg 2560 2940 3440 3470 4160 4420 5130 5215
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
16 RLC-PRC015-E4
General Data
Table G-6 - General Data RTAD High Efficiency Low Noise with Night Noise Set Back option
Size 85 100 115 125 145 150
Cooling capacity (5) (6) kW 285.9 334.4 402.9 459.2 502.8 534.1
Power input (7) kW 97.5 128.6 150 189.6 191.0 213.0
Energy Efficiency Ratio (5) (6)
(as Eurovent) kW/kW 2.93 2.60 2.69 2.42 2.63 2.51
ESEER (as Eurovent) kW/kW 3.96 3.54 3.53 3.29 3.55 3.32
IPLV (According to ARI conditions
44°F leaving water temperature,
95°C entering air temperature) kW/kW 4.49 4.05 4.00 3.76 3.99 3.77
Compressor
Quantity 2 2 2 2 2 2
Nominal Size (1) tons 40/40 50/50 60/60 70/70 85/70 85/85
Evaporator
Evaporator Model EG140 EG170 EG200 EG200 EG250 EG250
Water Storage l 270 222 204 204 415 415
Minimum Flow l/s 6.0 7.3 8.8 8.8 11.6 11.6
Maximum Flow l/s 20.8 24.6 30.7 30.7 38 38
Condenser
Qty of Coils 2 2 2 2 2 2
Coil Length mm 3658 3658 4572 4572 5486 5486
Coil Height mm 1626 1626 1626 1626 1626 1626
Fin series fins/ft 192 192 192 192 192 192
Number of Rows 3/3 3/3 3/3 3/3 3/3 3/3
Condenser Fans
Quantity (1) 3/3 3/3 4/4 4/4 5/5 5/5
Diameter mm 762 762 762 762 762 762
Total Air Flow m3/s 19.89 19.92 25.73 25.76 31.51 31.53
Nominal RPM 550 550 550 550 550 550
Tip Speed m/s 28.1 28.1 28.1 28.1 28.1 28.1
Motor kW kW 1.05 1.05 1.05 1.05 1.05 1.05
Minimum Starting/Oper Ambient(2)
Standard Unit °C 0 0 0 0 0 0
Low Ambient Unit °C -18 -18 -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2
% Minimum Load (3) 17 17 17 17 17 17
Operating Weight kg 3440 3570 4005 4115 5490 5545
Shipping Weight kg 3175 3245 3800 3915 5080 5135
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
RLC-PRC015-E4 17
General Data
Table G-7 - General Data RTAD Standard High External Static Pressure
Size 85 100 115 125 145 150 165 180
Cooling capacity (5) (6) kW 264.4 317.5 366.0 397.7 492.2 526.7 577.7 621.3
Power input (7) kW 113.3 145.1 170.4 205.4 217.6 238.9 253.2 275.9
Energy Efficiency Ratio (5) (6)
(as Eurovent) kW/kW 2.33 2.19 2.15 1.94 2.26 2.21 2.28 2.25
ESEER (as Eurovent) kW/kW 2.91 2.80 2.83 2.65 2.94 2.80 2.86 2.76
IPLV (According to ARI conditions
44°F leaving water temperature,
95°C entering air temperature) kW/kW 3.25 3.17 3.23 3.06 3.31 3.16 3.21 3.11
Compressor
Quantity 2 2 2 2 2 2 2 2
Nominal Size (1) tons 40/40 50/50 60/60 70/70 85/70 85/85 100/85 100/100
Evaporator
Evaporator Model EG120 EG140 EG170 EG200 EG200 EG200 EG250 EG250
Water Storage l 106 270 222 204 204 204 415 415
Minimum Flow l/s 4.1 6.0 7.3 8.8 8.8 8.8 11.6 11.6
Maximum Flow l/s 17.3 20.8 24.6 30.7 30.7 30.7 38 38
Condenser
Qty of Coils 2 2 2 2 2 2 2 2
Coil Length mm 2743 3658 3658 3658 4572 4572 5486 5486
Coil Height mm 1626 1626 1626 1626 1626 1626 1626 1626
Fin series Fins/ft 192 192 192 192 192 192 192 192
Number of Rows 3/3 2/2 3/3 3/3 3/3 3/3 3/3 3/3
Condenser Fans
Quantity (1) 3/3 3/3 3/3 3/3 5/4 5/5 6/5 6/6
Diameter mm 762 762 762 762 762 762 762 762
Total Air Flow m3/s 18.46 21.53 20.4 20.35 28.67 30.69 34.86 36.84
Nominal RPM 935 935 935 935 935 935 935 935
Tip Speed m/s 37.3 37.3 37.3 37.3 37.3 37.3 37.3 37.3
Motor kW kW 1.05 2.05 3.05 4.05 5.05 6.05 7.05 8.05
Min Starting/Oper Ambient(2)
Standard Unit °C 0 0 0 0 0 0 0 0
Low Ambient Unit °C -18 -18 -18 -18 -18 -18 -18 -18
General Unit
Refrigerant R134a R134a R134a R134a R134a R134a R134a R134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2 2 2
% Min. Load (3) 17 17 17 17 17 17 17 17
Operating Weight (4) kg 2760 3205 3655 3670 4260 4520 5440 5525
Shipping Weight (4) kg 2660 2940 3440 3470 4060 4320 5030 5115
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
18 RLC-PRC015-E4
General Data
Table G-8 - General Data RTAD High Efficiency High External Static Pressure
