Professional Documents
Culture Documents
Features
• 19” rack mounting
• High power density
• Intelligent system controls
• Pre-configured software
• Onboard secure web server
• Push-in easy to fit circuit breakers
• Low voltage disconnect
• Fast on-line expansion of rectifiers (hot-swap)
• High efficiency and unity power factor
• Easy to use menu & full color display
• Optional batteries
• Compatible with Eaton’s Energy Saver (ES) rectifier
Technical Specifications
Input Options
AC Supply Nominal: 120V, 240V Battery* Eaton Extended Battery Module (EBM)
Operating Range: 90V – 275V PW5130 48V EBM RM
Power Factor † >0.99 (50 – 100% Output Current) P/N 103006587-6591
Efficiency † >96% peak Weight: 29.5kg [65lb]
>95% (20% to 100% load, 230Vac) Dimensions (H,W,D*): 85mm (2U), 432mm (19”
mounting), 487mm
Output *Additional space is required at the rear for cables.
DC Output 43 – 57.5V
Voltage Range Typical Run time values* (see graph).
DC Output 240V AC: APR48-ES: 4.0kW
Battery Run Time (minutes)
Power APR48-3G: 3.6kW
(maximum*) † EPR48-3G: 1.8kW
Environmental
Operating Rated: -10°C to +50°C [-14°F to +122°F]
Temperature Extended*: -40°C to +70°C [-40°F to +158°F]
Range
*Output current is derated above 50°C [122°F]
Mechanical
Dimensions 2U , 19” mounting, 13.2” [335mm]*
H,W,D
* Additional clear depth space is required for Equipment Power (watts))
exhaust air.
Α = Required number of battery modules.
System
*Battery times are approximate and vary depending
System SC200
on factors such as:
Controller
- load configuration
DC Distribution 12-way circuit breakers (2 x Battery, 10 x Load)
- battery charge
Module Circuit breaker type: Magnetic/Hydraulic, push fit
- battery age and temperature.
Battery circuit breakers: Heinemann AC1R Series
* Other battery options available - consult your local
Typical ranges available: 30A, 40A, 50A, 60A, 70A
Eaton agent.
Battery Cables CKBATT-02 Eaton EBM 5130 connection cable,
Load circuit Breakers: Heinemann JC1S Series
2000mm long
Typical ranges available: 6A,10A, 15A, 20A, 25A,
or CKBATT-01 ‘other batteries’ connection cable,
30A
2000mm long
Communication USB direct
Equipment Customer Equipment Connection Cable
Features 10BaseT Ethernet, TCP/IP, SNMP, Modbus-TCP,
Cable CKLOAD-00 10-way connection loom, 1000mm long
Modbus-RTU and on board web server
EBM Rack Included with EBM5130 as standard
RS232 to external PSTN or GSM modem (modem
Mounting Kit
not included)
Rectifier Blank For unused rectifier positions
Panels Certifications
All products comply with International Standards.
Software
North America UL (Canada, USA), FCC Class B
DCTools Configuration software.
Europe CE
Free download from:
Australia and New Zealand C-Tick
www.powerware.com/downloads
PowerManagerII Remote control and monitoring software In the interests of continual product improvement all specifications are
subject to change without notice.
† Power factor, efficiency and DC output power are dependant on
rectifier model fitted. Refer to the rectifier data sheet for further
details.
Features
• 19” rack mounting
• High power density
• Intelligent system controls
• Pre-configured software
• Onboard secure web server
• Push-in easy to fit circuit breakers
• Low voltage disconnect
• Fast on-line expansion of rectifiers (hot-swap)
• High efficiency and unity power factor
• Easy to use menu & full color display
• Optional batteries
Technical Specifications
Input Options
AC Supply Nominal: 120V, 240V Battery* Eaton Extended Battery Module (EBM)
Operating range: 90V – 275V PW5130 48V EBM RM
Power Factor † >0.99 (50 – 100% output current) P/N 103006587-6591
Efficiency † 91% (50 – 100% output current)
Weight: 29.5kg [65lb]
Output Dimensions (H,W,D*): 85mm (2U), 432mm (19”
DC Output 43 – 57.5V mounting), 487mm
Voltage Range *Additional space is required at the rear for cables.
DC Output 240V AC: 4.5kW
Power 120V AC: 2.25kW Typical run time values* (see graph).
(maximum*) †
Battery Run Time (minutes)
* Based on five rectifiers fitted, refer to EPR48-3G
rectifier data sheets.
