You are on page 1of 7

C-FIX 1.121.0.

0
Database version
2023.12.14.12.55
Date
05/01/2024

Grow Vertex Co., Ltd.

1 Empire Tower Fl. 47th Unit 4703


(River 38)
South Sathorn Rd., Yannawa, Sathorn,
Bangkok 10120
Phone: +66 2 6863461
Fax: +66 2 0266874
info@growvertex.co.th
www.growvertex.co.th

Design Specifications
Anchor
Anchor system fischer Injection system FIS EM plus
Injection resin FIS EM Plus 390 S
Fixing element Threaded rod FIS A M 16 x 130 R,
stainless steel, Property Class R-70
Calculated anchorage 80 mm
depth

Design Data Anchor design in Concrete according European Technical


Assessment ETA-17/0979, Option 1,
Issued 17/06/2020

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 1
C-FIX 1.121.0.0
Database version
2023.12.14.12.55
Date
05/01/2024

Geometry / Loads / Scale units


mm, kN, kNm

Value of design actions (including

partial safety factor for the load) Static

Not drawn to scale

Input data

Design method ETAG 001, Technical Report TR 029


Base material Customized, Test specimen: Cylinder 150 x 300 mm,
Compressive strength = 28.0 N/mm²
Concrete condition Cracked, dry hole
Temperature range 24 °C long term temperature, 40 °C short term temperature
Reinforcement No or standard reinforcement. No edge reinforcement. With
reinforcement against splitting
Drilling method Hammer drilling
Installation type Push-through installation
Annular gap Annular gap filled
Type of loading Permanent-Transient/Static
Base plate location Base plate flush installed on base material
Base plate geometry 250 mm x 250 mm x 15 mm
Profile type Rectangular hollow tube cold formed (120x60x5)

Design actions *⁾
# NSd VSd,x VSd,y MSd,x MSd,y MT,Sd Type of loading
kN kN kN kNm kNm kNm
1 -21.95 9.70 0.00 0.00 0.00 0.00 Permanent-Transient/Static

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 2
C-FIX 1.121.0.0
Database version
2023.12.14.12.55
Date
05/01/2024

*⁾ The required partial safety factors for actions are included

Resulting anchor forces


Tensile action Shear Action Shear Action x Shear Action y
Anchor no. kN kN kN kN
1 0.00 2.43 2.43 0.00
2 0.00 2.43 2.43 0.00
3 0.00 2.43 2.43 0.00
4 0.00 2.43 2.43 0.00

max. concrete compressive strain : 0.01 ‰


max. concrete compressive stress : 0.4 N/mm²
Resulting tensile actions : 0.00 kN , X/Y position ( 0 / 0 )
Resulting compression actions : 21.95 kN , X/Y position ( 0 / 0 )

Resistance to shear loads

Proof Action Capacity Utilisation βV


kN kN %
Steel failure without lever arm * 2.43 35.26 6.9
Concrete pry-out failure 9.70 106.08 9.1
Concrete edge failure 9.70 26.92 36.0

* Most unfavourable anchor

Steel failure without lever arm

( VRd,s )

VRk,s γMs VRd,s VSd βVs


kN kN kN %
55.00 1.56 35.26 2.43 6.9

βVs
Anchor no. % Group N° Decisive Beta
1 6.9 1 βVs;1
2 6.9 2 βVs;2
3 6.9 3 βVs;3
4 6.9 4 βVs;4

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 3
C-FIX 1.121.0.0
Database version
2023.12.14.12.55
Date
05/01/2024

Concrete pry-out failure

( VRd,cp )

Eq. (5.7a)

Eq. (5.3)

Eq. (5.3a)

Eq. (5.3c)

Eq. (5.3d)

Eq. (5.3e)

VRk,cp γMcp VRd,cp VSd βV,cp


kN kN kN %
159.12 1.50 106.08 9.70 9.1

βV,cp
Anchor no. % Group N° Decisive Beta
1, 2, 3, 4 9.1 1 βV,cp;1

Concrete edge failure

( VRd,c )

Eq. (5.8)