Size 85 100 115 125 145 150
Cooling capacity (5) (6) kW 285.5 346.3 402.6 471.5 507.7 544.3
Power input (7) kW 108.8 138.7 164.4 200.4 207.8 228.6
Energy Efficiency Ratio (5) (6)
(as Eurovent) kW/kW 2.62 2.50 2.45 2.36 2.45 2.38
ESEER (as Eurovent) kW/kW 3.25 3.02 3.00 2.89 3.02 2.87
IPLV (According to ARI conditions
44°F leaving water temperature,
95°C entering air temperature) kW/kW 3.67 3.42 3.35 3.24 3.36 3.19
Compressor
Quantity 2 2 2 2 2 2
Nominal Size (1) tons 40/40 50/50 60/60 70/70 85/70 85/85
Evaporator
Evaporator Model EG140 EG170 EG200 EG200 EG250 EG250
Water Storage l 270 222 204 204 415 415
Minimum Flow l/s 6.0 7.3 8.8 8.8 11.6 11.6
Maximum Flow l/s 20.8 24.6 30.7 30.7 38 38
Condenser
Qty of Coils 2 2 2 2 2 2
Coil Length mm 3658 3658 4572 4572 5486 5486
Coil Height mm 1626 1626 1626 1626 1626 1626
Fin series fins/ft 192 192 192 192 192 192
Number of Rows 3/3 3/3 3/3 3/3 3/3 3/3
Condenser Fans
Quantity (1) 3/3 4/4 4/4 5/5 6/5 6/6
Diameter mm 762 762 762 762 762 762
Total Air Flow m3/s 20.5 24.62 26.71 30.74 34.92 36.91
Nominal RPM 935 935 935 935 935 935
Tip Speed m/s 37.3 37.3 37.3 37.3 37.3 37.3
Motor kW kW 1.05 2.05 3.05 4.05 5.05 6.05
Minimum Starting/Oper Ambient(2)
Standard Unit °C 0 0 0 0 0 0
Low Ambient Unit °C -18 -18 -18 -18 -18 -18
General Unit
Refrigerant R134a R134a R134a R134a R134a R134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2
% Minimum Load (3) 17 17 17 17 17 17
Operating Weight (4) kg 3340 3470 4005 4100 5390 5445
Shipping Weight (4) kg 3075 3145 3800 3900 4980 5035
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
RLC-PRC015-E4 19
General Data
English Units
Table G-9- General Data RTAD Standard
Size 85 100 115 125 145 150 165 180
Cooling capacity (5) (6) tons 78.2 95.5 111.5 127.2 147.0 157.2 171.4 184.1
Power input (7) kW 99.7 129.2 149.1 187.4 191.1 210.4 223.1 243.5
Energy Efficiency Ratio (5) (6)
(as Eurovent) MBH/kW 9.42 8.87 8.97 8.15 9.25 8.97 9.21 9.08
ESEER (as Eurovent) MBH/kW 11.91 11.33 11.63 10.95 11.98 11.36 11.60 11.16
IPLV (According to ARI conditions
44°F leaving water temperature,
95°C entering air temperature) MBH/kW 13.44 12.69 13.17 12.52 13.44 12.80 12.86 12.56
Compressor
Quantity 2 2 2 2 2 2 2 2
Nominal Size (1) tons 40/40 50/50 60/60 70/70 85/70 85/85 100/85 100/100
Evaporator
Evpaporator Model EG120 EG140 EG170 EG200 EG200 EG200 EG250 EG250
Water Storage gallon 28.0 71.3 58.6 53.9 53.9 53.9 109.6 109.6
Minimum Flow gpm 65.0 95.1 115.7 139.5 139.5 139.5 183.9 183.9
Maximum Flow gpm 274.2 329.7 389.9 486.6 486.6 486.6 602.3 602.3
Condenser
Qty of Coils 2 2 2 2 2 2 2 2
Coil Length ft 108.0 144.0 144.0 144.0 180.0 180.0 216.0 216.0
Coil Height ft 64.0 64.0 64.0 64.0 64.0 64.0 64.0 64.0
Fin series fins/ft 192 192 192 192 192 192 192 192
Number of Rows 3/3 2/2 3/3 3/3 3/3 3/3 3/3 3/3
Condenser Fans
Quantity (1) 3/3 3/3 3/3 3/3 5/4 5/5 6/5 6/6
Diameter ft 30 30 30 30 30 30 30 30
Total Air Flow cfm 49836 59519 56595 56638 78377 83145 95117 99757
Nominal RPM 915 915 915 915 915 915 915 915
Tip Speed ft/s 122 122 122 122 122 122 122 122
Motor kW kW 1.57 1.57 1.57 1.57 1.57 1.57 1.57 1.57
Minimum Starting/Oper Ambient(2)
Standard Unit °F 32 32 32 32 32 32 32 32
Low Ambient Unit °F 0 0 0 0 0 0 0 0
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2 2 2
% Minimum Load (3) 17 17 17 17 17 17 17 17
Operating Weight (4) lb 6085 7066 8058 8091 9392 9965 11993 12181
Shipping Weight (4) lb 5864 6482 7584 7650 8951 9524 11089 11277
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
20 RLC-PRC015-E4
General Data
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
RLC-PRC015-E4 21
General Data
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
22 RLC-PRC015-E4
General Data
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
RLC-PRC015-E4 23