Environmental
Operating Rated: -10°C to +50°C [-14°F to +122°F]
Temperature Extended*: -40°C to +70°C [-40°F to +158°F]
Range
*Output current is derated above 50°C [122°F]
Mechanical
Dimensions 3U, 19” mounting, 13.2” [335mm]*
H,W,D
* Additional clear depth space is required for
exhaust air.
Equipment Power (watts))
System
System
Controller
SC200 • = Required number of battery modules.
Software
Certifications
DCTools Configuration software.
All products comply with international standards.
Free download from:
www.powerware.com/downloads
North America UL (Canada, USA), FCC Class B
PowerManagerII Remote control and monitoring software
Europe CE
Australia and New Zealand C-Tick
† Power factor, efficiency and DC output power are dependant on
rectifier model fitted. Refer to the rectifier data sheet for further In the interests of continual product improvement all specifications are
details. subject to change without notice.
Features
• Easy to install
• Slimline 19” rack mounting
• Extended runtime -18Ahr capacity
• Modular and scaleable
• Service maintenance free VLRA batteries
Technical Specifications
Output
DC Output 48V nominal
Voltage
DC Output 18Ahr
Capacity Maximum input/output current should not exceed
55Amps
Mechanical
Weight 29.5kg
Dimensions 85mm (2U), 432mm (19” mounting), 487mm*
H,W,D
* Additional space is required at the rear for cables.
Battery
Certifications
All products comply with international standards. Contact your local
Eaton DC representative for details on the specific product versions
available with these safety and EMC approvals:
North America UL listed
Europe CE
Output
DC Output 21.5V – 32V / 43-57.5V In the interests of continual product improvement all specifications are
Voltage Range subject to change without notice.
DC Output APS3-300 48V: 6.0kW
Power 24V: 4.32kW
(maximum)†* APS6-300 48V: 10.8kW
APS6-500 48V: 12.0kW
24V: 8.64kW
* Ratings are stated without LVD’s fitted. In some
cases lower ratings may result when LVDs are
used.
Environmental
Operating -40°C to +70°C [-40°F to +158°F]
Temperature
Range* * Refer to rectifier data sheet for more information.
Output current is derated above 50°C [122°F] and
below -10°C [14°F]
Mechanical
Dimensions APS3-300: 3U, 19” mounting, 306mm [12”]*
H,W,D APS6-300: 6U, 19” mounting, 306mm [12”]*
APS6-500: 6U, 19” mounting, 306mm [12”]*
System
System SC200 or SC100
Controller
DC Distribution APS3-300: 12-way circuit breakers
Module (2 x battery, 10 x load)
APS6-300: 20-way circuit breakers
(4 x battery, 16 x load)
APS6-500: 20-way circuit breakers
(4 x battery, 16 x load)
Communication USB direct*
Features 10BaseT Ethernet*, TCP/IP*, SNMP*, Modbus-
TCP*, Modbus-RTU* and on board web server*
RS232 to external PSTN or GSM modem (modem
not included)
*SC200 only
Low Voltage APS3-300: optional battery LVD
Disconnect APS6-300: optional 200A LVD’s for battery
(LVD) or load, or both.
APS6-500: optional 400A LVD’s for battery
or load, or both.
Rectifier Blank For unused rectifier positions
Panels
Options External Surge Protection
Environmental
Temperature Rated: -10°C – +50°C [14°F – +122°F]
Range* Extended: -40°C – +65°C [-40°F – 149°F]
Mechanical
Dimensions 3U [5.25”, 133mm], 19” [483mm] mounting,
H,W,D 14” [356mm]*
System
System SC200 as standard.
Controller SC100 optional.
DC Distribution 10-way circuit breakers (2 x Battery, 8 x Load).
Module Load circuit breakers: Heinemann AMIR Series
5A,10A, 20A, 30A, 40A, 50A, 70A, 80A, 100A.
Battery circuit breakers: Heinemann AMIR 100A or
AMIP 120A.
Communication USB direct*
Features 10BaseT Ethernet*, TCP/IP*, SNMP*, Modbus-
TCP*, Modbus-RTU* and on board web server*
RS232 to external PSTN or GSM modem (modem
not included)
*SC200 only
Low Voltage Battery disconnect: 200A internal.
Disconnect
(LVD)
Rectifier Blank For unused rectifier positions.
Panels
Options Relay Rack
Batteries.
