You are on page 1of 6

PG Infracon Pvt Ltd.

SR-64,DLF Phase-3 ,Gurgaon-122002

Date : 04.02.2022

M/s.LIMRA FIRE & SECURITY PVT LTD


Plot No. 15, LGF Pocket 1
Jasola Vihar, New Delhi-25.

Kind Attention : Mr Faisal – 9911045312.

Object :- Purchase Ordre FOR SITC OF FAS , PA System , WLD & Rodent for Compass –Gurgaon .

Dear Sir,
We are pleased to place Purchase LOI for the Purchase Order FOR SITC OF FA S , PA System ,
WLD & Rodent Wire for Compass –Gurgaon as per approved T.D.S.

TERMS & CONDITIONS:

1. Price INR 9,00,000/-


(Price Break- As per Annexure I)

2 Price Basis : SITC Basis (Upto Site).

3 GST : GST Extra as applicable.

4 Payment Terms : 20 % Advance ,balance back to back .

5 Documents to be sent along : Inspection report & Technical Data sheets, Test certificates,
with the material Guarantee certificate with the material also to be send ,Billing
and Completion Certificate .
6 Packing & Forwarding : Inclusive in the order value.

7 Freight Charges : Inclusive in the order value.

8 Contractual Delivery date : Supply within given schedule.

9 Onsite Warranty/DLP : Warranty Will be standard.


PG Infracon Pvt Ltd. SR-64,DLF Phase-3 ,Gurgaon-122002
10 Product Approval : Supplier is fully responsible for for approval and delivered
material.Delivery should be as per technical specifications and
Approved GTP.
11 Price Validity : Till Completion of Project .

12 Quantity Variation : Quantity may increase/decrease as per project requirement.

For PG Infracon Pvt Ltd. Dimple


Sharma
GM Procurement & PGI .

Note : Kindly return signed & stamped copy of this Purchase Order as a token of your unconditional
acceptance within 2 days from the date of issuance of this Purchase Order.
ELECTRICAL WORK SUMMARY
COMPASS

SITC
SR. DESCRIPTION
Amount(INR)
A FAS & PA 8,06,090.00
B WLD & RODENT 93,910.00
TOTAL AMOUNT WITHOUT GST 9,00,000.00

Page 1 of 1
Integrated Fire Alarm, Voice Evacuation & Telephone Talkback System
Supply, Unit Supply,
Sl. No Description Unit Qty
Rate Amount

A Fire Panel & Annunciators MAKE: MORLEY


SITC of Intelligent Analog Addressable Type Photo-Thermal Detector with Dual LED and inbuilt isolator,
Hard Addressable Having rotary decade Address swicthes from 01-99, complete with Mounting Base. The
detector shall share the analog datapoints to the panel. The detector shall have 6 levels of smoke
sensitivity. The detector shall operate in both ROR (10 ºC) and Fixed heat (58 ºC) basis requirement.
1 Nos 75 1900 142500
Operating Voltage shall be 15 to 28 Vdc. The Detector shall meet RoHS standard & shall confirm to BS
5839 Standards and Duly Approved by EN54/LPCB Make:- Morley IAS /Notifier/ Gent
(Model -HM/PTSE/I + MI/B501AP/IV)
HM-PSE-S2, HM-PSE-S2-I

SITC of Intelligent Analog Addressable Type Rate of Rise/Fixed Heat Detector Complete with Dual LED and
inbuilt isolator, Hard Addressable Having rotary decade Address swicthes from 01-99, complete with
Mounting Base. Operating Voltage shall be 15 to 28 Vdc. The Detector shall meet RoHS standard & shall
2 confirm to BS 5839 Standards and Duly Approved by EN54/LPCB Make:- Morley IAS /Notifier/ Gent 3 1800 5400
(Model HM/FHSE/I or HM/RHSE/I + MI/B501AP/IV) HM-PSE-S2, HM-PSE-S2-I -
Photoelectric Smoke
Detector

SITC of approved make Addressable Loop Powered Sounders cum Strobes with inbuilt isolators.
Operating Temp shall be of -25°C to +70°C. The device shall have anti-tamper mechanism. Addressing
shall be with user friendly rotary decimal switches. Device shall have 32 different tones @ 90 dB & 1 Hz
3 Flasher, High output LED technology and superior lens design optimize light outputs. The device shall be Nos 3 4600 13800
compatible with the detector base. The device shall be IP21C rated & shall meet EN54-Part 23 guideline.
Make:- Morley IAS /Notifier/ Gent (Model WSS-PR-N05 + MI/B501AP/IV)
HM-MCP-GLASS

SITC of Intelligent Analog Addressable Control/Output Modules having option of RAIL or Surface
Mounting with Tri Colour LED status Indicator with Built in Short Circuit Isolators having Visible Rotary
Decade Address Swicthes from 01-99, for initiating Hooter/Sounder/Strobes. Operating Temp: -20 ºC to
4 +60 ºC & Operating voltage 15 to 30 Vdc. The module shall conform to BS5839 Standards and Duly Nos 5 2500 12500
Approved by EN54/LPCB Make:- Morley IAS /Notifier/ Gent
(Model MI/DCMO )
MI-DCMO

Supply, installation, testing & commissioning of 1 Loop Micro processor based 2 wire fault tolerant loop,
required loop networkable type ( loop accessing maximum 99 detectors and 99 modules ) fire
alarm/detection control panel. The panel shall be able to give location of all fire/fault conditions of
addressable units via the address codes. Further, the panel must be able to automatically switch ON
/OFFrespective control module when ever any alarm is triggered. The panel shall have rectifier, Loop
5 cards, 80 character L C D unit to indicate Fire/Fault Signal with address and analog output, Nos 1 62000 62000 DXC panel.
external/inbuilt printer to log all fire or fault events complete in all respects.The Panel Shallbe Sheet Steel
Painted, selaed to IP30. The Panel Shall have 20 Zones with Individual LEd Indicators, expandable to 80
LED Indicators. The Panel Shall have 3 Serial Ports. and as per specifications. conforming to BS5839
Standards and Duly Approved by EN54/LPCB
(Make:- Morley IAS /Notifier/ Gent (Model 714/001/115)