General Data
Table G-13 - General Data RTAD Standard Low Noise with Night Noise Set Back
Size 85 100 115 125 145 150 165 180
Cooling capacity (5) (6) tons 71.4 90.7 104.2 113.2 137.4 144.6 162.0 172.2
Power input (7) kW 109.4 133.3 159.4 194.5 207 231.8 238.7 264.3
Energy Efficiency Ratio (5) (6)
(as Eurovent) MBH/kW 7.85 8.15 7.85 6.99 7.98 7.51 8.15 7.81
ESEER (as Eurovent) MBH/kW 11.19 11.12 10.92 10.00 11.33 10.47 11.12 10.41
IPLV (According to ARI conditions
44°F leaving water temperature,
95°C entering air temperature) MBH/kW 12.83 12.62 12.59 11.63 12.90 12.01 12.59 11.94
Compressor
Quantity 2 2 2 2 2 2 2 2
Nominal Size (1) tons 40/40 50/50 60/60 70/70 85/70 85/85 100/85 100/100
Evaporator
Evpaporator Model EG120 EG140 EG170 EG200 EG200 EG200 EG250 EG250
Water Storage gal. 28.0 71.3 58.6 53.9 53.9 53.9 109.6 109.6
Minimum Flow gpm 65.0 95.1 115.7 139.5 139.5 139.5 183.9 183.9
Maximum Flow gpm 274.2 329.7 389.9 486.6 486.6 486.6 602.3 602.3
Condenser
Qty of Coils 2 2 2 2 2 2 2 2
Coil Length ft 108.0 144.0 144.0 144.0 180.0 180.0 216.0 216.0
Coil Height ft 64.0 64.0 64.0 64.0 64.0 64.0 64.0 64.0
Fin series fins/ft 192 192 192 192 192 192 192 192
Number of Rows 37318 37289 37318 37318 37318 37318 37318 37318
Condenser Fans
Quantity (1) 2/2 3/3 3/3 3/3 4/4 4/4 5/5 5/5
Diameter ft 30 30 30 30 30 30 30 30
Total Air Flow cfm 29601 45090 42250 42293 54625 54646 66851 66893
Nominal RPM 690 690 690 690 690 690 690 690
Tip Speed ft/s 92 92 92 92 92 92 92 92
Motor kW kW 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75
Minimum Starting/Oper Ambient(2)
Standard Unit °F 32 32 32 32 32 32 32 32
Low Ambient Unit °F 0 0 0 0 0 0 0 0
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2 2 2
% Minimum Load (3) 17 17 17 17 17 17 17 17
Operating Weight (4) lb 5886 7066 8058 8091 9612 10185 12214 12401
Shipping Weight (4) lb 5644 6482 7584 7650 9171 9744 11310 11497
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
24 RLC-PRC015-E4
General Data
Table G-14 - General Data RTAD High Efficiency Low Noise with Night Noise Set Back
Size 85 100 115 125 145 150
Cooling capacity (5) (6) tons 81.3 95.1 114.6 130.6 143.0 151.9
Power input (7) kW 97.5 128.6 150 189.6 191 213
Energy Efficiency Ratio (5) (6)
(as Eurovent) MBH/kW 10.00 8.87 9.18 8.26 8.97 8.56
ESEER (as Eurovent) MBH/kW 13.51 12.08 12.04 11.23 12.11 11.33
IPLV (According to ARI conditions
44°F leaving water temperature,
95°C entering air temperature) MBH/kW 15.32 13.82 13.65 12.83 13.61 12.86
Compressor
Quantity 2 2 2 2 2 2
Nominal Size (1) tons 40/40 50/50 60/60 70/70 85/70 85/85
Evaporator
Evpaporator Model EG140 EG170 EG200 EG200 EG250 EG250
Water Storage gal. 71.3 58.6 53.9 53.9 109.6 109.6
Minimum Flow gpm 95.1 115.7 139.5 139.5 183.9 183.9
Maximum Flow gpm 329.7 389.9 486.6 486.6 602.3 602.3
Condenser
Qty of Coils 2 2 2 2 2 2
Coil Length ft 144.0 144.0 180.0 180.0 216.0 216.0
Coil Height ft 64.0 64.0 64.0 64.0 64.0 64.0
Fin series fins/ft 192 192 192 192 192 192
Number of Rows 37318 37318 37318 37318 37318 37318
Condenser Fans
Quantity (1) 3/3 3/3 4/4 4/4 5/5 5/5
Diameter ft 30 30 30 30 30 30
Total Air Flow cfm 42145 42208 54519 54582 66766 66808
Nominal RPM 690 690 690 690 690 690
Tip Speed ft/s 92 92 92 92 92 92
Motor kW kW 0.75 0.75 0.75 0.75 0.75 0.75
Mininimum Starting/Oper Ambient(2)
Standard Unit °F 32 32 32 32 32 32
Low Ambient Unit °F 0 0 0 0 0 0
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2
% Minimum Load (3) 17 17 17 17 17 17
Operating Weight (4) lb 7584 7871 8830 9072 12103 12225
Shipping Weight (4) lb 7000 7154 8378 8631 11199 11321
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
RLC-PRC015-E4 25
General Data
Table G-15 - General Data RTAD Standard High External Static Pressure
Size 85 100 115 125 145 150 165 180