Features
The Eaton® 3G Access Power The APS6-400 series has up to
• High power density (12kW @ 48V/6U, 19”)
Solutions are ideal for low to 12kW of power output, it
• Suitable for both 19” relay rack or enclosed cabinet medium power telecommuni- features state-of-the-art 48 volt
• High efficiency and unity power factor cations applications requiring 3G Access Power Rectifiers, an
• Easy fit plug-in hydraulic/magnetic circuit breakers. compact, efficient and flexible integral DC distribution panel,
DC power supplies with or easy to fit plug-in hydraulic
• 20-way load and 6-way battery distributions without batteries. Typical magnetic circuit breakers, and
• Single or dual low voltage disconnect (LVD) options applications include standby DC optional low voltage disconnect
• SC200 or SC100 intelligent system controller power for customer premises (LVD) modules for battery and
equipment, outdoor power non priority loads.
• Onboard energy management software optimizes operating plants, data networks and IP
efficiency for lower OPEX The advanced system controller
routers.
• Pre-configured software for quick & simple deployment offers high-level
A technician friendly user- communications capability for
• Remote access (TCP/IP, web browser, SNMP) interface includes a full color real time information. It also
• Easy plug-and-go rectifier set-up menu screen and is has built-in intelligence for
• Fast on-line rectifier expansion (hot-plug) preconfigured for fast install optimizing system efficiency,
and easy commissioning. and comprehensive alarm and
system status notifications,
The 19” rack mount system is
which are all designed to
ideal for rapid deployment into
minimize operational expenses.
customer facilities or
enclosures. Other features include
temperature compensated
All system settings are fully
voltage output, automated
adjustable in software and
equalize charging, and
stored in transferable
integrated battery testing, for
configuration files for
maximum battery life under a
repeatable one-step system
wide range of environmental
set-up.
conditions.
Technical Specifications
Input Software
AC Supply† Nominal: 120V, 208-240V DCTools Configuration software.
Operating Range: 90V – 275V* Free download from:
www.powerware.com/downloads
* Output power derates below 175V AC. PowerManagerII Remote control and monitoring software
Power Factor† >0.99 (50 – 100% Output Current)
Efficiency† By system rectifier type: Certifications
APR48-ES: >95% (20 - 100% output current) North America: UL listed 1801, cUL, FCC
APR48-3G: 92% (50 - 100% output current)
Total Harmonic <5% THD from 50% to 100% at load. In the interests of continual product improvement all specifications are
Distortion subject to change without notice.
Output
DC Output 43 – 57.5V
Voltage Range
DC Output Rectifier type: APR48-3G APR48-ES
Power 120V AC: 6.6kW @ 48V 8.0kW @ 48V
(maximum) 208-240V AC: 10.8kW @ 48V 12kW @ 48V
Environmental
Temperature
Range Rated: -10°C to +45°C [14°F to +122°F]
Mechanical
Dimensions 6U [10.5”, 267mm], 19” [483mm] mounting,
H,W,D 15.3” [390mm]*
System
System SC200 as standard.
Controller SC100 optional.
DC Distribution 26-way circuit breakers (6 x Battery, 20 x Load).
Module Load circuit breakers: Heinemann AMIR Series
5A,10A, 20A, 30A, 40A, 50A, 70A, 80A, 100A, 120A
(2-pole).
Battery circuit breakers:
6 x Heinemann AMIR 80A, 100A
or 3 x Heinemann AMIP 120A, 150A, 200A.
Communication USB direct.
Features of 10BaseT Ethernet, TCP/IP, SNMP, On board web
SC200 server.
RS232 to external PSTN or GSM modem (modem
not included).
Low Voltage Battery disconnect: 400A internal.
Disconnect Non priority load: 200A internal.
(LVD) (Optional)
Rectifier Blank For unused rectifier positions.
Panels
Options Relay Rack
Batteries.
Features
• Compact 9U, 19” sub-rack
• Up to 12 rectifier modules
• Compatible with Eaton Energy Saver (ES) Rectifiers
• Pre-configured software
• High power density (400A/9U)
• Dual AC input
• Fast on-line expansion of rectifiers (hot-swap)
• High efficiency and unity power factor
• Priority and non priority options for DC distributions
Technical Specifications
Input Software
AC Supply† 100 – 240V, 50 – 60Hz (nominal) DCTools Configuration software.
