You are on page 1of 6

Fieldbus Power Hub, Advanced

Diagnostic Module
HD2-DM-A
< Comprehensive diagnostics for fieldbus physical layer and power
supply
< Plug-in Module for the FieldConnex Power Hub
< Precise measurements through passive circuits
< For commissioning, online monitoring and troubleshooting
< For FOUNDATION Fieldbus H1 and PROFIBUS PA
< Installation in Zone 2/Class I, Div. 2
< System state and fault indication via LEDs
< Display of data in the safety of the control room
< Automatic setup of diagnostic system
< Full software integration into PCS and PAM possible

Function
Designed as a plug-in module for the FieldConnex® Power Hub, this Advanced Diagnostic Module (ADM) is a comprehensive measurement tool
for the physical layer of up to four fieldbus segments. It's passive input circuits leave the physical layer untouched for exact data. The ADM detects
gradual or sudden changes and helps trace even intermittent malfunctions.
The ADM supports commissioning, online monitoring and troubleshooting. It can be integrated tightly into the DCS and PAM via a separate
diagnostic bus, making the fieldbus physical layer itself a managable asset. Configuration tools automate setup of the ADM and of selected DCS.
The Diagnostic Manager is the software for display and operation from the safety of the control room. The Professional Edition provides powerful
functions and wizards simplifying and automating work procedures: an embedded expert system, a data historian, and a built-in oscilloscope (see
datasheet DTM-FC.AD*).

Connection

Bulk
-+

PS ADM Alarm
Diagnosis/Alarm +
-
Release date: 2022-07-04 Date of issue: 2022-07-04 Filename: 131000_eng.pdf

S-+ S-+ S-+ S-+


Trunk 1 Trunk 2 Trunk 3 Trunk 4

Zone 2/Div. 2

Technical Data
General specifications
Design / Mounting Motherboard based
Supply
Rated voltage Ur 19.2 ... 35 V
Rated current Ir 110 ... 30 mA
Power dissipation max. 2 W
Fieldbus connection

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com 1
HD2-DM-A
Technical Data
Number of segments 4
Fieldbus type FOUNDATION Fieldbus/PROFIBUS PA
Rated voltage UN 9 ... 32 V
Indicators/operating means
LED PRI PWR green: on, primary bulk power supply connected
LED SEC PWR green: on, secondary bulk power supply connected
LED Seg 1...4 yellow: bus activity; red 2 Hz flashing: alarm; red: hardware error
Fault signal VFC alarm 1 A, 50 V DC, normally closed
DIP switch diagnostic address 1...247, binary coded
Interface
Interface type diagnostic bus: RS 485
Galvanic isolation
Fieldbus segment/Fieldbus segment functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Fieldbus segment/Supply functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013
Standard conformity
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529
Shock resistance EN 60068-2-27
Vibration resistance EN 60068-2-6
Ambient conditions
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Relative humidity < 95 % non-condensing
Shock resistance 15 g 11 ms
Vibration resistance 1 g , 10 ... 150 Hz
Pollution degree max. 2, according to IEC 60664
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection type motherboard specific
Core cross section motherboard specific
Housing material Polycarbonate
Housing width 18 mm
Housing height 106 mm
Housing depth 128 mm
Release date: 2022-07-04 Date of issue: 2022-07-04 Filename: 131000_eng.pdf

Degree of protection IP20


Mass approx. 100 g
Mounting motherboard mounting
Mating cycles 100
Data for application in connection with hazardous areas
Certificate TÜV 04 ATEX 2500 X
Marking 1 II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EU EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
FM certificate FM 19 US 0015 X and FM 19 CA 0011 X
FM marking AEx/Ex ec IIC T4
IECEx approval
IECEx certificate IECEx TUN 13.0038X
IECEx marking Ex nA IIC T4 Gc

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com 2
HD2-DM-A
Technical Data
Certificates and approvals
Marine approval DNV A-14038
Patents This product may be covered by the following patent: US7,698,103
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals
where applicable. For information see www.pepperl-fuchs.com.