Cooling capacity (5) (6) tons 75.2 90.3 104.1 113.1 140.0 149.8 164.3 176.7
Power input (7) kW 113.3 145.1 170.4 205.4 217.6 238.9 253.2 275.9
Energy Efficiency Ratio (5) (6)
(as Eurovent) MBH/kW 7.95 7.47 7.34 6.62 7.71 7.54 7.78 7.68
ESEER (as Eurovent) MBH/kW 9.93 9.55 9.66 9.04 10.03 9.55 9.76 9.42
IPLV (According to ARI conditions
44°F leaving water temperature,
95°C entering air temperature) MBH/kW 11.09 10.82 11.02 10.44 11.29 10.78 10.95 10.61
Compressor
Quantity 2 2 2 2 2 2 2 2
Nominal Size (1) Tons 40/40 50/50 60/60 70/70 85/70 85/85 100/85 100/100
Evaporator
Evpaporator Model EG120 EG140 EG170 EG200 EG200 EG200 EG250 EG250
Water Storage gal. 28.0 71.3 58.6 53.9 53.9 53.9 109.6 109.6
Minimum Flow gpm 65.0 95.1 115.7 139.5 139.5 139.5 183.9 183.9
Maximum Flow gpm 274.2 329.7 389.9 486.6 486.6 486.6 602.3 602.3
Condenser
Qty of Coils 2 2 2 2 2 2 2 2
Coil Length ft 108.0 144.0 144.0 144.0 180.0 180.0 216.0 216.0
Coil Height ft 64.0 64.0 64.0 64.0 64.0 64.0 64.0 64.0
Fin series fins/ft 192 192 192 192 192 192 192 192
Number of Rows 37683 37654 37683 37683 37683 37683 37683 37683
Condenser Fans
Quantity (1) 3/3 3/3 3/3 3/3 5/4 5/5 6/5 6/6
Diameter ft 30 30 30 30 30 30 30 30
Total Air Flow cfm 39115 45619 43225 43119 60748 65028 73864 78060
Nominal RPM 935 935 935 935 935 935 935 935
Tip Speed ft/s 122 122 122 122 122 122 122 122
Motor kW kW 2.23 2.23 2.23 2.23 2.23 2.23 2.23 2.23
Min Starting/Oper Ambient(2)
Standard Unit °F 32 32 32 32 32 32 32 32
Low Ambient Unit °F 0 0 0 0 0 0 0 0
General Unit
Refrigerant R134a R134a R134a R134a R134a R134a R134a R134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2 2 2
% Min. Load (3) 17 17 17 17 17 17 17 17
Operating Weight (4) lb 6085 7066 8058 8091 9392 9965 11993 12181
Shipping Weight (4) lb 5864 6482 7584 7650 8951 9524 11089 11277
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
26 RLC-PRC015-E4
General Data
Table G-16 - General Data RTAD High Efficiency High External Static Pressure
Size 85 100 115 125 145 150
Cooling capacity (5) (6) tons 81.2 98.5 114.5 134.1 144.4 154.8
Power input (7) kW 108.8 138.7 164.4 200.4 207.8 228.6
Energy Efficiency Ratio (5) (6)
(as Eurovent) MBH/kW 8.94 8.53 8.36 8.05 8.36 8.12
ESEER (as Eurovent) MBH/kW 11.09 10.30 10.24 9.86 10.30 9.79
IPLV (According to ARI conditions
44°F leaving water temperature,
95°C entering air temperature) MBH/kW 12.52 11.67 11.43 11.05 11.46 10.88
Compressor
Quantity 2 2 2 2 2 2
Nominal Size (1) tons 40/40 50/50 60/60 70/70 85/70 85/85
Evaporator
Evpaporator Model EG140 EG170 EG200 EG200 EG250 EG250
Water Storage gal. 71.3 58.6 53.9 53.9 109.6 109.6
Minimum Flow gpm 95.1 115.7 139.5 139.5 183.9 183.9
Maximum Flow gpm 329.7 389.9 486.6 486.6 602.3 602.3
Condenser
Qty of Coils 2 2 2 2 2 2
Coil Length ft 144.0 144.0 180.0 180.0 216.0 216.0
Coil Height ft 64.0 64.0 64.0 64.0 64.0 64.0
Fin series fins/ft 192 192 192 192 192 192
Number of Rows 37683 37683 37683 37683 37683 37683
Condenser Fans
Quantity (1) 3/3 4/4 4/4 5/5 6/5 6/6
Diameter ft 30 30 30 30 30 30
Total Air Flow cfm 43437 52167 56595 65134 73991 78208
Nominal RPM 935 935 935 935 935 935
Tip Speed ft/s 122 122 122 122 122 122
Motor kW kW 2.23 2.23 2.23 2.23 2.23 2.23
Minimum Starting/Oper Ambient(2)
Standard Unit °F 32 32 32 32 32 32
Low Ambient Unit °F 0 0 0 0 0 0
General Unit
Refrigerant R134a R134a R134a R134a R134a R134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2
% Minimum Load (3) 17 17 17 17 17 17
Operating Weight (4) lb 7363 7650 8830 9039 11883 12004
Shipping Weight (4) lb 6779 6934 8378 8598 10979 11100
Notes:
(1) Data containing information on two circuits shown as follows: ckt1/ckt2
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50°F) ambient and 7°C (44°F) leaving chilled water temperature, not each individual circuit.