175 – 275V full power output up to 50°C [122°F] Free download from:
90 – 175V reduced power output www.powerware.com/downloads
Dual AC input - 1Ø, 2Ø or 3Ø (one supply feed per PowerManagerII Remote control and monitoring software
6-rectifier shelf)
Power Factor† >0.99 (50 – 100% Output Current) Certifications
Efficiency† APR48-3G : 92% (50 – 100% Output Current) All products comply with international standards. Contact your local
APR48-ES : >96% peak Eaton DC representative for details on the specific product versions
>95% (20% to 100% load, 230Vac) available with these safety and EMC approvals:
Output Europe CE
DC Output 43 – 57.5V Australia / C-tick
Voltage Range New Zealand
DC Output APR48-3G : 17.2kW @ 48V
Power APR48-ES : 17.2kW @ 48V In the interests of continual product improvement all specifications are
(maximum)†* * Ratings are stated without LVD’s fitted. In some subject to change without notice.
cases lower ratings may result when LVDs are
used.
Environmental
Operating -40°C to +70°C [-40°F to +158°F]
Temperature Output current is derated above 40°C [104°F] and
Range below -10°C [14°F]
Mechanical
Dimensions 9U, 19” mounting, 306mm [12”]*
H,W,D
* Additional clear space is required for exhaust air.
System
System SC200 or SC100
Controller
DC Distribution 20-way circuit breakers (4 x Battery, 16 x Load)
Module
Communication USB direct*
Features 10BaseT Ethernet*, TCP/IP*, SNMP*, Modbus-
TCP*, Modbus-RTU* and on board web server*
RS232 to external PSTN or GSM modem (modem
not included)
*SC200 only
Low Voltage Optional battery LVD, or non priority LVD, or battery
Disconnect and non priority LVD’s. (Contactors 400A
(LVD) rated)
Rectifier Blank For unused rectifier positions
Panels
Options External Surge Protection
Features
• Innovative system design reduces shipping costs and is easily
assembled on-site
• Integrated batteries with optional rack heights
• Reduced rack-depth option (450mm) ideal for installations with
restricted space
• Integral DC distribution
• Wide AC input voltage range
• Hot swappable rectifiers
• High power density
• Pre-configured software
• Flexible modular design
• Remote monitoring and control
• Ethernet communications offering SNMP
• Compatible with Eaton Energy Saver (ES) Rectifiers
Technical Specifications
Input Options
AC Supply† 230/400 3Ø+N+PE (cabinets may be supplied Battery Rack Extension kit for extending battery rack from
from 230V single-phase) Extension 450mm to 600mm depth, is available for 1150 and
120/208 3Ø+PE (specific version with protection 1350mm battery racks
in each phase) DC Distribution 22 Load MCB (18mm) positions *
230/400 dual, single or 3-phase connection 4 Battery MCB (27mm) positions *
(specific version)
Frequency 50/60Hz (nominal) *other configurations available
Power Factor† >0.99 (50 – 100% Output Current) Cabinet Doors Optional doors available for battery racks and
Efficiency † >96% peak Power Box
>95% (20% to 100% load, 230Vac) Rectifier Blank For unused rectifier positions
Panels
Output
DC Output 43 – 57.5V Software
Voltage Range PowerManagerII Remote control and monitoring for small to large
Maximum DC APR48-3G : 16.2kW networks
Output Power† * APR48-ES : 18.0kW DCTools Configuration Software. Free download from
* Ratings are stated with LVD’s fitted. www.powerware.com/downloads
Environmental Certifications
Operating -40°C to +70°C Maximum output power is All products comply with International Standards. Contact your local
Temperature derated according to rectifier used:- Eaton DC product representative for details on the specific product
Range APR48-3G: below -10°C and above 50°C versions available with these safety and EMC approvals:
APR48-ES: below -10°C and above 55°C Europe CE
Battery Rack:
1150mm – Maximum 4 Battery Shelves (258mm
min. space)
1350mm – Maximum 4 Battery Shelves (308mm
min. space)
1471mm – Maximum 5 Battery Shelves (262mm
min. space)
Weight System cabinet: <110kg (excluding rectifiers and
batteries)
Rectifiers : APR48-3G/APR48-ES: 1.7kg
Finish Cabinet is constructed with a galvanised finish
(unpainted)
System
System Controller Extended functionality: SC200
Communication USB direct
Features 10BaseT Ethernet, TCP/IP, SNMP, Modbus-TCP,
Modbus-RTU and on board web server
RS232 to external PSTN or GSM modem (modem
not included)
Features
• Intelligent system management features
• Pre-configured software
• High power density
• Fast on-line expansion of rectifiers (hot-swap)
• High efficiency and unity power factor
• Range of DC distribution configurations