Cables & Conduits:


Supplying, drawing, connecting, testing & commissioning of 2core, 1.5 sq. mm. stranded copper
8 conductor, twisted pair, pvc insulated PVC sheathed,aluminium myler tape shielded FRLS wire in existing Mtrs. 800 50 40000 Approved Make
conduit. (For Fire Detection & Alarm System)

Supply and laying in position the following sizes of 25/20MM Dia PVC. conduits including providing all
9 Mtrs. 200 55 11000 Approved Make
accessories complete as required. (For Fire Detection)

D Notification Devices MAKE:


HONEYWELL/BOSCH
42U Equipment Rack: Floor mountable Equipment Rack for housing PA Network Controller , Amplifiers
1 and Music Source at required location with required slots as per the equpement requirement. Nos 1 37740 37740

SITC of 8 zone IP based, digital Voice Alarm controller expandable upto 2000 zones. The voice alarm
controller should be able to connect directly over Ethernet. It should have functions like the audio
playing, zone control, fault monitoring, volume control and amplifier switchover. The Voice alarm
controller should also have the following functions:
. 255 Priorities
2 Nos 1 167450 167450 HCU-2000 Intevoi
. Time schedule broadcasts
. Capable of amplifier redundancy
. 8 trigger inputs/outputs
Takes music input from external source

Supplying, installing, testing and commissioning approved make Sounder cum Strobe rated at 80 dBA @
3 Nos R.O
3m for Audible annunciation and 115cd flashintg at 1 Hz for visual indication. UL Listed
Supply, Installation, Testing and Commissioning of Amplifiers of 480 watts output,Class D amplifier, Low
4 Heat dissipation, integrated with Slave console, Power ON LED indiactions etc. complete with all Nos 1 30000 30000
accessories as required. HN-IA500I
6W/3W,1.5W Metal grille ceiling speaker with built in 100V transformer. SPL at rated power/1W 95dB /
88dB (1m & 1kHz)
5 It is a full range loudspeaker for speech and music reproduction in shops, department stores, schools, Nos 60 850 51000
oces, stadium, hotels and HN-CL06/ 6W CEILING
restaurants. LOUDSPEAKER
6W/3W,1.5W ABS Material wall mount speaker with built in 100V transformer. SPL at rated power/1W
96dB / 88dB (1m & 1kHz)
6 It is a full range loudspeaker for speech and music reproduction in shops, department stores, schools, Nos 2 1300 2600
oces, stadium, hotels and
restaurants. HN-WM06
SITC of IP based Networkable touch screen paging station for selection of zones, supervision of
system status, setting of scheduled broadcasts with the following functions:
. Built-in monitoring loudspeaker
7 Nos 1 40000 40000
. Detachable goose-neck microphone
. LCD touchscreen display
E Telephone Talkback
Supplying, installing, testing and commissioning approved make Addressable Fire Fighter's Telephone
1 Jack with suitable supervised module for two way communication between Remote Fire Fighter & Fire Nos 4 4200 16800
Command Center. UL Listed
Supplying, installing, testing and commissioning approved make Portable type Fire Telephone Handset
1 for two way communication between Remote Fire Fighter & Fire Command Center. UL Listed Nos 2 13500 27000

F Cables & Conduits

Supplying & laying of 2x1.5 sqm fire survival armoured cable, 600/1000V rated with annealed copper
conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene
1 Rmt. 1000 133 133000 MAKE: EXCEL
Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath
complete as required.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit
2
as required. (From Fire panel to repeater panel)
1 run of cable Rmt. 100 45 4500 cat 6 cable
3 SITC of 2 C X 1.5 Sq mm multi stranded twisted armoured FRLS cable. Rmt. 100 88 8800

TOTAL 8,06,090
RODENT & WLD
Total Installation/ Total
S. No. Description Unit Qty. Supply/Unit
Supply Unit Installation
B RODENT & WLD
1 RODENT FOR SERVER + HUB + UPS BATTERY ROOM MAKE: MASER

Supply, Installation, testing & Commissioning of Master Console Capable of


1.1 connecting to 12 satellites complete as required and as per specifications. Set 2 9000 18000 2000 4000

Supply, Installation, testing & Commissioning of Satellite units complete as


1.2 Nos 5 700 3500 175 875
required and as per specifications.

Supply, Installation, testing & Commissioning of Wire in existing 16 gauge MS


1.3 Mtr 80 22 1760 10 800
conduit complete as required and as per specifications.

Supply, Installation, testing & Commissioning of Bracket Stand complete as


1.4 Nos 1 650 650 0
required and as per specifications.

WATER LEAK DETECTION SYSTEM FOR SERVER ROOM & HUB ROOM MAKE: C
2
SYSTEM

Supply, Installation of Leak detection system 6 zone control Digital Panel with
Display, Power supply & all required accessories including module . The panel
Set 2 9000 18000 2500 5000
should have the capability to be integrated to the BMS/Fire Panel.
2.1

Supply, Installation, testing & Commissioning of Water leak sensor cables


including Jumper cables, End cap, Cable saddles, tag complete as required. Mtr 60 490 29400 20 1200
2.2

Supply, Installation, testing & Commissioning of Electronic Hooter for water


sensing indication including required 2 core copper cable betwwen Hooter and Nos 3 3400 10200 175 525
2.3 Panel.
TOTAL 81510 12400