(4) With aluminium fins.
(5) At Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air temperature.
(6) Ratings based on sea level altitude and evaporator fouling factor or 0.017615 m2°K/kW
(7) Unit kW input, including fans
RLC-PRC015-E4 27
Hydraulic Data
1 = 085 STD
2 = 115 STD, 100 HE
3 = 100 STD, 085 HE
4 = 125 STD, 145 STD, 150 STD, 115 HE, 125 HE
5 = 165 STD, 180 STD, 145 HE, 150 HE
Figure 5 - RTAD 115HE - 125HE - 145SE - 150SE Single pump available static pressure
1
2
1 = LRN 208-13/5.5
2 = LRN 208-14/7.5
3 = SIL 208-16/11
4 = SIL 208-17/15
28 RLC-PRC015-E4
Hydraulic Data
Figure 6 - RTAD 115HE - 125HE - 145SE - 150SE Dual pump available static pressure
2
1
1 = JRN 208-13/5.5
2 = JRN 208-14/7.5
3 = DIL 208-16/11
4 = DIL 208-17/15
Figure 7 - RTAD 145HE - 150HE - 165SE - 180SE Single Pump Available Static Pressure
1 = LRN 208-13/5.5
2 = LRN 208-14/7.5
3 = SIL 208-16/11
4 = SIL 208-17/15
RLC-PRC015-E4 29
Hydraulic Data
Figure 8 - RTAD 145HE - 150HE - 165SE - 180SE Dual pump Available static pressure
1 = JRN 208-13/5.5
2 = JRN 208-14/7.5
3 = DIL 208-16/11
4 = DIL 208-17/15
Figure 9 - RTAD 115HE - 125HE - 145SE - 150SE Pump Capacity Curve Single Pump
1 = LRN 208-13/5.5
2 = LRN 208-14/7.5
3 = SIL 208-16/11
4 = SIL 208-17/15
30 RLC-PRC015-E4
Hydraulic Data
Figure 10 - RTAD 115HE - 125HE - 145SE - 150 SE Pump Capacity Curve Dual Pump
1 = LRN 208-13/5.5
2 = LRN 208-14/7.5
3 = SIL 208-16/11
4 = SIL 208-17/15
Figure 11 - RTAD 145HE - 150HE - 165SE - 180SE Pump Current Curve Single Pump
25
4
20
3
15
2
A
10
1
0
0 5 10 15 20 25 30 35 40 45
1 = JRN 208-13/5.5
2 = JRN 208-14/7.5
3 = DIL 208-16/11
4 = DIL 208-17/15
RLC-PRC015-E4 31
Hydraulic Data
Figure 12 - RTAD 145HE - 150HE - 165SE - 180SE Pump Current Curve Dual Pump
2
A
1 = JRN 208-13/5.5
2 = JRN 208-14/7.5
3 = DIL 208-16/11
4 = DIL 208-17/15
32 RLC-PRC015-E4
Controls
Chiller Unit Controls No other chiller control system in addition, microcomputer controls
Trouble-Free Installation, Start-Up the marketplace duplicates this allow for more types of protection
and Operation performance. such as over and under voltage!