• Battery condition monitoring
• Wide AC input voltage range
• Seismic rated cabinet
• Remote monitoring and control
• Full length security door (optional)
• Compatible with Eaton Energy Saver (ES) Rectifiers
Technical Specification
Input Options
AC Supply† 3P+N+PE, 3P+PE, 2P+PE, 1P+N+PE AC Distribution Coordinated transient protection up to 40kA, 8/20μs
50/60Hz (nominal) Incoming isolator
Individual rectifier MCBs
Other options available depending on system DC Distribution A wide range of DC distribution elements are
capacity. available including:
Power Factor† >0.99 (20 – 100% Maximum System Current) 24 x 18mm MCBs (1-63A)
Efficiency† >96% peak 16 x 27mm MCBs (10-125A)
>95% (20% to 100% load, 230Vac) 10 x DIN00 type HRC fuses (20-160A)
6 x DIN1 type HRC fuses (63-250A)
Output 6 x DIN2 type HRC fuses (100-400A)
DC Output 40 – 57.5V 4 x DIN3 type HRC fuses (400-630A)
Voltage Range 4 x DIN4 type HRC fuses (800-1200A)
Typical DC APR48-3G : 72kW (1500A @ 48V) Low Voltage Single or dual LVD can be configured as battery or
Output Power†* APR48-ES : 80kW (1667A @ 48V) Disconnect load disconnect including non-priority load
* Ratings are stated without LVD’s fitted. In some (LVD) disconnect.
cases lower ratings may result when LVDs are Rectifier Blank For unused rectifier positions
used. Panels
SiteSure Input/output modules to monitor and control
external equipment
Environmental
CellSure Comprehensive battery monitoring and fault
Operating -25°C to +50°C
diagnosis system with patented state-of-health
Temperature
algorithms.
Range* * Output current is derated above 50°C [122°F].
Refer to rectifier data sheet for more information.
Software
PowerManagerII Remote control and monitoring software
Mechanical
DCTools Configuration Software. Free download from
Dimensions 2000mm [78.7”], 600mm [23.6”], 600mm [23.6”]
www.powerware.com/downloads
H,W,D
Weight 200kg [443lb]
Typical configuration with 40 APR-3G rectifier Certifications
modules. All products comply with International Standards. Contact your local
Eaton DC representative for details on the specific product versions
available with these safety and EMC approvals:
System
Europe CE
Rectifiers APR48-3G
Australia / C-tick, Seismic rating to NZS4203
APR48-ES
New Zealand
System Controller SC100/SC200
Communications USB direct*
In the interests of continual product improvement all specifications are
Features 10BaseT Ethernet*, TCP/IP*, SNMP*, Modbus- subject to change without notice.
TCP*, Modbus-RTU* and on board web server*
RS232 to external PSTN or GSM modem (modem
not included)
*SC200 only
Features
• High power density.
• High efficiency and unity power factor.
• Fast on-line expansion of rectifiers (hot-swap).
• Integrated batteries.
• Low voltage disconnects for battery and non priority loads.
• Easy fit plug-in hydraulic/magnetic circuit breakers.
• Flexible AC input.
• Intelligent system management features.
• Pre-configured software for quick & simple deployment.
• Automatic battery condition testing.
• Remote access (TCP/IP, web browser, SNMP).
• Energy management software optimizes operating efficiency
for lower OPEX.
• All cabling top entry with optional rear cable duct extension for
raised floor cable access.
Technical Specification
Input Mechanical
AC Supply North America: Dimensions
Voltage* 3P 208Vac nominal H,W,D 2000mm [78.7”], 600mm [23.6”], 600mm [23.6”]
2P 240Vac nominal
With rear cable
Global: duct extension 2000mm [78.7”], 600mm [23.6”], 750mm [29.6”]
3P + N 230/400Vac nominal H,W,D
1P + N 230Vac nominal Weight DV2-A20B-xxxx:
AC Input 900kg [1980lb] typical maximum with 20 rectifier
Frequency 50/60 Hz modules and 4 x 48V/150Ah battery strings.
System
Rectifier APR24-3G APR48-3G APR48-ES Environ-
Module* mental
Operating -25°C [-13°F] to 40°C [104°F]*
Nominal Temperature
Output 24Vdc 48Vdc 48Vdc Range
Voltage Humidity <95% non-condensing
Output Altitude <2000m (6500’). Thermally de-rates above this
Voltage range 20–30Vdc 40–58Vdc 40–58Vdc altitude, to a maximum altitude of 4000m
Max Number
of Rectifiers 10 20 20 Certifications (Pending)
Maximum DC All products comply with International Standards. Contact your local
Power 14.4kW 36kW 40kW
†
Eaton Power Quality representative for details on the specific product
Maximum versions available with these safety and EMC approvals:
Load Current 500A 600A 600A
Efficiency >91% >92% >96% North America: UL Listed 1801, cUL, FCC
† Maximum DC power includes load and battery recharge. *Refer to rectifier specifications for more information.