Product Photo

Matching System Components


FBTA-228-BPFB-R-8R Compact Fieldbus Power Hub Motherboard for Invensys FBM 228

MBHC-FB-4.HSC* Compact Fieldbus Power Hub Motherboard with Host System Connectors
Release date: 2022-07-04 Date of issue: 2022-07-04 Filename: 131000_eng.pdf

MBHC-FB-4R.HSC* Compact Fieldbus Power Hub Motherboard with Host System Connectors

MBHC-FB-4.GT* Fieldbus Power Hub, Motherboard for Gateway and Power Supply Modules

Accessories
DTM-FC.AD* User-Interface for Advanced Diagnostics, Professional Edition

DTM-FC.AD Software user interface for advanced diagnostic modules; license for up to a maximum of 100 segments

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com 3
HD2-DM-A
Accessories
DTM-FC.AD.1 Software user interface for advanced diagnostic modules; license for 100 segments or more

DTM-FC.AD.UPG Advanced diagnostics upgrade license from V1.x to V2.x for plants with up to 100 segments

DTM-FC.AD.1.UPG Advanced diagnostics upgrade license from V1.x to V2.x for plants with 100 or more segments

PACTware 4.1 FDT Framework

PACTware 5.0 FDT Framework


Release date: 2022-07-04 Date of issue: 2022-07-04 Filename: 131000_eng.pdf

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com 4
Fieldbus Power Hub, Advanced Diagnostic Module HD2-DM-A

Additional Information

Dimensions and Assembly


Dimensions complete redundant system* Dimensions Advanced Diagnostic Module*

5
14
Moduladresse
module address
1
0
Bit 7 6 5 4 3 2 1 0

128 mm (5")
162 mm (6.4")
36 mm ADRESSAUSWAHL / ADDRESS SELECTION

(1.4") 15 Moduladresse
module address

1
7
0
6
0
5
0
4
0
Bit
3
0
2
0 0
1 0
1
2 0 0 0 0 0 0 1 0
3 0 0 0 0 0 0 1 1

246 1 1 1 1 0 1 1 0
247 1 1 1 1 0 1 1 1
Hinweis: Die Moduladressen sind nur im Bereich von 1 bis 247 g ltig (bin„r kodiert).
Note: The module addresses are only valid in the range from 1 to 247 (binary coded).

106 mm (4.2") 10

18 mm
(0.7")
110 mm (4.3")

1 220 mm (8.7")
246 mm (9.7")
6 11 12 13

7
OFF

Host A Host B Host A Host B Host A Host B Host A Host B

- +
S-+ S-+

2
SEG1
ON
OFF

S-+ S-+
SEG1
+ - S

SEG2

3
ON

221 mm (8.7")
SEG2
+ - S

4
OFF

S-+ S-+
SEG3
SEG3
+ - S

ON
OFF

S-+ S-+
SEG4

8
+ - S

SEG4
ON

9
PWR PWR
PRI SEC

- +

*all dimensions without tolerance


indication
10 Plug connections to Motherboard
Description: 11 LED Seg 1 ... Seg 4
1 Power Supply Modules, see separate data sheets 12 LED green SEC Power
2 Advanced Diagnostic Module 13 LED green PRI Power
3 Connections for fieldbus trunk, terminator switch 14 Dip-Switch-Array for diagnostic address or address on the
4 Screening/earthing kit for trunk cables shield, optional accessory diagnostics bus
5 Mounting slot for DIN rail 15 Address selection overview
6 Motherboard, see separate data sheets
Release date: 2022-07-04 Date of issue: 2022-07-04 Filename: 131000_eng.pdf

7 Connections for alarm, voltage free contact and diagnostics bus


8 Connections for redundant host
9 Connections for redundant bulk power supply

Installation
System topology

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

5
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Fieldbus Power Hub, Advanced Diagnostic Module HD2-DM-A
1 ... 31

Work- Converter ...


Ethernet -> RS 485 HD2-DM-A HD2-DM-A
station

Segment 121

Segment 122

Segment 123

Segment 124
Segment 1

Segment 2

Segment 3

Segment 4
Installation notes see manual.

Accessories

• Software User Interface for monitoring up to or including 100 fieldbus segments: Diagnostic Manager, Professional Edition
DTM-FC.AD
• Software User Interface for monitoring more than 100 fieldbus segments: Diagnostic Manager, Professional Edition
DTM-FC.AD.1
• KT-MB-GT2AD Diagnostic Gateway
Release date: 2022-07-04 Date of issue: 2022-07-04 Filename: 131000_eng.pdf

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

6
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

You might also like