Adaptive Control means the Unit Overall, the safety controls help
Control Module (UCM-CLD) directly Safety Controls keep the building running and out of
senses the control variables that A centralized microcomputer offers trouble.
govern operation of the chiller: a higher level of machine protection.
motor current draw, evaporator Since the safety controls are The End Of Nuisance Trip-Outs And
temperature, condenser smarter, Unnecessary Service Calls
temperature, etc. When any of the they limit compressor operation to Unnecessary service calls and
variables approaches a limit avoid compressor or evaporator unhappy tenants are avoided. The
condition where the unit may be failures, thereby minimizing unit does not nuisance trip or
damaged or shut down on a safety, nuisance shutdown. During unnecessarily shut down. Only
the UCM takes corrective action to abnormal operating conditions, the when the UCM has exhausted the
avoid shutdown and keep the chiller UCM will continue to optimize corrective actions it can take and the
operating. It does this through chiller performance by taking the unit is still violating an operating
combined actions of compressor corrective action necessary to avoid limit will the unit shut down.
slide valve modulation, electronic shutdown. CONTROLS ON OTHER CHILLERS
expansion valve modulation and fan This keeps cooling capacity TYPICALLY SHUT DOWN THE
staging. available until the problem can be CHILLER, QUITE PROBABLY JUST
Additionally, the UCM optimizes solved. Whenever possible, the WHEN IT IS NEEDED THE MOST.
total unit power consumption chiller is allowed to perform its For example:
during normal operating conditions. function; make chilled water. In A typical five-year-old chiller with
dirty coils might trip-out on high
Figure 13 - Unit control module with Clear Language Display Keypad (UCM-CLD) pressure cutout on a 38°C day in
August. A hot day is just when
comfort cooling is needed the most.
In contrast, the air-cooled Series R
chiller with an Adaptive Control
microprocessor will stage fans on,
modulate electronic expansion
valve, and modulate slide valve as it
approaches a high pressure cutout.
Thereby KEEPING THE CHILLER ON-
LINE JUST WHEN YOU NEED IT THE
MOST.
Generic Building
Automation System
Controls
Simple Interface With Other Control
Systems
Microcomputer controls afford
simple interface with other control
systems, such as time clocks,
building automation systems and
ice storage systems. Wiring to the
unit can be as simple as two wires!
This means you can have the
flexibility to meet job requirements
while not having to learn a
complicated control system.
RLC-PRC015-E4 33
Controls
Monitoring And Diagnostics features that can be used to Automation Systems or Remote
Since the microcomputer provides interface with building control Display
all control functions, it can easily systems.
indicate such parameters as leaving External Chilled Water Set point
chilled water temperature and Allows the external setting
capacity stage. If a failure does
Standard Features: independent of the front panel
occur, one of over 90 individual External Auto/Stop setpoint by a 2-10 VDC input, or a
diagnostic and operating codes will A job site provided contact closure 4-20 mA input.
be used to indicate the problem, will turn the unit on and off.
giving more specific information Note: Do not use the chilled water External Current Limit Set point
about the failure. All of the pump to stop the chiller. Allows the external setting
monitoring and diagnostic independent of the front panel
information is displayed directly on Chilled Water flow Interlock setpoint by a 2-10 VDC input, or a
a microcomputer display. A job site provided contact closure 4-20 mA input.
from a chilled water pump contactor
Interface With The Trane Integrated or a flow switch is required and will Ice Making Control
Comfort™ System (ICS) allow unit operation if a load exists. Provides interface with ice making
When the air-cooled Series R® chiller This feature will allow the unit to control systems.
is used in conjunction with a Trane run in conjunction with the pump
Tracer® system, the unit can be system.
Chilled Water Temperature Reset
monitored and controlled from a Reset can be based on return water
remote location. The air-cooled External Interlock temperature or outdoor air
Series R chiller can be controlled to A job site supplied contact opening temperature.
fit into the overall building wired to this input will turn the unit
automation strategy by using time off and require a manual reset of the
of day scheduling, timed override, unit microcomputer. This closure is Interface with other
duty cycling, demand limiting, and typically triggered by a job site control systems
chiller sequencing. A building owner supplied system such as a fire Stand-Alone Unit
can completely monitor the air- alarm. Interface to stand-alone units is very
cooled Series R chiller from the simple; only a remote auto/stop for
Tracer system, as all of the Chilled Water Pump Control scheduling is required for unit
monitoring information indicated on Unit controls provide an output to operation. Signals from the chilled
the microcomputer can be read off control chilled water pump(s). One water pump contactor auxiliary or a
the Tracer system display. In contact closure to the chiller is all flow switch are wired to the chilled
addition, all the powerful diagnostic that is required to initiate the chilled water flow interlock. Signals from a
information can be read back at the water system. time clock or some other remote
Tracer system. Best of all, this device are wired to the external
powerful capability comes over a Remote Running and Alarm auto/stop input.
single twisted pair of wires! Indication Contacts
Air-cooled Series R chillers can The unit provides three single- Note: Do not use the chilled water
interface with many different pole/double-throw contact closures pump to stop the chiller.
external control systems, from to indicate that a failure has
simple stand- alone units to ice occurred, if any compressors are Required Features
making systems. Each unit requires running, or if the compressors are External Auto/Stop (Standard)
a single-source, three-phase power running at maximum capacity. These Chilled Water flow Interlock
supply, a 115-volt control power contact closures may be used to (Standard)
transformer handles both the trigger job site supplied alarm lights
evaporator heat tape and the unit or alarm bells. Additional Features That May Be
controls. The control transformer is Used
directly fed from the 400/3/50 supply Optional Features: Remote Running and Alarm
in the control panel. For basic stand- Communication Interface (CSR Indication Contacts (provided on the
alone applications, the interface Communication Interface Option) UCM-CLD main module)
with outside control is no different Capability for communication External Interlock (Standard)
than for other Trane chillers. withTrane Tracer ® Building Chilled Water Temperature Reset
However, the RTAD units have many
34 RLC-PRC015-E4
Controls
External Trane Devices Required - Interface With Other In addition, the signals may be
None provided over the twisted wire pair
Building Automation from a Tracer ® system.