Eq. (5.8a)

Eq. (5.8b/c)

Eq. (5.8e)

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 4
C-FIX 1.121.0.0
Database version
2023.12.14.12.55
Date
05/01/2024

Eq. (5.8f)

Eq. (5.8g)

Eq. (5.8h)

VRk,c γMc VRd,c VSd βV,c


kN kN kN %
40.38 1.50 26.92 9.70 36.0

βV,c
Anchor no. % Group N° Decisive Beta
1, 3 36.0 1 βV,c;1
2, 4 36.0 2 βV,c;2

Resistance to combined tensile and shear loads

Proof successful (5.9b)

Information concerning the anchor plate


Base plate details
Plate thickness specified by user without proof t = 15 mm

Profile type Rectangular hollow tube cold formed (120x60x5)

Technical remarks
All data and information in the software is based on fischer products and common engineering knowledge. Please
check all the proof results against local valid standards and approvals.
As fischer is not the design office, the attached is no guarantee for incorrect input or assumptions. Any
recommendations have to be approved by the building-authority or project engineer. Results are valid only for
anchor system calculated in the attached. If any part of the system is changed, it will invalidate this report and new
calculations would be required. The calculation was done under the assumption that a sufficient
splitting reinforcement is available. In this case the spliiting
failure can be omitted.
The transmission of the anchor loads to the supports of the concrete member shall be shown for the ultimate limit state and
the serviceability limit state; for this purpose, the normal verifications shall be carried out under due consideration of the
actions introduced by the anchors. For these verifications the additional provisions given in the current design method shall
be taken into account.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate (if present) must
be sufficiently stiff. The C-Fix anchor plate design is based on a proof of stresses and does not allow a statement about the
stiffness of the plate. The proof of the necessary stiffness is not carried out by C-Fix.

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 5
C-FIX 1.121.0.0
Database version
2023.12.14.12.55
Date
05/01/2024

Installation data
Anchor
Anchor system fischer Injection system FIS EM
plus
Injection resin FIS EM Plus 390 S (other cartridge Art.-No. 544155
sizes available)
Fixing element Threaded rod FIS A M 16 x 130 R, Art.-No. 44975
stainless steel, Property Class R-70

Accessories FIS MR Plus Art.-No. 545853


FIS DM S Pro Art.-No. 563337
Compressed-air cleaning tool Art.-No. 93286
compressed air (oil-free), min. 6 bar By job site
Cleaning brush BS 16/18 Art.-No. 78181
SDS Plus-V II 18/150/200 Art.-No. 531836
or alternatively
FHD 18/320/450 Art.-No. 546600
Hammer drilling with or without
suction
Alternative cartdriges FIS EM Plus 585 S Art.-No. 544165
FIS EM Plus 1500 S Art.-No. 544173
The shown cartdriges are
alternative to the highlighted
one above with the same approval
number.

Installation details
Thread diameter M 16
Drill hole diameter d0 = 18 mm
Drill hole depth h2 = 95 mm
Calculated anchorage hef = 80 mm
depth
Drilling method Hammer drilling
Borehole cleaning 2 times blowing,
2 times brushing,
2 times blowing
required activities according the
given instruction in the approval
No borehole cleaning required in
case of using a hollow drill bit, e.g.
fischer FHD.
Installation type Push-through installation
Annular gap Annular gap filled
Maximum torque Tinst,max = 60.0 Nm
Socket size 24 mm
Base plate thickness t = 15 mm
Total fixing thickness tfix = 15 mm
Tfix,max
Volume of resin per drill 12 ml/6 scale divisions
hole

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 6
C-FIX 1.121.0.0
Database version
2023.12.14.12.55
Date
05/01/2024

Base plate details


Base plate material S 275
Base plate thickness t = 15 mm
Clearance hole in base df=20 mm
plate

Attachment
Profile type Rectangular hollow tube
cold formed (120x60x5)

Anchor coordinates

x y
Anchor no. mm mm
1 -75 75
2 75 75
3 -75 -75
4 75 -75

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 7

You might also like