Supervisory SC200 System capacity will vary depending on number of rectifiers and batteries
Module selected.
Commun- 10 baseT Ethernet port, web server, SNMP agent In the interests of continual product improvement all specifications are
ications subject to change without notice.
Batteries Type: Front access VRLA
48V: Up to 600Ahr per cabinet using four strings of
150Ahr batteries.
24V: Up to 1200Ahr per cabinet using eight strings
of 150Ahr batteries.
Extension Up to six extension battery cabinets fitted with
Battery either four strings of 48V or eight strings of 24V in
Cabinets each cabinet
DC
Distribution
Load circuit
Breakers 20-way total
Single Width Heinemann AMIR Series 5A, 10A, 20A,
Circuit 30A, 40A, 50A, 70A, 80A, 100A
Breakers
Dual Width Heinemann AMIP 120A, 150A, 200A
Circuit
Breakers
Triple Width Heinemann AMIP 250A
Circuit
Breakers
Battery Circuit Heinemann AM1P, 200A integrated into battery
Breakers shelf
Low Volt 1 x battery disconnect, 1 x 400A non-priority load
Disconnect (10 positions for non priority, 10 positions for
Options priority).
Features
• 24” x 24” cabinet
• 4 Battery Shelves
• Optional DC distribution with easy fit plug-in hydraulic/magnetic
circuit breakers.
• UL Listed
Technical Specification
System Interconnections Certifications (Pending)
Commun- All products comply with international standards. Contact your local Eaton DC
ications Screw terminals representative for details on the specific product versions available with these
Power Direct onto busbars safety and EMC approvals:
Batteries*
Type Front access VRLA
48V Batteries Up to 600Ahr per cabinet using four strings of
150Ahr batteries.
24V Batteries: Up to 1200Ahr per cabinet using eight strings of
150Ahr batteries.
*Maximum of 6 battery cabinets added to the power cabinet
per system
Mechanical
Dimensions
H, W, D 2000mm [78.7”], 600mm [23.6”], 600mm [23.6”]
Features
• Intelligent system management features
• Pre-Configured Software
• High Power Density
• Fast On-Line Expansion of Rectifiers (Hot-Swap)
• High Efficiency and Unity Power Factor
• Range of DC distribution configurations
• Battery condition monitoring
• Wide AC input voltage range
• Seismic rated cabinet
• Remote monitoring and control
• Full length security door (optional)
Technical Specifications
Input Options
Nominal AC 3P+PE, Δ 208VAC AC Distribution Coordinated transient protection up to 40kA, 8/20μs
Supply 3P+N+PE, Y 230/400VAC Incoming isolator
50/60Hz Individual rectifier MCBs
Power Factor >0.99* (20 – 100% Maximum System Current) DC Distribution A wide range of DC distribution elements are
Efficiency up to 92%* available including:
24 x 18mm MCBs (1-63A)
Output 16 x 27mm MCBs (10-125A)
DC Output 40 – 58V 10 x DIN00 type HRC fuses (20-160A)
Voltage Range 6 x DIN1 type HRC fuses (63-250A)
Typical DC 46kW - 750kW † 6 x DIN2 type HRC fuses (100-400A)
Output Power 4 x DIN3 type HRC fuses (400-630A)
4 x DIN4 type HRC fuses (800-1200A)
Low Voltage Single or dual LVD can be configured as battery or
Environmental
Disconnect load disconnect including non-priority load
Operating -25°C to +50°C*
(LVD) disconnect.
Temperature
Rectifier Blank For unused rectifier positions
Range
Panels
SiteSure Input/output modules to monitor and control
Mechanical external equipment
Dimensions 2000mm [78.7”], 600mm [23.6”], 600mm [23.6”] CellSure Comprehensive battery monitoring and fault
H,W,D diagnosis system with patented state-of-health
Weight 200kg [443lb] algorithms.
Typical configuration with 16 CR48-3G rectifier
modules.
Software
PowerManagerII Remote control and monitoring software
System DCTools Configuration Software. Free download from
System Controller SC200 www.powerware.com/downloads