Note: All wiring outside the unit is Systems
supplied at the job site. The air-cooled Series R chillers can Required Features
interface with non-Trane building External Auto/Stop (Standard)
automation systems via hard wire Ice Making Control (Requires CSR
TRANE Integrated connections. Several capabilities Communications Interface, option)
Comfort™ System may be utilized:
Interface Additional Features That May Be
A single twisted pair of wires tied Required Features Used
directly between the air-cooled External Auto/Stop (Standard) Remote Running and Failure
Series R ® chiller and a Tracer ® Indication Contacts
system provides control, monitoring Additional Features That May Be Communications Interface (For
and diagnostic capabilities. Control Used Tracer Systems)
functions include auto/stop, External Interlock (Standard) Chilled Water Temperature Reset
adjustment of leaving water External Demand Limit (Set point) (Indoor zone reset not available with
temperature set point, compressor (Requires CSR Communications ice making option).
operation lockout for kW demand Interface, option)
limiting and control of ice making Remote Running and Alarm External Trane Devices Required -
mode. The Tracer system reads Indication Contacts (Standard) None
monitoring information such as External Chilled Water Set point
entering and leaving evaporator (Requires CSR Communications
water temperatures and outdoor air Interface, option)
temperature. Over 60 individual Chilled Water flow Interlock
diagnostic codes can be read by the (Standard)
Tracer system. In addition, the Tracer
system can provide sequencing External Trane Devices Required -
control for two to six units on the None
same chilled water loop. Pump
sequencing control can be provided Ice Making Systems
from the Tracer system. Tracer ICS is An ice making option may be
not available in conjunction with the ordered with the air-cooled Series R®
remote display or the external set chiller. The unit will have two
point capability. operating modes, ice making and
normal daytime cooling. In the ice
Required Features making mode, the air-cooled Series
Communications Interface (Requires R chiller will operate at full
CSR Communications Interface, compressor capacity until the return
option) chilled fluid temperature entering
the evaporator meets the ice making
Additional Features That May Be set point. This ice making set point is
Used manually adjusted on the unit's
Chilled Water Temperature Reset microcomputer. Two input signals
Ice Making Control are required to the air-cooled
Series R chiller for the ice making
External Trane Devices Required option. The first is an auto/stop
Tracer Summit® or Tracer Chiller signal for scheduling and the second
Plant Control is required to switch the unit in
between the ice making mode and
normal daytime operation. The
signals are provided by a remote job
site building automation device such
as a time clock or a manual switch.
RLC-PRC015-E4 35
Controls
Required Features
Communications Interface
36 RLC-PRC015-E4
Job Site Data
RLC-PRC015-E4 RLC-PRC015-E4 37
Electrical Data
38 RLC-PRC015-E4
Electrical Data
RLC-PRC015-E4 39
Electrical Data
40 RLC-PRC015-E4
Electrical Data
RLC-PRC015-E4 41
Dimensional Data
42 RLC-PRC015-E4
Dimensional Data
RTAD RTAD A B C D E F G H J K L M N P
85 STD 85 STD3507 838 1778 1490 ---- 371 185 1372 2068 538 1792 1000 40
100-115-125
100-115-125STD STD
85-100 HE
4426 815 2840 1950 ---- 395 185 1372 2068 564 2844 2000 40
85-100 HE 100
115-125 HE
145-150 STD145-150 STD
115-125 HE 5351 1245 3302 1606 1606 415 205 1392 2088 1483 2844 1000 46
145-150 HE
165-180 STD165-180 STD
145-150 HE 6370 1723 3800 1946 1946 448 205 1492 2188 2224 2952 1000 46
Note: for High Efficiency Low noise and High ambient units, use dimensions of the High efficiency units.
RLC-PRC015-E4 43
Dimensional Data
Expansion vessel
Without Without 50 litres 50 litres 80 litres 80 litres
RTAD 115 HE - RTAD 125 HE -RTAD 145 SE - RTAD 150 SE Pump model (kg) (lbs) (kg) (lbs) (kg) (lbs)
LRN 208-13/5.5 - LRN 208-14/7.5 400 882 460 1014 500 1102
Single pump
SIL 208-16/11 - SIL 208-17/15 455 1003 515 1135 555 1224
JRN 208-13/5.5 - JRN 208-14/7.5 490 1080 550 1213 590 1301
Dual pump
SIL 208-16/11 - SIL 208-17/15 600 1323 660 1455 700 1543
RTAD 145 HE - RTAD 150 HE -RTAD 165 SE - RTAD 180 SE
LRN 208-13/5.5 - LRN 208-14/7.5 510 1124 570 1257 610 1345
Single pump
SIL 208-16/11 - SIL 208-17/15 565 625 625 1378 665 1466
Dual pump JRN 208-13/5.5 - JRN 208-14/7.5 600 1323 660 1455 700 1543
SIL 208-16/11 - SIL 208-17/15 710 1565 770 1698 810 1786
44 RLC-PRC015-E4
Mechanical Specifications
General start and operate between of 4°C (39 The unit control module, utilizing
Units are leak and pressure tested at F) to the maximum possible Adaptive Control™ microprocessor,
35 bar high side, 19 bar low side, ambient of the selected unit. automatically takes action to avoid
then evacuated and charged. unit shutdown due to abnormal
Packaged units ship with a full Compressor and Lube Oil System operating conditions associated
operating charge of oil and The rotary screw compressor is with low refrigerant temperature,
refrigerant. semi-hermetic, direct drive, 3000 high condensing temperature and
Unit panels, structural elements and rpm, with capacity control slide motor current overload. Should the
control boxes are constructed of valve, a load/unload valve, rolling abnormal operating condition
galvanized steel and mounted on a element bearings, differential continue until a protective limit is
welded structural steel base. Unit refrigerant pressure oil pump, oil violated, the unit will be shut down.
panels and control boxes are filter and oil heater. The motor is a Unit protective functions include
finished with an air-dry paint suction gas cooled, hermetically loss of chilled water flow,
RAL 1019. sealed, two-pole squirrel cage evaporator freezing, loss of
induction motor. Oil separator refrigerant, low refrigerant pressure,
Evaporator devices are provided separate from high refrigerant pressure, reverse
The evaporator is a tube-in-shell the compressor. Check valves in the rotation, compressor starting and
heat exchanger design with compressor discharge and lube oil running over current, phase loss,
internally finned copper tubes roller system are provided. phase imbalance, phase reversal,
expanded into the tube sheet. The and loss of oil flow.
evaporator is designed, tested and Refrigeration Circuits A menu driven digital display
stamped in accordance with the Each unit has two refrigerant indicates over 20 operating data
appropriate pressure vessel code circuits, with one rotary screw points including chilled water set
approval for a refrigerant side compressor per circuit. Each point, current limit Set point, leaving
working pressure of 32 bar. The refrigerant circuit includes a liquid chilled water temperature,
evaporator is designed for a water line shutoff valve, removable core evaporator and condenser
side working pressure of 14 bar. filter drier, charging port and an refrigerant pressures and
Water connections are flanged. The electronic expansion valve. Fully temperatures. Over 60 diagnostic
evaporator has one water pass with modulating compressors and checks are made and displayed
a series of internal baffles. Each electronic expansion valves provide when a problem is detected. The
shell includes a vent, a drain and variable capacity modulation over digital display can be read and
fittings for temperature control the entire operating range. advanced on the unit without
sensors and is insulated with 3 /4 - opening any control panel doors.
inch Armaflex II or equal insulation Unit Controls Standard power connections
(K=0.26). Heat tape is provided to All unit controls are housed in a include main three phase power and
protect the evaporator from freezing weather-tight enclosure with hinged two 115 volt single phase power
at ambient temperatures down to - doors to allow for customer connections for control power and
18°C. connection of power wiring and heat tape.
remote interlocks.
Condenser and Fans All controls, including sensors, are Starters
Air-cooled condenser coils have factory mounted and tested prior to Starters are housed in a
aluminum fins mechanically bonded shipment. All cataloged units weathertight enclosure with
to internally finned seamless copper comply to EN 60204 and are EMC removable cover plate to allow for
tubing. The condenser coil has an compatible. customer connection of power
integral subcooling circuit. Microcomputer controls provide all wiring.
Condensers are factory proof and control functions including start-up Wye Delta closed transition starters
leak tested at 35 bar. Direct-drive and shut down, leaving chilled water are standard on all RTAD units.
vertical discharge air foil temperature control, compressor
ZephyrWing condenser fans are and electronic expansion valve
dynamically balanced. Three-phase modulation, fan sequencing, anti-
condenser fans motors with recycle logic, automatic lead/lag
permanently lubricated ball bearing compressor starting and load
are provided. Standard units will limiting.
RLC-PRC015-E4 45
Notes
46 RLC-PRC015-E4
Notes
RLC-PRC015-E4 47
Literature Order Number RLC-PRC015-E4
Date 1108
Supersedes RLC-PRC015-E4_0903
Trane has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice. Only qualified technicians should perform the
installation and servicing of equipment referred to in this publication.
www.trane.com
Trane bvba
For more information, contact your local Chaussée de Wavre 1789 - 1160 Brussels, Belgium
sales office or e-mail us at comfort@trane.com ON 0888.048.262 - RPR BRUSSELS